technical paper #2 - iiarweb.iiar.org/membersonly/pdf/tc/t350.pdf · asme b31.3, process piping...
TRANSCRIPT
© IIAR 2005 33
Abstract
The paper examines issues faced by engineers, contractors and owners when designing, installing andoperating refrigeration piping. It reviews piping mechanical design by discussing applicable pipingcodes and the suitability of piping, castings, bolting and gasket materials as well as welding methodsfor low-, normal- and high-temperature service. It then analyzes pipe-sizing methods for a variety ofapplications, emphasizing the effects of undersizing or oversizing liquid piping, vapor lines and controlvalves. This evaluation is followed by a discussion on piping layout issues, in particular, layout ofcompressor suction mains, wet suction returns, elevated equipment and condensers. The paperconcludes with a presentation of special cases such as thermal expansion in liquid CO2 andsubcooled refrigerant lines, vapor condensation in hot gas and instrument tubing, liquid hammer,liquid carryover, internal and external corrosion, and a comparison of pumped and gravity-fedoverfeed systems.
2005 IIAR Ammonia Refrigeration Conference & Exhibition, Acapulco, Mexico
Technical Paper #2
Refrigeration Piping: A Simplified Guide to a Modern Approach
Paul DanilewiczPaul Orlando
Toromont Process SystemsHouston, Texas
ACKNOWLEDGEMENT
The success of the technical program of the 27th Annual Meeting of theInternational Institute of Ammonia Refrigeration is due to the quality of the technicalpapers in this volume. IIAR expresses its deep appreciation to the authors,reviewers, and editors for their contributions to the ammonia refrigeration industry.
Board of Directors, International Institute of Ammonia Refrigeration
ABOUT THIS VOLUME
IIAR Technical Papers are subjected to rigorous technical peer review.
The views expressed in the papers in this volume are those of the authors, not theInternational Institute of Ammonia Refrigeration. They are not official positions ofthe Institute and are not officially endorsed.
EDITORSM. Kent Anderson, President
Chris Combs, Project CoordinatorGene Troy, P.E., Technical Director
International Institute of Ammonia Refrigeration1110 North Glebe Road
Suite 250Arlington, VA 22201
+ 1-703-312-4200 (voice)+ 1-703-312-0065 (fax)
www.iiar.org
2005 Ammonia Refrigeration Conference & ExhibitionFairmont Acapulco Princess
Acapulco, Mexico
Technical Paper #2 © IIAR 2005 35
Introduction
Numerous articles, handbooks and manuals in our industry discuss good piping
practices for ammonia refrigeration systems. There is also a good understanding of
the major issues related to the subject among the designers, contractors, and end-
users of the refrigeration plants. The goal of this paper is not to repeat what has
already been written on the topic of ammonia piping. Instead, the paper shall
discuss the design issues that, in the authors’ opinion, are much ignored by the
industry but contribute significantly to the problems encountered in refrigeration
plants. The paper also presents modern piping design methods.
Mechanical Design Issues
This section covers the following mechanical design topics:
• Piping design for low temperatures
• Cast, malleable and nodular iron in refrigeration systems
• ASME piping classes
• ASHRAE 15 safety standard for refrigeration systems
Piping Design for Low Temperatures
Carbon steel is the material of choice for pipe, valves and other components used in
ammonia refrigeration systems and screw compressor lubricant service. At low
temperatures, however, carbon steel becomes brittle and loses flexibility and
toughness. For safety reasons, piping codes establish guidelines to ensure that the
materials used in piping systems provide adequate strength and flexibility at all
service temperatures.
The code most commonly used in industrial refrigeration piping is ASME B31.5,
Refrigeration Piping Code, although some end users, especially outside the food
Refrigeration Piping: A Simplified Guide to a Modern Approach — Paul Danilewicz and Paul Orlando
36 © IIAR 2005 Technical Paper #2
processing industry, require designers and installers to conform to the more stringent
ASME B31.3, Process Piping Code. (ASME B31.3, 2004; ASME, 2001)
Prior to the 2001 edition, the ASME B31.5 code stated that impact tests were not
required for ferrous material used in fabricating a piping system operating between
-20°F and -150°F [-29°C and -101°C], provided that the maximum circumferential or
longitudinal tensile stress, resulting pressure, thermal stresses, and bending stress
between the supports did not exceed 40% of the allowable stress of the material at
100°F [38°C].
The latest edition of ASME B31.5 brought the requirements more in line with the
methodology used in B31.3 and Section VIII of the ASME Boiler and Pressure Vessel
(B&PV) Code. (ASME B&PV, 2004) The new rules establish the minimum
temperature above which the material is exempt from impact test requirements
based on the grade of carbon steel and the thickness of the material. For operating
temperatures between -20°F and -50°F [-29°C and -46°C], if the system is to operate
below the nominal impact-test exemption temperature, the code allows the designer
to determine the additional reduction in minimum metal temperature for which
impact testing is not required. This reduction in minimum temperature is based on
the ratio of the design tensile stresses to the normal (room temperature) allowable
stress for a given material. (Figure 1) For metal temperatures below -50°F [-46°C],
the old 40% rule applies (i.e., impact testing is not required if this ratio is less than
40%.) Note that if the design temperature is below -55°F [-48°C] and the ratio is
less than 30%, ASME B31.3 requires impact testing.
Typically, for higher operating temperatures, designers specify SA-106 grade B
seamless or SA-53 grade B ERW piping. For the pipe wall thicknesses typically
encountered in refrigeration piping, these materials have a maximum allowable
stress rated at temperatures above -20°F [-29°C]. For lower operating temperatures,
the specifications quite often call for SA-333 grade 6 material, which is impact-tested
by the producing mill at a minimum temperature of -55°F [-48°C].
2005 IIAR Ammonia Refrigeration Conference & Exhibition, Acapulco, Mexico
Technical Paper #2 © IIAR 2005 37
Suppliers charge a substantial premium for impact-tested carbon steel pipe and
fittings. A recent informal survey showed that SA-333 grade 6 piping had a 10% to
20% higher cost than SA-106 grade B seamless piping, and a 40% to 50% higher
cost than SA-53 grade B ERW. The premium is even higher for large forgings used to
manufacture flanges, unions and other butt-welded fittings. Figure 2 details a price
comparison among the different types of material.
For packaged refrigeration systems, the cost of low-temperature carbon piping as a
percentage of total job costs is not as large as for field-installed systems. The piping
runs are typically short on packaged units and use of low-temperature specialty
piping material is usually limited to compressor suction lines. The cost becomes
significant for packaged units if the customer is concerned that the piping is suitable
for the normal boiling temperature (saturation temperature) of the refrigerant at
atmospheric pressure and specifies that all piping shall be rated for this temperature.
In the case of ammonia, the equivalent saturation temperature at sea-level
atmospheric pressure is -28.0°F [-33.3°C]. For R-22, the equivalent saturation
temperature is -41.3°F [-40.7°C] and for R-507, -52.1°F [-46.7°C]. In the packaged
refrigeration systems supplied to refineries, hydrocarbons such as propane and
propylene are quite often the refrigerants of choice; their saturation temperatures
are -38.4°F and -48.7°F [-39.1°C and -44.8°C] respectively. Some customers
require that the piping system be rated for these low temperatures at full design
working pressures.
The situation is dramatically different for ammonia refrigeration systems in typical
food processing installations, which have hundreds of feet of large diameter pipe,
valves and fittings operating at metal temperatures below the minimum -20°F
[-29°C]. At times, large overfeed systems have substantial wet suction lines or
liquid lines that operate at temperatures of -40°F [-40°C] or lower.
Valve manufacturers use either cast/ductile iron or impact-tested cast steel materials
to ensure that their products can operate at suitably low temperatures. This same
Refrigeration Piping: A Simplified Guide to a Modern Approach — Paul Danilewicz and Paul Orlando
38 © IIAR 2005 Technical Paper #2
practice applies to manufacturers of pressure regulators, level switches, etc.
However, to meet piping code requirements, system suppliers must either install
expensive impact-tested piping or prove that the piping system will not be
overstressed at low temperatures considering the reduced maximum allowable
stresses of the piping material.
In refrigeration systems, operating pressures at low temperatures are typically very
low because the vapor pressure of the refrigerant falls as the temperature drops. For
example, ammonia vapor pressure at 100°F is 211.9 psia [38°C/14.41 bar]. At -35°F
[-37°C], it is only 12.1 psia [0.823 bar]. It is apparent that the stresses imposed on
the piping due to direct refrigerant pressure will be generally low. The majority of
the stress that the designer will have to consider is a thermal stress due to
expansion or contraction of the piping when its operating temperature fluctuates
between ambient and operating temperatures.
Currently, system designers may choose from several software packages to verify
the stresses imposed on piping. By using this software, the system designer can
prove the suitability of non-impact-tested, less-expensive piping materials for
operation at low temperatures. In most cases, a software analysis for large systems
proves to be beneficial because non-impact-tested piping costs far less than
impact-tested materials.
Many companies use three-dimensional modeling as their standard method for
laying out the piping in the plant, which makes the analysis quite simple. The
models are used to estimate the labor required for the installation, to prepare bills of
materials, and to create isometric drawings for pipe spools. Once the model has
been created, the pipe runs can be evaluated using the stress analysis software. If
the initial analysis shows that the allowable stresses would be exceeded, the
designer can reduce them by modifying the proposed layout and location of the
anchor points. Installations designed in such a manner are safe, less expensive and
meet the piping code requirements. This type of design process does not just apply
2005 IIAR Ammonia Refrigeration Conference & Exhibition, Acapulco, Mexico
Technical Paper #2 © IIAR 2005 39
to low-temperature applications; designers may check stresses in other types of
piping systems as well, including hot gas lines or compressor discharge lines.
Figures 3 and 4 illustrate a sample analysis of a -50°F [-46°C] wet suction line and
120°F [49°C] hot gas line. In the example, the suction main and hot gas runs were
first drawn using computer-aided design (CAD) software based on a typical roof
routing of the piping mains. Once the mains had been designed, the pipe supports
were added to the drawing, and the system was then evaluated using piping-stress-
analysis software. The analysis showed that both SA106 grade B and SA 333 grade 6
piping materials were suitable for the installation, based on the pipe size and
thickness, ambient temperature range, operating pressures and temperatures, and
fluid density.
Process requirements define operating temperatures. While the designer cannot
change this constraint, he or she can lay out the plant pipe in such a manner to
limit the imposed thermal stresses. When laying out system pipe runs, no single rule
assures that the proposed layout will not exceed the maximum allowable stresses for
the material. Instead, a common sense approach that considers the behavior of pipe
subjected to temperature fluctuations should guide the design process. The system
design must allow the pipe to move without breaking the welds and prevent it from
becoming overly stressed while it experiences temperature reductions or increases.
One good method to mitigate such stresses in a pipe run is to add a few elbows to
create a loop that can flex when the pipe run expands or contracts. Also, vessels and
attached pipe can be installed such that thermal expansion and contraction will not
cause forces acting on the nozzles to exceed the maximum allowable limits.
Like pipe, all other components must be suitable for operation at the design
operating temperature. The ASME B31.5 piping code does not require the use of
impact-tested carbon steel bolting for temperatures above -50°F [-46°C] as long as
the bolting used is high strength A193 grade B7. The designer also needs to confirm
that the elastomers used for gaskets and seals are not only compatible with the
Refrigeration Piping: A Simplified Guide to a Modern Approach — Paul Danilewicz and Paul Orlando
40 © IIAR 2005 Technical Paper #2
refrigerant, but that they will maintain sealing capabilities at low temperatures.
Neoprene, which is the most common elastomer used in ammonia systems, is
usually rated for temperatures above -40°F [-40°C]. For temperatures below this
threshold, the designer may have to consider either PTFE gaskets or spiral wound
stainless steel gaskets that are suitable for very low operating temperatures.
Also, the welding procedures used in fabricating piping systems should be rated for
the minimum metal design temperature. A suitable Welding Procedure Specification
(WPS) and Procedure Qualification Record (PQR) must be prepared in accordance
with Section IX of the B&PV Code, and a set of pipe coupons must be impact-tested
at the minimum design metal temperature to be used for the procedure. The main
reason for the impact-testing requirement is to establish the heat input required to
achieve the desired weld toughness at the design temperature. Although the B&PV
Code does not specifically require that the welding consumables be impact-tested
for the minimum metal temperature, it may be beneficial to utilize impact-tested or
low-temperature-rated consumables to assure that the coupon passes the impact test.
Also, the welders must be currently qualified to perform the approved WPS.
It is worth pointing out that common stainless steel materials such as type 304, 304L,
316 or 316L do not require impact testing, nor does aluminum. Stainless steel and
aluminum are commonly used in the construction of evaporator coils in air units.
Cast, Malleable and Nodular Iron in Refrigeration Systems
Valve manufacturers commonly use cast, malleable and nodular types of iron. Most
of the relief valves and regulators used in ammonia refrigeration are made of gray
cast iron or ductile iron materials. The ASME B31.5 code allows cast and malleable
types of iron as long as they are not used for hydrocarbon or flammable fluid service
at temperatures above 300°F [149°C] or operating pressures above 300 psig
[20.4 barg]. Restrictions against nodular iron are somewhat different; the code
prohibits the use of nodular iron above 1000 psig [20.4 barg], which obviously
2005 IIAR Ammonia Refrigeration Conference & Exhibition, Acapulco, Mexico
Technical Paper #2 © IIAR 2005 41
would not be a common case with ammonia refrigeration. Notably, the code allows
the usage of cast, malleable and nodular iron for temperatures above -150°F
[-101°C] without impact testing.
ANSI/ASME Piping Classes
The ASME B16 Committee developed several standards to ensure consistency in the
design and application of valves, flanges, fittings and gaskets. The committee
defined several pressure-temperature classes for a variety of cast and forged
materials. The two main steel flange classes defined by the ASME B16.5 standard
that are commonly used in ammonia refrigeration piping are Class 150 and 300.
(ASME, 2003) The similar classes for cast and nodular irons are defined as Class 125
and 250. The class defines the maximum allowable working pressure for which a
given component can be used depending on the system operating temperature.
Figure 5 details the basic pressure ratings for both classes and common carbon and
stainless steel materials. Class 150 and 300 represent nominal 150-psig [10.2-barg]
and 300-psig [20.4-barg] designs, respectively. For carbon and stainless steel fittings,
the maximum allowable working pressure decreases as temperature increases. For
example, for Class 150 carbon steel flanges, the maximum allowable working
pressure at 100°F [38°C] is 284 psig [19.3 barg] and falls to 200 psig [13.6 barg] at
392°F [200°C]. The examination of the pressure-temperature charts for each class
shows that if the refrigeration system is designed entirely for 300-psig [20.4 barg]
maximum allowable working pressure, Class 150 valves, flanges or other
components should not be used. As indicated above, for Class 150, the maximum
pressure rating at any temperature is less than 300 psig [20.4 barg]. This restriction
is also applicable to compressor suction flanges or flanges supplied with pressure
vessels, heat exchangers or pumps. Some compressor and pump manufactures
utilize Class 150 flanges at compressor or pump suction connections; thus, they
should not be used if the low side of the system is protected with a relief valve set
for 300 psig [20.4 barg].
Refrigeration Piping: A Simplified Guide to a Modern Approach — Paul Danilewicz and Paul Orlando
42 © IIAR 2005 Technical Paper #2
ANSI/ASHRAE 15-2004 and Mechanical Design
ASHRAE 15-2004, a model refrigeration safety code, provides recommendations for
the design pressures for refrigeration systems. The code states that all equipment
should be designed for a 29” Hg vacuum [23 Torr]. For the low side of ammonia
systems, the code requires 138 psig [9.39 barg] minimum design pressure, which is
equivalent to 80°F [27°C] saturation temperature. For the high side, with an
evaporative or water-cooled condenser, the code recommends a 210-psig [14.3-barg]
design, which corresponds to 104°F [40°C] saturation temperature. If air-cooled
condensers are used, then the minimum high side design pressure should be
280 psig [19.0 barg], equivalent to a 122°F [50°C] saturation temperature.
If a designer expects ambient or inside temperatures hotter than 80°F [27°C],
he/she should then design the system for the pressure equivalent to the maximum
expected temperature, with at least a 15% margin of safety to account for tolerance
in the relief valve set pressure. For example, for a 95°F [35°C] ambient, which is a
common temperature experienced in the summer in the southern U.S., the
equivalent saturation gauge pressure is 181 psig [12.3 barg]. At 100°F [38°C], the
ammonia vapor pressure is 197 psig [13.4 barg]. For these temperatures, even a
200-psig [13.6-barg] low side design appears to be insufficient.
Designing the low side for 250 psig [17.0 barg] can prevent the relief valves from
opening and releasing ammonia during elevated ambient temperatures. For systems
designed for 250 psig [17.0 barg] and operating temperatures below 212°F [100°C],
Class 150 flanges and fittings can still be used on the compressors, pumps, vessels
and heat exchangers.
At times, designers specify the high side of the system for 300 psig [20.4 barg].
Many ammonia systems use evaporative condensers operating at 181 psig
[12.3 barg], with occasional excursions to 210 from 240 psig [14.3 to 16.3 barg]. The
differential between these pressures and the 300-psig [20.4-barg] relief valve set
2005 IIAR Ammonia Refrigeration Conference & Exhibition, Acapulco, Mexico
Technical Paper #2 © IIAR 2005 43
point permits the valve to remain securely closed, preventing weeping that can occur
when the differential is less than 25 psi [1.7 barg], as would be the case had the
design pressure been chosen at 250 psig [17.0 barg].
