Technical brochure Temperature controller
type EKC 100
Introduction The controller is used for temperature control of refrigeration plant.
Operation, setting and programming are optimised and simplified as much as possible.
The controller is designed so that temperature control and defrost control can be made via pump down or start/stop of the compressor.
Parameter Min.value
Max.value
Factory setting
Actual settingFunction Code
Normal operationTemperature (set point) --- -60°C 25°C 0°CThermostatDifferential r1 1 K 20 K 2 KDisplay adjust r4 -20 K 20 K 0 KCompressorMin. ON-time c1 0 min. 15 min. 0 min.Min. OFF-time c2 0 min. 15 min. 0 min.DefrostDefrost stop temperature d2 0°C 25°C /off 25°C /offInterval between defrost starts d3 0 hours 48 hours 8 hoursMax. defrost duration d4 0 min. 99 min. 45 min.Displacement of time on cutin of defrost at start-up d5 0 min. 15 min. 0 min.MiscellaneousDelay of output signal after start-up o1 0 min 15 min 0 minFault codeSensor error Er
SW = 1.1XFunctions and settings
Set temperature1. Push the middle button until the temperature value
is shown2. Push the upper or the lower button and select the
new value3. Push the middle button to select the setting.
Manual start or stop of a defrost• Push the lower button for five seconds.
Set menu1. Push the upper button until a parameter is shown2. Push the upper or the lower button and find that
parameter you want to change3. Push the middle button until the parameter value
is shown4. Push the upper or the lower button and select the
new value5. Push the middle button again to enter the value. Time out 20 sec.
Warning ! Direct start of compressors *To prevent compressor breakdown parameter c1 and c2 should be set according to suppliers requirements or in general :Hermetic Compressors c2 min. 5 minutesSemihermetic Compressors c2 min. 8 minutes and c1 min. 2 to 5 minutes ( Motor from 5 to 15 KW )* ) Direct activating of solenoid valves does not require settings different from factory (0)
2 Technical brochure RD8AZ602 © Danfoss 12/2008 EKC 100
DE-
BD
Type Function Voltage Number Code no.
EKC 100 Temperature controller230 V 60 084B8610
115 V 60 084B8611
Ordering
Technical data
Electrical connection
Supply voltage 230 V a.c. +10/-15 %. 0.5 VA, 50/60 Hz
Sensor connec-tion
NTC 5000 ohm / 25°C. Fx type EKS 211
Accuracy
Measuring range -60 to +50°C
Controller±1 K below -0°C±0.5 K between -0 to +10°C ±1 K above +10°C
NTC sensor ±0.5 K at 0°C
Display LED, 2 digits
Light-emitting diode (LED)
Indicates cut-in relay
Electrical con-nection cable
Max.1,5 mm2 multi-core cable on supply and relays.Max. 1 mm2 on sensorsTerminals are mounted on the circuit board
Relay
CE UL
Rated voltage 250 V 240 V a.c.
I 10 (6) A10 A Resistive 5FLA 30LRA
The relay is a 16 A relay, but conductor lanes and derating mean that 10 (6) A must not be exceeded
Environments
0 - 55°C, during operation-40 - 70°C, during transport
20 - 80% Rh, not condensed
No shock influence / vibrations
DensityIP 20 / IP 65 from front.Buttons are imbedded in the front.
ApprovalsEU Low Voltage Directive and EMC demands re CE-marking complied withLVD tested acc. EN 60730-1 and EN 60730-2-9, A1, A2EMC tested acc. EN50082-1 and EN 60730-2-9, A2
Regulation starts when the voltage is on.
NTC - temperature sensor type EKS 211: Please refer to tech. brochure RD8AY
(115 V a.c.)
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed.All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.