Technical Committee on Private Water Supply Piping Systems MEMORANDUM DATE: June 26, 2013 TO: Principal and Alternate Members of the Technical Committee on Private Water Supply Piping Systems FROM: Matt Klaus, Principal Fire Protection Engineer/NFPA Staff Liaison SUBJECT: AUT-PRI AGENDA PACKAGE – A2015 Pre-First Draft Meeting ________________________________________________________________________ Enclosed is the agenda for the Pre-First Draft meeting for NFPA 13, Standard for the Installation of Sprinkler Systems, NFPA 24, Standard for the Installation of Private Fire Service Mains and Their Appurtenances, and NFPA 291 Recommended Practice for Fire Flow Testing and Marking of Hydrants. NFPA 13, 24 and 291 have entered the Annual 2015 revision cycle and will produce 2016 Editions. It is imperative that you review the attached public input in advance, with your ideas and substantiations for your views. If you have alternate suggestions for text changes, please come prepared with the words and respective substantiation. For administrative questions, please feel free to contact Elena Carroll at (617) 984-7952. For technical questions, please feel free to contact Matt Klaus at (617) 984-7448. You can also reach either of us via e-mail at [email protected] or [email protected] . We look forward to meeting everyone in St, Louis, MO at the St. Louis Union Station - a DoubleTree by Hilton Hotel

Upload: lyque

Post on 08-Jun-2018

219 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

Technical Committee on

Private Water Supply Piping Systems

MEMORANDUM

DATE: June 26, 2013 TO: Principal and Alternate Members of the Technical Committee on Private Water Supply Piping Systems FROM: Matt Klaus, Principal Fire Protection Engineer/NFPA Staff Liaison SUBJECT: AUT-PRI AGENDA PACKAGE – A2015 Pre-First Draft Meeting ________________________________________________________________________ Enclosed is the agenda for the Pre-First Draft meeting for NFPA 13, Standard for the Installation

of Sprinkler Systems, NFPA 24, Standard for the Installation of Private Fire Service Mains and

Their Appurtenances, and NFPA 291 Recommended Practice for Fire Flow Testing and Marking

of Hydrants. NFPA 13, 24 and 291 have entered the Annual 2015 revision cycle and will

produce 2016 Editions. It is imperative that you review the attached public input in advance,

with your ideas and substantiations for your views. If you have alternate suggestions for text

changes, please come prepared with the words and respective substantiation.

For administrative questions, please feel free to contact Elena Carroll at (617) 984-7952.

For technical questions, please feel free to contact Matt Klaus at (617) 984-7448. You can

also reach either of us via e-mail at [email protected] or [email protected]. We look forward

to meeting everyone in St, Louis, MO at the St. Louis Union Station - a DoubleTree by Hilton

Hotel

Page 2: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

Table of Contents

Part 1 - Meeting Agenda

Part 2 - Committee Address List

Part 3 – New Process Worksheets

Part 4 – A2012 ROC Meeting Minutes

Part 5 - A2015 Key Dates

Part 6- PRI Public Input

Page 3: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

Technical Committee on Private Water Supply Piping Systems

Pre-First Draft Meeting

July 10-11, 2013 St. Louis Union Station - a DoubleTree by Hilton Hotel

1820 Market St. One Union Station St Louis, Missouri, 63103

AGENDA

Wednesday, July 10, 2013

1. Call to Order – 8:00 AM 2. Introductions of Members and Staff 3. Review and Approval of A2012 ROC Meeting Minutes 4. Review of A2015 Revision Cycle and Meeting Schedule 5. Review of Distributed Material and Workload

b. Overview of Public Input c. Overview of Potential Committee First Revisions

6. Review NFPA 24 Rewrite Work To Date 7. Establish Ne Task Groups if Necessary 8. Adjourn 12:00 PM 9. Lunch 12:00 PM – 1:00 PM 10. New Process Training and Mock Meeting 1:00 PM – 4:00 PM

Thursday, July 11, 2013

11. Reconvene for Task Group Meetings – 8:00AM 12. Adjourn (TBD)

Page 4: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

PART 2 –

COMMITTEE ADDRESS LIST

Page 5: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

Address List No PhonePrivate Water Supply Piping Systems AUT-PRI

Automatic Sprinkler Systems

Matthew J. Klaus06/19/2013

AUT-PRI

Kenneth W. Wagoner

ChairParsley Consulting Engineers350 West 9th Avenue, Suite 206Escondido, CA 92025-5053

SE 8/5/2009AUT-PRI

James B. Biggins

PrincipalGlobal Risk Consultants Corporation15732 West Barr RoadManhattan, IL 60442-9012Alternate: William J. Gotto

SE 1/1/1996

AUT-PRI

Phillip A. Brown

PrincipalAmerican Fire Sprinkler Association, Inc.12750 Merit Drive, Suite 350Dallas, TX 75251Alternate: Jeffrey J. Rovegno

IM 10/6/2000AUT-PRI

James A. Charrette

PrincipalAllan Automatic Sprinkler Corp. of So. California3233 Enterprise StreetBrea, CA 92821National Fire Sprinkler AssociationInstaller/MaintainerAlternate: Ronald N. Webb

IM 7/26/2007

AUT-PRI

Flora F. Chen

PrincipalHayward Fire Department, California777 B StreetHayward, CA 94541

E 10/20/2010AUT-PRI

Stephen A. Clark, Jr.

PrincipalAllianz Risk Consulting, LLC1003 Reece DriveHoschton, GA 30548Alternate: Andrew C. Higgins

I 1/14/2005

AUT-PRI

Jeffry T. Dudley

PrincipalNational Aeronautics & Space Administration503 Glenbrook CircleRockledge, FL 32955

U 10/20/2010AUT-PRI

Byron E. Ellis

PrincipalEntergy Corporation5564 Essen Lane, Mail Code L-ESSN-2MBaton Rouge, LA 70809Edison Electric Institute

U 7/23/2008

AUT-PRI

Brandon W. Frakes

PrincipalXL Global Asset Protection Services196 Shady Grove LaneAdvance, NC 27006Alternate: Mark A. Bowman

I 1/15/2004AUT-PRI

David B. Fuller

PrincipalFM Global1151 Boston Providence TurnpikePO Box 9102Norwood, MA 02062-9102

I 7/26/2007

AUT-PRI

Robert M. Gagnon

PrincipalGagnon Engineering2660 Daisy RoadWoodbine, MD 21797

SE 4/1/1994AUT-PRI

Tanya M. Glumac

PrincipalLiberty Mutual Property20 Riverside RoadWeston, MA 02493-2231Alternate: Luke Hilton

I 1/10/2008

AUT-PRI

LaMar Hayward

Principal3-D Fire Protection, Inc.PO Box 50845Idaho Falls, ID 83405

IM 8/2/2010AUT-PRI

Alan R. Laguna

PrincipalMerit Sprinkler Company, Inc.930 Kenner AvenuePO Box 1447Kenner, LA 70062-1447

IM 10/3/2002

1

Page 6: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

Address List No PhonePrivate Water Supply Piping Systems AUT-PRI

Automatic Sprinkler Systems

Matthew J. Klaus06/19/2013

AUT-PRI

John Lake

PrincipalCity of Gainesville306 NE 6th Avenue, Building BPO Box 490, Station 9Gainesville, FL 32602-0490

E 1/31/2001AUT-PRI

George E. Laverick

PrincipalUL LLC333 Pfingsten RoadNorthbrook, IL 60062-2096Alternate: Michael G. McCormick

RT 4/15/2004

AUT-PRI

James M. Maddry

PrincipalJames M. Maddry, P.E.3680 Foxfire PlaceMartinez, GA 30907

SE 1/1/1991AUT-PRI

Kevin D. Maughan

PrincipalTyco Fire Protection Products1467 Elmwood AvenueCranston, RI 02910Alternate: Cliff Hartford

M 1/14/2005

AUT-PRI

Bob D. Morgan

PrincipalFort Worth Fire Department1000 Throckmorton StreetFort Worth, TX 76102

E 8/2/2010AUT-PRI

David S. Mowrer

PrincipalBabcock & Wilcox Technical Services, LLCY-12 National Security ComplexPO Box 2009, MS-8107Oak Ridge, TN 37831-8107Alternate: Austin L. Smith

U 1/1/1982

AUT-PRI

Dale H. O'Dell

PrincipalNational Automatic Sprinkler Fitters LU 66914698 Stallion TrailsVictorville, CA 92392United Assn. of Journeymen & Apprentices of thePlumbing & Pipe Fitting IndustryAlternate: Charles W. Ketner

L 8/2/2010AUT-PRI

Adam P. Olomon

PrincipalAon/RRS/Schirmer Engineering6455 South Shore Blvd., Suite 400League City, TX 77573

I 8/2/2010

AUT-PRI

Shawn C. Olson

PrincipalClackamas County Fire District #12930 SE Oak Grove BoulevardMilwaukie, OR 97267

E 10/18/2011AUT-PRI

Sam P. Salwan

PrincipalEnvironmental Systems Design, Inc.175 West Jackson Blvd., Suite 1400Chicago, IL 60604Alternate: Martin Ramos

SE 1/1/1989

AUT-PRI

Daniel Sanchez

PrincipalCity of Los AngelesBuilding & Safety201 North Figueroa Street, Suite 400Los Angeles, CA 90012

E 10/29/2012AUT-PRI

James R. Schifiliti

PrincipalFire Safety Consultants, Inc.2420 Alft Lane, Suite 100Elgin, IL 60124Illinois Fire Prevention Association

IM 1/18/2001

AUT-PRI

Peter T. Schwab

PrincipalWayne Automatic Fire Sprinklers, Inc.222 Capitol CourtOcoee, FL 34761-3033

IM 7/29/2005

2

Page 7: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

Address List No PhonePrivate Water Supply Piping Systems AUT-PRI

Automatic Sprinkler Systems

Matthew J. Klaus06/19/2013

AUT-PRI

J. William Sheppard

PrincipalSheppard & Associates, LLC24756 Tudor LaneFranklin, MI 48025Alternate: Larry Keeping

SE 1/1/1984AUT-PRI

Scott M. Twele

PrincipalThe RJA Group, Inc.Rolf Jensen & Associates, Inc.591 Camino de la Reina, Suite 1025San Diego, CA 92108Alternate: James A. Zimmerman

SE 10/20/2010

AUT-PRI

Jon R. Ackley

Voting AlternateDalmatian Fire, Inc.5670 West 73rd StreetIndianapolis, IN 46278National Fire Sprinkler AssociationDesign

M 10/29/2012AUT-PRI

Michael Larsen

Voting AlternateAmway Inc.7575 FultonAda, MI 49355

U 03/07/2013

AUT-PRI

Mark A. Bowman

AlternateXL Global Asset Protection Services13467 Chevington DrivePickerington, OH 43147Principal: Brandon W. Frakes

I 1/15/2004AUT-PRI

William J. Gotto

AlternateGlobal Risk Consultants Corporation100 Walnut Avenue, 5th FloorClark, NJ 07066Principal: James B. Biggins

SE 8/5/2009

AUT-PRI

Cliff Hartford

AlternateTyco Fire Protection2034 Falkey RoadPhelps, NY 14532Principal: Kevin D. Maughan

M 10/4/2007AUT-PRI

Andrew C. Higgins

AlternateAllianz Risk Consultants, LLC38 Kilbride DrivePinehurst, NC 28374Principal: Stephen A. Clark, Jr.

I 3/21/2006

AUT-PRI

Luke Hilton

AlternateLiberty Mutual Property13830 Ballantyne Corporate Place, Suite 525Charlotte, NC 20277-2711Principal: Tanya M. Glumac

I 10/1/1996AUT-PRI

Larry Keeping

AlternateProfessional Loss Control3413 Wolfedale Road, Suite 6Mississauga, ON L5C 1V8 CanadaPrincipal: J. William Sheppard

SE 03/07/2013

AUT-PRI

Charles W. Ketner

AlternateNational Automatic Sprinkler Fitters LU 669Joint Apprenticeship & Training Committee7050 Oakland Mills RoadColumbia, MD 20732United Assn. of Journeymen & Apprentices of thePlumbing & Pipe Fitting IndustryPrincipal: Dale H. O'Dell

L 8/2/2010AUT-PRI

Michael G. McCormick

AlternateUL LLC333 Pfingsten RoadNorthbrook, IL 60062-2096Principal: George E. Laverick

RT 10/20/2010

3

Page 8: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

Address List No PhonePrivate Water Supply Piping Systems AUT-PRI

Automatic Sprinkler Systems

Matthew J. Klaus06/19/2013

AUT-PRI

Martin Ramos

AlternateEnvironmental Systems Design, Inc.175 West Jackson Blvd., Suite 1400Chicago, IL 60604Principal: Sam P. Salwan

SE 3/15/2007AUT-PRI

Jeffrey J. Rovegno

AlternateMr. Sprinkler Fire Protection100 Derek PlaceRoseville, CA 95678American Fire Sprinkler AssociationPrincipal: Phillip A. Brown

IM 8/5/2009

AUT-PRI

Austin L. Smith

AlternateBabcock & Wilcox Y-12, LLCPO Box 2009, MS 8107Oak Ridge, TN 37831-8107Principal: David S. Mowrer

U 3/1/2011AUT-PRI

Ronald N. Webb

AlternateS.A. Comunale Company, Inc.2900 Newpark DriveBarberton, OH 44203National Fire Sprinkler AssociationInstaller/MaintainerPrincipal: James A. Charrette

IM 8/2/2010

AUT-PRI

James A. Zimmerman

AlternateThe RJA Group, Inc.600 West Fulton Street, Suite 500Chicago, IL 60661-1242Principal: Scott M. Twele

SE 03/05/2012AUT-PRI

Frans Alferink

Nonvoting MemberWavin Overseas7700 Ad DedemsvaartRollepaal 19Dedemsvaart, OV 7701 BR Netherlands

U 10/29/2012

AUT-PRI

Matthew J. Klaus

Staff LiaisonNational Fire Protection Association1 Batterymarch ParkQuincy, MA 02169-7471

12/16/2010

4

Page 9: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

PART 3 –

NEW PROCESS WORKSHEETS

Page 10: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

March 13, 2012

TERMS New Terms Old Terms

Input Stage – Stage where Public Input is sought to develop the First Draft.

Report on Proposals (ROP) Stage

Public Input (PI) – A recommended change submitted for consideration by the Technical Committee. Each Public Input (PI) shall include new, modified or deleted text as appropriate and technical substantiation to support the recommended change.

