Models ZXM2 Expansion Modules TB-223 EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected] Leave this bulletin on the job site for future reference! The advanced ZXM2 Expansion Module allows you to easily add additional zones to the UZC4 Zone Control System. You can gain up to 18 additional zones for a total of 22. The robust and superior design, intuitive firmware, simple setup options, and easy to understand wiring, makes the UZC4 Zoning system the Contractors dream. Combined with EWC motorized dampers and practically any off-the-shelf heat/cool, heatpump or Multistage thermostat, EWC Controls once again proves to be the innovative leader in the residential & light commercial Forced Air Zoning industry. P/N 090375A0223 REV. F Copyright 2005-2008 EWC Controls Inc., All Rights Reserved © C W1 W2 O Y1 Y2 R G B E C W1 W2 O Y1 Y2 R G B E M6 M4 M2 M1 M6 M4 M2 M1 D M P R D M P R MXR MXC F1 TB1 TB2 TB3 TB4 TB5 DMPR STATUS LED1 LED2 LED3 T S T A T T S T A T SW1 R4 R3 R2 R1 R10 R9 R5 R6 R7 R8 D4 D5 D7 D8 D6 D9 D3 K1 K2 R11 R15 R12 R13 R14 C1 C2 D1 D2 R17 R19 R21 R22 R16 R18 R20 C3 C5 C4 U2 U3 C6 U4 U5 C7 R32 R34 R36 R29 R30 R31 R33 R35 R37 R38 R39 R41 R43 R46 R45 R40 R42 R44 R27 R25 R28 R26 R24 R23 R47 U6 U1 Y1 C8 J1 Z1 J2 C10 C9 C11 C12 C13 C14 C16 C20 C15 C17 C19 C18 ZXM2 ZXM2 > > > > > > > > 1 2 4 8 0 0 0 0 A A A A 5 6 5 5 6 6 POLARIZED ISOLATING DAMPER POWER TERMINAL BLOCK & 2.5 amp BREAKER Rugged Damper Motor Terminal Blocks with ZONE ID blocks Heavy duty 10 amp contact rated relays Rugged 10 pin Expansion Header Rugged & Versatile Thermostat Terminal Blocks 4 Switch ZONE ADDRESS Bank Bright STATUS LED and DAMPER LED’S with ZONE ID blocks FIELD ZONE ID Blocks Bus Cable not shown for clarity Model ZXM2 Expansion Module The ZXM2 Expansion Module can add up to 16 zones with 1 to 8 expansion modules on a UZC4 control system. Compatible with most Off the shelf 1 or 2 stage Conventional Heat/Cool or Heat Pump Thermostats. All Mechanical, Digital/Electronic, Dual Mode, and Internet Compatible Thermostats that operate on 24vac. Battery powered or Power robbing thermostats that draw less than 20 ma of current are also accepted. The ZXM2 Expansion features automatic changeover from any thermostat allowing for individual zone comfort from the HVAC system. The STATUS LED pulses as a steady heart beat to indicate active Micro- processor status. LEDs indicate which dampers are open. Zone Capacity Compatible Thermostats Automatic Heat/Cool Changeover Status LED Damper LEDs Operating Conditions INPUT VOLTAGE: PANEL: 19-30VAC 60 Hz, Supplied via bus cable from UZC4. DAMPERS: 19-30VAC 60 Hz, Transformer 40-60VA Max. NEC Class 2. CURRENT DRAW: Max 8VA @ 24VAC. OVER-CURRENT PROTECTION: PANEL: 4.0 amp or 96VA. Protected via UZC4. DAMPERS: 2.5 AMP or 60VA TEMPERATURE: -20° to 160°F (-29° to 71°C) HUMIDITY: 0% - 95% RH Non-Condensing. Operating Power

Upload: others

Post on 07-Jul-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: TB4 ZXM2 - EWC · Models ZXM2 Expansion Modules TB-223 EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.comFile Size:

Models ZXM2 Expansion Modules

TB-223EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]

Leave this bulletin on the job site for future reference!

The advanced ZXM2 Expansion Module allows you to easily add additional zones to the UZC4 Zone Control System. You can gain up to 18 additional zones for a total of 22. The robust and superior design, intuitive firmware, simple setup options, and easy to understand wiring, makes the UZC4 Zoning system the Contractors dream. Combined with EWC motorized dampers and practically any off-the-shelf heat/cool, heatpump or Multistage thermostat, EWC Controls once again proves to be the innovative leader in the residential & light commercial Forced Air Zoning industry.

