Technical documentation
BWL-1-A, BWL-1-l air source � BWS-1 ground source � BWW-1 ground water source
High efficiency heat pumps
2
Description: • Airsourceheatpumpsforexternalorinternalinstallationwithaheatingoutputof8,10,12or14kWforheatingwatertemperaturesupto63°Candairtemperaturesfrom-25°Cto40°C
• VariablespeedECradialfan• "WolfEasyConnectSystem"withafullywiredconnectionfromheatpumptotheWPM-1heat
pumpmanager incl.BMprogrammingmodule,5mlongcableset inthestandarddeliveryforBWL-1-I,availableasanaccessoryforBWL-1-A;maybeextendedbytheWRSWolfcontrolsystemforadditionalenergysources,e.g.solar
• Convenientcommissioningduetopre-configuredhydraulicschemesinWPM-1• Extremelyquietoperationthankstocompressorwithdoublevibrationisolation,integralflexible
corrugatedstainlesssteelpipesandnoiseattenuatingcasing• EnergyefficientDHWheatingwithoptionalECOmode• IntegralcontrolforhighefficiencyA-ratedpumpsand3-waydivertervalve• Integralelectronicallycontrolledelectricboosterheater,forheatingbackupinlinewithdemand• Negligiblepowerconsumptioninstandbymode• Integralheatmeter,canbeextendedtodisplaySPF/DPFviaelectricitymeter'sSinterface• Dischargeforinternalunitcanbeconnectedeithertotherightorleftandcanthereforebesited
inacorner• AwardedEHPAqualitylabelforall-roundguaranteeofqualityandhighestlevelofenvironmental
andconsumerprotection• AllappliancetypesmeettheBAFAsubsidyguidelinesforefficientheatpumps
Wolfhighefficiencyheatpumps• InWolfhighefficiencyheatpumps,upto80%ofheatingenergycomesfromfreenaturalenergy.
•AWolfhighefficiencyheatpumpenablesyoutomakeanactivecontributiontowardsreducingemissions,includingCO2.
• Wolfhighefficiencyheatpumpsaresuitableformonoenergeticoperationcoveringtheentireheatdemandofabuilding.
•Novaluablelivingspaceistakenupbyaboilerortankroom;noneedtostorefuel.
•Nochimneyorfluesystemrequired.
Systemscheme–internalinstallationSystemscheme–externalinstallation
WolfhighefficiencyBWL-1airsourceheatpumps
ExternalinstallationBWL-1-A
*A2/W35toEN14511(BWL-1-08)
InternalinstallationBWL-1-IWPM-1withBM
COP3.8*
Awarded EHPA quality
label
European Quality Label
for Heat Pumps
chec
k th
e va
lidity
of t
his
labe
l at w
ww
.ehp
a.or
g/Q
L
3
Specification BWL-1-A BWL-1-I
BWL-1-A BWL-1-I
CA
B
CA
B
TYPE BWL-1-08-A
BWL-1-08-I
BWL-1-10-A
BWL-1-10-I
BWL-1-12-A
BWL-1-12-I
BWL-1-14-A
BWL-1-14-I
Heatingoutput/COtoEN14511 A2/W35 kW/- 8,4/3,8 9,6/3,7 11,7/3,7 13,5/3,6 A7/W35 kW/- 8,7/4,5 9,8/4,4 11,9/4,3 13,6/4,2 A7/W45 kW/- 10,4/3,7 11,7/3,6 14,4/3,5 13,0/3,3 A10/W35 kW/- 9,9/4,7 11,1/4,6 13,8/4,5 13,7/4,5 A-7/W35 kW/- 7,5/3,3 8,5/3,2 10,4/3,1 11,3/3,0Overallheight Amm 1665 1665 1665 1665 1665 1665 1665 1665Overallwidth Bmm 1505 985 1505 985 1505 985 1505 985Overalldepth Cmm 1105 810 1105 810 1105 810 1105 810Heatingflow/heatingreturn/connection G(fem.) 1½" 1½" 1½" 1½"Unrestrictedcross-section,airducts mm - 550x550 - 550x550 - 550x550 - 550x550Soundpowerlevel(A7/W35) dB(A) 56 50 56 50 58 52 61 55Soundpressurelevel,internal,at1mdistanceaveragedaroundheatpump(intheinstallationroom)
dB(A) - 46 - 46 - 48 - 50
Soundpressurelevel,external,at1mdistanceaveragedaroundairconnections(freefield)
dB(A) 47 - 47 - 49 - 51 -
Soundpressurelevel,external,at5mdistanceaveragedaroundairconnections(freefield)
dB(A) 33 - 33 - 35 - 37 -
Soundpressurelevel,external,at10mdistanceaveragedaroundairconnections(freefield)
dB(A) 27 - 27 - 29 - 31 -
