technical clarification for kbf trading & contg. co - jw marriot hotel qatar

1
Customer Ref.: T023 Oracle: TC-141356- 01-00 DOCUMENT TITLE Page 1 of 1 TECHNICAL CLARIFICATION Date: 09/03/2015 Seri al No CUSTOMER REQUIREMENTS MESC CLARIFICATION FINAL DECISION BY PURCHASER 1 Electrical Specification Section 16120 Cl. 2.2.A refers multi core cables 35mm2 and above is to be sectoral shape & Cl. 2.3 refers conductor to be compacted. MESC offer power and control cables with conductor of stranded annealed plain circular non-compacted copper Class 2 as per IEC 60228. 2 BOQ refers fire rated cables. MESC offer fire resistant cables CU/XLPE/LSHF rated 0.6/1kV as per IEC 60502-1 (halogen content (outer sheath) ≤ 0.5%). Technical Engineer: Technical Manager:

Upload: just4cable

Post on 22-Dec-2015

221 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Technical Clarification for Kbf Trading & Contg. Co - Jw Marriot Hotel Qatar

Customer Ref.: T023Oracle: TC-141356-01-00 DOCUMENT TITLE Page 1 of 1

TECHNICAL CLARIFICATION Date: 09/03/2015

Serial No

CUSTOMER REQUIREMENTS MESC CLARIFICATIONFINAL

DECISION BYPURCHASER

1

Electrical Specification Section 16120 Cl. 2.2.A refers multi core cables 35mm2 and above is to be sectoral shape & Cl. 2.3 refers conductor to be compacted.

MESC offer power and control cables with conductor of stranded annealed plain circular non-compacted copper Class 2 as per IEC 60228.

2 BOQ refers fire rated cables.MESC offer fire resistant cables CU/XLPE/LSHF rated 0.6/1kV as per IEC 60502-1 (halogen content (outer sheath) ≤ 0.5%).

Technical Engineer: Technical Manager: