technical clarification for kbf trading & contg. co - jw marriot hotel qatar
TRANSCRIPT
Customer Ref.: T023Oracle: TC-141356-01-00 DOCUMENT TITLE Page 1 of 1
TECHNICAL CLARIFICATION Date: 09/03/2015
Serial No
CUSTOMER REQUIREMENTS MESC CLARIFICATIONFINAL
DECISION BYPURCHASER
1
Electrical Specification Section 16120 Cl. 2.2.A refers multi core cables 35mm2 and above is to be sectoral shape & Cl. 2.3 refers conductor to be compacted.
MESC offer power and control cables with conductor of stranded annealed plain circular non-compacted copper Class 2 as per IEC 60228.
2 BOQ refers fire rated cables.MESC offer fire resistant cables CU/XLPE/LSHF rated 0.6/1kV as per IEC 60502-1 (halogen content (outer sheath) ≤ 0.5%).
Technical Engineer: Technical Manager: