Technical Proposal

Technical Proposal

Submitted on: 3/3/15

Rep: James Murphy, Davis Controls

For: DuPont

By: Jack Nicholson

FLEXIM Americas Corporation

FLEXIM Americas Corporation

250-V Executive Drive

Edgewood, NY 11717 USA

Tel: (631) 492-2300 Fax: (631) 492-2117 Website: www.FLEXIM.com

Email: [email protected]

Table of Contents

1. Introduction

2. Ultrasonic Flowmeter Measuring Principle

3. Mounting and typical installations

4. Measurement Requirements

5. Description of the Proposed Ultrasonic Flowmeter

5.1 Features / Benefits

5.2 Technical Data for Instruments Offered

5.2.1 FLUXUS G601

5.2.2 Transducer Q

5.2.3 Transducer Mounting Fixture: Transducer chain mount

5.2.4 Laboratory Calibration Results

6. Bill of Materials/Price Proposal

7. Commissioning Services (Optional)

8. Delivery & Warranty

Introduction

FLEXIM Americas Corporation is a wholly owned subsidiary of FLEXIM GmbH, established in the United States in 2005 as the North & Central American Office to manage engineering, development, production Sales & Marketing and After-sale Services to our customer in the region. Since this time FLEXIM Americas has successfully delivered over 8,000 metering solutions for the most demanding of metering conditions including to all of the majors in the Oil & Gas sector.

Ultrasonic Flowmeter Measuring Principle

The proposed flow meter employs the transit time difference principle for flow measurement. Ultrasonic signals are emitted by a transducer installed on one side of a pipe, reflected on the opposite side and received by a second transducer. These ultrasonic signals are emitted alternatively in the direction of flow and against it.

As the medium in which the signals propagate is flowing, the transit time of the ultrasonic signals in the flow direction is shorter than against the flow direction.

The transit time difference t is measured and allows to determine the average flow velocity on the propagation path of the ultrasonic signals. A flow profile correction is then performed in order to obtain the area average of the flow velocity, which is proportional to the volume flow.

Transit time difference correlation principle

The received ultrasonic signals will be checked for their usefulness for the measurement and the plausibility of the measured values will be evaluated. The complete measuring cycle is controlled by the integrated microprocessors. Disturbance signals will be eliminated.

Mounting and typical installation

Single versus Dual channel configurations:

A single channel meter incorporates one set of transducers. A Dual channel meter incorporates 2 sets and computes the average velocity: The decision to purchase a single channel or dual channel meter is one of price/performance. With adequate straight run of pipe a single beam performance will be similar to a dual beam. A dual beam will have repeatability in the order of 1.0 to 0.5% better than a single beam. With shorter straight runs a dual channel is recommended because flow profile errors will have a greater effect on the accuracy. In summary a dual beam offers slightly better accuracy and redundancy.

Typical Installations

Requirements & Application Analysis

The application condition requirements for the application are:

Pipe Size: OD, WT

Medium

Temp

Hazardous Area

Available Straight Run

Power

Inputs

Outputs

Description of the proposed ultrasonic flowmeter

Features/Benefits

The proposed ultrasonic flowmeter has the following features:

Fit for Purpose FLEXIM Transducers Factory matched and calibrated Stainless Steel Transducers (hermetically sealed) and armored stainless steel cable delivers the robustness required of a portable or permanent device. Intelligent design transducer contains a microchip read by the meter that contains the calibration information. Competing devices are error prone when the transducer type is not input correctly.

Transducer Temperature Compensation The only Clamp-on meter that employs an RTD inside the transducer block as per ASME MFC 5M. A temperature algorithm compensates for calibration shifts due to temperature changes. Without this compensation the accuracy drift due to temperature change will 1% for a 30degF change.

PermaLokTrack Mount System For permanent installations the Stainless Steel PermaLok Track provides the highest level of transducer support and protection. FLEXIM has engineered a permanent solid coupling material for sonically coupling the transducer to the pipe. With the protection of the PermaLok track and the permanent coupling pads there is no need to periodically re-couple transducers.

Broadened Application Range FLEXIM incorporates a dynamic power delivery scheme that delivers the power to the transducers required to get the signal through the liquid.

Ease of Use The meter is designed to be intuitive and is very easy to program. Installation of entire meter can be easily accomplished in less than 4 hours.

FLEXIM Flexibility All FLEXIM meters can be configured to adapt to the application conditions at hand. If the upstream straight run is less than 10 diameters , the users may employ a number of mitigating techniques:

Multi-bounce transducer mounting allows the meter to average out local disturbances of the flow profile over a longer axial distance on the pipe. An even number of traverses (up to 8) simply cancels all cross-flow, non-axial influences on the flow velocity measured.

