THERMAL buiLding SOLuTiOnS WWW.PEnTAiRTHERMAL.COM
TECHNICAL HANDBOOK KEEp pEOpLE AND INfrAsTruCTurE sAfE frOm HArm, ENHANCE BuILDINg pErfOrmANCE AND BrINg COmfOrT INTO THE HOmE.
Pentair’S thermal BUilding SolUtionS
2 THERMAL buiLding SOLuTiOnS
A b C
A COLd AMbiEnT = HigH POWER OuTPuT If the temperature in the immediate vicinity of the self-regulating heating cable
is cold, the heat output from the heating cable is increased. The polymeric core of the cable contracts, which creates many electrical paths across the integrated carbon particles.
b WARM AMbiEnT = LOW POWER OuTPuT In response to a warmer environment, the heat output of the self-regulating
cable is reduced. The polymeric core of the cable expands, reducing the electrical paths.
C HOT AMbiEnT = ViRTuALLy nO OuTPuT If the temperature in the environment of the self-regulating heating cable
reaches a high temperature, the heat output is minimal. Due to the maximum expansion of the polymeric core of the cable, most of the electrical paths are broken.
TESTEd And quALifiEd• Stringent production monitoring• Approved BS EN 62395
(IEC62395)• VDE approved• CE marked
buiLding & infRASTRuCTuRE SOLuTiOnS
We provide quality solutions for winter safety, comfort and performance to building and infrastructure design, construction, operation and main-tenance professionals. From pipe freeze protection to maintaining fluid
temperatures and melting snow, detecting leaks or heating floors, you can rely on Pentair’s solutions & services for greater safety, comfort and performance.
THE HEART Of OuR SOLuTiOnS
In 1970, Raychem first developed and launched self-regulating electric heating cables. The cable delivers the right amount of heat exactly when and where it is needed. As the temperature drops, more heat is produced. Conversely, as the temperature rises, less heat is produced. But there are many more benefits:
• Thesmartcablescanbeoverlappedwithoutanyriskofoverheating.• Theheatingcablescanbecuttolength‘inthefield’.Thismeansadditional
flexibility when plans do not correspond to the ”real life” situation on site. • Thelengthofpipecorrespondstothelengthofcablethatyouneed.
RObuST COnSTRuCTiOn• Long service life assured through
modified polyolefin or fluorpolymer insulation and jacket materials.
LifE TiME• Intensive tests according to
recognized scientific procedures. Results: self-regulating heating cables have a service life in excess of 20 years.
Mitglied in der European RadiantFloor Heating Association e.V.
Member of the European Ra di ant Floor Heat ing Association e.v.
Our products satisfy the requirements of the relevant European Directives.
• Heat loss calculations for piped services• Product selection based upon actual systems designed in Revit• Automatic calculation of BOM including accessories• Circuit information, power requirements & circuit lengths• Engineering specification content for installed products
* Complete Trace Heating Revit Schedule direct in the BIM
Trace-it is available,free of charge from Autodesk SEEK.
3Technical handbook
iT’S nOT OnLy THE CAbLE!The combination of a self-regulating heating cable and a smart control unit allows for dynamic management of the heating cable’s power output dependent on parameters such as ambient temperature and moisture. These will help you and your customers to comply with today’s building regulations on energy savings. A complete Raychem system can result in energy savings of up to 80% !
Pentair offers a set of tools and services that aim to simplify the professional´s life. Not only do we offer the best quality products, we also support them with unrivalled services.
CuSTOMER SERViCE CEnTRE And TECHniCAL SuPPORT TEAM
RAyCHEM “TRACE-iT”, Add-in SOfTWARE PACKAgE fOR AuTOdESK REViT MEP
• Multi-lingual customer service representatives to answer all your questions
• Fast order handling & shipment Europe-wide
• Free documentation service
• “On demand” technical advice• Free designs and quotations• Direct support to specifiers and installers• Training support upon request• Complete after-sales service• Also for non-standard applications our team can assist
you in finding the right heating solution. Do not hesitate to get in touch with us Free phone 0800 96 90 13 or Free fax 0800 96 86 24.
Our control units (e.g. HWAT-ECO) are designed for easy set-up and operation. They are easy to access for fast wiring. Ergonomic buttons, intuitive menu-driven operation and pre-installed programmes allow for quick set-up.
Specific connection systems have been designed and configured to be fully compatible with our heating cables. The RayClic connection system cuts installation time by 80%. Inserting the stripped cable into the module and a few screws is all it takes.
1
2
4
5
3
4
4 THERMAL buiLding SOLuTiOnS
OVERViEW Of APPLiCATiOnS
5Technical handbook
CONTENTSHot water temperature maintenance 6
frost protection for pipes 20
frost protection for gutters and downpipes 40
snowmelting of ramps, steps, footpaths and accessways
52
Electrical underfloor heating 55
multiple application control & monitoring system
62
general installation instructions for self-regulating heat-tracing systems
18
38
64
Technical data – Choice of accessories 67
1
7
2
3
4
5
6ho
t wat
er te
mpe
ratu
re
main
tena
nce
Fros
t pro
tect
ion
for p
ipes
Fros
t pro
tect
ion fo
r gu
tters
and d
ownp
ipes
Snow
mel
ting o
f ram
ps,
step
s, fo
otpa
ths a
nd
acce
sswa
ys
elec
trica
l und
erflo
or
heat
ing
Cont
rol &
m
onito
ring s
yste
mge
nera
l ins
talla
tion
inst
ruct
ions
6 THERMAL buiLding SOLuTiOnS
hot w
ater
tem
pera
ture
m
ainte
nanc
e An HygiEniC SySTEMLess water volume and less heat loss in the pipe work help prevent bacterio-logical problems.
A fLExibLE And SPACE-SAVing SySTEMThe space requirement for pipes has been reduced because there are no return pipes. Risers, shafts and openings can be optimised freeing space for other services.
LOW inVESTMEnT COSTSThe heating cable is simply fixed on the supply pipe. There is no need for return pipe work, valves or pumps, nor for complex design and balancing work associated with return systems.
LOWER POWER COnSuMPTiOnThe heat loss in the system is significantly lower as only the heat loss from the feed pipe (and not from the return pipe) is to be compensated for. There is also no power requirement for circulation pumps.The single-pipe system can be used with a smaller boiler and as there is no cold return water coming into the boiler, the heat-up of the water is more efficient.The intelligent HWAT-ECO control unit saves power e.g. it can lower the temperature or switch off during water consumption peaks.
nO MAinTEnAnCE COSTSThe system has no mechanical parts such as a recirculation pump or control valves. There are no parts to wear out.
LOng LifETiMEThe selfregulating Raychem heating cable has a lifetime of over 40 years.
HOT WATER TEMPERATuRE MAINTENANCEProviding the comfort of instant hot water is the key requirement of any modern hot water system. The Raychem single-pipe system keeps water at the right temperature in a building’s water distribution pipe work. The intelligent system first keeps the investment cost low and then it operates economically and efficiently.
Gel-filled end seal (RayClic-E-02)
4-way connection (RayClic-X-02)
Power connection (RayClic-CE-02)
Sensor HWAT-ECO (incl.) A three-wire PT-100 temperature sensor (HARD-78) can be installed optionally in an immersion pipe installed on site.
Residual current device (rcd) (30 mA) Circuit-breaker (C type)
Heating cable (HWAT-L, M or R)
Temperature control unit (HWAT-ECO)
1
2
7
3
3
4
5 6
1 5
2
63
74
7Technical handbook
hot w
ater
tem
pera
ture
m
ainte
nanc
e
1 HEATing CAbLE SELECTiOn Optimum water temperature maintenance for single family houses, flats, offices, hotels, hospitals, convalescent homes, sports centres, ...
Heating cable type HWAT-L HWAT-M HWAT-RPower output 7W/m at 45°C 9 W/m at 55°C 12 W/m at 70°CMax. exposure temperature 65°C 65°C 80°COuter jacket colour yellow orange redControl unit: HWAT-ECO – recommended for
enhanced energy - efficiency
essential
Control unit: HWAT-T55 recommended recommended mandatory
Control unit: ACS 30 – recommended (project size >1500 m); see page 62
recommended (project size >1500 m); see page 62
Legionella prevention Possibility of thermal legionella prevention up to the draw-off points
dESign guidE, COnTROL uniTS And ACCESSORiES
1 Copper conductor (1.2 mm2)2 Self-regulating heating element3 Modified polyolefin insulation4 Aluminium foil wrap5 Protective tinned copper braid6 Modified polyolefin protective outer jacket.
Technical data: see page 67 The heating cable is installed in a straight line on the pipeworkThe heating cable can be traced right up to the draw-off points Total length of pipe to be traced+ approx. 0.3 m per connection+ approx. 1.0 m per T-connection+ approx. 1.2 m per 4-way connection= required heating cable length
Pipe size (mm) 15 22 28 35 42 54Insulation thickness (mm) 20 20 25 30 40 50
Ambient temperature: 18°C Thermal conductivity λ = 0.035 W/(m.K) For other thermal conductivity insulation materials, contact your Pentair representative.
Thermal losses in W/m, pipe 55°C in 18°C ambient temp. insulation dn 15 dn 20 dn 32 dn 40 dn 50
15 mm 10 12 16 18 2120 mm 9 10 14 15 1830 mm 7 8 11 12 1440 mm 6 7 9 10 1250 mm 6 7 8 9 1060 mm 5 6 8 8 9
1
5
2 3
4 6
4 inSuLATiOn THiCKnESSES
3 HEATing CAbLE LEngTH
2 COMPOSiTiOn Of THE HWAT-L/M/R HEATing CAbLE
8 THERMAL buiLding SOLuTiOnS
6 CHECKLiST fOR PLAnning THE inSTALLATiOn The system design should take into account:
• Pipediameterandmaterial • Insulationtypeandthickness • Ambienttemperature • Circuitsshoulddividetheplumbingintologicalsegments • Don’texceedthemaximumcircuitlength • Showconnectionlocationsonthedrawings • Locatepowerconnectionsneartheelectricalpanel • LocateT-connectionsinaccessibleareas
7 TESTing Of THE inSTALLATiOn See page 64
8 COnTROL PAnELS Control Panel: Steel plate housing, wall-mounted version, equipped with mains power switch, RCD/CB combination, inlet and outlet terminals. Completely as-sembled, turnkey condition wired and inspected cable guides in base of housing. The control panel contains a HWAT-ECO temperature control.
SbS-01-HM-ECO-10 Control panel for heating circuit, basic version. • PCN:390056-000
hot w
ater
tem
pera
ture
m
ainte
nanc
e
5 ELECTRiCAL PROTECTiOn
Thermal losses in W/m, pipe 55°C in 5°C ambient temp. insulation dn 15 dn 20 dn 32 dn 40 dn 50
15 mm 13 16 21 24 2820 mm 12 13 18 20 2330 mm 10 11 14 16 1840 mm 8 10 12 13 1550 mm 8 9 11 12 1360 mm 7 8 10 11 12
Calculations with TraceCalc PRO • Maintaintemperature55°C• Buildinginterior• Safetyfactor10%• Mineralwool,thermalconductivityat40°C0.041W/mk
• Thetotallengthofheatingcabledeterminesthenumberandsizeofthe circuit breakers
• Residualcurrentdevice(rcd):30mArequired• Powercablingfortheheatingcablesaccordingtolocalregulationsw• Thepowerconnectionmustbecarriedoutbyanapprovedelectricalinstaller
Circuit-breaker to bSEn 60898 (type C) : the maximum length of the heating circuit is based on a minimum start-up temperature of +12°C, 230 VAC.
HWAT-L HWAT-M HWAT-R10 A 80 m 50 m 50 m13 A 110 m 65 m 65 m16 A 140 m 80 m 80 m20 A 180 m 100 m 100 m
9Technical handbook
SbS-03-HV-ECO-10 Control panel for 2 to 3 heating circuits.• PCN:035958-000
SbS-06-HV-ECO-10 Control panel for 4 to 6 heating circuits. • PCN:539268-000
SbS-09-HV-ECO-10 Control panel for 7 to 9 heating circuits. • PCN:294452-000
9 COnTROL uniTS
HWAT-ECO Electronic temperature control unit with integrated clock• Building-specificprogramme• Boilertemperaturemonitoring• Economyprogrammes• Passwordprotection• Simpleuserinterface• CompatiblewithHWAT-L/M/Rheatingcables• BMSinterface• Alarmoutputs
Technical data: see page 13
HARd-78 PT-100 temperature sensor (HARD-78) for assembly in sensor pipe installed on site.