Temperature,heatingwateroperatinglimits °C +20to+63 +20to+63 +20to+63 +20to+63Max.temp.ofheatingwaterat-7°Coutsidetemp. °C +55 +55 +55 +55Temperature,airoperatinglimitsin°C °C -25to+40 -25to+40 -25to+40 -25to+40Refrigeranttype/charge(hermeticallysealedrefrigerantcircuit) -/kg R407C/3.4 R407C/4.4 R407C/4.5 R407C/5.1Maximumoperatingpressure,refrigerantcircuit bar 30 30 30 30Refrigerantoil FV50S FV50S FV50S FV50SWaterflowrate:minimum(7K)/nominal(5K)/maximum(4K)2)
l/min 23/32/40 25.5/35.6/44.6 30.9/43.2/54.2 35.6/50/62.3
Heatpumppressuredropatnominalwaterflowrate
mbar 110 124 165 240
AirflowrateatamaximumexternalpressureforA2/W35toEN14511
m³/h 3200 3200 3400 3800
Maximumexternalpressure(adjustable) Pa - 20-50 - 20-50 - 20-50 - 20-50Output,el.boosterheater,3phases,400V kW 1to6 1to6 1to6 1to8Max.currentdrawn,el.boosterheater A 9.6 9.6 9.6 12.8Maximumpowerconsumption/compressorcurrentwithinapplicationlimits
kW/A 3.92/7.3 4.56/8.0 5.59/10.0 6.46/11.6
Powerconsumption/currentdrawn/cosφforA2/W35toEN14511
kW/A/- 2.21/4.5/0.71 2.59/4.7/0.80 3.16/5.9/0.77 3.75/6.9/0.78
Start-upcurrent(softstart) A 26 31 37 39Max.numberofcompressorstartsperhour 1/h 3 3 3 3TypicalBWL-1powerconsumptioninstandbyLP(lowpower) W 5.8 5.8 5.8 5.8IPrating IP IP24 IP24 IP24 IP24Weight1) kg 202 217 225 242 226 244 237 255Electricalconnection/MCB(omnipolar) Compressor 3~PE/400VAC/50Hz/10A(C) 3~PE/400VAC/50Hz/16A(C)
El.boosterheater 3~PE/400VAC/50Hz/10A(B)3~PE/400VAC/50Hz
/16A(B) Controlvoltage 1~NPE/230VAC/50Hz/10A(B)
1)AdditionalcasingcoversforBWL-1-08A/-10A/-12A/-14Aaresuppliedseparately(weight:37kg).2)Theflowrateshouldnotfallbelowthenominalflowrateinordertoensuretheheatpumpoperateswithhighenergyefficiency.Theinformationprovidedinthistableassumesacleanheatexchanger.
4
WolfhighefficiencyBWS-1groundsourceheatpumps
Description: • Groundsourceheatpumpsforusingnaturalenergythroughgeothermalcollectorsorgeothermalprobeswithaheatingoutputof6,8,10,12or16kW;forheatingwatertemperaturesupto63°Candamin.brinetemperatureof-5°C
• Smallfootprintduetocompactdesign
• Clearappliancelayout;alltheessentialcomponentsaccessiblefromthefront
• "WolfEasyConnectSystem"withafullywiredcableset(4mlong)fromheatpumptotheWPM-1heatpumpmanagerincl.BMprogrammingmodule,maybeextendedbytheWRSWolfcontrolsystemforadditionalenergysources,e.g.solar
• FittedwithenergyefficienthighefficiencyA-ratedpumpsforheatingcircuitandbrinecircuitand3-waydivertervalveforDHWcylinderheating
• EnergyefficientDHWheatingwithoptionalECOmode
• Extremelyquietoperationthankstocompressorwithdoublevibrationisolation,integralhydrauliccompensatorsandnoiseattenuatingcasing
• Integralelectronicallycontrolledelectricboosterheater,forheatingbackupinlinewithdemand
• Integralheatmeter,canbeextendedtodisplaySPF/DPFviaelectricitymeter'sSinterface• CanbecombinedwithCEW-1-200DHWcylindertoformaheatingcentre
• Safetyassembliesfortheheatingandbrinecircuit
• ExtensionwithBKMcoolingmoduleforpassivecooling(option)
• AwardedEHPAqualitylabelforall-roundguaranteeofqualityandhighestlevelofenvironmentalandconsumerprotection
• AllappliancetypesmeettheBAFAsubsidyguidelinesforefficientheatpumps
Systemscheme–geothermalcollector Systemscheme–geothermalprobe
COP4.7*
LayoutBWS-1
InternalinstallationBWS-1
*B0/W35toEN14511WPM-1withBM
Brinecircuitsafetyassembly
Heatingcircuitsafetyassembly
Evaporator
Brinecircuitpump
Brinepressuresensor
Brineinlettemperaturesensor
Expansionvalve
Heatingcircuitpump
