H-41 (A) Photo electric sensor (B) Fiber optic sensor (C) Door/Area sensor (D) Proximity sensor (E) Pressure sensor (F) Rotary encoder (G) Connector/ Socket (H) Temp. controller (I) SSR/ Power controller (J) Counter (K) Timer (L) Panel meter (M) Tacho/ Speed/ Pulse meter (N) Display unit (O) Sensor controller (P) Switching mode power supply (Q) Stepper motor& Driver&Controller (R) Graphic/ Logic panel (S) Field network device (T) Software (U) Other Economical Dual Display type, PID Control TCN Series Features Economical dual display type, PID control ● Realizes ideal temp. controlling with newly developed PID control algorithm and 100ms high speed sampling Built-in relay output or SSR output selectable : Enables to phase control and cycle control with SSR drive output(SSRP function) ● Dramatically increased visibility using wide display part ● Mounting space saving with compact design : Approx. 38% reduced size compared with existing model(depth-based) Ordering information Specifications Series TCN4S TCN4M TCN4H TCN4L Power supply AC power 100-240VAC 50/60Hz AC/DC power 24VAC 50/60Hz, 24-48VDC Allowable voltage range 90 to 110% of rated voltage Power consumption AC power Max. 5VA(100-240VAC 50/60Hz) AC/DC power Max. 5VA(24VAC 50/60Hz), Max. 3W(24-48VDC) Display method 7 Segment (PV: red, SV: green), Other display(green, red) LED Character size PV(W×H) 7.0×15.0mm 9.5×20.0mm 7.0×14.6mm 11.0×22.0mm SV(W×H) 5.0×9.5mm 7.5×15.0mm 6.0×12.0mm 7.0×14.0mm Input type RTD DPt100Ω, Cu50Ω (allowable line resistance max. 5Ω per a wire) Thermocouple K(CA), J(IC), L(IC), T(CC), R(PR), S(PR) Display accuracy 1 RTD At room temperature (23℃ ±5℃): (PV ±0.5% or ±1℃, select the higher one) ±1digit Out of room temperature range: (PV ±0.5% or ±2℃, select the higher one) ±1digit Thermocouple Control output Relay 250VAC 3A 1a SSR 12VDC ±2V 20mA Max. Alarm output AL1, AL2 Relay output: 250VAC 1A 1a Control method ON/OFF control, P, PI, PD, PID control Hysteresis 1 to 100℃/℉ (0.1 to 50.0℃/℉) variable 1: At room temperature (23±5) Thermocouple C R, S type, below 200℃: (PV ±0.5% or ±3℃, select the higher one) ±1digit Thermocouple R, S type, over 200: (PV ±0.5% or ±2℃, select the higher one) ±1digit Thermocouple L(IC) type, RTD Cu50Ω: (PV ±0.5% or ±2℃, select the higher one) ±1digit Out of room temperature range Thermocouple R, S type, below 200℃: (PV ±1.0% or ±6℃, select the higher one) ±1digit Thermocouple R, S type, over 200: (PV ±0.5% or ±5℃, select the higher one ±1digit RTD Cu50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1digit Setting type Item Digit Size Auxiliary output Power supply Control output R Relay contact output+SSRP output (AC power) Relay contact output+SSR output (AC/DC power) 2 24VAC 50/60Hz, 24-48VDC 4 100-240VAC 50/60Hz 2 Alarm1+Alarm2 output S DIN W48×H48mm M DIN W72×H72mm H DIN W48×H96mm L DIN W96×H96mm 4 9999(4digit) CN Dual display type, set by touch switch T Temperature controller CN T S 2 4 R 4

Upload: others

Post on 17-Mar-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: TCN Series Economical Dual Display type, PID Control · RTD Cu50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1digit Setting type Item Digit Size Auxiliary output Power supply

H-41

(A) Photoelectric sensor

(B) Fiberopticsensor

(C) Door/Areasensor

(D) Proximitysensor

(E) Pressuresensor

(F) Rotaryencoder

(G) Connector/Socket

(H)Temp.controller

(I)SSR/Powercontroller

(J) Counter

(K) Timer

(L) Panelmeter

(M)Tacho/Speed/ Pulsemeter

(N)Displayunit

(O)Sensorcontroller

(P)Switchingmode powersupply

(Q)Steppermotor&Driver&Controller

(R)Graphic/Logicpanel

(S)Fieldnetworkdevice

(T) Software

(U) Other

Economical Dual Display type, PID ControlTCN Series

Features

Economical dual display type, PID control

Realizesidealtemp.controllingwithnewlydevelopedPIDcontrolalgorithmand100mshighspeedsamplingBuilt-in relay output or SSR output selectable : Enables to phase control and cycle control with SSR drive output(SSRP function)DramaticallyincreasedvisibilityusingwidedisplaypartMountingspacesavingwithcompactdesign:Approx.38%reducedsizecomparedwithexistingmodel(depth-based)

Ordering information

SpecificationsSeries TCN4S TCN4M TCN4H TCN4L

Powersupply

ACpower 100-240VAC50/60HzAC/DCpower 24VAC50/60Hz,24-48VDC

Allowablevoltagerange 90to110%ofratedvoltagePowerconsumption

ACpower Max.5VA(100-240VAC50/60Hz)AC/DCpower Max.5VA(24VAC50/60Hz),Max.3W(24-48VDC)

Displaymethod 7Segment(PV:red,SV:green),Otherdisplay(green,red)LED

Charactersize

PV(W×H) 7.0×15.0mm 9.5×20.0mm 7.0×14.6mm 11.0×22.0mmSV(W×H) 5.0×9.5mm 7.5×15.0mm 6.0×12.0mm 7.0×14.0mm

InputtypeRTD DPt100Ω,Cu50Ω(allowablelineresistancemax.5Ωperawire)Thermocouple K(CA),J(IC),L(IC),T(CC),R(PR),S(PR)

Displayaccuracy※1

RTD Atroomtemperature(23 ±5):(PV±0.5%or±1, select the higherone)±1digitOutofroomtemperaturerange:(PV±0.5%or±2, select the higherone)±1digitThermocouple

Controloutput

Relay 250VAC3A1aSSR 12VDC±2V20mAMax.