Download a Public Input Form for documents in Fall 2013 and subsequent cycles

Proposal

First Draft Meeting ROP Meeting

First Revision (FR) – Proposed changes to the text of an NFPA Standard developed by the responsible Committee(s) in the Input Stage. Each First Revision shall contain the new, modified or deleted text as appropriate. A First Revision shall be established through a Meeting Vote and shall only require a simple majority to proceed to ballot. Only First Revisions that pass ballot will show in the First Draft. Each First Revision shall contain a Committee Statement that substantiates the proposed change to the document.

Committee Proposal or Accepted Public Proposal

Committee Input (CI) – A CI can be established during the First Draft Technical Committee meeting (without balloting) in order to highlight the concept to obtain public comment; often used for newer ideas, topics that aren’t fully fleshed out or controversial topics. A Committee Input (CI) can also be a First Revision (FR) that fails to receive support of the technical committee through letter ballot. Committee Inputs shall maintain the original FR Committee Statement and shall contain a notification to the reviewer documenting that the CI represents a failed FR.

“Trial Balloon” or an Accepted Proposal (or Committee Proposal) that Failed Ballot

Committee Statement (CS) – A Committee Statement is the committee’s response to a Public Input (PI), Public Comment (PC) or the committee’s technical substantiation for a proposed First Revision. A committee statement shall be established through a Meeting Vote and shall only require a simple majority to proceed.

Committee Statement

First Draft Report – The First Draft Report documents the Input Stage; it shall contain the First Draft, Public Input, Committee Input, Committee and Correlating Committee Statements, Correlating Input, Correlating Notes and Ballot Statements.

ROP

First Draft – The draft of the proposed new or revised standard showing in legislative text all First Revisions and First Correlating Revisions that have passed ballot.

ROP Draft

Correlating Committee (CC) Technical Correlating Committee

Correlating Committee Statement – The Correlating Committee’s response to a Public Input (PI), Committee Input (CI), Public Comment (PC) or the Correlating Committee’s technical substantiation for a correlating change to proposed Revision or a correlative CCFR. It shall be established through a Meeting Vote and shall only require a simple majority to proceed.

TCC Note

Correlating Committee First Revision (CCFR) – Correlating Committee First Revisions are proposed revisions to the Technical Committee’s First Revisions that are required to correlate the proposed document. Each CCFR shall contain a Correlating Committee Statement that substantiates the Revision. A CCFR shall be established through a Meeting Vote and shall only require a simple majority to proceed to letter ballot. CCFRs that fail to receive CC support through letter ballot shall not be published as part of the First Draft.

TCC Note

Technical Committee First Draft meeting - Spring 2012 Page 2 of 34 V.2 3/13/2012

Page 11: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

Comment Stage Report on Comments (ROC) Stage

Public Comment – Changes submitted by the public during public Comment Stage.

Public Comment

Second Draft Meeting ROC Meeting

Second Revision (SR) – Similar to First Revision, but in the Comment Stage. Proposed changes to the text by the TC that have passed ballot.

Committee Comment or Accepted Public Comment

Committee Comment – A Committee Comment shall be a Second Revision (SR) that fails to receive support of the TC through ballot. Committee Comments shall maintain the original Committee Statement and shall contain a notification to the reviewer documenting that the Committee Comment represents a failed SR.

Committee Comment that failed ballot

Committee Action – An action by a TC to accept or reject a Comment. This occurs only in the Comment Stage and the action itself is not balloted.

Committee Action

Second Draft Report – The Second Draft Report documents the Comment Stage; it shall contain the Second Draft, Public Comments with corresponding Committee Actions and Committee Statements, Committee Comments, Correlating Revisions and Ballot Statements.

ROC

Second Draft – The draft of the proposed new or revised standard showing in legislative text all Second Revisions and Second Correlating Revisions that have passed ballot.

ROC Draft

 

Technical Committee First Draft meeting - Spring 2012 Page 3 of 34 V.2 3/13/2012

Page 12: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

NEW PROCESS ACTIONS AND MOTIONS  

New Process Actions and Motions‐ Final‐ 2/13/2012   

Possible Action 1:  Resolve PIs, (no change to Section) 

  Action Required Sample MotionsStep One:  Committee generates a statement  to respond  to (resolve) 

each PI #    

I make a motion (move) to resolve PI#___ with the following committee statement:    Approval by a meeting vote (simple majority) and not subject to ballot  (Regs 4.3.7.3 & 4.3.7.3.2) 

Possible Action 2:  Create First Revision ‐ Change to a Section  

  Action Required Sample MotionsStep One: (1st option) 

 Committee generates a First Revision   I make a motion (move) to revise Section ___      as follows:…………   Approval by a meeting vote (simply majority) and final approval through ballot (Regs 4.3.9.2.3) 

Step Two: (1st option) 

Committee generates a statement substantiating the change.    

  Approval by a meeting vote (simply majority) (Regs 4.3.7.3) 

     

Step One: (2nd option) 

Committee generates a First Revision using one or more PIs as the starting point. 

I make a motion to revise Section __ using PI#__ as the basis for change.  Approval by a meeting vote (simply majority) and final approval through ballot (Regs 4.3.9.2.3)

Step Two:  (2nd option)  

If the revision is associated with one or more PIs the committee generates a statement  to respond  to (resolve) each PI   

I make a motion (move) to resolve PIs # through ## with the following statement:      Approval by a meeting vote (simply majority) and not subject to ballot  (Regs 4.3.7.3 & 

4.3.7.3.1) 

Possible Action 3:  Create Committee Input – (Trial Balloon/Placeholder)

  Action Required  Sample Motions Step One:  

Committee generates a Committee Input (proposed revision) for public consideration and solicitation of Public Comments   

I make a motion (move) to create a CI with a proposed revision to  X.X.X as follows:   Approval by a meeting vote (simply majority) and not subject to ballot  (Regs 4.3.8) 

Step Two:  Committee generates a statement   to explain the intent and why it is seeking public consideration and soliciting Public Comments   

  Approval by a meeting vote (simply majority) (Regs 4.3.7.1) 

 

Technical Committee First Draft meeting - Spring 2012 Page 8 of 34 V.2 3/13/2012

Page 13: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

PART 4 –

A2012 ROC MEETING MINUTES

Page 14: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

NFPA Technical Committee on Private Water Supply Piping

ROC Meeting

Newport Beach Marriott

Newport Beach, California September 29, 2011

MEETING MINUTES

1. Call to Order. TC Chair Ken Wagoner called the meeting to order at 8:00.

2. Self-Introductions of members and guests. Members of the committee introduced themselves and reviewed the contact information. The meeting attendance list is attached to these minutes.

3. Review of Distributed Meeting Materials. Staff Liaison Matt Klaus provided

an overview of the agenda materials that were sent to the committee and posted on the committee web page.

4. Approval of A12-ROP Draft Meeting Minutes. The minutes of the A12-ROP Meeting were reviewed and approved without modification.

5. Review of Meeting Procedures and Revision Process. Matt Klaus gave a presentation on the overall meeting guidelines and the NFPA Regulations Governing TC operations.

6. Work Load . TC Chair Ken Wagoner discussed the logistics for the meeting and

the process to complete the ROC meeting.

7. Public and Committee Comments. The committee then processed the comments. See the ROC for the official actions on the proposals.

8. New Business:

a. The TC plans to form an inter-committee task group with the SSD TC to address “held” comments on water supply data and hydrant flow testing. Staff to send a request to the FPRF for a code fund project (completed).

b. The TC developed a new task group to work on an off-cycle rewrite of

NFPA 24. The task group roster is as follows:

Page 15: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

Karl Weigand Pete Schwab Jim Biggins Jim Charrette George Laverick Phil Brown David Fuller

9. Adjournment. Meeting adjourned at 2:30 pm.

Page 16: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith
Page 17: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith
Page 18: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith
Page 19: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

PART 5 –

A2015 KEY DATES

Page 20: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

2015 ANNUAL REVISION CYCLE *Public Input Dates may vary according to standards and schedules for Revision Cycles may change.  Please check the NFPA Website for the most up‐to‐date information on Public Input Closing Dates and schedules at 

www.nfpa.org/document # (i.e. www.nfpa.org/101) and click on the Next Edition tab.

 Process Stage 

 Process Step 

 Dates for 

TC 

Dates forTC with CC 

  Public Input Closing Date*  7/8/2013  7/8/2013 

  Final Date for TC First Draft Meeting  12/13/2013  9/13/2013 

Public Input  Posting of First Draft and TC Ballot  1/31/2014  10/25/2013 

Stage  Final date for Receipt of TC First Draft ballot  7/21/2014  11/15/2013 

(First Draft)  Final date for Receipt of TC First Draft ballot ‐ recirc  2/28/2014  11/22/2013 

  Posting of First Draft for CC Meeting    11/29/2013 

  Final date for CC First Draft Meeting    1/10/2014 

  Posting of First Draft and CC Ballot    1/31/2014 

  Final date for Receipt of CC First Draft ballot    2/21/2014 

  Final date for Receipt of CC First Draft ballot ‐ recirc    2/28/2014 

  Post First Draft Report for Public Comment  3/7/2014  3/7/2014 

   

  Public Comment Closing Date for Paper Submittal*  4/11/2014  4/11/2014 

  Public Comment Closing Date for Online Submittal (e‐PC)*   5/16/2014  5/16/2014 

  Final Date to Publish Notice of Consent Documents (Standards that received no Comments) 

5/30/2014  5/30/2014 

  Appeal Closing Date for Consent Standards (Standards that received no Comments) 

6/13/2014  6/13/2014 

  Final date for TC Second Draft Meeting  10/31/2014  7/25/2014 

Comment  Posting of Second Draft and TC Ballot  12/12/2014  9/5/2014 

Stage    Final date for Receipt of TC Second Draft ballot  1/2/2015  9/26/2014 

(Second  Final date for receipt of TC Second Draft ballot ‐ recirc  1/9/2015  10/3/2014 

Draft)  Posting of Second Draft for CC Meeting    10/10/2014 

  Final date for CC Second Draft Meeting    11/21/2014 

  Posting of Second Draft for CC Ballot    12/12/2014 

  Final date for Receipt of CC Second Draft ballot    1/2/2015 

  Final date for Receipt of CC Second Draft ballot ‐ recirc    1/9/2015 

  Post Second Draft Report for NITMAM Review  1/16/2015  1/16/2015 

 

Tech Session  Notice of Intent to Make a Motion (NITMAM) Closing Date  3/6/2015  3/6/2015 

Preparation  Posting of Certified Amending Motions (CAMs) and Consent Standards 

5/1/2015  5/1/2015 

(& Issuance)  Appeal Closing Date for Consent Standards  5/16/2015  5/16/2015 

  SC Issuance Date for Consent Standards  5/26/2015  5/26/2015 

 

Tech Session  Association Meeting for Standards with CAMs  6/22‐25/2016  6/22‐25/2016 

 

Appeals and  Appeal Closing Date for Standards with CAMs  7/15/2015  7/15/2015 

Issuance  SC Issuance Date for Standards with CAMs  8/20/2015  8/20/2015 

 

Approved___  October 18, 2011       _                                              Revised__March 7, 2013_____________ 

Page 21: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

PART 6 –

PUBLIC INPUT

Page 22: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/21/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 225/477

Public Input No. 492-NFPA 13-2013 [ Section No. 9.3.7.1 [Excluding any Sub-Sections] ]

Original Hide Markup

Where seismic protection is provided, C-type clamps (including beam and large flange clamps) used to attach hangers to the building structureshall be equipped with a restraining strap unless the provisions of 9.3.7.1.1 are satisfied. C-type clamps with or without restraining straps shallnot be used to attach hangers of any pipe for which lateral bracing has been omitted per the provisions of 9.3.5.5.10 or any pipe attached to thatpipe.

Statement of Problem and Substantiation for Public Input

Where lateral bracing is omitted, piping will be subject to large and repeated lateral deflections that could damage or displace c-clamp hangers on the pipe for which the bracing is omitted or on the attached pipe (e.g., branch lines attached to a cross main).

Related Public Inputs for This Document

Related Input Relationship

Open Public Input No. 489-NFPA 13-2013 [Section No. 9.3.5.5.10]

Submitter Information Verification

Submitter Full Name:Christopher Deneff

Organization: FM Global

Submittal Date: Fri May 31 10:34:15 EDT 2013

Copyright Assignment

I, Christopher Deneff, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both the Proposed

Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in w hich this

Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this copyright

assignment.

By checking this box I aff irm that I am Christopher Deneff, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained therein. I

understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and effect as a handw ritten

signature

Public Input No. 444-NFPA 13-2013 [ Section No. 10.7.2 ]

Original Hide Markup

10.7.2

The torquing of bolted joints shall be checked be checked against manufacturer's requirments . [ 24: 10.7.2]

Statement of Problem and Substantiation for Public Input

By requiring checking torque against manufacturer's requirements will ensure that proper torquing is achieved.

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 15:56:25 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both the Proposed Change

and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in w hich this Public Input in

this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained therein. I understand

and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and effect as a handw ritten signature

/TerraView/Content/13-2013.ditamap/2/C1370010855649.xml

/TerraView/Content/13-2013.ditamap/2/C1369857385406.xml

Page 23: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/21/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 226/477

Public Input No. 446-NFPA 13-2013 [ New Section after 10.7.4 ]

TITLE OF NEW CONTENT

Type your content here ...

10.7.4.1 Plugs shall be recorded as to their location.

10.7.4.2 Plugs shall be verified to be removed prior to recommencement of work.

Statement of Problem and Substantiation for Public Input

the installation of plugs is important, but so is the tracking of where they are installed and their removal to ensure that the piping is not blocked when placed in service.

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 15:58:53 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both the Proposed Change

and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in w hich this Public Input in

this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained therein. I understand

and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and effect as a handw ritten signature

Public Input No. 448-NFPA 13-2013 [ Section No. 10.8.3.1.4.4 ]

Original Hide Markup

10.8.3.1.4.4

The diameter of holes shall be 1 ⁄ 8 in. (3.2 mm) larger than that of rods or bolts . [ 24: 10.8.3.1.4.4]

Statement of Problem and Substantiation for Public Input

provides clarification for use of bolts

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 16:01:56 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both the Proposed Change

and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in w hich this Public Input in

this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained therein. I understand

and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and effect as a handw ritten signature

/TerraView/Content/13-2013.ditamap/2/C1369857533165.xml

/TerraView/Content/13-2013.ditamap/2/C1369857716520.xml

Page 24: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/21/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 227/477

Public Input No. 450-NFPA 13-2013 [ Section No. 10.8.3.3.1 ]

Original Hide Markup

10.8.3.3.1

The strap shall be 3 ⁄ 4 in. (19.1 mm) thick and 2 1 ⁄ 2 in. (63.5 mm) wide , regardless of pipe diameter . [ 24: 10.8.3.3.1]

Statement of Problem and Substantiation for Public Input

provides definition regarding the size of piping vs. the size of the straps

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 16:07:17 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both the Proposed Change

and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in w hich this Public Input in

this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained therein. I understand

and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and effect as a handw ritten signature

Public Input No. 452-NFPA 13-2013 [ New Section after 10.8.3.4 ]

TITLE OF NEW CONTENT

Type your content here ...