Scrollcompressor
BDFvalve,brinecircuitBDFvalve,heatingcircuit
Electricboosterheater
Heatingcircuitpressuresensor
Heatingcircuitflowsensor
Flowratesensor
Condenser
3-waydivertervalveheating–DHW
HPpressureswitch
LPpressureswitch
Hotgastemperature
Brineoutlettemperaturesensor
Suctiongastemperature
Awarded EHPA quality
label
European Quality Label
for Heat Pumps
chec
k th
e va
lidity
of t
his
labe
l at w
ww
.ehp
a.or
g/Q
L
5
Specification BWS-1
A
C B
= = = = =
5x95
665
Brineinlet
Heatingflow
DHWreturn
Brineoutlet
Heatingreturn
DHWflow
TYPE BWS-1-06 BWS-1-08 BWS-1-10 BWS-1-12 BWS-1-16Heatingoutput/COPtoEN255 B0/W35 kW/- 5,9/4,7 8,4/4,7 10,8/4,7 12,0/4,7 16,8/4,6 B0/W55 kW/- 5,3/2,8 7,4/2,8 9,2/2,9 10,5/2,8 15,8/2,8 B5/W35 kW/- 6,9/5,3 9,7/5,4 12,3/5,4 13,8/5,3 19,9/5,3 B-5/W45 kW/- 4,8/3,1 6,8/3,2 8,6/3,1 9,7/3,1 14,7/3,2Overallheight Amm 740 740 740 740 740Overallwidth Bmm 600 600 600 600 600Overalldepth Cmm 650 650 650 650 650Heatingflow/return,DHWflow/return,brineinlet/outlet
G(male) 1½" 1½" 1½" 1½" 1½"
Soundpowerlevel dB(A) 41 42 42 43 43Soundpressurelevelat1mdistanceaveragedaroundheatpump(insidetheroom)
dB(A) 39 40 40 41 41
Temperature,heatingwateroperatinglimits °C +20to+63 +20to+63 +20to+63 +20to+63 +20to+63Temperature,brineoperatinglimits °C -5to+20 -5to+20 -5to+20 -5to+20 -5to+20Refrigeranttype/charge(hermeticallysealedrefrigerantcircuit) -/kg R407C/1.8 R407C/2.0 R407C/2.25 R407C/2.8 R407C/3.1Maximumoperatingpressure,refrigerantcircuit bar 30 30 30 30 30Refrigerantoil FV50S FV50S FV50S FV50S FV50SWaterflowrate:minimum(7K)/nominal(5K)/maximum(4K)1)
l/min 12.1/16.6/21.6 17.2/24/30 22.0/30.8/38.3 24.6/34.1/43.3 34.4/48.3/60
ResidualheadatDT5K mbar 580 510 450 480 4403-wayvalveforDHWheatingcircuit Integral Integral Integral Integral IntegralHighefficiencyheatingcircuitpump WiloYonosPara
25/7,5WiloYonosPara
25/7,5WiloYonosPara
25/7,5WiloStratosPara
25/1-8WiloStratosPara
25/1-8Brineflowrate:minimum(5K)/nominal(4K)/maximum(3K)
l/h 15/18.3/25 20/25.8/34.3 26.6/33.3/44.1 29.1/36.6/48.3 40.8/50.8/67.8
ResidualheadatDT4K(30%brine/0°C) mbar 480 440 410 550 440Minimumbrineconcentration/frostprotection %/°C 25/-13 25/-13 25/-13 25/-13 25/-13Highefficiencybrinecircuitpump WiloStratosPara
25/1-7WiloStratosPara
25/1-7WiloStratosPara
25/1-7WiloStratosPara
25/1-8WiloStratosPara
25/1-8Output,el.boosterheater,3phases,400V kW 1to6 1to6 1to6 1to6 1to6Max.currentdrawn,el.boosterheater A 9.6 9.6 9.6 9.6 9.6Maximumpowerconsumption/compressorcurrentwithinapplicationlimits
kW/A 2.28/4.2 3.2/5.8 3.85/7.0 4.71/8.4 6.53/11.7
Powerconsumption/currentdrawncos φforB0/W35
kW/A/-
1.26/2.5/0.72 1.79/3.2/0.80 2.3/4.4/0.76 2.55/4.6/0.79 3.65/6.9/0.76
Powerconsumptionofheatingcircuitpumpatnominalflowrate
W 45 55 60 100 110
Powerconsumptionofbrinepumpatnominalflowrate
W 55 60 65 110 120
Directstart-upcurrent/softstart A 27/- -/21 -/26 -/31 -/39
Max.noofcompressorstarts 1/h 3 3 3 3 3
TypicalBWS-1powerconsumptioninstandbyLP(lowpower) W 5.8 5.8 5.8 5.8 5.8IPrating IP IP20 IP20 IP20 IP20 IP20Weight kg 141 145 149 169 174Powersupply/MCB(omnipolar)
3~PE/400VAC/
50Hz/16A(C) Compressor 3~PE/400VAC/50Hz/10A(C) El.boosterheater 3~PE/400VAC/50Hz/10A(B) Controlvoltage 1~NPE/230VAC/50Hz/10A(B)
1)Theflowrateshouldnotfallbelowthenominalflowrateinordertoensuretheheatpumpoperateswithhighenergyefficiency.Theinformationprovidedinthistableassumesacleanheatexchanger.
6
• Watersourceheatpumpsforusingnaturalenergythroughwellwaterwithaheatingoutputof7,11,13,15or21kW;forheatingwatertemperaturesupto63°Candawellwatertemperatureof7–22°C
• IntermediateheatexchangerconsistingofNI-solderedstainlesssteelpanels,diffusiontightinsulated
• Smallfootprintduetocompactdesign
• Clearappliancelayout;alltheessentialcomponentsaccessiblefromthefront
• „WolfEasyConnectSystem“withafullywiredcableset(4mlong)fromheatpumptotheWPM-1heatpumpmanagerincl.BMprogrammingmodule,maybeextendedbytheWRSWolfcontrolsystemforadditionalenergysources,e.g.solar
• FittedwithenergyefficienthighefficiencyA-ratedpumpsforheatingcircuitandbrinecircuitand3-waydivertervalveforDHWcylinderheating
• EnergyefficientDHWheatingwithoptionalECOmode
• Extremelyquietoperationthankstocompressorwithdoublevibrationisolation,integralhydrauliccompensatorsandnoiseattenuatingcasing
• Integralelectronicallycontrolledelectricboosterheater,forheatingbackupinlinewithdemand
• Integralheatmeter,canbeextendedtodisplaySPF/DPFviaelectricitymeter’sSinterface• CanbecombinedwithCEW-1-200DHWcylindertoformaheatingcentre
• Safetyassembliesfortheheatingandbrinecircuit
• ExtensionwithBKMcoolingmoduleforpassivecooling(option)
• AllappliancetypesmeettheBAFAsubsidyguidelinesforefficientheatpumps
Systemscheme–extractionandabsorbingwell
WolfhighefficiencyBWW-1groundwatersourceheatpumps
LayoutBWW-1
InternalinstallationBWW-1
*W10/W35toEN14511WPM-1withBM
Brinecircuitsafetyassembly
Heatingcircuitsafetyassembly
Evaporator
Brinecircuitpump
Brinepressuresensor
Brineinlettemperaturesensor
Expansionvalve
Heatingcircuitpump
Scrollcompressor
BDFvalve,brinecircuitBDFvalve,heatingcircuit
Electricboosterheater
Heatingcircuitpressuresensor
Heatingcircuitflowsensor
Flowratesensor
Condenser
3-waydivertervalveheating–DHW
HPpressureswitch
LPpressureswitch
Hotgastemperature
Brineoutlettemperaturesensor
Suctiongastemperature
COP5,6*
Description:
BWM
7
TYPE BWW-1-07 BWW-1-11 BWW-1-13 BWW-1-15 BWW-1-21: BWS-1-06 +
BWM-SBWS-1-08 +
BWM-SBWS-1-10 +
BWM-SBWS-1-12 +
BWM-LBWS-1-16 +
BWM-LHeatingoutput/COPtoEN14511 W10/W35 kW/- 7,1/5,4 10,5/5,6 13,3/5,6 15,0/5,5 20,8/5,5 W10/W45 kW/- 6,9/4,2 10,0/4,4 12,2/4,3 14,0/4,3 19,3/4,3 W10/W55 kW/- 6,2/3,2 9,3/3,3 11,5/3,2 13,5/3,3 17,0/3,3OverallheightBWS-1 Amm 740 740 740 740 740OverallwidthBWS-1 Bmm 600 600 600 600 600OveralldepthBWS-1 Cmm 650 650 650 650 650OverallheightBWM Dmm 355 355 355 545 545OverallwidthBWM Emm 245 245 245 245 245OveralldepthBWM Fmm 200 200 200 200 200Heatingflow/return,DHWflow/return,brineinlet/outlet G(male) 1½“ 1½“ 1½“ 1½“ 1½“ConnectionsofBWM G(AG) 1¼“ 1¼“ 1¼“ 1¼“ 1¼“Soundpowerlevel dB(A) 41 42 42 43 43Soundpressurelevelat1mdistanceaveragedaroundheatpump(insidetheroom)
dB(A) 39 40 40 41 41
Max.operatingpressureheating/brine/wellcircuit bar 3/3/3 3/3/3 3/3/3 3/3/3 3/3/3Temperature,heatingwateroperatinglimits °C +20bis+63 +20bis+63 +20bis+63 +20bis+63 +20bis+63Temperature,wellwateroperatinglimits °C +7bis+22 +7bis+22 +7bis+22 +7bis+22 +7bis+22Refrigeranttype/charge(hermeticallysealedrefrigerantcircuit) -/kg R407C/1,8 R407C/2,0 R407C/2,25 R407C/2,8 R407C/3,1Maximumoperatingpressure,refrigerantcircuit bar 30 30 30 30 30Refrigerantoil FV50S FV50S FV50S FV50S FV50SBrinecapacityinBWS-1withBWM Ltr. 4,7 5,2 5,7 7,3 7,8Waterflowrate:minimum(7K)/nominal(5K)/maximum(4K)1)
Ltr./min 14,6/20,3/25,4 21,4/30,1/37,6 27,3/38,1/47,6 30,7/43,0/53,7 42,6/59,6/74,5
ResidualheadatDT5K mbar 530 430 340 420 1503-wayvalveforDHWheatingcircuit integriert integriert integriert integriert integriertHighefficiencyheatingcircuitpump WiloYonosPara
25/7,5WiloYonosPara
25/7,5WiloYonosPara
25/7,5WiloStratosPara
25/1-8WiloStratosPara
25/1-8Residualheadforpipeworkbrinecircuit mbar 160(42) 200(42) 210(42) 140(58) 140(58)(forflowratel/min) %/°C 25/-13 25/-13 25/-13 25/-13 25/-13Minimumbrineconcentration/frostprotectionuptoHighefficiencypump(EEI<0,23)brinecircuit
WiloStratosPara25/1-8
WiloStratosPara25/1-8
WiloStratosPara25/1-8
WiloStratosPara25/1-8
WiloStratosPara25/1-8
NominalflowrateatDT4K Ltr./min 27 42 52 58 82PressuredropwellwaterinBWMatnominalflowrate mbar 24 53 85 134 257Output,el.boosterheater,3phases,400V kW 1bis6 1bis6 1bis6 1bis6 1bis6Max.currentdrawn,el.boosterheater A 9,6 9,6 9,6 9,6 9,6Maximumpowerconsumption/compressorcurrentwithinapplicationlimits
kW/A 2,89/4,2 3,2/5,8 3,85/7,0 4,71/8,4 6,53/11,7
Powerconsumption/currentdrawncos φforB0/W35 kW/A/- 1,35/2,5/0,75 1,85/3,2/0,81 2,3/4,4/0,76 2,64/4,7/0,79 3,79/7,0/0,81Powerconsumptionofheatingcircuitpumpatnominalflowrate
W 45 55 60 100 110
Powerconsumptionofbrinepumpatnominalflowrate
W 55 60 65 110 120
Directstart-upcurrent/softstart A 27/- -/21 -/26 -/31 -/39
Max.noofcompressorstarts 1/h 3 3 3 3 3
TypicalBWS-1powerconsumptioninstandbyLP(lowpower) W 5,8 5,8 5,8 5,8 5,8IPrating IP IP20 IP20 IP20 IP20 IP20Weight kg 151 156 160 185 190Powersupply/MCB(omnipolar)
3~PE/400VAC/
50Hz/16A(C) Compressor 3~PE/400VAC/50Hz/10A(C)
El.boosterheater 3~PE/400VAC/50Hz/10A(B)
Controlvoltage 1~NPE/230VAC/50Hz/10A(B)1)Theflowrateshouldnotfallbelowthenominalflowrateinordertoensuretheheatpumpoperateswithhighenergyefficiency.Theinformationprovidedinthistableassumesacleanheatexchanger.
D
E
F
BWS-1 BWM
A
C B
= = = = =
5x95
665
Brineinlet
Heatingflow
DHWreturn
Brineoutlet
Heatingreturn
DHWflow
Specification BWW-1
8
Controlunit
WPM-1 heat pump manager with BM programming module(incl. outside temperature sensor)
• Roomtemperature-dependent/weather-compensatedtemperaturecontrollerwithtimeprogramsforcentralandDHWheatingforregulatingoneheatingcircuit,onecircuitwithmixer,andDHWheating
• Flexiblewallmounting• Fullywiredelectricalconnectionfromtheheatpumpto
theWPM-1with"WolfEasyConnectSystem"• Theentiresystemcanbedisconnectedfromthepowersupplywithasinglemainsisolatorin
theWPM-1• Easycommissioningduetopre-configuredhydraulicschemes• Heatmeter• SPF(SeasonalPerformanceFactor)displayplusDPF(DailyPerformanceFactor)displaypossible
throughconnectionofthepulsesignalfromtheon-siteelectricitymeterwithSinterface• ProgrammableinputforDHWcirculationkey,HTG/DHWblock,externaldemand(ON/OFF,0-10V)• ProgrammableoutputforDHWcirculationpump(timecontrolorpushbutton),alarmoutput,
swimmingpoolheatingpump• Floatingcontactforstartingasecondheatsource• Acousticalarm• eBUSinterface
2-w
ire e
BUS
conn
ecti
on
MM mixer module
• Extensionmoduleforregulatingonemixercircuit
• Weather-compensatedflowtemperaturecontrol• Easycontrollerconfigurationbyselectingoneof
thepresetsystemversions• BMprogrammingmodulecanbeclippedintothe
boilerorextendedasaremotecontrolwithwallmountingbase
• Rast5connectiontechnology• Incl.flowtemperaturesensor
1 ... 7
SM1 solar module
• Extensionmoduleforregulatingonesolarcircuit• InconjunctionwithWolfboilers,greaterenergysavingsthrough
intelligentcylinderreheating,i.e.blockingcylinderreheatingwhenthereissufficientsolarenergy(solarboilerstop)
• Temperaturedifferentialcontrolforoneheatconsumer• Maximumcylindertemperaturelimit• Displayofthesetandactualvaluesonthe
BMprogrammingmodule• Integralhoursrunmeter• Optionalconnectionofheatmeters• Rast5connectiontechnology• Incl.collectorsensorandcylindersensor,eachwithsensorwell
9
Controlunit2-
wire
eBU
S co
nnec
tion
Radio clock (DCF77 signal) with outside temperature sensorforautomatictimeadjustment.
Wireless remote control(onlyinconjunctionwithareceiverforwirelessoutsidetemperaturesensorandremotecontrol)Onewirelessremotecontrolpermixercircuit.
Wireless outside temperature sensor(onlyinconjunctionwithareceiverforwirelessoutsidetemperaturesensorandremotecontrol,partno.2744209).
Wireless receiver for wireless outside temperature sensorand wireless remote controlincl.radioclock(DCF77signal).
Pleaserefertothepricelistforfurtheraccessories.
SM2 solar module
• Extensionmoduletocontrolasolarthermalsystemwithupto3cylindersand2collectorarrays,incl.1collectorsensorand1cylindersensor,eachwithsensorwell
• Easycontrollerconfigurationbyselectingoneofthepresetsystemversions
• InconjunctionwithWolfboilers,greaterenergysavingsthroughintelligentcylinderreheating,i.e.blockingcylinderreheatingwhenthereissufficientsolarenergy(solarboilerstop)
• Capturingtheamountofheat• Displayofthesetandactualvaluesonthe
BMprogrammingmodule• eBUSinterface• Rast5connectiontechnology
Cascade module KM
• Extension module for cascade configuration of up to five heat pumps including electric heating
• Extension module for cascade configuration of up to four heat pumps in combination with an additional heat source (i.e. CGB-2 or COB)
• Optional automatic changeover to the additional heat source for shw preparation
• Automatic changeover to the additional heat source when value falls below the adjusted bivalence point
• Automatic changeover from heat pump to additional heat source during lockout period through electric supply company
10
Heatpumpaccessories
CEW-1-200DHWcylinder• DimensionsanddesignmatchedtotheWolfheatpumprange•CanbeinstalledincombinationwithBWS-1-06/08/10stackedorsidebysideasaheating
centre.CanbecombinedsidebysidewithBWL-1-08/10• CanbeinstalledasaHydrotowerincombinationwiththeCPM-1-70/7buffermodule• Protectiveanodeaccessiblefromthefront;interiorwithspecialenamelcoating• RigidPUfoamthermalinsulationforlowestradiationlosses• HighlyefficientinternalindirectdualcoilforconvenientDHWheating