Alarmoutput AL1,AL2Relayoutput:250VAC1A1aControlmethod ON/OFFcontrol,P,PI,PD,PIDcontrolHysteresis 1to100/ (0.1to50.0/)variable※1: Atroomtemperature(23±5)

ThermocoupleCR,Stype,below200: (PV±0.5%or±3, select the higherone)±1digitThermocoupleR,Stype,over200:(PV±0.5%or±2, select the higherone)±1digitThermocoupleL(IC)type,RTDCu50Ω:(PV±0.5%or±2, select the higherone)±1digit

OutofroomtemperaturerangeThermocoupleR,Stype,below200: (PV±1.0%or±6, select the higherone)±1digitThermocoupleR,Stype,over200:(PV±0.5%or±5, select the higherone±1digitRTDCu50Ω:(PV±0.5%or±3, select the higherone)±1digit

Settingtype

Item

Digit

Size

Auxiliaryoutput

Powersupply

Controloutput

RRelaycontactoutput+SSRPoutput(ACpower)Relaycontactoutput+SSRoutput(AC/DCpower)

2 24VAC50/60Hz,24-48VDC4 100-240VAC50/60Hz

2 Alarm1+Alarm2output

S DINW48×H48mmM DINW72×H72mmH DINW48×H96mmL DINW96×H96mm

4 9999(4digit)

CN Dualdisplaytype,setbytouchswitch

T Temperaturecontroller

CNT S 2 4 R4

Page 2: TCN Series Economical Dual Display type, PID Control · RTD Cu50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1digit Setting type Item Digit Size Auxiliary output Power supply

H-42

TCN Series

Specifications

Connections

TCN4S

TCN4M TCN4H/L

※ TCN4Serieshasselectablecontroloutput;Relayoutput,andSSRPoutput.AC/DCvoltagetypehasRelayoutputandSSRoutputanditisselectable.

※2: Theweightiswithpackagingandtheweightinparenthesesisonlyunitweight.※Environmentresistanceisratedatnofreezingorcondensation.

※1:PowersupplyACpower:100-240VAC5VA50/60HzAC/DCpower:24VAC5VA50/60Hz,24-48VDC3W

Series TCN4S TCN4M TCN4H TCN4L Proportionalband(P) 0.1to999.9/Integraltime(I) 0to9999sec.Derivativetime(D) 0to9999sec.Controlperiod(T) 0.5to120.0sec.Manualreset 0.0to100.0%Samplingperiod 100ms

Dielectricstrength

ACPower 2,000VAC50/60Hz1min.(betweeninputterminalandpowerterminal)AC/DCpower 1,000VAC50/60Hz1min.(betweeninputterminalandpowerterminal)

Vibration 0.75mmamplitudeatfrequencyof5to55HzineachofX,Y,Zdirectionsfor2hours

Relaylifecycle

Mechanical OUT:Over5,000,000times,AL1/2:Over5,000,000times

Electrical OUT:Over200,000times(250VAC3Aresistiveload)AL1/2:Over300,000times(250VAC1Aresistiveload)

Insulationresistance Min.100MΩ(at500VDCmegger)Noiseresistance ±2kVR-phase,S-phasethesquarewavenoise(pulsewidth:1us)bythenoisesimulatorMemoryretention Approx.10years(whenusingnon-volatilesemiconductormemorytype)

Environ-ment

Ambienttemperature -10to50,storage:-20to60Ambienthumidity 35to85%RH,storage:35to85%RH

Insulationtype Doubleinsulationorreinforcedinsulation(mark: ,Dielectricstrengthbetweenthemeasuringinputpartandthepowerpart:ACpower2kV,AC/DCPower1kV)

Approval

Weight※2 Approx.147g(Approx.100g)

Approx.203g(Approx.133g)

Approx.194g(Approx.124g)

Approx.275g(Approx.179g)

13

19

14

20

15

21

16

22

17

23

18

24

SSROUT:12VDC±2V20Max.

※1

SOURCE:100-240VAC5VA50/60,24VAC5VA50/60,24-48VDC3W

B' RTD TC

SENSOR

AL1OUT:250VAC1A1a

AL2OUT:250VAC1A1a

RelayOUT:250VAC1A1a B

A

1

7

2

8

3

9

4

10

5

11

6

12

1 7

2 8

3 94 10

5 11

6 12

SSROUT:12VDC±2V20mAMax.

※1SOURCE:100-240VAC5VA50/60,24VAC5VA50/60,24-48VDC3W

B' RTD TC

SENSOR

AL1OUT:250VAC1A1a

AL2OUT:250VAC1A1a

RelayOUT:250VAC1A1a

B

A

1

7

2

8

3

9

4

5

6

10

11

12

13

14

15

16

17

18

SSROUT:12VDC±2V20Max.

※1

SOURCE:100-240VAC5VA50/60,24VAC5VA50/60,24-48VDC3W

B' RTD TC

SENSOR

AL1OUT:250VAC1A1a

AL2OUT:250VAC1A1a

RelayOUT:250VAC3A1a

B

A

Page 3: TCN Series Economical Dual Display type, PID Control · RTD Cu50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1digit Setting type Item Digit Size Auxiliary output Power supply

H-43

(A) Photoelectric sensor

(B) Fiberopticsensor

(C) Door/Areasensor

(D) Proximitysensor

(E) Pressuresensor

(F) Rotaryencoder

(G) Connector/Socket

(H)Temp.controller

(I)SSR/Powercontroller

(J) Counter

(K) Timer

(L) Panelmeter

(M)Tacho/Speed/ Pulsemeter

(N)Displayunit

(O)Sensorcontroller

(P)Switchingmode powersupply

(Q)Steppermotor&Driver&Controller

(R)Graphic/Logicpanel

(S)Fieldnetworkdevice

(T) Software

(U) Other

Economical Dual Display type, PID Control

Dimensions TCN4S

TCN4M

TCN4H

TCN4L

Panel cut-out

Panel cut-out

Panel cut-out

Panel cut-out

RSA-COVER (48×48mm)

RMA-COVER (72×72mm)

RHA-COVER (48×96mm)

RLA-COVER (96×96mm)

Terminal cover(sold separately)

22 48.4

13

68.5

70

91.5

47.2

13 91.5

94

13

<Bracket>

<Bracket>

<Bracket>

<Bracket>

Min.65

Min.65

45+0.6 0

45+0.6

0

Min.90

Min.90

68+0.7 0

68+0.7

0

(unit:mm)

Min.115

Min.65

45+0.6 0

92+0.8

0

Min.115

Min.115

92+0.8 0

92+0.8

0

96 6 664.5

101.5

Terminalcover

48 6 664.5

101.5

96

Terminalcover

72 6 664.5

77.5

Terminalcover

48 6 1164.5

56

Terminalcover

Page 4: TCN Series Economical Dual Display type, PID Control · RTD Cu50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1digit Setting type Item Digit Size Auxiliary output Power supply

H-44

TCN Series

4. Auto tuning lamp: ATlampflashesbyevery1secduringoperatingautotuning.5. key:Usedwhenenteringintoparametersettinggroup,returningtoRUNmode,movingparameter,andsavingsettingvalues.