P/N 090375A0223 REV. F Copyright 2005-2008 EWC Controls Inc., All Rights Reserved ©

CW1 W2O Y1Y2RG

B

E

CW1 W2O Y1Y2RG

B

E

M6M4M2M1

M6M4M2M1

DMPR

DMPR

MXR

MXC

F1

TB1

TB2

TB3

TB4

TB5

DMPR

STATUSLED1

LED2

LED3

TSTAT

TSTAT

SW1

R4R3

R2R1

R10

R9

R5 R6

R7

R8D4

D5

D7

D8

D6

D9

D3

K1

K2 R11

R15

R12

R13

R14

C1C2

D1

D2

R17 R19 R21 R22

R16 R18 R20

C3

C5

C4

U2

U3

C6

U4

U5

C7

R32 R34 R36

R29 R30 R31

R33 R35 R37 R38 R39

R41 R43 R46R45

R40 R42 R44

R27R25

R28R26R24

R23

R47

U6

U1

Y1

C8

J1

Z1

J2

C10

C9

C11

C12

C13 C14

C16

C20

C15 C17

C19C18

ZXM2ZXM2

>>

>>

>>

>>

12480

000

AAAA

5

6

5

5

6

6

POLARIZEDISOLATINGDAMPERPOWER TERMINALBLOCK &2.5 ampBREAKER

Rugged Damper Motor Terminal BlockswithZONE IDblocks

Heavy duty 10 ampcontact rated relays

Rugged 10 pin Expansion Header

Rugged &VersatileThermostat Terminal Blocks

4 Switch ZONE ADDRESS Bank

Bright STATUS LEDand DAMPER LED’Swith ZONE ID blocks

FIELDZONE ID Blocks

Bus Cable not shown for clarity

Model ZXM2 Expansion ModuleThe ZXM2 Expansion Module can add up to 16 zones with 1 to 8 expansion modules on a UZC4 control system.

Compatible with most Off the shelf 1 or 2 stage Conventional H e a t / C o o l o r H e a t P u m p Thermostats. All Mechanical, Digital/Electronic, Dual Mode, and Internet Compatible Thermostats that operate on 24vac. Battery powered or Power robbing thermostats that draw less than 20 ma of current are also accepted.

The ZXM2 Expansion features automatic changeover from any thermostat allowing for individual zone comfort from the HVAC system.

The STATUS LED pulses as a steady heart beat to indicate active Micro- processor status.

LEDs indicate which dampers are o p e n .

Zone Capacity

CompatibleThermostats

AutomaticHeat/CoolChangeover

Status LED

Damper LEDs

Operating Conditions

INPUT VOLTAGE:

PANEL: 19-30VAC 60 Hz, Supplied via

bus cable from UZC4.

DAMPERS: 19-30VAC 60 Hz,

Transformer 40-60VA Max. NEC Class 2.

CURRENT DRAW: Max 8VA @ 24VAC.

OVER-CURRENT PROTECTION:

PANEL: 4.0 amp or 96VA. Protected

via UZC4.

DAMPERS: 2.5 AMP or 60VA

TEMPERATURE: -20° to 160°F (-29° to 71°C)

HUMIDITY: 0% - 95% RH Non-Condensing.

Operating Power

Page 2: TB4 ZXM2 - EWC · Models ZXM2 Expansion Modules TB-223 EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.comFile Size:

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]

FIELD BUS CABLE ROUTINGFIELD BUS CABLE ROUTING

UZC4MAIN

CONTROL PANEL

ZONES 1-4

ON 1234

CTS 206-4

ZXM2ZONES 5-6

TO PASS THE BUS CABLE THROUGH THE KNOCK OUTS OF THE HOUSING, FOLD THE 10-PIN HEADER

AGAINST THE CABLE SO IT WILL FIT EASILY.

FIELD BUS CABLES ARE ROUGHLY 40” IN LENGTH, SECURE CABLE AS NECESSARY.

KNOCK-OUT ON HOUSING

All Expansion module Dip switch banks must be set correctly for proper zone address identification. The 1st expansion module would be zones 5 & 6. The 2nd expansion module would be zones 7 & 8. The 3rd expansion module would be zones 9 & 10. And so on up the line for a total of 22 zones.

The switches are set for you at the factory unless you are expanding the system in the field. It is a good idea to check them anyway.

DO NOT CONNECT OR DISCONNECT BUS CABLES WHILE POWER IS APPLIED TO THE SYSTEM. DOING SO MAY DAMAGE THE ZXM2 MODULES AND VOIDS ALL WARRANTIES.