DHW cylinder CEW-1-200Height 1290mmWidth 600mmDepth 650mmCapacity 180lOperatingpressure 10barIndirectcoilsurfacearea 2.3m²Heatingconnection G1½"maleWeight 147kg
BWS-1andCEW-1-200sidebyside
BWS-1heatingcentrewithCEW-1-200stacked
11
CPM-1-70buffermodule• Fullyplumbedandwiredasseparatingcylinder(functionslikealowlossheader)orcylinderinseries• CPM-1-70/7canbeinstalledasaHydrotowerincombinationwiththeCEW-1-200DHWcylinder• RigidPUfoamthermalinsulationforlowestradiationlosses• HighefficiencyA-ratedheatingcircuitpumpalreadyfitted• Safetyassemblywiththermalinsulation• 3-wayvalveforDHWheatingalreadyfitted• 4mconnectingcabletotheWPM-1heatpumpmanager
CPM-1-70/7(7mpump)forBWL-1-08,BWL-1-10CPM-1-70/8(8mpump)forBWL-1-12
Buffer module CPM-1-70Height 740mmWidth 600mmDepth 650mmCapacity 70lOperatingpressure 3barConnections G1½"maleWeight 62kg
BWL-1-10-AwithCPM-1-70/7andCEW-1-200Hydrotower
BWL-1-10-IwithadjacentCPM-1-70/7andCEW-1-200Hydrotower
Heatpumpaccessories
12
DHW cylinder Type SEW-1 300 400Cylindercapacity l 288 375Coldwaterconnection Amm 55 55Centralheatingreturn Bmm 222 222Sensorwell Cmm 656 791DHWcirculation Dmm 786 921Centralheatingflow Emm 886 1156DHWconnection Fmm 1229 1586Overallheight Gmm 1310 1660Serviceflange Hmm 277 277Diameterincl.thermalinsulation Imm 705 705Heatingwater(primary) bar/°C 10/110 10/110DHW(secondary) bar/°C 10/95 10/95Coldwaterconnection Rp 1¼" 1¼"Centralheatingreturn female 1¼" 1¼"DHWcirculation female ¾ ¾Centralheatingflow female 1¼" 1¼"DHWconnection Rp 1¼" 1¼"Indirectcoilsurfacearea m² 3.5 5.1Coilcontent l 27 39Weight kg 134 185
• SEW-1-300forheatpumpswithapproximateheatingoutputofupto15kWforaDHWdraw-offrateofupto367litresat40°C
SEW-1-400forheatpumpswithapproximateheatingoutputofupto20kWforaDHWdraw-offrateofupto482litresat40°C
• Internalindirectdualcoilforshortheat-uptimesandconvenientDHWheating
• HighlyeffectiverigidPUfoamthermalinsulationbelowthefoiljacketforlowheatlosses;silver
• Theinteriorofthecylinderisprotectedbyaspecialenamelcoatingandaprotectivemagnesiumanode
• Inspectionandcleaningaperturesforeasymaintenance
SEW-1DHWcylinder
A
B
CD
E
FG
H
I
• Uptoapprox.12kWheatingoutput;highlyefficientinternalindirectdualcoilforconvenientDHWheating
• Additionaldualcoilforusewithsolar
• HighlyeffectiverigidPUfoamthermalinsulationbelowthefoiljacketforlowheatlosses;silver
• Theinteriorofthecylinderisprotectedbyaspecialenamelcoatingandaprotectivemagnesiumanode
• Inspectionandcleaningaperturesforeasymaintenance
SEM-1W-360DHWcylinderforadditionalconnectionofsolarcollectors
Solar DHW cylinder Type SEM-1W 360Cylindercapacity l 360Coldwaterconnection Amm 55Heating/solarreturn Bmm 606/221Heating/solarcylindersensor Cmm 965/385DHWcirculation Dmm 860Heating/solarflow Emm 1146/470DHWconnection Fmm 1526Electricboosterheater(opt.) Gmm 540Thermometerconnection Hmm 1400Overallheight Imm 1630Diameterincl.insulation Jmm 705Serviceflange Lmm 277Heatingwater(primary) bar/°C 10/110DHW(secondary) bar/°C 10/95Coldwaterconnection Rp 1¼"Centralheatingreturn female 1¼"DHWcirculation female ¾"Centralheatingflow female 1¼"DHWconnection Rp 1¼"Indirectcoilsurfacearea(heating) m² 3.2Solarindirectcoilsurfacearea m² 1.3Indirectcoilcontent(heating) l 27Solarindirectcoilcontent l 11Weight kg 182
Heatpumpaccessories
13
HeatpumpaccessoriesSPU-1-200buffercylinderforoptimisingheatpumpruntimes
• Steelbuffercylinderwith200litrewatercapacity
• Operationasaseparatingcylinderoracylinderinseriesforheatingwater
• HighlyeffectiverigidPUfoamthermalinsulationbelowthefoiljacketforlowheatlosses;silver
• Five1½"femaleconnectionsforheatingwaterandelectricboosterheater
• Boilerdrain&fillvalveandsensorwellalreadyfitted
Buffer cylinder Type SPU-1 200Cylindercapacity l 200Drainandfillconnection Amm 85Heatingwaterconnection Bmm 256Sensorwell,sensor/thermostat Cmm 358Electricboosterheater(max.6kW) Dmm 460Heatingwaterconnection Emm 910Airventvalve/safetyvalve Fmm 1140Overallheight Gmm 1140Diameterincl.thermalinsulation Hmm 610Max.operatingpressure bar 3Max.operatingtemperature °C 95Heatingwaterconnection(4pce) female 1½"Electricboosterheater female 1½"Sensor/thermostat female ½"BDFvalve female ½"Airventvalve/safetyvalve female 1"Weight kg 48A