6. Adjustment: Usedwhenenteringintosetvaluechangemode,digitmovinganddigitup/down.7. Digital input key:Press + keysfor3sec.tooperatethesetfunction(RUN/STOP,alarmoutputreset,autotuning)indigitalinputkey[DI-K].

8. Temperature unit(/) indicator:Itshowscurrenttemperatureunit.

Product mounting TCN4S(48×48mm) Series Other Series

※Mounttheproductonthepanel,fastenbracketbypushingwithtoolsasshownabove.

Parts description

SV setting

1

3

2

4

1

23

4

5 6

7

8

Youcansetthetemperaturetocontrolwith keys.SetrangeiswithinSVlowerlimitvalue[L-SV]toSVhigherlimitvalue[H-SV].Ex)Incaseofchangingsettemperaturefrom210ºCto250ºC

Pressanykeyamong keyinRUN

mode,therightdigitatSVdisplayflashesanditenterstoSVsetting.

Press keytomovethedesireddigit.(100→101→102→103→100)

Press or keytomovethedesirednumber(1→5).

Press keytosavethevalueanditcontrolswiththissetvalue.(eventhoughthereisnokeyinputforover3sec.,itsavesautomatically.)

1. Present temperature (PV) display (red) RUNmode:Presenttemperature(PV)display. Parametersettingmode:Parameterdisplay.

2. Set temperature (SV) display (green) RUNmode:Settemperature(SV)display. Parametersettingmode:Parametersettingvaluedisplay.

3. Control/Alarm output display lamp AL1/AL2:ItturnsONwhenthealarmoutputisON. OUT:ItturnsONwhenthecontroloutputisON. ※DuringSSRdrivecontroloutputtypeinCYCLE/PHASEcontrol,this

lampturnsONwhenMVisover3.0%.

Page 5: TCN Series Economical Dual Display type, PID Control · RTD Cu50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1digit Setting type Item Digit Size Auxiliary output Power supply

H-45

(A) Photoelectric sensor

(B) Fiberopticsensor

(C) Door/Areasensor

(D) Proximitysensor

(E) Pressuresensor

(F) Rotaryencoder

(G) Connector/Socket

(H)Temp.controller

(I)SSR/Powercontroller

(J) Counter

(K) Timer

(L) Panelmeter

(M)Tacho/Speed/ Pulsemeter

(N)Displayunit

(O)Sensorcontroller

(P)Switchingmode powersupply

(Q)Steppermotor&Driver&Controller

(R)Graphic/Logicpanel

(S)Fieldnetworkdevice

(T) Software

(U) Other

Economical Dual Display type, PID Control

Parameter setting group

※Press keyover3secinanysettinggroup,itsavesthesetvalueandreturnstoRUNmode.(Press keyonceinSVsetting,itreturnstoRUNmode).※Ifnokeyenteredfor30sec.,itreturnstoRUNmodeautomaticallyandthesetvalueofparameterisnotbesaved.※Press keyagainwithin1sec.afterreturningtoRUNmode,itadvancesofthefirstparameterofprevioussettinggroup.※Press keytomovenextparameter.※ Thisparametermightnotbedisplayeddependingonotherparametersettings.※ Setparameteras'Parameter2group→Parameter1group→Settingofsetvalue'orderconsideringparameterrelationofeachsettinggroup.

※1:ItisnotdisplayedforAC/DCpowermodel(TCN4 -22R).

Run mode

SV setting Parameter 1 group Parameter 2 group

AL1alarmtemperature

AL2alarmtemperature

Inputsensor

Temperatureunit

Inputcorrection

Inputdigitalfilter

SVlow-limitvalue

SVhigh-limitvalue

ControloutputoperationControltype

Controloutputtype

SSRdriveoutputmethod※1

Controlcycle

AL1alarmoperationmode

AL2alarmoperationmode

Alarmoutputhysteresis

LBAmonitoringtime

LBAdetectionband

Digitalinputkey

ControloutputMVincaseof

inputbreakerror Locksetting

Autotuning

Proportionalband

Integraltime

Derivativetime

Manualreset

Hysteresis

Pressanykeyamong, , ,

PAR1

IN-Tㅑㅑ MAvF

PAR2

AL1 UNIT IN-Bㅑㅑ

L-SV H-SV O-FTC-MD

OUT SSrM T AL-1

AL-2AHYSLBaTLBaㅑㅑB

DI-K ErMV LOC

AL2

AT

P

I

D

REST

HYS

2sec.

3sec. 3sec.

4sec.

Page 6: TCN Series Economical Dual Display type, PID Control · RTD Cu50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1digit Setting type Item Digit Size Auxiliary output Power supply

H-46

TCN Series

※1:S :Pressanykeyamong , , .※2:Aftercheckingorchangingsettingvalueineachparameter,press keytosave

andmovetonextparametersetting.※3:Itisdisplayedwhencontroltypeparameter[C-MD]ofparameter2groupisset PID.※Press keyfor3sec.toreturnRUNmodeatanyparameter.※ Thisparametermightnotbedisplayeddependingonotherparametersettings.

※1:S :Pressanykeyamong , , .※2:Aftercheckingorchangingsettingvalueineachparameter,press keytosave

andmovetonextparametersetting.※3:Itisdisplayedwhencontroltypeparameter[C-MD]ofparameter2groupisset PID.※Press keyfor3sec.toreturnRUNmodeatanyparameter.※ Thisparametermightnotbedisplayeddependingonotherparametersettings.

Setrange:Deviationalarm(-F.StoF.S),Absolutevaluealarm(temperaturerange)※ Incasealarmoperationmode[AL-2]ofParameter2groupisAM)_/SBa /BA ,noparametersisdisplayed.

Setrange:0.1to999.9/

Setrange:0to9999sec.※IntegraloperationisOFFwhensetvalueis"0".