10.8.3.4.1 Material selected shall be compatible with the piping material to be installed.

Statement of Problem and Substantiation for Public Input

material compatibility is necessary to avoid potential electrolysis between dissimilar metals

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 16:15:20 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both the Proposed Change

and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in w hich this Public Input in

this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained therein. I understand

and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and effect as a handw ritten signature

/TerraView/Content/13-2013.ditamap/2/C1369858037477.xml

/TerraView/Content/13-2013.ditamap/2/C1369858520115.xml

Page 25: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/21/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 228/477

Public Input No. 453-NFPA 13-2013 [ New Section after 10.10.2.4.1 ]

TITLE OF NEW CONTENT

Type your content here ...

10.10.2.4.1.1 Opening and closing of hydrants shall be completed under both static pressure (no flow) and flow conditions.

Statement of Problem and Substantiation for Public Input

by adding that the hydrant has to be operated under no flow and flow conditions, ensures proper operation of the hydrant

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 16:22:46 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both the Proposed Change

and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in w hich this Public Input in

this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained therein. I understand

and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and effect as a handw ritten signature

Public Input No. 192-NFPA 13-2013 [ Section No. 11.1.2 ]

Original Hide Markup

11.1.2* Adjacent Hazards or Design Methods.

For buildings with two or more adjacent hazards or design methods, the following shall apply:

(1) Where areas are not physically separated by a barrier or partition capable of delaying heat from a fire in one area from fusing sprinklers inthe adjacent area, the required sprinkler protection for the more demanding design basis shall extend 15 ft (4.6 m) beyond its perimeter.

(2) The requirements of 11.1.2 (1) shall not apply where the areas are separated by a barrier partition that is capable of preventing delayingheat from a fire in one area from fusing sprinklers in the adjacent area.

(3) The requirements of 11.1.2 (1) shall not apply to the extension of more demanding criteria from an upper ceiling level to beneath a lowerceiling level where the difference in height between the ceiling levels is at least 2 ft (0.6 m).

Statement of Problem and Substantiation for Public Input

The terminology between sections 11.1.2(1) and 11.1.2(2) needs to be consistent. One currently uses the terminology "delay" while the other uses the term "prevent". Since "prevent" has a more permanent connotation, its use here is inappropriate. All we are trying to do is delay the operation of sprinklers in the remote area until sprinklers over the fire have had a chance to open.

Submitter Information Verification

Submitter Full Name:Roland Asp

Organization: National Fire Sprinkler Association

Affilliation: NFSA E&S Committee

Submittal Date: Thu Apr 18 16:16:42 EDT 2013

Copyright Assignment

I, Roland Asp, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both the Proposed Change

and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in w hich this Public Input in

this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Roland Asp, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained therein. I understand and

intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and effect as a handw ritten signature

/TerraView/Content/13-2013.ditamap/2/C1369858966346.xml

/TerraView/Content/13-2013.ditamap/2/C1366316202831.xml

Page 26: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

PART 6 –

NFPA 24 PUBLIC INPUT

Page 27: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 1/85

Public Input No. 57-NFPA 24-2013 [ Global Input ]

NOTE: This proposal appeared as Comment 24-24 (Log #CC5) which was held fromthe A12 ROC on Proposal 24-1.

Correlate Annex C and D through extract (or copy) from NFPA 291.

Additional Proposed Changes

File Name Description Approved

Open

24_PI_57_Held_Comment_24-24_TC_AUT-PRI_.pdf

Held Comment 24-24

Statement of Problem and Substantiation for Public Input

This will provide consistency between the two documents.

Submitter Information Verification

Submitter Full Name:TC on AUT-PRI

Organization: TC on Private Water Supply Piping Systems

Submittal Date: Thu May 23 11:46:43 EDT 2013

Copyright Assignment

I, TC on AUT-PRI, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am TC on AUT-PRI, and I agree to be legally bound by the above

Copyright Assignment and the terms and conditions contained therein. I understand and intend that, by

checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the

same legal force and effect as a handw ritten signature

Public Input No. 60-NFPA 24-2013 [ Section No. 2.3.3 ]

Original Hide Markup

/TerraView/Content/24-2013.ditamap/2/C1369324003836.xml

Page 28: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 2/85

2.3.3 AWWA Publications.

American Water Works Association, 6666 West Quincy Avenue, Denver, CO80235.

AWWA C104, Cement Mortar Lining for Ductile Iron Pipe and Fittings for Water,2008.

AWWA C105, Polyethylene Encasement for Ductile Iron Pipe Systems, 2005.

AWWA C110, Ductile Iron and Gray Iron Fittings, 2008.

AWWA C111, Rubber-Gasket Joints for Ductile Iron Pressure Pipe and Fittings,2000.

AWWA C115, Flanged Ductile Iron Pipe with Ductile Iron or Gray Iron ThreadedFlanges, 2005.

AWWA C116, Protective Fusion-Bonded Epoxy Coatings for the Interior andExterior Surfaces of Ductile-Iron and Gray-Iron Fittings for Water Supply Service,2003.

AWWA C150, Thickness Design of Ductile Iron Pipe, 2008.

AWWA C151, Ductile Iron Pipe, Centrifugally Cast for Water, 2002.

AWWA C153, Ductile-Iron Compact Fittings for Water Service, 2006.

AWWA C200, Steel Water Pipe 6 in. and Larger, 2005.

AWWA C203, Coal-Tar Protective Coatings and Linings for Steel Water PipelinesEnamel and Tape — Hot Applied, 2002.

AWWA C205, Cement-Mortar Protective Lining and Coating for Steel Water Pipe 4in. and Larger — Shop Applied, 2007.

AWWA C206, Field Welding of Steel Water Pipe, 2003.

AWWA C207, Steel Pipe Flanges for Waterworks Service — Sizes 4 in. Through144 in., 2007.

AWWA C208, Dimensions for Fabricated Steel Water Pipe Fittings, 2007.

AWWA C300, Reinforced Concrete Pressure Pipe, Steel-Cylinder Type, 2004.

AWWA C301, Prestressed Concrete Pressure Pipe, Steel-Cylinder Type, 2007.

AWWA C302, Reinforced Concrete Pressure Pipe, Non-Cylinder Type, 2004.

AWWA C303, Reinforced Concrete Pressure Pipe, Steel-Cylinder Type,Pretensioned, 2002.

AWWA C400, Standard for Asbestos-Cement Distribution Pipe, 4 in. Through 16in. (100 mm through 400 mm), for Water Distribution Systems, 2003.

AWWA C401, Standard for the Selection of Asbestos-Cement Pressure Pipe 4 in.through 16 in. (100 mm through 400 mm), 2003.

AWWA C600, Standard for the Installation of Ductile Iron Water Mains and TheirAppurtenances, 2005.

AWWA C602, Cement-Mortar Lining of Water Pipe Lines 4 in. and Larger — inPlace, 2006.

AWWA C603, Standard for the Installation of Asbestos-Cement Pressure Pipe,2005.

AWWA C900, Polyvinyl Chloride (PVC) Pressure Pipe, 4 in. Through 12 in., forWater Distribution, 2007.

AWWA C905, AWWA Standard for Polyvinyl Chloride (PVC) Pressure Pipe and

Page 29: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 3/85

Fabricated Fittings, 14 in. Through 48 in. (350 mm Through 1,200 mm), 2010.

AWWA C906, Polyethylene (PE) Pressure Pipe and Fittings, 4 in. (100 mm)Through 63 in. (1575 mm) for Water Distribution, 2007.

AWWA C909, Molecularly Oriented Polyvinyl Chloride (PVCO) Pressure Pipe, 4IN through24 IN. (100 MM through 600 MM ), for Water Wastewater, andReclaimed Water Service,03/01/2010

AWWA M11, A Guide for Steel Pipe Design and Installation, 4th edition, 2004.

Statement of Problem and Substantiation for Public Input

PVC-O solves the problem of the low impact of PVC-U at low temperatures and the problem that PVC-u is more sensitive to water hammer. PVC-O is not.This type of pipe is in use all over the world, produced by a number of different companies and with a good track record. The pipe is in use since approx. 1990.Several of our customers have asked to use this pipe also for fire fighting lines, but it failes to be registered in NFPA24

Submitter Information Verification

Submitter Full Name:Frans Alferink

Organization: Wavin Overseas

Affilliation: S2renginieros, Bogota, Colombia. Antonio Yesid Lopez

Submittal Date: Thu May 23 14:32:52 EDT 2013

Copyright Assignment

I, Frans Alferink, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Frans Alferink, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1369333972795.xml

Page 30: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 4/85

Public Input No. 1-NFPA 24-2012 [ Section No. 3.3.15.2 ]

Original Hide Markup

3.3.15.2 Indicating Valve.

A valve that has components that show if the valve is open or closed. Examplesare outside screw and yoke (OS&Y) gate valves and underground gate valves withindicator posts.

Statement of Problem and Substantiation for Public Input

Examples belong in the annex. Another PI places the language in the annex.

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Wed Dec 12 16:40:06 EST 2012

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

Public Input No. 65-NFPA 24-2013 [ Section No. 4.1.3 ]

Original Hide Markup

/TerraView/Content/24-2013.ditamap/2/C1355348406942.xml

Page 31: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 5/85

4.1.3

Working plans shall be drawn to an indicated scale on sheets of uniform size, witha plan of each floor as applicable, and shall include the following items that pertainto the design of the system:

(1) Name of owner

(2) Location, including street address

(3) Point of compass

(4) A graphic representation of the scale used on all plans

(5) Name and address of contractor

(6) Size and location of all water supplies

(7) Size and location of standpipe risers, hose outlets, hand hose, monitornozzles, and related equipment

(8) The following items that pertain to private fire service mains:

(a) Size

(b) Length

(c) Location

(d) Weight

(e) Material

(f) Point of connection to city main

(g) Sizes, types, and locations of valves, valve indicators, regulators,meters, and valve pits

(h) Depth at which the top of the pipe is laid below grade

(i) Method of restraint

(9) The following items that pertain to hydrants:

(a) Size and location, including size and number of outlets and whetheroutlets are to be equipped with independent gate valves

(b) Thread size and coupling adapter specifications if different fromNational Standard Hose Threads as defined by NFPA 1963

(c) Whether hose houses and equipment are to be provided, and bywhom

(d) Static and residual hydrants used in flow

(e) Method of restraint

(10) Size, location, and piping arrangement of fire department connections

Statement of Problem and Substantiation for Public Input

Specifying National Standard identifies the specific type of thread that should be the standard for hydrants. Hdyrants that utilize hose threads other than National Standard should be idenfied on the drawings

Submitter Information Verification

Submitter Full Name:John Campbell

Page 32: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 6/85

Organization: Telgian Corporation

Submittal Date: Wed May 29 16:31:48 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

Public Input No. 56-NFPA 24-2013 [ New Section after 5.1.2 ]

NOTE: This proposal appeared as Comment 24-1 (Log #3) which was held from theA12 ROC on Proposal 24-4.

Do not take the action in Proposal 24-4. Instead, revise section 5.1.3 and insert an annexnote as follows: 5.1.3* Where the volume and pressure available from a water supply are determinedthrough a waterflow test, an adjustment shall be made to the test data to account for dailyand seasonal fluctuations. A.5.1.3 Flow tests that are run during the middle of a business day often do not accountfor peak water demands at other times of the day or water use during other times of year. Under ideal circumstances, NFPA 24 would have a specific value to apply to all situations,but that is not practical given the wide variations of water supplies in use and thevariations of when waterflow tests are conducted. Waterflow tests conducted close topeak water usage times would need less of an adjustment than waterflow tests conductedduring low water usage times. Consultation with the water authority may be necessary todetermine an appropriate adjustment factor. Use of 24 hour gages at a hydrant can behelpful in determining day to day fluctuations. In addition, the user should also considerother water usage factors such as simultaneous industrial use, the potential for futuredemand on the system in the area of the test (depending on how well developed the areaalready is) and other conditions that would affect the water supply.

Additional Proposed Changes

File Name Description Approved

Open 24_PI_56_Held_Comment_24-1_Kelly_.pdf Held Comment 24-1

Statement of Problem and Substantiation for Public Input

While some of the material currently in section 5.1.3 is more appropriate in the annex, the basic concept of requiring some adjustment to the data is still needed in the body of the standard. It is completely irresponsible to conduct a waterflow test at a hydrant at a time of very low water

/TerraView/Content/24-2013.ditamap/2/C1369859508645.xml

Page 33: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 7/85

demand and believe that you are going to have all of that flow and pressure available when a fire occurs a few hours later during a regular and known peak demand time. As proposed, the rule would only apply in those situations where the waterflow test is being performed and would not apply to the development of water supply data from other sources. The concept of evaluating the water supply for possible interruptions from flood or ice conditions has been intentionally dropped from the language because this does not have to do with the flow or pressure available. This concept should be a part of the determination as to whether the water supply is “reliable” enough to use at all, which is a completely different concept and should not be tied to evaluating data from a flow test.

Submitter Information Verification

Submitter Full Name:KEVIN KELLY

Organization: [ Not Specified ]

Submittal Date: Thu May 23 11:37:20 EDT 2013

Copyright Assignment

I, KEVIN KELLY, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am KEVIN KELLY, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1369323440256.xml

Page 34: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 8/85

Public Input No. 43-NFPA 24-2013 [ Section No. 5.2.1 ]

Original Hide Markup

5.2.1 Private Fire Service Mains.

Pipe smaller than 6 in. (152 mm) in diameter shall not be installed as a privateservice main supplying hydrants. A minimum 8 in. (203.2mm) diameter pipeshall be utilized for systems supplying multiple fire hydrants unless it canbe demonstrated that a smaller main will provide the proposed and futuredevelopment with adequate pressure and fire-flow.

Statement of Problem and Substantiation for Public Input

Makes this standard compatible with AWWA and other regional standards. Fire hydrants should only be connected to water mains adequately sized to carry necessary fire flows. Private fire service mains that serve residential, industrial, or commercial developments may require larger mains to assure adequate pressure and fire-flow for current and future development needs.

Submitter Information Verification

Submitter Full Name:Doug Hohbein

Organization: Northcentral Fire Code Develop

Submittal Date: Tue Apr 02 22:42:17 EDT 2013

Copyright Assignment

I, Doug Hohbein, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Doug Hohbein, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1364956937148.xml

Page 35: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 9/85

Public Input No. 66-NFPA 24-2013 [ Section No. 5.3.2 ]

Original Hide Markup

5.3.2

Where meters are required by other authorities, they shall be listed for fireservice .

Statement of Problem and Substantiation for Public Input

provides consistency with other NFPA standards on equipment being listed for fire service

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 16:33:56 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

Public Input No. 67-NFPA 24-2013 [ New Section after 5.8 ]

TITLE OF NEW CONTENT

Type your content here ...

5.8.1* Suction Screening shall be removable or an in situ cleaning shall be provided. [20:4.14.8.3]

5.8.2 Screens shall be so arranged that they can be cleaned or repaired withoutdisturbing the intake pipe. [20: 4.14.8.5]

5.8.3 Mesh screens shall be brass, copper, Monel, stainless steel, or other equivalentcorrosion-resistant metallic material wire screen of 0.50 in. (12.7 mm) maximum mesh

/TerraView/Content/24-2013.ditamap/2/C1369859636293.xml

Page 36: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 10/85

and No. 10 B&S gauge. [20: 4.14.8.6]

5.8.4 Where flat panel mesh screens are used, the wire shall be secured to a metal framesliding vertically at the entrance to the intake. [20: 4.14.8.7]

5.8.5 Where the screens are located in a sump or depression, they shall be equipped witha debris-lifting rake. [20: 4.14.8.8]

5.8.6 Periodically, the screens shall be removed for inspection, and accumulated debrisshall be removed.

5.8.7 Coninuous slot screens shall be brass, copper, Monel, stainless steel, or otherequivalent corrosion-resistant metallic material of 0.125 in. (3.2 mm) maximum slot andprofile wire construction. [20: 4.14.8.10]

5.8.8 Screens shall have at least 62.5 percent open area. [20: 4.14.8.11]

5.8.9 Where zebra mussel infestation is present or reasonably anticipated, the screensshall be constructed of a material with demonstrated resistance to zebra musselattachment or coated with a material with demonstrated resistance to zebra musselattachment. [20: 4.14.8.12]

5.8.10 The overall area of the screen shall be at least 1.6 times the net screen openingarea. [20: 4.14.8.13]

Statement of Problem and Substantiation for Public Input

adding details on the screens provides for the screen construction and consistency with other standards that utilize screens on intakes from open bodies of water (NFPA20) . wording is similar to that found in NFPA 20.

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 16:38:24 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1369859904934.xml

Page 37: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 11/85

Public Input No. 47-NFPA 24-2013 [ Section No. 5.9.1 [Excluding any

Sub-Sections] ]

Original Hide Markup

Where a fire department connection is required by other standards and when theauthority having jurisdiction requires it to be at a remote fire department connection,for systems requiring one by another standard, a location remote from the building,the fire department connection shall be provided as described in Section 5.9.

Additional Proposed Changes

File Name Description Approved

Open LK_NFPA_24-2013_Proposal_1_of_5.docx Cover Sheet

Statement of Problem and Substantiation for Public Input

This proposed revision is strictly editorial, as the current text is a bit awkward.

Submitter Information Verification

Submitter Full Name:Larry Keeping

Organization: Professional Loss Control

Submittal Date: Mon May 13 13:37:40 EDT 2013

Copyright Assignment

I, Larry Keeping, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Larry Keeping, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1368466660289.xml

Page 38: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 12/85

Public Input No. 48-NFPA 24-2013 [ Section No. 5.9.1.4 ]

Original Hide Markup

5.9.1.4

Fire department connections shall be equipped with listed plugs or caps that aresecured and arranged for easy removal by fire departments.

Additional Proposed Changes

File Name Description Approved

Open LK_NFPA_24-2013_Proposal_2_of_5.docx Cover Sheet

Statement of Problem and Substantiation for Public Input

There is no need to utilize listed plugs or caps for a fire department connection. Often, the nice new brass ones that come with a listed FDC go missing and have to be replaced. To avoid repetitions of such losses, one option that building owners may choose is to replace them with vandal resistant “break away” or “knock off” caps, which are economical, unattractive to brass scavengers and they generally make poor ash trays. These devices are not usually listed and they do not need to be, because components such as FDC caps and plugs do not affect system performance.

Submitter Information Verification

Submitter Full Name:Larry Keeping

Organization: Professional Loss Control

Submittal Date: Mon May 13 13:39:34 EDT 2013

Copyright Assignment

I, Larry Keeping, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Larry Keeping, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1368466774145.xml

Page 39: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 13/85

Public Input No. 44-NFPA 24-2013 [ New Section after 5.9.1.5 ]

5.9.1.6 The AHJ shall have the authority to require locking fire departmentconnection ( FDC ) plugs or caps on all water-based fire protection systems. (1:13)

Statement of Problem and Substantiation for Public Input

Makes this standard compatible with NFPA 1 Chapter 13 and gives AHJ's the ability to require locking caps for FDC’s on private water systems where jurisdictions do not utilize NFPA 1.

Submitter Information Verification

Submitter Full Name:Doug Hohbein

Organization: Northcentral Fire Code Develop

Submittal Date: Tue Apr 02 22:43:26 EDT 2013

Copyright Assignment

I, Doug Hohbein, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Doug Hohbein, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1364957006703.xml

Page 40: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 14/85

Public Input No. 68-NFPA 24-2013 [ Section No. 5.9.2.1 ]

Original Hide Markup

5.9.2.1

The fire department connection(s) shall use an NH internal threaded swivel fitting(s)with an NH standard thread(s) , except as modified by 5 . 9.2.3.

Statement of Problem and Substantiation for Public Input

As currently written, the section contradicts the previous (unmodified) section 4.1.3(9)(b). By allowing for an exception for the use of non-standard threads, clarification is provided.

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 16:57:00 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1369861020850.xml

Page 41: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 15/85

Public Input No. 17-NFPA 24-2012 [ New Section after 5.9.3.2 ]

5.9.3.2.1

Control valves shall be permitted to be installed downstream of the point where the firedepartment connection piping connects to the system piping.

A.5.9.3.2.1

Figure A.5.9.3.2.1(a) and Figure A.5.9.3.2.1(b) depict fire department connections to theunderground pipe.

Add Annex Figures A.5.9.3.2.1 (a) and A.5.9.3.2.1 (b) as taken from NFPA 13A.8.17.2.4.4 (a) and A.17.2.4.4 (b)

Additional Proposed Changes

File Name Description Approved

Open FDC_s.JPG FDC's connected to underground as taken from NFPA 13

Statement of Problem and Substantiation for Public Input

Clarifies that valves can be downstream of FDC's and correlates with NFPA 13.

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Thu Dec 13 13:16:34 EST 2012

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1355422594010.xml

Page 42: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith
Page 43: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 16/85

Public Input No. 89-NFPA 24-2013 [ Section No. 5.9.3.2 ]

Original Hide Markup

5.9.3.2

No shutoff valve shall be permitted in the piping from the fire departmentconnection piping to the point that the fire department connection pipingconnects to the system piping fire service main .

Additional Proposed Changes

File Name Description Approved

Open 24_Brown.pdf Cover Sheet

Statement of Problem and Substantiation for Public Input

The use of the term "system piping" has caused confusion on just where a fire department connection (fdc) can be installed. They read this as meaning that you cannot have any shutoff valve between the fdc and the system sprinkler system. Thus the arrangement shown in Figure A.3.3.11 would not be allowed sense there is two shutoff valves shown between the fdc and the sprinklered building.The term "fire service main" is used in Figure A.5.9(b).

Submitter Information Verification

Submitter Full Name:Phillip Brown

Organization: American Fire Sprinkler Association

Submittal Date: Mon Jun 03 11:27:30 EDT 2013

Copyright Assignment

I, Phillip Brow n, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Phillip Brow n, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1370273250628.xml

Page 44: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 17/85

Public Input No. 18-NFPA 24-2012 [ New Section after 5.9.4.2 ]

5.9.4.2.1

The automatic drip shall be permitted to be buried where permitted by the authority havingjurisdiction.

5.9.4.2.2

Where the automatic drip is buried as allowed by 5.9.4.2.1, the outlet shall discharge intoa bed of crushed stone or pea gravel.

Statement of Problem and Substantiation for Public Input

The 2013 edition was modified to require access to the ball drip. Many AHJ's require that fire department connections (FDC) are remote. NFPA suggests that the check valve for the FDC be located as close to the connection to the system as possible. This could leave long sections of underground piping with no pressure. This piping could get cut and one will not know about it until an NFPA 25 inspection is performed or the fire department pumps into the connection. Many AHJ's want water brought as close to the FDC as possible to avoid this situation. By requiring access to the ball drip, this could require a vault or deep meter box costing hundreds of dollars. This new section gives the AHJ an allowance to require the automatic drip close to the FDC and still have water on the underground piping for supervision.

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Thu Dec 13 13:46:36 EST 2012

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1355424396453.xml

Page 45: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 18/85

Public Input No. 19-NFPA 24-2012 [ Section No. 5.9.4.3 ]

Original Hide Markup

5.9.4.3

An automatic drip shall not be required in areas where the piping is not subject tofreezing.

Statement of Problem and Substantiation for Public Input

There are many areas in the country where the temperature of the air will dip below 32 degrees Fahrenheit but will never last long enough to freeze a 4" or 6" pipe. Technically this means that freezing has been achieved because water freezes at 32° FH. This change gives allowance for these climate areas.

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Thu Dec 13 13:55:14 EST 2012

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1355424914791.xml

Page 46: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 19/85

Public Input No. 45-NFPA 24-2013 [ Section No. 5.9.4.3 ]

Original Hide Markup

5.9.4.3

An automatic drip shall not be required in on fire department connections forsystems located in areas not subject to freezing.

Statement of Problem and Substantiation for Public Input

As presently written, this requirement may be confused as to mean that the location of the automatic drip cannot be in an area where it would freeze. In actuality, the automatic drip is not required on any part of a system that is located in a geographical area that is not subject to freezing climates.

Submitter Information Verification

Submitter Full Name:John Chartier

Organization: Northeastern Regional Fire Cod

Submittal Date: Thu Apr 11 08:24:44 EDT 2013

Copyright Assignment

I, John Chartier, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am John Chartier, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1365683084230.xml

Page 47: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 20/85

Public Input No. 22-NFPA 24-2012 [ New Section after 5.9.5.1 ]

5.9.5.2

Fire department connections shall not be connected on the suction side of fire pumps.

Statement of Problem and Substantiation for Public Input

This is important information that should be located in this section. Renumber accordingly.

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Thu Dec 13 15:25:43 EST 2012

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1355430343095.xml

Page 48: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 21/85

Public Input No. 69-NFPA 24-2013 [ Section No. 5.9.5.1 ]

Original Hide Markup

5.9.5.1 *

Fire Remote fire department connections shall be located at the nearest point offire department apparatus accessibility or at a location approved by the authorityhaving jurisdiction.

Statement of Problem and Substantiation for Public Input

the section needs to be specific in that it is referencing remote fire department connections. Fire department connections mounted on buildings are under the jurisdiction of NFPA 13. Identifying "remote" keeps the informatoin specific to remotely located hydrants.

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 16:59:34 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1369861174921.xml

Page 49: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 22/85

Public Input No. 70-NFPA 24-2013 [ Section No. 5.9.5.2 ]

Original Hide Markup

5.9.5.2 *

Fire Remote fire department connections shall be located and arranged so thathose lines can be attached to the inlets without interference.

Statement of Problem and Substantiation for Public Input

the section needs to be specific in that it is referencing remote fire department connections. Fire department connections mounted on buildings are under the jurisdiction of NFPA 13. Identifying "remote" keeps the informatoin specific to remotely located hydrants.

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 17:02:34 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1369861354245.xml

Page 50: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 23/85

Public Input No. 71-NFPA 24-2013 [ Section No. 5.9.5.3 ]

Original Hide Markup

5.9.5.3 *

Each fire remote fire department connection shall be designated by a sign asfollows:

(1) The sign shall have raised or engraved letters at least 1 in. (25.4 mm) inheight on a plate or fitting.

(2)

Statement of Problem and Substantiation for Public Input

the section needs to be specific in that it is referencing remote fire department connections. Fire department connections mounted on buildings are under the jurisdiction of NFPA 13. Identifying "remote" keeps the informatoin specific to remotely located hydrants.

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 17:03:18 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

* The sign shall indicate the type of system for which the connection isintended.

/TerraView/Content/24-2013.ditamap/2/C1369861398873.xml

Page 51: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 24/85

Public Input No. 21-NFPA 24-2012 [ Section No. 5.9.5.4 ]

Original Hide Markup

5.9.5.4

Where the system demand pressure exceeds 150 psi (10.3 bar), the sign requiredby 5.9.5.3 a sign located at the fire department connection shall indicate therequired design inlet pressure.

Statement of Problem and Substantiation for Public Input

Almost all the fire department connection plates indicating the connection type (autosprinkler, standpipe or both) are bought directly from the fire department connection manufacturers. Engraving these with the required inlet pressure is impractical. Also, since the sign referred to requires one inch high letters, it could be construed that the pressure information should also be the same size. In the fire sprinkler business, when a higher pressure requirement must be posted, we have custom made signs produced and placed on or at the FDC.

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Thu Dec 13 15:11:57 EST 2012

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1355429517654.xml

Page 52: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 25/85

Public Input No. 72-NFPA 24-2013 [ Section No. 5.9.5.5 ]

Original Hide Markup

5.9.5.5

Where a fire remote fire department connection only supplies a portion(s) of thebuilding, a sign shall be attached to indicate the portion(s) of the building supplied.

Statement of Problem and Substantiation for Public Input

the section needs to be specific in that it is referencing remote fire department connections. Fire department connections mounted on buildings are under the jurisdiction of NFPA 13. Identifying "remote" keeps the informatoin specific to remotely located hydrants.

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 17:04:07 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1369861447626.xml

Page 53: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 26/85

Public Input No. 49-NFPA 24-2013 [ Section No. 6.1.1 ]

Original Hide Markup

6.1.1

All Except as permitted by 6.2.1, all valves controlling connections to watersupplies and to supply pipes to sprinklers water-based fire protection systemsshall be listed indicating valves.

Additional Proposed Changes

File Name Description Approved

Open LK_NFPA_24-2013_Proposal_3_of_5.docx Cover Sheet

Statement of Problem and Substantiation for Public Input

During the previous revision cycle the words “listed indicating” were deleted from 6.2.1. This created a conflict whereby 6.1.1 and 6.2.5 call for listed indicating valves on water supplies, but 6.2.1 does not. The proposed text is offered as a resolution to this conflict. Additionally the modification to 6.2.1 would require the configuration to be acceptable to the AHJ and the proposed Annex text would offer an explanation for the matter.Also, in 6.1.1 the specific reference to “sprinklers” was revised to “water-based fire protection systems”, since private fire service mains supply other types of systems as well.

Submitter Information Verification

Submitter Full Name:Larry Keeping

Organization: Professional Loss Control

Submittal Date: Mon May 13 13:40:56 EDT 2013

Copyright Assignment

I, Larry Keeping, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Larry Keeping, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1368466856383.xml

Page 54: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 27/85

Public Input No. 73-NFPA 24-2013 [ New Section after 6.2.1 ]

TITLE OF NEW CONTENT

Type your content here ...

6.2.1.1 When more than one valve is installed in a water system, all valves shall be of thesame opening direction.

Statement of Problem and Substantiation for Public Input

addresses the possibility of installing different opening direction valves in the same system by requiring that all valves be of the same operating characteristic

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 17:05:09 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1369861509504.xml

Page 55: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 28/85

Public Input No. 50-NFPA 24-2013 [ Section No. 6.2.1 ]

Original Hide Markup

6.2.1 *

At least one approved control valve shall be installed in each source of watersupply.

Additional Proposed Changes

File Name Description Approved

Open LK_NFPA_24-2013_Proposal_3_of_5.docx Cover Sheet

Statement of Problem and Substantiation for Public Input

During the previous revision cycle the words “listed indicating” were deleted from 6.2.1. This created a conflict whereby 6.1.1 and 6.2.5 call for listed indicating valves on water supplies, but 6.2.1 does not. The proposed text is offered as a resolution to this conflict. Additionally the modification to 6.2.1 would require the configuration to be acceptable to the AHJ and the proposed Annex text would offer an explanation for the matter.Also, in 6.1.1 the specific reference to “sprinklers” was revised to “water-based fire protection systems”, since private fire service mains supply other types of systems as well.

Submitter Information Verification

Submitter Full Name:Larry Keeping

Organization: Professional Loss Control

Submittal Date: Mon May 13 13:42:33 EDT 2013

Copyright Assignment

I, Larry Keeping, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Larry Keeping, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1368466953958.xml

Page 56: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 29/85

Public Input No. 88-NFPA 24-2013 [ Section No. 6.2.2 ]

Original Hide Markup

6.2.2

No shutoff valve shall be permitted in the piping from the fire departmentconnection to the point that the fire department connection piping connectsto the system piping fire service main .

Additional Proposed Changes

File Name Description Approved

Open 24_Brown.pdf Cover Sheet

Statement of Problem and Substantiation for Public Input

The use of the term "system piping" has caused confusion on just where a fire department connection (fdc) can be installed. They read this as meaning that you cannot have any shutoff valve between the fdc and the system sprinkler system. Thus the arrangement shown in Figure A.3.3.11 would not be allowed sense there is two shutoff valves shown between the fdc and the sprinklered building.The term "fire service main" is used in Figure A.5.9(b).

Submitter Information Verification

Submitter Full Name:Phillip Brown

Organization: American Fire Sprinkler Association

Submittal Date: Mon Jun 03 11:24:43 EDT 2013

Copyright Assignment

I, Phillip Brow n, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Phillip Brow n, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1370273083412.xml

Page 57: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 30/85

Public Input No. 51-NFPA 24-2013 [ Section No. 6.2.5 ]

Original Hide Markup

6.2.5*

In a connection serving as one source of supply, listed indicating valves or postindicator valves control valves in accordance with 6.1.1 and 6.2.1 shall be installedon both sides of all check valves required in 6.2.3.

Additional Proposed Changes

File Name Description Approved

Open LK_NFPA_24-2013_Proposal_3_of_5.docx Cover Sheet

Statement of Problem and Substantiation for Public Input

During the previous revision cycle the words “listed indicating” were deleted from 6.2.1. This created a conflict whereby 6.1.1 and 6.2.5 call for listed indicating valves on water supplies, but 6.2.1 does not. The proposed text is offered as a resolution to this conflict. Additionally the modification to 6.2.1 would require the configuration to be acceptable to the AHJ and the proposed Annex text would offer an explanation for the matter.Also, in 6.1.1 the specific reference to “sprinklers” was revised to “water-based fire protection systems”, since private fire service mains supply other types of systems as well.

Submitter Information Verification

Submitter Full Name:Larry Keeping

Organization: Professional Loss Control

Submittal Date: Mon May 13 13:43:38 EDT 2013

Copyright Assignment

I, Larry Keeping, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Larry Keeping, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1368467018249.xml

Page 58: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 31/85

Public Input No. 74-NFPA 24-2013 [ Section No. 6.2.8 ]

Original Hide Markup

6.2.8 *

The following requirements shall apply where a gravity tank is located on abuilding:

(1) Both control valves shall be outside screw and yoke or listed indicatingvalves.

(2) All fittings inside the building, except the drain tee and heater connections,shall be under the control of a listed valve.

Exception: Welded fittings do not require a control valve.

Statement of Problem and Substantiation for Public Input

welded fittings should not require a control valve as they by their very nature, are typically not removed

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 17:07:32 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1369861652435.xml

Page 59: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 32/85

Public Input No. 29-NFPA 24-2012 [ Section No. 7.1.1 [Excluding any

Sub-Sections] ]

Original Hide Markup

Hydrants shall be of an approved type and have not less than a 6 in. (152 mm)diameter connection with the mains. be listed for fire protection.

Statement of Problem and Substantiation for Public Input

This standard requires valves to be listed. Hydrants are a vital component of private fire service mains and they should be listed as well. Listed hydrants are readily available and are not cost prohibitive. The minimum pipe size requirement has been deleted as it is located in 5.2.1 which is more appropriate. The only instance where a hydrant should not have to be listed is a draft hydrant which is outside the scope of this standard.

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Thu Dec 13 16:34:50 EST 2012

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1355434490527.xml

Page 60: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 33/85

Public Input No. 30-NFPA 24-2012 [ Section No. 7.1.1.1 [Excluding any

Sub-Sections] ]

Original Hide Markup

A valve shall be installed in the in each hydrant connection.

Statement of Problem and Substantiation for Public Input

Clarifies that each hydrant shall have its own isolation valve.

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Thu Dec 13 16:41:20 EST 2012

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1355434880470.xml

Page 61: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 34/85

Public Input No. 75-NFPA 24-2013 [ New Section after 7.1.1.1.1 ]

TITLE OF NEW CONTENT

Type your content here ...

7.1.1.1.1.1 Valves shall be clearly identified and kept free of obstructions.

Statement of Problem and Substantiation for Public Input

this additional wording should assist in preventing valves from being buried or paved over.

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 17:09:45 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1369861785818.xml

Page 62: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 35/85

Public Input No. 31-NFPA 24-2012 [ Section No. 7.1.1.1.1 ]

Original Hide Markup

7.1.1.1.1

Valves in the hydrant connection shall Valves required by 7.1.1.1 shall be installedwithin 20 ft (6.1 m) of the hydrant.

Statement of Problem and Substantiation for Public Input

Modified for readability

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Thu Dec 13 16:42:54 EST 2012

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1355434974047.xml

Page 63: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 36/85

Public Input No. 32-NFPA 24-2012 [ Section No. 7.1.1.1.2 ]

Original Hide Markup

7.1.1.1.2

Where valves cannot be located in it is impractical to locate valves in accordancewith 7.1.1.1.1, other valve locations shall be permitted where permitted asapproved by the authority having jurisdiction.

Statement of Problem and Substantiation for Public Input

Modified wording from cannot to impractical.

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Thu Dec 13 16:45:13 EST 2012

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1355435113386.xml

Page 64: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 37/85

Public Input No. 33-NFPA 24-2012 [ Section No. 7.1.3 ]

Original Hide Markup

7.1.3 2.1

Where local fire department connections do not conform to NFPA 1963, theauthority having jurisdiction shall designate the connection to be used.

Statement of Problem and Substantiation for Public Input

Manual of Style.

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Thu Dec 13 16:55:39 EST 2012

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1355435739495.xml

Page 65: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 38/85

Public Input No. 34-NFPA 24-2012 [ Section No. 7.2.4 ]

Original Hide Markup

7.2.4 3.1

Where hydrants cannot be located in accordance with 7.2.3, locations closer than40 ft (12.2 m) from the building or wall hydrants shall be permitted to be used wherepermitted where approved by the authority having jurisdiction.

Statement of Problem and Substantiation for Public Input

Renumbered as appropriate and modified wording for readability.

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Thu Dec 13 16:58:47 EST 2012

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1355435927838.xml

Page 66: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 39/85

Public Input No. 35-NFPA 24-2012 [ Section No. 7.2.5 ]

Original Hide Markup

7.2.5

Hydrants shall not be installed installed adjacent to retaining walls at less than theequivalent depth of burial from retaining walls where burial found in 10.4.4 wherethere is danger of frost through the walls.

Statement of Problem and Substantiation for Public Input

Reworded to give user guidance as to where to find burial depths. 10.4.4 will be renumbered in another PI to conform to manual of style.

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Thu Dec 13 17:05:35 EST 2012

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

Public Input No. 36-NFPA 24-2012 [ Section No. 7.3 ]

Original Hide Markup

7.3 Installation.

7.3.1*

/TerraView/Content/24-2013.ditamap/2/C1355436335966.xml

Page 67: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 40/85

7.3.1*

Hydrants shall be set on flat stones or concrete slabs and shall be provided withsmall stones (or the equivalent) , concrete slabs, or approved equivalent.

7.3.2

Small stones or an approved equivalent shall be placed about the drain to ensuredrainage.

7.3.2 2.1

Where soil is of such a nature that the hydrants hydrant will not drain properlywith the arrangement specified in 7.3.1 2 , or where groundwater stands at levelsabove that of the above the drain, the hydrant drain shall be plugged at the time ofinstallation.

7.3.2.1 2

If

Hydrants with the drain

is

plugged

, hydrants

that are

in service in cold climates shall be pumped out after usage.

7.3.2.2

Such hydrants

3

Hydrants with the drain plugged shall be marked to indicate the need for pumpingout after usage.

7.3.3*

The center of a hose outlet shall be not less than 18 in. (457 mm) above final gradeor, where located in a hose house, .

7.3.3.1

The center of a hose outlet shall not be more than 36 in. (914 mm) above finalgrade.

7.3.3.2

The center of a hose outlet located in a hose house shall not be less than 12 in.(305 mm) above the floor.

7.3.4

Hydrants shall be fastened to piping and anchored be restrained in accordancewith the requirements of Chapter 10.

7.3.5

Hydrants shall be protected if subject to mechanical damage.

7.3.6 5.1

The means of hydrant protection shall be arranged in a manner so that it does notinterfere with the connection to, or operation of, hydrants the hydrant .

Page 68: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 41/85

7.3.7

The following shall not be installed in the service stub between a fire hydrant andprivate water supply piping:

(1) Check valves

(2) Detector check valves

(3) Backflow prevention valves

(4) Other similar appurtenances

Statement of Problem and Substantiation for Public Input

Modified numbering to meet manual of style. Added a maximum height requirement that is shown on Annex Figure A.7.3.1 (b). Modified wording for readability.

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Fri Dec 14 08:47:58 EST 2012

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1355492878369.xml

Page 69: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 42/85

Public Input No. 76-NFPA 24-2013 [ New Section after 7.3.3 ]

TITLE OF NEW CONTENT

Type your content here .

7.3.4 the center of a hose outlet shall not be greater than 48 in (1.2 m) above final grade,or where located in a hose house, 24 in (610 mm) above the floor.

Renumber subsequent sections accordingly.

Statement of Problem and Substantiation for Public Input

Minimum heights are provided in the previous section. Maximum heights should be provided to prevent installations that prevent proper use of the device.

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 17:11:23 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1369861883653.xml

Page 70: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 43/85

Public Input No. 77-NFPA 24-2013 [ Section No. 7.3.4 ]

Original Hide Markup

7.3. 4 5

Hydrants shall be fastened to piping and anchored in accordance with therequirements of Chapter 10 .

Statement of Problem and Substantiation for Public Input

renumbering based on comment provided for new 7.3.4

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 17:13:53 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1369862033614.xml

Page 71: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 44/85

Public Input No. 78-NFPA 24-2013 [ Section No. 7.3.5 ]

Original Hide Markup

7.3. 5 6

Hydrants shall be protected if subject to mechanical damage.

Statement of Problem and Substantiation for Public Input

renumbering based on comment provided for new 7.3.4

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 17:14:51 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1369862091680.xml

Page 72: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 45/85

Public Input No. 55-NFPA 24-2013 [ Section No. 7.3.6 ]

Original Hide Markup

7.3.6

The means of hydrant protection shall be arranged in a manner that does not interferewith the connection to, or operation of, hydrants.

Statement of Problem and Substantiation for Public Input

2006 Fire code section 508.5.6 states that hydrants subject to impact by motor vehicles, shall be provided with guard posts or other approved means that comply with section 312.

Section 312 states that the spacing between posts shall not exceed 4 (four) foot on center and not less than 3 (three) feet from protected object. The demensions stated have been investgated numerous times in the field to confirm that it is not possible to provide the protection required using 4 (four) posts.

Currently architects/designers are calling for the use of 4 posts, it is not possible to maintain the 4 foot on center between posts and the 3 foot clearance from the protected object without adding an additional post.

This concern is usually handled through the architect of record for the project, but it comes with a change order/additional cost to the owner.

Submitter Information Verification

Submitter Full Name:Manuel C Rios

Organization: Clark County School District

Submittal Date: Fri May 17 09:52:50 EDT 2013

Copyright Assignment

I, Manuel C Rios, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Manuel C Rios, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1368798770624.xml

Page 73: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 46/85

Public Input No. 79-NFPA 24-2013 [ Section No. 7.3.6 ]

Original Hide Markup

7.3. 6 7

The means of hydrant protection shall be arranged in a manner that does notinterfere with the connection to, or operation of, hydrants.

Statement of Problem and Substantiation for Public Input

renumbering based on comment provided for new 7.3.4

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 17:15:22 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1369862122479.xml

Page 74: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 47/85

Public Input No. 80-NFPA 24-2013 [ Section No. 7.3.7 ]

Original Hide Markup

7.3. 7 8

The following shall not be installed in the service stub between a fire hydrant andprivate water supply piping:

(1) Check valves

(2) Detector check valves

(3) Backflow prevention valves

(4) Other similar appurtenances

Statement of Problem and Substantiation for Public Input

renumbering based on comment provided for new 7.3.4

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 17:16:00 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1369862160669.xml

Page 75: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 48/85

Public Input No. 53-NFPA 24-2013 [ Section No. 8.1.2 ]

Original Hide Markup

8.1.2

Hose shall be stored so it is accessible and is protected from the weather bystoring .