B
C
D
E
F/G
H
(furthercylinderscanbefoundinthe"Cylindersystems"documentation)
14
BKMcoolingmodule• PreassembledunitforpassivecoolingwithBWS-1-06/08/10/12/16groundsourceheatpump
• Utilisationofthecooltemperaturesundergroundinsummerbymeansofgeothermalprobes
• Mostaffordableandenvironmentallyresponsiblewaytocool,asitrequiresnocompressoroperation
• Hightransferrateduetolargeheatexchangersurfacearea
Heatpumpaccessories
Nominal cooling output at B5 / W20 (2,3 m3/h - 1,9 m3/h)
kW 19
Coolingoutputifheatingandcoolingsourcehavebeendesignedforheating:
withBWS-1-06 kW ca.2
withBWS-1-08 kW ca.3
withBWS-1-10 kW ca.3
withBWS-1-12 kW ca.4
withBWS-1-16 kW ca.5
Height mm 401
Width mm 498
Depth mm 188
Weight kg 16
Threadedconnections:
Heatinginlet,externalthread G 11/4“
Heatingoutlet,externalthread G 11/4“
Brineinlet,internalthread Rp 11/4“
Brineoutlet,internalthread Rp 11/4“
Max.permiss.pressureheating/coolingcircuit bar 3
Max.permiss.Pressurebrinecircuit bar 3
Pressuredropheating/coolingcircuitat1,9m³/h mbar 43
Pressuredropbrinecircuitwithcoolingoperationat2,3m³/h mbar 90
Pressuredropbrinecircuitwithheatingoperationat2,3m³/h mbar 37
Permiss.temperaturerangeheating/coolingcircuit °C 3-110
Permiss.temperaturerangebrinecircuitincoolingoperation °C 3-25
Permiss.temperaturerangebrinecircuitinheatlingoperation °C 2-25
Powerconsumption VA 0-5
Thecoolingmoduleisnotapprovedforusewithgeothermalcollectors(surfacecollectors),asthesoilriskstobedriedoutasaconsequenceofunfavourablesoilstructure.Thismaycausealockoutofthecontacttothecollector.
Attention
15
WolfhighefficiencyheatpumpStandard delivery/accessories Partofstandarddelivery
AccessoryBWL-1-
..ABWL-1-
..IBWS-1 BWW-1
WPM-1heatpumpmanagerforwallmounting(alwaysessential)
IntermediateheatexchangerBWM-1 - - -
Controlledelectricboosterheater6kW(8kWforBWL-1-14)
Rotatingfieldandphasemonitor
Electronicallycontrolledsoftstartforcompressor
8/10/12/16kW
11/13/15/21kW
Heatmeter
CEW-1-200DHWcylinder;capacity180litresupto10kW
CPM-1-70buffermodulewithhighefficiencyheatingcircuitpumps,3-waydivertervalveforDHWheating,DHWassemblyandsafetyassembly
- -
DHWdivertervalve
HighefficiencyA-ratedheatingcircuitpump
HighefficiencyA-ratedbrinecircuitpump - -
Connectionsetforexpansionvesselwithcapvalveforheating
Heatingsafetyassembly(safetyvalve,pressuregauge,autom.airventvalve)
Brinesafetyassembly - -
Manualheatingairventvalve
Heatingoverflowvalve
Flexibleconnectionset,heating
Flexibleconnectionset,brine - - -
SEW-1-300DHWcylinder,300litrecapacity
SEW-1-400DHWcylinder,400litrecapacity
SEM-1W-360DHWcylinder,360litrecapacity
SPU-1-200buffercylinder,200litrecapacity
SPU-2buffercylinder(500/800/1000/1500)
BSP-W1000/BSP-W-SL1000stratificationcylinderwithfreshwatermoduleforsolarDHWheatingandcentralheatingbackup
Airduct(shortorlong) - - -
Airductbend - - -
Airductbezel - - -
Weathergrille - - -
Guardgrille - - -
Airductsealingtapeset - - -
Powerandcontrolcables("WolfEasyConnectSystem") / /
Sensorformixer,cylinderorbuffer
Brinedistributor -
Brineconcentrate20litre - - -
Brineconcentrate3litre - - -
BKMcoolingmodule - -
Titel Dokumentation Wärmepumpe_Umschlag 11.06.13 15:14 Seite 2
2014
/11G
BSu
bjec
ttomod
ifica
tions
Wolf GmbH, PO Box 1380, D-84048 Mainburg, Tel.: +49 87 51 / 74-0, Fax: +49 87 51 / 74-1600, Internet: www.wolf-heiztechnik.de
Part-No.: 48 00 556
The extensive equipment range of the system supplier Wolf offers the ideal solution for commercial and industrial buildings, innew build and modernisation projects alike. The range of Wolf control units can meet any demand for heating convenience.All equipment is easy to operate and works with high energy efficiency and reliability. Photovoltaic and solar thermalsystems can be quickly integrated into existing systems. Wolf equipment is easily and quickly installed and maintained.
The competent brand for energy saving systems