Setrange:0to9999sec.※DerivativeoperationisOFFwhensetvalueis"0".

Setrange:0.0to100.0%※ItisdisplayedinP,PDcontrol.

Setrange KCaH, JIcH,LIcH,TCcH,RPR,SRP,DPtH,CUsH:1to100/ KCaL, JIcL,LIcL,TCcL,DPtL,CUsL:0.1to50.0/※ItisdisplayedinON/OFFcontrol.

※FrontATlampflashesduringautotuningoperation.

Setrange KCaH, JIcH,LIcH,TCcH,RPR,SRP,DPtH,CUsH:-999to999/ KCaL, JIcL,LIcL,TCcL,DPtL,CUsL:-199.9to999.9/

Setrange:0.1to120.0sec.※ Setinputdigitalfiltertimeforaverageinputvalueaffectedcontrol,anddisplayvalue.

※ Ifchangingtemperatureunit,SV, IN-B, H-SV, L-SV,AL1, AL2, LBaT, LBaB, AHYSparametervaluesareinitialized.

Setrange:Referto'Inputsensorandtemperaturerange'.※ Ifchanginginputsensor,SV, IN-B, H-SV, L-SV,

AL1, AL2, LBaT, LBaB, AHYSparametervaluesareinitialized.

Parameter 1 group

Parameter 2 group

Setrange:Deviationalarm(-F.StoF.S),Absolutevaluealarm(temperaturerange)※ Incasealarmoperationmode[AL-1]ofParameter2groupisAM)_/SBa /BA ,noparametersisdisplayed.

AL1alarmtemperature

AL2alarmtemperature

Auto-tuning

Proportionalband

Integraltime

Derivationtime

Manualreset

Hysteresis

Run mode

※3

PAR1

AL1

AL2

AT

P

I

D

REST

HYS

1250

1250

OFF ON

01)0

0000

0000

05)0

002

S

S

S

S

S

S

S

※1S

※2

2sec. 3sec.

Inputsensor

Temperatureunit

Inputcorrection

Inputdigitalfilter

PAR2

IN-T KCaH KCaL CUsL

UNIT ?C ?F

IN-B 0000

MAvF 00)1

※1S

S

S

S

※2

4sec.

3sec.

Run mode

Page 7: TCN Series Economical Dual Display type, PID Control · RTD Cu50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1digit Setting type Item Digit Size Auxiliary output Power supply

H-47

(A) Photoelectric sensor

(B) Fiberopticsensor

(C) Door/Areasensor

(D) Proximitysensor

(E) Pressuresensor

(F) Rotaryencoder

(G) Connector/Socket

(H)Temp.controller

(I)SSR/Powercontroller

(J) Counter

(K) Timer

(L) Panelmeter

(M)Tacho/Speed/ Pulsemeter

(N)Displayunit

(O)Sensorcontroller

(P)Switchingmode powersupply

(Q)Steppermotor&Driver&Controller

(R)Graphic/Logicpanel

(S)Fieldnetworkdevice

(T) Software

(U) Other

Economical Dual Display type, PID Control

※Whenchangingcontroloutputoperation,ErMVisinitialized.

※Whenchangingcontroltype,ErMV,DI-KareinitializedasOFF.

※Itisdisplayedwhenselectingcontroloutput[OUT]asSSR.ItisnotdisplayedforAC/DCpowermodel(TCN4 -22R).

Setrange:0.5to120.0sec.IncaseofRelayoutput[RLY]ofcontroloutput[OUT]itissetas20.0sec.IncaseofSSRoutput[SSR]ofthat,itissetas2.0sec.※ItisnotdisplayedwhenSSRdriveoutput[SSrM]methodissetasCYCL, PHAS.

Setrange:0to9999sec.※'0'isset,loopbreakalarmfunctionisOFF.※ItisdisplayedwhenAL1,AL2alarmoperationmode[AL-1,AL-2]ssetasLBa.

Setrange:0to999(0.0to999.9)/※'0'isset,loopbreakalarmfunctionisOFF.※ ItisdisplayedwhenAL1,AL2alarmoperationmode[AL-1,AL-2]issetasLBa andLBaTisnot'0'.

Setrange:0.0to100.0%※Only0.0,100%aredisplayedwhenON/OFFcontrol.※WhenchangingPIDcontrol↔ON/OFFcontrol,ifMVisbelow100.0%,itisinitializedas0.0%.

Setrange:Withintheratedtemperaturerangebyinputsensor[L-SV ≤(H-SV-1digit)]※WhenchangingSVlowerlimitvalue,ifSV< L-SV,SVisinitializedasL-SV.

Setrange:Withintheratedtemperaturerangebyinputsensor[H-SV ≥(L-SV+1digit)]※WhenchangingSVlowerlimitvalue,ifSV>H-SVisinitializedasH-SV.

Formoredetailsreferto Functions' Alarm'.※Black:Flashes,Gray:Fixed※ WhenchangingAL1,AL2alarmoperationmode,AL1,AL2alarmtemperaturevalueareinitialized.

Press + keysfor3sec.anditexecutesthesetfunction.Formoreinformation,refertoFunctions' Digitalinputkey'.

※Whencontroltype[C-MD]isONOF,ATisnotdisplayed.

LOC1:Locksparameter2groupLOC2:Locksparameter1,2groupLOC3:Locksparameter1,2groupandSVsetting※ ParametersettingvaluesarestillpossibletocheckwhileLockmodeisON.

Referto Functions' Alarmoutputhysteresis'.※ ItisnotdisplayedwhenAL1,AL2alarmoperationmode[AL-1,AL-2]issetasAM)_,SBa ,LBa .

SVlow-limitvalue

SVhigh-limitvalue

Controloutputoperation

Controltype

Controloutputtype

SSRdriveoutputmethod

Controlcycle

AL1alarmoperationmode

AL2alarmoperationmode

Alarmoutputhysteresis

LBAmonitoringtime

LBAdetectionband

Digitalinputkey

ControloutputMVincaseofinputbreakerror

Locksetting

L-SV

H-SV

O-FT

C-MD

OUT

SSrM

AL-1

AL-2

DI-K

LBaB

LBaT

AHYS

T

ErMV

LOC

STND

AM!A

AM@A

STOP

0002

0000

001

02)0

AlRE AT OFF

00)0

OFF LOC1 LOC2 LOC3

CYCL PHAS

-050

1200

HEAT

PID

RLY

COOL

ONOF

SSR

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

Page 8: TCN Series Economical Dual Display type, PID Control · RTD Cu50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1digit Setting type Item Digit Size Auxiliary output Power supply

H-48

TCN Series

Factory default

Input type and range

Parameter 1 group Parameter 2 group

Inputsensor Display Temperaturerange() Temperaturerange()

Thermocouple

K(CA)KCaH -50to1200 -58to2192KCaL -50.0to999.9 -58.0to999.9

J(IC)JIcH -30to800 -22to1472JIcL -30.0to800.0 -22.0to999.9

L(IC)LIcH -40to800 -40to1472LIcL -40.0to800.0 -40to999.9

T(CC)TCcH -50to400 -58to752TCcL -50.0to400.0 -58.0to752.0

R(PR) R PR 0to1700 32to3092S(PR) S PR 0to1700 32to3092

RTDDPt100Ω

DTtH -100to400 -148to752DPtL -100.0to400.0 -148.0to752.0

Cu50ΩCUsH -50to200 -58to392CUsL -50.0to200.0 -58.0to392.0

Parameter Factorydefault

SVsetting - 0

AL1alarmtemperature AL1 1250

AL2alarmtemperature AL2 1250

Autotuning AT OFF

Proportionalband P 01)0

Integraltime I 0000

Derivativetime D 0000

Manualreset REST 05)0

Hysteresis HYS 002

Parameter Factorydefault

Inputsensor IN-T KCaH

Temperatureunit UNIT ?C

Inputcorrection IN-B 0000

Inputdigitalfilter MAvF 00)1

SVlow-limitvalue L-SV -050

SVhigh-limitvalue H-SV 1200

Controloutputoperation O-FT HEAT

Controltype C-MD PID

Controloutput OUT RLY

SSRdriveoutputmethod SSrM STND

Controlcycle T 02)0

AL1alarmoperationmode AL-1 AMiA

AL2alarmoperationmode LA-2 Am@A

Alarmoutputhysteresis AHYS 001

LBAmonitoringtime LBaT 0000

LBAdetectionband LBaB 0002

Digitalinputkey DI-K STOP

ControloutputMVincaseofinputbreakerror ErMV 00)0

Locksetting LOC OFF

Page 9: TCN Series Economical Dual Display type, PID Control · RTD Cu50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1digit Setting type Item Digit Size Auxiliary output Power supply

H-49

(A) Photoelectric sensor

(B) Fiberopticsensor

(C) Door/Areasensor

(D) Proximitysensor

(E) Pressuresensor

(F) Rotaryencoder

(G) Connector/Socket

(H)Temp.controller

(I)SSR/Powercontroller

(J) Counter

(K) Timer

(L) Panelmeter

(M)Tacho/Speed/ Pulsemeter

(N)Displayunit

(O)Sensorcontroller

(P)Switchingmode powersupply

(Q)Steppermotor&Driver&Controller

(R)Graphic/Logicpanel

(S)Fieldnetworkdevice

(T) Software

(U) Other

Economical Dual Display type, PID Control

Functions

Alarm operation

Alarm [ AL-1 / AL-2 ] Therearetwoalarmswhichoperateindividually.Youcansetcombinedalarmoperationandalarmoption.Usedigitalinputkey(setasAlRE)orturnOFFpowerandre-startthisunittoreleasealarmoperation.

Alarmoperation

Alarmoption

AM!A

Sensor break alarmThefunctionthatalarmoutputwillbeONwhensensorisnotconnectedorwhensensor'sdisconnectionisdetectedduringtemperaturecontrolling.Youcancheckwhetherthesensorisconnectedwithbuzzerorotherunitsusingalarmoutputcontact.Itisselectablebetweenstandardalarm[SBaA],oralarmlatch[SBaB].

Alarm optionMode Name DescriptionAM .A Standardalarm Ifitisanalarmcondition,alarmoutputisON.Ifitisaclearalarmcondition,alarmoutputisOFF.AM .B Alarmlatch Ifitisanalarmcondition,alarmoutputisONandmaintainsONstatus.

AM .C Standbysequence1Firstalarmconditionisignoredandfromsecondalarmcondition,standardalarmoperates.Whenpowerissuppliedanditisanalarmcondition,thisfirstalarmconditionisignoredandfromthesecondalarmcondition,standardalarmoperates.

AM .DAlarmlatchandstandbysequence1

Ifitisanalarmcondition,itoperatesbothalarmlatchandstandbysequence.Whenpowerissuppliedanditisanalarmcondition,thisfirstalarmconditionisignoredandfromthesecondalarmcondition,alarmlatchoperates.

AM .E Standbysequence2Firstalarmconditionisignoredandfromsecondalarmcondition,standardalarmoperates.Whenre-appliedstandbysequenceandifitisalarmcondition,alarmoutputdoesnotturnON.Afterclearingalarmcondition,standardalarmoperates.

AM .FAlarmlatchandstandbysequence2

Basicoperationissameasalarmlatchandstandbysequence1.ItoperatesnotonlybypowerON/OFF,butalsoalarmsettingvalue,oralarmoptionchanging.Whenre-appliedstandbysequenceandifitisalarmcondition,alarmoutputdoesnotturnON.Afterclearingalarmcondition,alarmlatchoperates.

Mode Name Alarmoperation Description

AM)_ - - Noalarmoutput

AM!

Deviationhigh-limitalarm

SV100

PV110

OFF ONH

PV90

SV100

OFF ONHIfdeviationbetweenPVandSVashigh-limitishigherthansetvalueofdeviationtemperature,thealarmoutputwillbeON.

Highdeviation:Setas10 Highdeviation:Setas-10

AM@

Deviationlow-limitalarm

PV90

SV100

OFFON H

SV100

PV110

OFFON HIfdeviationbetweenPVandSVaslow-limitishigherthansetvalueofdeviationtemperature,thealarmoutputwillbeON.

Lowerdeviation:Setas10 Lowerdeviation:Setas-10

AM#

Deviationhigh/low-limitalarm

PV90

PV120

SV100

OFFON ONH HIfdeviationbetweenPVandSVashigh/low-limitishigherthansetvalueofdeviationtemperature,thealarmoutputwillbeON.

