We have done this technical data guide to enable you to choose between our standard solutions and optionals. The guide is divided in four nominal evaporation temperatures of -12ºC, -20ºC, -30ºC and -40ºC ranges. Each one is a separated guide to make easier to work with them. Ask for it!

TRANSCRIPT

Page 1: Technical Guide for Screw Compressor Packages easy definition HX -40
Page 2: Technical Guide for Screw Compressor Packages easy definition HX -40

INDEX

GENERAL CHARACTERISTICS 3

Motor compressor unit 3

Identification code of the unit. 4

Description of the components 5

Mechanical elements as optionals 9

Electrical elements as options

TECHNICAL DATA AND PERFORMANCE OF THE UNIT 12

Technical data of the standard unit 12

Performance of the unit with nominal Vi 14

Performance of the unit with nominal Vi and fitted with condensing high pressure (apc) as

optional 25

How to select the motor size 36

Sound levels 48

Auxiliary data charts 50

OPERATING AREA 52

HOW TO SELECT A UNIT 53

Example nº 1 of how to select a unit 53

Example nº 2 of how to select a unit 54

DIMENSIONS AND CONNECTION POINTS 57

2

Page 3: Technical Guide for Screw Compressor Packages easy definition HX -40

GENERAL CHARACTERISTICS

Motor compressor unit.

The new version of motor compressors groups has been designed in order to meet the requirements of the medium-high

power of the industrial refrigeration installations.

These motor compressors groups use NH3 as refrigerant, which is high energetically efficient and environmentally

friendly. They can be installed inside the rooms (machine room).

The products range is divided in ten sizes with a nominal refrigeration power range from 40 to 220 kW. The units are

fitted with the standard equipment with the possibility of adding a wide range of option items, which allows us to adapt

our products to the requirements of the different designs of installations.

Each unit is fitted with the following standard equipment: a screw compressor XRV; an electric motor IP23; an

horizontal oil separator; a discharge line fitted with manual valve and check valve; a suction line fitted with filter ( in

the four smallest units inside the compressor), a manual valve and a check valve; an oil circuit fitted with an oil pump

and an oil cooler by thermosyphon. These main elements will be delivered together with an oil charge.

The superfeed system is a very important option, because it increases considerably the efficiency of the unit energy.

All our units are factory aligned and with the oil circuits previously tested, in order to allow a quick and safe

installation.

Identification code of the unit.

Find below the description of the nomenclature, made of a sequence of alphanumeric characters that is used to identify

the groups and their option items.

3

Superfeed option s : NH3 superfeed

scr : NH3 superfeed, + regulation valve.

Group type GMT HX -40 Motor compressor group XRV, nominal evaporating temperature -40 ºC

Other options

Options for control panel-board Bdc : field bus cc : control panel-board with Twido ccs : control panel-board with ET200 ccs+: control panel-board with S7-300

Options for oil cooler eaw : cooling oil by water eai : cooling oil by injected NH3

Options for motor mcv : motor, activated by a variable speed drive up to 3000 rpm. m+ : oversized motor. __hz: motor, activated by a variable frequency drive > 50 hz

Units sizes 40,60,70,90,110,130,180,200,220

GMT HX 130 -40 s mcv eaw cc dcc pam apc tra

Page 4: Technical Guide for Screw Compressor Packages easy definition HX -40

Description of components.

1.- Compressor. It is an oil flooded type, rotary and positive-displacement machine, fitted with a continuous capacity

control.The main characteristic is that it doesn´t need a oil pump to operate. The compression process is made by a

housing and a gearing set, which consists on two helicoidal type rotors (a four lobes male rotor and a six holes female

rotor). This gearing set allows the

gas to go from a suction door to a

reducer size discharge door. In all

units the volumetric relation can be

easily modified between 2,6-5,0

modifying the discharge section.

2.- Electric motor. It is a

triphasic, low voltage machine,

fitted with: a squirrel-cage rotor, an

internal refrigeration system 400 V,

50 Hz, a class B insulation, an IP23

protection device according to the

standard EN 60034 - Part V,

construction shape according DIN

IEC 34, IM B3, an IP55 protection

device of the terminal box.

3.- Oil separator. It is a

receiver, built according to

category IV, design pressure of 21

bar, according to the pressure

equipment directive PED 97/23/CE. It meets two important functions: the first and most important one is to separate

oil from the discharge gas. It makes it in two steps:

Step 1: Via a primary separator, that allows achieving an efficiency level up to 50 ppm.

Step 2: Via a secondary separator, which uses coalescent filters that allows achieving an efficiency level up to 5 ppm.

The oil separator performs the second function of being the metallic structure on which is support the GMT unit. This

structure consists on two legs and both metallic supports corresponding to the motor and the compressor.

The separator is fitted with two sight-glasses located on its primary area and one sight-glass located on its secondary

area. It is also equipped with two oil heating resistors and the oil charge. On one of its side, there is a removable cap to

replace the coalescent filters when they lose separation efficiency

4.- Oil circuit. It is necessary to check the good quality of the oil in order to ensure the correct operation of the

compressor. The oil shall be clean and with the proper temperature so that it will get the required viscosity (when

entering the compressor) to perform correctly the functions of injection, lubrication and control capacity.

4

Page 5: Technical Guide for Screw Compressor Packages easy definition HX -40

Main components:

4.1.- Line from oil separator to oil cooler. Formed by valve ans associated piping.

4.2.- Oil cooler. These coolers

These coolers have been specially

disegned for the marine and

industrial refrigeration of oil. It is a

oil cooler refrigerated by liquid NH3

using the termosyphon system ,

working with tube bundles, compact

and light. Its function is essential

for the operation of the compressor

and it is to cool oil to 50ºC to keep

the right lubricating conditions of

the compressor.

4.1

4.4

4.3 4.2

4.5

4.7

4.9

4.8

4.3.- Line from oil cooler to

micronic filter. Conection

between the oil cooler and the

micronic filter.

4.4.- Micronic filter.The fuction of the micronic filter is to avoid the return of metallic particles and

impurities to the compresor. It has a removable lid to replace the filter with a new one when required.

4.5.- Line from micronic filter to oil collector. Formed by a valve and a relief valve

4.6.- Oil colector. The function is to distribute the oil into the compressor through the injection connections

lubrication to front bearings, lubrication to back bearings and feeding of the to the capacity control system.

Also includes a temperature measuring device and a 4-20 mA sensor for the oil injection temperature.

4.7.- Oil return line . The oil that has been separated in the secondary oil separartor must be send back to the

oil circuit and we do it throw this line that connects the secondary separator with the suction line by means of a

valve, filter, needle valve and piping.

4.8.- Capacity control system. Formed by a 4 way valve and 4 tubes one to get oil, oil relief, charge and

discharge.

5.- Coupling. It is a rigid type, made of steel sheets, which can absorb angular misalignment between 1 º and 1.3 º per

sheet, axials between 2 and 2.6 mm. and radials between 2 to 2.5 mm., depending on the model.

6.- Coupling protection device. It is made of aluminium and prevents access to moving parts of the group.

7.- Suction line. It consists of a stop valve, a check valve and a filter fitted with a grid of 200. It is also fitted with a

connection for capacity control, a connection for oil return, a connection for low pressure, a connection for a free valve

and a blind device to capture the suction temperature.

5

Page 6: Technical Guide for Screw Compressor Packages easy definition HX -40

8.- Discharge line . SFormed by two stretchs one from crompressor to separator with a blind device to capture the

temperatura and a 4-20 mA sensor to capture the discharge temperatura and another one from oil separator to the system

formed by a diferential regulation valve which function is to keep the pressure diference between discharge and suction

to guarantee the oil flow required in the compressor, check valve and stop valve.

9.- Set of safety valves. It consists of two safety valves placed in parallel on the oil separator, which have been set

at 21 bar, a safety valve mounted on the oil cooler and located on the side of the tubes also set at 21 bar and a relief

valve mounted in the oil cooler and located on the shell side. All of them led to a common collector.

10.- Set of automatisms. Formed by a manifold, in which four gauges, three pressure probes of 4-20 mA and four

stop valves are integrated. It is also fitted with an oil level pressure switch and a twice high pressure switch with a

single output. Three temperature probes of 4-20 mA, to measure the temperature of oil, which is going to be injected in

the compressor, the oil temperature in the oil separator and the discharge temperature

6

Page 7: Technical Guide for Screw Compressor Packages easy definition HX -40

Mechanical elements as optionals.

s.- Superfeed. It is an option that involves an increase of the

refrigeration capacity. This increase is higher than the one of the absorbed

power, which means an increase of the efficiency of the group. It can be

used for two reasons: 1) to increase the efficiency of the group and 2) to

reach a certain output without increasing the size of the compressor. It

consists of a stop valve (1), a check valve (2), a 200 mesh filter (3) and a

thermowell (4) for measuring temperature.

24 1

3

scr.- Superfeed with regulating valve. It is a complement of the Superfeed option, described in the previous

paragraph. It will be used when there are several groups working in

parallel in the same installation. In this way, when a group reduces

its capacity, (the superfeed intermediate pressure comes close to the

suction pressure), this option will prevent losing performance and

efficiency in both groups and it will allow operating at 100%

capacity. To perform this function, it is fitted with the following

components: filter (1), check valve (2), thermowell to take

temperatures (3), pilot regulation (4), regulating valve of differential

pressure (5) and stop valve (6), piping, low pressure connection(7)

3 5

4

26

7 1

mcv.- Motor activated by a variable frequency drive between 1500 and 3000 rpm. This option can be used:

1) To start the compressor, via a controlled variation of the frequency. 2) To improve the efficiency of the group with

part load. It consists of the replacement of the standard motor, described in Section 2 on page 5, with a motor fitted with

NDE insulated bearing and reinforced wiring insulation.

m+ .- Oversized motor. When we are located in the area of red characters in the chart “motor selection” and the

absorbed power is greater than the one provided by the standard motor. Therefore, we should choose this option m+, to

increase one size the standard motor

__hz .- Operating with the variable frequency drive > 50 Hz. Depending on the group, the working point and

the operating maximum frequency, it may be necessary to change the oil separator, oil cooler, Ø of piping, oil pump,

electric motor, to use this option. Therefore, consult it before ordering it.

eaw .- Oil cooling by water. This option uses water to cool oil, via a cooler which has been designed for this

purpose.

eai .- Oil cooling by injection. This option ignores the cooler and replace it with an injection of NH3 to a

connection that has the compressor casing. Is made through a solenoid valve and a thermostatic valve which controls

the discharge temperature.

7

Page 8: Technical Guide for Screw Compressor Packages easy definition HX -40

tra .- Oil thermoregulation. This option allows maintaining at all

times the oil temperature controlled and therefore its optimum

lubrication conditions. To obtain this situation, it is necessary to

install an oil bypass (1), which starts in a "T" connection (2), and

ends in a three-ways valve (3), which keeps the oil injection

temperature controlled.

3

2

1

dcc .- Twin connections. This option is used when a group is designed to serve multiple services at different times.

This option modifies the standard suction line adding a “T” (1) and

another stop valve (2), keeping the same filter ( in the XRV 127 models

as the one shown in the picture the suction filter is inside the

compressor), the same check valve (3) and the same stop valve (4).

3 4

1

2

pam .- Marine atmosphere paint. This option is used for units located outdoors. It consists of:

1. The IP23 protection standard motor is replaced with an IP55 protection motor.

2. The welding of the metal sheets of the separator, motor support, compressor support, uni (2) keeping the

same filter ( In legs shall be continuous welding and not by segments.

3. The separator and its metal sheets, the supports and the legs will be treated with a blasting procedure of 5

to 2 ½ grade.

4. Paint as follows:

a. Apply an epoxy primer coating with 60% of Zinc powder. Thickness: 60 microns.

b. Then, apply an anti-corrosive intermediate coating of epoxy-polyamide. Thickness 100 microns.

c. Finally, apply a polyurethane-acrylic enamel. Thickness: 30 microns.

apc .- Condensing high pressure. If in the design of the installation, it has been considered the possibility of

working at condensing temperatures between 39 and 45 º C and since part loads are not accepted in these cases, it is

necessary to equip the unit with the option apc. This option involves installing one oversized oil cooler and the

appropriate electric motor for working at the above mentioned temperatures.

8

Page 9: Technical Guide for Screw Compressor Packages easy definition HX -40

Electrical elements as optionals.

bdc .- Field bus. Prewired in the group between the digital and analogic automatisms throw I/O distributors to a field

bus. It makes easier and simplifies the communication between the group and the electrical panel that is reduced to 2

hoses of 5 wires each for communication and power supply . The components all of them with IP67 protection grade

are :

3

2

1 Monobloc distributor for field bus CANopen type 8 I/O.

(1) 6

5

4

Modular coupling for CANopen type field bus(2)

4 analogic inputs distributor Compact type (3)

Keypad consisting in :

o Box. (4)

o Emergency stop. (5)

o Two “run” and “breakdown” indicators in the

front side of the box. (6)

Wiring as per IP67 protection grade installation type.

cc .- Control panel-board. This control panel-board consists of an electric panel board (protection level IP66), with

the following main elements:

TWIDO PLC with 24 digital inputs, 16 digital outputs and 8 analog inputs.

Communication Interface, placed on the front part of the panel.(1)

A protection bipolar circuit breaker for the PLC.

2 A protection DC bipolar circuit breaker for the PLC

power supply. 1

Monopolar protection circuit breaker for the capacity

valves.

4

3 Shut-off general switch in discharge line, placed on one

lateral side of the panel. (2)

Two indicators: Breakdown and Run, located on the

front part of the panel. (3)

Emergency stop on the front of the panel.(4)

Six output relays of 230V ca.

Connections terminals BC and user terminals BU.

Base of switch.

9

Page 10: Technical Guide for Screw Compressor Packages easy definition HX -40

Main functions of the control system. Regulation of the suction pressure, PID capacity control between 10 and

100%, control of oil minimum temperature, control of the compressor operating hours, starts timing, configuration of

parameters by touch keyboard, diagnostic and historical data of alarms. Control for operating the group inside its limits.

Functions related to the digital inputs. Confirmation compressor running,, confirmation oil resistances running,

emergency stop, indication 10% of capacity, oil level pressure switch and high pressure switch.

Functions related to digital outputs. Order for compressor control, order, order for oil resistances control, order

for emergency stop, control of capacity charge valve, control of capacity discharge valve, through signal to relay, green

pilot running, red pilot breakdown.

Functions related to analog inputs. Consumption of the compressor motor, indication of the compressor capacity,

discharge pressure, suction pressure, oil temperature inside separator, oil temperature to compressor and discharge

temperature.

Communication Interface. It consists of a programmable touch screen of 5,7” in 16 levels of grey colours, with a

resolution of 1024 x 1024, connected to the PLC by the serial port COM2 RJ45 (RS485)

ccs .- ET 200 control pane. EControl panel with IP66 protection grade with the following main elemments :

PLC Siemens CPU ET 200 with 8 digital inputs, 8 digital outputs, and 8 analogic inputs.

Communication interface in the front side of the box.

Bipolar nagnetothermic circuit breaker to protect the PLC.

Bipolar magnetothermic DC circuit breaker to protect the PLC’s power supply.

Monopolar protection circuit breaker for the capacity valves.

Shut-off general switch in discharge line, placed on one lateral side of the panel.

Two indicators: Breakdown and Run, located on the front part of the panel.

Emergency stop on the front of the panel.

Six output relays of 24V cc.

Connections terminals BC and user terminals BU.

Base of switch.

With functions similar to the ones described in the cc optional

Communication interface CScreen of 4,5” with 160 x 64 pixel resolution monoccrome ( yellow-green) . Control

elements consisting in 8 function programable keys ( 4 with led ), 23 system keys communication with PLC through

RS232 serial port.

Ccs+ .- S7 300 control panel. Control panel with IP66 protection grade with the following main elemments :

PLC Siemens CPU S7 313C with 24 digital inputs, 16 digital outputs, and 8 analogic inputs.

Communication interface in the front side of the box.

Bipolar nagnetothermic circuit breaker to protect the PLC.

Bipolar magnetothermic DC circuit breaker to protect the PLC’s power supply.

10

Page 11: Technical Guide for Screw Compressor Packages easy definition HX -40

Monopolar protection circuit breaker for the capacity valves.

Shut-off general switch in discharge line, placed on one lateral side of the panel.

Two indicators: Breakdown and Run, located on the front part of the panel.

Emergency stop on the front of the panel.

Six output relays of 24V cc.

Connections terminals BC and user terminals BU.

Base of switch.

With functions similar to the ones described in the cc optional

Communication interface The same as described in the ccs optional.

11

Page 12: Technical Guide for Screw Compressor Packages easy definition HX -40

12

Page 13: Technical Guide for Screw Compressor Packages easy definition HX -40

13

TECHNICAL DATA AND PERFORMANCE OF THE UNIT

Technical data of the Standard unit.

UNIT MODEL 40 60 70 90 110 130 180 200 220 Units Refrig. capacity (1) 37,9 54 68,7 82,6 104,7 126,3 175,7 193,9 214,7 Kw Absorved power(1) 34,5 47,5 59,3 70,7 85 102,6 130,9 148,7 166,5 Kw COP(1) 1,10 1,14 1,16 1,17 1,23 1,23 1,34 1,30 1,29 Volumetric rate Vi 5,0 5,0 5,0 5,0 5,0 5,0 5,0 5,0 5,0 Refrigerant NH3 Oil Ultracool 68

Data of compressors.

Type Rotatory bi-screw Units Model 127-R1 127-R3 127-R4 127-R5 163/193 204/110 204/145 204/165 204/193 Capacity 30-100% 10-100% Weight 265 265 265 265 388 636 660 690 736 Kg Moment of inertia 0,0303 0,0663 0,0968 0,1309 0,124 0,214 0,278 0,345 0,4 Kg*m2 Start up torque 3,1 3,1 3,1 3,1 10 10 10 10 10 N*m Maximum turn speed 5000 3600 3600 3000 3600 3600 3600 3600 3600 rpm Turn direction CW ACW ACW ACW CW CW CW CW CW

Data of oil separators.

Type Horizontal double phase Units Diameter 406 406 406 406 508 508 508 610 610 mm Length 1800 2000 2000 2000 2400 2400 2600 2800 2800 mm

Coalescent filters RSC0438 RSC0438 RSC0438 RSC0438 RSC1140 RSC1140 RSC1140 RSC1140 RSC1140 Qty of filters 1 1 1 1 1 1 1 2 2 Nº Oil charge 48 55 55 55 76 76 87 128 128 lts

Design pressure 21 bar

Page 14: Technical Guide for Screw Compressor Packages easy definition HX -40

14

Data of motors.

Type Low voltage asynchronous motor Units Nominal power 55 75 75 90 110 132 160 200 200 Kw Nominal voltage 400 V Type of protection IP 23 Housing size 200L 225M 225M 250S 250M 280M 315S 315M 315M Direction of rotation Both directions

Data of connections.

Type BW sch40 Units Suction diameter 65 80 80 80 100 100 100 125 125 mm Discharge diameter 25 32 32 32 40 40 50 50 50 mm Termosyphon diam. 50 mm Superfeed diameter 32 32 40 40 40 40 50 65 65 mm

(1) Evaporating temperature = -40 ºC. Condensing temperature = 35 ºC. Useful superheat = 0 ºC. Total superheat = 0 ºC. Loss of charge in suction line = 0 bar.

Loss of charge in discharge line 0,15 bar. Subcooling = 3 ºC. Oil temperature 50 ºC.

(2) Only when the unit is fitted with the superfeed option “s

Page 15: Technical Guide for Screw Compressor Packages easy definition HX -40

Performance of the unit with nominal Vi

Condensation T 32 33 34 35 36 37 38

MODEL Evaporation

T Frig

P. Kw Abs P.

Kw COP Frig P. Kw

Abs P.

Kw COP Frig

P. KwAbs

P. Kw COPFrig P.

Kw

Abs P. Kw COP Frig

P. Kw

Abs P.

Kw COP Frig

P. Kw

Abs P.

Kw COP

Frig P.

Kw

Abs P.

Kw COP

-45 29,0 31,1 0,93 28,6 31,9 0,90 28,3 32,6 0,87 27,9 33,3 0,84 27,6 34,1 0,81 27,2 34,9 0,78 26,8 35,7 0,75

-44 30,8 31,4 0,98 30,5 32,1 0,95 30,2 32,8 0,92 29,8 33,5 0,89 29,5 34,3 0,86 29,1 35,1 0,83 28,7 35,9 0,80

-43 32,8 31,6 1,04 32,4 32,3 1,00 32,1 33,0 0,97 31,7 33,8 0,94 31,4 34,5 0,91 31,0 35,3 0,88 30,6 36,1 0,85

-42 34,7 31,8 1,09 34,4 32,5 1,06 34,1 33,3 1,02 33,7 34,0 0,99 33,4 34,7 0,96 33,0 35,5 0,93 32,6 36,3 0,90

-41 36,8 32,1 1,15 36,5 32,8 1,11 36,1 33,5 1,08 35,8 34,3 1,04 35,4 35,0 1,01 35,0 35,8 0,98 34,7 36,5 0,95

-40 38,9 32,4 1,20 38,6 33,1 1,17 38,3 33,8 1,13 37,9 34,5 1,10 37,5 35,3 1,06 37,2 36,0 1,03 36,8 36,8 1,00

-39 41,1 32,7 1,26 40,8 33,4 1,22 40,5 34,1 1,19 40,1 34,8 1,15 39,7 35,6 1,12 39,4 36,3 1,08 39,0 37,1 1,05

-38 43,5 33,0 1,32 43,1 33,7 1,28 42,7 34,4 1,24 42,4 35,1 1,21 42,0 35,9 1,17 41,6 36,6 1,14 41,2 37,4 1,10

-37 45,5 34,0 1,34 45,1 34,7 1,30 44,7 35,4 1,26 44,4 36,2 1,23 44,0 36,9 1,19 43,6 37,7 1,16

-36 47,6 35,1 1,36 47,2 35,8 1,32 46,8 36,5 1,28 46,4 37,3 1,25 46,0 38,0 1,21

-35 49,4 36,9 1,34 49,0 37,6 1,30 48,5 38,4 1,26

-34 51,6 38,0 1,36 51,2 38,7 1,32

GM

T H

X 4

0-40

-33 53,9 39,1 1,38

-45 35,0 34,1 1,03 34,7 34,9 1,00 34,4 35,7 0,96 34,0 36,6 0,93 33,7 37,5 0,90 33,3 38,4 0,87 32,9 39,4 0,84

-44 37,2 34,3 1,09 36,9 35,1 1,05 36,5 35,9 1,02 36,2 36,8 0,98 35,9 37,7 0,95 35,5 38,6 0,92 35,1 39,5 0,89

-43 39,4 34,5 1,14 39,1 35,3 1,11 38,8 36,1 1,07 38,4 37,0 1,04 38,1 37,9 1,01 37,7 38,8 0,97 37,4 39,7 0,94

-42 41,7 34,7 1,20 41,4 35,5 1,17 41,1 36,3 1,13 40,8 37,2 1,10 40,4 38,1 1,06 40,1 39,0 1,03 39,7 39,9 0,99

-41 44,1 35,0 1,26 43,8 35,8 1,22 43,5 36,6 1,19 43,1 37,4 1,15 42,8 38,3 1,12 42,4 39,2 1,08 42,1 40,1 1,05

-40 46,6 35,2 1,32 46,3 36,0 1,28 45,9 36,9 1,25 45,6 37,7 1,21 45,3 38,6 1,17 44,9 39,4 1,14 44,6 40,3 1,10

-39 49,1 35,5 1,38 48,8 36,3 1,34 48,5 37,1 1,31 48,2 38,0 1,27 47,8 38,8 1,23 47,5 39,7 1,20 47,1 40,6 1,16

-38 51,8 35,8 1,45 51,5 36,6 1,41 51,2 37,4 1,37 50,8 38,3 1,33 50,5 39,1 1,29 50,2 40,0 1,25 49,8 40,9 1,22

-37 54,2 36,9 1,47 53,9 37,7 1,43 53,6 38,6 1,39 53,3 39,4 1,35 52,9 40,3 1,31 52,5 41,2 1,28

-36 56,8 38,1 1,49 56,5 38,9 1,45 56,1 39,7 1,41 55,8 40,6 1,37 55,4 41,5 1,34

-35 59,1 40,1 1,47 58,7 40,9 1,43 58,4 41,8 1,40

-34 61,8 41,3 1,50 61,4 42,2 1,46

GM

T H

X 4

0-40

s

-33 64,6 42,5 1,52

15

Page 16: Technical Guide for Screw Compressor Packages easy definition HX -40

Condensation T 32 33 34 35 36 37 38

MODEL Evaporation

T Frig

P. Kw Abs P.

Kw COP Frig P. Kw

Abs P.

Kw COP Frig

P. KwAbs

P. Kw COPFrig P.

Kw

Abs P. Kw COP Frig

P. Kw

Abs P.

Kw COP Frig

P. Kw

Abs P.

Kw COP

Frig P.

Kw

Abs P.

Kw COP

-45 41,5 42,8 0,97 41,0 43,8 0,94 40,6 44,8 0,91 40,2 45,9 0,88 39,7 46,9 0,85 39,2 48,0 0,82 38,7 49,1 0,79

-44 44,1 43,1 1,02 43,6 44,1 0,99 43,2 45,1 0,96 42,8 46,1 0,93 42,3 47,2 0,90 41,8 48,3 0,87 41,4 49,4 0,84

-43 46,7 43,4 1,08 46,3 44,4 1,04 45,9 45,4 1,01 45,4 46,4 0,98 45,0 47,5 0,95 44,5 48,5 0,92 44,0 49,6 0,89

-42 49,5 43,8 1,13 49,1 44,7 1,10 48,7 45,7 1,06 48,2 46,7 1,03 47,8 47,8 1,00 47,3 48,8 0,97 46,8 49,9 0,94

-41 52,4 44,1 1,19 52,0 45,1 1,15 51,5 46,1 1,12 51,1 47,1 1,08 50,6 48,1 1,05 50,1 49,2 1,02 49,7 50,2 0,99

-40 55,4 44,5 1,24 55,0 45,5 1,21 54,5 46,5 1,17 54,0 47,5 1,14 53,6 48,5 1,11 53,1 49,5 1,07 52,6 50,6 1,04

-39 58,5 44,9 1,30 58,1 45,9 1,27 57,6 46,9 1,23 57,1 47,9 1,19 56,7 48,9 1,16 56,2 49,9 1,13 55,7 51,0 1,09

-38 61,7 45,4 1,36 61,3 46,3 1,32 60,8 47,3 1,29 60,3 48,3 1,25 59,8 49,3 1,21 59,3 50,3 1,18 58,8 51,4 1,15

-37 64,6 46,8 1,38 64,1 47,7 1,34 63,7 48,7 1,31 63,2 49,7 1,27 62,6 50,8 1,23 62,1 51,8 1,20

-36 67,6 48,2 1,40 67,1 49,2 1,36 66,6 50,2 1,33 66,1 51,2 1,29 65,5 52,3 1,25

-35 70,2 50,7 1,38 69,6 51,7 1,35 69,1 52,8 1,31

-34 73,3 52,2 1,40 72,8 53,3 1,37

GM

T H

X 6

0-40

-33 76,6 53,8 1,42

-45 51,1 46,0 1,11 50,7 47,1 1,08 50,4 48,2 1,04 50,0 49,4 1,01 49,5 50,6 0,98 49,1 51,8 0,95 48,6 53,1 0,92

-44 54,1 46,3 1,17 53,8 47,4 1,13 53,4 48,5 1,10 53,0 49,7 1,07 52,6 50,8 1,03 52,2 52,0 1,00 51,7 53,3 0,97

-43 57,2 46,6 1,23 56,9 47,7 1,19 56,5 48,8 1,16 56,2 49,9 1,12 55,8 51,1 1,09 55,3 52,3 1,06 54,9 53,5 1,03

-42 60,5 47,0 1,29 60,1 48,0 1,25 59,8 49,1 1,22 59,4 50,3 1,18 59,0 51,4 1,15 58,6 52,6 1,11 58,2 53,8 1,08

-41 63,8 47,3 1,35 63,5 48,4 1,31 63,2 49,5 1,28 62,8 50,6 1,24 62,4 51,8 1,21 62,0 52,9 1,17 61,6 54,2 1,14

-40 67,3 47,7 1,41 67,0 48,8 1,37 66,7 49,9 1,34 66,3 51,0 1,30 65,9 52,1 1,26 65,5 53,3 1,23 65,1 54,5 1,19

-39 71,0 48,1 1,47 70,6 49,2 1,44 70,3 50,3 1,40 69,9 51,4 1,36 69,5 52,5 1,32 69,1 53,7 1,29 68,7 54,9 1,25

-38 74,7 48,6 1,54 74,4 49,6 1,50 74,0 50,7 1,46 73,7 51,8 1,42 73,3 52,9 1,38 72,9 54,1 1,35 72,5 55,3 1,31

-37 78,3 50,1 1,56 77,9 51,1 1,52 77,6 52,2 1,48 77,2 53,4 1,45 76,8 54,5 1,41 76,4 55,7 1,37

-36 82,0 51,6 1,59 81,6 52,7 1,55 81,2 53,8 1,51 80,8 55,0 1,47 80,4 56,1 1,43

-35 85,4 54,3 1,57 85,0 55,4 1,53 84,6 56,6 1,49

-34 89,3 55,9 1,60 88,9 57,1 1,56

GM

T H

X 6

0-40

s

-33 93,4 57,6 1,62

16

Page 17: Technical Guide for Screw Compressor Packages easy definition HX -40

Condensation T 32 33 34 35 36 37 38

MODEL Evaporation

T Frig

P. Kw Abs P.

Kw Frig

P. KwCOPAbs P.

Kw COP Frig

P. KwAbs

P. Kw COPFrig P.

Kw

Abs P. Kw COP Frig

P. Kw

Abs P.

Kw COP Frig

P. Kw

Abs P.

Kw COP

Frig P.

Kw

Abs P.

Kw COP

-45 52,8 53,5 0,99 52,3 54,7 0,96 51,8 56,0 0,92 51,2 57,3 0,89 50,7 58,6 0,87 50,1 59,9 0,84 49,6 61,3 0,81

-44 56,0 53,9 1,04 55,5 55,1 1,01 55,0 56,3 0,98 54,5 57,6 0,95 54,0 58,9 0,92 53,4 60,3 0,89 52,8 61,6 0,86

-43 59,4 54,3 1,09 58,9 55,5 1,06 58,4 56,7 1,03 57,9 58,0 1,00 57,3 59,3 0,97 56,8 60,6 0,94 56,2 62,0 0,91

-42 62,9 54,7 1,15 62,4 55,9 1,12 61,9 57,1 1,08 61,3 58,4 1,05 60,8 59,7 1,02 60,2 61,0 0,99 59,7 62,4 0,96

-41 66,5 55,1 1,21 66,0 56,3 1,17 65,5 57,6 1,14 64,9 58,8 1,10 64,4 60,1 1,07 63,8 61,4 1,04 63,2 62,8 1,01

-40 70,3 55,6 1,26 69,8 56,8 1,23 69,2 58,0 1,19 68,7 59,3 1,16 68,1 60,6 1,12 67,5 61,9 1,09 66,9 63,2 1,06

-39 74,2 56,1 1,32 73,7 57,3 1,28 73,1 58,5 1,25 72,5 59,8 1,21 72,0 61,1 1,18 71,4 62,4 1,14 70,8 63,7 1,11

-38 78,3 56,7 1,38 77,7 57,9 1,34 77,1 59,1 1,31 76,6 60,3 1,27 76,0 61,6 1,23 75,4 62,9 1,20 74,8 64,2 1,16

-37 81,9 58,4 1,40 81,3 59,6 1,36 80,8 60,9 1,33 80,2 62,1 1,29 79,5 63,4 1,25 78,9 64,7 1,22

-36 85,7 60,2 1,42 85,1 61,4 1,39 84,5 62,7 1,35 83,9 64,0 1,31 83,2 65,3 1,27

-35 89,0 63,3 1,41 88,3 64,6 1,37 87,7 65,9 1,33

-34 93,0 65,2 1,43 92,3 66,5 1,39

GM

T H

X 7

0-40

-33 97,2 67,2 1,45

-45 65,4 57,0 1,15 65,0 58,3 1,12 64,6 59,7 1,08 64,2 61,1 1,05 63,7 62,5 1,02 63,2 64,0 0,99 62,7 65,6 0,96

-44 69,2 57,3 1,21 68,8 58,7 1,17 68,4 60,0 1,14 68,0 61,4 1,11 67,6 62,9 1,07 67,1 64,3 1,04 66,6 65,9 1,01

-43 73,2 57,7 1,27 72,8 59,1 1,23 72,4 60,4 1,20 72,0 61,8 1,16 71,5 63,2 1,13 71,1 64,7 1,10 70,6 66,2 1,07

-42 77,3 58,2 1,33 76,9 59,5 1,29 76,5 60,8 1,26 76,1 62,2 1,22 75,7 63,6 1,19 75,2 65,1 1,16 74,7 66,6 1,12

-41 81,5 58,6 1,39 81,1 59,9 1,35 80,7 61,3 1,32 80,3 62,7 1,28 79,9 64,1 1,25 79,5 65,5 1,21 79,0 67,0 1,18

-40 85,9 59,1 1,45 85,5 60,4 1,42 85,1 61,8 1,38 84,7 63,1 1,34 84,3 64,5 1,31 83,9 66,0 1,27 83,4 67,4 1,24

-39 90,5 59,6 1,52 90,1 60,9 1,48 89,7 62,3 1,44 89,3 63,6 1,40 88,9 65,0 1,37 88,4 66,4 1,33 88,0 67,9 1,30

-38 95,2 60,2 1,58 94,8 61,5 1,54 94,4 62,8 1,50 94,0 64,2 1,47 93,6 65,5 1,43 93,2 67,0 1,39 92,7 68,4 1,36

-37 99,7 62,0 1,61 99,4 63,4 1,57 98,9 64,7 1,53 98,5 66,1 1,49 98,1 67,5 1,45 97,6 69,0 1,42

-36 104,4 63,9 1,63 104,0 65,3 1,59 103,6 66,7 1,55 103,2 68,1 1,52 102,7 69,5 1,48

-35

GM

T H

X 7

0-40

s

108,9 67,3 1,62 108,4 68,7 1,58 108,0 70,1 1,54

-34 113,9 69,3 1,64 113,4 70,8 1,60

-33 119,1 71,4 1,67

17

Page 18: Technical Guide for Screw Compressor Packages easy definition HX -40

Condensation T 32 33 34 35 36 37 38

MODEL Evaporation

T Frig

P. Kw Abs P.

Kw COP Frig P. Kw

Abs P.

