technical research on evaporative air conditioners … · technical research on evaporative air...

57
TECHNICAL RESEARCH ON EVAPORATIVE AIR CONDITIONERS AND FEASIBILITY OF RATING THEIR ENERGY PERFORMANCE Prepared for SA Department of Transport Energy and Infrastructure On behalf of the E3 Committee Dept of the Environment, Water, Heritage and Arts Prepared by Professor Wasim Saman Dr. Frank Bruno Mr. Steven Tay Date of issue March 2010

Upload: hadang

Post on 19-Aug-2018

238 views

Category:

Documents


0 download

TRANSCRIPT

TECHNICAL RESEARCH ON EVAPORATIVE AIR CONDITIONERS AND FEASIBILITY OF RATING THEIR ENERGY PERFORMANCE

Prepared for SA Department of Transport Energy

and Infrastructure

On behalf of the E3 Committee

Dept of the Environment, Water,

Heritage and Arts

Prepared by Professor Wasim Saman

Dr. Frank Bruno

Mr. Steven Tay

Date of issue March 2010

1

2

Contents

Executive Summary ........................................................................................................ 4

1. Product Profile ............................................................................................................. 6

1.1 Types of evaporative air conditioners ..................... 6

1.2 Suitability for use in Australia ................... 11

1.3 Market share of evaporative air conditioners ................... 14

1.4 Types of heating systems ................... 15

1.4.1 Reverse Cycle Air Conditioners ................................................................ 15

1.4.2 Ground Coupled System ............................................................................. 17

1.4.3 Gas Heating ...................................................................................................... 17

1.4.4 Wood Heating .................................................................................................. 18

1.4.5 Solar Heating ................................................................................................... 20

1.4.6 Hydronic Heating ............................................................................................ 20

1.5 Energy consumption of evaporative air conditioners ................... 21

1.5.1 Cooling effects and energy used .............................................................. 21

1.5.2 Estimates of energy consumption of cooling capacity of energy consumption in different parts of Australia ..................................................... 22

1.6 Energy consumption of the components of evaporative air conditioners ................... 25

2. Regulatory Approaches ....................................................................................... 26

2.1 Australian standards ................... 26

2.2 International regulations and standards ................... 26

2.3 Standard test conditions …………….. 29

2.4 Shortcomings of current standards ………………………. 29

3. Testing/Rating Method ....................................................................................... 30

3.1 Review of available energy consumption testing procedure/methodology ................... 30

3.2 Development of a test methodology ................... 30

3.3 Proposed test conditions ................... 32

3.4 Proposed parameter for rating energy performance ................... 32

3.5 Application of the proposed testing and rating procedures to new technologies ................... 33

4. Performance Evaluation Information ......................................................... 34

4.1 Development of information for rating/labelling ................... 34

4.2 Proposed information for rating/labelling ................... 34

4.3 A parameter for rating the energy performance of evaporative air conditioners ................... 35

3

4.4 Example of the calculation of SEER ................... 36

4.5 Procedure for evaluation of the rating of the energy, cooling

capacity and comfort performance parameters ................... 36

5. Conclusions and recommendations ............................................................. 38

References .............................................................................................................................. 39

Appendix 1: Available Evaporative Air Conditioners in Australia & Their Key

Specifications ........................................................................................................................ 40

Appendix 2: Raw Air Conditioner Data in Figs 6 & 7 (ABS data)............................... 47

Appendix 3: Energy Consumption in a Typical Adelaide Hot Day ........................... 49

Appendix 4: Energy Consumption in a Typical Adelaide Summer Day ................... 51

Appendix 5: Industry Contact List .................................................................................... 53

Appendix 6: Glossary of terms ........................................................................................... 54

4

Executive Summary The installation of mechanical air conditioning appliances has become a normal requirement

in almost all new and existing Australian dwellings. While the use of refrigerated air

conditioners have been rapidly increasing, the market share of evaporative air conditioners

has witnessed a steady decline and currently makes up less than 20% of the installed systems

in Australian dwellings. Domestic air conditioning has considerable impact on energy use and

peak power demand. Evaporative air conditioners generally consume less energy but require

water for their operation.

This report will build on the information provided by a previously completed initial report by

the authors (Saman and Bruno, 2008). The report was discussed by industry Commonwealth

and State Government representatives in a workshop held on June, 2008. The proposed work

takes into consideration feedback received from the workshop participants and aims to

implement some of the recommendations put forward by the report and agreed upon by the

workshop participants.

In developing a draft methodology for rating the energy performance of evaporative coolers,

it has been proposed previously that the process should be carried out alongside a parallel

process being instigated for rating the water consumption of evaporative coolers and

incorporating them in the Water Efficiency Labelling Scheme (WELS). The development of a

combined procedure for rating both energy and water consumption has been recommended in

a report recently submitted by the authors (Saman, Bruno and Liu, 2009). This report

incorporates and updates some of the information gathered in the previous reports on the size

and features on the evaporative air conditioning market.

The report includes available information on energy consumption of evaporative air

conditioners and calculations of typical energy consumption and performance of evaporative

air conditioners in different Australian locations. The results highlight the suitability of using

evaporative air conditioners in most Australian locations except in the hot humid regions. The

report also demonstrates the sensitivity of the cooling capacity and energy consumption to the

air moisture content.

This report also reviews currently available local and international regulations and standards

for testing, labelling and rating evaporative air conditioners. The California Appliance

Efficiency Regulations include a procedure for evaluating and rating the energy performance

of evaporative air conditioners. Iran is the only country that currently conducts a mandatory

comparative labelling program for energy consumption of evaporative air conditioners. A

proposed test and evaluation methodology for rating energy performance is put forward. It is

proposed that independent testing should be carried out alongside water consumption testing

using a single test facility. The report sets out a detailed proposed procedure for carrying out

standard testing of evaporative air conditioners to evaluate their energy consumption

characteristics. The proposed testing procedure supplements the current Australian Standards

AS/NZS 2913-2000.

The report proposes the use of a new location specific ―Seasonal Energy Efficiency Ratio‖ as

the key parameter for evaluating the energy performance of evaporative air conditioners. This

parameter can be evaluated through calculations based on the standard test results and the

annual temperature and humidity variations for a typical year. Based on the test and

calculation results, it also proposes the evaluation of a number of other parameters which will

5

characterize comfort provision, cooling capacity energy use and cost for tested systems. These

parameters will provide useful information to consumers, manufacturers/suppliers and

governments. As the performance of evaporative air conditioners, is dependant on local

temperature and humidity patterns, these parameters can be evaluated by computer modeling

for all main Australian locations. An interactive computational tool has been developed to

evaluate the key cooling capacity, comfort and energy consumption parameters for major

cities in Australia with the input data being the results of the proposed testing methodology.

Early consultation with manufacturers, suppliers and users groups is considered to be an

important step in progressing a labelling/rating system for energy and water use in

evaporative air conditioners. A technical study for further developing a standard test

procedure, testing facilities and methodology for independent testing, rating/labelling of both

water and energy use in evaporative air conditioners, as well as modifying the current test

standard to provide for this, is also recommended.

6

1. Product Profile

1.1 Types of evaporative air conditioners

The utilisation of water evaporation for cooling purposes has its origins well entrenched in

history. Evidence of evaporative cooling applications by ancient people of the Middle East is

widely documented and some of these applications are still in use in the Middle East today.

They include the use of porous water vessels, the wetting of pads made of dried vegetables

which cover the doors and windows facing the prevailing wind and directing the prevailing

wind into pools of running water in underground rooms (Saman, 1993). Early Australians also

used different forms of evaporative air cooling to obtain some comfort in the hot dry climates

of outback Australia.

Direct evaporative air conditioning is ideal for arid climates where water is available. The

direct evaporative air conditioners currently produced have, by and large, overcome the

drawbacks associated with older systems. In addition to more efficient fan and duct designs

and control systems, the use of plastics for the bodywork, cellulose and other synthetic

materials for the pads together with automatic water bleeding or flushing has resulted in more

reliable operation with little maintenance. Many of today‘s evaporative air conditioners have

quite sophisticated control systems with variable air speeds and pad wetting rates. The one

remaining inherent drawback associated with direct cooling is the water saturation limit

inherent in the process. Even with saturation efficiency over 80%, which is common for

many modern systems, the air supplied may not provide cooling comfort if the outside air

temperature is high and/or its moisture content is high and close to saturation with water

vapour. The lowest possible temperature limit attained by direct evaporative cooling is the

wet bulb temperature at which the delivered air is fully saturated with moisture.

Evaporative air conditioners can be categorised as direct, indirect, two- and multi-stage.

Direct evaporative air conditioners are the most popular in the market. As shown in Fig.1 (a),

outside air is drawn through wetted filter pads, where the hot dry air is cooled and humidified

through water evaporation. The evaporation of water takes some heat away from the air

making it cooler and more humid. The dry-bulb temperature of the air leaving the wetted pads

approaches the wet-bulb temperature of the ambient air. Direct evaporative air conditioners

are more effective in dry climates. As they produce warmer, more humid air in comparison

with refrigerated air conditioners, considerably more air volumes are required to produce the

same cooling effect. The cool/humid air is used once and cannot be reused. Evaporation

(saturation) effectiveness is the key factor in determining the performance of evaporative air

conditioners. It is defined by Eqn.1. This property determines how close the air being

conditioned is to the state of saturation. Usually, the efficiency is 85-95% (ASHRAE

Handbook, 2007).

'tt

tte

1

21

100 (1)

Where

e = direct evaporation (saturation) efficiency, %

1t = dry-bulb temperature of entering air, oC

2t = dry-bulb temperature of leaving air, oC

't = wet-bulb temperature of entering air, oC

7

FAN

FAN

FAN

Figure 1: Types of evaporative air conditioners: (a) direct; (b) indirect & (c) two-stage combined

(Wang et al., 2000).

The saturation efficiency also has an impact on water consumption. Increased saturation

effectiveness is associated with higher water consumption. However, as higher saturation

effectiveness produces conditioned air at lower temperatures, the overall impact of having

higher saturation effectiveness is usually an improved energy and water consumption per unit

cooling output.

Indirect evaporative air cooling is shown in Fig.1(b).The principle of operation of indirect

evaporative cooling is the use of cool air produced by direct evaporative cooling (secondary

air stream shown in Fig. 1(b)) to cool another air stream which is used for space cooling by

the use of a heat exchanger. As cooling of the primary air stream takes place by heat transfer

across the heat exchanger walls without the mixing of the 2 air streams, the primary air stream

becomes cooler without an increase in its humidity. Indirect evaporative air conditioners are

effective in regions with moderate/high humidity. Indirect evaporative cooling effectiveness is

defined in Eqn.2. According to manufacturers‘ rating, this effectiveness ranges from 0.6-0.80

(ASHRAE Handbook, 2004).

'

1

21

s

ie

tt

tt (2)

Where

ie = indirect evaporative cooling effectiveness

8

1t = dry-bulb temperature of entering primary air, oC

2t = dry-bulb temperature of leaving primary air, oC

'st = wet-bulb temperature of entering secondary air,

oC

Two stage or indirect/direct evaporative air conditioners combine both direct and indirect

evaporative principles. In two-stage evaporative air conditioners, the first stage (indirect)

sensibly cools the primary air (without increasing its moisture content) and the air is

evaporatively cooled further in the second stage (direct) as shown in Fig.1(c). The dry-bulb

temperature of the supplied primary air can be reduced to 6 K or more below the secondary

air wet-bulb temperature (ASHRAE Handbook, 2004) without adding too much moisture. As

two-stage evaporative coolers produce lower temperatures, they consequently require less air

delivery in comparison with the direct systems. Heidarinejad et al. (2009) experimentally

studied the cooling performance of two-stage evaporative cooling systems under the climate

conditions of seven Iranian cities. It has been found that the saturation efficiency (as defined

in equation 1 above) of the indirect/direct evaporative air conditioner varies in a range of

108~111%. Also, over 60% energy can be saved using this system compared to a vapour

compression system. However, it consumes 55% more water in comparison with direct

evaporative cooling system for the same air delivery rate. Monitoring the electricity

consumption of evaporative and conventional refrigerated cooling systems in a small

commercial building has demonstrated considerable energy savings and improved thermal

comfort with evaporative cooling (Saman, et al. 1995). Indirect evaporative cooling can also

be used as a component of multistage air conditioning systems which may also include

refrigerated cooling stages. In such cases, the indirect evaporative cooling may be sufficient

for the provision of typical summer cooling requirements. The refrigerated stage operation is

limited to peak demand days.

Indirect evaporative air conditioners have been gaining more popularity in the market in

recent years. Recently, both Seeley International and Clear Solar have started marketing

indirect evaporative air conditioners. Seeley has been developing such air conditioners for a

number of years. Clear Solar is marketing a product developed in USA by Coolerado.

Both products produce air at conditions closer to refrigerated systems. Unlike conventional air

conditioning units, they use no ozone-depleting chemicals and have mainly one energy-

consuming component, the fan. The heart of both systems which sets them apart from

conventional evaporative coolers is a unique wetting system, a modular heat and mass

exchanger and the way the air flows through it.

In 2008, Coolerado received a grant to build a solar-powered mobile demonstration cooler

which brought Coolerado to the attention of a broader audience. The unit is outfitted with four

PV panels to power the cooler, and the cooler helps the solar array run at a lower temperature

and hence improved efficiency by about 15%.

Seeley has drawn together its most innovative and energy efficient technologies and merged

them with what it has been developing behind the scenes, over the past 14 years. The result is

Climate Wizard, a product that incorporates a patented revolutionary heat exchanger which

ensures that no moisture is added to the air entering the conditioned space, and at the same

time it maximises the effectiveness of all of the elements necessary to best facilitate the heat

exchange process.

9

Climate Wizard delivers significantly colder air than can be achieved by traditional

evaporative cooling. It delivers air at temperatures near, and at times, below, those produced

by refrigerated air conditioning. According to the manufacturer, Climate Wizard uses up to 54%

less energy than a fixed speed refrigerated system. Based on independent testing by the

University of South Australia, Climate Wizard is able to provide pre-cooled ―make-up air‖ to

large commercial refrigeration plants, resulting in energy savings of up to 35%, and at times,

even more. A Slim-line version for domestic applications, designed for installation against the

outer walls of homes, has approximately the same footprint as a water heater. Air is delivered

through the space between the outer wall and the roof into the home and then through a

conventional ducting system in the ceiling space, and into the rooms of homes. Ducting and

fittings are the same dimensions as for traditional refrigerated systems.

The main focus of this report is direct evaporative air conditioners as most units in current use

within Australia are of this variety. However, the scope of the report also includes indirect and

two-stage systems in view of their recent entry into the Australian market.

A direct evaporative air conditioner is an enclosed metal or plastic box with louvers on the

sides containing a fan or a blower with an electric motor, a number of cooling pads, a water

circulation pump to wet the cooling pads and a float valve to maintain a proper water level in

the reservoir. Fig. 2 illustrates the components in a typical evaporative air conditioner.

Figure 2: Schematic diagram of the components of a typical direct evaporative air conditioner.

Types of evaporative air conditioners range from portable units, window/wall units and

ducted units for residential and commercial use. Portable units cool one room at a time. They

are fitted with legs and wheels and can be moved easily from room to room. A small pump is

utilized to keep the cooling pads wet and water is needed to be periodically filled manually in

the internal water storage tank. Typical portable evaporative air conditioners are shown in

Fig.3. However, this report only examines plumbed units/systems and therefore the portable

10

units will be excluded from the discussion. Window/wall evaporative air conditioners are

mounted through exterior windows or walls and they can cool larger areas than the portable

units. A window evaporative unit is presented in Fig. 4. Ducted evaporative air conditioners

make up the vast majority in use in Australia. They are usually mounted on the roof and the

cooled air is delivered through ducts to each room in the building. Fig. 5 shows residential

roof ducted evaporative air conditioners with different profiles. Both window/wall and ducted

units have a water bleeding system to control the water salinity under a certain level.

Figure 3: Portable evaporative air conditioners

(http://www.convair.net.au/convairnew/peac/ConvairPEAC.html).

11

Figure 4: (a) Window evaporative air conditioner; (b) View from cooled space; (c) View from outside.

(http://www.bonaire.com.au/evaporativecooling/window/default.aspx)

Figure 5: Residential roof ducted evaporative air conditioners with different profiles.

1.2 Suitability for use in Australia

Using the Australian summer design conditions, Tables 1 and 2 include the estimates of the

performance parameters of direct and indirect evaporative air conditioners. The parameters

include the outlet temperature, relative humidity and cooling capacity for 8 Australian

locations.

(b)

(c)

(a)

12

Table 1: Performance of direct evaporative air conditioners at some Australian locations

AIRAH

Design

Conditions

Air conditioner

Supply Conditions

Cooling Capacity

(kW) Based on

10 000 m3/hr

air flow Dry Bulb

(°C) Wet Bulb

(°C) Dry Bulb

Temperature

(°C)

Relative

Humidity

(%)

Adelaide 37.0 20.1 22.6 46.3 14.9

Brisbane 30.8 22.8 24.0 75.9 10.2

Canberra 34.3 18.1 20.5 43.0 22.2

Darwin 34.4 23.6 25.2 69.3 6.1

Hobart 27.1 16.8 18.4 59.2 29.5

Melbourne 34.3 19.4 21.7 50.0 18.3

Perth 36.6 20.1 22.5 47.5 15.1

Sydney 31.1 19.8 21.5 61.8 18.8

The first two columns of Table 1 show the AIRAH design conditions of the dry and wet bulb

temperatures for eight cities in Australia. The dry bulb temperatures of the air leaving the

direct evaporative air conditioner are presented in the third column. The temperatures of the

air leaving the direct evaporative air conditioner can be calculated from Eqn. 1, based on the

assumption that the saturation efficiency of the direct evaporative air conditioner is 85%. The

relative humidity of the air leaving the evaporative air conditioner is also included in the table.

Based on a nominal volume flow rate of 10,000 m3/hr for the air conditioner, the cooling

capacity of the direct evaporative air conditioner is computed based on Eqn. 3 below. Table 1

shows that despite the relatively low temperatures achieved by direct evaporative air

conditioners, the low cooling capacity and high humidity produced in the tropical and

subtropical regions (Darwin, Brisbane) make their use impractical. However, comfort cooling

conditions (temperature and relative humidity) and high cooling capacities are achievable in

all other Australian locations having relatively cool and/or dry summers.

One option for extending the climatic regions where evaporative cooling is effective is the use

of indirect or 2 stage indirect/direct evaporative cooling. The use of a heat exchanger to cool

the outside air without humidifying it by making use of indirect evaporative cooling systems

was developed in Australia in the 1960s and 1970s; plate heat exchangers were manufactured

and marketed (Pescod, 1968 & Pescod, 1979). From the manufacturing view point, the main

challenge of the system is the size and cost of the heat exchanger required to achieve good

effectiveness and low pressure loss. Work has been done at the University of South Australia

13

to develop low cost heat exchangers optimised for heat recovery as well as indirect

evaporative cooling purposes (Saman & Kilsby, 1999).

Both indirect evaporative air conditioners which have recently been introduced into the

Australian market are based on multistage indirect evaporative cooling and achieve lower

temperatures without increasing the air humidity, thus enabling them to compete directly with

refrigeration systems. Consequently less air is required for producing the required cooling

capacity in comparison with direct systems.

Table 2: Performance of indirect evaporative air conditioners at some Australian locations

AIRAH

Design

Conditions

Air conditioner

Supply Conditions

Cooling Capacity

(kW) Based on

2 000 m3/hr air flow

Dry Bulb

(°C) Wet Bulb

(°C) Dry Bulb (°C) Relative

Humidity

(%)

Adelaide 37.0 20.1 15.9 70.4 6.3

Brisbane 30.8 22.8 20.8 92.1 3.5

Canberra 34.3 18.1 14.1 64.7 7.3

Darwin 34.4 23.6 20.9 89.9 3.4

Hobart 27.1 16.8 14.2 77.2 7.2

Melbourne 34.3 19.4 15.7 72.9 6.4

Perth 36.6 20.1 16.0 71.4 6.2

Sydney 31.1 19.8 17.0 81.9 5.7

The first two columns of Table 2 show the AIRAH design conditions of the dry and wet bulb

temperatures for eight major cities in Australia. The dry bulb temperature and relative

humidity of the air leaving the indirect evaporative air conditioner are presented in the third

and fourth columns. The temperatures of the air leaving the indirect evaporative air

conditioner is calculated from Eqn. 2, based on the assumption that the direct evaporative

saturation efficiency is 125%. With the wet and dry bulb temperatures of the air leaving the

evaporative air conditioner determined, the relative humidity of the air leaving the evaporative

air conditioner can then be computed. Based on a reduced nominal volume flow rate of 2,000

m3/hr, the cooling capacity of the indirect evaporative air conditioner is computed based on

Eqn. 3 below.

14

1.3 Market share of evaporative air conditioners

There are currently four major local evaporative air conditioner manufacturers: Air Group

Australia Pty Ltd, Carrier Australia Pty Ltd, Climate Technologies Pty Ltd and Seeley

International Pty Ltd. The evaporative air conditioners that are currently available in Australia

together with their key available specifications (such as type, energy input, water bleeding

system, fan and pad type, supply flow rate, control system and evaporation efficiency) are

listed in Appendix 1.

Figure 6 shows the national penetration of air conditioners and the number of air conditioners

(including refrigerated and evaporative) utilised in residential houses in Australia from 1994

to 2008 (ABS, 2008). Penetration is the proportion of households having a particular type of

air conditioner. The refrigerated air conditioners refer to the reverse cycle and cooling only

refrigerated air conditioners, non-ducted or ducted. Between 1999 and 2008, there has been a

sharp increase in penetration and the number of refrigerated air conditioners. The penetration

rose from 34.7% in 1999 to 66.4% in 2008, which is nearly double in 10 years. The number of

evaporative air conditioners slowly increased from 0.41 million in 1994 to 1.03 million in

2005, before slightly decreasing between 2005 and 2008.

Figure 6: National penetration and number of air conditioners (ABS, 2008)

Fig. 7 illustrates some trends in the share of installed stock of air conditioners which are of the

evaporative variety, both by state and nationally. The share of evaporative air conditioners

reached a peak (27.4%) in 1999 and gradually went down to 18.6% in 2008. Also, for most of

the states, the evaporative air conditioner share decreased since 1999. However, evaporative

air conditioners are still popular in suitable climatic zones – Western Australia, Australian

Capital Territory, Victoria and South Australia where their market share is around 30%.

However, the general trend is a clear reduction of market share in the face of competition

from refrigerated systems. The raw data for Figs. 6 and 7 is listed in Appendix 2.