Lowerdeviation:Setas10,Highdeviation:Setas20

AM$

Deviationhigh/low-limitreservealarm

PV90

PV120

SV100

OFF OFFONH HIfdeviationbetweenPVandSVashigh/low-limitishigherthansetvalueofdeviationtemperature,thealarmoutputwillbeOFF.

Lowerdeviation:Setas10,Highdeviation:Setas20

AM%

Absolutevaluehighlimitalarm

PV90

SV100

OFF ONH

SV100

PV110

OFF ONH

IfPVishigherthantheabsolutevalue,theoutputwillbeON.

Absolute-valueAlarm:Setas90

Absolute-valueAlarm:Setas110

AM^

Absolutevaluelowlimitalarm

PV90

SV100

OFFON H

SV100

PV110

OFFON H

IfPVislowerthantheabsolutevalue,theoutputwillbeON.

Absolute-valueAlarm:Setas90

Absolute-valueAlarm:Setas110

SBa SensorbreakAlarm - ItwillbeONwhenitdetectssensordisconnection.LBa LoopbreakAlarm - ItwillbeONwhenitdetectsloopbreak.

※ H:Alarmoutputhysteresis[AHYS]

※Conditionofre-appliedstandbysequenceforstandbysequence1,alarmlatchandstandbysequence1:PowerONConditionofre-appliedstandbysequenceforstandbysequence2,alarmlatchandstandbysequence2:PowerON,changingsettemperature,alarmtemperature[AL1,AL2]oralarmoperation[AL-1,AL-2],switchingSTOPmodetoRUNmode.

Page 10: TCN Series Economical Dual Display type, PID Control · RTD Cu50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1digit Setting type Item Digit Size Auxiliary output Power supply

H-50

TCN Series

Loop break alarm(LBA) Itcheckscontrolloopandoutputsalarmbytemperaturechangeofthesubject.Forheatingcontrol(coolingcontrol),whencontroloutputMVis100%(0%forcoolingcontrol)andPVisnotincreasedoverthanLBAdetectionband[LBaB]duringLBAmonitoringtime[LBaT],orwhencontroloutputMVis0%(100%forcoolingcontrol)andPVisnotdecreasedbelowthanLBAdetectionband[LBaB]duringLBAmonitoringtime[LBaT],alarmoutputturnsON.

Startcontrolto① WhencontroloutputMVis0%andPVisnotdecreasedbelowthanLBAdetectionband[LBaB]duringLBAmonitoringtime[LBaT]

① to ② ThestatusofchangingcontroloutputMV(LBAmonitoringtimeisreset.)

② to ③ WhencontroloutputMVis0%andPVisnotdecreasedbelowthanLBAdetectionband[ LBaB]duringLBAmonitoringtime[LBa]loopbreakalarm(LBA)turnsONafterLBAmonitoringtime.

③ to ④ ControloutputMVis0%andloopbreakalarm(LBA)turnsandmaintainsON.

④ to ⑥ ThestatusofchangingcontroloutputMV(LBAmonitoringtimeisreset.)

⑥ to ⑦ WhencontroloutputMVis100%andPVisnotincreasedoverthanLBAdetectionband[LBaT]duringLBAmonitoringtime[LBaT],loopbreakalarm(LBA)turnsONafterLBAmonitoringtime.

⑦ to ⑧ WhencontroloutputMVis100%andPVisincreasedoverthanLBAdetectionband[LBaB]duringLBAmonitoringtime[LBaT]loopbreakalarm(LBA)turnsOFFafterLBAmonitoringtime.

⑧ to ⑨ ThestatusofchangingcontroloutputMV(LBAmonitoringtimeisreset.)

※Whenexecutingauto-tuning,LBAdetectionband[LBaB]andLBAmonitoringtimeareautomaticallysetbasedonautotuningvalue.Whenalarmoperationmode[AL-1,AL-2]issetasloopbreakalarm(LBA)[LBa ],LBAdetectionband

[LBaB]andLBAmonitoringtime[LBaT]parameterisdisplayed.

Temperature

SV

LBAmonitoring time

PV

LBA detectionband

LBA detectionband

LBA detectionband

LBA detectionband

LBAinvalid

LBAinvalid

LBAinvalid

LBAmonitoring time

LBAmonitoring time

LBAmonitoring time

LBAmonitoring time

Controloutput

MV

100%

Time

① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨

0%Loop breakalarm(LBA)

SSRvoltageoutput(12VDC)

INPUT LOAD

Load

Power100-240VAC50/60Hz

Temperature controller(TCN4Series) SSR Module

※Whenselectingphaseorcyclecontrolmode,the power supply for load and temperature controller must be the same.※ IncaseofselectingPIDcontroltypeandphase[PHAS]/cycle[CYCL]controloutputmodes,controlcycle[T]isnotallowedtoset.

※ ForAC/DCpowermodel(TCN4 -22R),thisparameterisnotdisplayedanditisavailableonlystandardcontrolbyrelayorSSR.

Realizinghighaccuracyandcosteffectivetemperaturecontrolwithbothcurrentoutput(4-20mA)andlinearoutput(cyclecontrolandphasecontrol)

SSRPoutputisselectableoneofstandardON/OFFcontrol,cyclecontrol,phasecontrolbyutilizingstandardSSRdrivevoltageoutput.

SelectoneofstandardON/OFFcontrol[STND],cyclecontrol[CYCL],phasecontrol[PHAS]atSSrMparameterofsetting2group.Forcyclecontrol,connectzerocrossturn-onSSR(randomturn-onSSRisalsoavailable).Forphasecontrol,connectrandomturn-onSSR.

SSR drive output function(SSRP function) [ SSrM]

Page 11: TCN Series Economical Dual Display type, PID Control · RTD Cu50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1digit Setting type Item Digit Size Auxiliary output Power supply

H-51

(A) Photoelectric sensor

(B) Fiberopticsensor

(C) Door/Areasensor

(D) Proximitysensor

(E) Pressuresensor

(F) Rotaryencoder

(G) Connector/Socket

(H)Temp.controller

(I)SSR/Powercontroller

(J) Counter

(K) Timer

(L) Panelmeter

(M)Tacho/Speed/ Pulsemeter

(N)Displayunit

(O)Sensorcontroller

(P)Switchingmode powersupply

(Q)Steppermotor&Driver&Controller

(R)Graphic/Logicpanel

(S)Fieldnetworkdevice

(T) Software

(U) Other

Economical Dual Display type, PID Control

Standard ON/OFF control mode [ STND]

Cycle control mode [ CYCL]

Phase control mode [ PHAS]

AmodetocontroltheloadinthesamewayasRelayoutputtype.(ON:outputlevel100%,OFF:outputlevel0%)

AmodetocontroltheloadbyrepeatingoutputON/OFFaccordingtotherateofoutputwithinsettingcycle.HavingimprovedON/OFFnoisefeaturebyZeroCrosstype.

AmodetocontroltheloadbycontrollingthephasewithinAChalfcycle.Serialcontrolisavailable.RANDOMTurn-ontypeSSRmustbeusedforthismode.

Heatingoperation

Controloutput

ON OFF

SVTemperature

Hysteresis[HYS]

Auto tuning [ AT] Hysteresis [ HYS]Autotuningmeasuresthecontrolsubject'sthermalcharacteristicsandthermalresponserate,andthendeterminesthenecessaryPIDtimeconstant.(Whencontroltype[C-MD]issetasPID,itisdisplayed.)

Iferror[OPEN]occursduringautotuning,itstopsthisoperationautomatically.

Tostopautotuning,changethesetasOFF.(ItmaintainsP,I,Dvaluesofbeforeautotuning.)

IncaseofON/OFFcontrol,setbetweenONandOFFintervalsashysteresis.(Whencontroltype[C-MD]issetasONOF,itisdisplayed.)

Ifhysteresisistoosmall,itmaycausecontroloutputhunting(takeoff,chattering)byexternalnoise,etc.

Manual reset [ REST]WhenselectingP/PDcontrolmode,certaintemperaturedifferenceexistsevenafterPVreachesstablestatusbecauseheater'srisingandfallingtimeisinconsistentduetothermalcharacteristicsofcontrolledobjects,suchasheatcapacity,heatercapacity.Thistemperaturedifferenceiscalledoffsetandmanualreset[REST]functionistoset/correctoffset.WhenPVandSVareequal,resetvalueis50.0%.Aftercon-trolisstable,PVislowerthanSV,resetvalueisover50.0%orPVishigherthanSV,resetvalueisbelow50.0%.

Manualreset[REST]bycontrolresult

Temperature unit selection [ UNIT]Afunctiontoselectdisplaytemperatureunit.UnitdisplaylampwillbeONwhenconvertingtemperatureunit.

Input correction [ IN-B]Controlleritselfdoesnothaveerrorsbuttheremaybeerrorbyexternalinputtemperaturesensor.Ex)Ifactualtemperatureis80butcontrollerdisplays

78,setinputcorrectionvalue[IN-B]as002andcontrollerdisplays80.

※ Astheresultofinputcorrection,ifcurrenttemperaturevalue(PV)isovereachtemperaturerangeofinputsensor,itdisplaysHHHHorLLLL.

Input digital filter [ MAvF]Ifcurrenttemperature(PV)isfluctuatingrepeatedlybyrapidchangeofinputsignal,itreflectstoMVandstablecontrolisimpossible.Therefore,digitalfilterfunctionstabilizescurrenttemperaturevalue.Forexample,setinputdigitalfiltervalueas0.4sec,anditappliesdigitalfiltertoinputvaluesduring0.4secanddisplaysthisvalues.Currenttemperaturemaybedifferentbyactualinputvalue.

SV High/Low limit [ L-SV / H-SV] ItsetsSVhigh/lowlimitLimitrangeofusingtemperaturewithintemperaturerangeforeachsensor,usercanset/changesettemperature(SV)withinSVhighlimit[H-SV]toSVlowlimit[L-SV].(※L-SV>H-SVcannotbeset.)

Whenchanginginputtype[IN-T],SVhighlimit[H-SV]andSVlowlimit[L-SV]ofusingtemperaturewillbeinitializedasmax./min.valueofsensortemperaturerangeautomatically.

50Cycle 50Cycle50% 80%

AC

OUT

ON ONOFF OFF

AC

OUT

10% 50%

AC

OUT

SV

PV

Offset

Setbelow50.0asresetvalue

Setover50.0asresetvalue

Offset

※ ManualresetfunctionisapplicableonlytoP/PDcontrolmode.

Page 12: TCN Series Economical Dual Display type, PID Control · RTD Cu50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1digit Setting type Item Digit Size Auxiliary output Power supply

H-52

TCN Series

Display Description Troubleshooting

OPENFlashesifinputsensorisdisconnectedorsensorisnotconnected.

Check inputsensorstate.

HHHHFlashesifmeasuredsensorinputishigherthantemperaturerange. Wheninput iswithin

theratedtemperaturerange, this displaydisappears.LLLL

Flashesifmeasuredsensorinputislowerthantemperaturerange.

Display Description

OFF Lockoff

LOC1 Lockparametergroup2

LOC2 Lockparametergroup1,2

LOC3 Lockparametergroup1,2,SVsetting

Cool / Heat function [ O-FT]

Lock setting [ LOC] Error

Control output MV [ ErMV] when input sensor line is broken [ OPEN] / setting error [ ERSV] occur

Control method selection [ C-MD] ItisselectablePID,ON/OFFcontrol.IncaseofON/OFF[ONOF]mode,Hysteresis[HYS]parameterisdisplayed.

IncaseofPID[PID]mode,Proportionalband[P],Integraltime[I],andDerivativetime[ T]parametersaredisplayed.

AfunctiontopreventchangingSVandparametersofeachsettinggroup.ParametersettingvaluesarestillpossibletocheckwhileLockmodeisON.

Generallytherearetwowaystocontroltemperature,one(heat-function)istoheatwhenPVisgettingdown(heater).Theother(cool-function)istocoolwhenPVisgettinghigher(freezer).ThesefunctionsareoperatingoppositelywhenitisON/OFFcontrolorproportionalcontrol.ButinthiscasePIDtimeconstantwillbedifferentduetoPIDtimeconstantwillbedecidedaccordingtocontrolsystemwhenitisPIDcontrol.Cool-function[COOL]andheat-function[HEAT]mustbesetcorrectlyaccordingtotheapplication,ifsetasoppositefunction,itmaycauseafire.(Ifsetcool-function[COOL]atheater,itwillbemaintainedONanditmaycauseafire.)

Avoidchangingheat-functiontocool-functionorcool-functiontoheat-functionwhentheunitisoperating.

Itisimpossibletooperatebothfunctionatonceinthisunit.Therefore,onlyonefunctionshouldbeselectedonly.