• Diameterofsensorcable4mm• Diameterofsensorelement6mm• Lengthofsensorelement50mm• Sensorlengthtotal3m
HWAT-T55 Thermostat with line sensor for hot-water branch lines and small hot-water pipe networks for HWAT-L, M and R (up to max. 50 m heating cable length) • Temperaturecontrolwithlinesensor •DIN-Railmounted(35mm) •ManualON/OFF • Digitaltemperaturedisplay •3operationmode–ON/ECO/OFF •3pre-sethotwatermaintaintemperatures55°C,50°C,45°C;editable • Overandlowertemperaturealarm • Timerfunctionforenergysavingmode/nightreduction • PCN:294452-000
Technical data: see page 16
HWAT-T55-Sensor Temperature line sensor for HWAT-T55 thermostat for fixing on hot water pipe • NTC2K-sensor •Sensorlength:10m •Diametersensorlength:4mm • Diametersensorprobe:5mm •Lengthsensorprobe:20mm •Temperaturerange:0°Cbis+70°C • PCN:1244-015847 Technical data: see page 16
HWAT-T55
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18
hot w
ater
tem
pera
ture
m
ainte
nanc
e
10 THERMAL buiLding SOLuTiOnS
10 ACCESSORiES RayClic-CE-02 Power connection
• With1.5mpowercable• Endsealandsupportbracket• IP68• Externaldimension:L=240mm
W = 64 mm H = 47 mm
RayClic-T-02 T-connection• Connectionfor3cables• Endsealandsupportbracket• IP68• Externaldimension:L=270mm
W = 105 mm H = 42 mm
RayClic-PT-02 Power T-connection• 3connectionswithintegral1.5mpowercable• 3endsealsand1supportbracket• IP68• Externaldimension:L=270mm
W = 105 mm H = 42mm
RayClic-S-02 Splice for joining 2 lengths of heating cable• Connectionfor2cableswith1supportbracket• IP68• Externaldimension:L=240mm
W = 64 mm H = 47 mm
RayClic-PS-02 Powered splice• Connectionfor2cableswithintegral1.5mpowercable• 2endsealsand1supportbracket• IP68• Externaldimension:L=270mm
W = 105 mm H = 42 m
RayClic-x-02 4-way connection• Connectionfor4cables• 2endsealsand1supportbracket• IP68• Externaldimension:L=270mm
W = 105 mm H = 42 mm
hot w
ater
tem
pera
ture
m
ainte
nanc
e
11Technical handbook
RayClic-E-02 Gel-filled end seal• Forsystemextensions(tobeorderedseparately)• IP68
KbL-10 Cable ties• Onepackof100requiredforapprox.30mofpipework• Length:370mm• TemperatureandUVresistant
Use ATE-180 on plastic pipes
gT-66 Heat-resistant glass cloth tape• Forsteelpipesorforanyinstallationbelow4.4°C• 20mrollforapprox.20mofpipework
Use ATE-180 on plastic pipes
gS-54 Glass cloth tape for attaching heating cable to pipe• Forstainless-steelpipesorforanyinstallationbelow4.4°C• 16mperroll,12mmwidth
ATE-180 Aluminium adhesive tape• Heatresistantupto150°C• 55mrollforapprox.50mofpipework
On plastic pipes: the heating cable must be covered with aluminium adhesive tape along its entire length
iEK-20-M (for HWAT-L, -M) / Insulation entry kit iEK-25-04 (for HWAT-R) • Insertionofheatingcableinmetalcladding
• Consistsof:metalfasteners,metricglandandjointseal
LAb-i-01 Electric traced label• Tobeplacedat5mintervalsoninsulationsurface
ELECTRICTRACED
R
hot w
ater
tem
pera
ture
m
ainte
nanc
e
12 THERMAL buiLding SOLuTiOnS
Cabinet type unit SbS-01-HM-ECO-10
SbS-03-HV-ECO-10
SbS-06-HV-ECO-10
SbS-09-HV-ECO-10
Number of heating circuits 1 3 6 9Enclosure version Wall version Wall version Wall version Wall versionDimensions Width mm 380 380 600 600
Height mm 600 600 600 600Depth mm 210 210 210 210
Weight (ready to dispatch) approx. kg 21 22 32 33Connected rating kW 4,5 14 28 42Customer fuse protection max. A 1 x 25A
NH-003 x 32A NH-00
3 x 40A NH-00
3 x 63A NH-00
Enclosure featuresMains isolator switch, 3-pin, 25 A unit 1 1Mains isolator switch, 3-pin, 32 A unit 1Mains isolator switch, 3-pin, 63 A unit 1 1Line protection switch, S 2A unit 1 1 1 1Transformer 230/24 VAC unit 1 1 1 1Combination of RCD / Circuit breaker, C 20A, 30 mA, 4-pin with auxiliary switch
unit 1* 1 2 3
Power contactor 3 x 35° unit 1 2 3Auxiliary contactor unit 1 2 2 2`Operating‘ indicator unit 1 1 2 3`Fault‘ indicator unit 1 1 1 1HWAT-ECO Control unit 1 1 1 1Programmable logic module unit – – 1 1* 2-pin
11 gEnERAL inSTALLATiOn inSTRuCTiOn See page 67
hot w
ater
tem
pera
ture
m
ainte
nanc
e
13Technical handbook
70
85
(Dimensions in mm)
MOduLE LAyOuT
TECHniCAL dATA
HWAT-ECO TEMPERATuRE COnTROL uniT
A Power supply on (green LED)b Power to heater on (green LED)C Legionella prevention (green LED) - heating cable 100% powered - increased risk of scalding
d Maintain temperature lowered following boiler temperature decrease (green LED) - boiler temperature is lower than expected.E Error (red LED) Change menu selection or position cursor
Escape, backspace or NO
Confirm selection, new value or YES
Product description HWAT-ECOuse Only for HWAT-L/M/R heating cablesSelectable maintain temperature 37°C to 65°C in max. 48 timer blocs
per dayOperating voltage 230 VAC (+10%, –10%), 50 HzSwitching capacity 20 A / AC 230V Internal power consumption 2,5 VACircuit breaker Max. 20 A, C-CharacteristicPower cable section entry 1.5 - 4 mm2 for fixed wiring onlyAuxiliary cable section entry up to 16 AWG (1.3 mm2)Weight 880 gMounting options Wall mount with 2 screws or DIN railCable glands (entries) 2 x M20 and 1 x PG13.5 with 3 inputs
for external wires of 3-5 mmProtection level IP 54Ambient temperature 0°C to 40°CHousing material ABSInternal temperature alarm 85°CMaster/slave cable 2-wire twisted pair shielded, max.
1.3 mm2 core and insulation of 500 VMaster/Slave Master is selectable in the unit,
up to 8 slaves can be con nect edBMS interface 0 - 10 VDCAlarm relay contacts Max. 24VDC or 24 VAC, 1 A, SPDT
voltage free
Boiler tem per a ture sensor PTC KTY 81-210 or PT 100 2-wirePower correction factor 60% to 140%
(fine tuning of maintained temperature)Clock back-up time Min. 1 year with lithium battery
CR2025 (3V)Clock accuracy ±10 minutes per yearReal time clock Automatic summer/winter time
and leap year correctionParameters stored in non-volatile All parameters, except date and
time memoryApproval VDE according to EN 60730EMC According to EN 50081-1/2 for emission
and EN 50082-1/2 for immunity
A B C D E
165
85
hot w
ater
tem
pera
ture
m
ainte
nanc
e
14 THERMAL buiLding SOLuTiOnS
Raychem requires the use of a 30 mA residual current device and a C-Characteristic circuit breaker to provide maximum safety and protection from fire.
The unit complies with IEC1000-3-3 (flicker) if installed according to part 3 of VDE 0838. To avoid flicker install the unit in such a way that at the current value of the systems start-up temperature (max. 20 A per heating circuit) the voltage drop does not exceed 1% at the power supply of the lighting apparatus (normally subpanel).
PROgRAMME The HWAT-ECO has 7 different building specific time/temperature programmes. These programmes are based on our long experience for optimum comfort and energy saving. For user specific changes in the programming, the Edit timer programme can be used.
Programme name building typeProgramme 0 Constant temperature (±55°C)Programme 1 Apartment blockProgramme 2 Prison / BarracksProgramme 3 HospitalProgramme 4 HotelProgramme 5 Sports centre / Swimming poolProgramme 6 Office
in addition, user specific programmes can be created Temperature can be varied in 1/2 h blocks to any desired temperature between: OFF, economy t°, maintain t° and legionella prevention (100% powered, increased risk of scalding)
hot w
ater
tem
pera
ture
m
ainte
nanc
e
15Technical handbook
hot w
ater
tem
pera
ture
m
ainte
nanc
e
Self-regulating heating cable
Self-regulating heating cable
Self-regulating heating cable
Temperature sensor
L1
L2
L3
N
PE
L’ N’ PE
BMS TEMP
L B AN
HWAT-ECO
L’ N’ PE
BMS
L B AN
HWAT-ECO
L’ N’ PE
BMS TEMP
L B AN
HWAT-ECO
Alarm Alarm Alarm
Optional
*
**
+ + +TEMP
***
cable type RS-485, 2-pole contact ****
WiRing diAgRAM fOR HWAT-L / HWAT-M / HWAT-R WiTH HWAT-ECO TEMPERATuRE COnTROL uniT
* Two- or four-pole electrical protection by circuit breaker may be needed for local circumstances, standards and regulations
** Depending on the application, one- or three-pole circuit-breakers or contactors may be used
*** Optional: Potential-free circuit-breaker for connection to the BMS**** The earth wire of shielded RS-485 cable needs to be connected to the
BMS (-) terminal of each HWAT-ECO in the Master / Slave network.
16 THERMAL buiLding SOLuTiOnS
diSPLAy
TECHniCAL dATA
HOuSing
TEMPERATuRE SEnSOR
4 3 2
A0
1
HWAT T55
Abmessungen / Dimensions
abne
hmba
rre
mov
able
30 (1.18)
46 (1.81)
58 (2.28)
A LED display (parameter and error indications)0 Control relay ON1 Eco-Mode/night reduction activated2 Programming/confirmation button3 Reduce value4 Increase value
Operating voltage AC 230V, +10%/-10%, 50 HzPower consumption <= 5VAControl relay (heating) 230 VAC, max 16AConnecting terminals 2,5 mm², screwedTemperature setting range**consider local hygienic standard
40°C - 60°C; factory settings: 55°C
Switching hysteresis +/–2KAccuracy +/- 1,5 K including temperature probeStorage temperature –20°C bis +55°CStorage temperature –20°C bis +55°C
Programmable parameter settings3 pre-set temperatures 55°C ; 50°C, 45°C factory settings;
editableTimer 24 hour display, 1 min intervalEconomy-mode/duration 3-8 hours interval per hour
factory settings 6 hoursEconomy-mode/starting time 23:00 factory settings; editable
Error codesHot water-temperature -monitoring - Temperature exceeds 66°C
- Temperature is too low (min 5K deviation from maintain temperature)
Sensor - Sensor-short circuit- Sensor-open loop / Sensor not connected
Heating cable - Power output relay defective- Heating cable not connected
Dimensions 51,5 mm x 87, 5mm x 58mm (B/H/T)Material Housing ABSIP rating IP 20 ( IP 30 in panel)Installation DIN 35 mm rail mountedMinimum installations temperature 5°C
HWAT –T55- Sensor Type NTC 2K( 2 wires)Sensor length 10 mDiameter sensor length 4 mmDiameter sensor probe 5 mmLength sensor 20 mmTemperature range 0°C to +70°C
THERMOSTAT HWAT-T55TEMPERATuRE COnTROL WiTH (PiPE) LinE SEnSOR fOR HOT WATER bRAnCH LinES And SMALL HOT WATER PiPE nETWORKS
hot w
ater
tem
pera
ture
m
ainte
nanc
e
17Technical handbook
hot w
ater
tem
pera
ture
m
ainte
nanc
e
COnnECTiOn SCHEME fOR THERMOSTAT HWAT-T55
HWAT-T55
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18
(AC 230V)L N
10
1 2 4 5 6 7 8 9
11 17 18- +
Powersupply K2
Alarm
PE
K1 Heating cable
(AC 230V)L
L
N
N
10
4 5 6 7 8 9
11 17 18- +
Powersupply K2
AlarmK1
Heating cable
Thermostat HWAT-T55
Heating cable
MaxC 16A
30 mA
2A
ca. 45° ca. 45°
18 THERMAL buiLding SOLuTiOnS
12 inSTALLATiOn inSTRuCTiOnS fOR HWAT-L/M/R CAbLES• Theheatingcableshouldbeinstalledinastraightline
on the pipework.• Installondrysurfaces• Minimuminstallationtemperature:–10°C
installation of self-regulating heating cables• Storeinadryandcleanplace.• Temperaturerange:–40°Cto+60°C.• Protectanycableendswithanendseal.
Avoid:• sharpedges• hightractiveforce• kinkingandcrushing• walkingordrivingoverthecable• moistureatcableinterfaces
horizontal pipes
For plastic pipes use aluminium adhesive tape ATE-180. Place it over the entire length of the pipe
GT-66 / GS-54 adhesive tape
It is not necessary to spiral the cable around the pipe
Install the heating cables on the outside of the pipe bend
Cable tie KBL-10
90°
Cut the heating cable at right angles
Smallest bending radius: 10 mm
Horizontal pipe
Vertical pipe
max. 300 mm
Wall/floor transitThe thickness of thermal insulation must be continuous otherwise compensate by adding heating cable.
HOT WATER TEMPERATuRE MAINTENANCEho
t wat
er te
mpe
ratu
re
main
tena
nce
ca. 45° ca. 45°
19Technical handbook
RayClic-T-connection Electric traced label
IEK-20-M / IEK-25-04 for insertion of heating cable in metal cladding
≤ 3 m
≤ 3 m HWAT-M and HWAT-R
insulation
≤ 3 m
≤ 3 m HWAT-L
> 3 m
> 3m + Rayclic
RayClic
• Runthecableoverpipesuspensions• Donotclampthecable
MASTER
230V
L N RayClicHWAT
PT100 sensor probe installed within the hot water supply pipe work.
Standard installation of PT100 Sensor with in-pipe sensor probe.
hot w
ater
tem
pera
ture
m
ainte
nanc
e
20 THERMAL buiLding SOLuTiOnS
EASy TO inSTALLThe heating cable is simply fixed onto the pipe – under the thermal insula-tion. Connections are quickly made with the fast RayClic connectors.
duRAbLE And RELiAbLEThe cable’s large copper conduc-tors make it a reliable solution and its specially formulated outer jacket protects it from severe environmental conditions.
LOW POWER COnSuMPTiOnThe smart RAYSTAT -ECO control unit calculates a duty-cycle proportional to the expected minimum temperature. Where a simple ambient thermostat would energize the heating cable for 100%, the “smart” controller would energize for a fraction of the time, resulting in significant extra savings.
FROST PROTECTION FOR PIPESfrozen pipes can be a costly problem. When pipes are exposed to sub-zero tempera-tures they can burst, leading to considerable damage and disruption. The Raychem frost protection system for pipes provides an efficient solution. The self-regulating heating cable, combined with an adequate insulation, prevents water pipes, fire mains, sprinkler systems and fuel oil lines from freezing.
Thermostat with line or ambient temperature sensor
Residual current device (30 mA) Circuit-breaker (C type)
T-Connection (RayClic-T-02) (Not for FS-C-2X / FS-C10-2X)
Power connection (RayClic-CE-02) (Not for FS-C-2X / FS-C10-2X)
Frost protection heating cable (FS-A-2X, FS-B-2X, FS-C-2X or FS-C10-2X)
Electrical traced label (LAB-I-01)
Junction box (JB16-02)
End seal (RayClic-E-02) (Not for FS-C-2X / FS-C10-2X)
1
2
7
8
3
45
6
1 5
2
7
6
3
84
Optional: SBS-xx-SV control panel contains: RCD (30 mA), Circuit breaker (CB) (C characteristics) space available in switch cabinet for installation of a thermostat.