Kw COP Frig

P. KwAbs

P. Kw COP Frig P. Kw

Abs P. Kw COP Frig

P. Kw

Abs P.

Kw COP Frig

P. Kw

Abs P.

Kw COP

Frig P.

Kw

Abs P.

Kw COP

-45 63,5 63,8 1,00 63,0 65,3 0,96 62,4 66,8 0,93 61,8 68,3 0,90 61,2 69,9 0,88 60,5 71,5 0,85 59,9 73,1 0,82

-44 67,4 64,2 1,05 66,8 65,7 1,02 66,3 67,2 0,99 65,7 68,7 0,96 65,0 70,3 0,93 64,4 71,9 0,90 63,8 73,5 0,87

-43 71,5 64,7 1,10 70,9 66,2 1,07 70,3 67,6 1,04 69,7 69,2 1,01 69,1 70,7 0,98 68,4 72,3 0,95 67,8 73,9 0,92

-42 75,6 65,2 1,16 75,0 66,7 1,13 74,4 68,1 1,09 73,8 69,6 1,06 73,2 71,2 1,03 72,6 72,8 1,00 71,9 74,4 0,97

-41 80,0 65,8 1,22 79,4 67,2 1,18 78,8 68,7 1,15 78,1 70,2 1,11 77,5 71,7 1,08 76,9 73,3 1,05 76,2 74,9 1,02

-40 84,5 66,3 1,27 83,9 67,8 1,24 83,2 69,2 1,20 82,6 70,7 1,17 82,0 72,2 1,13 81,3 73,8 1,10 80,6 75,4 1,07

-39 89,1 67,0 1,33 88,5 68,4 1,29 87,9 69,8 1,26 87,2 71,3 1,22 86,6 72,8 1,19 85,9 74,4 1,15 85,2 76,0 1,12

-38 94,0 67,6 1,39 93,4 69,0 1,35 92,7 70,5 1,32 92,0 71,9 1,28 91,4 73,5 1,24 90,7 75,0 1,21 90,0 76,6 1,17

-37 98,4 69,7 1,41 97,7 71,1 1,37 97,1 72,6 1,34 96,4 74,1 1,30 95,7 75,7 1,26 94,9 77,2 1,23

-36 103,0 71,8 1,43 102,3 73,3 1,40 101,5 74,8 1,36 100,8 76,3 1,32 100,1 77,9 1,28

-35 106,9 75,5 1,42 106,2 77,1 1,38 105,4 78,6 1,34

-34 111,8 77,8 1,44 111,0 79,4 1,40

GM

T H

X 9

0-40

-33 116,8 80,1 1,46

-45 78,9 67,5 1,17 78,5 69,1 1,14 78,0 70,7 1,10 77,6 72,4 1,07 77,0 74,1 1,04 76,5 75,9 1,01 76,0 77,7 0,98

-44 83,5 68,0 1,23 83,0 69,5 1,19 82,6 71,1 1,16 82,1 72,8 1,13 81,6 74,5 1,10 81,1 76,2 1,06 80,6 78,0 1,03

-43 88,2 68,4 1,29 87,8 70,0 1,25 87,3 71,6 1,22 86,9 73,2 1,19 86,4 74,9 1,15 85,9 76,7 1,12 85,4 78,4 1,09

-42 93,1 69,0 1,35 92,7 70,5 1,31 92,2 72,1 1,28 91,8 73,7 1,24 91,3 75,4 1,21 90,8 77,1 1,18 90,3 78,9 1,14

-41 98,1 69,5 1,41 97,7 71,1 1,38 97,3 72,7 1,34 96,9 74,3 1,30 96,4 75,9 1,27 95,9 77,6 1,24 95,4 79,4 1,20

-40 103,4 70,1 1,47 103,0 71,7 1,44 102,6 73,2 1,40 102,1 74,8 1,36 101,6 76,5 1,33 101,2 78,2 1,29 100,7 79,9 1,26

-39 108,8 70,7 1,54 108,4 72,3 1,50 108,0 73,8 1,46 107,6 75,5 1,43 107,1 77,1 1,39 106,6 78,8 1,35 106,1 80,5 1,32

-38 114,5 71,4 1,60 114,1 72,9 1,56 113,7 74,5 1,53 113,2 76,1 1,49 112,7 77,7 1,45 112,3 79,4 1,41 111,8 81,1 1,38

-37 119,9 73,6 1,63 119,5 75,2 1,59 119,1 76,8 1,55 118,6 78,4 1,51 118,1 80,1 1,47 117,6 81,8 1,44

-36 125,6 75,9 1,66 125,1 77,5 1,62 124,7 79,1 1,58 124,2 80,8 1,54 123,7 82,5 1,50

-35 131,0 79,8 1,64 130,5 81,5 1,60 130,0 83,2 1,56

-34 137,0 82,3 1,67 136,5 84,0 1,63

GM

T H

X 9

0-40

s

-33 143,2 84,7 1,69

18

Page 19: Technical Guide for Screw Compressor Packages easy definition HX -40

Condensation T 32 33 34 35 36 37 38

MODEL Evaporation

T Frig

P. Kw Abs P.

Kw COP Frig P. Kw

Abs P.

Kw COP Frig

P. KwAbs

P. Kw COP Frig P. Kw

Abs P. Kw COP Frig

P. Kw

Abs P.

Kw COP Frig

P. Kw

Abs P.

Kw COP

Frig P.

Kw

Abs P.

Kw COP

-45 81,6 76,0 1,07 81,0 77,9 1,04 80,5 79,7 1,01 79,9 81,6 0,98 79,2 83,6 0,95 78,6 85,6 0,92 77,9 87,6 0,89

-44 86,3 76,7 1,12 85,7 78,5 1,09 85,2 80,3 1,06 84,6 82,2 1,03 84,0 84,1 1,00 83,3 86,1 0,97 82,6 88,1 0,94

-43 91,1 77,4 1,18 90,5 79,1 1,14 90,0 81,0 1,11 89,4 82,8 1,08 88,8 84,7 1,05 88,1 86,7 1,02 87,5 88,7 0,99

-42 96,0 78,1 1,23 95,5 79,8 1,20 94,9 81,6 1,16 94,3 83,5 1,13 93,7 85,4 1,10 93,1 87,4 1,07 92,5 89,3 1,03

-41 101,1 78,8 1,28 100,6 80,6 1,25 100,0 82,4 1,21 99,4 84,2 1,18 98,8 86,1 1,15 98,2 88,0 1,12 97,6 90,0 1,08

-40 106,4 79,6 1,34 105,8 81,4 1,30 105,3 83,2 1,27 104,7 85,0 1,23 104,1 86,9 1,20 103,4 88,8 1,17 102,8 90,8 1,13

-39 111,9 80,4 1,39 111,3 82,2 1,35 110,7 84,0 1,32 110,1 85,8 1,28 109,5 87,7 1,25 108,9 89,6 1,22 108,2 91,5 1,18

-38 117,5 81,3 1,45 116,9 83,0 1,41 116,3 84,8 1,37 115,7 86,6 1,34 115,1 88,5 1,30 114,5 90,4 1,27 113,8 92,3 1,23

-37 122,8 83,9 1,46 122,2 85,7 1,43 121,6 87,5 1,39 120,9 89,3 1,35 120,3 91,3 1,32 119,6 93,2 1,28

-36 128,3 86,6 1,48 127,6 88,4 1,44 126,9 90,2 1,41 126,3 92,2 1,37 125,6 94,1 1,33

-35 133,2 91,2 1,46 132,5 93,1 1,42 131,8 95,0 1,39

-34 139,0 94,0 1,48 138,3 96,0 1,44

GM

T H

X 1

10-4

0

-33 145,0 97,0 1,49

-45 99,3 80,4 1,24 99,0 82,4 1,20 98,5 84,4 1,17 98,1 86,5 1,13 97,5 88,7 1,10 97,0 90,9 1,07 96,4 93,2 1,03

-44 104,7 81,1 1,29 104,4 83,1 1,26 104,0 85,1 1,22 103,5 87,2 1,19 103,0 89,3 1,15 102,5 91,5 1,12 102,0 93,8 1,09

-43 110,3 81,8 1,35 109,9 83,8 1,31 109,6 85,8 1,28 109,1 87,8 1,24 108,7 90,0 1,21 108,2 92,2 1,17 107,7 94,4 1,14

-42 116,0 82,5 1,41 115,6 84,5 1,37 115,3 86,5 1,33 114,9 88,6 1,30 114,4 90,7 1,26 114,0 92,8 1,23 113,5 95,1 1,19

-41 121,8 83,3 1,46 121,5 85,3 1,43 121,2 87,3 1,39 120,8 89,3 1,35 120,4 91,4 1,32 119,9 93,6 1,28 119,4 95,8 1,25

-40 127,9 84,1 1,52 127,6 86,1 1,48 127,2 88,0 1,45 126,9 90,1 1,41 126,5 92,2 1,37 126,0 94,3 1,34 125,6 96,5 1,30

-39 134,1 85,0 1,58 133,8 86,9 1,54 133,5 88,9 1,50 133,1 90,9 1,46 132,7 93,0 1,43 132,3 95,1 1,39 131,9 97,3 1,35

-38 140,6 85,8 1,64 140,3 87,7 1,60 140,0 89,7 1,56 139,6 91,8 1,52 139,2 93,8 1,48 138,8 96,0 1,45 138,4 98,2 1,41

-37 147,0 88,6 1,66 146,6 90,6 1,62 146,3 92,6 1,58 145,9 94,7 1,54 145,5 96,9 1,50 145,1 99,0 1,46

-36 153,6 91,5 1,68 153,2 93,6 1,64 152,8 95,6 1,60 152,4 97,8 1,56 152,0 100,0 1,52

-35 160,0 96,6 1,66 159,6 98,7 1,62 159,1 100,9 1,58

-34 167,0 99,7 1,68 166,5 101,9 1,63

GM

T H

X 1

10-4

0 s

-33 174,2 102,9 1,69

19

Page 20: Technical Guide for Screw Compressor Packages easy definition HX -40

Condensation T 32 33 34 35 36 37 38

MODEL Evaporation

T Frig

P. Kw Abs P.

Kw COP Frig P. Kw

Abs P.

Kw COP Frig

P. KwAbs

P. Kw COP Frig P. Kw

Abs P. Kw COP Frig

P. Kw

Abs P.

Kw COP Frig

P. Kw

Abs P.

Kw COP

Frig P.

Kw

Abs P.

Kw COP

-45 98,4 91,8 1,07 97,8 94,0 1,04 97,2 96,3 1,01 96,6 98,6 0,98 95,9 100,9 0,95 95,2 103,3 0,92 94,5 105,8 0,89

-44 104,0 92,6 1,12 103,4 94,8 1,09 102,8 97,0 1,06 102,1 99,3 1,03 101,5 101,6 1,00 100,8 104,0 0,97 100,1 106,4 0,94

-43 109,7 93,4 1,17 109,1 95,6 1,14 108,5 97,8 1,11 107,9 100,0 1,08 107,2 102,3 1,05 106,5 104,7 1,02 105,9 107,1 0,99

-42 115,7 94,3 1,23 115,1 96,4 1,19 114,4 98,6 1,16 113,8 100,8 1,13 113,1 103,1 1,10 112,5 105,5 1,07 111,8 107,9 1,04

-41 121,8 95,2 1,28 121,2 97,3 1,25 120,6 99,5 1,21 119,9 101,7 1,18 119,3 104,0 1,15 118,6 106,3 1,12 117,9 108,7 1,08

-40 128,2 96,1 1,33 127,6 98,3 1,30 126,9 100,4 1,26 126,3 102,6 1,23 125,6 104,9 1,20 124,9 107,2 1,16 124,2 109,6 1,13

-39 134,9 97,1 1,39 134,2 99,2 1,35 133,6 101,4 1,32 132,9 103,6 1,28 132,2 105,9 1,25 131,5 108,2 1,22 130,7 110,5 1,18

-38 141,8 98,1 1,44 141,1 100,2 1,41 140,4 102,4 1,37 139,7 104,6 1,34 139,0 106,9 1,30 138,2 109,2 1,27 137,5 111,5 1,23

-37 148,3 101,3 1,46 147,5 103,4 1,43 146,8 105,6 1,39 146,1 107,9 1,35 145,3 110,2 1,32 144,5 112,5 1,28

-36 155,0 104,5 1,48 154,2 106,7 1,44 153,4 109,0 1,41 152,6 111,3 1,37 151,8 113,6 1,34

-35 161,1 110,1 1,46 160,2 112,4 1,43 159,4 114,7 1,39

-34 168,1 113,6 1,48 167,3 115,9 1,44

GM

T H

X 1

30-4

0

-33 175,5 117,1 1,50

-45 124,0 94,6 1,31 123,7 96,8 1,28 123,5 99,2 1,24 123,2 101,6 1,21 122,8 104,1 1,18 122,5 106,6 1,15 122,1 109,2 1,12

-44 130,5 95,4 1,37 130,3 97,6 1,33 130,1 100,0 1,30 129,8 102,3 1,27 129,5 104,8 1,24 129,2 107,3 1,20 128,8 109,9 1,17

-43 137,3 96,2 1,43 137,1 98,5 1,39 136,9 100,8 1,36 136,6 103,1 1,32 136,3 105,6 1,29 136,0 108,1 1,26 135,7 110,6 1,23

-42 144,3 97,1 1,49 144,1 99,3 1,45 143,9 101,6 1,42 143,6 104,0 1,38 143,4 106,4 1,35 143,1 108,9 1,31 142,8 111,4 1,28

-41 151,5 98,0 1,55 151,3 100,3 1,51 151,1 102,6 1,47 150,9 104,9 1,44 150,7 107,3 1,40 150,4 109,8 1,37 150,1 112,3 1,34

-40 158,9 99,0 1,61 158,8 101,2 1,57 158,6 103,5 1,53 158,4 105,9 1,50 158,2 108,3 1,46 157,9 110,7 1,43 157,6 113,2 1,39

-39 166,7 100,0 1,67 166,5 102,3 1,63 166,3 104,5 1,59 166,1 106,9 1,55 165,9 109,2 1,52 165,7 111,7 1,48 165,4 114,2 1,45

-38 174,7 101,1 1,73 174,5 103,3 1,69 174,3 105,6 1,65 174,1 107,9 1,61 173,9 110,3 1,58 173,7 112,7 1,54 173,4 115,2 1,51

-37 182,8 104,4 1,75 182,6 106,6 1,71 182,4 109,0 1,67 182,2 111,3 1,64 182,0 113,8 1,60 181,7 116,3 1,56

-36 191,2 107,7 1,77 191,0 110,1 1,73 190,7 112,4 1,70 190,5 114,9 1,66 190,3 117,4 1,62

-35 199,6 113,6 1,76 199,4 116,0 1,72 199,2 118,5 1,68

-34 208,6 117,2 1,78 208,3 119,7 1,74

GM

T H

X 1

30-4

0 s

-33 217,9 120,9 1,80

20

Page 21: Technical Guide for Screw Compressor Packages easy definition HX -40

Condensation T 32 33 34 35 36 37 38

MODEL Evaporation

T Frig

P. Kw Abs P.

Kw COP Frig P. Kw

Abs P.

Kw COP Frig

P. KwAbs

P. Kw COP Frig P. Kw

Abs P. Kw COP Frig

P. Kw

Abs P.

Kw COP Frig

P. Kw

Abs P.

Kw COP

Frig P.

Kw

Abs P.

Kw COP

-45 136,8 117,1 1,17 136,0 119,9 1,13 135,1 122,8 1,10 134,3 125,7 1,07 133,4 128,7 1,04 132,4 131,8 1,00 131,5 135,0 0,97

-44 144,6 118,1 1,22 143,7 120,9 1,19 142,9 123,7 1,16 142,0 126,6 1,12 141,1 129,6 1,09 140,2 132,6 1,06 139,2 135,8 1,03

-43 152,6 119,2 1,28 151,8 121,9 1,25 150,9 124,7 1,21 150,0 127,6 1,18 149,1 130,5 1,14 148,2 133,6 1,11 147,2 136,7 1,08

-42 160,9 120,3 1,34 160,0 123,0 1,30 159,2 125,8 1,27 158,3 128,6 1,23 157,4 131,5 1,20 156,4 134,5 1,16 155,5 137,6 1,13

-41 169,5 121,4 1,40 168,6 124,1 1,36 167,7 126,9 1,32 166,8 129,7 1,29 165,9 132,6 1,25 165,0 135,6 1,22 164,0 138,7 1,18

-40 178,4 122,6 1,45 177,5 125,3 1,42 176,6 128,1 1,38 175,7 130,9 1,34 174,7 133,8 1,31 173,8 136,7 1,27 172,8 139,8 1,24

-39 187,6 123,9 1,51 186,7 126,6 1,48 185,8 129,3 1,44 184,8 132,1 1,40 183,9 135,0 1,36 182,9 137,9 1,33 181,9 141,0 1,29

-38 197,3 125,2 1,58 196,3 127,8 1,54 195,3 130,6 1,50 194,4 133,4 1,46 193,3 136,3 1,42 192,3 139,2 1,38 191,3 142,2 1,35

-37 206,3 129,2 1,60 205,3 131,9 1,56 204,2 134,7 1,52 203,2 137,6 1,48 202,1 140,5 1,44 201,1 143,5 1,40

-36 215,6 133,3 1,62 214,5 136,1 1,58 213,4 139,0 1,54 212,3 141,9 1,50 211,2 144,9 1,46

-35 224,1 140,4 1,60 222,9 143,4 1,56 221,8 146,3 1,52

-34 233,9 144,8 1,62 232,7 147,8 1,57

GM

T H

X 1

80-4

0

-33 244,1 149,4 1,63

-45 172,6 120,8 1,43 172,3 123,7 1,39 172,0 126,7 1,36 171,6 129,8 1,32 171,1 133,0 1,29 170,7 136,2 1,25 170,2 139,5 1,22

-44 181,8 121,8 1,49 181,5 124,7 1,45 181,2 127,7 1,42 180,8 130,8 1,38 180,4 133,9 1,35 180,0 137,1 1,31 179,5 140,4 1,28

-43 191,2 122,9 1,56 190,9 125,8 1,52 190,6 128,8 1,48 190,3 131,8 1,44 189,9 134,9 1,41 189,5 138,1 1,37 189,1 141,3 1,34

-42 200,9 124,1 1,62 200,7 126,9 1,58 200,4 129,9 1,54 200,1 132,9 1,51 199,7 136,0 1,47 199,4 139,1 1,43 199,0 142,4 1,40

-41 211,0 125,3 1,68 210,7 128,1 1,64 210,5 131,1 1,61 210,2 134,0 1,57 209,9 137,1 1,53 209,5 140,2 1,49 209,1 143,5 1,46

-40 221,4 126,5 1,75 221,1 129,4 1,71 220,9 132,3 1,67 220,6 135,3 1,63 220,3 138,3 1,59 220,0 141,4 1,56 219,6 144,6 1,52

-39 232,1 127,8 1,82 231,9 130,7 1,77 231,6 133,6 1,73 231,4 136,5 1,69 231,1 139,6 1,66 230,8 142,7 1,62 230,4 145,9 1,58

-38 243,2 129,2 1,88 243,0 132,0 1,84 242,8 134,9 1,80 242,5 137,9 1,76 242,2 140,9 1,72 241,9 144,0 1,68 241,6 147,2 1,64

-37 254,5 133,4 1,91 254,3 136,3 1,87 254,0 139,2 1,82 253,8 142,3 1,78 253,5 145,4 1,74 253,1 148,6 1,70

-36 266,2 137,7 1,93 266,0 140,6 1,89 265,7 143,7 1,85 265,4 146,8 1,81 265,1 150,0 1,77

-35 278,0 145,2 1,92 277,7 148,3 1,87 277,4 151,4 1,83

-34 290,5 149,8 1,94 290,2 153,0 1,90

GM

T H

X 1

80-4

0 s

-33 303,5 154,5 1,96

21

Page 22: Technical Guide for Screw Compressor Packages easy definition HX -40

Condensation T 32 33 34 35 36 37 38

MODEL Evaporation

T Frig

P. Kw Abs P.

Kw COP Frig P. Kw

Abs P.

Kw COP Frig

P. KwAbs

P. Kw COP Frig P. Kw

Abs P. Kw COP Frig

P. Kw

Abs P.

Kw COP Frig

P. Kw

Abs P.

Kw COP

Frig P.

Kw

Abs P.

Kw COP

-45 151,0 133,1 1,13 150,1 136,3 1,10 149,2 139,5 1,07 148,2 142,8 1,04 147,2 146,3 1,01 146,2 149,8 0,98 145,1 153,4 0,95

-44 159,6 134,2 1,19 158,7 137,3 1,16 157,8 140,6 1,12 156,8 143,9 1,09 155,8 147,2 1,06 154,8 150,7 1,03 153,7 154,3 1,00

-43 168,4 135,4 1,24 167,5 138,5 1,21 166,6 141,7 1,18 165,6 145,0 1,14 164,6 148,3 1,11 163,6 151,8 1,08 162,5 155,3 1,05

-42 177,6 136,6 1,30 176,7 139,7 1,26 175,7 142,9 1,23 174,7 146,1 1,20 173,7 149,5 1,16 172,7 152,9 1,13 171,6 156,4 1,10

-41 187,1 138,0 1,36 186,1 141,0 1,32 185,1 144,2 1,28 184,1 147,4 1,25 183,1 150,7 1,22 182,1 154,1 1,18 181,0 157,6 1,15

-40 196,9 139,3 1,41 195,9 142,4 1,38 194,9 145,5 1,34 193,9 148,7 1,30 192,9 152,0 1,27 191,8 155,4 1,23 190,7 158,8 1,20

-39 207,1 140,8 1,47 206,1 143,8 1,43 205,1 146,9 1,40 204,0 150,1 1,36 202,9 153,4 1,32 201,9 156,8 1,29 200,7 160,2 1,25

-38 217,7 142,2 1,53 216,7 145,3 1,49 215,6 148,4 1,45 214,5 151,6 1,42 213,4 154,9 1,38 212,3 158,2 1,34 211,1 161,6 1,31

-37 227,7 146,8 1,55 226,6 149,9 1,51 225,4 153,1 1,47 224,3 156,4 1,43 223,1 159,7 1,40 221,9 163,1 1,36

-36 237,9 151,5 1,57 236,8 154,7 1,53 235,6 157,9 1,49 234,4 161,3 1,45 233,1 164,7 1,42

-35 247,3 159,6 1,55 246,1 162,9 1,51 244,8 166,3 1,47

-34 258,2 164,6 1,57 256,9 168,0 1,53

GM

T H

X 2

00-4

0

-33 269,5 169,7 1,59

-45 191,2 137,5 1,39 191,0 140,7 1,36 190,7 144,0 1,32 190,3 147,4 1,29 189,9 151,0 1,26 189,5 154,6 1,23 189,0 158,3 1,19

-44 201,1 138,6 1,45 200,8 141,8 1,42 200,6 145,1 1,38 200,2 148,5 1,35 199,9 152,0 1,31 199,5 155,6 1,28 199,0 159,3 1,25

-43 211,3 139,8 1,51 211,1 143,0 1,48 210,8 146,3 1,44 210,5 149,7 1,41 210,2 153,1 1,37 209,8 156,7 1,34 209,4 160,4 1,31

-42 221,9 141,1 1,57 221,7 144,3 1,54 221,4 147,5 1,50 221,1 150,9 1,47 220,8 154,4 1,43 220,5 157,9 1,40 220,1 161,5 1,36

-41 232,9 142,4 1,64 232,7 145,6 1,60 232,4 148,9 1,56 232,1 152,2 1,52 231,8 155,7 1,49 231,5 159,2 1,45 231,1 162,8 1,42

-40 244,3 143,8 1,70 244,0 147,0 1,66 243,8 150,2 1,62 243,5 153,6 1,59 243,2 157,0 1,55 242,9 160,6 1,51 242,5 164,2 1,48

-39 256,1 145,2 1,76 255,9 148,4 1,72 255,6 151,7 1,69 255,4 155,0 1,65 255,1 158,5 1,61 254,7 162,0 1,57 254,4 165,6 1,54

-38 268,3 146,7 1,83 268,1 149,9 1,79 267,9 153,2 1,75 267,6 156,5 1,71 267,3 160,0 1,67 267,0 163,5 1,63 266,7 167,1 1,60

-37 280,8 151,5 1,85 280,6 154,7 1,81 280,3 158,1 1,77 280,0 161,5 1,73 279,7 165,0 1,69 279,4 168,6 1,66

-36 293,7 156,3 1,88 293,5 159,7 1,84 293,2 163,1 1,80 292,9 166,7 1,76 292,5 170,3 1,72

-35 306,8 164,8 1,86 306,5 168,3 1,82 306,2 171,9 1,78

-34 320,6 170,1 1,89 320,3 173,7 1,84

GM

T H

X 2

00-4

0 s

-33 334,9 175,5 1,91

22

Page 23: Technical Guide for Screw Compressor Packages easy definition HX -40

Condensation T 32 33 34 35 36 37 38

MODEL Evaporation

T Frig

P. Kw Abs P.

Kw COP Frig P. Kw

Abs P.

Kw COP Frig

P. KwAbs

P. Kw COP Frig P. Kw

Abs P. Kw COP Frig

P. Kw

Abs P.

Kw COP Frig

P. Kw

Abs P.

Kw COP

Frig P.

Kw

Abs P.

Kw COP

-45 167,2 150,9 1,11 166,2 154,5 1,08 165,2 158,3 1,04 164,1 162,1 1,01 163,0 166,1 0,98 161,9 170,2 0,95 160,7 174,3 0,92

-44 176,7 151,6 1,17 175,7 155,3 1,13 174,6 159,0 1,10 173,6 162,8 1,07 172,5 166,8 1,03 171,3 170,8 1,00 170,2 174,9 0,97

-43 186,5 152,5 1,22 185,4 156,1 1,19 184,4 159,8 1,15 183,3 163,6 1,12 182,2 167,5 1,09 181,1 171,6 1,06 179,9 175,7 1,02

-42 196,6 153,4 1,28 195,6 157,0 1,25 194,5 160,7 1,21 193,4 164,5 1,18 192,3 168,4 1,14 191,2 172,4 1,11 190,0 176,5 1,08

-41 207,1 154,4 1,34 206,0 158,0 1,30 205,0 161,7 1,27 203,9 165,5 1,23 202,7 169,4 1,20 201,6 173,3 1,16 200,4 177,4 1,13

-40 218,0 155,5 1,40 216,9 159,1 1,36 215,8 162,8 1,33 214,7 166,5 1,29 213,5 170,4 1,25 212,3 174,4 1,22 211,1 178,4 1,18

-39 229,3 156,7 1,46 228,2 160,3 1,42 227,0 163,9 1,38 225,8 167,7 1,35 224,7 171,5 1,31 223,5 175,5 1,27 222,2 179,5 1,24

-38 241,0 157,9 1,53 239,9 161,5 1,49 238,7 165,2 1,45 237,5 168,9 1,41 236,2 172,7 1,37 235,0 176,7 1,33 233,7 180,7 1,29

-37 252,0 162,8 1,55 250,8 166,5 1,51 249,5 170,2 1,47 248,3 174,0 1,43 247,0 177,9 1,39 245,7 182,0 1,35

-36 263,4 167,8 1,57 262,1 171,6 1,53 260,8 175,4 1,49 259,4 179,3 1,45 258,1 183,3 1,41

-35 273,8 176,8 1,55 272,4 180,7 1,51 271,0 184,7 1,47

-34 285,8 182,2 1,57 284,4 186,2 1,53

GM

T H

X 2

20 -

40

-33 298,3 187,7 1,59

-45 210,4 155,3 1,35 210,1 159,2 1,32 209,6 163,1 1,29 209,2 167,1 1,25 208,6 171,3 1,22 208,1 175,5 1,19 207,4 179,9 1,15

-44 221,7 156,1 1,42 221,3 159,9 1,38 220,9 163,9 1,35 220,5 167,9 1,31 220,0 172,0 1,28 219,5 176,2 1,25 218,9 180,5 1,21

-43 233,2 157,0 1,49 232,9 160,8 1,45 232,5 164,7 1,41 232,1 168,7 1,38 231,7 172,8 1,34 231,2 177,0 1,31 230,6 181,3 1,27

-42 245,1 158,0 1,55 244,8 161,8 1,51 244,5 165,6 1,48 244,1 169,6 1,44 243,7 173,7 1,40 243,2 177,9 1,37 242,7 182,2 1,33

-41 257,4 159,0 1,62 257,1 162,8 1,58 256,8 166,7 1,54 256,4 170,6 1,50 256,0 174,7 1,47 255,6 178,9 1,43 255,1 183,2 1,39

-40 270,1 160,1 1,69 269,8 163,9 1,65 269,5 167,8 1,61 269,2 171,7 1,57 268,8 175,8 1,53 268,4 179,9 1,49 268,0 184,2 1,45

-39 283,2 161,3 1,76 282,9 165,1 1,71 282,6 168,9 1,67 282,3 172,9 1,63 281,9 177,0 1,59 281,6 181,1 1,55 281,2 185,3 1,52

-38 296,7 162,6 1,83 296,5 166,3 1,78 296,2 170,2 1,74 295,9 174,2 1,70 295,5 178,2 1,66 295,2 182,3 1,62 294,8 186,6 1,58

-37 310,5 167,7 1,85 310,2 171,5 1,81 309,9 175,5 1,77 309,6 179,5 1,72 309,2 183,6 1,68 308,9 187,9 1,64

-36 324,8 172,9 1,88 324,5 176,9 1,83 324,1 180,9 1,79 323,8 185,0 1,75 323,4 189,2 1,71

-35 339,2 182,4 1,86 338,8 186,5 1,82 338,5 190,7 1,77

-34 354,4 188,0 1,89 354,0 192,2 1,84

GM

T H

X 2

20 -

40 s

-33 370,2 193,8 1,91

23

Page 24: Technical Guide for Screw Compressor Packages easy definition HX -40

Performance of the unit with nominal Vi and fitted with condensing high pressure (apc) as optional

Condensation T 39 40 41 42 43 44 45

MODEL Evaporation

T

Frig. P.

Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P.

Kw COP Frig.

P. Kw Abs. P.

Kw COP Frig.

P. Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P. Kw COP

Frig. P.

Kw

Abs. P.