Wheninputsensorlineisbrokenorsettingvalueerroroccurs,thisfunctionistosetcontroloutput.YoucansetON/OFFsettingforON/OFFcontrol,MVsettingforPIDcontrol.

Alarm output hysteresis [ AHYS] ItdisplaysalarmoutputONandOFFintervalandhysteresisisappliedtobothAL1OUTandAL2OUT.•KCaH, JIcH, LIcH, TCcH, RPR, SPR, DPtH,CUsH

:1to100•KCaL, JIcL, LIcL, TCcL,DPtL,CUsL:0.1to50.0Ex)AL1alarmoperation[AL-1]:AM#A,AL1alarmoperation[AL1]:10, Alarmoutputhysteresis[AHYS]:4

210

190

Temperature

SV200

ONOFF

AL1OUT

210 206 190 194

:4

:4PV

Time

Digital input key( + 3sec.) [ DI-K]Parameter Operation

OFF OFF Itdoesnotusedigitalinputkeyfunction.

RUN/STOP STOP

Itisavailabletopauseoncontroloutputandauxiliaryoutput(exceptloopbreakalarm,sensorbreakalarm)exceptcontroloutputoperatesnormallyasset.Pressdigitalinputkeyfor3sectore-starttheoperation.

RUN

t t t t

STOP

t:3sec.

STOP RUNRUN

Clearalarmoutputfunction AlRE

Itisavailabletoclearalarmoutputbyforce.(Itisonlywhenalarmoptionisalarmlatch,standbysequence.)Clearalarmisabletoonlyforoutofalarmoperationrange.Alarmoperatesnormallyrightafterclearalarm.

Autotunning AT

Autotuningfunction,itissameasautotuningfunction[AT]ofparameter1group.(Youcanexecuteautotuningfromparameter1group,andfinishitbydigitalinputkey.)※Whencontroltype[C-MD]issetasPID, AT isdisplayed.WhenitissetasONOF,digitalinputkey[DI-K]ischangedasOFF.

Control output type selection [ OUT] Itisselectableoutputtype;relayoutput[RLY],SSRdriveoutput[SSR].

Page 13: TCN Series Economical Dual Display type, PID Control · RTD Cu50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1digit Setting type Item Digit Size Auxiliary output Power supply

H-53

(A) Photoelectric sensor

(B) Fiberopticsensor

(C) Door/Areasensor

(D) Proximitysensor

(E) Pressuresensor

(F) Rotaryencoder

(G) Connector/Socket

(H)Temp.controller

(I)SSR/Powercontroller

(J) Counter

(K) Timer

(L) Panelmeter

(M)Tacho/Speed/ Pulsemeter

(N)Displayunit

(O)Sensorcontroller

(P)Switchingmode powersupply

(Q)Steppermotor&Driver&Controller

(R)Graphic/Logicpanel

(S)Fieldnetworkdevice

(T) Software

(U) Other

Economical Dual Display type, PID Control

Output connectionsSeeH-139pageforoutput.

Application of relay output type

KeepAlengthaslongaspossiblewhenwiringthetemperaturecontrollerandtheload.IfwirelengthofAisshort,counterelectromotiveforcewhichoccursfromacoilofmagnetswitch&powerrelaymayflowinpowerlineoftheunit,anditmaycausemalfunction.IfwirelengthofAisshort,pleaseconnectmylarcondensers104(630V)onthebothendsof" "(magnetcoil)toprotectelectromotiveforce.

Voltageoutputterminal

TCNSeries SSR

Loadpower

Power

+

-

INPUT

LOAD

※ SSRshouldbeselectedbythecapacityofload,otherwise,itmayshort-circuitandresultinafire.IndirectheatedshouldbeusedwithSSRforefficientworking.

※ Pleaseuseacoolingplateoritmaycausethecapabilitydeterioration,breakdownofSSRforalongusage.

※ RefertotheH-50pageforphase/cyclecontrolconnections.

Application of SSR drive output method

When the load (Heater etc) is not operatedPleasecheckoperationoftheOUTlamplocatedinfrontpaneloftheunit.IftheOUTlampdoesnotoperate,pleasechecktheparameterofallprogrammedmode.Iflampisoperating,pleasechecktheoutput(Relay,SSRdrivevoltage)afterseparatingoutputlinefromtheunit.

When it displays OPEN during operationThisisawarningthatexternalsensorisopen.Pleaseturnoffthepowerandcheckthewirestateofthesensor.Ifsensorisnotopendisconnectsensorlinefromtheunitandshorttheinput+,-terminal.Turnonthepoweroftheunitandcheckthecontrollerdisplaysroomtemperature.Ifthisunitcannotdisplayroomtemperature,thisunitisbroken.Pleaseremovethisunitandcontactourservicecenter.(Whentheinputmodeisthermocouple,itisavailabletodisplayroomtemperature.)

Proper usage Simple "error" diagnosis

Theconnectionwireofthisunitshouldbeseparatedfromthepowerlineandhighvoltagelineinordertopreventfrominductivenoise. Forcrimpterminal,selectfollowingshapedterminal(M3)

Max.5.8mm Max.5.8mm

Pleaseinstallpowerswitchorcircuit-breakerinordertocutpowersupplyoff. Theswitchorcircuit-breakershouldbeinstallednearbyusers. Thisunitisdesignedfortemperaturecontrollingonly.Donotapplythisunitasavoltagemeteroracurrentmeter. IncaseofusingRTDsensor,3-wiretypemustbeused.Ifyouneedtoextendtheline,3-wiresmustbeusedwiththesamethicknessastheline.Itmightcausetemperaturedifferenceiftheresistanceoflineisdifferent. Incaseofmakingpowerlineandinputsignallineclose,linefilterfornoiseprotectionshouldbeinstalledatpowerlineandinputsignallineshouldbeshielded. Keepawayfromthehighfrequencyinstruments.(Highfrequencyweldingmachine&sewingmachine,bigcapacitiveSCRcontroller) Whensupplyingmeasuredinput,ifHHHHorLLLLisdisplayed,measuredinputmayhaveproblem.Turnoffthepowerandchecktheline. Installationenvironment

Itshallbeusedindoor. AltitudeMax.2000m. PollutionDegree2 InstallationCategoryⅡ.

Caution for using

TCNSeries A

Relaycontactterminal

Heater

PowerCondenser

0.1630V

MagnetorRelaycontact