Sizing of Piping Runs
New Tools for Selecting Refrigerant Pipe Sizes
Design engineers may choose among a wide variety of selection charts for sizing
refrigerant piping. These charts are generally based on the Darcy equation, which is
suitable for single-phase flow of both liquids and gases as long as the average flow
velocity does not exceed approximately 0.3 Mach. For vapor flow, the equation can
be used only when the pressure losses in the pipe run are relatively low, which is
the case for a majority of pipe runs. This limitation is due to the fact that for vapors,
as the pressure decreases, the specific volume increases. Thus, for the same mass
flow rate the average flow velocity increases. However, because the Darcy equation
assumes a constant average flow velocity for calculation of the pressure drop, it
becomes less accurate as vapor pressure drops increase in size.
This Darcy-based methodology does not address two-phase flow situations, common
for all overfeed systems. The ammonia refrigeration industry has circumvented this
problem by the practice of selecting wet suction lines one size larger than the dry
suction line required for the given duty. Also, some refrigeration system designers
and pipe sizing software developers have adopted Beattie’s simplistic method of
calculating pressure drop in two-phase flow. (Beattie, 1982)
For some time, the process industry has used simulation software to aid engineers in
designing process equipment, such as absorbers, strippers, mixers, etc. Industries
that compress gases also use this software, especially for compression of wet mixed
hydrocarbon gases. Further, the software aids in the design of carbon dioxide
Refrigeration Piping: A Simplified Guide to a Modern Approach — Paul Danilewicz and Paul Orlando
44 © IIAR 2005 Technical Paper #2
purification and liquefaction plants. The software output is essential engineering
data that is then used for selecting all heat exchangers, pressure vessels and piping
for single- and two-phase flows in the plant. A typical Process Flow Diagram, a
software output report, and an example of pipe sizing are included in Figures 6
through 8.
There are many advantages to using simulation software for plant design. The
software allows for a detailed analysis of the plant performance, including predicting
system performance under different operating situations. It eliminates guessing in
the design process by rigorously calculating all relevant flow data. It assures that all
pipe sizes are correct and designed for the actual plant requirements. The software
output can also be used to confirm that compressors, pumps and other equipment
selected have enough capacity. The software allows for optimizing plant
performance by allowing the designer to evaluate different what-if scenarios.
Obviously, the software can also be a handy tool for analyzing existing installations.
The Effects of Undersizing or Oversizing Piping Systems
Liquid Lines: It is essentially impossible to oversize liquid lines from a flow and
pressure drop point of view. The designer has to be aware that the larger-than-
necessary liquid lines will contribute to overall plant liquid inventory, which in turn
will require a larger receiver volume, adding cost to the installation. Undersized
liquid piping causes liquid pressure to drop, which in turn will cause flash gas to
form during flow. Flash gas has an adverse impact on the performance of expansion
valves. This problem is especially acute for liquid lines containing saturated liquid.
For pumped liquid overfeed or pressure-fed liquid systems, excessive pressure drop
in liquid piping can result in insufficient liquid pressure at the expansion valve to
overcome the pressure drop at the required flow through the evaporator.
When analyzing liquid lines, the designer has to be aware of the consequences of
installing larger-than-necessary liquid control valves. In the case of thermostatic
2005 IIAR Ammonia Refrigeration Conference & Exhibition, Acapulco, Mexico
Technical Paper #2 © IIAR 2005 45
expansion valves, if the valve is too big, it can become unstable, which in turn can
result in poor control and eventual flooding of the evaporator. The valve seats of
automated or hand-operated expansion valves for flooded evaporators will wear out
faster if forced to operate barely open for long periods. On the other hand, if the
control or expansion valve is too small, the evaporator will starve. Also, some
solenoid valves require a minimum pressure differential to operate properly. If liquid
line solenoid valves are oversized, there may not be enough flow to create a
pressure drop adequate to hold the valve open.
Designers should also take advantage of the fact that the plant can operate more
efficiently at lower-than-design ambient dry- or wet-bulb temperatures, which occur
the majority of the time. At low ambient conditions, the differential pressure
between the high and low side of the system can be substantially less than the
design differential pressure, which reduces the required compressor horsepower.
Therefore, both liquid and hot gas lines should be sized for flow at the reduced
differential pressure to take advantage of these conditions. Otherwise, the plant will
pay an expensive penalty due to the excessive power consumption.
Suction Lines: Special care should be taken when sizing suction lines. The lower the
design suction temperature, the greater the effect of undersizing. Undersized low
temperature suction piping and components will result in increased compressor
horsepower requirements for the same refrigeration duty. As the pressure decreases,
the gas specific volume and the horsepower-per-ton increase (assuming constant
condensing pressure). The lower suction pressure requires a greater compression
ratio to compress the refrigerant vapor to condensing pressure.
As the suction pressure decreases, the required compressor volumetric flow
increases. For the same duty, this may result in having to provide larger compressor
capacity, thus increasing equipment costs. A good approach to avoid excessive
capital costs is to establish the optimum economical velocity based on a comparison
of initial and operating costs. (Richards, 1984) Based on the historical relationship
Refrigeration Piping: A Simplified Guide to a Modern Approach — Paul Danilewicz and Paul Orlando
46 © IIAR 2005 Technical Paper #2
between these costs, several design recommendations for the compressor suction
lines have been developed. One contractor proposed the following recommendations
in a form of overall pressure drop per 100 feet of equivalent length of pipe:
-40ºF — 0.15 to 0.20 psi
-20ºF — 0.25 psi
+15ºF — 0.5 psi
+35ºF — 1 psi
Another economics-based method is described in IIAR’s Ammonia Refrigeration
Piping Handbook. (IIAR, 2004) The Handbook includes several tables for both
suction and discharge lines.
Again, the overall pressure loss must be considered when selecting isolation and
control valves. For isolation valves, angle or butterfly designs are recommended
because they require less pressure drop than globe valves. Control valves should be
selected and sized to allow proper operation of the valves at the lowest pressure
drop that is economically feasible. However, if the system design requires a greater
pressure drop for a certain piece of equipment (e.g., multiple evaporators operating
at different evaporating temperatures connected to a common suction header), then
the designer should disregard this guideline.
Check valves should also be specified taking into account the overall pressure loss.