NOTE:THE ZXM-2 PACKAGE CONTAINS AN EXPANSION HEADER AND A 3-CONNECTOR CABLE (ITEMS NOT SHOWN). THESE ITEMS ARE ONLY REQUIRED IF YOU ARE EXPANDING A UZC6 TO A UZC8, CONTACT TECH. SUPPORT FOR DETAILS.

UZC6UZC6

Page 3: TB4 ZXM2 - EWC · Models ZXM2 Expansion Modules TB-223 EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.comFile Size:

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected] 3

FIELD BUS CABLE ROUTINGFIELD BUS CABLE ROUTING

DO NOT CONNECT OR DISCONNECT BUS CABLES WHILE POWER IS APPLIED TO THE SYSTEM. DOING SO MAY DAMAGE THE ZXM2 MODULES AND VOIDS ALL WARRANTIES.

UZC4MAIN

CONTROL PANEL

ZONES 1-4

ON 1234

CTS 206-4

ZXM2ZONES 5-6

ON 1234

CTS 206-4

ZXM2ZONES 7-8

ON 1234

CTS 206-4

ZXM2ZONES 9-10

UZC10UZC10

UZC4MAIN

CONTROL PANEL

ZONES 1-4

ON 1234

CTS 206-4

ZXM2ZONES 5-6

ON 1234

CTS 206-4

ZXM2ZONES 7-8

UZC8UZC8

Page 4: TB4 ZXM2 - EWC · Models ZXM2 Expansion Modules TB-223 EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.comFile Size:

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]

UZC4MAIN

CONTROL PANEL

ZONES 1-4

ON 1234

CT

S 2

06

-4

ZXM2ZONES 5-6

ON 1234

CT

S 2

06

-4

ZXM2ZONES 7-8

ON 1234

CT

S 2

06

-4

ZXM2ZONES 9-10

ON 1234

CT

S 2

06

-4

ZXM2ZONES 11-12

ON 1234

CT

S 2

06

-4

ZXM2ZONES 13-14

UZC14UZC14

FIELD BUS CABLE ROUTINGFIELD BUS CABLE ROUTING

UZC4MAIN

CONTROL PANEL

ZONES 1-4

ON 1234

CT

S 2

06

-4

ZXM2ZONES 5-6

ON 1234

CT

S 2

06

-4

ZXM2ZONES 7-8

ON 1234

CT

S 2

06

-4

ZXM2ZONES 9-10

ON 1234

CT

S 2

06

-4

ZXM2ZONES 11-12

DO NOT CONNECT OR DISCONNECT BUS CABLES WHILE POWER IS APPLIED TO THE SYSTEM. DOING SO MAY DAMAGE THE ZXM2 MODULES AND VOIDS ALL WARRANTIES.

UZC12UZC12

Page 5: TB4 ZXM2 - EWC · Models ZXM2 Expansion Modules TB-223 EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.comFile Size:

FIELD BUS CABLE ROUTINGFIELD BUS CABLE ROUTING

UZC18UZC18

DO NOT CONNECT OR DISCONNECT BUS CABLES WHILE POWER IS APPLIED TO THE SYSTEM. DOING SO MAY DAMAGE THE ZXM2 MODULES AND VOIDS ALL WARRANTIES.

UZC4MAIN

CONTROL PANEL

ZONES 1-4

ON 12

34

CT

S 2

06

-4

ZXM2ZONES 5-6

ON 12

34

CT

S 2

06

-4

ZXM2ZONES 7-8

ON 12

34

CT

S 2

06

-4

ZXM2ZONES 9-10

ON 12

34

CT

S 2

06

-4

ZXM2ZONES 11-12

ON 12

34

CT

S 2

06

-4

ZXM2ZONES 13-14

ON 12

34

CT

S 2

06

-4

ZXM2ZONES 15-16

ON 12

34

CT

S 2

06

-4

ZXM2ZONES 17-18

UZC4MAIN

CONTROL PANEL

ZONES 1-4

ON 123

4

CT

S 2

06

-4ZXM2

ZONES 5-6

ON 123

4

CT

S 2

06

-4

ZXM2ZONES 7-8

ON 123

4

CT

S 2

06

-4

ZXM2ZONES 9-10

ON 123

4

CT

S 2

06

-4

ZXM2ZONES 11-12

ON 123

4

CT

S 2

06

-4

ZXM2ZONES 13-14

ON 123

4

CT

S 2

06

-4

ZXM2ZONES 15-16

UZC16UZC16

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected] 5

Page 6: TB4 ZXM2 - EWC · Models ZXM2 Expansion Modules TB-223 EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.comFile Size:

UZC22UZC22

UZC4MAIN

CONTROL PANEL

ZONES 1-4

ON 12

34

CT

S 2

06

-4

ZXM2ZONES 5-6

ON 12

34

CT

S 2

06

-4

ZXM2ZONES 7-8

ON 12

34

CT

S 2

06

-4

ZXM2ZONES 9-10

ON 12

34

CT

S 2

06

-4

ZXM2ZONES 11-12

ON 12

34

CT

S 2

06

-4

ZXM2ZONES 13-14

ON 12

34

CT

S 2

06

-4

ZXM2ZONES 15-16

ON 12

34

CT

S 2

06

-4

ZXM2ZONES 19-20

ON 12

34

CT

S 2

06

-4

ZXM2ZONES 21-22

ON 12

34

CT

S 2

06

-4

ZXM2ZONES 17-18

UZC20UZC20

UZC4MAIN

CONTROL PANEL

ZONES 1-4

ON 12

34

CT

S 2

06

-4

ZXM2ZONES 5-6

ON 12

34

CT

S 2

06

-4

ZXM2ZONES 7-8

ON 12

34

CT

S 2

06

-4

ZXM2ZONES 9-10

ON 12

34

CT

S 2

06

-4

ZXM2ZONES 11-12

ON 12

34

CT

S 2

06

-4

ZXM2ZONES 13-14

ON 12

34

CT

S 2

06

-4

ZXM2ZONES 15-16

ON 12

34

CT

S 2

06

-4

ZXM2ZONES 17-18

ON 12

34

CT

S 2

06

-4

ZXM2ZONES 19-20

FIELD BUS CABLE ROUTINGFIELD BUS CABLE ROUTING

DO NOT CONNECT OR DISCONNECT BUS CABLES WHILE POWER IS APPLIED TO THE SYSTEM. DOING SO MAY DAMAGE THE ZXM2 MODULES AND VOIDS ALL WARRANTIES.

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]

Page 7: TB4 ZXM2 - EWC · Models ZXM2 Expansion Modules TB-223 EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.comFile Size:

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected] 7

DAMPER WIRING, DAMPER TESTING AND POWER SUPPLY SOLUTIONS

TESTING DAMPER MOTORS

SR /SRE Power Open / Spring Close Dampers - Connect 24vac common & hot to the two motor (M) terminals. Damper should Open. Remove 24vac hot. Damper should Close.

ND / URD / SMD / BMD Dampers - Connect 24vac common to terminal 1 and 24vac hot to terminal 4. Damper should Open. Remove 24vac hot from terminal 4 and apply to terminal 6. Damper should Close

SR /SRE Power Close / Spring Open Dampers - Connect 24vac common & hot to the two motor (M) terminals. Damper should Close. Remove 24 vac hot. Damper should Open.

The Expansion module motor blocks must be powered by a separate transformer. This advanced design provides automatic 2.5amp over-current protection for each Expansion module motor block and allows a maximum 60va transformer to be connected. This means that you can directly connect a theoretical maximum of 12 Genuine ND/URD dampers to a single 2 zone expansion module. Now you no longer have to isolate & power up multiple dampers using field installed relays. The Expansion modules provide the isolation for you. See the diagram below for typical wiring solutions for dampers.

Separate 24 vac Transformer 60va MAX

L1

L2

H

C

46

14

61

46

14

61

M1M2M4M6

MXR

MXC

F1

M1M2M4M6

DMPR

DMPR

To Line VoltageProvide over current protection

THERMALCIRCUITBREAKER

Ge

nu

ine

ND

an

d U

RD

da

mp

ers

wir

ed

in s

eri

es

or

pa

ralle

l co

nfi

gu

rati

on

. N

OT

E: S

om

e o

lde

r s

tyle

da

mp

ers

an

d

co

mp

eti

tor’

s d

am

pe

rs c

an

no

t b

e p

ara

lle

led

an

d m

us

t b

e is

ola

ted

or

wir

ed

in

ta

nd

em

. C

on

tac

t E

WC

Co

ntr

ols

T

ec

hn

ica

l Su

pp

ort

for a

ss

ista

nc

e.

Typical damper power wiring for a ZXM2 Expansion Module. A single damper on the first expansion zone

and three dampers on the next. Your actual number of dampers per zone may vary.