8.1.2.1 Hose shall be permitted to be stored in hose houses or by placing hosereels or hose carriers in weatherproof enclosures.

Additional Proposed Changes

File Name Description Approved

Open LK_NFPA_24-2013_Proposal_4_of_5.docx Cover Sheet

Statement of Problem and Substantiation for Public Input

This proposed revision editorial in nature, to clarify the intent. It is common practice for some industrial fire brigades to store their hose at their fire halls and/or on their fire trucks, but as written the current text seems to imply that it is mandatory to put the hose in hose houses or on reels or carriers in weatherproof enclosures.

Submitter Information Verification

Submitter Full Name:Larry Keeping

Organization: Professional Loss Control

Submittal Date: Mon May 13 13:46:06 EDT 2013

Copyright Assignment

I, Larry Keeping, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Larry Keeping, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1368467166586.xml

Page 76: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 49/85

Public Input No. 81-NFPA 24-2013 [ Section No. 8.3.1 ]

Original Hide Markup

8.3.1

Hose houses shall be of substantial construction onfoundations stable foundations .

Statement of Problem and Substantiation for Public Input

adding "stable" ensures that the hose houses are not installed on loose soils

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 17:17:04 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

Public Input No. 38-NFPA 24-2012 [ Section No. 10.1 ]

Original Hide Markup

10.1* Piping Materials.

10.1.1* Listing.

Piping shall be listed for fire protection service or All piping used in private fireservice mains shall be in accordance with Section 10.1.1

10.1.1.1

Piping used in private fire service mains shall comply with the standards in Table10.1.1 .

/TerraView/Content/24-2013.ditamap/2/C1369862224204.xml

Page 77: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 50/85

10.1.1.2

Piping not shown in Table 10.1.1 shall be specifically listed for use in private fireservice mains.

Table 10.1.1 Manufacturing Standards for Underground Pipe

Materials and Dimensions Standard

Ductile Iron

Cement Mortar Lining for Ductile Iron Pipe and Fittings for WaterAWWAC104

Polyethylene Encasement for Ductile Iron Pipe SystemsAWWAC105

Ductile Iron and Gray Iron Fittings, 3 in. Through 48 in., for Water andOther Liquids

AWWAC110

Rubber-Gasket Joints for Ductile Iron Pressure Pipe and FittingsAWWAC111

Flanged Ductile Iron Pipe with Ductile Iron or Gray Iron ThreadedFlanges

AWWAC115

Protective Fusion-Bonded Epoxy Coatings for the Interior and ExteriorSurfaces of Ductile-Iron and Gray-Iron Fittings for Water SupplyService

AWWAC116

Thickness Design of Ductile Iron PipeAWWAC150

Ductile Iron Pipe, Centrifugally Cast for WaterAWWAC151

Ductile-Iron Compact Fittings for Water ServiceAWWAC153

Standard for the Installation of Ductile Iron Water Mains and TheirAppurtenances

AWWAC600

Steel

Steel Water Pipe 6 in. and LargerAWWAC200

Coal-Tar Protective Coatings and Linings for Steel Water PipelinesEnamel and Tape — Hot Applied

AWWAC203

Cement-Mortar Protective Lining and Coating for Steel Water Pipe 4 in.and Larger — Shop Applied

AWWAC205

Field Welding of Steel Water PipeAWWAC206

Steel Pipe Flanges for Waterworks Service — Sizes 4 in. Through 144in.

AWWAC207

Dimensions for Fabricated Steel Water Pipe FittingsAWWAC208

A Guide for Steel Pipe Design and InstallationAWWAM11

Concrete

Reinforced Concrete Pressure Pipe, Steel-Cylinder TypeAWWAC300

Prestressed Concrete Pressure Pipe, Steel-Cylinder TypeAWWAC301

Reinforced Concrete Pressure Pipe, Non-Cylinder TypeAWWAC302

Page 78: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 51/85

Reinforced Concrete Pressure Pipe, Steel-Cylinder Type,Pretensioned

AWWAC303

Standard for Asbestos-Cement Distribution Pipe, 4 in. Through 16 in.,for Water Distribution Systems

AWWAC400

Standard for the Selection of Asbestos-Cement Pressure PipeAWWAC401

Cement-Mortar Lining of Water Pipe Lines 4 in. and Larger — in PlaceAWWAC602

Standard for the Installation of Asbestos-Cement Water PipeAWWAC603

Plastic

Polyvinyl Chloride (PVC) Pressure Pipe, 4 in. Through 12 in., for WaterDistribution

AWWAC900

Polyvinyl Chloride (PVC) Pressure Pipe, 14 in. Through 48 in., forWater Distribution

AWWAC905

Polyethylene (PE) Pressure Pipe and Fittings, 4 in. (100 mm) Through63 in. (1575 mm) for Water Distribution

AWWAC906

Copper

Specification for Seamless Copper TubeASTM B75

Specification for Seamless Copper Water TubeASTM B88

Requirements for Wrought Seamless Copper and Copper-Alloy TubeASTM B251

10.1.2 Steel Pipe.

Steel piping pipe shall not be used for general underground service unless inprivate fire service mains execpt as permitted in 10.1.2.1 and 10.1.2.2.

10.1.2.1

Steel pipe shall be permitted to be used in private fire service whens whenspecifically listed for such

service

use .

10.1.3 Steel Pipe Used with Fire Department Connections.

Where externally coated and wrapped and internally galvanized, steel pipe shall

2.2

Steel pipe installed in accordance with 10.1.2.2 shall be permitted to be usedbetween the check valve and the outside hose coupling for the hose coupling(s) onthe fire department connection.

10.1.

4

2.2.1

Steel pipe shall be internally galvanized.

10.1.2.2.2

Steel pipe shall be wrapped and coated with approved materials to preventcorrosion.

10.1.3 * Pipe Type and Class.

Page 79: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 52/85

10.1.3 * Pipe Type and Class.

The requirements of 10.1.3 shall be considered when selecting the type and classof pipe

for a particular underground installation shall be determined through considerationof the following factors:

(1) Fire resistance of the pipe

(2) Maximum system working pressure

(3) Depth at which the pipe is to be installed

(4) Soil conditions

(5) Corrosion

(6) Susceptibility of pipe to other external loads, including earth loads,installation beneath buildings, and traffic or vehicle loads

10.1.5 * Working Pressure.

Piping, fittings, and other system components shall be rated for the maximumsystem working pressure to which they are exposed but shall not be rated at lessthan 150 psi (10 bar).

10.1.6 * Lining of Buried Pipe.

10.1.6.1

Unless the requirements of 10.1.6.2 are met, all ferrous metal pipe

to be used.

10.1.3.1

The fire resistance of the pipe shall be considered when piping passes abovegrade.

10.1.3.1.1

Piping acceptable for underground shall be permitted to extend 24 in. (0.6m)through the floor or wall into the building without regards to 10.1.3.1.

10.1.3.2

The maximum system working pressure shall be considered.

10.1.3.2.1

When a fire department connection is installed, the pressure from the firedepartment connection shall not be considered as part of the system workingpressure.

10.1.3.3

The depth of bury of the pipe and susceptibility to earth loads and traffic or vehicleloads shall be considered.

10.1.3.4

The type of soil and potential for corrosion shall be considered.

Page 80: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 53/85

10.1.4 * Working Pressure.

All pipe used in private fire service mains shall be rated at a minimum of 150 psi (10bar).

10.1.4.1

When the system working pressure exceeds 150 psi (10 bar), piping shall be ratedfor the maximum system working pressure.

10.1.5* Lining of Buried Pipe.

10.1.5.1

Except as permitted in 10.1.2.2, all ferrous metal piping shall be lined inaccordance with the applicable standards in Table 10.1.1 .

10.1.6.2

Steel pipe utilized in fire department connections and protected in accordance withthe requirements of 10.1.3 shall not be required to be internally lined.

Statement of Problem and Substantiation for Public Input

Modified to follow manual of style. Eliminated some repetitive text. Added allowance for piping to extend into building for riser connection to correlate with NFPA 13 (6.3.1.1.1).

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Tue Dec 18 08:44:36 EST 2012

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

Public Input No. 59-NFPA 24-2013 [ Section No. 10.1.1 ]

Original Hide Markup

10.1.1 * Listing.

Piping shall be listed for fire protection service or shall comply with the standards

/TerraView/Content/24-2013.ditamap/2/C1355838276424.xml

Page 81: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 54/85

in Table 10.1.1.

Table 10.1.1 Manufacturing Standards for Underground Pipe

Materials and Dimensions Standard

Ductile Iron

Cement Mortar Lining for Ductile Iron Pipe and Fittings for WaterAWWAC104

Polyethylene Encasement for Ductile Iron Pipe SystemsAWWAC105

Ductile Iron and Gray Iron Fittings, 3 in. Through 48 in., for Water andOther Liquids

AWWAC110

Rubber-Gasket Joints for Ductile Iron Pressure Pipe and FittingsAWWAC111

Flanged Ductile Iron Pipe with Ductile Iron or Gray Iron ThreadedFlanges

AWWAC115

Protective Fusion-Bonded Epoxy Coatings for the Interior and ExteriorSurfaces of Ductile-Iron and Gray-Iron Fittings for Water SupplyService

AWWAC116

Thickness Design of Ductile Iron PipeAWWAC150

Ductile Iron Pipe, Centrifugally Cast for WaterAWWAC151

Ductile-Iron Compact Fittings for Water ServiceAWWAC153

Standard for the Installation of Ductile Iron Water Mains and TheirAppurtenances

AWWAC600

Steel

Steel Water Pipe 6 in. and LargerAWWAC200

Coal-Tar Protective Coatings and Linings for Steel Water PipelinesEnamel and Tape — Hot Applied

AWWAC203

Cement-Mortar Protective Lining and Coating for Steel Water Pipe 4in. and Larger — Shop Applied

AWWAC205

Field Welding of Steel Water PipeAWWAC206

Steel Pipe Flanges for Waterworks Service — Sizes 4 in. Through144 in.

AWWAC207

Dimensions for Fabricated Steel Water Pipe FittingsAWWAC208

A Guide for Steel Pipe Design and InstallationAWWAM11

Concrete

Reinforced Concrete Pressure Pipe, Steel-Cylinder TypeAWWAC300

Prestressed Concrete Pressure Pipe, Steel-Cylinder TypeAWWAC301

Reinforced Concrete Pressure Pipe, Non-Cylinder TypeAWWAC302

Reinforced Concrete Pressure Pipe, Steel-Cylinder Type,Pretensioned

AWWAC303

Page 82: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 55/85

Standard for Asbestos-Cement Distribution Pipe, 4 in. Through 16 in.,for Water Distribution Systems

AWWAC400

Standard for the Selection of Asbestos-Cement Pressure PipeAWWAC401

Cement-Mortar Lining of Water Pipe Lines 4 in. and Larger — inPlace

AWWAC602

Standard for the Installation of Asbestos-Cement Water PipeAWWAC603

Plastic

Polyvinyl Chloride (PVC) Pressure Pipe, 4 in. Through 12 in., forWater Distribution

AWWAC900

Polyvinyl Chloride (PVC) Pressure Pipe, 14 in. Through 48 in., forWater Distribution

AWWAC905

Polyethylene (PE) Pressure Pipe and Fittings, 4 in. (100 mm) Through63 in. (1575 mm) for Water Distribution

AWWAC906

Molecularly Oriented Polyvinyl Chloride (PVCO) Pressure Pipe, 4 INthrough24 IN. (100 MM through 600 MM ), for Water Wastewater, andReclaimed Water Service

AWWA

C909

Copper

Specification for Seamless Copper TubeASTM B75

Specification for Seamless Copper Water TubeASTM B88

Requirements for Wrought Seamless Copper and Copper-Alloy TubeASTM B251

Statement of Problem and Substantiation for Public Input

Molecular Modified PVC pipes (PVC-O) have a higher resistance against imoact and water hammer effects. It is not sensitive in installation, also not when installed at low temperatures. So the PVC-O pipe is more robust then our PVC-U and hence it should be included in the list.

Related Public Inputs for This Document

Related Input Relationship

Open

Public Input No. 60-NFPA24-2013 [Section No.2.3.3]

One is related to the reference to the relevantstandard., the order to include in the list of material

Submitter Information Verification

Submitter Full Name:Frans Alferink

Organization: Wavin Overseas, The Netherlands / Pavco Colombia

Affilliation: S2rEnginieros, Bogota Colombia, Mr. Antonio Yesid Lopez

Submittal Date: Thu May 23 12:38:17 EDT 2013

Copyright Assignment

Page 83: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 56/85

I, Frans Alferink, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Frans Alferink, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

Public Input No. 39-NFPA 24-2012 [ Section No. 10.2 ]

Original Hide Markup

10.2 Fittings.

All fittings used in private fire service mains shall be in accordance with section10.2.

10.2. 1 *

Buried

Buried Fittings

.

Fittings shall be of an approved type with joints and pressure class ratings

10.2.1.1

All buried fittings used in private fire service mains shall be approved.

10.2.1.2

Fittings specifically listed for use in private fire service mains shall be permitted tobe used.

10.2.1.2.1

When listed fittings are used, they shall be installed in accordance with their listinglimitations, including installation instructions.

10.2.1.3

Buried fittings shall have the same pressure class rating as the pipe.

10.2.1.4

Buried fittings shall be compatible with the pipe used.

10.2.2 Standard Fittings.

/TerraView/Content/24-2013.ditamap/2/C1369327097416.xml

Page 84: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 57/85

10.2.2.

1

1

All fittings used in private fire service mains installed aboveground shall be inaccordance with 10.2.2.

10.2.2.2

Fittings shall meet the standards in Table 10.2.2.1 2 or shall be in accordancewith 10.2.3 2 . 4 .

Table 10.2.2.1 Fittings 2 Fittings Materials and Dimensions

Materials and Dimensions Standard

Cast Iron

Gray Iron Threaded Fittings, Classes 125 and 250ASMEB16.4

Gray Iron Pipe Flanges and Flanged Fittings, Classes 12, 125, and250

ASMEB16.1

Malleable Iron

Malleable Iron Threaded Fittings, Class 150 and 300ASMEB16.3

Steel

Factory-Made Wrought Steel Buttweld FittingsASMEB16.9

Buttwelding EndsASMEB16.25

Specification for Piping Fittings of Wrought Carbon Steel and AlloySteel for Moderate and Elevated Temperatures

ASTM A234

Pipe Flanges and Flanged Fittings, NPS 1 ⁄ 2 Through 24ASMEB16.5

Forged Steel Fittings, Socket Welded and ThreadedASMEB16.11

Copper

Wrought Copper and Bronze Solder Joint Pressure FittingsASMEB16.22

Cast Bronze Solder Joint Pressure FittingsASMEB16.18

Page 85: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 58/85

10.2.2.2

In addition to the standards in Table 10.2.2.2 , CPVC fittings shall also be

3

CPVC fittings shall be in accordance with 10.2.3 2.4 and with the portions of theASTM standards specified in Table 10.2.2.2 3 that apply to fire protection service.

Table 10.2.2.2 Specially 3 Specially Listed Fittings Materials and Dimensions

Materials and Dimensions Standard

Chlorinated Polyvinyl Chloride (CPVC) Specification for Schedule 80CPVC Threaded Fittings

ASTM F437

Specification for Schedule 40 CPVC Socket-Type FittingsASTM F438

Specification for Schedule 80 CPVC Socket-Type FittingsASTM F439

10.2.3 Special Listed Fittings2 .

Other types of fittings investigated for suitability in automatic sprinkler installationsand listed for this service, including, but not limited to, polybutylene, CPVC, andsteel differing from that provided in Table

4

Fittings specifically listed for use in fire protection systems shall be permitted to beused.

10.2.2. 4. 1

When listed fittings are used , they shall be

permitted when

installed in accordance with their listing limitations, including installationinstructions.

10.2.4 Pressure Limits3 Working Pressure .

Listed fittings shall be permitted for the system pressures as specified in theirlistings, but not less than All fittings used in private fire service mains shall berated at a minimum of 150 psi (10 bar).

10.2.3.1

When the system working pressure exceeds 150 psi (10 bar) , fittings shall berated for the maximum system working pressure .

Statement of Problem and Substantiation for Public Input

Modified for manual of style

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Tue Dec 18 09:49:47 EST 2012

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

Page 86: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 59/85

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1355842187167.xml

Page 87: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 60/85

Public Input No. 87-NFPA 24-2013 [ Section No. 10.4.5 ]

Original Hide Markup

10.4.5

Pipe under railroad tracks shall be buried at a minimum depth of 4 ft (1.2m) , the owner/operator of the railroad track must be contacted for theirrequirements .

Additional Proposed Changes

File Name Description Approved

Open 24_Brown.pdf Cover Sheet

Statement of Problem and Substantiation for Public Input

It is not unusual for a user/operator of a railroad track to require a minimum of 10 ft from top of rail to top of pipe passing under their rail. This could be a very costly error for the installer if they failed to contact the owner/operator of the railroad track.

Submitter Information Verification

Submitter Full Name:Phillip Brown

Organization: American Fire Sprinkler Association

Submittal Date: Mon Jun 03 11:19:51 EDT 2013

Copyright Assignment

I, Phillip Brow n, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Phillip Brow n, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

Public Input No. 54-NFPA 24-2013 [ Section No. 13.2 ]

Original Hide Markup

/TerraView/Content/24-2013.ditamap/2/C1370272791759.xml

Page 88: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 61/85

13.2 Mains Not Supplying Hydrants.

For mains that do not supply hydrants, sizes smaller than 6 in. (152 mm) shall bepermitted to be used, subject to the following restrictions:

(1) The main shall supply only the following types of systems:

(a) Automatic sprinkler systems

(b) Open sprinkler systems

(c) Water spray fixed systems

(d) Foam systems

(e) Class II standpipe Standpipe systems

(2) Hydraulic calculations shall show that the main is able to supply the totaldemand at the appropriate pressure.

(3) Systems that are not hydraulically calculated shall have a main at least aslarge as the riser.

Additional Proposed Changes

File Name Description Approved

Open LK_NFPA_24-2013_Proposal_5_of_5.docx Cover Sheet

Statement of Problem and Substantiation for Public Input

This change is proposed to align 13.2 (e) with the text of 5.2.2 (e), which was revised during the last cycle to delete the “Class II” reference. As discussed then, there should not be a requirement which specifies a 6” minimum water supply for all Class I & III standpipes. NFPA 14 requires that all new standpipes be hydraulically calculated, so this standard should not dictate a minimum size for the private fire service mains that supply them.

Submitter Information Verification

Submitter Full Name:Larry Keeping

Organization: Professional Loss Control

Submittal Date: Mon May 13 13:47:41 EDT 2013

Copyright Assignment

I, Larry Keeping, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Larry Keeping, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1368467261443.xml

Page 89: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 62/85

Public Input No. 2-NFPA 24-2012 [ New Section after A.3.3.11 ]

A.3.3.15.2

Examples are outside screw and yoke (OS&Y) gate valves and underground gate valveswith indicator posts.

Statement of Problem and Substantiation for Public Input

Examples belong in the annex.

Related Public Inputs for This Document

Related Input Relationship

Open Public Input No. 1-NFPA 24-2012 [Section No. 3.3.15.2]

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Wed Dec 12 16:43:47 EST 2012

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1355348627963.xml

Page 90: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 63/85

Public Input No. 28-NFPA 24-2012 [ Section No. A.3.4.1.3 ]

Original Hide Markup

A.3.4.1.3 Private Fire Hydrant.

Where connected to a public water system, the private hydrants are supplied by aprivate service main that begins at the point of service designated by the authorityhaving jurisdiction, usually at a manually operated valve near the property line.

Statement of Problem and Substantiation for Public Input

The term "Point of Service" is a legally defined term in the State of Florida. This use of that term causes some confusion. Removing the phrase of service does not change the intent of this section.

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Thu Dec 13 16:25:46 EST 2012

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1355433946790.xml

Page 91: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 64/85

Public Input No. 27-NFPA 24-2012 [ Section No. A.4.1 ]

Original Hide Markup

A.4.1

Underground mains should be designed so that the system can be extended with aminimum of expense with minimum expense . Possible future plant expansionfuture expansion should also be considered and the piping designed so that it isnot covered by buildings future buildings .

Statement of Problem and Substantiation for Public Input

Modified wording for readability.

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Thu Dec 13 16:23:17 EST 2012

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

Public Input No. 24-NFPA 24-2012 [ Section No. A.5.4 ]

Original Hide Markup

Print Reload Page Close Show Cart

/TerraView/Content/24-2013.ditamap/2/C1355433797825.xml

Page 92: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 65/85

A.5.4

Where connections are made from public waterworks systems, such systemsshould be guarded against possible contamination as follows (see AWWA M14 orlocal plumbing code or consult the local water purveyor ):

(1) For private fire service mains with direct connections from public waterworksmains only or with fire pumps installed in the connections from the streetmains, no tanks or reservoirs, no physical connection from other watersupplies, no antifreeze or other additives of any kind, and with all drainsdischarging to atmosphere, dry well, or other safe outlets, an approved doublecheck valve assembly is recommended.

(2) For private fire service mains with direct connections from the public watersupply main plus one or more elevated storage tanks or fire pumps takingsuction from aboveground covered reservoirs or tanks (all storage facilities arefilled or connected to public water only, and the water in the tanks is to bemaintained in a potable condition), an approved double check valve assemblyis recommended.

(3) For private fire service mains directly supplied from public mains with anauxiliary water supply, such as a pond or river on or available to the premisesand dedicated to fire department use; or for systems supplied from publicmains and interconnected with auxiliary supplies, such as pumps takingsuction from reservoirs exposed to contamination or rivers and ponds; drivenwells, mills, or other industrial water systems; or for systems or portions ofsystems where antifreeze or other solutions are used, an approved reduced-pressure zone-type backflow preventer is recommended.

(4) For private fire service mains with fire department connections located within1750 ft (533.4 m) of a non potable water source, an approved reduced-pressure zone-type backflow preventer is recommended.

Statement of Problem and Substantiation for Public Input

This is an AWWA requirement that is being increasingly enforced. Since this standard includes annex language on backflow prevention, this should be added.

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Thu Dec 13 15:35:10 EST 2012

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

Page 93: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 66/85

Public Input No. 82-NFPA 24-2013 [ New Section after A.5.6 ]

TITLE OF NEW CONTENT

Type your content here ...

A.5.8.1 In the selection of screen material, consideration should be given to prevention offouling from aquatic growth. Antifouling is best accomplished with brass or copper wire.[20: A.4.14.8]

Statement of Problem and Substantiation for Public Input

adding the detail on the screens provided consistency with other NFPA standards that address screens on intakes from open bodies of water (NFPA20). Wording is consistent with NFPA 20.

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 17:19:39 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1355430910267.xml

/TerraView/Content/24-2013.ditamap/2/C1369862379229.xml

Page 94: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 67/85

Public Input No. 25-NFPA 24-2012 [ Section No. A.5.6 ]

Original Hide Markup

A.5.6

A fire pump installation consisting of pump, driver, and suction supply, when ofadequate capacity and reliability and properly located, makes a goodsupply makes an acceptable supply . An automatically controlled fire pump takingor pumps taking water from a water main of adequate capacity, or taking draftunder a head from a reliable storage of adequate capacity, is permitted to be, undercertain conditions, accepted by the authority having jurisdiction as a single supply.

Statement of Problem and Substantiation for Public Input

Acceptable is a better term than good. added language to indicate that some occupancies will utilize more than one pump.

Related Public Inputs for This Document

Related Input Relationship

Open Public Input No. 13-NFPA 24-2012 [Section No. 5.6]

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Thu Dec 13 15:49:11 EST 2012

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

Public Input No. 83-NFPA 24-2013 [ Section No. A.5.9 ]

/TerraView/Content/24-2013.ditamap/2/C1355431751338.xml

Page 95: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 68/85

Original Hide Markup

A.5.9

The fire department connection should be located not less than 18 in. (457mm) and not more than 4 ft (1.2 m) above the level of the adjacent grade oraccess level. Typical A typical fire department connections are connection isshown in Figure A.5.9(a) and Figure A . 5.9(b). Where a hydrant is notavailable, other water supply sources such as a natural body of water, a tank, or areservoir should be utilized. The water authority should be consulted when anonpotable water supply is proposed as a suction source for the fire department.

Figure A.5.9(a) Typical

Fire Department Connection.

Figure A.5.9(b) Typical

City Water Pit — Valve Arrangement with Fire Department Connection .

Statement of Problem and Substantiation for Public Input

Page 96: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 69/85

Figure 5.9(a) as currently shown shows a fire department connection supplied by piping interior to a building, which falls under the jurisdiction of NFPA 13. This standard addresses remote fire department connections and as such, removing the figure eliminates confusion on piping of these devices.

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 17:22:59 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1369862579570.xml

Page 97: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 70/85

Public Input No. 20-NFPA 24-2012 [ Section No. A.5.9.5.2 ]

Original Hide Markup

A.5.9.5.2

Obstructions to fire department connections include, but are not limited to,buildings, fences, posts, landscaping, other fire department connections, gas fireprotection equipment, gas meters, and electrical equipment.

Additional Proposed Changes

File Name Description Approved

Open PIV.jpg Blocked FDC

Statement of Problem and Substantiation for Public Input

It is common to see a Yard PIV obstruct a fire department connection.

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Thu Dec 13 14:52:34 EST 2012

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1355428354065.xml

Page 98: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith
Page 99: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 71/85

Public Input No. 23-NFPA 24-2012 [ Section No. A.5.9.5.3 ]

Original Hide Markup

A. 5.9.5. 3 6

Where a fire department connection services multiple buildings, structures, orlocations, a sign should shall be provided indicating the buildings, structures, orlocations served.

Statement of Problem and Substantiation for Public Input

This information should not be in the annex. This proposal moves it into the body of the standard. It is understood that fire departments should perform preplanning and know the purpose of the FDC's prior to a fire event. However, a sign indicating such helps facilitate a response at 3:00 am in the morning.

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Thu Dec 13 15:30:57 EST 2012

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1355430657523.xml

Page 100: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 72/85

Public Input No. 26-NFPA 24-2012 [ Section No. A.5.9.5.3(2) ]

Original Hide Markup

A.5.9.5.3(2)

Examples for wording of signs are:

AUTOSPKR

AUTO SPKR

OPEN SPKR

.

STANDPIPE

AND

STANDPIPE -SPRINKLER

DRY STANDPIPE

STANDPIPE-AUTO SPKR

Statement of Problem and Substantiation for Public Input

Updated list with terms commonly found on different manufacturers' websites.

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Thu Dec 13 15:54:43 EST 2012

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1355432083973.xml

Page 101: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 73/85

Public Input No. 52-NFPA 24-2013 [ New Section after A.6.1.5 ]

A.6.2.1 A connection to a municipal water supply may utilize a non-indicating tappingsleeve and valve as the valve controlling the water supply.

Additional Proposed Changes

File Name Description Approved

Open LK_NFPA_24-2013_Proposal_3_of_5.docx Cover Sheet

Statement of Problem and Substantiation for Public Input

During the previous revision cycle the words “listed indicating” were deleted from 6.2.1. This created a conflict whereby 6.1.1 and 6.2.5 call for listed indicating valves on water supplies, but 6.2.1 does not. The proposed text is offered as a resolution to this conflict. Additionally the modification to 6.2.1 would require the configuration to be acceptable to the AHJ and the proposed Annex text would offer an explanation for the matter.Also, in 6.1.1 the specific reference to “sprinklers” was revised to “water-based fire protection systems”, since private fire service mains supply other types of systems as well.

Submitter Information Verification

Submitter Full Name:Larry Keeping

Organization: Professional Loss Control

Submittal Date: Mon May 13 13:44:47 EDT 2013

Copyright Assignment

I, Larry Keeping, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Larry Keeping, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

Public Input No. 40-NFPA 24-2013 [ Section No. A.10.4.1 ]

Original Hide Markup

/TerraView/Content/24-2013.ditamap/2/C1368467087960.xml

Page 102: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 74/85

A.10.4.1

The following documents apply to the installation of pipe and fittings:

(1) AWWA C603, Standard for the Installation of Asbestos-Cement Pressure Pipe

(2) AWWA C600, Standard for the Installation of Ductile-Iron Water Mains and TheirAppurtenances

(3) AWWA M11, A Guide for Steel Pipe Design and Installation

(4) AWWA M41, Ductile Iron Pipe and Fittings

(5) Concrete Pipe Handbook , American Concrete Pipe Association

(6) Handbook of PVC Pipe, Uni-Bell PVC Pipe Association

(7) Installation Guide for Ductile Iron Pipe, Ductile Iron Pipe Research Association

(8) Thrust Restraint Design for Ductile Iron Pipe, Ductile Iron Pipe ResearchAssociation

As there is normally no circulation of water in private fire mains, they require greaterdepth of covering than do public mains. Greater depth is required in a loose gravelly soil(or in rock) than in compact soil containing large quantities of clay. The recommendeddepth of cover above the top of underground yard mains is shown in Figure A.10.4.1.

Figure A.10.4.1 Recommended Depth of Cover (in feet) Above Top ofUnderground Yard Mains.

Statement of Problem and Substantiation for Public Input

Modify Figure A.10.4.1. This program does not allow for easy manipulation of figures so I will explain the change in the substantiation. Currently there are gradient lines separating the bury depths (IE: 2.5-3, 3.5-4, 4.5-5, etc. However, tehre are no clear lines drawn for the following separations (3'-3.5', 4'-4.5', 5'-5.5', 6'-6.5', 7'-7.5'). Either additional lines should be drawn or the numbers north of the existing lines need to be increaded by 6".

Submitter Information Verification

Submitter Full Name:Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Submittal Date: Thu Jan 17 08:47:10 EST 2013

Copyright Assignment

I, Peter Schw ab, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

Page 103: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 75/85

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Peter Schw ab, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

Public Input No. 61-NFPA 24-2013 [ Section No. A.10.6.3.1 ]

Original Hide Markup

A.10.6.3.1

Items such as sidewalks or patios should not be included as they are no differentfrom roadways. See Figure A.10.6.3.1 .

Figure A.10.6.3.1 Riser Entrance Location.

[Replace existing figure with new Figure A.10.6.3.1]

Additional Proposed Changes

File Name Description Approved

Open Figure_A-10-6-3-1.tif New figure to replace existing Figure A.10.6.3.1

Statement of Problem and Substantiation for Public Input

The figure needs to be revised. The pipe leading up to the transition to the riser does not need to be ductile iron. Any type of acceptable underground should be permitted. This is consistent with the change to NFPA 24 last cycle to allow up to 24 inches of pipe above ground to make the transition to the riser.

Submitter Information Verification

Submitter Full Name:Roland Asp

Organization: National Fire Sprinkler Association

/TerraView/Content/24-2013.ditamap/2/C1358430430969.xml

Page 104: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 76/85

Affilliation: NFSA E&S Committee

Submittal Date: Fri May 24 16:13:28 EDT 2013

Copyright Assignment

I, Roland Asp, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Roland Asp, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1369426408592.xml

Page 105: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 77/85

Public Input No. 84-NFPA 24-2013 [ Section No. A.10.6.3.1 ]

Original Hide Markup

A.10.6.3.1

Items such as sidewalks or patios should not be included as they are no different fromroadways. See Figure A.10.6.3.1.

Figure A.10.6.3.1 Riser Entrance Location.

Statement of Problem and Substantiation for Public Input

need to provide an annular space around the lead-in piping penetrating the floor to conform with the clearance requirements in NFPA 13

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 17:27:54 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1369862874072.xml

Page 106: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 78/85

Public Input No. 62-NFPA 24-2013 [ Section No. A.10.6.4 ]

Original Hide Markup

A.10.6.4

The individual piping standards should be followed for load and bury depth,accounting for the load and stresses imposed by the building foundation.

Figure A.10.6.4 shows location where pipe joints would be prohibited.

[Revise figure as shown in proposed new Figure A.10.6.4]

Figure A.10.6.4 Pipe Joint Location in Relation to Foundation Footings.

Additional Proposed Changes

File Name Description Approved

Open Figure_A-10-6-4.tif New Figure A.10.6.4 to replace old one

Statement of Problem and Substantiation for Public Input

The figure needs to be revised. The pipe leading up to the transition to the riser does not need to be ductile iron. Any type of acceptable underground should be permitted. This is consistent with the change to NFPA 24 last cycle to allow up to 24 inches of pipe above ground to make the transition to the riser.

Submitter Information Verification

Submitter Full Name:Roland Asp

Organization: National Fire Sprinkler Association

Affilliation: NFSA E&S Committee

Submittal Date: Fri May 24 16:17:53 EDT 2013

Copyright Assignment

I, Roland Asp, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

Page 107: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 79/85

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Roland Asp, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1369426673753.xml

Page 108: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

No fittings

Acceptable pipe material

System riser

Acceptable Material

Joint restraint

F1GL'REA.I0.6.4 Pipe Joint Location in Relation to Founda· tion Footings.

Page 109: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 80/85

Public Input No. 85-NFPA 24-2013 [ Section No. A.10.6.4 ]

Original Hide Markup

A.10.6.4

The individual piping standards should be followed for load and bury depth, accounting forthe load and stresses imposed by the building foundation.

Figure A.10.6.4 shows location where pipe joints would be prohibited.

Figure A.10.6.4 Pipe Joint Location in Relation to Foundation Footings.

Statement of Problem and Substantiation for Public Input

need to provide an annular space around the lead-in piping penetrating the floor to conform with the clearance requirements in NFPA 13

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 17:29:05 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1369862945482.xml

Page 110: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 81/85

Public Input No. 63-NFPA 24-2013 [ Section No. A.10.6.5 ]

Original Hide Markup

A.10.6.5

Sufficient clearance should be provided when piping passes beneath foundations orfooters. See Figure A.10.6.5 .

Figure A.10.6.5 Piping Clearance from Foundation.

[Revise figure as shown in new Figure A.10.6.5]

Additional Proposed Changes

File Name Description Approved

Open Figure_A-10-6-5.tif New figure to replace existing A.10.6.5

Statement of Problem and Substantiation for Public Input

The figure needs to be revised. The pipe leading up to the transition to the riser does not need to be ductile iron. Any type of acceptable underground should be permitted. This is consistent with the change to NFPA 24 last cycle to allow up to 24 inches of pipe above ground to make the transition to the riser.

Submitter Information Verification

Submitter Full Name:Roland Asp

Organization: National Fire Sprinkler Association

Affilliation: NFSA E&S Committee

Submittal Date: Fri May 24 16:20:12 EDT 2013

Copyright Assignment

I, Roland Asp, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

Page 111: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 82/85

By checking this box I aff irm that I am Roland Asp, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1369426812977.xml

Page 112: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

12in. min.

System riser

Acceptable Material

J a int restraint

Acceptable pipe material

BGUREA.l0.6.5 Piping Clearance from Fotmdation.

Page 113: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 83/85

Public Input No. 86-NFPA 24-2013 [ Section No. A.10.6.5 ]

Original Hide Markup

A.10.6.5

Sufficient clearance should be provided when piping passes beneath foundations orfooters. See Figure A.10.6.5.

Figure A.10.6.5 Piping Clearance from Foundation.

Statement of Problem and Substantiation for Public Input

need to provide an annular space around the lead-in piping penetrating the floor to conform with the clearance requirements in NFPA 13

Submitter Information Verification

Submitter Full Name:John Campbell

Organization: Telgian Corporation

Submittal Date: Wed May 29 17:29:51 EDT 2013

Copyright Assignment

I, John Campbell, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am John Campbell, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1369862991266.xml

Page 114: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 84/85

Public Input No. 64-NFPA 24-2013 [ Section No. A.10.8.3 ]

Original Hide Markup

A.10.8.3

A method for providing thrust restraint is the use of restrained joints. A restrainedjoint is a special type of joint that is designed to provide longitudinal restraint.Restrained joint systems function in a manner similar to that of thrust blocks,insofar as the reaction of the entire restrained unit of piping with the soil balancesthe thrust forces.

The objective in designing a restrained joint thrust restraint system is to determinethe length of pipe that must be restrained on each side of the focus of the thrustforce. This will be a function of the pipe size, the internal pressure, the depth ofcover, and the characteristics of the solid surrounding the pipe.

The following documents apply to the design, calculation, and determination ofrestrained joint systems:

(1) Thrust Restraint Design for Ductile Iron Pipe , Ductile Iron Pipe ResearchAssociation

(2) AWWA M41, Ductile Iron Pipe and Fittings

(3) AWWA M9, Concrete Pressure Pipe

(4) AWWA M11, A Guide for Steel Pipe Design and Installation

(5) Thrust Restraint Design Equations and Tables for Ductile Iron and PVCPipe , EBAA Iron, Inc.

Figure A.10.8.3 shows an example of a typical connection to a fire protectionsystem riser utilizing restrained joint pipe.

[Revise figure as shown in new Figure A.10.8.3]

Figure A.10.8.3 Typical Connection to Fire Protection System Riser IllustratingRestrained Joints.

Additional Proposed Changes

File Name Description Approved

Open Figure_A-10-8-3.tiff New figure to replace existing Figure A.10.8.3

Page 115: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 85/85

Statement of Problem and Substantiation for Public Input

The figure needs to be revised. The pipe leading up to the transition to the riser does not need to be ductile iron. Any type of acceptable underground should be permitted. This is consistent with the change to NFPA 24 last cycle to allow up to 24 inches of pipe above ground to make the transition to the riser.

Submitter Information Verification

Submitter Full Name:Roland Asp

Organization: National Fire Sprinkler Association

Affilliation: NFSA E&S Committee

Submittal Date: Fri May 24 16:23:05 EDT 2013

Copyright Assignment

I, Roland Asp, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Roland Asp, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/24-2013.ditamap/2/C1369426985038.xml

Page 116: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

Fire

Acceptable Material

Acceptable Material

F1GUREA.l0.8.3 'I}'Pical Connection to Fire Protection Sys­tem Riser Illustrating Restrained Joints.

Page 117: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

PART 6 –

NFPA 291 PUBLIC INPUT

Page 118: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 1/3

Public Input No. 3-NFPA 291-2013 [ Section No. 3.3 ]

Original Hide Markup

3.3 General Definitions.

3.3.1 Rated Capacity.

The flow available from a hydrant at the designated residual pressure (ratedpressure), either measured or calculated.

3.3.2 Residual Pressure.

The pressure that exists in the distribution system, measured at the residualhydrant at the time the flow readings are taken at the flow hydrants.

3.3.3 Static Pressure.

The pressure that exists at a given point under normal distribution systemconditions measured at the residual hydrant with no hydrants flowing.

3.3.4 US National Grid

An alphanumeric point reference system that has been overlaid on the UniversalTransverse Mercator (UTM) numerical grid. Every modest size home in a discretearea (city) can be described using 8-digits (e.g., 1234 5678). By adding a two-letterprefix (e.g., XX 1234 5678) the location is uniquely identified regionally (state-wide).US National Grid is functionally identical to Military Grid Reference System(MGRS), used by US military and NATIO since 1949. In the case of hydrants, an8-digit coordinate would uniquely identify the location and it could be used tocalculate approximate distances, when necessary.

Statement of Problem and Substantiation for Public Input

Defines what US National Grid is and how it can benefit hydrant location information.

Related Public Inputs for This Document

Related Input Relationship

Open Public Input No. 2-NFPA 291-2013 [Chapter A] main input and definition

Submitter Information Verification

Submitter Full Name:Albert Studt

Organization: URS Federal Technical Services

Submittal Date: Wed Jan 02 15:56:44 EST 2013

Copyright Assignment

I, Albert Studt, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

Print Reload Page Close Show Cart

Page 119: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 2/3

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Albert Studt, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

Public Input No. 2-NFPA 291-2013 [ Chapter A ]

Original Hide Markup

Annex A Explanatory Material

Annex A is not a part of the recommendations of this NFPA document but isincluded for informational purposes only. This annex contains explanatory material,numbered to correspond with the applicable text paragraphs.

A.3.2.1 Authority Having Jurisdiction (AHJ).

The phrase “authority having jurisdiction,” or its acronym AHJ, is used in NFPAdocuments in a broad manner, since jurisdictions and approval agencies vary, asdo their responsibilities. Where public safety is primary, the authority havingjurisdiction may be a federal, state, local, or other regional department or individualsuch as a fire chief; fire marshal; chief of a fire prevention bureau, labor department,or health department; building official; electrical inspector; or others havingstatutory authority. For insurance purposes, an insurance inspection department,rating bureau, or other insurance company representative may be the authorityhaving jurisdiction. In many circumstances, the property owner or his or herdesignated agent assumes the role of the authority having jurisdiction; atgovernment installations, the commanding officer or departmental official may bethe authority having jurisdiction.

A.3.2.2 Listed.

The means for identifying listed equipment may vary for each organizationconcerned with product evaluation; some organizations do not recognize equipmentas listed unless it is also labeled. The authority having jurisdiction should utilize thesystem employed by the listing organization to identify a listed product.

A.4. 11.2

Consider US National Grid coordinates for Location of hydrants, in additionto any other standard description. A coordinate to a precision of eightdigits equates to an area of 10 meters square (33' x 33'). In practically allcases, this will uniquely define the hydrant. Two oordinates can also beused for distance calculations between hydrants. Example: 17R NM 38774016

A.4. 13.1

When flow test data are needed, such data should not be more than 5 years oldsince conditions in the piping and system demands can change. It is not the intentof 4.13.1 to require routine 5-year testing of each hydrant if there is no immediateneed for flow test data or if test data less than 5 years old are available from anadjacent hydrant on the same grid.

/TerraView/Content/291-2013.ditamap/2/C1357160204652.xml

Page 120: Technical Committee on Private Water Supply … Committee on Private Water Supply Piping Systems ... Technical Committee on Private Water Supply Piping Systems ... Austin L. Smith

6/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 3/3

Statement of Problem and Substantiation for Public Input

The preferred coordinate system designed for land based operations is US National Grid. It is the standard for Florida, Minnesota, FEMA, DHS, etc.and is effectively the same system used by the military since 1949. The system uses no decimals, degrees, minutes, seconds and is scalable. 3 digits equates to and area of 100 meters square and 4 digits equates to an area of 10 meters square (33 feet x 33 feet). Practically everywhere, there would be only one hydrant per 10 meter square. Using simple math the distance between hydrants can be determined. Example: Hydrant1 at 17R NM 3877 4015, Hydrant2 at 17R NM 3877 4034. If easting and northing were not the same, use Pythagoras's theorem. In this case easting is the same, 3877 - 3877 = 0, 4034 - 4015 = 19 (10s) or 190 meters. Conversion to feet is easily done. US National Grid is widely available in GPS and smart phone applications.. It can be in the hands of hydrant testers for no cost in most cases. http://www.fgdc.gov/usng http://www.mngeo.state.mn.us/committee/emprep/download/USNG/index.html Summary: a technical enhancement for location identification

Submitter Information Verification

Submitter Full Name:Albert Studt

Organization: URS Federal Technical Services

Submittal Date: Wed Jan 02 15:28:56 EST 2013

Copyright Assignment

I, Albert Studt, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and

full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem

and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby

w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this

copyright assignment.

By checking this box I aff irm that I am Albert Studt, and I agree to be legally bound by the above Copyright

Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box,

I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

/TerraView/Content/291-2013.ditamap/2/C1357158536122.xml