When selecting check valves, both the operating and cracking pressure drop required
to lift or open the valve should be considered. Cracking pressure is the pressure drop
required for the valve to open and overcome valve spring pressure and/or disk or
piston weight. Oversized piston-type check valves will cause the piston to operate
too close to the seat, which, in the event of a minor upset, will cause the piston to
bounce off the seat. Also, when excessive forces are required to open check valves,
the resulting pressure drop fluctuation across the valve may lead to bouncing or
chattering and eventually damage the valve. The use of split-wafer check valves
allows minimum cracking force and low operating pressure drop if the valve is
2005 IIAR Ammonia Refrigeration Conference & Exhibition, Acapulco, Mexico
Technical Paper #2 © IIAR 2005 47
properly sized and installed. These valves are available with low-torque springs that
have very low valve cracking pressures.
In summary, when rating and selecting compressors, the designer must consider all
combined pressure drops between the evaporator and the compressor flange.
Hot Gas Lines: During hot gas defrost, the required hot gas duty is about twice the
refrigeration capacity of the evaporator that operates at a 10ºF [5.6K] temperature
difference. Hot gas piping should be sized to accommodate the volume of hot gas
required to condense this amount of vapor. Hot gas headers should be sized to
accommodate all of the evaporators scheduled to defrost at the same time. The
volume of hot gas flow is determined by the difference between the compressor
discharge pressure and the highest defrost pressure regulator setting on any of the
evaporators in the system. Piping should be designed to permit adequate flow even
when the condensing pressure is relatively low, such as during winter months. At
lower-than-design ambient conditions, undersized hot gas lines waste energy
unnecessarily and prolong defrost cycles. Extended defrost cycles give the
evaporators less time to recover between cycles, potentially compromising room
temperatures or causing product quality issues.
Piping Layout and Special Issues
Thermal Expansion of Subcooled Liquid
Subcooling: Subcooled liquid is frequently used in ammonia refrigeration plants and
is produced by cooling liquid below its saturation temperature at the prevailing
pressure. Subcooling may increase the efficiency of the refrigeration cycle and
prevent the formation of flash gas in downstream piping. In a two-stage system, for
example, by exchanging heat between liquid supply A (which feeds low-temperature
loads) and liquid supply B (which flashes off and is directed to the high-stage
Refrigeration Piping: A Simplified Guide to a Modern Approach — Paul Danilewicz and Paul Orlando
48 © IIAR 2005 Technical Paper #2
compressor), liquid supply A would become subcooled and its refrigerating effect
would increase. While the flash gas would increase the volume normally handled by
the high-stage compressor, the subcooling effect would reduce the amount of gas
handled by the low-stage compressor. However, because the high stage compressor
operates more efficiently in terms of Btuh/BHP than the low stage, the process
yields a net gain in efficiency.
Subcooling is required in piping that suffers excessive frictional pressure losses or
that must be delivered to elevated evaporators. In the case of elevated evaporators
fed with saturated ammonia at 95°F [35°C], for every 3.92 ft [1.19 m] of elevation
increase, the liquid vapor pressure falls by 1 psi [0.068 bar], causing subsequent
flashing of liquid.
Preventing flash gas is also important for sizing liquid expansion valves. Most of the
selection charts and software assume that pure liquid exists upstream of the
expansion device. If this is not the case, the device will either not operate properly,
or will be too small for the duty, and may eventually fail.
Thermal expansion of cold liquid: Consider a case in which we have trapped
subcooled liquid ammonia in a 200’ length of 2” schedule 40 pipe. If the subcooled
liquid were allowed to warm up from 10°F to 95°F [-12°C to 35°C], for example,
during system shutdown, it would expand, but how much?
The density of subcooled liquid ammonia at 10°F [-12°C] is approximately
40.9 lb/ft3 [656 kg/m3]. Therefore, the specific volume of the liquid is
0.0244 ft3/lb [0.00152 m3/kg]. At 95°F [35°C], its density would be 36.7 lb/ft3
[589 kg/m3]; specific volume would be 0.0272 ft3/lb [0.00170 m3/kg]. Thus, each
pound of trapped liquid would increase in volume by 0.0028 cubic feet [0.18 liters].
2005 IIAR Ammonia Refrigeration Conference & Exhibition, Acapulco, Mexico
Technical Paper #2 © IIAR 2005 49
The volume of the pipe in our example, 200’ of 2” schedule 40, is calculated:
200’ x 0.0233 ft3/linear foot = 4.66 ft3 [0.132 m3].
The mass of this volume of ammonia at 10°F [86.6 kg at -12°C] is:
4.66 ft3 x 40.9 lbs/ft3 = 190 lbs.
After warming to 95°F [35°C], the ammonia will expand to a volume of:
190 x 0.0272 = 5.17 ft3 [0.147 m3]
The net increase in liquid volume, then, would be:
5.17 – 4.66 = 0.51 ft3 [0.015 m3].
However, liquid ammonia cannot be compressed. Therefore, as trapped liquid warms,
the pipe will at first expand and stretch to accommodate the larger volume and rising
pressure. As the pressure exceeds the mechanical limits of the pipe, it will fail.
Fortunately, the designer of the system can address this problem by providing the
liquid a place in which to expand, such as an upstream or downstream vessel or
heat exchanger. Isolation valves at both ends of a liquid line should also be tagged
or labeled, advising the operator not to close both valves simultaneously. In
addition, liquid relief valves can be installed and piped either to a relief header or a
low side pressure vessel. In carbon dioxide installations, it is a common practice to
protect subcooled and saturated liquid lines with “pop-up” hydrostatic relief valves.
These relatively small and inexpensive devices prevent the rising of hydrostatic
pressure in the piping system by relieving expanding liquid to the atmosphere.