Fros
t pro
tect
ion
for p
ipes
Applicationfrost protection for pipework at max. 65°C operating temperatureFS-A-2X 10 W/m at 5°CFS-B-2X 26 W/m at 5°Cfrost protection for pipework at max. 95°C operating temperature and temperature maintenance for metal waste pipes with fatty waste waterFS-C-2X 31 W/m at 5°C
22 W/m at 40°Cfrost Protection for pipework to maximum 90°C operating temperature. for long circuit applications and central heating pipework.FS-C10-2X 10 W/m at 5°C
TraceCalc.Net Construction is a software tool for product selection based on actual project data. Visit www.pentairthermal.com
21Technical handbook
2 COMPOSiTiOn Of THE fS-A/b/C/C10-2x HEATing CAbLE
Fros
t pro
tect
ion
for p
ipes
dESign guidE, COnTROL uniTS And ACCESSORiES
1 HEATing CAbLE SELECTiOn
1 Copper conductor (1.2 mm2)
2 Self-regulating heating element3 Modified polyolefin insulation (FS-C-2X: Fluoropolymer)4 Protective tinned copper braid5 Modified polyolefin protective outer jacket.
Note: FS-C10-2X comprises copper conductors (1.4 mm2)
3 HEATing CAbLE LEngTHfrost protection down to –20°C.
Pipe diameterinsulation mm 15 22 28 35 42 54 67 76 108 125 150 200thicknesses Inches 1/2” 3/4” 1” 5/4” 11/2” 2” 21/2” 3” 4” 5” 6” 8”10 mm fs-a-2X
fs-C10-2X fs-B-2X fs-B-2X fs-B-2X fs-B-2X fs-B-2X fs-B-2X
15 mm fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-B-2X fs-B-2X fs-B-2X fs-B-2X fs-B-2X fs-B-2X
20 mm fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-B-2X fs-B-2X fs-B-2X fs-B-2X fs-B-2X
25 mm fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-B-2X fs-B-2X fs-B-2X fs-B-2X fs-B-2X
30 mm fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-B-2X fs-B-2X fs-B-2X fs-B-2X fs-B-2X
40 mm fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-B-2X fs-B-2X fs-B-2X fs-B-2X
50 mm fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-a-2Xfs-C10-2X
fs-B-2X fs-B-2X fs-B-2X
Frost protection cables FS-A-2X, FS-B-2X and FS-C10-2X are suitable for any pipe material (copper, threaded pipes, stainless steel pipes, plastic pipes and composite metal pipes without restriction).For plastic pipes, please use aluminium adhesive tape ATE-180. The frost protection cable should be covered along its entire length. Heat insulation l = 0.035 W/(m.K) or better.
important note: frost protection heating cables with fluorpolymer protective jacket must be used for solvent-containing, mixed and/or bitumen-coated heat insulation.
1 2 3
4 5
40°C temperature maintenance on pipelines for fatty waste water
Pipe diameter (mm)insulation 42 54 67 76 108 125 150 200thicknesses 11/2” 2” 21/2” 3” 4” 5” 6” 8”30 mm fs-C-2X 40 mm fs-C-2X fs-C-2X fs-C-2X 50 mm fs-C-2X fs-C-2X fs-C-2X fs-C-2X 60 mm fs-C-2X fs-C-2X fs-C-2X fs-C-2X fs-C-2X fs-C-2X fs-C-2X fs-C-2X
Min. ambient temperature –10°C. Heat insulation l = 0.035 W/(m.K) or better.
Cable type FS-C-2X should only be used in conjunction with pipework with a minimum continuous temperature resistance of 90°C. A line-sensing control thermostat (type AT-TS-14, RAYSTAT-CONTROL-10 or RAYSTAT-CONTROL-11-DIN) must be used on plastic pipework (setting approx. 40°C).
22 THERMAL buiLding SOLuTiOnS
The heating cable should be installed in a straight line on the pipework. Cable loops instead of T-connections can be made on short dead legs. (up to approx. 3 m)+ approx. 0.3 m per connection+ approx. 1.0 m per T-connection+ approx. 1.2 m per 4-way connectionAdditional cable required for increased heat sinks at valves from 2” and for uninsulated pipe supports (approx. 1 m)
= required heating cable length
• The total length of heating cable determines the number and size of the fuses • Residual current device (rcd) : 30 mA required, max. 500 m heating cable per rcd • Installation according to local regulations • The power connections must be carried out by an approved electrical installer • use C type circuit-breakers
Max. length of the heating circuit is based on a minimum switch-on temperature of 0°C, 230 VAC.
fS-A-2x fS-b-2x fS-C-2x fS-C10-2x4 A 45 m 25 m 20 m 45 m6 A 70 m 35 m 30 m 70 m
10 A 110 m 65 m 55 m 110 m13 A 130 m 85 m 70 m 130 m16 A 150 m 105 m 90 m 150 m20 A – – – 180 m
note: A splice can also be made using an S-06
6 TESTing Of THE inSTALLATiOn See page 64
7 COnTROL PAnELS Steel plate housing, wall-mounted version, equipped with mains isolator, RCD/CB combination(s), power contactor(s), indicators for‚ `Operation and Fault‘, operating mode selector switch, inlet and outlet terminals. Completely assem-bled, turnkey condition, wired and inspected. wiring schematics in panel housing An installation slot is provided for a RAYSTAT-CONTROL-11-DIN, RAYSTAT-CONTROL-10 and/or RAYSTAT-ECO-10 thermostat, each serving 3 heating circuits. Factory fitted. Please contact us for more information. Technical data: See page 29
4 CAbLE LEngTH
5 ELECTRiCAL PROTECTiOn
Fros
t pro
tect
ion
for p
ipes
23Technical handbook
SbS-03-SV Switch cabinet for 1 to 3 heating circuits.• PCN:355825-000
SbS-06-SV Control Panel for 4 to 6 heating circuits.• PCN:778308-000
SbS-09-SV Control Panel for 7 to 9 heating circuits.• PCN:767989-000
SbS-12-SV Control panel for 10 to 12 heating circuits.• PCN:1244-000025
for sprinkler systems Steel plate housing, wall-mounted version, equipped with mains power switch, low-voltage (LV) relay, RCD/CB combination(s), buzzer, power contactor(s), auxiliary contactor(s), operating mode selector switch, Indicators for `Operat-ing and Fault‘, `Mains power‘, inlet and outlet terminals. Completely assembled, wired and inspected. Wiring schematics included in housing 1 temperature controller is installed per heating circuit in the switch cabinet.
SbS-02-SnR Control panel for 2 heating circuits (Inc. redundant).
SbS-04-SnR Control panel for 4 heating circuits (Inc. redundant).
SbS-06-SnR Control panel for 6 heating circuits (Inc. redundant).
SbS-08-SnR Control Panel for 8 heating circuits (Inc. redundant).
SbS-10-SnR Control panel for 10 heating circuits (Inc. redundant).
SbS-12-SnR Control panel for 12 heating circuits (Inc. redundant).
8 THERMOSTATS
AT-TS-13 Thermostat• Adjustabletemperaturerange:–5°Cto+15°C• Line-sensingcontrolthermostatorambientthermostat• Max.switchingcurrent16A,250VAC
Technical data: see page 30
AT-TS-14 Thermostat• Adjustabletemperaturerange:0°Cto120°C• Temperaturemaintenanceonpipelinesforfattywastewater• Line-sensingcontrolthermostat• Max.switchingcurrent16A,250VAC Technical data: see page 30
Fros
t pro
tect
ion
for p
ipes
6 0 3 0
0 9 0
1 2 0
C °
A T -T S - 1 3
6 0 3 0
0 9 0
1 2 0
C °
A T -T S - 1 4
24 THERMAL buiLding SOLuTiOnS
RAySTAT-ECO-10 Ambient temperature thermostat• Adjustabletemperaturerange:0°Cto30°C• Max.switchingcurrent25A,250VAC• PASC(ProportionalAmbientSensingControl)forenergysaving• Alarmrelay:2Avoltfreewithindicationofsensorerrors,voltageerrors
and low or high temperature alarm• Displayforvisualindicationofparameters
Technical data: see page 32
RAySTAT-COnTROL-10 Line-sensing thermostat• Adjustabletemperaturerange:0°Cto150°C• Max.switchingcurrent25A,250VAC• Alarmrelay:2Avoltfreewithindicationofsensorerrors,voltageerrors
and low or high temperature alarm• Displayforvisualindicationofparameters Technical data: see page 34
RAySTAT-COnTROL-11-din Line sensing thermostat with digital display for DIN rail mounting applications.
• Settemperaturerange:0-65°C.• Digitaldisplayofmaintaintemperatureandalarminformation. 16A switching.• Lowtemperaturealarmfunction• DINrail/Panelmountablecontrol.• Sensortype:PT100.
Technical data: see page 36
Sb-100 Stainless steel support bracket • Speciallyconstructedtoprovideheatingcableprotectionbetweenpipeand
junction box via a tubular leg.• ForusewithAT-TS-13,AT-TS-14,JB16-02andRAYSTAT-CONTROL-10
Sb-101 Dual-leg support bracket, stainless steel• Heightleg:160mm• ForusewithAT-TS-13,AT-TS-14,JB16-02andRAYSTAT-CONTROL-10
Fros
t pro
tect
ion
for p
ipes
25Technical handbook
Sb-110 Support bracket, stainless steel• Heightleg:100mm• ForusewithAT-TS-13,AT-TS-14,andJB16-02
Sb-111 Support bracket, stainless steel• Heightleg:100mm• ForusewithAT-TS-13,AT-TS-14,andJB16-02
9 ACCESSORiES fOR fS-A-2x And fS-b-2x CAbLES fS-A-2x / fS-b-2x
Power connection RayClic-CE-02Splice RayClic-S-02Powered splice RayClic-PS-02T-connection RayClic-T-02Powered T-connection RayClic-PT-02Four way connection RayClic-X-02
note: A splice can also be made using an S-06
RayClic-CE-02 Power connection • With1.5mpowercable• Endsealandsupportbracket• IP68• Externaldimension:L=240mm
W = 64 mm H = 47 mm
note: RayClic components are not compatible with fS-C-2x /fS-C10-2x
RayClic-T-02 T-connection• Connectionfor3cables• Endsealandsupportbracket• IP68• Externaldimension:L=270mm
W = 105 mm H = 42 mm
note: RayClic components are not compatible with fS-C-2x /fS-C10-2x
RayClic-PT-02 Power T-connection• 3connectionswithintegral1.5mpowercable• 3endsealsand1supportbracket• IP68• Externaldimension:L=270mm
W = 105 mm H = 42 mm
note: RayClic components are not compatible with fS-C-2x /fS-C10-2x
Fros
t pro
tect
ion
for p
ipes
26 THERMAL buiLding SOLuTiOnS
RayClic-S-02 Splice for joining 2 lengths of heating cable• Connectionfor2cableswith1supportbracket• IP68• Externaldimension:L=240mm
W = 64 mm H = 47 mm
note: RayClic components are not compatible with fS-C-2x /fS-C10-2x
RayClic-PS-02 Powered splice• Connectionfor2cableswithintegral1.5mpowercable• 2endsealsand1supportbracket• IP68• Externaldimension:L=270mm
W = 105 mm H = 42 mm
note: RayClic components are not compatible with fS-C-2x /fS-C10-2x
RayClic-x-02 4-way connection• Connectionfor4cables• 2endsealsand1supportbracket• IP68• Externaldimension:L=270mm
W = 105 mm H = 42 mm
note: RayClic components are not compatible with fS-C-2x /fS-C10-2x
RayClic-E-02 Gel-filled end seal• Forsystemextensions(tobeorderedseparately)• IP68
note: RayClic components are not compatible with fS-C-2x /fS-C10-2x
10 ACCESSORiES fOR fS-C-2x And fS-C10-2x CAbLES for fS-C-2x/fS-
C10-2xPower connection 1 JB16-02 + 1 CE20-01 + JB-SB-08Splice 1 JB16-02 + 2 CE20-01 + JB-SB-08Powered splice 1 JB16-02 + 2 CE20-01 + JB-SB-08T-connection 1 JB16-02 + 3 CE20-01 + JB-SB-08Powered T-connection 1 JB16-02 + 3 CE20-01 + JB-SB-08Four way connection 1 JB16-02 + 4 CE20-01 + JB-SB-08
Jb16-02 Temperature-resistant junction box• ForFS-C-2XandFS-C10-2X• ForpowerconnectionorT-connection• IP66• 6x4mm2 terminals• 4Pg11/16,4M20/25knock-outentries
JB 16-02
A C 6 6 0 V
I P 6 6
Fros
t pro
tect
ion
for p
ipes
27Technical handbook
Jb-Sb-08 Single-leg support bracket • forjunctionandconnectionboxJB16-02
CE20-01 Connection and end seal kit for FS-C-2X/FS-C10-2X cables• Heat-shrinktechnique• M20gland
CCE-04-CT Cold lead connection and end seal kit• Connectionof3x1.5mm2 or 3 x 2.5 mm2 cold lead cable to self-regulating
heating cables FS-C -2X and FS-C10-2X.