Kw COP

-45 26,4 36,5 0,72 26,0 37,4 0,70 25,6 38,2 0,67 25,1 39,1 0,64 24,6 40,0 0,62 24,2 41,0 0,59 23,7 41,9 0,56

-44 28,3 36,7 0,77 27,9 37,5 0,74 27,5 38,4 0,72 27,0 39,3 0,69 26,6 40,2 0,66 26,1 41,1 0,63 25,6 42,0 0,61

-43 30,2 36,9 0,82 29,8 37,7 0,79 29,4 38,6 0,76 29,0 39,4 0,73 28,5 40,3 0,71 28,1 41,2 0,68 27,6 42,2 0,65

-42 32,2 37,1 0,87 31,8 37,9 0,84 31,4 38,8 0,81 31,0 39,6 0,78 30,5 40,5 0,75 30,1 41,4 0,73 29,6 42,3 0,70

-41 34,3 37,4 0,92 33,9 38,2 0,89 33,5 39,0 0,86 33,0 39,9 0,83 32,6 40,7 0,80 32,1 41,6 0,77 31,7 42,5 0,74

-40 36,4 37,6 0,97 36,0 38,4 0,94 35,6 39,3 0,91 35,1 40,1 0,88 34,7 41,0 0,85 34,2 41,9 0,82 33,8 42,8 0,79

-39 38,6 37,9 1,02 38,2 38,7 0,99 37,8 39,5 0,96 37,3 40,4 0,92 36,9 41,2 0,89 36,4 42,1 0,87 36,0 43,0 0,84

-38 40,8 38,2 1,07 40,4 39,0 1,04 40,0 39,8 1,00 39,6 40,6 0,97 39,1 41,5 0,94 38,7 42,4 0,91 38,2 43,3 0,88

-37 42,8 39,3 1,09 42,3 40,1 1,06 41,9 40,9 1,02 41,4 41,8 0,99 41,0 42,7 0,96 40,5 43,6 0,93

-36 44,7 40,4 1,11 44,3 41,3 1,07 43,9 42,1 1,04 43,4 43,0 1,01 42,9 43,9 0,98

-35 46,3 42,4 1,09 45,9 43,3 1,06 45,4 44,2 1,03

-34 48,4 43,7 1,11 48,0 44,5 1,08

GM

T H

X 4

0-40

apc

-33 50,6 44,9 1,13

-45 32,5 40,3 0,81 32,1 41,3 0,78 31,6 42,4 0,75 31,1 43,4 0,72 30,6 44,5 0,69 30,1 45,6 0,66 29,6 46,8 0,63

-44 34,7 40,5 0,86 34,3 41,5 0,83 33,8 42,5 0,80 33,3 43,5 0,77 32,9 44,6 0,74 32,3 45,7 0,71 31,8 46,8 0,68

-43 37,0 40,6 0,91 36,5 41,6 0,88 36,1 42,6 0,85 35,6 43,7 0,82 35,2 44,7 0,79 34,7 45,8 0,76 34,1 46,9 0,73

-42 39,3 40,8 0,96 38,9 41,8 0,93 38,4 42,8 0,90 38,0 43,8 0,87 37,5 44,9 0,84 37,0 46,0 0,81 36,5 47,1 0,78

-41 41,7 41,0 1,02 41,3 42,0 0,98 40,9 43,0 0,95 40,4 44,0 0,92 39,9 45,0 0,89 39,5 46,1 0,86 39,0 47,2 0,83

-40 44,2 41,3 1,07 43,8 42,2 1,04 43,4 43,2 1,00 42,9 44,2 0,97 42,5 45,2 0,94 42,0 46,3 0,91 41,5 47,4 0,88

-39 46,7 41,5 1,13 46,3 42,5 1,09 45,9 43,4 1,06 45,5 44,4 1,02 45,0 45,5 0,99 44,6 46,5 0,96 44,1 47,6 0,93

-38 49,4 41,8 1,18 49,0 42,7 1,15 48,6 43,7 1,11 48,2 44,7 1,08 47,7 45,7 1,04 47,2 46,7 1,01 46,7 47,8 0,98

-37 51,8 43,0 1,20 51,3 44,0 1,17 50,9 45,0 1,13 50,5 46,0 1,10 50,0 47,0 1,06 49,5 48,1 1,03

-36 54,2 44,3 1,22 53,8 45,3 1,19 53,3 46,3 1,15 52,8 47,3 1,12 52,3 48,3 1,08

-35 56,3 46,6 1,21 55,8 47,6 1,17 55,3 48,6 1,14

-34 58,8 47,9 1,23 58,3 48,9 1,19

GM

T H

X 4

0-40

apc

s

-33 61,5 49,3 1,25

24

Page 25: Technical Guide for Screw Compressor Packages easy definition HX -40

Condensation T 39 40 41 42 43 44 45

MODEL Evaporation

T

Frig. P.

Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P.

Kw COP Frig.

P. Kw Abs. P.

Kw COP Frig.

P. Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P. Kw COP

Frig. P.

Kw

Abs. P.

Kw COP

-45 38,2 50,3 0,76 37,7 51,4 0,73 37,2 52,6 0,71 36,6 53,8 0,68 36,0 55,1 0,65 35,4 56,4 0,63 34,8 57,7 0,60

-44 40,9 50,5 0,81 40,3 51,6 0,78 39,8 52,8 0,75 39,2 54,0 0,73 38,7 55,3 0,70 38,1 56,5 0,67 37,5 57,8 0,65

-43 43,5 50,7 0,86 43,0 51,9 0,83 42,5 53,1 0,80 41,9 54,2 0,77 41,4 55,5 0,75 40,8 56,7 0,72 40,2 58,0 0,69

-42 46,3 51,0 0,91 45,8 52,2 0,88 45,3 53,3 0,85 44,7 54,5 0,82 44,2 55,7 0,79 43,6 57,0 0,76 43,0 58,2 0,74

-41 49,2 51,3 0,96 48,6 52,5 0,93 48,1 53,6 0,90 47,6 54,8 0,87 47,0 56,0 0,84 46,4 57,2 0,81 45,8 58,5 0,78

-40 52,1 51,7 1,01 51,6 52,8 0,98 51,1 54,0 0,95 50,5 55,1 0,92 50,0 56,3 0,89 49,4 57,5 0,86 48,8 58,8 0,83

-39 55,2 52,1 1,06 54,6 53,2 1,03 54,1 54,3 1,00 53,6 55,5 0,97 53,0 56,7 0,94 52,4 57,9 0,91 51,8 59,1 0,88

-38 58,3 52,5 1,11 57,8 53,6 1,08 57,3 54,7 1,05 56,7 55,9 1,01 56,1 57,0 0,98 55,6 58,2 0,95 55,0 59,5 0,92

-37 61,1 54,0 1,13 60,5 55,1 1,10 60,0 56,3 1,07 59,4 57,4 1,03 58,8 58,6 1,00 58,2 59,9 0,97

-36 63,9 55,6 1,15 63,3 56,7 1,12 62,7 57,9 1,08 62,1 59,1 1,05 61,5 60,3 1,02

-35 66,2 58,3 1,14 65,6 59,5 1,10 65,0 60,7 1,07

-34 69,2 60,0 1,15 68,6 61,2 1,12

GM

T H

X 6

0-40

apc

-33 72,3 61,7 1,17

-45 48,2 54,3 0,89 47,6 55,7 0,86 47,1 57,0 0,83 46,5 58,4 0,80 46,0 59,9 0,77 45,3 61,3 0,74 44,7 62,9 0,71

-44 51,2 54,6 0,94 50,7 55,9 0,91 50,2 57,2 0,88 49,7 58,6 0,85 49,1 60,0 0,82 48,5 61,5 0,79 47,9 63,0 0,76

-43 54,4 54,8 0,99 54,0 56,1 0,96 53,4 57,4 0,93 52,9 58,8 0,90 52,3 60,2 0,87 51,8 61,7 0,84 51,1 63,1 0,81

-42 57,7 55,1 1,05 57,2 56,4 1,02 56,7 57,7 0,98 56,2 59,0 0,95 55,7 60,4 0,92 55,1 61,9 0,89 54,5 63,3 0,86

-41 61,1 55,4 1,10 60,7 56,7 1,07 60,2 58,0 1,04 59,6 59,3 1,01 59,1 60,7 0,97 58,5 62,1 0,94 57,9 63,6 0,91

-40 64,6 55,7 1,16 64,2 57,0 1,13 63,7 58,3 1,09 63,2 59,6 1,06 62,6 61,0 1,03 62,1 62,4 1,00 61,5 63,8 0,96

-39 68,3 56,1 1,22 67,8 57,4 1,18 67,3 58,6 1,15 66,8 60,0 1,11 66,3 61,3 1,08 65,7 62,7 1,05 65,2 64,1 1,02

-38 72,0 56,5 1,28 71,6 57,7 1,24 71,1 59,0 1,20 70,6 60,3 1,17 70,1 61,7 1,14 69,5 63,1 1,10 69,0 64,5 1,07

-37 75,5 58,1 1,30 75,0 59,4 1,26 74,5 60,7 1,23 74,0 62,1 1,19 73,4 63,4 1,16 72,9 64,8 1,12

-36 79,0 59,8 1,32 78,5 61,1 1,28 78,0 62,5 1,25 77,5 63,8 1,21 76,9 65,2 1,18

-35 82,2 62,9 1,31 81,6 64,3 1,27 81,1 65,7 1,23

-34 85,9 64,7 1,33 85,4 66,1 1,29

GM

T H

X 6

0-40

apc

s

-33 89,8 66,6 1,35

25

Page 26: Technical Guide for Screw Compressor Packages easy definition HX -40

Condensation T 39 40 41 42 43 44 45

MODEL Evaporation

T

Frig. P.

Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P.

Kw COP Frig.

P. Kw Abs. P.

Kw COP Frig.

P. Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P. Kw COP

Frig. P.

Kw

Abs. P.

Kw COP

-45 49,0 62,8 0,78 48,3 64,2 0,75 47,7 65,7 0,73 47,1 67,2 0,70 46,4 68,8 0,67 45,7 70,4 0,65 45,0 72,0 0,62

-44 52,2 63,0 0,83 51,6 64,5 0,80 51,0 66,0 0,77 50,3 67,5 0,75 49,7 69,0 0,72 49,0 70,6 0,69 48,3 72,2 0,67

-43 55,6 63,4 0,88 55,0 64,8 0,85 54,4 66,3 0,82 53,7 67,8 0,79 53,0 69,3 0,77 52,4 70,8 0,74 51,7 72,4 0,71

-42 59,1 63,7 0,93 58,5 65,2 0,90 57,8 66,6 0,87 57,2 68,1 0,84 56,5 69,6 0,81 55,8 71,1 0,78 55,1 72,7 0,76

-41 62,6 64,1 0,98 62,0 65,5 0,95 61,4 67,0 0,92 60,8 68,5 0,89 60,1 70,0 0,86 59,4 71,5 0,83 58,7 73,1 0,80

-40 66,3 64,6 1,03 65,7 66,0 1,00 65,1 67,4 0,97 64,5 68,9 0,94 63,8 70,4 0,91 63,1 71,9 0,88 62,4 73,4 0,85

-39 70,2 65,0 1,08 69,6 66,4 1,05 68,9 67,9 1,02 68,3 69,3 0,99 67,6 70,8 0,95 66,9 72,3 0,93 66,2 73,9 0,90

-38 74,2 65,6 1,13 73,5 66,9 1,10 72,9 68,3 1,07 72,2 69,8 1,03 71,5 71,3 1,00 70,9 72,8 0,97 70,1 74,3 0,94

-37 77,6 67,5 1,15 77,0 68,9 1,12 76,3 70,3 1,09 75,6 71,8 1,05 74,9 73,3 1,02 74,2 74,8 0,99

-36 81,2 69,4 1,17 80,6 70,9 1,14 79,9 72,3 1,10 79,1 73,8 1,07 78,4 75,3 1,04

-35 84,2 72,9 1,16 83,5 74,4 1,12 82,8 75,9 1,09

-34 88,1 75,0 1,17 87,3 76,5 1,14

GM

T H

X 7

0-40

apc

-33 92,0 77,1 1,19

-45 62,2 67,1 0,93 61,6 68,8 0,90 61,0 70,4 0,87 60,4 72,1 0,84 59,8 73,9 0,81 59,1 75,7 0,78 58,3 77,5 0,75

-44 66,1 67,4 0,98 65,5 69,0 0,95 65,0 70,7 0,92 64,3 72,4 0,89 63,7 74,1 0,86 63,0 75,9 0,83 62,3 77,7 0,80

-43 70,1 67,7 1,03 69,6 69,3 1,00 69,0 71,0 0,97 68,4 72,6 0,94 67,8 74,3 0,91 67,1 76,1 0,88 66,4 77,9 0,85

-42 74,2 68,1 1,09 73,7 69,7 1,06 73,2 71,3 1,03 72,6 72,9 0,99 72,0 74,6 0,96 71,3 76,4 0,93 70,6 78,2 0,90

-41 78,5 68,5 1,15 78,0 70,1 1,11 77,4 71,7 1,08 76,9 73,3 1,05 76,3 75,0 1,02 75,6 76,7 0,99 75,0 78,5 0,96

-40 82,9 68,9 1,20 82,4 70,5 1,17 81,9 72,1 1,14 81,3 73,7 1,10 80,7 75,4 1,07 80,1 77,1 1,04 79,5 78,8 1,01

-39 87,5 69,4 1,26 87,0 71,0 1,23 86,5 72,5 1,19 85,9 74,1 1,16 85,3 75,8 1,13 84,7 77,5 1,09 84,1 79,2 1,06

-38 92,2 69,9 1,32 91,7 71,4 1,28 91,2 73,0 1,25 90,7 74,6 1,21 90,1 76,3 1,18 89,5 77,9 1,15 88,8 79,7 1,11

-37 96,6 72,0 1,34 96,1 73,5 1,31 95,6 75,1 1,27 95,0 76,8 1,24 94,4 78,4 1,20 93,8 80,2 1,17

-36 101,2 74,1 1,37 100,6 75,7 1,33 100,1 77,3 1,29 99,5 79,0 1,26 98,8 80,7 1,23

-35 105,3 77,9 1,35 104,7 79,5 1,32 104,1 81,2 1,28

-34 110,2 80,1 1,37 109,5 81,8 1,34

GM

T H

X 7

0-40

apc

s

-33 115,2 82,4 1,40

26

Page 27: Technical Guide for Screw Compressor Packages easy definition HX -40

Condensation T 39 40 41 42 43 44 45

MODEL Evaporation

T

Frig. P.

Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P.

Kw COP Frig.

P. Kw Abs. P.

Kw COP Frig.

P. Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P. Kw COP

Frig. P.

Kw

Abs. P.

Kw COP

-45 59,2 74,8 0,79 58,5 76,6 0,76 57,8 78,3 0,74 57,0 80,2 0,71 56,3 82,0 0,69 55,5 83,9 0,66 54,7 85,9 0,64

-44 63,1 75,2 0,84 62,4 76,9 0,81 61,7 78,7 0,78 60,9 80,5 0,76 60,2 82,3 0,73 59,4 84,2 0,71 58,6 86,1 0,68

-43 67,1 75,6 0,89 66,4 77,3 0,86 65,7 79,0 0,83 65,0 80,8 0,80 64,2 82,6 0,78 63,4 84,5 0,75 62,6 86,4 0,72

-42 71,2 76,0 0,94 70,5 77,7 0,91 69,8 79,4 0,88 69,1 81,2 0,85 68,3 83,0 0,82 67,6 84,9 0,80 66,8 86,8 0,77

-41 75,5 76,5 0,99 74,8 78,2 0,96 74,1 79,9 0,93 73,4 81,7 0,90 72,6 83,4 0,87 71,8 85,3 0,84 71,0 87,2 0,81

-40 79,9 77,0 1,04 79,2 78,7 1,01 78,5 80,4 0,98 77,8 82,1 0,95 77,0 83,9 0,92 76,2 85,7 0,89 75,4 87,6 0,86

-39 84,5 77,6 1,09 83,8 79,3 1,06 83,1 80,9 1,03 82,3 82,7 1,00 81,5 84,4 0,97 80,8 86,3 0,94 80,0 88,1 0,91

-38 89,3 78,2 1,14 88,5 79,8 1,11 87,8 81,5 1,08 87,0 83,3 1,05 86,3 85,0 1,01 85,5 86,8 0,98 84,6 88,6 0,95

-37 93,5 80,5 1,16 92,7 82,2 1,13 91,9 83,9 1,10 91,1 85,6 1,06 90,3 87,4 1,03 89,5 89,2 1,00

-36 97,8 82,8 1,18 97,0 84,5 1,15 96,2 86,3 1,12 95,4 88,0 1,08 94,5 89,9 1,05

-35 101,4 86,9 1,17 100,6 88,7 1,13 99,7 90,5 1,10

-34 106,0 89,4 1,19 105,1 91,2 1,15

GM

T H

X 9

0-40

apc

-33 110,7 92,0 1,20

-45 75,4 79,5 0,95 74,8 81,4 0,92 74,1 83,4 0,89 73,4 85,4 0,86 72,7 87,5 0,83 72,0 89,6 0,80 71,2 91,8 0,78

-44 80,0 79,9 1,00 79,4 81,8 0,97 78,8 83,7 0,94 78,1 85,7 0,91 77,4 87,7 0,88 76,7 89,8 0,85 75,9 92,0 0,83

-43 84,8 80,3 1,06 84,2 82,1 1,03 83,6 84,0 0,99 82,9 86,0 0,96 82,3 88,0 0,93 81,5 90,1 0,90 80,8 92,2 0,88

-42 89,7 80,7 1,11 89,2 82,6 1,08 88,6 84,5 1,05 87,9 86,4 1,02 87,2 88,4 0,99 86,5 90,5 0,96 85,8 92,6 0,93

-41 94,8 81,2 1,17 94,3 83,0 1,14 93,7 84,9 1,10 93,0 86,8 1,07 92,4 88,8 1,04 91,7 90,9 1,01 91,0 92,9 0,98

-40 100,1 81,7 1,23 99,6 83,5 1,19 99,0 85,4 1,16 98,3 87,3 1,13 97,7 89,3 1,09 97,0 91,3 1,06 96,3 93,4 1,03

-39 105,6 82,3 1,28 105,0 84,1 1,25 104,4 86,0 1,21 103,8 87,9 1,18 103,2 89,8 1,15 102,5 91,8 1,12 101,8 93,9 1,08

-38 111,2 82,9 1,34 110,7 84,7 1,31 110,1 86,5 1,27 109,5 88,4 1,24 108,9 90,4 1,20 108,2 92,4 1,17 107,5 94,4 1,14

-37 116,5 85,3 1,37 115,9 87,2 1,33 115,3 89,1 1,30 114,7 91,0 1,26 114,1 93,0 1,23 113,4 95,0 1,19

-36 122,0 87,9 1,39 121,4 89,7 1,35 120,8 91,6 1,32 120,1 93,6 1,28 119,4 95,6 1,25

-35 127,0 92,3 1,38 126,4 94,3 1,34 125,7 96,3 1,31

-34 132,9 95,0 1,40 132,2 97,0 1,36

GM

T H

X 9

0-40

apc

s

-33 138,9 97,8 1,42

27

Page 28: Technical Guide for Screw Compressor Packages easy definition HX -40

Condensation T 39 40 41 42 43 44 45

MODEL Evaporation

T

Frig. P.

Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P.

Kw COP Frig.

P. Kw Abs. P.

Kw COP Frig.

P. Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P. Kw COP

Frig. P.

Kw

Abs. P.

Kw COP

-45 77,2 89,7 0,86 76,4 91,9 0,83 75,6 94,1 0,80 74,7 96,4 0,78 73,9 98,7 0,75 72,9 101,1 0,72 71,9 103,5 0,70

-44 81,9 90,2 0,91 81,2 92,4 0,88 80,4 94,6 0,85 79,6 96,8 0,82 78,7 99,1 0,79 77,8 101,4 0,77 76,9 103,8 0,74

-43 86,8 90,8 0,96 86,1 92,9 0,93 85,3 95,1 0,90 84,5 97,3 0,87 83,7 99,5 0,84 82,8 101,9 0,81 81,9 104,2 0,79

-42 91,8 91,4 1,00 91,1 93,5 0,97 90,3 95,6 0,94 89,5 97,8 0,92 88,7 100,1 0,89 87,9 102,4 0,86 87,0 104,7 0,83

-41 96,9 92,1 1,05 96,2 94,1 1,02 95,4 96,3 0,99 94,7 98,4 0,96 93,9 100,7 0,93 93,0 102,9 0,90 92,2 105,3 0,88

-40 102,1 92,8 1,10 101,4 94,8 1,07 100,7 96,9 1,04 99,9 99,1 1,01 99,2 101,3 0,98 98,3 103,6 0,95 97,5 105,9 0,92

-39 107,5 93,5 1,15 106,8 95,6 1,12 106,1 97,7 1,09 105,4 99,8 1,06 104,6 102,0 1,03 103,8 104,2 1,00 102,9 106,5 0,97

-38 113,1 94,3 1,20 112,4 96,4 1,17 111,7 98,5 1,13 110,9 100,6 1,10 110,1 102,8 1,07 109,3 105,0 1,04 108,5 107,3 1,01

-37 118,2 97,2 1,22 117,4 99,3 1,18 116,7 101,4 1,15 115,9 103,6 1,12 115,1 105,8 1,09 114,2 108,1 1,06

-36 123,4 100,2 1,23 122,6 102,3 1,20 121,8 104,4 1,17 121,0 106,7 1,13 120,2 108,9 1,10

-35 128,0 105,4 1,21 127,1 107,6 1,18 126,3 109,8 1,15

-34 133,5 108,5 1,23 132,6 110,7 1,20

GM

T H

X 1

10-4

0 a

pc

-33 139,2 111,7 1,25

-45 95,7 95,6 1,00 95,0 98,0 0,97 94,3 100,4 0,94 93,5 102,9 0,91 92,6 105,5 0,88 91,7 108,2 0,85 90,7 110,9 0,82

-44 101,4 96,1 1,05 100,7 98,5 1,02 100,0 100,9 0,99 99,2 103,4 0,96 98,4 106,0 0,93 97,5 108,6 0,90 96,6 111,3 0,87

-43 107,1 96,7 1,11 106,5 99,1 1,07 105,8 101,5 1,04 105,1 103,9 1,01 104,3 106,5 0,98 103,5 109,1 0,95 102,6 111,8 0,92

-42 112,9 97,3 1,16 112,3 99,7 1,13 111,7 102,1 1,09 111,0 104,5 1,06 110,3 107,1 1,03 109,5 109,6 1,00 108,7 112,3 0,97

-41 118,9 98,0 1,21 118,4 100,4 1,18 117,8 102,7 1,15 117,1 105,2 1,11 116,4 107,7 1,08 115,7 110,2 1,05 114,9 112,9 1,02

-40 125,1 98,8 1,27 124,5 101,1 1,23 124,0 103,5 1,20 123,3 105,9 1,16 122,7 108,4 1,13 122,0 110,9 1,10 121,2 113,5 1,07

-39 131,4 99,6 1,32 130,9 101,9 1,28 130,3 104,2 1,25 129,7 106,6 1,22 129,1 109,1 1,18 128,4 111,6 1,15 127,7 114,2 1,12

-38 137,9 100,4 1,37 137,4 102,7 1,34 136,8 105,0 1,30 136,3 107,4 1,27 135,7 109,9 1,23 135,0 112,4 1,20 134,3 115,0 1,17

-37 144,1 103,6 1,39 143,6 105,9 1,36 143,0 108,3 1,32 142,4 110,7 1,29 141,8 113,2 1,25 141,1 115,8 1,22

-36 150,5 106,8 1,41 150,0 109,2 1,37 149,4 111,6 1,34 148,8 114,1 1,30 148,1 116,7 1,27

-35 156,6 112,5 1,39 156,0 115,0 1,36 155,3 117,6 1,32

-34 163,4 116,0 1,41 162,8 118,5 1,37

GM

T H

X 1

10-4

0 ap

c s

-33 170,5 119,6 1,43

28

Page 29: Technical Guide for Screw Compressor Packages easy definition HX -40

Condensation T 39 40 41 42 43 44 45

MODEL Evaporation

T

Frig. P.

Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P.

Kw COP Frig.

P. Kw Abs. P.

Kw COP Frig.

P. Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P. Kw COP

Frig. P.

Kw

Abs. P.

Kw COP

-45 93,8 108,4 0,87 93,0 111,0 0,84 92,3 113,7 0,81 91,4 116,4 0,79 90,6 119,2 0,76 89,7 122,1 0,73 88,8 125,0 0,71

-44 99,4 109,0 0,91 98,6 111,5 0,88 97,9 114,2 0,86 97,1 116,9 0,83 96,2 119,7 0,80 95,3 122,5 0,78 94,4 125,4 0,75

-43 105,1 109,6 0,96 104,4 112,2 0,93 103,6 114,8 0,90 102,8 117,5 0,88 102,0 120,2 0,85 101,1 123,0 0,82 100,2 125,9 0,80

-42 111,0 110,4 1,01 110,3 112,9 0,98 109,5 115,5 0,95 108,7 118,1 0,92 107,9 120,9 0,89 107,1 123,6 0,87 106,2 126,5 0,84

-41 117,1 111,2 1,05 116,4 113,7 1,02 115,6 116,2 0,99 114,8 118,9 0,97 114,0 121,6 0,94 113,2 124,3 0,91 112,3 127,1 0,88

-40 123,5 112,0 1,10 122,7 114,5 1,07 121,9 117,1 1,04 121,1 119,7 1,01 120,3 122,3 0,98 119,4 125,1 0,96 118,6 127,8 0,93

-39 130,0 112,9 1,15 129,2 115,4 1,12 128,4 118,0 1,09 127,6 120,5 1,06 126,8 123,2 1,03 125,9 125,9 1,00 125,0 128,7 0,97

-38 136,7 113,9 1,20 135,9 116,4 1,17 135,1 118,9 1,14 134,3 121,5 1,11 133,5 124,1 1,08 132,6 126,8 1,05 131,7 129,5 1,02

-37 142,9 117,4 1,22 142,1 119,9 1,19 141,3 122,5 1,15 140,4 125,1 1,12 139,5 127,8 1,09 138,6 130,5 1,06

-36 149,3 121,0 1,23 148,5 123,5 1,20 147,6 126,1 1,17 146,7 128,8 1,14 145,8 131,5 1,11

-35 155,0 127,2 1,22 154,1 129,9 1,19 153,2 132,6 1,16

-34 161,8 131,0 160,9 133,7 1,20

GM

T H

X 1

30-4

0 ap

c

-33 168,8 134,9 1,25

-45 121,7 111,9 1,09 121,2 114,6 1,06 120,7 117,5 1,03 120,1 120,3 1,00 119,5 123,3 0,97 118,9 126,3 0,94 118,2 129,4 0,91

-44 128,4 112,5 1,14 128,0 115,3 1,11 127,5 118,1 1,08 127,0 120,9 1,05 126,4 123,8 1,02 125,8 126,8 0,99 125,2 129,9 0,96

-43 135,3 113,3 1,19 134,9 116,0 1,16 134,5 118,7 1,13 134,0 121,5 1,10 133,5 124,4 1,07 132,9 127,4 1,04 132,3 130,4 1,01

-42 142,4 114,0 1,25 142,1 116,7 1,22 141,7 119,5 1,19 141,2 122,3 1,16 140,7 125,1 1,12 140,2 128,1 1,09 139,6 131,1 1,07

-41 149,8 114,9 1,30 149,4 117,5 1,27 149,0 120,3 1,24 148,6 123,0 1,21 148,1 125,9 1,18 147,6 128,8 1,15 147,1 131,8 1,12

-40 157,3 115,8 1,36 157,0 118,4 1,33 156,6 121,1 1,29 156,2 123,9 1,26 155,8 126,7 1,23 155,3 129,6 1,20 154,8 132,6 1,17

-39 165,1 116,7 1,41 164,8 119,4 1,38 164,4 122,0 1,35 164,1 124,8 1,31 163,7 127,6 1,28 163,2 130,5 1,25 162,7 133,4 1,22

-38 173,1 117,7 1,47 172,8 120,4 1,44 172,5 123,0 1,40 172,2 125,8 1,37 171,8 128,6 1,34 171,3 131,4 1,30 170,9 134,3 1,27

-37 181,2 121,4 1,49 180,8 124,1 1,46 180,5 126,8 1,42 180,1 129,6 1,39 179,7 132,4 1,36 179,3 135,3 1,32

-36 189,4 125,2 1,51 189,1 127,9 1,48 188,7 130,7 1,44 188,4 133,5 1,41 187,9 136,4 1,38

-35 197,7 131,8 1,50 197,3 134,6 1,47 196,9 137,5 1,43

-34 206,5 135,8 1,52 206,1 138,7 1,49

GM

T H

X 1

30-4

0 ap

c s

-33 215,6 139,9 1,54

29

Page 30: Technical Guide for Screw Compressor Packages easy definition HX -40

Condensation T

39 40 41 42 43 44 45 MODEL

Evaporation T

Frig. P.

Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P.

Kw COP Frig.

P. Kw Abs. P.

Kw COP Frig.

P. Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P. Kw COP

Frig. P.

Kw

Abs. P.

Kw COP

-45 130,5 138,2 0,94 129,4 141,6 0,91 128,3 145,0 0,89 127,2 148,5 0,86 126,0 152,0 0,83 124,8 155,7 0,80 123,6 159,5 0,77

-44 138,2 139,0 0,99 137,2 142,3 0,96 136,1 145,6 0,93 135,0 149,1 0,91 133,9 152,6 0,88 132,7 156,3 0,85 131,4 160,0 0,82

-43 146,2 139,8 1,05 145,2 143,1 1,01 144,2 146,4 0,98 143,1 149,8 0,95 141,9 153,3 0,93 140,7 156,9 0,90 139,5 160,6 0,87

-42 154,5 140,8 1,10 153,4 144,0 1,07 152,4 147,3 1,03 151,3 150,7 1,00 150,2 154,1 0,97 149,0 157,7 0,94 147,8 161,3 0,92

-41 163,0 141,8 1,15 161,9 145,0 1,12 160,9 148,3 1,09 159,8 151,6 1,05 158,6 155,0 1,02 157,5 158,5 0,99 156,2 162,1 0,96

-40 171,7 142,9 1,20 170,7 146,1 1,17 169,6 149,3 1,14 168,5 152,6 1,10 167,4 156,0 1,07 166,2 159,5 1,04 165,0 163,1 1,01

-39 180,8 144,0 1,26 179,8 147,2 1,22 178,7 150,4 1,19 177,6 153,7 1,15 176,4 157,1 1,12 175,2 160,6 1,09 174,0 164,1 1,06

-38 190,2 145,3 1,31 189,1 148,4 1,27 188,0 151,6 1,24 186,9 154,9 1,21 185,7 158,3 1,17 184,5 161,7 1,14 183,3 165,2 1,11

-37 198,9 149,7 1,33 197,7 152,9 1,29 196,6 156,2 1,26 195,4 159,5 1,22 194,2 162,9 1,19 192,9 166,4 1,16

-36 207,8 154,3 1,35 206,6 157,5 1,31 205,4 160,9 1,28 204,1 164,3 1,24 202,8 167,7 1,21

-35 215,7 162,3 1,33 214,5 165,6 1,29 213,1 169,1 1,26

-34 225,2 167,1 1,35 223,8 170,6 1,31

GM

T H

X 1

80-4

0 ap

c

-33 234,9 172,1 1,37

-45 169,6 142,9 1,19 169,0 146,4 1,15 168,3 150,0 1,12 167,6 153,6 1,09 166,8 157,4 1,06 166,0 161,2 1,03 165,1 165,2 1,00

-44 179,0 143,7 1,25 178,4 147,2 1,21 177,8 150,7 1,18 177,1 154,4 1,15 176,4 158,1 1,12 175,6 161,9 1,08 174,8 165,8 1,05

-43 188,6 144,7 1,30 188,1 148,1 1,27 187,5 151,6 1,24 186,9 155,2 1,20 186,2 158,9 1,17 185,5 162,6 1,14 184,7 166,5 1,11

-42 198,5 145,7 1,36 198,0 149,1 1,33 197,5 152,6 1,29 196,9 156,1 1,26 196,2 159,8 1,23 195,6 163,5 1,20 194,8 167,3 1,16

-41 208,7 146,8 1,42 208,2 150,1 1,39 207,7 153,6 1,35 207,2 157,1 1,32 206,6 160,7 1,29 205,9 164,5 1,25 205,2 168,2 1,22

-40 219,2 147,9 1,48 218,8 151,3 1,45 218,3 154,7 1,41 217,8 158,2 1,38 217,2 161,8 1,34 216,6 165,5 1,31 215,9 169,3 1,28

-39 230,0 149,1 1,54 229,6 152,5 1,51 229,2 155,9 1,47 228,7 159,4 1,43 228,2 163,0 1,40 227,6 166,6 1,37 226,9 170,4 1,33

-38 241,2 150,4 1,60 240,8 153,8 1,57 240,4 157,2 1,53 239,9 160,7 1,49 239,4 164,2 1,46 238,9 167,9 1,42 238,3 171,6 1,39

-37 252,4 155,1 1,63 252,0 158,5 1,59 251,5 162,0 1,55 251,1 165,5 1,52 250,5 169,2 1,48 250,0 172,9 1,45

-36 264,0 159,9 1,65 263,5 163,4 1,61 263,1 166,9 1,58 262,6 170,5 1,54 262,0 174,2 1,50

-35 275,5 168,4 1,64 275,0 172,0 1,60 274,5 175,7 1,56

-34 287,8 173,5 1,66 287,3 177,2 1,62

GM

T H

X 1

80-4

0 ap

c s

-33 300,6 178,8 1,68

30

Page 31: Technical Guide for Screw Compressor Packages easy definition HX -40

Condensation T 39 40 41 42 43 44 45

MODEL Evaporation

T

Frig. P.

Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P.

Kw COP Frig.

P. Kw Abs. P.

Kw COP Frig.

P. Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P. Kw COP

Frig. P.

Kw

Abs. P.