A similar problem is encountered in low temperature cascade systems. These
systems utilize various refrigerants, including carbon dioxide. Because the critical
temperature of carbon dioxide is below typical ambient temperatures, it will develop
a high pressure at relatively moderate temperatures. For example, saturated carbon
dioxide’s vapor pressure at 50°F [10°C] is approximately 652 psia [44.4 bar]. In the
Refrigeration Piping: A Simplified Guide to a Modern Approach — Paul Danilewicz and Paul Orlando
50 © IIAR 2005 Technical Paper #2
case of R-23, another commonly used low temperature refrigerant, the vapor
pressure at the same temperature is 472 psia [32.1 bar]. In those installations, any
trapped saturated liquid must be vented to prevent the system pressure from rising
above its maximum allowable design pressure. Hydrostatic relief valves can be used
for this purpose.
Vapor Condensation in High Pressure Lines
One problem commonly overlooked is the effect of low ambient temperatures on
high-pressure refrigerant vapor lines, encountered when routing compressor
discharge lines or high-pressure vent lines through air-conditioned spaces or when
high-pressure pipes are installed outside the building.
At 95°F [35°C] condensing temperature, the ammonia vapor pressure is about
195.7 psia [13.31 bar]. If a system is shut down under this condition and the pipe
pressure is maintained at the pressure equivalent to the high ambient temperature,
then once the pipe wall temperature starts falling, the vapor refrigerant in the pipe
will begin to condense.
Condensing liquid may flow back down the compressor discharge lines and
accumulate on top of the compressor discharge check valve. If the check valve is not
fully closed, liquid will drain into the compressor’s oil separator. If the discharge line
is large enough and the oil separator does not have a heat source sufficiently great
to boil off all of the condensed liquid, the refrigerant will increasingly dilute the
compressor oil. At high levels of oil dilution, the oil viscosity can fall so far that the
oil will not provide sufficient bearing lubrication, causing compressor failure once
the compressor is restarted.
An easy and relatively inexpensive solution to this problem is to use inverted traps
for individual compressor discharge risers at the discharge header, or trap discharge
lines in which any condensed liquid can collect. The trap can be either drained with
2005 IIAR Ammonia Refrigeration Conference & Exhibition, Acapulco, Mexico
Technical Paper #2 © IIAR 2005 51
a liquid drainer to a high or low side vessel, or liquid can be allowed to boil off once
the system is restarted. Additionally, heat tracing and insulation may be applied to
maintain a warm pipe surface temperature to prevent liquid from condensing.
Differential pressure transmitters are not commonly used in ammonia refrigeration.
However, where they are used to measure liquid level in the high-pressure vessel, it
is important to heat-trace and insulate the vapor leg of the device. Otherwise, on a
cold day, liquid will condense in the tubing and stack up on the low side of the
transmitter. This condition may cause the transmitter to falsely indicate low liquid
levels in the vessels. Likewise, the tubing runs to the pressure transmitters and
pressure transducers on the high side of the system should not be trapped. They
should be installed to allow ammonia condensate to drain freely into the pipe.
Layout of Suction Piping and Liquid Carry-over
It is very important to prevent overfed liquid from reaching refrigerant compressors.
In a liquid-vapor separator vessel, the liquid-vapor flow velocity is reduced below a
certain critical velocity, and the vapor can no longer fully entrain liquid droplets.
The liquid droplets fall out of the vapor stream and settle into the liquid pool. The
separated vapor is saturated (but not wet), and is collected to flow into the
compressor. The key distinction between saturated and wet vapor is that saturated
vapor does not carry any free liquid droplets, while wet vapor includes liquid. All
liquid overfeed systems have wet return lines. The compressor suction lines should
be dry.
The maximum allowable flow velocity is usually determined from a well-known
industry equation:
Vmax = k
Refrigeration Piping: A Simplified Guide to a Modern Approach — Paul Danilewicz and Paul Orlando
ρl – ρv
ρv
52 © IIAR 2005 Technical Paper #2
where:
Vmax = maximum vapor flow velocity (ft/sec)
k = flow coefficient
ρl = liquid density (lb/ft3)
ρv = vapor density (lb/ft3)
Separation vessel manufacturers provide the maximum vessel capacity, expressed in
most cases in terms of tons of refrigeration. The capacity depends on the vessel size,
operating temperature, maximum allowable vessel flow velocity, vapor density, and
mass flow rate.
For example, consider a load of 80 tons of refrigeration (TR) [280 kW] at -40°F
[-40°C] with a 90°F [32°C] liquid supply. We wish to calculate the mass flow. First,
we determine the refrigerating effect of each pound of ammonia by subtracting the
enthalpy of the liquid (143 Btu/lb) from the vapor enthalpy (597 Btu/lb). The result,
454 BTU/lb [293 W-hr/kg], is the refrigerating effect.
We convert the TR units into Btu/hr and multiply by the refrigerating effect to
obtain the mass flow. The estimated mass flow is:
80TR x x =2,115 lb/hr [961 kg/hr]
Ammonia vapor density at -40°F [-40°C] is 0.04 lb/ft3 [0.64 kg/m3]. We divide the
mass flow by the density to obtain the volumetric flow rate:
x x = 881 ft3/min [25.0 m3/min]
Therefore, for a given vessel internal diameter, the flow velocity inside the vessel
can be easily established by dividing the volumetric flow rate by the vessel cross-
sectional area and comparing it with the maximum allowable velocity.
2005 IIAR Ammonia Refrigeration Conference & Exhibition, Acapulco, Mexico
12,000 Btu
Ton – hr
2,115 lb
hr
1 ft3
0.04 lb
1 hr
60 min
1 lb
454 Btu
Technical Paper #2 © IIAR 2005 53
The plant designer can depend on experienced refrigeration vessel manufacturers to
provide a vessel with a suitable capacity for the design conditions or follow the
maximum separating velocity guidelines published by ASHRAE.
Several additional factors must be considered to assure that the objective of liquid
separation is achieved. First, the designer must consider off-design conditions (e.g.,
system pull-down, heavy evaporator defrost duty) during which the actual flow may
be well above the steady state flow conditions. Second, all the wet and dry suction
vapor piping should be sloped back to the separation vessel to make sure that any
liquid condensed or entrained in the stream is returned into the separation vessel.
Third, all individual compressor suction lines should be piped to the top of the main
header in lieu of the bottom or side to prevent liquid refrigerant from draining back
down the suction riser during the off-cycle.