0.000

1.000

2.000

3.000

4.000

5.000

6.000

1992 1994 1996 1998 2000 2002 2004 2006 2008 2010

Year

Un

its

(mil

lio

ns)

0.0

10.0

20.0

30.0

40.0

50.0

60.0

70.0

Pen

etr

ati

on

(%

)

evaporative

refrigerated

total

penetration

15

Figure 7: Evaporative air conditioners percentage share of all installed domestic air conditioners by

state and nationally (ABS, 2008).

Refrigerated air conditioner sales in Australia had a distinct increase over the past 25 years

from less than 100,000 units per year in 1980 to more than 900,000 units a year in 2006

(Energy Efficient Strategies, 2008). The market is large and complex and at present there are

around 200 brands. The vast majority of domestic refrigerated air conditioners are imported.

The annual sales figure of rooftop evaporative air conditioners is approximately 60,000 units

and this figure has been reasonably stable over the last 5 years. Most of the residential ducted

evaporative air conditioners sold in Australia are manufactured domestically.

Despite the lower energy consumption of evaporative air conditioners in comparison with

other cooling systems, and improvements in the quality of products produced by the

Australian evaporative air conditioning industry, there is a general trend of a shrinking market

share. This is partly possibly a result of the competition provided by international

refrigeration system manufacturers and suppliers, particularly in marketing their products, as

well as cost advantages associated with larger scales production.

1.4 Types of heating systems

1.4.1 Reverse Cycle Air Conditioners

Refrigeration air conditioners shift heat from one location to another, using a compressor and

two heat exchangers linked by a refrigeration circuit. As electricity is required to operate the

compressor and fans which take the heat from the environment, they are the most efficient

form of electric heating. Unlike electrical resistance heaters which at most convert all

electrical input into heat (efficiency approach 100%), the heating output provided by a reverse

cycle air conditioner may be 3 to 6 times the electrical energy consumed by the system.

Refrigeration air conditioners are available as ―cooling only‖ units, or ―reverse cycle units‖

0.0

10.0

20.0

30.0

40.0

50.0

60.0

1992 1994 1996 1998 2000 2002 2004 2006 2008 2010

Year

Evap

ora

tive

air

con

dit

ion

er s

hare

(%

)

NSW Vic. Qld SA WA Tas. NT ACT Australia

16

which provide both cooling and energy efficient heating. There are a number of different

types of refrigeration air conditioners available:

window/wall units which are used for individual rooms or small open plan areas.

non-ducted split systems which are used for individual rooms or small open plan areas.

These differ to the above in that the 2 heat exchangers are separated, one being located

indoors and the other outdoors.

ducted systems (usually of the split type) which are used for large open plan areas or the

whole floor of a building.

multi-split systems, which have more than one indoor unit with more than one independent

indoor controls, with only one condenser unit located outside.

chillers which cool water as opposed to air. The cold water is then piped around the home

to cool the air with the use of heat exchangers.

Reverse cycle air conditioners are available as fixed-speed, inverter (variable speed) and

variable capacity (digital scroll).

Inverter (Variable Speed)

Conventional air conditioners have single speed compressors, which run at a constant speed

and vary their capacity by switching on and off at various times guided by the thermostat

setting. Their efficiency stays relatively constant at part load output. A new innovation in air

conditioner technology is the use of an inverter or variable speed drive in the motor system

that drives the compressor. While these systems tend to have lower performance at full load

than conventional air conditioners, they tend to be more efficient at part load operation, which

is a more common mode in a typical household. Air conditioners with a variable output

compressor allow the compressor output to be reduced to match the steady state output

required. They are, however, more expensive to buy. Inverter units are marked on the air

conditioner product listing at www.energyrating.gov.au and part load efficiency data is also

available for some inverter models.

Variable Capacity (Digital Scroll)

Varying the speed of a compressor is one means of varying the capacity of the cooler.

Another technology available to vary the capacity is the digital scroll.

Digital Scroll has two Scrolls which turn against each other around a common axis to

compress the refrigerant gas. The Digital Scroll compressor operates in two stages: the loaded

state and the unloaded state. During the loaded stage, the compressor operates like a standard

scroll and delivers full capacity. During the unloaded stage it does not deliver any capacity.

The continuous alternating of these stages of loaded and unloaded state in a specific period of

time (work cycle) determines the capacity modulation of the compressor.

The inverter technology usually allows the air conditioner to go down to about 40% capacity

whilst a digital scroll compressor can adjust between 10–100% capacity. Unlike an inverter,

the Energy Efficiency Ratio (see definition in section 1.5 below) of a digital scroll does not

improve as the capacity is reduced.

Generally the energy efficiency of refrigeration air conditioners is higher for space heating

compared to when they are used for space cooling.

17

1.4.2 Ground Coupled System

Like refrigeration air conditioners, ground coupled (sometimes referred to as geothermal)

systems are available as ―cooling only‖ types or ―reverse cycle‖.

Ground coupled heat pump systems can be used for residential space heating and cooling.

The ground just below the surface remains at approximately constant temperature all year

round. The underground temperature is greater than the outside air temperature in the winter

months, and less than the outside air temperature in the summer months. The ground source

heat pump can be used to draw the geothermal heat from the ground in the winter and release

the heat back into the ground in the summer.

The three principal components of a ground coupled heat pump system are the heat pump, the

ground connection and the conditioned air distribution system. The heat pump component is

a refrigeration system as used in a refrigeration air conditioner that uses outside air as a heat

sink/source, except it is connected to a ground loop and uses the ground, rather than the air, as

a heat sink/source. The ground connection, or ground loop, is buried underground, adjacent

to the residence to be heated and cooled.

The ground loop can be buried in various configurations. It can consist of loops of plastic

pipe placed vertically into the ground, several metres deep, and back-filled to provide good

ground contact. The loop can be buried horizontally in trenches, either in lengths of pipe or in

coils. The loop could also be placed at the bottom of a pond. A heat transfer fluid (usually

water) is circulated through the ground loop and the heat pump heat exchanger to complete its

ground connection. The heat pump system uses a standard conditioned air distribution system

of ductwork, like that which is used for other standard types of heating and cooling systems.

The relatively constant temperature of the earth enables a ground coupled heat pump system

to operate with a greater efficiency than an equivalent air-to-air system. It is generally

accepted that electrical energy use can be reduced by around 30% with ground coupled heat

pumps, when compared to a refrigerated air conditioner. Note that this comparison is

assuming both systems have fixed-speed compressors. Both of these systems could use an

inverter to increase energy efficiency.

The cost of a typical residential ground coupled heat pump installation, over a comparable air

sink/source system, would be in the range of 50 to 120% greater, depending on which type of

ground connection is used. Pond type ground source heat pumps tend to be the least

expensive of the systems. Although the initial cost is more, the annual savings can make

ground coupled heat pumps well worth the extra expense.

1.4.3 Gas Heating

Space heating systems using natural gas is very common in Australia where reticulated gas is

available. In areas where natural gas is not available, heaters can be run on liquefied

petroleum gas (LPG or ‗bottled‘ gas), although generally this is a significantly more

expensive option. Traditionally, gas heating has been used in dwellings having evaporative air

conditioning.

Victoria has the largest and most extensive gas distribution system and a high heating

requirement hence a high penetration of gas heating. Perth has milder climates but has well

18

established gas networks. Queensland has a very low heating requirement and a very limited

natural gas distribution system.

Gas space heaters consist of two main types; ducted units and non-ducted units.

Ducted units consist of a central heating unit, located either in the ceiling cavity, under the

floor or outside the home. The unit draws air from inside the house, warms it through a heat

exchanger and then pumps the warmed air back into the home through a system of ducts,

located in the ceiling or in the floor, depending on house design. The air for combustion is

drawn from outside and is flued to the outside after combustion so that no combustion

products enter the home. Some systems also allow zoning which gives the user control over

which rooms are heated, to what temperature, during what times of the day or night. Ducted

heating systems are generally more popular in colder climates, due to their large heating

capacity and their ability to heat the whole house. Ducted systems generally have a higher

capital and installation cost. All ducted systems use convection as the means of heating.

Non-ducted units consist of a range of types with differing heating delivery methods and

associated accessories. Non-ducted types can be split into flued and unflued systems. Fluing

systems externally exhaust the heater combustion products to the outside.

Unflued units are those where the gas combustion process takes place wholly within the room

being heated. The air for combustion is drawn from the room and the combustion products are

returned to the room. Typically unflued space heaters tend to be of smaller capacity. Portable

units are generally unflued. Unflued heaters also have nominally a high efficiency as all heat

is returned to the room, but there are requirements for ventilation as the combustion products

(water and carbon dioxide) also enter the room. There are several issues surrounding unflued

units. Each State has differing regulations pertaining to the use of unflued gas space heaters.

In Victoria, unflued heaters may only operate on LPG.

Non ducted units can also be split into three differing heat delivery methods; convection,

radiant and gas log (decorative) and combinations of these. Convection based units warm the

indrawn air and then pump it into the space to be warmed. Radiant units heat panels on the

face of the unit to a high temperature which then directs radiant heat energy towards the user,

who generally has be to in fairly close proximity to get the benefits. Many radiant heaters also

have a fan that moves air around the room as well (generally called radiant/convection

combination units). Gas log units use stylised ceramic logs and realistic flames to create a

traditional wood fire effect. They generally have large glass faces, which allows viewing of

the fire and radiation of some heat; most also have fans that help circulate the warmed air.

Gas space heaters display an Energy Rating Label with 1 to 6 stars. This label identifies the

energy efficiency of the heater—the more stars, the more efficient. Energy efficient units

produce more heat for each unit of gas consumed. High efficiency gas heaters use 90 per cent

of the heat contained in the gas.

1.4.4 Wood Heating

Wood heaters are available in a wide range of models that vary in output from small units

intended to heat a single room, to very large units with the capacity to heat relatively large

houses. The final selection will depend upon a number of factors: e.g. house design, insulation

levels and the length of time the heater is to be operated. Larger heaters are best suited to

homes with an open plan design where heat can be readily and effectively circulated to other

19

areas of the home. Most new wood heaters for sale in Australia are tested to determine their

output, energy efficiency and particle emissions levels under the Australian/New Zealand

Standards AS/NZS4012 and AS/NZS4013.

Wood heaters provide heat in one or a combination of the following ways:

(i) Radiation

(ii) Convection

(iii) Fan forced air distribution

There are no clear performance differences between cast iron and plate steel construction,

however, there are important differences in heat delivery. The main ways are by direct

radiation, convection or a combination of both. Fig. 8 shows a typical example of a wood

heater.

Figure 8: Wood heater (http://www.homeheat.com.au/pdf/fact.pdf)

Radiant wood heaters

Radiant wood heaters transfer about two-thirds of their heat output by radiation and about

one-third by convection. They have very hot surface temperatures and radiate their heat out in

all directions. The surfaces of objects such as walls, floors, ceilings, furniture and people that

face the wood heater are warmed directly by the radiated heat. However, they produce uneven

heat distribution with the warmth concentrated closer to the heater.

Convection wood heaters

Convection wood heaters have a ventilated casing around the firebox which is either tiled or

fabricated from metal. Heat is distributed by convective currents, with cooler air being drawn

in to rise between the firebox and the outer casing, keeping the outside of the unit relatively

cool. Convection heaters transfer about two-thirds of their heat output by convection and

about one third by radiation. Sometimes electric fans may be built in to increase the

convective air flow. Because warm air rises, these heaters tend to heat the room from the

ceiling down, and as a result it takes longer for the warmth to be felt. Reversible ceiling fans

can help overcome this. Convection wood heaters generally provide a fairly even heat

20

throughout a room and because their exterior surfaces are lower in temperature than radiant

models, they are less likely to cause burns from direct contact.

1.4.5 Solar Heating

Solar space heating has attracted considerable popularity in some European countries such as

Austria, Germany and Denmark. It is usually combined with domestic hot water provision

systems. The combi system has a larger water tank and solar collection system and has

produced good operational results.

There are very few solar air space heating products available in Australia. UniSA developed a

roof integrated solar air heating system which has proved capable of integration into metal

roofs. The Victorian company Sun Lizard offers a box type air-heater system which provides

a small quantity of heat. T3 Energy Pty Ltd, based in the Blue Mountains in NSW, has a

commercial solar hot air space heating product, which is being made available to households

throughout Australia. It is a modular system of clip together units that can be formed into roof

integrated arrays.

There are a number of companies in Australia who are able to design solar space heating

systems using commercially available solar hot water collectors. The heat may be distributed

through a hydronic heating system (see next section).

1.4.6 Hydronic Heating

Hydronic heating uses hot water to provide whole home heating.

In hydronic systems, water is heated, and then pumped through piping to panel radiators or

convectors positioned in each room. Heat is transferred directly from these to the room air. In-

slab (floor coil) systems are also available. In these, the heated water is pumped through

piping laid in a concrete slab floor during its construction. Heat is released into the slab, and

subsequently into the room.

The water can be heated using a gas boiler, solar water collectors or an electric driven air-to-

water heat pump. If solar water collectors are used then an auxiliary heating system is usually

also required.

Benefits of hydronic heating include:

Individual control valves to each panel allowing individual rooms or zones to be heated

independently, enabling running costs to be substantially lowered.

Panel radiators can provide effective heating for rooms with higher ceilings.

There is no dust circulation and air movement with silent radiant heat distribution (unless

using fan convectors).

Hydronic heating has been widely used in Europe for almost a century and is a proven

technology.

21

1.5 Energy consumption of evaporative air conditioners

1.5.1 Cooling effects and energy used

As evaporative air conditioners pumps 100% outside air to the space to be cooled, cooling is

achieved through replacing the expelled air from the room by inlet air from the air conditioner.

Therefore, the cooling capacity of an evaporative air conditioner can be defined as:

S = ρ qv Cp (tr-tin) (3)

Where

S: cooling capacity (kW)

ρ: density of standard air (1.20 kg/m3 for standard air)

qv: air volume flow rate corrected to standard temperature and pressure (m3/s)

Cp: Specific heat capacity of moist air at constant pressure (1.024 kJ/kg, based on a humidity

ratio of 10 g/kg) tin: air inlet dry bulb temperature to the conditioned space (°C)

tr: air outlet temperature from the conditioned space (°C)

If the air delivered by the air conditioner is at a temperature equal or greater than the air being

expelled from the space, then evaporative air conditioning is ineffective. Consequently,

cooling is only achieved when S has a positive value.

The psychrometric chart in Fig. 9 illustrates the evaporation process (red line) when air passes

through the pad of a direct evaporative air conditioner. The wet-bulb temperature of the

leaving air is the same as the wet-bulb temperature of the entering air. Then the humidity

ratios of both entering and leaving air can be determined from the psychrometric chart. The

value of tin is dependent on the outlet air dry bulb temperature from the air conditioner, which

is a function of the outside air dry and wet bulb temperatures and the evaporation

effectiveness of the cooler according to the equation:

(4)

Where

evaporation (saturation) effectiveness

inlet air dry bulb temperature (°C)

outlet air dry bulb temperature (°C)

inlet air wet bulb temperature (°C)

Consequently, the cooling capacity of an evaporative cooler is dependent on the inlet air dry

and wet bulb temperatures as well as the air flow rate and evaporation effectiveness of the

cooler. No cooling can be achieved if the air produced by the cooler is at a higher temperature

than the desired temperature of the air being exhausted from the room (usually taken to be

27°C). In order to evaluate a ―rated cooling capacity‖, the dry and wet bulb temperatures of

the outside air must be fixed. The evaporative cooler evaporation effectiveness (or efficiency)

must be evaluated experimentally at these conditions. Once the rated cooling capacity has

22

been established, a rated ―Energy Efficiency Ratio‖ can be determined as a measure of rating

the cooling effect being produced per unit electrical power being consumed.

(5)

Where

Energy Efficiency Ratio

cooling capacity (kW)

total input electrical Power (kW)

The total power consumption by the fan, pump and controller and the air flow rate under

conditions simulating the pressure losses in ducting along with all temperatures, must also be

measured at the same test under conditions simulating the rated outside dry and wet bulb

temperatures.

Figure 9: Psychrometrics of direct evaporative cooling.

1.5.2 Estimation of energy consumption in different parts of Australia

In an effort to provide indicative estimates of the energy required for evaporative air

conditioners, the energy consumption for cooling purposes has been calculated based on

typical yearly weather data for seven Australian cities (Adelaide, Brisbane, Canberra, Hobart,

Melbourne, Perth & Sydney) where cooling is necessary. The amount of energy consumption

for cooling purposes of the seven cities has been calculated based on the climatic data from

the Australian Climate Data Bank (ACDB). The results are presented in Tables 3 and 4. In

carrying out the calculation, it is assumed that the evaporation/saturation efficiency of the

cooling pad is 85%. The calculation is also based on a rule of thumb design guide used by

many suppliers which is that the evaporative air conditioner is assumed to be delivering the

equivalent volume of 30 air changes per hour. Two sizes of residential ducted units were

taken into consideration in the calculation:

Residential house with a conditioned area of 130m2 and a ceiling height of 2.4m. The

required air supply rate is 9360m3/h and the electricity consumption of the evaporative

cooler providing this air flow rate is estimated to be 810W.

Dry Bulb Temperature, °C

Hu

mid

ity ratio

, g m

oistu

re / kg

dry

air

Entering

air

Leaving

air

23

Residential house with a conditioned area of 200m2 and a ceiling height of 2.7m. The

required air supply rate is 16000m3/h and the electricity consumption of the evaporative

cooler is 1060W.

Table 3 shows that for all locations being considered except for Brisbane, there are only a few

hours in a typical year where a combination of high outside air temperature and high humidity

are encountered. This table demonstrates the suitability of direct evaporative air conditioners

to provide high cooling capacities and low temperature cooling in most Australian cities

except the tropical and semi tropical regions. Human thermal comfort can be normally

achieved when the temperature is below 27 °C and the moisture content is below 16 g/kg.

Therefore, the number of hours when the temperatures are above 27 °C and the moisture

content is above 16 g/kg for the different Australia locations have been specified in the table.

In order to have a better indication on the effectiveness of the evaporative cooler, the number

of hours that the dry bulb temperature of the air leaving the cooler that is above 25 °C are also

illustrated. The cooling capacity based on the air volume flow rate of 9,630 m3/hr and 16,000

m3/hr are calculated using Eqn. 3 for each hour of the day when cooling is deemed necessary

( when the outside dry bulb temperature is above 27 °C). The summation of the cooling

capacities will depict the total annual cooling capacity for each location. Dividing the total

annual cooling capacity by the number of hours when the outside dry bulb temperatures are

above 27 °C will result in the average cooling capacity.

Table 3: Estimates of cooling performance of Evaporative air conditioners for different unit sizes and

Australia locations.

Location

Duration

of

outside

dry bulb

temp

>27 °C

(hrs)

Duration

of cooler

moisture

content

>16 g/kg

(hrs)

Duration

of cooler

dry bulb

temp

>27 °C

(hrs)

Duration

of cooler

dry bulb

temp

>25 °C

(hrs)

Total annual

cooling capacity

(kWh)

Average

cooling

capacity

(kW)

9630

(m3/h)

16000

(m3/h)

9630

(m3/h)

16000

(m3/h)

Adelaide 845 38 4 18 20442.5 34944.5 24.2 41.4

Brisbane 572 325 0 39 7544.3 12896.3 13.2 22.5

Canberra 291 1 0 0 7845.3 13410.9 27.0 46.1

Hobart 36 0 0 0 867.6 1483.1 24.1 41.2

Melbourne 347 0 0 0 7401.8 12652.7 21.3 36.5

Perth 839 16 0 0 18261.8 31216.7 21.8 37.2

Sydney 276 100 0 0 4621.0 7452.1 16.7 28.6

The total annual electricity consumption to provide cooling during all hours when the outside

temperature is above 27°C has been calculated in Table 4 which demonstrates the low energy

consumption and cost associated with the use of these cooling systems. The table also

introduces a new parameter for evaluating the energy performance of evaporative air

conditioning systems, namely the Seasonal Energy Efficiency Ratio (SEER) which is the ratio

of annual cooling output of the air conditioner during the cooling season and the total annual

electrical energy usage to produce the cooling requirements. This ratio is a good measure of

the electrical energy effectiveness of cooling production under different climatic conditions. It

is a more comprehensive measure in comparison with the Energy Efficiency Ratio (EER)

24

commonly used for rating refrigeration system performance as the latter is a measure of the

performance at specified thermal test conditions only and does not take into consideration the

impact of temperature and humidity variation throughout the cooling season. The total annual

electricity consumption is the energy consumed by the evaporative coolers that supply air

volume flow rates of 9630 m3/hr and 16000 m

3/hr during the whole cooling season.

Table 4: Estimates of energy performance of evaporative air conditioners for different unit sizes and

Australia locations.

Location

Total annual electricity

consumption

(kWh)

Seasonal Energy Efficiency

ratio

(-)

9630 (m3/h) 16000 (m

3/h) 9630 (m

3/h) 16000 (m

3/h)

Adelaide 684.4 895.7 29.9 39.0

Brisbane 463.3 606.3 16.3 21.3

Canberra 235.7 308.5 33.3 43.5

Hobart 29.2 38.2 29.8 38.9

Melbourne 281.1 367.8 26.3 34.4

Perth 679.6 889.3 26.9 35.1

Sydney 223.6 292.6 20.7 27.0

Furthermore, the amount of energy consumption for cooling purposes has been calculated

based on hourly weather conditions in a typical hot day and a typical summer day from two

available climate data sources for Adelaide: (1) data supplied by ACADS-BSG (a specialist

building services simulation company) and (2) climate data from Australian Climate Data

Bank (ACDB). The typical hot day in this report refers to a day in which the 3:00pm dry-bulb

temperature is only exceeded on 10 days per year. The typical summer day refers to a day, in

which the 3:00pm dry-bulb temperature equals the average 3:00pm temperature of the

summer days requiring cooling. In the calculation, cooling is assumed to be switched on at

full speed during hours when the outside temperature exceeds 27oC and represents the

maximum energy consumption on those days. The hourly energy consumption in the typical

hot day and the typical summer day are listed in the tables in Appendix 3 and Appendix 4

respectively. The total energy consumption and the average energy consumption and energy

efficiency ratio are shown in Table 5.

25

Table 5: Estimates of energy consumption of Evaporative air conditioners on typical days in Adelaide.

Conditions

Source

of

Climate

Data

Period requires

cooling

Total cooling

capacity for

various air flow

rates (kW)

Average

cooling

capacity for

various air flow

rates (kW)

Average EER

for various air

flow rates

Total electricity

consumed for

various air flow

rates (kWh)

9360

(m3/h)

16000

(m3/h)

9360

(m3/h)

16000

(m3/h)

9360

(m3/h)

16000

(m3/h)

9360

(m3/h)

16000

(m3/h)

Adelaide

typical hot

day

ACAD-

BSG 6:00am~12:00am 445.8 762.0 23.5 40.1 29.0 37.8 29.0 37.8

ACDB 11:00am~11:00pm 278.4 476.0 21.4 36.6 26.4 34.5 26.4 34.5

Adelaide

typical

summer

day

ACAD-

BSG 10:00am~7:00pm 221.5 378.6 22.1 37.9 27.3 35.7 27.3 35.7

ACDB 11:00am~8:00pm 250.7 428.5 25.1 42.8 30.9 40.4 30.9 40.4

1.6 Energy consumption of the components of evaporative air conditioners

The energy consuming components of an evaporative cooler are the fan motor, water pump

and controller (manual or remote). The breakdown of the power consumption of these

components for domestic applications under typical operation conditions are: fan motor

(230W to 2200W), water pump (30W to 136.8W) and controller (approximately 24W).

Details of the rated energy consumption for components of various brands and specifications

are found in Appendix 1.

26

2. Regulatory Approaches

2.1 Australian standards

AS/NZS 2913-2000: Evaporative Air-conditioning Equipment

In Australia, AS/NZS 2913-2000 is the only regulatory instrument available for testing

evaporative air conditioners. This Standard was prepared by Standards Australia Committee

ME-62, Ventilation and Air conditioning. It applies to evaporative air-conditioning devices

which cool air by the evaporation of water. It prescribes a basis for rating specified features of

evaporative air-conditioning equipment, and specifies the test procedures and equipment

applicable for rating an evaporative air conditioner. It also includes basic minimum

requirements for construction. The performance testing requirements are designed to evaluate:

Air flow

Evaporation efficiency

Sound power measurements

Electrical consumption

While the evaporation efficiency indicates how close the cooled air is to saturation point,

which is the maximum limit for direct evaporative air conditioners, it does not give a direct

indication of the cooling capacity or attempt to link it to the electricity consumption. Note that

the evaporation (saturation) efficiency is given as a percentage. It is also quoted as

evaporation effectiveness which is a fraction below 1. Typical evaporation efficiency values

are 70 - 85% (effectiveness 0.7- 0.85).

The Standard also includes information for evaluating a nominal rating for the evaluation of

the rated cooling performance for inlet dry and wet bulb temperatures of 38°C and 21°C

respectively and a room dry bulb temperature of 27.4°C.

The Standard contains a requirement that the electricity consumption of a particular unit

should be measured during the evaporation efficiency test. However, no energy rating is

available. The Standard also lacks requirements to evaluate the water consumption.

In addition, this Standard does not include requirements for evaluating the performance of

indirect or two stage evaporative air conditioners.

2.2 International regulations and standards

United States ANSI/ASHRAE Standard 133-2008: Method of Testing Direct Evaporative

Air Coolers

This Standard was prepared by the American Society for Heating, Refrigeration and Air

Conditioning Engineers (ASHRAE). It establishes a uniform test method for rating the

saturation effectiveness, airflow rate and total power of packaged and component direct

evaporative air coolers. Other parameters to be measured under equilibrium conditions are the

static pressure differential across the evaporative cooler, density of air and speed of rotation of

the fan. The Standard does require the measurement of flow rate of the supplied water and its

electrical conductivity as a measure of the water quality.

27

The Standard requires that the inlet plenum air dry-bulb temperature shall be 45oC maximum,

the wet-bulb temperature shall be 5oC minimum, and the difference between these two

temperatures shall be 11oC minimum during the testing period. It also requires that the

conductivity of the water supplied shall be between 350 and 3500 µS.

United States ANSI/ASHRAE Standard 143-2000: Method of Testing for Rating Indirect

Evaporative Coolers

This Standard was prepared by ASHRAE. It provides standard test methods and calculational

procedures for establishing the cooling capacities and power requirements for indirect

evaporative coolers. The indirect evaporative coolers can be either self-contained or

components of a packaged system. The parameters tested under steady-state conditions

include:

Air flow rates for primary and secondary airstreams

Dry-bulb and wet-bulb temperatures of both primary and secondary airstreams when

entering and leaving heat exchanger

Electrical consumption

However, the Standard does not include coolers using mechanical refrigeration or thermal

storage to cool the primary or secondary air streams. Also, it does not include coolers that dry

the primary or secondary airstreams. The Standard does not require the evaluation of water

consumption.

California Appliance Efficiency Regulations

The California Appliance Efficiency Regulations include a procedure for evaluating and

rating the energy performance of evaporative coolers. This is achieved by evaluating the

Evaporative Cooler Efficiency Ratio (ECER). ECER is evaluated by Eqn.6. The conditions

specified for the evaluation of ECER are intake dry and wet bulb temperatures of 32.8 and

20.6°C (91 and 69°F) respectively for testing the evaporation efficiency and assumed room

outlet air temperature of 26.7°C (80°F).

WQttttECER wbdbdbroom /)))(((.081 (6)

Where

roomt = room dry-bulb temperature, oC

dbt = outdoor dry-bulb temperature, oC

wbt = outdoor dry-bulb temperature, oC

= saturation effectiveness divided by 100

Q = air flow rate, cfm

W = total power, W

No water consumption requirements are included in the Regulations.

Iran Labelling Program

Iran is the only country that currently conducts a mandatory comparative labelling program

for energy consumption of evaporative air conditioners (see example of the label and rating,

Fig. 10 and Table 6). The label design is based on the European label concept but as a mirror

image with efficiency grades in numbers rather than letters (Persian script). It shows

efficiency grades from 1 (most efficient - the shortest bar, which appears in green on the

28

original label) down to 7 (least efficient - the longest bar, which appears as red). The aim of

the Iranian program is to encourage local manufacturers to improve the energy efficiency of

their products. Studies conducted in cooperation with manufacturers revealed that there are a

variety of design changes possible, such as the use of more efficient fans and motors, pad

density and improved water circulation rate. These changes would make a considerable

impact on energy consumption without requiring major investment. Hence the labelling

scheme was launched in 1999 to encourage these changes.

The scheme is run by the Iran Energy Efficiency Organisation. Being the first country to

introduce labelling and MEPS has meant that Iran has had to develop its own test methods

and rating levels. The units are rated using an EER (Energy Efficiency Ratio) measurement to

compare products. Thresholds are shown in Table 6. Promotion of the energy label is largely

done by manufacturers who have found it to be a useful marketing tool. The testing should

comply with the Iranian Test Standards No. 4910 and No. 4911, which uses the Australia

Standard 2913-2000 as their reference test standard. To the authors‘ knowledge, water

consumption evaluation has not been considered in this scheme.

It is evident from the above that current Australian Standards do not require the evaluation of

water and energy use in evaporative air conditions. A standard procedure for evaluating both

energy and water consumption of evaporative air coolers is proposed for inclusion in the

Standards.

Table 6: Energy Efficiency Thresholds for Iranian Energy Label (Iran Energy Efficiency Organisation).

Rating EER Value

1 EER≥ 65

2 58≤EER<65

3 50≤EER<58

4 42≤EER<50

5 34≤EER<42

6 26≤EER<34

7 EER<26

Figure 10: Example of the Iranian energy label (Iran Energy Efficiency Organisation).

29

2.3 Standard test conditions

Table 7 compares the conditions stipulated for rating evaporative air conditioners in the

Australian Standard and California Code of Regulations (Standards Australia, 2000 &

California Energy Commission, 1998) and those used in the Australian Standards (Standards

Australia/ Standards New Zealand, 1998) for testing refrigeration air conditioners.

Table 7: Comparison of Rating Temperatures (°C) for evaporative and refrigeration systems

Evaporative,

Australian Standards

Evaporative,

California Code

Vapour Compression,

Australian standards

Outdoor Dry Bulb

Temperature

38 32.8 35

Outdoor wet Bulb

Temperature

21 20.6 24

Indoor Dry Bulb

Temperature

27.4 26.7 27

2.4 Shortcomings of current standards

Both the current Australian Standard and other available international standards suffer from

particular shortcomings which stand in the way of their use for reliably evaluating energy use

in space cooling. In view of the relative lack of definition of many of the test parameters, it is

difficult to compare many of the test results which are currently being carried out by the

manufacturers to satisfy the current Standard requirements. The Australian Standard includes

a procedure for calculating the ―rated cooling performance‖ calculated at ―nominal

conditions‖. While the evaporation efficiency test specifies that the air entering the test

appliance shall have a dry bulb temperature between 30° and 40°C with a wet bulb depression

of between 14K and 18K, the Appendix describing the method for calculating the rated

cooling performance is only informative and sets the dry and wet bulb temperatures for

nominal rating at 38°C and 21°C respectively which are conditions of low humidity favouring

high evaporative air conditioner performance.

While the evaporation efficiency is a significant factor in determining the cooling capacity of

specific evaporative air conditioners, it is little affected by test conditions. Other available

standards for evaluating energy use of evaporative air conditioners use a fixed set of outdoor

air conditions for determining the rated energy performance. If one set of rating outdoor air

temperature and humidity conditions is specified, the energy efficiency parameter selected

will only be valid for these conditions. Keeping in mind the wide range of design

temperatures and humidities encountered in different Australian locations (listed in Table 1),

location specific values are necessary for rating the energy performance of evaporative air

conditioners.

30

3. Testing/Rating Method

3.1 Review of available energy consumption testing procedure/methodology

Apart from the many references in the literature declaring the fact the energy consumption of

evaporative coolers being 20-50% of conventional vapour compression cooling systems, little

could be found in the international literature on methodologies proposed or being used for

rating evaporative air conditioners and comparing them with vapour compression systems.

Furthermore, no voluntary labelling programs covering evaporative air conditioners or

comparative or endorsement labels that include both evaporative and vapour compression air

conditioners could be found.

3.2 Development of a test methodology

It is proposed that both energy and water consumption testing be carried out using a single

test facility. A test rig presented in Fig. 11 is proposed to implement the testing for rating both

the energy and water consumption under controlled simulated outdoor temperature and

humidity conditions. The test requirements and conditions are to supplement current

Australian Standards AS/NZS 2913-2000 for measurement and will require additional

facilities for strict control to simulate the rating outdoor design conditions and input water

quality.

The test must comply with the following conditions:

Preset air temperature and humidity to simulate rating conditions with variation

allowed within specified tolerances

Input water quality to simulate mains water salinity level (measured by electrical

conductivity) within specified tolerances

Test measurements of new product to be carried out after a minimum number of hours

of operation, which would be a standardised time period

The following parameters need to be measured during the test after steady conditions have

been reached at each speed setting, for the purpose of evaluating both water and energy

performance:

Inlet and outlet dry and wet bulb temperatures

Air supply rates at different speed settings subject to a standardised pressure drop to

allow for the ducting system.

Electrical power consumption by the fan, water circulation pump and control/remote

systems

Pressure drop across the cooling system

Inlet water quality

Total water consumption

Total water dumped/bled off

Sound output level

The main significant output parameters of significance to energy/comfort considerations will

be evaluated at the rating conditions:

Evaporation effectiveness

Rated energy efficiency ratio; and

Cooling capacity

31

This will be produced in conjunction with parameters to evaluate water consumption and

sound output level

Figure 11: Schematic diagram of the proposed test rig.

The test rig has 2 separate air flow streams to enable a number of different types of

evaporative cooling systems to be tested. Each of these air flow streams has a fan (on the left

of Figure 11) which is used to bring outside air in to the test rig. In order to simulate the

desired temperature and humidity corresponding to the design conditions of a particular

location, the air is first conditioned to the desired properties using a combination of cooling

coil, heaters and humidifiers. The cooling coil is used to dry (dehumidify) the air which can

then be heated using the heaters. The humidifier introduces the desired amount of water into

the air.

The test rig has a number of stations where the properties of air are measured, namely the

static pressure, dry bulb and wet bulb temperatures. The fans after the conditioning equipment

are used to control the air pressure at various locations throughout the test rig so that testing

can be conducted at different pressures to simulate ducting losses.

Each air stream has a nozzle-type device which is used to measure the air flow rate. There are

two locations where water flow is measured, at the inlet into the test unit and also where water

32

dumping or bleeding occurs. The difference between the two is the water consumed in

cooling/humidifying the air.

In the test rig there is also another heater and humidifier (on the right of figure 11) which can

be used to simulate the heat load in a building. The heaters simulate heat and the humidifier

simulates moisture addition from perspiration and other sources.

3.3 Proposed test conditions

While the authors are unaware of the reasons behind the selection of the inlet air temperature

and humidity for evaporative air conditioner testing and rating, it is advisable that they should

be aligned with the values accepted by the wider air conditioning community which are those

used for rating other air conditioning systems in table 7 above. It is therefore proposed that the

outdoor dry and wet bulb temperatures used in the rating test procedure be modified to be

aligned with those used in vapour compression testing. From previous experience, it is

anticipated that the proposed changes will have little impact on the evaporation efficiency and

other output parameters of the tests which are almost independent of the test conditions within

the range under consideration. Furthermore, the parameter proposed below for rating the

seasonal energy consumption, while location sensitive will be little affected by the rating

conditions used in the test.

3.4 Proposed parameter for rating energy performance

Keeping in mind the performance sensitivity of evaporative air conditioners to the outdoor

temperature and humidity, a new parameter is proposed for providing the energy rating of

evaporative air conditioners. The proposed parameter is based on the annual performance of a

particular unit in a specific location. Using the test results (air supply rate, total electrical

power consumption and evaporation effectiveness) which are insensitive to temperature and

humidity variations, the hourly cooling capacity S for a specific unit can be evaluated in a

particular location for all hours of the year when cooling is required (temperature above 27oC)

as described in section 1.5 above. Typical year hourly weather data from the Australian

Climate Data Bank (ACDB) can be used for this purpose. The data will also enable an

estimation of the total electrical energy consumed during the hours of cooling. This enable the

evaluation of a new performance parameters which takes into consideration the overall annual

performance in a specific location, namely the Seasonal Energy Efficiency ratio, SEER,

where

(7)

33

3.5 Application of the proposed testing and rating procedures to new

technologies

Section 1 of this report has highlighted the emergence of new products which have been

developed to improve the comfort provisions of evaporative air conditioners throughout the

year by controlling the moisture content of the supplied air, namely indirect and two stage

evaporative air conditioners. The test procedure and methodology proposed in the report for

evaluating the energy and water use of evaporative air conditioners can be equally used for

the new products as well as the conventional systems. The test rig shown in Fig. 11 includes a

secondary air supply loop which is necessary for the indirect evaporative systems.

34

4. Performance Evaluation Information

4.1 Development of information for rating/labelling

Although evaporative air conditioners have been shown to generally consume less electrical

power compared with those based on refrigeration principles, their operation is only possible

in regions of low humidity where the air produced can be used to provide thermal comfort

cooling. In addition to their low energy consumption, other positive factors for their use are

the provision of 100% outside air and the high air velocities which decrease the perceived

operative temperature. On the other hand, the high humidity level associated with evaporative

air conditioners reduces the comfort perception.

Considering the Australian context, the climatic conditions in most Australian population

concentrations, except the tropical and semi tropical regions in Northern Australia, are

suitable for using evaporative cooling for most days in the year. Using typical performance

characteristics and typical year weather data for particular locations (specifically, the hourly

dry and wet bulb temperatures), the number of hours in the year when cooling is required, and

the number of hours when evaporative cooling is ineffective has been evaluated. This is a

significant piece of information which can be specified for particular evaporative coolers once

they have been tested as detailed in section 3 above. The information will assist the

consumers in determining their cooling system purchasing choice as well as governments

around Australia in making policy decisions on future energy and water requirements for air

conditioning.

4.2 Proposed information for rating/labelling

Both consumers and regulators require specific information to describe the performance of

evaporative air conditioners. Standardised information is necessary so that consumers can

compare between different products in order to make the purchasing decision. The

information outlets may comprise the following:

1. Manufacturers‘/suppliers‘ product information available on their websites, product

information booklets and publicity material

2. Government or independent publications and websites such as the energy rating

website www.energyrating.gov.au and the WELS water rating website

3. Rating labels affixed on the products (mandatory or voluntary)

The previous sections of this report have shown that once a specific evaporative air

conditioner has been subjected to a standard test (as described in section 3), a number of key

parameters can be evaluated to describe its performance at a particular location. As the rated

evaporation effectiveness and power consumption are almost independent of the climatic

condition for a particular air delivery rate, these will enable the evaluation of the following

parameters for a particular system:

1. Its cooling capabilities and potential provision of thermal comfort through the following

parameters:

Cooling capacity at the location design conditions

Number of hours per year when the system is unable to provide thermal comfort or as

a percentage of hours when cooling is required. The provision of thermal comfort is

deemed achievable at a particular hour if the outlet temperature of the evaporative air

conditioner does not exceed 25°C.

35

2. Its daily and annual energy consumption and cost through:

Average daily electrical energy use for cooling at the design conditions of the specific

location

Annual energy consumption and cost of cooling at the specific location

Energy use per kW of cooling

3. Its maximum power demand and contribution to the grid peak demand

4. Its greenhouse gas emission per kW of cooling and total annual greenhouse gas emission

This information along with similar parameters for water consumption will provide useful

data to consumers at the purchase stage. It is also significant for industry in aiding

competition and product development data. Government agencies will use the data in policy

formulation and planning.

4.3 A parameter for rating the energy performance of evaporative air

conditioners

In addition to the parameters proposed above for informing the stakeholders on the energy

and water consumptions of evaporative air conditioners, a single rating tool is necessary for

rating the energy consumption of different evaporative conditioners. The rating parameter will

enable direct comparison of different models. In order to enable the making of informed

purchasing decisions, the parameter should enable direct comparison with the performance of

vapour compression air conditioners.

The seasonal Energy efficiency Ratio (SEER) as described in section 3.4 above is proposed.

This SEER value is location specific. However, it is comparable with the EER values quoted

for other cooling systems as the latter gives an indication of the cooling effect produced per

unit electrical energy consumption at the standard test conditions. It is worth mentioning in

this context that SEER values can be evaluated for other types of air conditioners and is in

deed used in some countries as a means of providing good estimates of annual energy

consumption. However, this would require performance evaluation at a number of test

conditions rather than a single rating condition in current use.

The current energy star rating methodology of air conditioners is directly based on the rated

EER value. As shown in Table 8, cooling star rating is 1 for an EER value of 2.75. The rating

increases by one star for each 0.5 increase in the EER. As the proposed test conditions for

evaporative air conditioners is the same as the current test conditions for refrigeration air

conditioners, the measured EER values of specific refrigeration and evaporative air

conditioners can be used for a quick comparison between 2 specific appliances being

considered for a particular application.

It is proposed that SEER be converted to equivalent rating of evaporative air conditioners

using the equations developed for rating other air conditioners. This will serve as a means of

indirectly comparing the energy performance of evaporative coolers with other systems. It

will also reflect the suitability of evaporative air conditioning for use in particular locations. It

must be stressed here that the proposed methodology will be entirely separate from the star

rating system in use for refrigeration systems. The proposed rating methodology will produce

star ratings of above 10 for evaporative air conditioners. However, the two methods give

direct comparisons of the effectiveness of using electrical energy to generate a unit of cooling.

36

Table 8: Relationship between the Energy Efficiency Ratio (EER) and star

rating of cooling appliances

STAR

RATING

COOLING

1 2 3 4 5 6 10

EER

2.75 3.25 3.75 4.25 4.75 5.25 7.25

4.4 Example of the calculation of SEER

Based on an evaporative cooler with an air volume flow rate of 9630 m3/hr, the total annual

cooling capacity of Adelaide based on the climatic data from the Australian Climate Data

Bank (ACDB) is given as 20442.5 kWh in Table 3. The total electrical consumption of the

same location is given as 684.4 kWh in Table 4. Therefore, the SEER (Eqn. 7) can be

computed as follows:

4.5 Procedure for evaluation of the rating of the energy, cooling capacity

and comfort performance parameters

Figure 12 shows the flow chart for the procedure for the evaluation of the rating of the energy,

cooling capacity and comfort performance parameters. It is observed that modelling these

performance parameters requires the three variables obtained from the test together with the

annual weather data of the particular location. Eight performance parameters are evaluated

from the modelling as shown in the figure. The performance evaluation modelling procedure

can be carried out using an Excel spreadsheet. An interactive computational tool has been

developed to evaluate the following performance parameters for Adelaide, Brisbane, Canberra,

Hobart, Melbourne, Perth and Sydney:

Cooling capacity at design condition (kW)

Total annual cooling capacity (kWhr)

Annual energy consumption (kWhr)

Average daily electrical energy used under design condition (kWhr)

Seasonal Energy Efficiency Ratio (SEER)

Number of hours when cooling is required

Number of hours per year when the system is unable to provide thermal comfort

(Outlet temperature >25°C) Percentage of hours when cooling is required but t

Percentage of hours per year when system cannot provide cooling (Outlet temperature

>25°C).

37

Figure 12: Flow chart for the procedure for the evaluation of the rating of the energy

performance parameters

Test

Test

Power Input

Volume flow rate

Saturation Efficiency

Cooling capacity at the location design conditions

Total annual cooling capacity

Number of hours of the year when cooling is required

Number of hours per year when the system is unable to provide

thermal comfort

Percentage of hours when cooling is required but the system is

unable to provide thermal comfort

Average daily electrical energy use for cooling at the design

conditions of the specific location

Annual energy consumption for cooling at the specific location

Seasonal Energy Efficiency ratio

Seasonal Energy Efficiency Ratio

Modelling

Weather

Data

38

5. Conclusions and recommendations The report has highlighted the current status, recent developments, challenges and features of

evaporative air conditions which are locally produced products. In order to fill the

information gap on their energy (and water) requirements, a standard test procedure is

proposed to enable the characterisation of different units. A number of parameters have been

proposed to enable assessment of their suitability and energy consumption in different

Australian locations. The Seasonal Energy Efficiency ratio is proposed as a single parameter

for defining the energy consumption of evaporative air conditioners and enabling comparison

with refrigeration cooling units. An interactive computational tool has been developed for

evaluating these performance parameters.

In order to implement the proposed testing/rating regime, the following steps are proposed:

1. Early consultation with manufacturers, suppliers, governments and users groups will

be an important step in progressing a labelling/rating system for energy and water use in

evaporative air conditioners. The consultative process need to consider the following issues:

Suitability of the proposed standard test methodology

Defining specific test conditions (dry and wet bulb temperatures, indoor

temperature, pad conditions, water conditions and static pressure drop)

Range of sizes of units to be subjected to testing/rating

Testing at different speed settings

Incorporation of thermostat setting in cooling calculations

The need to use the same test facility and procedures for testing/rating indirect

and two stage systems

Suitability and appropriateness of the proposed parameters for providing

rating/labelling information

Choice of Australian locations for evaluating the proposed rating/labelling

parameters

Suitability and appropriateness of the proposed location specific Seasonal Energy

Efficiency Ratio as the key energy rating parameter

Suitability and effectiveness of using the star rating relationship currently used for

refrigeration cooling system as a means for providing the equivalent star rating of

evaporative air conditioner

2. Once a consensus is reached on fixing the items listed above, a more detailed study to

develop a standard testing procedure, required testing facilities and methodology for

independent testing, rating/labelling of both water and energy use in evaporative air

conditioners is recommended as the next step for progressing the rating of these systems. This

should also incorporate modifications to the current testing standard in AS/NZS 2913-2000

Evaporative air conditioning equipment.

39

References AIRAH technical handbook (2007), The Australian Institute of Refrigeration, Air Conditioning

and Heating, Inc.

ANSI/ASHRAE Standard 143-2000 (2000), Method of Test for Rating Indirect Evaporative Coolers, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.,

Atlanta.

ANSI/ASHRAE Standard 133-2008 (2008), Method of Testing Direct Evaporative Coolers, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., Atlanta.

ASHRAE Handbook (2007), HVAC Applications, American Society of Heating, Refrigerating

and Air-Conditioning Engineers, Inc., Atlanta.

ASHRAE Handbook (2004), HVAC Systems and Equipment, American Society of Heating,

Refrigerating and Air-Conditioning Engineers, Inc., Atlanta.

Australian Bureau of Statistics (1988), National Energy Survey: Weekly Reticulated Energy and Appliance Usage Patterns by Season Households, Australia 1985-86. (cat no. 8218.0).

Australian Bureau of Statistics (2007), Environmental Issues: People’s Views and Practices (cat no. 4602.0). Available on:

http://www.abs.gov.au/AUSSTATS/[email protected]/DetailsPage/4602.0Mar%202007?OpenDocument.

Australian Bureau of Statistics (2008), Environmental Issues: Energy Use and Conservation (cat no. 4602.0.55.001). Available on:

http://www.abs.gov.au/AUSSTATS/[email protected]/DetailsPage/4602.0.55.001Mar%202008?OpenD

ocument.

American Society of Heating, Refrigerating and Air Conditioning engineers, 2001,

‗Method of Testing Direct Evaporative Air Coolers ANSI/ASHRAE Standard 133-2001’

American Society of Heating, Refrigerating and Air Conditioning engineers, 2000,

‗Method of Test for Rating Indirect Evaporative Air Coolers ANSI/ASHRAE Standard 143-

2000’

Bom, G.J. (1999), Evaporative air-conditioning, World Bank Publications.

California Energy Commission, 1998, ‗Appliance energy Regulations, California Code of

Regulations’, Title 20, CEC-400-2006-002.

California Energy Commission (2006), California Appliance Efficiency Regulations, CEC-400-

2006-002-REV2.

Energy Efficiency Strategies, 2006, ‗Status of Air Conditioners in Australia –Updated with

2005 data‘ report prepared for the National Appliance and Equipment Energy Efficiency

Committee.

40

Energy Efficient Strategies (2008), Regulatory Impact Statement for Revision to the Energy Labelling Algorithms and Revised MEPs levels and Other Requirements for Air Conditioners. Available on: http://www.energyrating.gov.au/library/details200809-ris-ac.html.

Energyconsult PTY Ltd, 2002 ‘Voluntary Energy Labelling Possibilities for Evaporative and

Refrigerative Air Conditioners’ Report no:2002/05, Final Report prepared for the Australian

Greenhouse Office

Heidarinejad, G., Bozorgmehr, M., Delfani, S. & Esmaeelian, J. (2009), Experimental Investigation of Two-stage Indirect/direct Evaporative Cooling System in Various Climatic Conditions, Building and Environment, doi:10.1016/j.buildenv.2009.02.017.

Iran Energy Efficiency Organisation, www.iraneeo.com.

Pescod, D., (1968), Unit Air Cooler using Plastic Heat Exchanger with Evaporatively Cooled Pads. Australian Refrigeration Air Conditioning and Heating, 22, 9, 22.

Pescod, D., (1979), A Heat Exchanger for Energy Savings in Air Conditioning Plant. ASHRAE,

Trans. 85, 2, 238.

Saman, W.Y., (1993), Developments in Evaporative and Desiccant Cooling Systems and their Potential Application in Australia. Proc. Australasian Heat and Mass Transfer Conference,

Brisbane.

Saman, W.Y, (1994), Energy Conscious Ventilation with Indirect Heating and Cooling for Better Air Quality. Proc Indoor Health and Comfort Seminar, The Australian Institute of

Refrigeration, Air Conditioning and Heating.

Saman, W. and Mudge, L. 2002, ‗Development, Implementation and Promotion of a

Scoresheet for Household Greenhouse Gas Reduction in South Australia, Final Report

submitted to the Australian Greenhouse Office, Sustainable Energy Centre, University of

South Australia.

Saman, W.Y, Bruno, F. (2008), Developing a Methodology for Rating Evaporative Air

Conditioners. Report Submitted to the Australian Evaporative Air conditioner Manufacturers

and to Australian State and Commonwealth Governments, March, 2008.

Saman, W.Y., and Kilsby, R., (1999), Energy Efficient Heating, Dehumidification and Cooling System. Proc OzTech99, Taiwan.

Saman, W.Y., Percy, A., Sardelis, P., and McNab J., (1995), A Comparison between a Conventional Heat Pump System and One Incorporating Heat Recovery/Evaporative Cooling. Proc International Symposium on Energy, Environment and Economics, University of

Melbourne.

Standards Australia (2000), Evaporative Air conditioning Equipment AS 2913-2000. Standards Australia/ Standards New Zealand, (1998), Performance of Electrical Appliances- Airconditioners and Heat Pumps, Part 1.1: Non-Ducted Airconditioners and Heat Pumps-Testing and Rating for Performance, AS/NZS 3823.1.1:1998’.

41

Wang, S.K., Lavan, Z., Kreith, F., & Norton, P. (2000), Air Conditioning and Refrigeration Engineering, CRC Press.

www.energyrating.gov.au

http://www.wapa.gov/es/pubs/esb/2005/june/jun057.htm

http://www.coolerado.com/news/articles/

http://www.climatewizard.com.au/pdf/Climate%20Wizard%20brochure%200909.pdf

http://www.climatewizard.com.au/

http://www.homeheat.com.au/pdf/fact.pdf

42

Appendix 1: Available Evaporative Air Conditioners in Australia & Their Key Specifications

Brand Model Type

Motor

Power

input

(W)

Cooling

power

(kW)

Water bleeding

system

Fan

type

Supply

flow rate

(m3/h)

Pad type Control system Evaporation

efficiency

AIR GROUP AUSTRALIA

CoolBreeze

D095

residential

ducted

(Heritage)

600 7

Water Manager

(timed drain off

system)

Variable

speed

axial fan

7500

100mm

Celdek pads

(larger

model)

wall-mounted controller

with variable speed fan

control/thermostat control

(optional remote control)

D125 600 9 10000

D160 750 11 12500

D195 1000 13 15000

D230 1000 15 18000

D255 1000 17 19500

C125 residential

ducted

(Cascade)

600 9 10000 100mm

Celdek pads

(larger

model)

wall-mounted controller

with variable speed fan

control/thermostat control

(optional remote control)

C160 750 11 12500

C205 1000 14.5 16000

C240 1000 16.5 18500

CommercialAir

FD400 commercial

twin fan

unit

2×750

Water Manager

(timed drain off

system)

Variable

speed

axial fan

28000 Celdek pads

wall-mounted controller

with variable speed fan

control

FD500 2×1000 36000

FD095 commercial

unit, roof

mounted

for ducted

& plenum

applications

600

Variable

speed

axial fan

7500

Celdek pads

wall-mounted controller

with variable speed fan

control

FD125 600 10000

FD160 750 12500

FD195 1000 15000

FD230 1000 18000

FD255 1000 19500

FT095 commercial

top

discharge

unit, floor

mounted

600

Variable

speed

axial fan

7500

Celdek pads

wall-mounted controller

with variable speed fan

control

FT125 600 10000

FT160 750 12500

FT195 1000 15000

FT230 1000 18000

FT255 1000 19500

43

Appendix 1 (cont...)

Brand Model Type

Motor

Power

input

(W)

Cooling

power

(kW)

Water bleeding

system Fan type

Supply

flow rate

(m3/h)

Pad type Control system Evaporation

efficiency

AIR GROUP AUSTRALIA

CommercialAir

S240

commercial

side

discharge

unit,

wall/floor

mounted

1000

Water Manager

(timed drain off

system)

Axial fan 18500 100mm

Celdek pads variable speed fan control

S100

commercial,

wall

mounted

600 Axial fan 18500 75mm

Celdek pads variable speed fan control

FM240 mobile 1000 Axial fan 18500 100mm

Celdek pads variable speed fan control

CARRIER

Brivis Contour

L13

residential

ducted

6

Axial fan

Celdek pads

Wall-mounted controller

with thermostat control

L23 8.9

L33 12.4

L43 14

L53 15.8

L63 16.7

Brivis Profiler

P23

residential

ducted

8.6 AutoRefresh

water

management

system (periodic

drain off system)

Axial fan

Celdek pads

Wall-mounted controller

with thermostat control

P33 10.9

P43 13.2

P53 14.7

P63 16

Brivis Advance

F23D

residential

ducted

8.6 AutoRefresh

water

management

system (periodic

drain off system)

Axial fan

Celdek pads

F33D 11

F43D 13

F53D 15.4

44

Appendix 1 (cont...)

Brand Model Type

Motor

Power

input

(W)

Water

bleeding

system

Fan

type

Supply

flow

rate

(m3/h)

Pad

type

Control

system

Water

Pump

Type

Water

Pump

Power

(W)

Controller

Type

Controller

Power

(W)

CLIMATE TECHNOLOGY

Celair

Profile500

domestic

600 "Dialflo":

constant

bleeding

rate

(optional

dump

valve)

Low

noise

axial

fan

9326

Celdek

® filter

pads

Wall

mounted

thermostatic

control

Fasco 105.6 Tytronics 24

Profile600 750 11810 Fasco 105.6 Tytronics 24

Profile750 750 13810 Fasco 105.6 Tytronics 24

Profile850 750 15986 Fasco 105.6 Tytronics 24

Bonaire

Integra

VSS50

Residential

ducted

970

Bonaire

Aquamiser

Low

noise

axial

fan

9085

Celdek

® filter

pads

Remote

controller &

touch pad

controller

with

thermostat

control

Fasco 105.6 PNE 24

VSS55 970 10834 Fasco 105.6 PNE 24

VSM60 1040 12584 Fasco 105.6 PNE 24

VSM65 1040 14677 Fasco 105.6 PNE 24

VSL70 1540 16211 Fasco 105.6 PNE 24

VSL75 1540 17766 Fasco 105.6 PNE 24

Bonaire

Summer

Breeze

SBS50 970 9085

variable

speed control

& thermostat

control

Fasco 105.6 PNE 24

SBS55 970 10834 Fasco 105.6 PNE 24

SBM60 1040 12584 Fasco 105.6 PNE 24

SBM65 1040 14677 Fasco 105.6 PNE 24

SBL70 1540 16211 Fasco 105.6 PNE 24

SBL75 1540 17766 Fasco 105.6 PNE 24

45

Appendix 1 (cont...)