11 gEnERAL ACCESSORiES
S-06 In-line splice kit • forFS-A-2XandFS-B-2X
S-19 In-line splice kit • forFS-C-2XandFS-C10-2X
Fros
t pro
tect
ion
for p
ipes
28 THERMAL buiLding SOLuTiOnS
CCE-03-CR Cold lead connection and end seal kit• Connectionof3x1.5mm2 or 3 x 2.5 mm2 cold lead cable to self-regulating
heating cables FS-A-2X and FS-B-2X
KbL-10 Cable ties• Onepackof100requiredforapprox.30mofpipework• Length:370mm• TemperatureandUVresistant
Use ATE-180 on plastic pipes
gT-66 Heat-resistant glass cloth tape• Forsteelpipesorforanyinstallationbelow4.4°C• 20mrollforapprox.20mofpipework
Use ATE-180 on plastic pipes
gS-54 Glass cloth tape for attaching heating cable to pipe
• Forstainless-steelpipesorforanyinstallationbelow4.4°C• 16mperroll,12mmwidth
ATE-180 Aluminium adhesive tape• Heatresistant• 55mrollforapprox.50mofpipework
On plastic pipes: the heating cable must be covered with aluminium adhesive tape along its entire length
iEK-20-M Insulation entry kit• Insertionofheatingcableinmetalcladding• Consistsof:metalfastener,metricglandandjointseal
LAb-i-01 Electric traced label• Tobeplacedat5mintervalsoninsulationsurface
ELECTRICTRACED
R
Fros
t pro
tect
ion
for p
ipes
29Technical handbook
12 gEnERAL inSTALLATiOn inSTRuCTiOnS See page 67
13 SPECiAL inSTALLATiOn inSTRuCTiOnS PLACing Of SEnSOR
Ambient sensor Fasten the pipe sensor to the pipe-work (e.g. alu min i um adhesive tape)
Always place the sensor in the coldest part of the installation
unheated premises
Outdoors
Junction box
Heating cable
Sensor
Cabinet type SbS-03-SV SbS-06-SV SbS-09-SV SbS-12-SVMax. number of heating circuits 3 6 9 12Enclosure version Wall version Wall version Wall version Wall versionDimensions Width mm 380 600 760 760
Height mm 600 600 760 760Depth mm 210 210 210 210
Weight approx. kg 20 30 50 52Connected rating kW 11 22 33 42Customer fuse protection max. A 3 x 25A
NH-003 x 32A NH-00
3 x 63A NH-00
3 x 80A NH-00
Switch cabinet equipmentMains isolator switch, 3-pin, 25 A unit 1Mains isolator switch, 3-pin, 32 A unit 1Mains isolator switch, 3-pin, 63 A unit 1Mains isolator switch, 3-pin, 100 A unit 1Power isolator, S 2° unit 1 1 1 1Combination of RCD/CB, C 16A, 30 mA, 4-pin, with auxiliary switch
unit 1 2 3 4
Power contactor, 3 x 35A unit 1 2 3 4Auxiliary contactor unit 1 1 1 1Switch, 3 settings, 1-pin, ‚Manual-0-Automatic‘
unit 1 2 3 4
Indicator ‚Operating‘ unit 1 2 3 4Indicator ‚Fault‘ unit 1 1 1 1
When using standard control panels for frost protection additional control devices need to be installed. Factory fitting is possible. Please contact the person responsible at Pentair.
Fros
t pro
tect
ion
for p
ipes
30 THERMAL buiLding SOLuTiOnS
A Green LED Heating cable onb Red LED Sensor breakC Red LED Sensor short-circuit
Supply voltage 230 VAC +10% –15% 50/60 HzPower consumption ≤ 1.8 VAApproval CEMax. switching current 16 A, 250 VACMax. conductor size 2.5 mm2
Switching differential 0.6 to 1 KSwitching accuracy AT-TS-13 ±1 K at 5°C (calibration point)
AT-TS-14 ±2 K at 60°C (calibration point)Switch type SPST (normally open)Adjustable temperature range AT-TS-13 –5°C to +15°C
AT-TS-14 0°C to +120°C
Temperature setting insideExposure temperature –20°C to +50°CIngress protection IP65 according to EN 60529Entries 1 x M20 for supply cable (∅ 8-13 mm)
1 x M25 for connection heating cable (∅ 11–17 mm) 1 x M16 for sensor
Weight (without sensor) approx. 440 gMaterial ABSLid fixing nickel-plated quick release screwsMounting On wall or on support bracket
SB-110/SB-111
Type PTC KTY 83-110Length sensor cable 3 mDiameter sensor cable 5.5 mmDiameter sensor head 6.5 mmMax. exposure temperature sensor cable 160°C
The sensor cable may be extended up to 100 m using a cable with a cross-section of 1.5 mm2. The sensor cable should be shielded if it is laid in cable ducts or in the vicinity of high-voltage cables.
55
R
122
120
R
ABC
uniT LAyOuT
TECHniCAL dATA
LinE-SEnSing COnTROL And AMbiEnT THERMOSTATS (AT-TS-13 And AT-TS-14)
HOuSing
TEMPERATuR SEnSing(HARd-69)
Fros
t pro
tect
ion
for p
ipes
31Technical handbook
max. 16A/C
1 2
4 9 8 6
5 3
30 mA
L1
N
*
Thermostat
Temp. Pt 100 sensor
Self-regulating heating cable
L1
L2
L3
N
**
***
max. 16A/C
1 2 3
9 8 6
5
*
4
30 mA
*
6 0 3 0
0 9 0
1 2 0
C °
A T -T S - 1 3
Thermostat
Self-regulating heating cable
AT-TS-13/14 diRECT
WiRing diAgRAM fOR THERMOSTAT AT-TS-13 OR AT-TS-14
AT-TS-13/14 WiTH COnTACTOR
Temp. Pt 100 sensor
* Two- or four-pole electrical pro-tection by circuit-breaker may be needed for local circumstances, standards and regulations
** Depending on the application, one- or three-pole circuit-breakers or contactors may be used
*** Optional: Potential-free circuit-breaker for connection to the BMS
Fros
t pro
tect
ion
for p
ipes
32 THERMAL buiLding SOLuTiOnS
A LED Display (parameter and error indications)1 Battery activation2 Parameter menu selection 3 Increase value4 Decrease value
Operating Voltage 230 VAC, +10%/–10%, 50/60 HzPower Consumption ≤ 14 VA Main Relay (heating) Imax 25 A, 250 VAC, SPSTMain Terminals 3 x 0.75 mm2 to 4 mm2
Alarm Relay Imax 2 A, 250 VAC, SPDT, voltfreeAlarm Terminals (3 + ) x 0.75 mm2 to 2.5 mm2
Accuracy ±0.5 K at 5°CMain parameter settingsEnergy Saving Algorithm Proportional Ambient Sensing Control
(PASC) active below setpointTemperature Setpoint 0°C to + 30°C (switch off temperature)Minimum Expected Ambient –30°C to 0°C Temperature (heating 10 powered)Heater Operation if Sensor Error ON (100%) or OFFVoltage Free Operation YES or NO
Energy saving with Proportional Ambient Sensing Control (PASC)Duty cycle (power to heater on) depends on the ambient temperature. For example: If minimum temperature= –20°C and if maintain temperature (set point)= +5°C
diagnosed alarmsSensor Errors Sensor short / Sensor open circuitLow Temperature Min. expected ambient temperature
reachedVoltage Errors Low supply voltage / Output voltage / faultParameters can be programmed without power supply and parameters are stored in non-volatile memory.
Size 120 mm x 160 mm x 90 mmMaterial Grey polycarbonateExposure Temperature Range –40°C to +80°CIngress Protection IP 65 Entries 2 x M25, 1 x M20, 1 x M16Weight Approx. 800 gLid Transparent with 4 captive screwsMounting On wall or on support bracket
SB-100/SB-101
Sensor Type 3-wire Pt100 according to IEC Class BSensor Head 6 mm
Sensor cable can be extended up to 150 m when a cross-section of 3 x 1.5 mm2 is used. The sensor cable should be shielded if it is laid in cable ducts or in the vicinity of high-voltage cables.
- 1- 2- 3- 4
A
VD E
EnERgy SAVing fROST PROTECTiOn COnTROLLERRAySTAT-ECO-10
Ambient temperature–10 0 3 10
% ON
0 20 40 60 80 100
% ON
ambient t° % On–20 100 Min. Ambient–10 60
0 203 0 Set point
Result: At ambient temperature of –10°C, 50% energy is saved
diSPLAy
TECHniCAL dATA
HOuSing
TEMPERATuRE SEnSOR
–20
Fros
t pro
tect
ion
for p
ipes
33Technical handbook
Heating cable
Temp. Pt 100 sensor
Heating cable Temp. Pt 100 sensor
WiRing diAgRAM fOR RAySTAT-ECO-10
nORMAL OPERATiOn
VOLTAgE fREE OPERATiOn: REMOVE LinKS W1 And W2
* Electrical protection by circuit breaker may be needed for local circumstances, standards and regulations.
** Depending on the application, one or three-pole circuit breakers or contactors may be used.
Fros
t pro
tect
ion
for p
ipes
34 THERMAL buiLding SOLuTiOnS
- 1- 2- 3- 4
AA LED Display (parameter and error indications)1 Battery activation2 Parameter menu selection3 Increase value4 Decrease value
Operating Voltage 230 VAC, +10%/–10%, 50/60 HzPower Consumption ≤ 14 VA Main Relay (heating) Imax 25 A, 250 VAC, SPSTMain Terminals 3 x 0.75 mm2 to 4 mm2
Alarm Relay Imax 2 A, 250 VAC, SPDT, voltfreeAlarm Terminals (3 + ) x 0.75 mm2 to 2.5 mm2
Accuracy ±0.5 K at 5°CAmbient temperature –40°C to +40°CParameter settingsTemperature Setting 0°C to +150°CHysteresis 1 K to 5 KLow Temperature Alarm –40°C to +148°CHigh Temperature Alarm +2°C to +150°C or switched OFFHeater Operation if Sensor Error ON or OFFVoltage Free Operation YES or NOdiagnosed errorsSensor Errors Sensor short / Sensor open circuitTemperature Extremes High temperature / Low temperatureVoltage Errors Low supply voltage / Output faultParameters can be programmed without power supply and parameters are stored in non-volatile memory.
Size 120 mm x 160 mm x 90 mmMaterial Grey polycarbonateIngress Protection IP 65 Entries 2 x M25, 1 x M20, 1 x M16Weight Approx. 800 gLid Transparent with 4 captive screwsMounting On wall or on support bracket
SB-100/SB-101
Sensor Type 3-wire Pt100 according to IEC / Class B
Sensor Head 50 mm x ∅ 6 mmSensor Cable Length 3 m x ∅ 4 mmCable Exposure Temperature –40°C to +150°C
(+215°C, 1000 h max.)Sensor cable can be extended up to 150 m when a cross-section of 3 x 1.5 mm2 is used. The sensor cable should be shielded if it is laid in cable ducts or in the vicinity of high-voltage cables.
VD E
LinE-SEnSing THERMOSTAT WiTH ALARM RELAy RAySTAT-COnTROL-10
diSPLAy
TECHniCAL dATA
HOuSing
TEMPERATuRE SEnSOR
Fros
t pro
tect
ion
for p
ipes
35Technical handbook
WiRing diAgRAM fOR RAySTAT-COnTROL-10
nORMAL OPERATiOn
VOLTAgE fREE OPERATiOn: REMOVE LinKS W1 And W2
LN
1
Max.C 25 A
30 mA
5 L L 8 N N
W1 W2
R R
RAYSTAT-CONTROL-10
A B C
alarm*2A max.
Heating cable Temp. Pt 100 sensor
Heating cable Temp. Pt 100 sensor
* Electrical protection by circuit breaker may be needed for local circumstances, standards and regulations
** Depending on the application, one or three-pole circuit breakers or contactors may be used
*** Optional
Fros
t pro
tect
ion
for p
ipes
36 THERMAL buiLding SOLuTiOnS
RAySTAT-COnTROL-11-din LinE-SEnSing THERMOSTAT fOR RACK MOunTing WiTH ALARM RELAy
A LED display (parameter and error indications)0 Control relay ON1 Alarm relay activated2 Programming button3 Reduce value4 Increase value
Operating voltage 230 Vac, +10%/–10%, 50/60 HzPower consumption ≤5 VAControl relay (heating) Imax 16 A, AC 250 V, SPSTConnecting terminals 2.5 mm2 screwedAlarm relay Imax 8 A, AC 250 V, SPDT, voltage-freeAccuracy ±1 K at 0 to 50°COperating temperature –10°C to +55°CStorage temperature –20°C to +60°C
Programmable parameter settings Factory settingTemperature setting 0°C to +63°C 5°CHysteresis 1 K to 5 K 1 KLow temperature alarm –15°C to 0°C or „Off“
position.0°C
Heater operation if sensor error ON or OFF ONVoltage-free operation YES
Diagnosed errorsSensor error Sensor short-circuit / Sensor open-circuit /
3-wire sensor missingTemperature error Low temperatureAll parameters are stored in a non-volatile memory.
Dimensions 51.5 mm x 87.5 mm x 58 mm (W x H x D)Material Housing in ABSIngress protection IP 20 (IP 30 installed in switchgear cabinet)Mounting DIN 35 mm rack mounting
Type Pt 100 (3-wire technology) as per IEC class B
Sensor element 50 mm x ∅ 6 mm stainless steel sheathProtection rating IP 68Sensor cable length 3 m x ∅ 5 mmAmbient temperature –50°C to 105°C
The sensor can be extended with a 3-wire shielded cable with max. 7.5 Ω per wire (with 3 x 1.5 mm2 max. 150 m). The shielding should be earthed in the switchgear cabinet.
diSPLAy
TECHniCAL dATA
HOuSing
TEMPERATuRE SEnSOR
4 3 2
A0
1
Fros
t pro
tect
ion
for p
ipes
37Technical handbook
WiRing diAgRAM fOR RAySTAT-COnTROL-11-din
RAYSTAT-CONTROL-11-DIN
10 11 16 17 18
4 5 6 7 8 9
16 17 18
K2 Alarm
K1heatingcable
L N (AC 230V)
Heating cable
2-wire sensor3-wire sensor
MaxC 16A
2A
30 mA
Network mains
Heating cable
10 11 16 17 18
4 5 6 7 8 9
16 17 18
2-wire sensor3-wire sensor
Network mains
K2 alarm
K1heating cable
L N (AC 230V)
Max.C 16A
2A
nORMAL OPERATiOn
VOLTAgE-fREE OPERATiOn WiTH POWER COnTACTOR
* Regional factors, standards and regulations may require two to four-pole disconnection by circuit breakers/ground fault circuit interrupters.
** Depending on the application, both single and multipole contactors are possible.
Fros
t pro
tect
ion
for p
ipes
38 THERMAL buiLding SOLuTiOnS
12 inSTALLATiOn inSTRuCTiOnS fOR fS-A/b/C/C10-2x CAbLES• Theheatingcableshouldbeinstalledinastraightlineonthepipework.• Installondrysurfaces• Minimuminstallationtemperature:–10°C
installation of self-regulating heating cables• Storeinadryandcleanplace.• Temperaturerange:–40°Cto+60°C.• Protectanycableendswithanendseal.
Avoid:• sharpedges• hightractiveforce• kinkingandcrushing• walkingordrivingoverthecable• moistureatcableinterfaces
horizontal pipes
For plastic pipes use aluminium adhesive tape ATE-180. Place it over the entire length of the pipe
GT-66 / GS-54 adhesive tape
It is not necessary to spiral the cable around the pipe
Install the heating cables on the outside of the pipe bend
Cable tie KBL-10
90°
Cut the heating cable at right angles
Smallest bending radius: 10 mm
Horizontal pipe
Vertical pipe
max. 300 mm
FROST PROTECTION FOR PIPES
ca. 45° ca. 45°
Fros
t pro
tect
ion
for p
ipes
39Technical handbook
ca. 45° ca. 45°
RayClic-T-connection Electric traced label
IEK-20-M for insertion of heating cable in metal cladding
≤ 3 m
≤ 3 m
> 3 m
> 3m + Rayclic
RayClic
• Runthecableoverpipesuspensions• Donotclampthecable
Wall/floor transitThe thickness of thermal insulation must be continuous otherwise compensate by adding heating cable.
frost protection at valves:• Valvesupto2”(DN50):installthe
frost protection heating cables in a straight line
• ≥2”:layasshown• Alwaysinsulatevalves
Fros
t pro
tect
ion
for p
ipes
40 THERMAL buiLding SOLuTiOnS
PRACTiCAL TO inSTALLThe self-regulating cable can be close-ly spaced in gutters without the risk for overheating or burn-outs. There is a cable for each type of roof material.
ECOnOMiCAL TO OPERATEThe self-regulating effect saves energy by automatically increasing its heat output in icy water and decreasing its output in dry air. The smart EMDR-10 control unit only switches the heating cable on when necessary: after the detection of both low temperature and moisture.
FROST PROTECTION FOR GuTTERS AND DOWNPIPES
Ambient sensor EMDR-10 (incl.)
Moisture sensor EMDR-10 (Incl.)
Fixing bracket (GM-RAKE)
EMDR-10 Control unit
Residual current device (rcd 30 mA)Circuit-breaker (C type)
Connection RayClic CE-02
Heating cable GM-2X(T)
End seal (RayClic-E-02)
1
2
7
8
3
4
5
6
1 5
2
7
6
3
84
Melting and refreezing of ice can damage roofs and gutters. Heavy icicles may fall and cause injury. Standing water can leak through interior walls onto furnishings.The Raychem self-regulating snow melting system maintains water flow in gutters and drain pipes and provides a path whereby melting ice and snow can drain safely off the roof, along the gutter and down the drain pipe.
do not install RayClic immersed in water. do not bury RayClic in the ground.
Optional: SBS-xx.EV-10 control panel Contains: Residual current device (RCD 30 mA), Circuit Breaker (C characteristics) EMDR-10 control unit
Fros
t pro
tect
ion fo
r gu
tters
and d
ownp
ipes
41Technical handbook
1 2 3
4 5
2 COMPOSiTiOn Of gM-2x And gM-2xT
dESign guidE, COnTROL uniTS And ACCESSORiES
1 HEATing CAbLE SELECTiOn
1 Copper conductor (1.2 mm2)
2 Self-regulating heating element3 Insulation made of modified polyolefin 4 Tinned copper braid5 Protective jacket (uV-resistent) (Modified polyolefin jacket for GM-2X
and fluoropolymer jacket for GM-2XT) important note: When laying cables on asphalt, bitumen, roofing felt, etc., a cable with a special fluoropolymer jacket (gM-2xT) must be used.
Technical data: see page 67
3 CAbLE LEngTH
gM-2x, gM-2xT Self-regulating heating cable for gutters, drain pipes and roof surfaces:• 36W/minicedwaterand18W/minairat0°C
• Theheatingcableshouldbeinstalledinastraightlineinthegutter• Thecablelengthsshouldbeadjustedaccordingtothegeographicalsituation
and the gutters• Morethanonecableshouldbelaidinwidevalley,parapetorbox
gutters
Gutter length+ drainpipe length+ 1 m per connection+ 1 m in the soil (frost line)= required heating cable length
• Thelengthofheatingcabledeterminesthenumberandsizeofthe circuit breakers
• Residualcurrentdevice(rcd):30mArequired,max.500mheatingcable per rcd
• Installationaccordingtolocalregulations• Thepowerconnectionsmustbecarriedoutbyanapprovedelectricalinstaller• UseCtypecircuit-breakers
Max. length of the heating circuit is based on a minimum switch-on temperature of –10°C, 230 VAC.
gM-2x, gM-2xT6A 25 m
10 A 40 m13 A 50 m16 A 60 m20 A 80 m
4 ELECTRiCAL PROTECTiOn
5 TESTing Of THE inSTALLATiOn See page 64
Fros
t pro
tect
ion fo
r gu
tters
and d
ownp
ipes
42 THERMAL buiLding SOLuTiOnS
6 COnTROL uniTS
EMdR-10 Smart control unit• Withtemperatureandmoisturesensor• User-friendlycontrol• Savesupto80%energy• Max.switchingcapacity10A(otherwiseswitchingbycontactor)• Potentialfreealarmforsensorbreakage,sensorshortandpowerloss
Technical data: see page 48
HTS-d Standard thermostat• 2independantswitchingpoints• Max.switchingcurrent:16A-250VAC• Temperatureadjustmentrange:–20°Cto+25°C• Outdoorinstallation• Economicalforcircuitlengthsupto30m
Technical data: see page 50
7 ACCESSORiES fOR gM-2x/gM-2xT
RayClic-CE-02 Power connection • With1.5mpowercable• Endsealandsupportbracket• IP68• Externaldimension:L=240mm
W = 64 mm H = 47 mm
RayClic-T-02 T-connection• Connectionfor3cables• 1endsealand1supportbracket• IP68• Externaldimension:L=270mm
W = 105 mm H = 42 mm
• 3 0 • 2 0 • 1 0 • 0 • - 1
0 •
- 2 0
2 5 2 0 1 5 1 0
5
0
PE PE PE 1 2 3 4 5 6
7 8
9 10
11
AC 230V 50/60Hz
IP 20 Relais: 10(4)A, AC 230V
Alarm: 2(1)A, AC 230V Do not open while energized
Nicht unter Spannung öffnen
Ne pas ouvrir sous tension
R
EMDR-10
T2A IEC127–2/V
C
–25
–20 –15
–10 –5
TEST
C
–3
–2
–1 0 1 2
3 4 5
6
0
5 10 15
20 25 min
1 2 3 4 5 6
7 8 9
10
Fros
t pro
tect
ion fo
r gu
tters
and d
ownp
ipes
43Technical handbook
RayClic-PT-02 Power T-connection• Connectionfor3cableswith integral 1.5 m power cable • 3endsealsand1supportbracket• IP68• Externaldimension:L=270mm
W = 105 mm H = 42mm
RayClic-PS-02 Powered splice• Connectionfor2cableswithintegral1.5mpowercable• 2endsealsand1supportbracket• IP68• Externaldimension:L=270mm
W = 105 mm H = 42 m
RayClic-E-02 Gel-filled end seal• Forsystemextensions(tobeorderedseparately)• IP68
RayClic-Sb-02 Wall-mounted support bracket
gM-RAKE • Fixingbracket/edgeprotectionfordrainpipes• Spacerforuseinwidechannelsorgutterswheremorethanonerunofcable
is required (a spacer is placed every 100 cm)• VAsteelwithUV-resistantcableties
iceStop-gMK-RC Roof clip to secure heating cables to roofs and gutters.Adhesive can be applied on the underside of the roof clip. After curing of theadhesive the heating cable can be clipped between the clamps.
Fros
t pro
tect
ion fo
r gu
tters
and d
ownp
ipes
44 THERMAL buiLding SOLuTiOnS
gM-CLiP-S Clip for quick and reliable fixing of heating cable GM-2X and GM-2XT on wide down pipe funnel. •Material:StainlesssteelEN1.4310 •Wire:Ø2,5 mm •Height:55mm •Guttertype:widefunnelwithmax. Frame size of 10 mm •Boxcontent:10Clips/box •PCN:1244-013849 •Patent:001357560-0003
gM-CLiP-L Clip for quick and reliable fixing of heating cable GM-2X and GM-2XT on gutters with L-profile. •Material:StainlesssteelEN1.4310 •Wire:Ø2,5mm •Height:150 mm •Guttertype:gutterswithL-Profile 140-150 mm height with max. 15 m frame size •Boxcontent:10Clips/box •PCN:1244-013851 •Patent:001357560-0001 gM-CLiP-M Clip for quick and reliable fixing of heating cable GM-2X and GM-2XT on half round gutters . •Material:StainlesssteelEN1.4310 •Wire:Ø2,5 mm •Height:100 mm •Guttertype:guttershalf-round; Width: 100-150 mm Depth: 65-80 mm height with max. 17 m frame size •Boxcontent:10Clips/box •PCN:1244-013850 •Patent:001357560-0002
gM-HAngAR Structural support for wide roof inlet funnel for fast and easy installation of the heating cable GM-2X and GM-2XT. •Material:EdelstahlEN1.4301 •Wire:Ø4,0 mm •Hight:225mm •Guttertype:widefunnelwithmax. Frame size of 20 mm •Suitablefor:GM-2X,GM-2XT •Contentbox:5pcs/box •PCN:1244-013852
RAyCLiC-Sb-gM-METAL Bracket for mounting on metal standing seam roofs •Material:FeuerverzinkterStahl •Thickness:2,0 mm •Dimension:L120xB130xH42 mm •Guttertype:metalstandingseamroofs •Suitablefor:RayClic-CE,-S,-T,-PT, -PS and –X •Boxcontent:Unpacked;1pcs •PCN:1244-013853
1.0 meter
140-150 mm
1.0 meter
100-150 mm
65-80 mm
Fros
t pro
tect
ion fo
r gu
tters
and d
ownp
ipes
45Technical handbook
installation of self-regulating heating cables• Store in a dry and clean place.• Temperature range: –40°C to
+60°C.• Protect any cable ends with an
end seal.
Avoid:• sharp edges• high tractive force• kinking and crushing• walking or driving over the cable• moisture at cable interfaces
gM-SEAL-02 Adhesive for sticking and sealing common construction materials with a base of polyurethane perfectly suitable for metal or plastic gutters, roofing tiles and even asphalt and bitumen surfaces.
• 300mlpack
CCE-03-CR (for GM-2X only) Cold lead connection and end seal kit• Connectionof3x1.5mm2 or 3 x 2.5 mm2 cold lead cable to self-regulating
heating cable GM-2X
CCE-04-CT (for GM-2XT only) Cold lead connection and end seal kit• Connectionof3x1.5mm2 or 3 x 2.5 mm2 cold lead cable to self-regulating
heating cables GM-2XT
8 gEnERAL inSTALLATiOn inSTRuCTiOnS
Fros
t pro
tect
ion fo
r gu
tters
and d
ownp
ipes
46 THERMAL buiLding SOLuTiOnS
9 COnTROL PAnEL Steel plate housing, wall-mounted version, equipped with mains isolator, RCD/CB combination(s), indicators for `Operation and Fault‘, inlet and outlet terminals. Completely assembled, wired and inspected. Cable guides in base of housing An EMDR-10 control unit is installed in each switch cabinet. Technical data: see page 48
SbS-03-EV-10 Control panel up to 3 heating circuits • PCN:295014-000
SbS-06-EV-10 Control panel up to 6 heating circuits• PCN:458484-000
SbS-09-EV-10 Control panel up to 9 heating circuits• PCN:206336-000
SbS-12-EV-10 Control panel up to 12 heating circuits• PCN:282458-000
10 COnTROL uniT
EMdR-10 • Withtemperatureandhumiditysensor• Savesupto80%energy• Max.permittedswitchingcurrent10A(otherwiseswitchviapowercontactor)• Alarmrelaycontactforsensorbreak,sensorshortcircuitandpowerfailure.• PCN:449554-000
Technical data: see page 48
HTS-d Thermostat• Twoindependentlyadjustableswitchingpoints• Max.permittedswitchingcurrent16A-AC250V• Adjustmentrange–20°Cto+25°C• Assemblyinexternalarea• PCN:C71431-007
Technical data: see page 50
PE PE PE 1 2 3 4 5 6
7 8
9 10
11
AC 230V 50/60Hz
IP 20 Relais: 10(4)A, AC 230V
Alarm: 2(1)A, AC 230V Do not open while energized
Nicht unter Spannung öffnen
Ne pas ouvrir sous tension
R
EMDR-10
T2A IEC127–2/V
C
–25
–20 –15
–10 –5
TEST
C
–3
–2
–1 0 1 2
3 4 5
6
0
5 10 15
20 25 min
1 2 3 4 5 6
7 8 9
10
• 3 0 • 2 0 • 1 0 • 0 • - 1
0 •
- 2 0
2 5 2 0 1 5 1 0
5
0
Fros
t pro
tect
ion fo
r gu
tters
and d
ownp
ipes
47Technical handbook
FROST PROTECTION FOR GuTTERS AND DOWNPIPES11 SPECiAL inSTALLATiOn inSTRuCTiOnS
≥ 200 mm
box gutter < 200 mm• OneheatingcableofGM-2Xonly
≥ 200 mm
box gutter > 200 mm• MultipleheatingcablesofGM-2X• 2pcspacerGM-RAKEpermeterof
gutter edges: GM-RAKE provides mechanical protection against damages
fastening of the gutter cablesOn the roof, eaves bricks, gutter and drainpipe with GM-RAKE edge protection brackets (incl. cable ties).
do not install RayClic immersed in water.do not bury RayClic in the ground.
in the drainpipe: always install the cable as far as the frost-free area(approx. 1m deep)
Fros
t pro
tect
ion fo
r gu
tters
and d
ownp
ipes
48 THERMAL buiLding SOLuTiOnS
(Dimensions in mm)
PG9 (Dimensions in mm)
58 53
R
AC 230V 50/60Hz IP 20
Relais: 10(4)A, AC 230V Alarm: 2(1)A, AC 230V
Do not open while energized Nicht unter Spannung öffnen Ne pas ouvrir sous tension
EMDR-10
T2A IEC127–2/V
PE PE PE 1 2 3 4 5 6 7 8 9 10 11
C
–25
–20 –15
–10
–5 TEST
C –3
–2 –1
0 1 2 3 4 5
6
0
10
20 30 40
50
min
1 2 3 4 5 6
7 8 9
10
106
90
60
35 52 40
50 38
(Dimensions in mm)
Ø 9, 5
12 x 6
activ e sensor length 500
650 4 m
HOuSing
AMbiEnT TEMPERATuRE SEnSOR (ViA-du-A10)
MOiSTuRE SEnSOR (HARd-45)
TECHniCAL dATA
TEMPERATuRE And MOiSTuRE COnTROL uniT EMdR-10
Supply voltage 230 VAC, ±10%, 50HzPower consumption max. 4 VAMax. switching capacity Imax 10(4)A / 230 VAC, SPST,
potential 230 VACTemperature adjustment range –3°C to +6°C (factory setting +2°C)Lower limit temperature test, –25°C to –5°C
(factory setting adjustment range –15°C)Operating differential ±0.5 KMeasuring accuracy ±1.5 KMoisture adjustment range 1 (max. sensibility) to 10 (min. sensibility)
(factory setting 5)Post heating time adjustment range 0 to 60 minutes (factory setting 60 minutes)Alarm relay Imax 2(1)A / 230 VAC, SPDT, potential-freeMoisture sensor (output) Imax 315mA / 230 VAC, with fuse 5 x 20mm
T 315mA according to IEC127-2/VMounting DIN rail according to DIN EN 50022-35 Low voltage directive EN 60730EMC EN 50081-1 (emission) and EN 50082-1
(immunity)Terminals 2.5 mm2 (stranded conductors),
4 mm2 (solid conductors)Protection class II (panel mounted)
Ambient temperature range 0°C to +50°CIngress protection IP20Housing material Noryl (self-extinguishing according to uL
94 V-0)Weight approx. 350 g
Sensor type PTC (FL 103)Ingress protection IP54Terminals 2.5 mm2
Sensor cable 2 x 1.5 mm2, max. 100 m (not included)Exposure temperature –30°C to +80°CMounting Wall mounting
Sensor type PTCPower consumption 9 W to 18 WAmbient temperature range –30°C to +65°C continuousSupply voltage 230 VAC, ±10%, 50HzConnection cable 3 x 1.5 mm2, 4 m, the connection cable can
be extended to max. 100 m at 3 x 1.5 mm
Fros
t pro
tect
ion fo
r gu
tters
and d
ownp
ipes
49Technical handbook
WiRing diAgRAM fOR EMdR-10
EMdR-10 WiTHOuT COnTACTOR
EMdR-10 WiTH COnTACTOR
* Two- or four-pole electrical protection by circuit breaker may be needed for local circumstances, standards and regulations
** Depending on the application, one or three-pole circuit breakers or contactors may be used
*** Potential-free alarm contacts for connection to the BMS
PENL
Temperaturesensor
30mA
Heating cable
Moi
stur
e se
nsor
PE PE PE N N N L L LS T1 T2 Alarm
PE PE PE 1 2 3 4 5 6
7 8
9 10
11
AC 230V 50/60Hz
IP 20 Relais: 10(4)A, AC 230V
Alarm: 2(1)A, AC 230V Do not open while energized
Nicht unter Spannung öffnen
Ne pas ouvrir sous tension
R
EMDR-10
T2A IEC127–2/V
C
–25
–20 –15
–10 –5
TEST
C
–3
–2
–1 0 1 2
3 4 5
6
0
5 10 15
20 25 min
1 2 3 4 5 6
7 8 9
10
PE N
L1 L2 L3
PE PE PE N N N L L LS T1 T2 Alarm
Fros
t pro
tect
ion fo
r gu
tters
and d
ownp
ipes
50 THERMAL buiLding SOLuTiOnS
122 mm110 mm
120
mm
90 m
m
45 mm
29 mm
Self-regulatingheating cable
• 3 0 • 2 0 • 1 0 • 0 • - 1
0 •
- 2 0
2 5 2 0 1 5 1 0
5
0
* Two- or four-pole electrical protection by circuit-breaker may be needed for local circumstances, standards and regulations
THERMOSTAT HTS-d
TECHniCAL dATA
Temperature range –20°C to +25°COperating voltage AC 230 V, 50 HzMax. switch current 16 A / AC 250 VMax. exposure temperature 50°CSwitch temperature difference 1 K - 3 KTemperature setting under the housing coverProtective system IP 65
WiRing diAgRAM fOR HTS-d
HTS-d diRECT
Fros
t pro
tect
ion fo
r gu
tters
and d
ownp
ipes
51Technical handbook
COnTROL PAnEL
TECHniCAL dATAThe standard control panels for 3, 6, 9 or 12 heating circuits comprise a steel plate housing and are completely assembled, in turnkey condition, wired and inspected. Paintwork Structural paint, RAL 7035, light grayProtection class IP54 Location InteriorAmbient temperatures: +5°C to +35°C Cable inserts Metal plate in base of housing with metric
breakout aperturesVersion acc. to VDE 0660, Part 500 and VBG 4 Mains power connection 3-phase to 400V/230V, 50 Hz, with N and PE
Safety system for roof gutters
Cabinet type SbS-03-EV-10 SbS-06-EV-10 SbS-09-EV-10 SbS-12-EV-10Max. number of heating circuits 3 6 9 12Enclosure version Wall version Wall version Wall version Wall version Dimensions Width mm 380 380 600 760
Height mm 600 600 600 760 Depth mm 210 210 210 210
Weight approx. kg 20 30 32 52 Connected rating kW 14 28 42 56 Fuse protection provided max. by customer
A 3 x 32ANH-00
3 x 40ANH-00
3 x 63ANH-00
3 x 80A NH-00
Switch cabinet equipmentMains isolator switch, 3-pin, 32 A unit 1Mains isolator switch, 3-pin, 63 A unit 1 1Mains isolator switch, 3-pin, 100 A unit 1Power isolator, S 2° unit 1 1 1 1 Combination of RCD/CB, C 20A, 30 mA, 4-pin with auxiliary switch
unit 1 2 3 4
Power contactor, 3 x 35° unit 1 2 3 4 Auxiliary contactor unit 1 1 1 1 Indicator‘Operating‘ unit 1 2 3 4
Indicator ‘Fault‘ unit 1 1 1 1 EMDR-10 control unit unit 1 1 1 1
Fros
t pro
tect
ion fo
r gu
tters
and d
ownp
ipes
52 THERMAL buiLding SOLuTiOnS
APPLiCATiOn in COnCRETEThe Raychem range of products has been specifically designed to meet the requirements of commercial, indus-trial, and residential applications. Whether in concrete, sand, or asphalt, a Raychem system exists to provide a fast, reliable, and easy install solution.
Each Raychem heating solution is complete with a Smart control and monitoring unit, providing useful user data and excellent energy efficient performance. The multi-sensor control and monitoring device (VIA-Du-20) is compatible with all ramp snow melting solutions.
RAyCHEM SOLuTiOnS fOR COnCRETEProduct description
Reinforced concrete surfaces EM2-XR Self-Regulating heating cable for reinforced concrete ramps
Domestic and light commercial ground heating applications. EM2-CM Pre-terminated constant wattage heating mat for ramp, pavement
and track heating
Stairs; wheelchair access ramps EM4-CW 400V Pre-terminated constant wattage heating cable solution for larger concrete areas and stairs
* Optional, only needed when “local detection” is selected.
SNOW MELTING FOR RAMPS, ACCESS WAYS, AND FOOTPATHS
ice and snow on paths, loading bays, driveways, ramps, stairs and other access ways, can present a major problem causing accidents and delays. Raychem a ground heating solutions prevent snow and ice formation.
Ambient temperature sensor* VIA-Du-A10 (incl.)
Temperature and moisture sensor VIA-Du-S20
Connection cable (VIA-L1)
Control unit (VIA-Du-20)
Self-regulating heating cable (EM2-XR) or constant power heating cable (EM4-CW)
Connection and end seal kit (VIA-CE1)
Connection and end seal kit (VIA-CE1)
1 5
2
7
6
3
4
Optional: SBS-xx-VV-20/SBS-xx-CW-40/SBS-xx-CM-20 Contains: Control panel with RCD (30 mA),Circuit Breaker (C characteristics), mains contactor VIA-Du 20 control unit
1
5
2
7
6
6
3
4
Snow
mel
ting o
f ram
ps,
step
s, fo
otpa
ths a
nd
acce
sswa
ys
53Technical handbook
APPLiCATiOn in ASPHALT
For more information on snow melting products, please refer to document CDE-1540.
* Optional, only needed when “local detection” is selected.
Ambient temperature sensor* VIA-Du-A10 (incl.)
Temperature and moisture sensor VIA-Du-S20
Pre-engineered cold lead
Control unit (VIA-Du-20)
Mineral-Insulated heating cable (EM2-MI)
Connection between heater cable and cold lead (Pre-engineered)
1 4
2
6
5
3
Optional: SBS-xx-MV-20 Contains: control panel with RCD (30 mA), circuit breaker (C characteristics) Mains contactor for VIA-Du-20 control unit
1
5
2
63
4
RAyCHEM SOLuTiOnS fOR inSTALLATiOn diRECTLy bELOW HOT-POuREd ASPHALTProduct description
Installation in hot asphalt EM2-MI Mineral insulated, high temperature resistant heating cable for asphalt ramps
Snow
mel
ting o
f ram
ps,
step
s, fo
otpa
ths a
nd
acce
sswa
ys
54 THERMAL buiLding SOLuTiOnS
Product features & Selection guide:Product features EM2-xR EM2-Mi EM2-CM EM4-CW
Product Description Self-regulating heating cable
Mineral Insulated constant power heating cable
Constant power polymeric pre-terminat-ed ramp heating mat system
Constant power polymeric pre-termi-nated heating cable system
Features Extremely robust self-regulating heat-ing cable for flexible installation under severe site conditions
Pre-terminated heating cable with exceptional resistance to high temperature asphalt surfaces
Pre-terminated ramp, walkway, and track heating (Roll-out) mat for fast and simple installation
Pre-terminated con-stant power heating cable for larger areas & 400 V power supplies
Voltage Rating 230 Vac 230 Vac 230 Vac 400 Vac
Nominal power output
90 W/m @ 0°C 50 W/m 300 W/m2 25 W/m
Maximum circuit length
85 m 136 m 12.6 m2 (Mat size = 21 m x 0,60 m)
250 m
Maximum exposure temperature
100°C 250°C 65°C 65°C
Connections & termination
Cut-to-length system for flexible field termination (using Raychem heat-shrink components).Pre-terminated cable lengths (fixed or configured) available. Contact us.
Factory pre-terminated Factory pre-terminated Factory pre-terminated
Compatible control unit
VIA-Du-20 VIA-Du-20 VIA-Du-20 VIA-Du-20
Approvals VDE / CE VDE / CE VDE / CE VDE / CE
Suitable for installation on reinforcement bar
★★★ Highly recommended
★★ Recommended
★★ Recommended
Suitable for installa-tion in direct contact with hot poured asphalt
★★★ Highly recommended
Suitable for embed-ding in sand sub-level
★★ Recommended
★★ Recommended
★★★ Highly recommended
★★★ Highly recommended
Cold lead included Not as standard. Contact Pentair for information on Configured EM2-XR heating elements.
3 m (at each end of heater cable)
4 m 4 m
Dual Wire / Single Wire construction
Dual Single Dual Dual
SySTEM OVERViEW
Snow
mel
ting o
f ram
ps,
step
s, fo
otpa
ths a
nd
acce
sswa
ys
55Technical handbook
ELECTRICAL uNDERFLOOR HEATING
THE RAyCHEM undERfLOOR HEATing RAngE COMPRiSES:
5 gOOd REASOnS TO CHOOSE RAyCHEM SMART undERfLOOR HEATing1 Comfortable and safe2 Hassle free installation and
maintenance free3 Energy-efficient and cost saving4 Can be installed under all floor
coverings5 Total care warranty
Comfort is everything, especially in the home. With Raychem’s smart electrical underfloor heating, you can offer a beautiful warm floor; hassle free to your customers!
• T2Red:Theinnovativeanduniqueself-regulatingfloorheatingcable.• T2RedwithT2Reflecta:Theenergy-savingunderfloorheatingsystem.
This system combines the self-regulating heating cable T2Red with T2Reflecta, the grooved, thermally insulated, aluminium-covered plate.
• T2QuickNet:Theultrathinheatingmat(twopoweroptionsavailable).• T2Blue:Therobust,flexible,pre-terminated(dualwire,andscreened)
cable system.• T2Green:thelowoutputheatingcabledesignedspeciallyforverywell
insulated and near zero energy houses.• CeraPro:Theultrathin,robust,undertileheatingcablesolutionwith
“Tape & Mesh” fixing accessories included.• “Smart”thermostatswhichofferzoned,programmableheatingcontrol,
a requirement of Part L of the building regulations.• Acompleterangeofinstallationaccessoriesandcomponentsincluding: – Floor primers – Adhesives – Fixing accessories
elec
trica
l und
erflo
or
heat
ing
56 THERMAL buiLding SOLuTiOnS
12 15 20Total care warranty
Total care warranty
Total care warranty
12 15 20
12 15 20Total care warranty
Total care warranty
Total care warranty
12 15 20
SMART SERViCES fOR dESign And SPECifiCATiOn
OnLinE SuPPORT
SAfETy And RELiAbiLiTy
Pentair offers a comprehensive design and specification service for consultants and architects, free of charge.using bespoke floor heating design software, we provide:• Optimisedinstallationplansforthedesignerandinstallerin2&3dimensional
views.• Zonebyzoneproductdataincludingheatoutputperroomandperm2 in the
room.• Detailedbillofmaterials,optimisedbythesoftwaretominimisewaste.
With a design proposal complete, we provide specification support to ensure quality procurement.
Design and specification tools are available at:www.pentairthermal.com• Productselectionguide• A“Wedesignitforyou”e-requestservice.
The Raychem systems and services are supported by a dedicated specifications team. We can provide sound design advice specific to your project needs.
We are also available to:• Supportconsultantsandarchitectsatearlydesign/conceptstageand provide floor heating options.• Visittheprojectsitetosurveytherequirementsandmakerecommendations
for the consultant, client, and contractor.• ProvidecontactdetailsoflocalsuppliersandinstallersofRaychemfloor
heating systems.
Qualityproducts-installedandcheckedbyaprofessionalelectrician-assurehome owners the comfort of a warm floor with Total Care. When installing Raychem floor heating systems, electricians can now offer a 12 Year Total Care Warranty to their customers. Certified Pro* installers can extend the Total Care Warranty up to 20 years.Total Care = doing what it takes to assure a warm floor. In the rare event that our product would fail and we cannot repair it, we will not only provide you with a new product and pay the costs of installing it. We will also take care that the floor cov-ering is repaired or replaced to the equivalent standard.
LOCAL ExPERT TEAM SuPPORT
* For more information: ask for the Floorheating handbook or go to www.pentairthermal.com
elec
trica
l und
erflo
or
heat
ing
57Technical handbook
Subfloor
Levelling compound
T2Reflecta Plates
Wood floor underlayLaminate or wood
T2Red heating cable
Expansion joint
• TheT2Reflectasystemcombinestheself-regulatingT2Redheatingcablewiththe pre-grooved T2Reflecta; a thermally insulated, aluminium-covered plate.
• Providesextraenergysavingsof20%ormore• Canbeadaptedtoallroomsizesandbeinstalledon
most sub floors.• Firstchoiceforwoodenorlaminatefloorsindryareas.• Automaticallyadjustsitsheatoutputdependenton
ambient floor temperature.
T2REd WiTH T2REfLECTA: THE EnERgy-EffiCiEnT SOLuTiOn
Tiles
Wood
Laminate
Metal mesh
T2Red cable
Foil
Expansion jointTiles
WoodLaminate
Primer
T2Red cable
Levelling compoundSubfloorSubfloor
Water barrier
Adhesive
Screed
Adhesive
Insulat
ion
Wood floor
underlay
Adhesive Adhesive
Subfloo
r
Wood floor
underlay
T2REd: THE SELf- REguLATing HEATing CAbLE
Senses other sources of heat and adjusts its heat output accordingly. • Makeswetfloorsdryfaster.• Noriskofoverheating.• Canbeinstalledonallsubfloors(plastic,concrete,wood,
carpets) - in dry or wet areas.• Canbeadaptedtoallroomsizes.
ELECTRICAL uNDERFLOOR HEATING
elec
trica
l und
erflo
or
heat
ing
58 THERMAL buiLding SOLuTiOnS
Topfloor
T2QuickNet
Primer
Subfloor
Tile adhesive
Expansion joint
T2quiCKnET: THE idEAL SOLuTiOn fOR REnOVATiOn
• ThethinT2QuickNetmatistheidealsolutionforrenovationespeciallyfortilefloors. The ultra-thin (3 mm) mat is laid directly in the filler.
• Itcanbeinstalledonallsubfloorswhicharesufficientlyinsulatedandconforming to applicable building regulations.
• T2QuickNetexistsintwoversions:averypopular90W/m2 version and a 160 W/m2 version when more output is required.
Tiles
T2QuickNet Tile adhesive
Subfloor
Isolecta
10 mm
Expansion joint
T2quiCKnET + iSOLECTA inSuLATiOn bOARd
Ideal for renovation projects:• Extrainsulationlayer• Fastheatup:Reducingheatuptimebyadditionalinsulationlayer
underneathofT2QuickNet• Energysavingsupto65%duringheatupand20%insteadystate
conditions
elec
trica
l und
erflo
or
heat
ing
59Technical handbook
T2bLuE: THE fLExibLE undERfLOOR HEATing CAbLE
Tiles
Subfloor
Adhesive
Levelling compound
Waterproof membrane (optional)
Primer
T2Blue heating cable
Expansion joint
Tiles
Foil Insu
lation
type
Tile adhesive
Leveling co
mpound
Subf
loor
T2Blue h
eatin
g cable
Metal
mes
h
Expansion joint
• Theflexibleunderfloorheatingcableissuitableforinstallationdirectlyinalevelling compound, screed, or concrete.
• Heatingcablewithpre-fabricatedpowerconnectioncable• Idealforcomplexfloorlayouts.• Poweroutputflexibilitybyvaryingthedistancebetweenheatingcables.• Suitableforlayinginmilledgroovesinthescreed/concretewithoutincreasing
the total height of the floor structure
elec
trica
l und
erflo
or
heat
ing
60 THERMAL buiLding SOLuTiOnS
CeraPro heating cable
Subfloor
Isolecta 10 mm
Tiles
Tile
adhesive
Double sided tape
Mesh
Expansion joint
CERAPRO + iSOLECTA: THE RObuST, undER TiLE HEATing CAbLE SOLuTiOn
• Theultrathin,robustheatingcablecanbeinstalleddirectlyinthetileadhesivewithout the need for additional screeding over the heater.
• ThehighgradeFluoropolymermaterialgivehighresistancetomechanicaldamage during installation when compared with market alternatives.
• Itcanbeinstalledonbothwoodenandconcretesubfloors(maximuminstalledoutput of 100 W/m2 on wooden subfloors.)
• Theheaterspacingcanbeadjustedtoallowfortypicaloutputsbetween 100 and 150 W/m2.
• The8kitsizesaresuppliedcompletewith“Tape‘n’Mesh”installationproductsand an easy to use cable spacing guide.
• Isolectainsulationlayer
elec
trica
l und
erflo
or
heat
ing
61Technical handbook
RAYCHEM FLOOR HEATING THERMOSTATS
3 working modes• Constant Mode• Event Mode• Boost Mode3 Sets of settings• Event setting (programming of the weekly schedule)• user settings (settings that helps users customizing their thermostat)• Engineer settings (expert settings that help installers fine tune to
specific needs)
SOFTWARE IN 11 LANGUAGES 2 SENSORS / 4 SENSING MODES• Floor sensing• Room Sensing• Room sensing with floor limiter• No sensor mode
NRG-DM
ELEGANT LARGE AND CLEAR DISPLAYEASY NAVIGATION3 operation modes• Standard Comfort mode (1 temperature set point- manual on/off).• Editable program (4 temperature and time periods per day).• Holiday mode (standby).
CAPACITIVE TOUCH TECHNOLOGYONE GREEN LEAF BUTTON DOES IT ALL
GREEN LEAF ELEGANT PROGRAMMABLE THERMOSTAT
• Backlid LCD display• Heat-Booster function for fast heat up• Design for long lasting • Safety Easy to install
NRG-TEMP ROBUST AND EASY TO INSTALL THERMOSTATel
ectri
cal u
nder
floor
he
atin
g
62 THERMAL buiLding SOLuTiOnS
MuLTIPLE APPLICATION CONTROL &MONITORING SYSTEM
RAyCHEM ACS-30The Raychem ACS-30 system provides electronic control & monitoring for multi-circuit heat tracing applications, including pipe frost protection, surface snow melting, hot water temperature maintenance, gutter & roof de-icing, temperature flow maintenance, and electrical underfloor heating.
The Raychem ACS-30 can control up to 260 heat tracing circuits of any ap-plication, from a single user interface, allowing building owners and facilities managers to monitor and manage their building’s heat tracing systems from a single point.
ACS-30 is a modular control & moni-toring solution which can be designed to exactly meet the needs of the building. Power and control modules (PCMs) can be positioned throughout the building in accordance with the building system requirements. Multiple PCMs can be connected together pro-viding a complete view of the buildings heat tracing systems.
ACS-30-Eu-uiT2 User Interface Terminal (UIT)PCN: 1244-012864• Panelmountedtouchscreendisplay• Control&Monitoringof260heatingcircuits• 22cmXGAcolourtouchscreendisplay.• RS485,RS232,or10/100Base-TEthernetcommunicationportstoallow
communication with external distributed control systems or building management systems (BMS).
• BACnet,MetasysN2andLonWorkstoModbusprotocolgatewayswith pre-programmed Modbus registration is also available.
• TheACS-30-EU-UIT2unitisdesignedforindooruseinnon-hazardouslocationinstallations
ACS-30-Eu-PCM2 (Power & Control Module)6 Version available as standard:• 5,10,and15circuitcontrolperpanel• 20Aor32Aswitchingcapacitypercircuitavailable.• Powerconnection,control,andpowerdistributiontotheheattracingcircuits.• Robustenclosureisapprovedfornon-hazardousinstallationindoor.• PCMprovidesconnectiontotheincomingpowersupplyandpowerdistribution
& electrical protection to the heat tracing circuits.
The PCM module also provides:• Groundfaultmonitoring• Linecurrentmonitoring• Alarmcapability• RTD(ResistanceTemperatureDetector)inputcapabilityforeachindividual
heating circuit.
Raychem ACS-30 Multi-circuit, multi-application Control & Monitoring system for commercial heat tracing applications.
Cont
rol &
m
onito
ring s
yste
m
63Technical handbook
PCn Product name Product description EAn Code1244-012868 ACS-30-Eu-PCM2-5-20A Power Control Module for ACS-30
(5 circuit module with 20Amp electrical protection per circuit)
5414506014341
1244-012869 ACS-30-Eu-PCM2-10-20A Power Control Module for ACS-30 (10 circuit module with 20Amp electrical protection per circuit)
5414506014358
1244-012870 ACS-30-Eu-PCM2-15-20A Power Control Module for ACS-30 (15 circuit module with 20Amp electrical protection per circuit)
5414506014365
1244-012871 ACS-30-Eu-PCM2-5-32A Power Control Module for ACS-30 (5 circuit module with 32Amp electrical protection per circuit)
5414506014372
1244-012872 ACS-30-Eu-PCM2-10-32A Power Control Module for ACS-30 (10 circuit module with 32Amp electrical protection per circuit)
5414506014389
1244-012873 ACS-30-Eu-PCM2-15-32A Power Control Module for ACS-30 (15 circuit module with 32Amp electrical protection per circuit)
5414506014396
PCN: 1244-012867• Collectssensor/temperatureinputsformonitoringoftheheattracing.• 1RMMprovidesupto8sensorinputspermodulewithfeedback
to the ACS-30-Eu-uIT2 • Maximum16RMMdevicesperUserinterfaceterminal(UIT).• TwistedpairRS-485cableconnectsupto16RMMunitsproviding128
additional temperature monitoring sensor inputs. • Remotelylocatedadjacenttothedesiredmeasurementlocations.• ACS-30-EU-MONI-RMM2-Emodulecomespre-installedinsideacompact
enclosure.
PCN: 1244-012865• ExternalSensordeviceforGuttersnowmelting&de-icingapplications.• Providessmartsensorinputforroof&gutterde-icingapplications.• Temperature&moisturesensinginputfortheACS-30controlsystem.• Modulecanbepositionedneartotheheatedareaandisconnectedtothe
PCM module via a 3-wire cable. • 4mexternaltemperatureandmoisturesensortobepositionedattheheated
surface. The sensor cold lead cable can be extended to a maximum length of 100 m (using 3 x 1.5 mm2 cable.)
• TheoutputfromtheACS-30-EU-EMDR-10moduleenablestheswitchingof the heating circuits within the power & control module (PCM).
PCN: 1244-012866• External Sensor device for ground surface snow melting applications.• Providessmartsensorinputforsurfacesnowmeltingandde-icingapplications.• Themoduleprovidesgroundtemperatureandmoisturesensingforthe
ACS-30 control system. • PositionedneartotheheatedareaandisconnectedtothePCMmodulevia
a 3-wire cable. • Providedwitha15mexternalgroundtemperatureandmoisturesensorto
be positioned at the heated surface.• TheoutputfromtheACS-30-EU-VIA-DU-20-MODenablestheswitchingof
the heating circuits within the power & control module (PCM).
PCN: P000001983 The Raychem ProtoNode is an external, high performance multi-protocol gateway for customers needing protocol translation between Building Management Systems (BMS) using BACnet® or Metasys® N2 and the Raychem ACS-30 or TTSIM controllers.
• The most flexible and versatile multi-protocol device server on the market.• BACnetInternational’sBTLCertificationmakestheProtoNode-RERthe
most reliable gateway on the market.• Multi-clientandmulti-serversupportensuresinteroperabilitybetween
any Industrial and or Building Automation protocols. • Flashupgradable.
ACS-30-Eu-MOni-RMM2-E
ACS-30-Eu-EMdR-10-MOd
Protonode-RER-10K
ACS-30-Eu-ViA-du-20-MOd
Cont
rol &
m
onito
ring s
yste
m
64 THERMAL buiLding SOLuTiOnS
GENERAL INSTALLATION INSTRuCTIONS
general order of events • Thesystemisdesignedandtheinstallationplanned• Thepipeworkispressuretestedorotherwisecheckedforleaks• TheHWAT-L/M/Rcableistestedandtheninstalledonthedesignatedpipes• Thecomponentsareinstalledandeachcircuitistested• Thecorrectthermalinsulationisapplied,withoutdelay,labelledandthe
system test repeated• Thesupplyvoltagecablesandcircuitbreakersareinstalledtoeachcircuit• Thesystemiscommissioned(see“Systemstart-up”below)
Circuit protection• Supplyvoltage230VAC,50Hz• Therequiredprotectivemeasuresoftherelevantregulationsmustbe
complied with.• Ctypecircuitbreaker(anti-surgefuse)• Residualcurrentdevice(rcd30mA)required.Maximumapprox.500mof
self-regulating heating cable can be monitored per rcd
Testing• Visualinspectionfordamageandfault-freeinstallationoftheaccessories• Properinstallationofthesystem• Heatingcableaffixedtoallnecessarypipes• Nomechanicaldamagetoheatingcable(e.g.cuts,cracks,etc.)• Nothermaldamage• Properconnectionofallcomponentsincludingpowersupplies• Insulationresistancemeasurementwhenheatingcableisreceivedandbefore
and after installation of the thermal insulation. The test voltage should be 2500 Vdc, but it must not be lower than 500 Vdc. The insulation resistance, irrespective of the cable length, must not be less than 100 Mohms.
If the resistance falls below this value, the source of the fault must be investigated, eliminated, and re-tested.
• MeasurementA:Phaseandneutraltothebraid• MeasurementB:Braidtothepipework• Afterswitchingon,thecableendsmustbewarmafter5to10
minutes
instructions for the placing of the heat insulation• Forproblem-freeoperationoftheself-regulatingheatingcables,thematerial
quality and thickness of the thermal insulation should be in accordance with the design parameters, and this insulation must be installed correctly
• Allpartsofthepipework,includingvalves,walltransitpoints,etc.mustbefullyinsulated
Operation/System start-up• 1)Forsmallinstallations,turnonthecircuitbreakersandpreferablyleavethe
system overnight for the water to warm up and stabilise 2) For bigger installations or for a faster start-up, first turn on the main water
heater and open the outlet/tap at the end of the pipework run until the water feels warm and then turn on the circuit breakers
If the piping system is closed, such as by pressure-reducing valves or isolation valves, you must provide some method of pressure relief to allow for thermal expansion of the water during heat-up
• Undernormaloperatingconditions,theheatingcablesaremaintenance-free. Pentair recommend that the insulation resistance should be checked periodically and compared with the original values. If the reading falls below the minimum value (100 Mohms) determine the cause and rectify before re-use
• Thespecifiedmaximumambientandoperatingtemperaturesshould not be exceeded
• Intheeventofrepairtothepipework,theheatingcablemustbeprotectedagainst damage. Correct function of the electrical protection system should be maintained. To prevent shock or personal injury, turn off the power at the circuit breaker before testing or working on the heating cable or piping
Typical installation schedule for hot water temperature maintenance
Circuit protection, testing and operation for all systems
CHECKLiST fOR PRObLEM-fREE inSTALLATiOn And SAfE OPERATiOn
Measurement A
Measurement B
gene
ral i
nsta
llatio
n in
stru
ction
s
65Technical handbook
• Followingthecompletionoftherepairwork,thecircuitshouldonceagainbetested (see above)
• Alltheimportantpartsofthecontrols,thermostats,etc.mustbecheckedforcorrect operation once a year, normally in the autumn
Only for hot water temperature maintenanceNewly installed heating cables have lower power at start-up of the installation. The nominal power will be reached after approximately 4 weeks of continuous operation
• Themaintenancetemperatureshouldbe5°Cto10°Cbelowthehotwater temperature in the boiler
The actual installation times achieved may deviate according to the conditions on site.
PipeworkInstallation of heating cable on pipes including fastening, standard installation:
25 metres/hour
Connection system (electrical connection)RayClic-CE-02 2 min/pc.RayClic-S-02/RayClic-PS-02 4 min/pc.RayClic-T-02/RayClic-PT-02 6 min/pc.RayClic-X-02 8 min/pc.RayClic-E-02 1 min/pc.
Heat-shrink connection system (electrical connection)C25-21 15 min/pc.E-06 5 min/pc.CE20-01 20 min/pc.
OtherTesting, visual inspection, insulation resistance measurement (2x)
10 min/heating circuit
Connecting the heating circuit in the switch box 10 min/heating circuit
Standard installation times
gene
ral i
nsta
llatio
n in
stru
ction
s
66 THERMAL buiLding SOLuTiOnS
GENERAL INSTALLATION INSTRuCTIONS
Trouble shooting guidefault Possible causes MeasuresCircuit-breaker trips: Circuit breaker wrong type: e.g. type B
instead of C:Change to C Type
Circuit breaker undersized If the power supply cable permits, install a larger circuit breaker
Circuit too long Split the circuit on 2 circuit breakersShort-circuit/earth fault Eliminate short-circuit/earth fault
(cable ends should not be twisted)Circuit breaker faulty Replace faulty circuit breakerNo end seal Install end sealConductor (or cable) twisted un-twist and install end seal
RCD residual current device trips: More than 500 m of frost protection heating cable installed per rcd
Install additional rcd residual current device
Earth fault at connection or in end seal Rectify earth faultCable damaged Repair cable where damagedMoisture in the junction box Eliminate moisture
Pipeline does not become warm - Heating cable cold:
Circuit-breaker has tripped See section circuit breaker
Residual current device has tripped See section residual current deviceNo mains voltage Switch onCable or cold lead not connected Connect cable or cold leadCable not inserted correctly in connection system or end seal
Insert cable according to installation instructions (fully insert cable)
Water temperature is not maintained but the cable gives high output:
No insulation Insulation thickness insufficient Insulation according to tables in design guides
Insulation wet Dry insulationCold water is running from the boiler Test boiler temperatureCold water is pumping through mixer tap into the hot water pipe. Insulation according to tables in design guides.
Test the mixer tap
Note: Installation and operation information is available from Pentair in document reference: CDE-1547.
gene
ral i
nsta
llatio
n in
stru
ction
s
67Technical handbook
hot w
ater
tem
pera
ture
m
aint
enan
ce
Fros
t pro
tect
ion
for p
ipes
Fr
ost p
rote
ctio
n
for g
utte
rs an
d
down
pipe
s
Snow
mel
ting
for r
amps
, ac
cess
way
s, an
d fo
otpa
ths
Cabl
e typ
e hW
at-l
hWat
-mhW
at-r
FS-a
-2X
FS-B
-2X
FS-C
-2X
FS-C
10-2
Xgm
-2X/
gm-2
Xtem
2-Xr
em2-
mi
em2-
Cmem
4-CW
Colo
urM
att/G
loss
yno
min
al vo
ltage
230 V
AC
230 V
AC
230 V
AC
230 V
AC
230 V
AC
230 V
AC
230 V
AC
230 V
AC
230 V
AC
230 V
AC
230 V
AC
400 V
AC
nom
inal
powe
r ou
tput
(*
on in
sula
ted
met
al pi
pes)
7 W/m
at
45°C
9 W/m
at
55°C
12
W/m
at
70°C
10
W/m
at 5°
C26
W/m
at 5°
C31
W/m
at 5°
C
22 W
/m at
40°C
10 W
/m at
5°C
36 W
/m in
ice a
nd
18 W
/m in
air a
t 0°C
90 W
/m
at 0°
C50
W/m
300 W
/m2
25 W
/m
C-ty
pe ci
rcui
t-br
eake
r acc
ordi
ng
to se
lect
ed ki
t
max.
20 A
max.
20 A
max.
20 A
max.
16 A
max.
16 A
max.
16 A
max.
20 A
max.
20 A
max.
50 A
max.
20 A
max.
20 A
max.
20 A
max
. circ
uit
leng
th
180 m
20
A10
0 m
20 A
100 m
20
A15
0 m
16 A
105 m
16 A
90 m
16 A
180 m
20 A
80 m
20 A
85 m
50 A
136 m
21 m
(12
.6 m2
)25
0 m
min
. ben
ding
radi
us
10 m
m 10
mm
10 m
m10
mm
10 m
m10
mm
10 m
m10
mm
50 m
m50
mm
–30
mm
max
. con
tinou
s ex
posu
re
tem
pera
ture
65°C
65°C
80
°C65
°C65
°C95
°C90
°C65
°C10
0°C
250°
C65
°C65
°C
max
. exp
osur
e te
mpe
ratu
re
(pow
er-o
n con
ditio
n –
800 h
. cum
ulat
ive)
85°C
85°C
90°C
85°C
85°C
95°C
90°C
85°C
110°
C25
0°C
65°C
65°C
max
. dim
ensio
ns in
m
m (W
x h)
13.8
x 6.8
13
.7 x 7
.6
16.1
x 6.7
13.7
x 6.2
13.7
x 6.2
12.7
x 5.3
16 x
6.813
.7 x 6
.218
.9 x
9.5mi
n 4,8;
ma
x. 6,3
5,0 x
7,05,0
x 7,0
Wei
ght
0.12 k
g/m
0.12 k
g/m
0.14 k
g/m
0.13 k
g/m
0.13 k
g/m
0.13 k
g/m
0.14 k
g/m
0.13 k
g/m
0.27 k
g/m
––
–
appr
oval
s Bs
/ ÖV
E / VD
E / s
EV /
CsTB
/ sV
gW /
DVgW
/ CE
/ VD
ECE
/ VD
E
Cont
rol u
nits
HW
AT-T
55
(for b
ranch
line
s up
to 50
m on
ly)
HWAT
-ECO
**
HWAT
-T55
(fo
r bran
ch li
nes
up to
50m
only)
HWAT
-ECO
**
HWAT
-T55
(fo
r bran
ch li
nes
up to
50m
only)
AT-T
s-13
AT-T
s-14
rAYs
TAT-
CONT
rOL-1
0 rA
YsTA
T-EC
O-10
**
rAYs
TAT-
CONT
rOL-1
1-DI
N
AT-T
s-13
AT-T
s-14
rAYs
TAT-
CONT
rOL-1
0 rA
YsTA
T-EC
O-10
**rA
YsTA
T-CO
NTrO
L-11-
DIN
AT-T
s-13
AT-T
s-14
rAYs
TAT-
CONT
rOL-1
0 rA
YsTA
T-CO
NTrO
L-11-
DIN
AT-T
s-13
AT-T
s-14
rAYs
TAT-
CONT
rOL-1
0*
rAYs
TAT-
ECO-
10**
rAYs
TAT-
CONT
rOL-1
1-DI
N
EmDr
-10*
*HT
s-D
VIA-D
u-20
**VIA
-Du-
20**
VIA-D
u-20
**VIA
-Du-
20**
Conn
ectio
n sys
tem
Junc
tion b
ox–
––
––
JB16
-02
JB16
-02
–VIA
-JB2
VIA-J
B-2
VIA-J
B-2
VIA-J
B-2
Conn
ectio
n kit
rayC
licra
yClic
rayC
licra
yClic
rayC
licCE
20-0
1CE
20-0
1ra
yClic
VIA-C
E1pr
e-ins
talle
d
Supp
ort b
rack
etinc
luded
in
the k
itinc
luded
in
the k
itinc
luded
in
the k
itinc
luded
in th
e kit
includ
ed in
the k
itJB
-sB-
08
JB-s
B-08
includ
ed
in th
e kit
––
––
Appr
oval
s: B
S/VD
E/Ö
VE/E
RFA
/CE
* Fo
r max
circ
uit,
Rays
tat c
ontr
olle
r will
be
requ
ired.
**
TECHNICAL DATA Choice of accessories
68 THERMAL buiLding SOLuTiOnS
C-type Circuit
breaker (Ampères)
Cable type Max. Circuit length (m)
Max. length of the power cable
3 x 1,5 mm2 3 x 2,5 mm2 3 x 4 mm2 3 x 6 mm2 3 x 10 mm2 3 x 16 mm2
HWAT-L 80 120 205 325 490 n.a. n.a.HWAT-M 50 185 310 490 740 n.a. n.a.HWAT-R 50 135 220 355 535 n.a. n.a.
FS-A-2X/FS-C10-2X 110 50 85 135 205 n.a. n.a.10 FS-B-2X 65 40 70 110 165 n.a. n.a.
FS-C-2X 55 45 75 115 175 n.a. n.a.GM-2X/GM-2XT 40 45 70 115 175 n.a. n.a.
EM2-XR 17 50 85 135 205 n.a. n.a.EM-MI-PACK-26M 26 n.p. 110 180 270 n.a. n.a.EM-MI-PACK-36M 36 n.p. 80 130 195 n.a. n.a.
HWAT-L 110 95 155 250 375 n.a. n.a.HWAT-M 65 120 200 325 485 n.a. n.a.HWAT-R 65 115 190 300 455 n.a. n.a.
FS-A-2X/FS-C10-2X 130 45 70 115 175 n.a. n.a.13 FS-B-2X 85 30 55 85 125 n.a. n.a.
FS-C-2X 70 35 60 95 140 n.a. n.a.GM-2X/GM-2XT 50 35 60 95 140 n.a. n.a.
EM2-XR 22 40 65 105 160 n.a. n.a.EM-MI-PACK-48M 48 n.p. 60 95 145 n.a. n.a.
HWAT-L 140 70 115 185 280 n.a. n.a.HWAT-M 80 105 175 280 420 n.a. n.a.HWAT-R 80 90 150 245 370 n.a. n.a.
FS-A-2X/FS-C10-2X 150 40 65 100 150 n.a. n.a.16 FS-B-2X 105 25 45 70 105 n.a. n.a.
FS-C-2X 90 30 45 70 110 n.a. n.a.GM-2X/GM-2XT 60 30 50 75 115 n.a. n.a.
EM2-XR 28 30 50 80 125 n.a. n.a.EM-MI-PACK-60M 60 n.p. 45 75 115 195 n.a.
HWAT-L 180 n.p. 90 145 220 365 n.a.HWAT-M 100 n.p. 145 230 345 570 n.a.HWAT-R 100 n.p. 120 195 295 490 n.a.
20 FS-C10-2X 180 n.p. 45 70 110 n.a. n.a.GM-2X/GM-2XT 80 n.p. 35 60 85 145 n.a.
EM2-XR 35 n.p. 40 65 100 165 n.a.EM-MI-PACK-70M 70 n.p. 40 65 100 165 n.a.
25EM2-XR 45 n.p. n.p. 50 75 130 n.a.
EM-MI-PACK-88M 88 n.p. n.p. 50 80 130 n.a.32 EM2-XR 55 n.p. n.p. n.p. 65 105 n.a.
n.a. = Not applicablen.p. = Not permitted
TECHNICAL DATA dimensions of power cables Maximum power (Cold Lead) cable lengths based on circuit breaker sizing and cable conductor cross sectional area.
69Technical handbook
Pentair offers a set of tools and services that aim to simplify the professional´s life. Not only do we offer the best quality products, we also support them with unrivalled services.
An EffiCiEnT CuSTOMER SERViCE CEnTRE:• Multi-lingual customer service representatives to answer all your questions
• Fastorderhandling&shipmentEurope-wide
• Freedocumentationservice
LARgE TECHniCAL SuPPORT TEAM: • “Ondemand”technicaladviceandproductselection
• Designsupportandcostestimates
• Specificationsupport
• Trainingsupport
• Installation,testandcommissioningsupport
• Completeafter-salesservice
• OnlinedesigndESign WizARd TRACECALC nET• OnlinetechnicalSupportWWW.PEnTAiRTHERMAL.COM
[email protected] 0800 96 90 13FAX 0800 96 86 24
Our products satisfy the requirements of the relevant European Directives.
Mitglied in der European RadiantFloor Heating Association e.V.
Member of the European Ra di ant Floor Heat ing Association e.v.
CHARTEREd inSTiTuTE Of buiLding SERViCES EnginEERS
Pentair is also a proud industry supporter offering approved CPD courses via the Chartered Institute of Building Services Engineers. Courses include technical and application information for electrical underfloor heating and hot water temperature maintenance systems.For further information, please consult the CIBSE Course Directory or contact Pentair.
WWW. PEnTAiRTHERMAL.COM Our website provides you with all information from product selection to downloadable installation manuals.
70 THERMAL buiLding SOLuTiOnS
71Technical handbook
United KingdomTel: 0800 969 013Fax: 0800 968 [email protected]
irelandTel: 1800 654 241Fax: 1800 654 [email protected]
SoUth eaSt aSiaTel: +65 67685800Fax: +65 67322263
aUStraliaTel: +61 2 97920250Fax:+61 2 [email protected]
india - noidaTel: +91 120 464 9500Fax: +91 120 464 [email protected]
india - mUmBaiTel: +91 22 6775 8800/01Fax: +91 22 2556 [email protected]
UaeTel: +971 4 378 1700Fax: +971 4 378 [email protected]
EN-Raychem-TH-CDE0517 Rev12 THERMAL buiLding SOLuTiOnS
WWW.Pentairthermal.Com
PCN 1244-001241
All Pentair trademarks and logos are owned by Pentair. All other brand or product names are trademarks or registered marks of their respective owners. Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice. Pentair is an equal opportunity employer.