Trapped lines, obviously, does not slope back to the vessel, so individual suction lines
and mains should not be trapped. Traps will accumulate liquid until it is pushed back
to the separator, which in turn can overload the separator and create overall system
instability. If it is not possible to drain the liquid back to the vessel, then a means to
return liquid must be provided (e.g., collection pots, a double riser return).
Another issue that needs to be considered while designing liquid-vapor separation
systems is how to return the collected liquid back into the system. If the separator
operates at an intermediate pressure, then liquid can be drained back to the low side
of the system utilizing the differential pressure between the intermediate and low
sides. If the separator also acts as an intercooler, collected liquid can vaporize during
desuperheating of the boosters discharge vapor. The low side separators, however,
require a source of heat to boil off the refrigerant. In ammonia systems, this is
typically achieved with a boil-off coil installed in the bottom of the vessel through
which warm liquid refrigerant is circulated. Another suitable, but much less efficient
way, is to use an electric heater or vessel heat tracing. It is also possible to collect
liquid in a liquid trap and return it by pushing it with discharge gas, or a pump, into
an intermediate pressure vessel.
Refrigeration Piping: A Simplified Guide to a Modern Approach — Paul Danilewicz and Paul Orlando
54 © IIAR 2005 Technical Paper #2
Risers for flooded shell-and-tube evaporators operate below their flooding velocities
much of the time and must be large enough to allow separated liquid to drain back
while allowing vapor to flow out of the exchanger.
Pumped and Gravity-fed Evaporators
Pumped systems are common for liquid overfeed applications. Gravity-fed (also
called thermosyphon) systems are also frequently used for evaporators and for
cooling compressor oil.
Piping of pumped systems is quite simple. The refrigerant pump develops sufficient
head, normally 30-40 psi, to deliver liquid to even the most remote evaporators in
the plant. The piping from the pump to the evaporators can be routed in any
manner and the system will operate properly as long as the pump flow is large
enough for the duty and pump head is greater than the pressure drop between the
pump and the evaporator.
In the case of gravity fed evaporators, the driving force to supply liquid to the
evaporator is the elevation difference between the liquid level above the evaporator
and the evaporator itself, plus the difference between the density of liquid in the
supply line and the liquid-vapor mix in the return piping. This force must overcome
liquid line pressure losses, pressure drop across the evaporator and the static head of
the liquid-vapor mix in the return line.
It should be noted that for gravity systems, the amount of liquid supplied to the
evaporator would depend on the evaporator heat load. As the heat load increases,
the amount of liquid vaporized increases, causing the density of vapor liquid-vapor
mix leaving the evaporator to decrease. Thus, as the heat load increases, the amount
of liquid flowing into the evaporator also increases, which increases the pressure
losses (which are proportional to the square of the flow velocity).
2005 IIAR Ammonia Refrigeration Conference & Exhibition, Acapulco, Mexico
Technical Paper #2 © IIAR 2005 55
If the system is designed for a 3 to 1 overfeed ratio at the given heat load, then the
liquid supply line will carry 3 times as much liquid as necessary for vaporization.
Thus, the return line will carry two times more liquid than vapor in terms of mass
flow. If the piping is undersized or pressure losses through the evaporator are too
high, the system will self-compensate by moving less than design overfeed ratio
through the evaporator because the flow velocity will decrease and the density
difference between supply and return will increase.
In the case of gravity-fed systems, it is important that the evaporator’s surge drum is
sized properly and capable of storing fluctuating and transient liquid levels without
tripping the high-liquid-level switch installed on the drum. Other important issues
requiring attention in gravity-fed systems are oil management and prevention of oil
and water accumulation in the evaporator coil. The most efficient way to prevent oil
accumulation in the evaporator is to avoid drawing liquid from the bottom of the
surge drum, which permits oil to accumulate on the bottom, and to provide for
draining oil from the bottom of the surge drum and the coil.
Both pumped and gravity systems can be utilized for a variety of evaporators and
refrigerants. In the process refrigeration industry, thermosyphon arrangements are
popular for heat exchangers that cool viscous liquids, such as ethylene glycol. In
those cases, the viscous brine flows through the shell side of the evaporator while
liquid refrigerant is supplied to the tube side of the exchanger. For the same reason,
oil flows on the shell side of a typical shell-and-tube thermosyphon oil cooler.
Not only ammonia, but also a variety of other refrigerants are used in pumped or
gravity systems in process refrigeration. The installations utilizing the other
refrigerants are designed in a similar fashion. However, for most of these, the
overfeed ratio is usually lower, because the amount of mass required for
vaporization is much greater. As a result, the velocity through the exchangers is high
enough for a reasonable heat transfer coefficient even at low overfeed ratios.
Refrigeration Piping: A Simplified Guide to a Modern Approach — Paul Danilewicz and Paul Orlando
56 © IIAR 2005 Technical Paper #2
Avoiding Liquid Hammer
Special precautions must be taken in the design and layout of refrigeration piping to
avoid the conditions that allow for the sudden deceleration of liquid flow, which can
result in failure of components and/or piping. This phenomenon is commonly
known as liquid hammer. It can occur when high-pressure vapor is suddenly
introduced in a low-pressure line partially filled with liquid. The liquid becomes
entrained, forming a slug that grows and accelerates until it seals the pipe off
completely and is propelled with the full velocity of gas flowing in the pipe. Liquid
hammer can occur during defrost either when pressure is released too quickly from
an evaporator at the end of the cycle, or, when condensate that forms in a hot gas
line is propelled with the hot gas when released into an evaporator.
Because hot gas velocities can easily reach 100 feet per second, the pressure of the
liquid slug upon impact can exceed 3,000 psig [200 bar] (IIAR, 1992) Soft gas defrost
cycles may be used to prevent this situation and piping should be designed to
prevent liquid slugs from hitting a dead end in the piping.
Cleanliness
With carbon steel piping, particulates and moisture potentially may remain in the
system after assembly. These contaminants can wreak havoc with components such
as solenoids, check valves and regulators, plug strainers and orifices, and worst of all,
damage compressors. After assembly, the piping system should be cleaned and dried.