Proper location of the interrogating sonic beam (in the plane of an upstream elbow for example) assures that the instrument will see the fast flowing core of the liquid flow stream.

Multi-beam interrogation of the flow stream through the use of two or more transducer pairs will tend to average out locally asymmetrical distribution of the flow velocity field.

Reduced Noise Susceptibility All FLEXIM flow computers are fully shielded and utilize TRIAX cabling (provides for an additional armored outer shield) to prevent/minimize the influence of external noise sources.

Signal Detection The signal processing of the transmitted signal is NOT based upon a ZERO crossing detection which relies heavily on a match between the wall thickness of the pipe and a selected transducers operating frequency. Rather FLEXIM employs a signal correlation function in which the entire receive signal is utilized resulting in a more robust signal detection process.

Application Guarantee All meters sold. FLEXIM goes to great lengths to qualify each and every application and as such provides an application guarantee on each meter sold. We will ensure satisfaction with ALL metering solutions provided by FLEXIM.

Support In addition to FLEXIMs full-service operation center on Long Island, New York, and we have factory certified sales and service representatives located throughout the US and Canada. FLEXIM provides a free telephone hotline for assistance when you need it, including after hours 7 days a week till 12AM.

Total Cost of Ownership No need for recalibration, no wear mechanism, no pressure drop, no additional flanges, valving, by-pass, etc...

Proven Reliability 190 year calculated MTBF

Technical Data of Instruments Offered

FLUXUS G601FLUXUS G601 is designed especially for permanent installation. With one or two flow channels and versatile electrical inputs and outputs, it can be optimally configured for your measuring application. A variety of process parameters can be measured and handled.

Technical Data

FLUXUS G601

Measureable flow

velocity:

0.03 to 115 ft/sec

Repeatability:

0.15 % of reading 0.01 m/s

Anticipate Accuracy:

Traceable wet flow calibration at factory

1 to 1.5 % of reading 0.01 m/s

Operating temperature:

-20 to +50 C

Ingress protection:

IP65, NEMA 4x

Area Certification:

FMC Class I Div 2

Power supply:

110-240 V/50-60 Hz (power supply unit

Outputs:

RS-485

1 x 4-20 mA active

Frequency (Optional)

Internal Datalogger

Dimensions

External Dimension of G601

Transducer

The transducers together with the transmitter receive a calibration with water as medium. The proposed transducer is delivered with a calibration certificate. For this application we recommend CDQ1NZ7 which will cover the full spectrum of your pipe sizes

Transducer Mounting Fixture:

FLEXIMs chain mounting kit covers all pipe sizes from 0.5 up to 2.5. These mounting kits are easy to mount and work great in all portable applications that involves the need to periodically move the transducers to different pipes. Made from stainless steel you dont have to worry about maintenance or breakages.

Laboratory Calibration Results

Out of Box 3rd Party testing on pipe sizes 4, 8, 12 & 20, by CEESI Labs verifies meter accuracy typically 1.5%

Bill of Materials

Please issue purchase order(s)

FLEXIM AMERICAS CORPORATION

250-V Executive Drive

Edgewood, NY 11717

Terms: NET 30

FOB: Factory

Freight: Pre-Pay and Add

Validity: 90 Days

Commissioning Services

A FLEXIM service engineer can assist in the installation and start-up of the hardware being proposed. This service assumes that the flow computers and junction boxes are mounted, appropriate conduit is run to the pipes, transducer and temperature cable is pulled to the flow computer and transducers and temperature junction boxes, and A/C power is connected to the meter. FLEXIMs service engineer will be responsible for installing flow and temperature transducers, terminating transducer and temperature cables and performing calibration and commissioning of each system.

Scope of Work:

Work Performed by Other:

Mount meters

Run and install power to meters

Run Conduit for Power / Transducer Cables / Temperature Cables

Run cables in conduit (when required)

Work Performed by FLEXIM:

Terminate Transducer / Temperature Cables

Install Transducers / Temperature sensors on Pipe

Note: This will require cutting insulation - every attempt will be made to leave the insulation intact but insulation touch up may be required (by others).

Support Requirements:

On Site personnel to provide the following logistical support to FLEXIM personnel

Escort and access to the installations sites

Ladders / External Power / Lighting / Access

Delivery and Warranty

The terms of delivery shall be within 4 weeks from the date of order confirmation / technical clarification.

FLEXIM guarantee that the design, engineering and the instrument supplied shall be free from defects. All defective material shall be replaced free of charge within 12 months from the date of delivery of the instruments whichever comes earlier.

Page 10 of 14

FLEXIM AMERICAS Corporation

250-V Executive Dr. Edgewood NY 11717 631-492-2300 www.FLEXIM.com