Kw COP

-45 144,0 157,1 0,92 142,9 160,8 0,89 141,7 164,7 0,86 140,5 168,7 0,83 139,2 172,8 0,81 137,8 176,9 0,78 136,4 181,2 0,75

-44 152,6 157,9 0,97 151,5 161,7 0,94 150,3 165,5 0,91 149,1 169,4 0,88 147,8 173,4 0,85 146,5 177,5 0,82 145,1 181,8 0,80

-43 161,4 158,9 1,02 160,3 162,6 0,99 159,1 166,4 0,96 157,9 170,3 0,93 156,6 174,2 0,90 155,3 178,3 0,87 154,0 182,5 0,84

-42 170,5 160,0 1,07 169,4 163,6 1,04 168,2 167,4 1,01 167,0 171,2 0,98 165,7 175,1 0,95 164,4 179,2 0,92 163,1 183,3 0,89

-41 179,9 161,1 1,12 178,7 164,7 1,08 177,6 168,5 1,05 176,4 172,3 1,02 175,1 176,2 0,99 173,8 180,2 0,96 172,5 184,2 0,94

-40 189,6 162,4 1,17 188,4 166,0 1,14 187,2 169,7 1,10 186,0 173,4 1,07 184,7 177,3 1,04 183,4 181,2 1,01 182,1 185,3 0,98

-39 199,6 163,7 1,22 198,4 167,3 1,19 197,2 170,9 1,15 196,0 174,7 1,12 194,7 178,5 1,09 193,4 182,5 1,06 192,0 186,5 1,03

-38 210,0 165,1 1,27 208,8 168,7 1,24 207,5 172,3 1,20 206,3 176,0 1,17 205,0 179,9 1,14 203,7 183,8 1,11 202,3 187,7 1,08

-37 219,5 170,1 1,29 218,2 173,8 1,26 217,0 177,5 1,22 215,6 181,3 1,19 214,3 185,2 1,16 212,9 189,1 1,13

-36 229,3 175,3 1,31 228,0 179,0 1,27 226,7 182,8 1,24 225,3 186,7 1,21 223,9 190,6 1,17

-35 238,1 184,4 1,29 236,7 188,2 1,26 235,3 192,2 1,22

-34 248,5 189,9 1,31 247,1 193,8 1,27

GM

T H

X 2

00-4

0 ap

c

-33 259,3 195,6 1,33

-45 188,5 162,0 1,16 187,9 165,9 1,13 187,3 169,9 1,10 186,6 174,0 1,07 185,8 178,2 1,04 184,9 182,6 1,01 184,0 187,0 0,98

-44 198,5 163,0 1,22 198,0 166,9 1,19 197,4 170,9 1,16 196,7 174,9 1,12 196,0 179,1 1,09 195,1 183,4 1,06 194,2 187,8 1,03

-43 208,9 164,1 1,27 208,4 167,9 1,24 207,8 171,9 1,21 207,2 175,9 1,18 206,5 180,1 1,15 205,7 184,3 1,12 204,8 188,7 1,09

-42 219,6 165,3 1,33 219,1 169,1 1,30 218,6 173,0 1,26 218,0 177,0 1,23 217,3 181,1 1,20 216,5 185,3 1,17 215,7 189,7 1,14

-41 230,7 166,5 1,39 230,2 170,3 1,35 229,7 174,2 1,32 229,1 178,2 1,29 228,5 182,3 1,25 227,8 186,5 1,22 227,0 190,8 1,19

-40 242,1 167,9 1,44 241,7 171,6 1,41 241,2 175,5 1,37 240,6 179,5 1,34 240,0 183,6 1,31 239,4 187,7 1,27 238,6 192,0 1,24

-39 254,0 169,3 1,50 253,6 173,0 1,47 253,1 176,9 1,43 252,6 180,9 1,40 252,0 184,9 1,36 251,3 189,1 1,33 250,6 193,3 1,30

-38 266,3 170,8 1,56 265,9 174,5 1,52 265,4 178,4 1,49 264,9 182,3 1,45 264,3 186,4 1,42 263,7 190,5 1,38 263,0 194,8 1,35

-37 278,6 176,1 1,58 278,1 179,9 1,55 277,6 183,9 1,51 277,1 187,9 1,47 276,5 192,0 1,44 275,8 196,3 1,41

-36 291,3 181,6 1,60 290,8 185,5 1,57 290,3 189,5 1,53 289,7 193,6 1,50 289,1 197,9 1,46

-35 304,0 191,2 1,59 303,4 195,3 1,55 302,8 199,5 1,52

-34 317,5 197,1 1,61 316,9 201,3 1,57

GM

T H

X 2

00-4

0 ap

c s

-33 331,6 203,1 1,63

31

Page 32: Technical Guide for Screw Compressor Packages easy definition HX -40

32

Condensation T 39 40 41 42 43 44 45

MODEL Evaporation

T

Frig. P.

Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P.

Kw COP Frig.

P. Kw Abs. P.

Kw COP Frig.

P. Kw

Abs. P.

Kw COP

Frig. P.

Kw

Abs. P. Kw COP

Frig. P.

Kw

Abs. P.

Kw COP

-45 159,5 178,6 0,89 158,2 183,0 0,86 156,9 187,4 0,84 155,5 192,0 0,81 154,1 196,7 0,78 152,6 201,6 0,76 151,0 206,5 0,73

-44 169,0 179,2 0,94 167,7 183,5 0,91 166,4 188,0 0,89 165,0 192,5 0,86 163,6 197,2 0,83 162,2 202,0 0,80 160,6 206,9 0,78

-43 178,7 179,9 0,99 177,5 184,2 0,96 176,2 188,6 0,93 174,8 193,2 0,91 173,4 197,8 0,88 172,0 202,6 0,85 170,5 207,4 0,82

-42 188,8 180,7 1,04 187,5 185,0 1,01 186,2 189,4 0,98 184,9 193,9 0,95 183,5 198,5 0,92 182,0 203,2 0,90 180,6 208,1 0,87

-41 199,1 181,6 1,10 197,9 185,8 1,06 196,6 190,2 1,03 195,2 194,7 1,00 193,8 199,3 0,97 192,4 204,0 0,94 190,9 208,8 0,91

-40 209,9 182,6 1,15 208,6 186,8 1,12 207,3 191,2 1,08 205,9 195,6 1,05 204,5 200,2 1,02 203,1 204,9 0,99 201,6 209,7 0,96

-39 220,9 183,6 1,20 219,6 187,9 1,17 218,3 192,2 1,14 216,9 196,7 1,10 215,5 201,2 1,07 214,1 205,8 1,04 212,6 210,6 1,01

-38 232,4 184,8 1,26 231,1 189,0 1,22 229,7 193,3 1,19 228,4 197,8 1,15 226,9 202,3 1,12 225,5 206,9 1,09 224,0 211,7 1,06

-37 243,0 190,3 1,28 241,6 194,6 1,24 240,2 199,0 1,21 238,7 203,5 1,17 237,2 208,1 1,14 235,7 212,8 1,11

-36 253,9 195,9 1,30 252,4 200,2 1,26 250,9 204,7 1,23 249,4 209,3 1,19 247,9 214,0 1,16

-35 263,6 206,1 1,28 262,0 210,7 1,24 260,4 215,3 1,21

-34 275,1 212,1 1,30 273,5 216,7 1,26

GM

T H

X 2

20 -

40 a

pc

-33 287,0 218,2 1,32

-45 206,8 184,3 1,12 206,0 188,9 1,09 205,2 193,6 1,06 204,3 198,4 1,03 203,4 203,4 1,00 202,3 208,4 0,97 201,2 213,6 0,94

-44 218,3 185,0 1,18 217,6 189,5 1,15 216,8 194,2 1,12 216,0 199,0 1,09 215,1 203,9 1,05 214,1 208,9 1,02 213,1 214,1 1,00

-43 230,1 185,7 1,24 229,4 190,3 1,21 228,7 194,9 1,17 227,9 199,7 1,14 227,1 204,6 1,11 226,2 209,6 1,08 225,2 214,7 1,05

-42 242,2 186,6 1,30 241,6 191,1 1,26 240,9 195,7 1,23 240,2 200,5 1,20 239,4 205,3 1,17 238,6 210,3 1,13 237,7 215,4 1,10

-41 254,6 187,5 1,36 254,1 192,0 1,32 253,5 196,6 1,29 252,8 201,3 1,26 252,1 206,2 1,22 251,3 211,1 1,19 250,4 216,2 1,16

-40 267,5 188,6 1,42 266,9 193,0 1,38 266,4 197,6 1,35 265,7 202,3 1,31 265,0 207,1 1,28 264,3 212,1 1,25 263,5 217,1 1,21

-39 280,7 189,7 1,48 280,2 194,2 1,44 279,7 198,7 1,41 279,1 203,4 1,37 278,4 208,2 1,34 277,7 213,1 1,30 276,9 218,1 1,27

-38 294,3 190,9 1,54 293,9 195,4 1,50 293,3 199,9 1,47 292,8 204,6 1,43 292,2 209,4 1,40 291,5 214,2 1,36 290,8 219,3 1,33

-37 308,0 196,6 1,57 307,5 201,2 1,53 306,9 205,8 1,49 306,4 210,6 1,45 305,7 215,5 1,42 305,0 220,5 1,38

-36 322,1 202,5 1,59 321,6 207,2 1,55 321,0 211,9 1,51 320,4 216,8 1,48 319,7 221,8 1,44

-35 336,1 213,3 1,58 335,5 218,2 1,54 334,9 223,1 1,50

-34 351,1 219,6 1,60 350,5 224,6 1,56

GM

T H

X 2

20 -

40 a

pc s

-33 366,7 226,1 1,62

Page 33: Technical Guide for Screw Compressor Packages easy definition HX -40

HOW TO SELECT THE MOTOR SIZE

The charts allow us to select the motor size to be used : nominal or oversized

Condensation T MODEL 32 33 34 35 36 37 38

Evaporation T Selection of motor size

-45 m m m m m m m -44 m m m m m m m -43 m m m m m m m -42 m m m m m m m -41 m m m m m m m -40 m m m m m m m -39 m m m m m m m -38 m m m m m m m -37 m m m m m m -36 m m m m m -35 m m m -34 m m

GM

T H

X 4

0 -4

0

-33 m

Condensation T MODEL 32 33 34 35 36 37 38

Evaporation T Selection of motor size

-45 m m m m m m m -44 m m m m m m m -43 m m m m m m m -42 m m m m m m m -41 m m m m m m m -40 m m m m m m m -39 m m m m m m m -38 m m m m m m m -37 m m m m m m -36 m m m m m -35 m m m -34 m m

GM

T H

X 4

0 -4

0 s

-33 m

33

Page 34: Technical Guide for Screw Compressor Packages easy definition HX -40

Condensation T MODEL 32 33 34 35 36 37 38

Evaporation T Selection of motor size

-45 m m m m m m m -44 m m m m m m m -43 m m m m m m m -42 m m m m m m m -41 m m m m m m m -40 m m m m m m m -39 m m m m m m m -38 m m m m m m m -37 m m m m m m -36 m m m m m -35 m m m -34 m m

GM

T H

X 6

0 -4

0

-33 m

Condensation T MODEL 32 33 34 35 36 37 38

Evaporation T Selection of motor size

-45 m m m m m m m -44 m m m m m m m -43 m m m m m m m -42 m m m m m m m -41 m m m m m m m -40 m m m m m m m -39 m m m m m m m -38 m m m m m m m -37 m m m m m m -36 m m m m m -35 m m m -34 m m

GM

T H

X 6

0 -4

0 s

-33 m

34

Page 35: Technical Guide for Screw Compressor Packages easy definition HX -40

Condensation T MODEL 32 33 34 35 36 37 38

Evaporation T Selection of motor size

-45 m m m m m m m -44 m m m m m m m -43 m m m m m m m -42 m m m m m m m -41 m m m m m m m -40 m m m m m m m -39 m m m m m m m -38 m m m m m m m -37 m m m m m m -36 m m m m m -35 m m m -34 m m

GM

T H

X 7

0 -4

0

-33 m

Condensation T MODEL 32 33 34 35 36 37 38

Evaporation T Selection of motor size

-45 m m m m m m m -44 m m m m m m m -43 m m m m m m m -42 m m m m m m m -41 m m m m m m m -40 m m m m m m m -39 m m m m m m m+ -38 m m m m m m m+ -37 m m m m m m+ -36 m m m m+ m+ -35 m m+ m+ -34 m+ m+

GM

T H

X 7

0 -4

0 s

-33 m+

35

Page 36: Technical Guide for Screw Compressor Packages easy definition HX -40

Condensation T MODEL 32 33 34 35 36 37 38

Evaporation T Selection of motor size

-45 m m m m m m m -44 m m m m m m m -43 m m m m m m m -42 m m m m m m m -41 m m m m m m m -40 m m m m m m m -39 m m m m m m m -38 m m m m m m m -37 m m m m m m -36 m m m m m -35 m m m -34 m m

GM

T H

X 9

0 -4

0

-33 m

Condensation T MODEL 32 33 34 35 36 37 38

Evaporation T Selection of motor size

-45 m m m m m m m -44 m m m m m m m -43 m m m m m m m -42 m m m m m m m -41 m m m m m m m -40 m m m m m m m -39 m m m m m m m -38 m m m m m m m+ -37 m m m m m m+ -36 m m m m m+ -35 m m+ m+ -34 m+ m+

GM

T H

X 9

0 -4

0 s

-33 m+

36

Page 37: Technical Guide for Screw Compressor Packages easy definition HX -40

Condensation T MODEL 32 33 34 35 36 37 38

Evaporation T Selection of motor size

-45 m m m m m m m -44 m m m m m m m -43 m m m m m m m -42 m m m m m m m -41 m m m m m m m -40 m m m m m m m -39 m m m m m m m -38 m m m m m m m -37 m m m m m m -36 m m m m m -35 m m m -34 m m

GM

T H

X 1

10 -

40

-33 m

Condensation T MODEL 32 33 34 35 36 37 38

Evaporation T Selection of motor size

-45 m m m m m m m -44 m m m m m m m -43 m m m m m m m -42 m m m m m m m -41 m m m m m m m -40 m m m m m m m -39 m m m m m m m -38 m m m m m m m -37 m m m m m m -36 m m m m m+ -35 m m m+ -34 m+ m+

GM

T H

X 1

10 -

40 s

-33 m+

37

Page 38: Technical Guide for Screw Compressor Packages easy definition HX -40

Condensation T MODEL 32 33 34 35 36 37 38

Evaporation T Selection of motor size

-45 m m m m m m m -44 m m m m m m m -43 m m m m m m m -42 m m m m m m m -41 m m m m m m m -40 m m m m m m m -39 m m m m m m m -38 m m m m m m m -37 m m m m m m -36 m m m m m -35 m m m -34 m m

GM

T H

X 1

30 -

40

-33 m

Condensation T MODEL 32 33 34 35 36 37 38

Evaporation T Selection of motor size

-45 m m m m m m m -44 m m m m m m m -43 m m m m m m m -42 m m m m m m m -41 m m m m m m m -40 m m m m m m m -39 m m m m m m m -38 m m m m m m m -37 m m m m m m -36 m m m m m -35 m m m -34 m m+

GM

T H

X 1

30 -

40 s

-33 m+

38

Page 39: Technical Guide for Screw Compressor Packages easy definition HX -40

Condensation T MODEL 32 33 34 35 36 37 38

Evaporation T Selection of motor size

-45 m m m m m m m -44 m m m m m m m -43 m m m m m m m -42 m m m m m m m -41 m m m m m m m -40 m m m m m m m -39 m m m m m m m -38 m m m m m m m -37 m m m m m m -36 m m m m m+ -35 m m m+ -34 m+ m+

GM

T H

X 1

80 -

40

-33 m+

Condensation T MODEL 32 33 34 35 36 37 38

Evaporation T Selection of motor size

-45 m m m m m m m -44 m m m m m m m -43 m m m m m m m -42 m m m m m m m -41 m m m m m m m -40 m m m m m m m+ -39 m m m m m m m+ -38 m m m m m m m+ -37 m m m m m+ m+ -36 m m m m+ m+ -35 m+ m+ m+ -34 m+ m+

GM

T H

X 1

80 -

40 s

-33 m+

39

Page 40: Technical Guide for Screw Compressor Packages easy definition HX -40

Condensation T MODEL 32 33 34 35 36 37 38

Evaporation T Selection of motor size

-45 m m m m m m m -44 m m m m m m m -43 m m m m m m m -42 m m m m m m m -41 m m m m m m m -40 m m m m m m m -39 m m m m m m m -38 m m m m m m m -37 m m m m m m -36 m m m m m -35 m m m -34 m m

GM

T H

X 2

00 -

40

-33 m

Condensation T MODEL 32 33 34 35 36 37 38

Evaporation T Selection of motor size

-45 m m m m m m m -44 m m m m m m m -43 m m m m m m m -42 m m m m m m m -41 m m m m m m m -40 m m m m m m m -39 m m m m m m m -38 m m m m m m m -37 m m m m m m -36 m m m m m -35 m m m -34 m m

GM

T H

X 2

00 -

40 s

-33 m

40

Page 41: Technical Guide for Screw Compressor Packages easy definition HX -40

Condensation T MODEL 32 33 34 35 36 37 38

Evaporation T Selection of motor size

-45 m m m m m m m -44 m m m m m m m -43 m m m m m m m -42 m m m m m m m -41 m m m m m m m -40 m m m m m m m -39 m m m m m m m -38 m m m m m m m+ -37 m m m m m m+ -36 m m m m m+ -35 m m+ m+ -34 m+ m+

GM

T H

X 2

20 -

40

-33 m+

Condensation T MODEL 32 33 34 35 36 37 38

Evaporation T Selection of motor size

-45 m m m m m m m -44 m m m m m m m+ -43 m m m m m m m+ -42 m m m m m m m+ -41 m m m m m m m+ -40 m m m m m m m+ -39 m m m m m m+ m+ -38 m m m m m m+ m+ -37 m m m m m+ m+ -36 m m m+ m+ m+ -35 m+ m+ m+ -34 m+ m+

GM

T H

X 2

20 -

40 s

-33 m+

41

Page 42: Technical Guide for Screw Compressor Packages easy definition HX -40

42

Sound levels.

SPL = Sound pressure levels, with reference to 2x10-5 Pa. The sound pressure levels are values calculated by applying the ISO-3744 relation (Eurovent 8/1) and refer to a distance of 1 meter away from the external surface of units operating in the open field with directivity factor 2 and the units operating in nominal conditions in the cooling mode.

SOUND PRESSURE LEVELS SPL AT 1 MT IN (dBA) MODEL 1 2 3 4 5 6 7 8 9 10 Min. Max. Medium

GMT HX 40 -40 78 82 82 84 82 81 81 81 85 83 78 85 82 GMT HX 60 -40 81 81 82 82 81 80 80 81 82 82 80 82 81 GMT HX 70 -40 81 82 82 82 82 81 81 83 85 83 81 85 82 GMT HX 90 -40 82 82 82 83 81 81 82 82 84 82 81 84 82 GMT HX 110 -40 83 82 83 84 83 82 82 82 85 83 82 85 83 GMT HX 130 -40 83 83 83 84 83 82 82 83 85 83 82 85 83 GMT HX 180 -40 82 82 84 85 82 82 82 83 85 84 82 85 83 GMT HX 200 -40 82 81 82 85 83 83 82 82 84 83 81 85 83 GMT HX 220 -40 81 82 83 84 83 82 81 83 84 83 81 84 83

Page 43: Technical Guide for Screw Compressor Packages easy definition HX -40

SOUND PRESSURE LEVELS SPL AT 5 MT IN (dBA) MODEL 1 2 3 4 5 6 7 8 9 10 Min. Max. Medium

GMT HX 40 -40 67 66 67 67 66 66 66 67 67 67 66 67 67 GMT HX 60 -40 71 71 71 68 70 71 72 73 71 70 68 73 71 GMT HX 70 -40 71 71 71 70 70 71 72 72 72 71 70 72 71 GMT HX 90 -40 72 72 72 71 70 72 73 73 71 72 70 73 72 GMT HX 110 -40 76 75 76 75 75 75 75 75 75 75 75 76 75 GMT HX 130 -40 75 75 75 75 75 76 75 75 75 75 75 76 75 GMT HX 180 -40 77 77 78 76 77 78 77 78 78 77 76 78 77 GMT HX 200 -40 72 72 70 71 70 72 73 72 70 70 70 73 71 GMT HX 220 -40 71 73 72 72 71 72 73 72 71 71 71 73 72

SOUND PRESSURE LEVELS SPL AT 10 MT IN (dBA) MODEL 1 2 3 4 5 6 7 8 9 10 Min. Max. Medium

GMT HX 40 -40 61 60 61 60 60 60 61 61 61 61 60 61 61 GMT HX 60 -40 61 62 61 59 60 61 61 61 61 61 59 62 61 GMT HX 70 -40 65 66 65 65 66 65 65 66 66 65 65 66 65 GMT HX 90 -40 65 66 66 65 65 66 66 65 66 66 65 66 66 GMT HX 110 -40 66 67 67 65 65 67 66 66 66 66 65 67 66 GMT HX 130 -40 69 69 69 68 69 69 68 69 69 70 68 70 69 GMT HX 180 -40 72 72 72 71 71 71 72 73 72 72 71 73 72 GMT HX 200 -40 65 65 65 65 65 65 65 66 66 65 65 66 65 GMT HX 220 -40 66 66 65 65 65 65 65 66 65 65 65 66 65

43

Page 44: Technical Guide for Screw Compressor Packages easy definition HX -40

Auxiliary data charts

The following 5 charts show how the refrigerating capacity and the absorbed power change when some of he following

parameters are modified:

Loss of charge in the suction line.

CHART 1. It shows two correction factors

1) FAP.F. which is applied to the refrigerating capacity

2) FAP.A. which is applied to the total power absorbed by the unit.

CORRECTION FACTOR fΔPASP ΔPASP (bar) FAP.F. FAP.A.

0,00 1,00 1,00

0,05 0,98 1,00

0,10 0,96 0,99

0,15 0,94 0,99

0,20 0,92 0,98

44

Loss of charge in the discharge line.

CHART 2. It shows two correction factors:

1) FDP.F. applied to the refrigerating capacity

2) FDP.A. applied to the total power absorbed by the unit.

CORRECTION FACTOR fΔPDES ΔPDES (bar) FDP.F. FDP.A.

0,00 1,00 0,99

0,10 1,00 1,00

0,15 1,00 1,00

0,20 1,00 1,00

0,30 1,00 1,01

Useful superheat.

CHART 3. It shows two correction factors:

1) FRUP.F., applied to the refrigerating capacity

2) FRUP.A , applied to the total power absorbed by the unit.

CORRECTION FACTOR fRU USEF. SUPERHEAT

(ºC) FRUP.F. FRUP.A.

0 1,00 1,00

1 1,00 1,00

2 1,00 1,00

3 0,99 1,00

4 0,99 1,00

Page 45: Technical Guide for Screw Compressor Packages easy definition HX -40

45

Total superheat.

CHART 4. It shows two correction factors:

1) FRTP.F., applied to the refrigerating capacity

2) FRTP.A., applied to the total power absorbed by the unit.

CORRECTION FACTOR FRT

TOTAL SUPERHEAT (ºC) FRTP.F. FRTP.A.

0 1,00 1,00

1 1,00 1,00

2 0,99 1,00

3 0,99 1,00

4 0,98 1,00

Subcooling CHART 5. It shows two correction factors:

1) FSP.F., applied to the refrigerating capacity

2) FSP.A.,, applied to the total power absorbed by the unit.

CORRECTION FACTOR FSUB.

SUBOOLING (ºC) FSP.F. FSP.A.

0 0,99 1,00

1 0,99 1,00

2 1,00 1,00

3,00 1,00 1,00

4 1,00 1,00

Page 46: Technical Guide for Screw Compressor Packages easy definition HX -40

OPERATING LIMITS.

The graphic below shows the area, in which it is guaranteed the proper operating of the units .

If the units operate outside this area, their guarantee will be immediately cancelled.

46

Page 47: Technical Guide for Screw Compressor Packages easy definition HX -40

47

4.

HOW TO SELECT A UNIT

1. In the section “Technical data and performance of the unit” the charts show the refrigerating capacity, total

absorbed power and COP of the units, depending on their evaporating and condensing temperatures.

2. All values of charts, included in this technical manual, have been obtained as the result of using the refrigerant

R717.

3. The values of the performance charts have been obtained as the result of considering a loss of charge in the

suction line of 0 bar. With other values of loss of charge, it is necessary to use the correction factor of FAP.F.

for refrigerating capacity and the correction factor FAP.A. for the absorbed power. Both factors are indicated in

CHART 1.

4. The values of the performance charts have been obtained as the result of considering a loss of charge of 0,15

bar. With other values of loss of charge, it is necessary to use the correction factor FDP.F. for the refrigerating

capacity and FDP.A. for the absorbed power. Both factors are indicated in CHART 2.

5. The values of performance charts have been obtained as the result of considering a useful superheat of 0 ºC.

With other useful superheat values, it is necessary to use the correction factor FRUP.F. for the refrigerating

capacity and FRUP.A. for the absorbed power. Both factors are indicated in CHART 3.

6. The values of performance charts have been obtained as the result of considering a total superheat of 0 ºC. With

other total superheat values, it is necessary to use the correction factor FRTP.F. for the refrigerating capacity

and FRTP.A. for the absorbed power. Both factors are indicated in CHART

7. The values of the performance charts have been obtained as the result of considering a subcooling of 3 ºC. With

other subcooling values, it is necessary to use the correction factor FSP.F. for the refrigerating capacity and

FSP.A. for the absorbed power. Both factors are indicated in CHART 5.

8. Use the chart “Sound levels” for the acoustic checking.

Page 48: Technical Guide for Screw Compressor Packages easy definition HX -40

48

.

Example nº1 of how to select a unit.

Select a unit suitable for supplying a refrigerating capacity of 94 kW under the following conditions:

Evaporating temperature:-39 ºC

Condensing temperature 35 ºC

Consider also that:

The loss of charge, calculated for the suction line, will be of 0,10 bar.

The loss of charge, calculated for the discharge line to the condenser, will be of 0,15 bar.

The evaporators installed inside the rooms will be flooded type and therefore the useful superheat will be of 0

ºC.

Owing to the big distance between the rooms and the compressor, the total superheat will be of 2º C.

This installation will be fitted with a liquid receiver, that is the reason why the subcooling will be of 0 ºC.

According to the requested refrigerating capacity and after checking the chart “Technical data of the Standard

unit”, select the model whose denomination will be “GMT HX 110 -40” .

For this unit model and according to the chart “Performance of the unit with nominal Vi”, we obtain the following

data:

Refrigerating capacity 110,1kW

Total absorbed power 85,8 KW

COP 1,28

If the values of loss of charge, superheat and subcooling are different from those indicated in the chart “Technical

data of the Standard unit”, it is necessary to use the following correction factors:

Chart 1, for a loss of charge in the suction line of 0,11 bar, the correction factors are FAP.F. = 0,96 and FAP.A.

= 0,99

Chart 2, for a loss of charge in the discharge line of 0,15 bar, the correction factors are FDP.F. = 1,00 and FDP.A.

= 1,00.

Chart 3, for a useful superheat of 0 ºC, the correction factors are FRUP.F. =1,00 and FRUP.A. = 1,00.

Chart 4, for a total superheat of 2 ºC, the correction factors are FRTP.F. = 0,99 and FRTP.A. = 1,00.

Chart 5, for a subcooling of 0 ºC, the correction factors are FSP.F. = 0,99 and FSP.A. = 1,00.

So, from the previous data we obtain the following results:

Refrigerating capacity = 110,1 x 0,96 x 1,00 x 1,00 x 0,99 x 0,99 = 103,6 kW

Total absorbed power =85,8 x 0,99 x 1,00 x 1,00 x 1,00 x 1,00 = 84,9 kW

COP = 103,6/84,9 = 1,22

At this moment of the selection procedure, it is possible to use the option superfeed and apply it to a smaller model than

the previous one. According to the chart “Technical data of the standard unit” the suitable model is “GMT HX 90

-40 s”.

Page 49: Technical Guide for Screw Compressor Packages easy definition HX -40

49

For the selected model and according to the chart “Performance of the unit with nominal Vi” we obtain the

following data:

Refrigerating capacity 107,6 kW

Total absorbed power 75,5 kW

COP 1,59.

The correction factors are the same than the ones mentioned above, and therefore the definitive data of the unit are:

Refrigerating capacity = 107,6 x 0,96 x 1,00 x 1,00 x 0,99 x 0,99 = 101,2 kW

Total absorbed power =75,5 x 0,99 x 1,00 x 1,00 x 1,00 x 1,00 = 74,7 kW

COP = 1,35

The efficiency obtained with the second selection is higher than the one of the first selection.

According to the data that have been obtained previously, the group to be selected is “GMT HX 90 -40 s”.

To know the motor type to be used for this application, see chart “How to select the motor size”. Then, select a cell

of the chart according to the unit data: the unit model (HX-90 40s), the evaporating temperature (-39 ºC) and the

condensing temperature (35 ºC). If there is an m in the selected cell, that means, that we need a nominal motor type.

The chart “Sound levels” shows the values of sound pressure levels in dBA, which have been measured at 1 meter high

and 1, 5 and 10 meters around the unit. In this case, the maximum level that has been measured at 1 meter around the

unit, is of 84 dBA.

Therefore, the selected unit is GMT HX 90 -40 s and has got the following data:

Refrigerating capacity 101,2 kW.

Total absorbed power 74,7 kW.

COP 1,35

Maximum sound pressure level at 1 meter around the unit: 83 dBA.

Example nº2 of how to select a unit.

Select a unit suitable for supplying a refrigerating capacity of 112 kW under the following conditions:

Evaporating temperature:-40 ºC

Condensing temperature 45 ºC

Consider also that:

The loss of charge, calculated for the suction line, will be of 0,10 bar.

The loss of charge, calculated for the discharge line to the condenser, will be of 0,15 bar.

The evaporators installed inside the rooms will be flooded type and therefore the useful superheat will be of 0

ºC.

Owing to the big distance between the rooms and the compressor, the total superheat will be of 2º C.

This installation will be fitted with a liquid receiver, that is the reason why the subcooling will be of 0 ºC.

According to the requested refrigerating capacity and after checking the chart “Technical data of the Standard

unit”, select the model whose denomination will be “GMT HX 130 -40 apc” .

Page 50: Technical Guide for Screw Compressor Packages easy definition HX -40

50

.

For this unit model and according to the chart “Performance of the unit with nominal Vi”, we obtain the following

data:

Refrigerating capacity 118,6kW

Total absorbed power 127,8 KW

COP 0,93

If the values of loss of charge, superheat and subcooling are different from those indicated in the chart “Technical

data of the Standard unit”, it is necessary to use the following correction factors:

Chart 1, for a loss of charge in the suction line of 0,11 bar, the correction factors are FAP.F. = 0,96 and FAP.A.

= 0,99

Chart 2, for a loss of charge in the discharge line of 0,15 bar, the correction factors are FDP.F. = 1,00 and FDP.A.

= 1,00.

Chart 3, for a useful superheat of 0 ºC, the correction factors are FRUP.F. =1,00 and FRUP.A. = 1,00.

Chart 4, for a total superheat of 2 ºC, the correction factors are FRTP.F. = 0,99 and FRTP.A. = 1,00.

Chart 5, for a subcooling of 0 ºC, the correction factors are FSP.F. = 0,99 and FSP.A. = 1,00.

So, from the previous data we obtain the following results:

Refrigerating capacity = 118,6 x 0,96 x 1,00 x 1,00 x 0,99 x 0,99 = 113,8 kW

Total absorbed power =127,8 x 0,99 x 1,00 x 1,00 x 1,00 x 1,00 = 126,5 kW

COP = 113,8/126,5 = 0,90

At this moment of the selection procedure, it is possible to use the option superfeed and apply it to a smaller model than

the previous one. According to the chart “Technical data of the standard unit” the suitable model is “GMT HX

110 -40 apc s”.

For the selected model and according to the chart “Performance of the unit with nominal Vi” we obtain the

following data:

Refrigerating capacity 121,2 kW

Total absorbed power 113,5 kW

COP 1,07.

The correction factors are the same than the ones mentioned above, and therefore the definitive data of the unit are:

Refrigerating capacity = 121,2 x 0,96 x 1,00 x 1,00 x 0,99 x 0,99 = 116,4 kW

Total absorbed power =126,5 x 0,99 x 1,00 x 1,00 x 1,00 x 1,00 = 112,4 kW

COP = 121,2/113,5= 1,04

The efficiency obtained with the second selection is higher than the one of the first selection.

According to the data that have been obtained previously, the group to be selected is “GMT HX 90 -40 s”.

Page 51: Technical Guide for Screw Compressor Packages easy definition HX -40

51

To know the motor type to be used for this application, see chart “How to select the motor size”. Then, select a cell

of the chart according to the unit data: the unit model (HX-90 40s), the evaporating temperature (-40 ºC) and the

condensing temperature (45 ºC). If there is an m in the selected cell, that means, that we need a nominal motor type.

The chart “Sound levels” shows the values of sound pressure levels in dBA, which have been measured at 1 meter high

and 1, 5 and 10 meters around the unit. In this case, the maximum level that has been measured at 1 meter around the

unit, is of 84 dBA.

Therefore, the selected unit is GMT HX 90 -40 s and has got the following data:

Refrigerating capacity 101,2 kW.

Total absorbed power 74,7 kW.

COP 1,35

Maximum sound pressure level at 1 meter around the unit: 85 dBA.

Page 52: Technical Guide for Screw Compressor Packages easy definition HX -40

52

DIMENSIONS AND CONNECTION POINTS

Page 53: Technical Guide for Screw Compressor Packages easy definition HX -40

53