Steps should be taken to reduce the amount of contaminants initially introduced into
the system:
• To reduce the amount of rust in the system, piping should be kept capped at all
times until it is welded to the system.
• Welding slag should be removed or procedures used that reduce the amount of
slag introduced into the system.
2005 IIAR Ammonia Refrigeration Conference & Exhibition, Acapulco, Mexico
Technical Paper #2 © IIAR 2005 57
• Procedures should be used to keep foreign materials from being placed or
forgotten in the system such as rags, welding rods, soap stones and other items
and checks performed to insure such items are not left in the system before
sealing.
• Prior to system start up, socks should be installed in strainers to collect the initial
mass of particulate.
Water Contamination
The introduction of moisture in the system should be minimized. Purchasing
ammonia from a reliable vendor who provides refrigerant grade ammonia with
certification is one step to help reduce moisture content. The sometimes-overlooked
situation during installation is when a pipe penetration, through the building wall,
for example, is sealed on the cold side but not sealed on the warm side. When the
cold side is subject to temperatures below the dew point of the air on the warm
side, water will condense inside the pipe even in dry climates. If the water is not
removed, it will introduce a large volume of moisture into the system.
The refrigeration system should be initially dried out to an acceptably low moisture
content and should be periodically checked. The effects of moisture contamination
can be found in IIAR Bulletin No. 108. (IIAR, 1986)
Purgers should be used to remove air in the systems that operate in a vacuum. A
method of removing air-borne moisture should also be provided. An ammonia/water
distiller is a good way to periodically remove moisture.
Excessive oil is also considered to be a contaminant in the system. Equipment
should be in place to reduce the amount of oil introduced into the system by having
properly sized oil separators. The oil pots and other oil accumulation point drains to
remove accumulated oil from the system should also be provided. Where applicable,
systems should be in place to return or recycle oil back to the compressors.
Refrigeration Piping: A Simplified Guide to a Modern Approach — Paul Danilewicz and Paul Orlando
58 © IIAR 2005 Technical Paper #2
Conclusion
The paper reviewed only the most common mechanical, sizing and layout challenges
experienced designing ammonia refrigeration systems. The IIAR Ammonia
Refrigeration Piping Handbook should be consulted for detailed design
recommendations and practices. New design tools, used in the chemical process
industry, have also been presented to show the readers the direction in which the
refrigeration industry may turn in the near future.
2005 IIAR Ammonia Refrigeration Conference & Exhibition, Acapulco, Mexico
Technical Paper #2 © IIAR 2005 59
References
ASME. B31.5: Refrigeration Piping and Heat Transfer Components. American Society
of Mechanical Engineers (ASME). 2001.
ASME. B16.5: Pipe Flanges and Flanged Fittings. American Society of Mechanical
Engineers (ASME). 2003.
ASME B31.3. B31.3: Process Piping. American Society of Mechanical Engineers
(ASME). 2004.
ASME B&PV. Boiler and Pressure Vessel Code: Section VIII, Pressure Vessels.
American Society of Mechanical Engineers (ASME). 2004.
Beattie, W. International Journal of Multiphase Flow. Vol. 8, No 1, pp 83-87. 1982.
IIAR. Bulletin No. 108: Guidelines for: Water Contamination in Ammonia
Refrigeration Systems. International Institute of Ammonia Refrigeration (IIAR). 1986.
IIAR. Bulletin No. 116: Avoiding Component Failure in Industrial Refrigeration
Systems Caused by Abnormal Pressure or Shock. International Institute of Ammonia
Refrigeration (IIAR). 1992.
IIAR. Ammonia Refrigeration Piping Handbook. International Institute of Ammonia
Refrigeration (IIAR). 2004.
Richards, W.V. Practical Pipe Sizing for Refrigerant Vapor Lines. Proceedings of the
IIAR Ammonia Refrigeration Conference & Exhibition. 1984.
Refrigeration Piping: A Simplified Guide to a Modern Approach — Paul Danilewicz and Paul Orlando
60 © IIAR 2005 Technical Paper #2
Figure 1: Impact Exemption Criteria from ASME B31.5-2001
2005 IIAR Ammonia Refrigeration Conference & Exhibition, Acapulco, Mexico
Reprinted by permission from ASME
Technical Paper #2 © IIAR 2005 61
Refrigeration Piping: A Simplified Guide to a Modern Approach — Paul Danilewicz and Paul Orlando
Figure 2: Cost Escalation Factors for Low-Temperature Materials
960"
1200"
2400"
2400"
960"
960"960"
1218"
24"
24"
72"
72"
72"
72"
240
"
240
"
8" SUCTION LINE
3" HOT GAS LINE
Figure 3: Suction and Hot Gas Mains in Pipe Stress Analysis
62 © IIAR 2005 Technical Paper #2
2005 IIAR Ammonia Refrigeration Conference & Exhibition, Acapulco, Mexico
Figure 4: Sample of Suction Main Stress Calculations
Technical Paper #2 © IIAR 2005 63
Refrigeration Piping: A Simplified Guide to a Modern Approach — Paul Danilewicz and Paul Orlando
Figure 5: Pressure Rating for Different Piping Classes
64 © IIAR 2005 Technical Paper #2
2005 IIAR Ammonia Refrigeration Conference & Exhibition, Acapulco, Mexico
Fig
ure
6:
Sam
ple
So
ftw
are
Ou
tpu
t -
Pro
cess
Flo
w D
iag
ram
Technical Paper #2 © IIAR 2005 65
Refrigeration Piping: A Simplified Guide to a Modern Approach — Paul Danilewicz and Paul Orlando
Figure 7: Sample Software Output - System Mass Balance
66 © IIAR 2005 Technical Paper #2
2005 IIAR Ammonia Refrigeration Conference & Exhibition, Acapulco, Mexico
Figure 8: Sample Software Output - Pipe Sizing Calculations
Technical Paper #2 © IIAR 2005 67
Notes:
Refrigeration Piping: A Simplified Guide to a Modern Approach — Paul Danilewicz and Paul Orlando
Notes: