tech talk - june 05
TRANSCRIPT
-
7/31/2019 Tech Talk - June 05
1/5
TECHTALK
34 JUNE 05 MOTOR INDUSTRY MAGAZINE WWW.MOTOR.ORG.UK
In part 1 (May issue) we discussed aspects
of electrical circuits and related test
equipment which must be understood if
you are to diagnose electrical faults
accurately and quickly. Here, we look at
the further application of such knowledge
to the fault-finding process.
REVISION IN BRIEF
In part 1 there was a detailed look at the 4
essential electrical rules: A digital voltmeter
displays the difference in voltage between
where you place the black probe and where
you place the red probe; the voltage after the
last resistance in a circuit will always be zeroproviding current can flow; volt drop will occur
across a resistance, providing current can flow;
and the volt drop across a resistance in a series
circuit is in direct proportion to the comparative
resistances values.
So far, we have studied the application of
these rules to the diagnostic process with a few
examples of open circuit faults (breaks in the
circuit).
Now we will discuss other fault types and
use tricks of the trade to enable you to
accurately diagnose faults very quickly andconfidently.
Short circuit faults
Open circuit faults are only one of several types
of fault that you could encounter. A short
circuit fault is where current flows in a circuit
(when it should not be) due to an unwanted
route to earth.
The location of the short to earth dictates
the effect that it will have on the circuit. It could
lead to a blown fuse/tripped circuit breaker,
melted looms or worse, a fire but it couldalso lead to a discharged battery through the
permanent on condition of an electrical
consumer. This latter problem is more generally
known as a parasitic drain fault, which we
will return to later.
A short circuit fault will blow a fuse when
there is no resistance in the circuit to limit
current flow. An excess of current flow in a
wire will lead to rapid heat build up resulting
in the blown fuse (hopefully!). A fuse is a weak
link by design and its current rating is such
that it will fail before the circuit can be
damaged. Once the fuse has blown, current
can no longer flow in the circuit, and so the
circuit is protected. A blown fuse can be a very
good indication that a short circuit has
occurred.
The circuit in example 1 has suffered a
short circuit fault. The short has led to the fuse
blowing. If we wish to diagnose the fault using
a voltmeter, we have a problem. The voltmeter
will confirm that the fuse has blown (batteryvoltage into the fuse, 0 volts out) but it is little
use in identifying the location of the short.
By linking the symptom (blown fuse) to the
circuit layout, we know immediately that the
short must lie between the output from the
fuse and the supply terminal of lamp 1. We
can be sure of this because if the fault were
after the lamp no symptom would be
presented, as this is an earth wire anyway; if
the fault was before the fuse, the fuse would
not have blown and we would have had a fire
to deal with. This is the reason that fuses are
placed as physically close to the battery as
possible that way, more of the circuit is
protected.
If the fuse is replaced with a new one, the
fuse will simply blow again. A method to
alleviate this problem would be to place a testlamp across the fuse block terminals (fuse
removed), thereby placing a resistance in the
circuit. Now that there is a resistance to current
flow in the circuit, the circuit will not be at risk
of damage. The short circuit fault will result in
the test lamp illuminating. To diagnose the
exact location of the short we now start to
disconnect connectors in turn on the circuit
ESSENTIAL ELECTRICAL SKILLS PART 2
Example 1
Example 1 test light use
-
7/31/2019 Tech Talk - June 05
2/5
WWW.MOTOR.ORG.UK MOTOR INDUSTRY MAGAZINE JUNE 05 35
and observe the reaction of the test lamp.
When the test light goes out (upon
disconnection of a connector), the fault must
lie after that connector but before the
connector that had no effect on the test light
(upon disconnection).
The connector that you disconnect first will
be dictated by ease of access and minimal trim
removal. Remember that trim rarely refits as
well as the manufacturer fitted it in the first
place.
In example 1, the first connector to be
disconnected is d. If the test lamp goes out
we know the short must have occurred in
between the lamp and connector d. In this
instance the test lamp stayed illuminated and
so the fault isnt there. The next process is to
reconnected d and disconnect c. Bydisconnecting c the test lamp goes out telling
us that the fault lies between c and d.
Important! It is rare for a fuse on a
modern motor vehicle to protect only one
circuit. Because of this, the test light will
not go out, it will simply dim once the
fault is isolated. This is because your test
light is now supplying the other circuits
that the fuse protects, and current will be
flowing in the series circuits that you have
just created with your lamp. It is common
for relays to chatter as your test light iscreating volts drop on the supply side of
their windings.
Hint always choose a test lamp with
a high wattage bulb. The higher the
wattage, the lower the resistance the bulb
will have. This ensures that the difference
in test light brightness is more noticeable
when the fault has been isolated through
disconnection.
PROGRESS CHECK
Refer to the diagram in example 1 to answerthis question:
The test light went out (or dimmed
significantly) upon disconnection of connector
a, but the test lamp was unaffected by the
disconnection of connector b. Where does the
fault lie?
Answer available at the end of this article.
Example 2 shows a parasitic drain fault. This
is a fault on a circuit where there is an earth
located between a consumer and its switch
(providing the switch is on the earth side of the
circuit). This way, even if the switch is open or
closed, current is able to flow through the
consumer and it will remain on.
As the switchs position has no affect on
whether the consumer is on or not, electrical
control of the consumer is no longer possible
and it will run unnecessarily.
The diagnosis of such a fault can be simple
or complex depending upon the nature of the
problem and the circuit that has been affected.
In example 2, it is likely that the fault symptom
will be visible through a simple visual inspectionof the vehicle i.e. you will notice that the light
is on (a courtesy light for example).
In this instance, circuit disconnection is
again the method to use in order to identify the
location of the fault. We know the fault must
lie in between the lamp and the switch, and so
the fault can only lie in two places; between
the lamp and connector e, or connector e
and the switch. If we disconnect connector e
and the lamp stays on, the fault must lie in
between the lamp and connector e; if we
disconnect connector e and the lamp goesout, the fault must lie in between connector
e and the switch. In the example shown, the
lamp would go out when connector e is
disconnected.
If the consumer affected by a parasitic drain
fault displays no visible or audible symptoms
(such as a boot light), your approach needs to
be different. The customer will complain of a
flat battery (due to drainage through the
parasitic fault), but a look at the vehicles service
history will show that its been fitted with a
new battery already. Firstly, confirm that there
is not a charging fault on the vehicle. Once you
have confirmed that the vehicle is charging
efficiently, you should suspect parasitic drain.
Confirm this by measuring current draw from
the battery with all systems switched off. To do
this, place an ammeter in series with the
negative lead of the battery and measure the
current flow. Always fit the ammeter to the
negative side in order to observe safe practice
regarding correct disconnection of a battery.
Important! You should ensure that you
fit the ammeter without breaking theconnection that the vehicle has with the
negative post of the battery. This can be
done by ensuring that your ammeter leads
are in place before lifting the lead clamp
free of the battery post. This is necessary,
as some faults will disappear temporarily
if the circuit powers down.
Do not forget to remove the keys from
the ignition key cylinder and lock all doors.
Leave the vehicle for at least 10 minutes
before taking your reading as multiplex
systems that may be present take sometime to go to sleep.
As a guide, the battery draw should be no
more than about 0.1 amps (it will never be 0
amps due to systems that never power down
completely such as the clock and ECU memory
functions). If your reading is significantly more,
then you have confirmed a parasitic problem.
If you are unsure of what is an acceptable
current drain rate, the amp hour rating of the
OEM battery is often a good indication. For
example, if the battery is rated at 100
amp/hours, a current draw of 1 amp would
Example 2
-
7/31/2019 Tech Talk - June 05
3/5
TECHTALK
36 JUNE 05 MOTOR INDUSTRY MAGAZINE WWW.MOTOR.ORG.UK
render the battery flat in 4 days (100 hours).
Not too good if you have left your vehicle at
an airport for 2 weeks!
Your next step should be to confirm that
the vehicle has not been fitted with any
accessories recently that could be causing
excessive drain (car phone kits etc.). If all is well,
then you are looking for a genuine parasitic
short circuit fault.
PARASITIC SHORT CIRCUIT
FAULT DIAGNOSIS
Start removing fuses one at a time until there
is a significant reduction in battery current draw
(leave your ammeter in place). The fuse that
affected your ammeter significantly is
protecting the faulty circuit. Through effectiveuse of the wiring diagram you can now
approach your fault through disconnection as
previously discussed. Be careful, though. Some
fuses will be protecting circuits that do not
power down, such as the clock and ECUs. You
are looking for asignificantreduction in battery
draw.
HIGH RESISTANCE FAULTS
Example 1
In the circuit pictured in example 1 there is an
unwanted resistance, i.e. a corroded terminal
in connector a. As has been previouslystated; a resistance is a resistance to current
flow, and so it will reduce the amount of
current able to pass through the lamp, causing
it to glow dimly. We can locate this fault with
the use of our voltmeter.
The first measurement to make would be
at terminal d of the lamp. In this example
we do not get 12 volts at terminal d, so the
resistance must be on the positive side. We
then measure the voltage at terminal a on
the circuit to check supply voltage is correct. In
this example the supply voltage is 12 volts. We
then check the voltage at terminal b of
connector a. The measurement is 12 volts
so we now know that the wire between a
and b is good. We then check the voltage
at terminal c of connector a. In this
example we find that the voltage is
considerably less than 12v so we have now
confirmed that the fault (high resistance) lies
in connector a between terminals b and
terminal c.
Example 2
In example 2 the corroded terminal is in
connector a that is now positioned on the
earth side of the lamp (the resistance). The
symptom will be identical to the problematic
circuit in example 1 i.e. a dim bulb.
Again, the voltmeter is the tool of choice.
In this example, the voltage at terminal b ofthe lamp will be supply voltage. This confirms
that the resistance is not on the supply side
and therefore must be further along in the
circuit on the earth side.
The voltage rules previously discussed tell
us that The voltage after the last resistance in
a circuit will always be 0 volts providing current
can flow. With this rule in mind, we would
expect the voltage at terminal c of the lamp
to be 0 volts. However, the lamp is not the last
resistance in this example, the fault is (the
corroded terminals). When we measure thevoltage at terminal c, and find that it is
perhaps 3 or 4 volts (dependent upon the
comparative resistance values of the lamp and
the corroded terminals see rule 4 at the start
of this article), we know that we are looking
for a high resistance fault on the earth side.
When we check the voltage at terminal d
of connector a we will have the same
voltage reading as found at terminal c of
the lamp. This confirms that the circuit
between terminal c of the lamp and
terminal d of the connector is good. A
voltage check at terminal e of connector a
will show 0 volts. We now know that we are
after the last resistance, so that resistance must
be in connector a. Fault found!
COMMON MISTAKES!
Example 1
It can be seen that the circuit in example 1
has a break in the wire on the earth side. The
technician in this example has placed both
probes of the voltmeter onto the circuit,
rather than putting the black probe onto
chassis earth. As can be seen, the meter is
displaying 0 volts. This is because of rule 1 -
A digital voltmeter displays the difference in
voltage between where you place the black
probe and where you place the red probe.
The voltage where the red probe has beenplaced is 12v and the voltage where the black
probe has been placed is also 12v. There is
no difference between 12 and 12, so the
meter displays no difference 0 volts. It is
easy to misinterpret this reading as meaning
no supply!
There are circumstances under which
using the meter this way is advantageous
checking earth wires is typical. If in example
1 you had first confirmed that the supply to
the lamp was good using the voltmeter with
the black probe on the chassis (12 volt readingdisplayed) you could then confirm that the
earth wire is good or bad by using the meter
as pictured. If the meter now read 0 volts
when placing the black probe on the earth
wire, the earth must be faulty.
In example 2, it can be seen that there is
a high resistance fault in connector A. It can
also be seen that the voltmeter is displaying
12volts, and therefore is not indicating any
problem on the supply side of the lamp. The
reason is that the technician has disconnected
the circuit at the lamp in order to probe the
-
7/31/2019 Tech Talk - June 05
4/5
terminal. This action has prevented current
from flowing and therefore no volts drop has
occurred across the resistance (the fault). Rule
3 - Volt drop will only occur across a resistance,
providing current can flow.
Always keep the circuit complete and back
probe terminals!
Although these articles are detailed, you
have only 4 things to remember, and these are
our voltage rules quoted throughout.
Remember them, and electrical systems will
hold no fear for you!
Answer to progress check: The harness
must be shorted to ground in between
connectors a and b.
ProAuto is an automotive technical
training company based in Shrewsbury,
Shropshire. Its core business is the design
and delivery of technical training to the
automotive industry, which includes
vehicle manufacturers, component man-
ufacturers, diagnostic equipment man-
ufacturers and independent garages. The
company runs courses from numerous
venues nationally. Further details on
www.proautotraining.com, email info@
proautotraining.com, or telephone 01743
709679.Example 2
In a series of local training sessions for
motor factors, garage proprietors and
seminars for representative bodies such
as the IMI, Gates is advocating a re-
evaluation of drive systems maintenance.
In less than a generation, the role of the front-
end drive systems has been completely
transformed. Drive systems no longer simply
support the engine plant. They drive a rangeof key engine components that todays high
performance engines depend upon and
deliver the power to the auxiliary systems such
as air conditioning. So, the drive systems in
todays vehicles not only make the vehicles
more efficient and reliable they also make
them more comfortable to drive.
However, belt and tensioner man-
ufacturers Gates says the approach to drive
systems maintenance has not necessarily
evolved at the same pace as technological
change. The principles that may have beenappropriate when changing a belt in the
1970s do not apply to a belt installed as part
of a scheduled change on todays vehicle,
commented the companys technical
manager Iain Mitchell.
The engine layouts are more complex
and tensioning systems can differ slightly on
subsequent models in the same range. The
installed tension of the belts must be set
precisely, using a tool designed to do the job.
Theres no room for error. Failure of one drive
can easily lead to trouble with the other so it
makes sense to check over the components
of both the timing belt drive and the accessory
drive at the same time. Unfortunately, not
everyone always appreciates that, added
Mitchell.
IMI members from Cheshire and more
recently from the Shropshire region are
among a growing number of technical
specialist audiences to have heard the Gates
case for a complete overhaul of the front-enddrive systems as part of every scheduled belt
change. The seminars they attended covered
belt technology, installation procedures, fault
diagnostics and tension setting techniques.
The seminars also explode a few myths. For
example, its made clear that technicians
should never attempt to cure noise by easing
the tension of a belt.
Andrew Vaux, the Gates presenter at
recent events, emphasises the need for
technicians to make thorough checks of all of
the components in the timing belt drivesystem and all of the components in the
accessory drive system as well.
Changing the belt only should never be
an option, says Vaux. Since the lifetime of
all components is more or less the same, the
best solution to guarantee perfect and safe
performance is to change both belts and
metal components using a kit. In many cases,
replacing only the timing belt, tensioner and
pulleys /idlers may not even be sufficient.
While belt kits have been available for
some time, Gates has gone a step further in
order to support its case with the introduction
of the PowerGrip Kit Plus. Depending on
the application, this includes timing belt(s),
idler(s), belt tensioner units, other parts
needed for a complete overhaul (bolts,
springs, etc), oil seal(s) and/or O-rings and a
mileage sticker. In a further move, for certain
applications, Gates is planning to introduce a
Power Grip Kit Plus in early summer that also
includes the appropriate water pump.If theres a worn tensioner, an oil or water
leak or even a damaged main drive system
cover, the lifespan of the timing belt can
be compromised, with serious consequences
for the engine, says Iain Mitchell. The
technician must be sure that at the time of
the scheduled belt replacement, the water
DRIVE SYSTEMS MAINTENANCE
38 JUNE 05 MOTOR INDUSTRY MAGAZINE WWW.MOTOR.ORG.UK
TECHTALK
-
7/31/2019 Tech Talk - June 05
5/5
TECHTALK
40 JUNE 05 MOTOR INDUSTRY MAGAZINE WWW.MOTOR.ORG.UK
SMART SERVICESmartrepairer.com is a web site from Power-Tec providinginformation about panel repair on both steel and aluminium, plus
other smart-type repair techniques.
It lists repairers offering this type of work both alphabetically
and by region. There are also sections devoted to tips, seminars
and training.
Further information on 01926 484187.
HELP FROM HELLAAdvice for workshops on air conditioning, electronics, electrics orlighting problems is now available from Hella through a technical
helpline.
Staffed by specialists with a workshop background, the helpline
is available to all aftermarket garages and repairers, supplying answers
to diagnostic, parts operation and fitting queries across a full range
of car, light commercial and CV applications.
The helpline is not intended to service general catalogue and
application enquiries; these will continue to be handled by Hellas
customer services department.
Helpline calls are charged at 1.20 per minute, inclusive of VAT,
and Hella says most enquiries should be resolved within five minutes.To guard against improper use, calls are limited to a maximum
duration of 25 minutes (charged at 30). In the event of a call
exceeding this length, the customer is asked to hang up and dial a
second time.
The helpline number is 09056 700 999. Further information
on 01295 272233.
Forte has extended its sponsorship of engine diagnostic management seminars to cover a
programme of diesel training for independent garages.
The half-day, Saturday morning HDI (High Pressure Direct Injection) and PDI (Piezo Direct
Injection) courses are being run by Eric Mitchell of AT Training. They are specifically geared
towards independent garage technicians who are working on the latest common rail
technology, but do not have ready access to the type of in depth courses offered within franchise
dealer groups.
Cost is 35 (plus VAT) per person.
Contact Rachel Roberts at Forte on 024 76 474069.
More than 140 new car and light commercial model references arelisted in the latest editions of the Mahle and Knecht filter catalogues.
Models using OE filtration supplied by Mahle now include the
Citroen C4, MK5 Golf, Skoda Octavia and BMW M5.
As well as oil, fuel and panel air filters, the catalogues feature
Mahles Micro-Star cabin filters.
FILTER FACTS
pump has the ability and integrity to complete
another full duty cycle because if the water
pump fails, coolant will leak and can
contaminate the belt. Long-term coolant
contamination will eventually lead to timing
belt failure.
On the issue of training, Andrew Vaux
said: In a garage with more than one
technician, or a business or dealership with
more than one location, there are likely to be
alternative approaches to timing belt
replacement procedures - probably related to
differences in the type of training received or
the relative experience of the technicians on
site. Unless everybodys approach is always the
same, oversights occur and problems in the
future may arise such as premature failure
of a belt.
He says that such a procedure should
specify the tools that technicians should
always use, indicate all of the components
that should be inspected, as well highlighting
the parts that should always be replaced.
Ultimately, the overhaul approach
means an additional cost to the car owner,
but the performance and long term reliability
of the engine will be significantly increased.
Formalising the procedure adds a quality
control measure that makes the garage more
efficient, adds a level of protection for the
garage and improves the quality of service that
the customer receives.
Gates provides free support and advice for
drive system diagnostic skills. It also provides
guidance on the introduction of a formal
inspection and installation procedure.
For further information contact:
Iain Mitchell on 01387 242075, email
DIESEL TRAINING FROM FORTE