Brand Model Type

Motor

Power

input

(W)

Water

bleeding

system

Fan

type

Supply

flow

rate

(m3/h)

Pad

type

Control

system

Water

Pump

Type

Water

Pump

Power

(W)

Controller

Type

Controller

Power

(W)

CLIMATE TECHNOLOGY

Bonaire

Durango WEAC628

Window-

mounted 250

Constant

bleed

3 speed

axial

fan

4500

Celdek

filter

pads

3 speed

control Fasco 52.8 Switch 24

Bonaire

B&C

B18

Commercial

ducted

750 "Dialflo":

constant

bleeding

rate

(optional

dump

valve)

centrifu

gal fan

with 2

speed

motor

9360

Celdek

®/Aspe

n

Wall-

mounted 2

speed motor

control

Fasco 105.6 Switch 24

B23 750 11484 Fasco 105.6 Switch 24

B33 1500 14040 Fasco 105.6 Switch 24

B36 1500 14583 Fasco 105.6 Switch 24

700C 2200 19798 Fasco 136.8 Switch 24

Bonaire Seasonmak

er DF

commercial,

window,wall

-mounted

425 "Dialflo"

direct

dive

dual fan

13300

Celdek

®

100mm

filter

pads

variable

speed control Fasco 105.6 Tytronics 24

46

Appendix 1 (cont...)

Brand Model Type

Nominal

Input

Power (W)

(motor /

controller /

pump)

Nominal

Motor

Shaft

Power

(W)

Cooling

Effect

(kW)

Water bleeding

system Fan type

Supply

flow

rate

(m3/h)

Pad type Control

system

Evaporation

efficiency

(%) (nom)

SEELEY INTERNATIONAL

Coolair

CPL450

Residential

ducted

710 340 7.3

Standard bleed

system

(optional

WATERmanagerTM

system)

Axial fan

6030

75 and 90

mm thick

Chillcel®

pads

Wall

mounted

Thermostat

control,

variable

speed

induction

motor

85 to 90

CPL700 700 430 9.1 6160 85 to 90

CPL850 1040 600 11.5 8880 85 to 90

CPL1100 1170 750 14.1 9630 85 to 90

Braemar

LCB250

Residential

ducted

540 360 8

WATERmanagerTM

system Axial fan

5200

90 mm

thick

Chillcel®

pads

Wall

mounted

Thermostat

control,

variable

speed

induction

motor

85 to 90

LCB350 850 500 9.5 6800 85 to 90

LCB450 865 700 12.3 7880 85 to 90

LCB550 1340 930 14.7 10560 85 to 90

Breezair

EXH130

Residential

ducted

850 500 8.4

WATERmanagerTM

system or bleed

system

Ultra quiet

centrifugal

fan (super

efficient

Hushpower

motor)

5630

90 and

100mm

thick

Chillcel®

pads

Wall

mounted

Thermostat

control or RF

Remote

Thermostat,

Inverter

Drive motor

85 to 90

EXH150 860 550 9.8 7000 85 to 90

EXH170 1350 750 12.6 8350 85 to 90

EXH190 1740 1100 14.4 9300 85 to 90

EXH210 2140 1500 15.5 10030 85 to 90

EXH215 2110 1500 15.4 10100 85 to 90

47

Appendix 2: Raw Air Conditioner Data in Figs 6 & 7 (ABS data)

NSW Vic. Qld SA WA Tas. NT(b) ACT Aust.

Mar-08 Total No. of Air Conditioners ('000) 1579.0 1428.3 1043.4 550.2 661.9 71.5 56.6 80.0 5470.9

Penetration 66.4

Proportion (%)

Reverse cycle 77.7 41.9 70.2 59.4 52.0 96.1 21.3 56.3 61.3

Cooling only 8.5 28.4 21.1 13.2 13.5 0.0 58.7 0.0 17.6

Evaporative 11.6 27.1 4.4 26.2 33.6 2.7 17.5 32.3 18.6

Refrigerated 86.2 70.3 91.3 72.6 65.5 96.1 80.0 56.3 78.9

No.('000)

Evaporative 183.2 387.1 45.9 144.2 222.4 1.9 9.9 25.8 1017.6

Refrigerated 1361.1 1004.1 952.6 399.4 433.5 68.7 45.3 45.0 4316.5

Mar-05 Total No. of Air Conditioners('000) 1391.2 1152.1 886.2 541.0 542.5 37.7 50.3 60.0 4661.0

Penetration 59.4

Proportion (%)

Reverse cycle 78.0 36.3 61.2 53.4 41.6 90.8 16.2 59.1 56.6

Cooling only 7.6 29.4 26.6 16.5 17.8 2.0 65.1 11.1 19.4

Evaporative 12.7 31.3 9.8 29.4 39.1 6.7 17.1 28.7 22.0

Refrigerated 85.6 65.7 87.8 69.9 59.4 92.8 81.3 70.2 76.0

No.('000)

Evaporative 176.7 360.6 86.8 159.1 212.1 2.5 8.6 17.2 1025.4

Refrigerated 1190.9 756.9 778.1 378.2 322.2 35.0 40.9 42.1 3542.4

Mar-02 Total No. of Air Conditioners ('000) 1074.7 972.4 551.1 487.9 444.4 19.5 48.8 35.7 3634.6

Penetration 48.6

Proportion (%)

Reverse cycle 71.4 30.3 47.7 50.5 35.6 93.6 9.2 54.3 48.8

Cooling only 12.5 35.7 37.7 19.8 23.7 0.0 70.8 15.9 25.6

Evaporative 12.6 29.7 11.8 29.2 39.1 6.4 18.5 27.6 22.7

Refrigerated 83.9 66.0 85.4 70.3 59.3 93.6 80.0 70.2 74.4

No.('000)

48

Appendix 2 (Cont…)

Evaporative 135.4 288.8 65.0 142.5 173.8 1.2 9.0 9.9 825.1

Refrigerated 901.7 641.8 470.6 343.0 263.5 18.3 39.0 25.1 2704.1

Mar-99 Total No. of Air Conditioners('000) 659.2 757.8 330.3 329.1 324.9 4.7 43.6 23.5 2473.0

Penetration 34.7

Proportion (%)

Reverse cycle 59.4 30.3 23.5 35.4 23.9 53.7 4.3 56.4 36.8

Cooling only 16.6 40.8 49.7 27.6 27.2 19.0 77.2 12.2 32.3

Evaporative 20.8 24.3 20.5 36.0 47.8 15.4 17.6 28.7 27.4

Refrigerated 76.0 71.1 73.2 63.0 51.1 72.7 81.5 68.6 69.1

No.('000)

Evaporative 137.1 184.1 67.7 118.5 155.3 0.7 7.7 6.7 677.6

Refrigerative 501.0 538.8 241.8 207.3 166.0 3.4 35.5 16.1 1708.8

Mar-94 Total No. of Air Conditioners('000) 664.7 593.5 201.2 349.1 217.0 4.3 35.3 17.3 2082.4

Penetration 32.5

Proportion (%)

Reverse cycle 67.5 41.6 36.6 52.9 33.2 51.5 15.0 50.7 50.0

Cooling only 14.2 36.7 39.1 23.4 33.3 8.9 63.3 13.6 27.4

Evaporative 16.1 16.8 18.9 23.1 30.3 31.2 20.0 34.6 19.5

Refrigerated 81.7 78.3 75.7 76.3 66.5 60.4 78.3 64.3 77.4

No.('000)

Evaporative 107.0 99.7 38.0 80.6 65.8 1.3 7.1 6.0 406.1

Refrigerative 543.1 464.7 152.3 266.4 144.3 2.6 27.6 11.1 1611.8

49

Appendix 3: Energy Consumption in a Typical Adelaide Hot Day

ACAD-BSG 18th of Feb.

Time

Dry-bulb temp (°C)

Wet-bulb temp (°C)

Entering air

humidity ratio

(g/kg)

Leaving air dry-

bulb temp (°C)

Cooling capacity for various air flow

rate (kW) EER for various air flow rate (-)

Electricity consumed for

various air flow rate (kW)

9360 16000 9360 16000 9360 16000

1 26.8 17.2 8.31 18.6

2 27 16.7 7.63 18.2

3 26.9 16.1 6.98 17.7

4 26.7 15.5 6.38 17.2

5 26.7 15.1 5.94 16.8

6 27.2 15 5.62 16.8 32.5 55.5 40.1 52.4 0.81 1.06

7 28 15.4 5.74 17.3 31.0 53.0 38.3 50.0 0.81 1.06

8 29.2 15.8 5.70 17.8 29.4 50.2 36.2 47.3 0.81 1.06

9 30.5 16.5 5.97 18.6 26.8 45.9 33.1 43.3 0.81 1.06

10 31.9 17.1 6.10 19.3 24.5 41.9 30.3 39.6 0.81 1.06

11 33.1 17.7 6.32 20.0 22.3 38.2 27.6 36.0 0.81 1.06

12 34 18.4 6.81 20.7 20.0 34.2 24.7 32.3 0.81 1.06

13 34.8 19.1 7.37 21.5 17.7 30.3 21.9 28.6 0.81 1.06

14 35.5 19.7 7.86 22.1 15.8 26.9 19.4 25.4 0.81 1.06

15 36.2 20.1 8.10 22.5 14.3 24.5 17.7 23.1 0.81 1.06

16 36.6 19.9 7.67 22.4 14.7 25.1 18.1 23.7 0.81 1.06

17 36.2 19.4 7.18 21.9 16.2 27.7 20.0 26.2 0.81 1.06

18 34.8 18.5 6.61 20.9 19.3 33.1 23.9 31.2 0.81 1.06

19 32.8 17.6 6.32 19.9 22.7 38.9 28.1 36.7 0.81 1.06

20 30.9 16.8 6.15 18.9 25.8 44.2 31.9 41.7 0.81 1.06

21 29.5 16.3 6.14 18.3 27.9 47.6 34.4 44.9 0.81 1.06

22 28.6 16.1 6.28 18.0 28.8 49.3 35.6 46.5 0.81 1.06

23 28.2 16.3 6.68 18.1 28.5 48.7 35.2 45.9 0.81 1.06

24 28.2 16.7 7.14 18.4 27.4 46.8 33.8 44.2 0.81 1.06

Total (kWh) 445.8 762.0 550.3 718.9 15.4 20.1

Average (kW) 23.5 40.1 29.0 37.8 0.81 1.06

50

Appendix 3 (Cont…)

ACDB-ADEL 18th of Feb.

Time

Dry-bulb temp (°C)

Wet-bulb temp (°C)

Entering air

humidity ratio

(g/kg)

Leaving air dry-

bulb temp (°C)

Cooling capacity for various air flow

rate (kW) EER for various air flow rate (-)

Electricity consumed for

various air flow rate (kW)

9360 16000 9360 16000 9360 16000

1 21.7 9.1 15740.00 11.0

2 21 9.6 15310.00 11.3

3 20.6 10.1 14850.00 11.7

4 20.1 11.2 14750.00 12.5

5 20.1 12 14650.00 13.2

6 20.6 12.6 14455.00 13.8

7 21.2 13.2 14955.00 14.4

8 22.5 13.7 15375.00 15.0

9 23.9 14.3 16395.00 15.7

10 26.3 14.8 16820.00 16.5

11 28.7 15.5 17615.00 17.5 30.4 52.0 37.5 49.0 0.81 1.06

12 31.3 15.9 18535.00 18.2 28.1 48.0 34.7 45.3 0.81 1.06

13 33.2 17.1 19130.00 19.5 23.9 40.9 29.5 38.6 0.81 1.06

14 35 18 19620.00 20.6 20.6 35.2 25.4 33.2 0.81 1.06

15 35.8 19.5 19340.00 21.9 16.2 27.6 19.9 26.0 0.81 1.06

16 36.8 19.2 19920.00 21.8 16.5 28.2 20.4 26.6 0.81 1.06

17 36.7 19.5 19730.00 22.1 15.7 26.9 19.4 25.3 0.81 1.06

18 36.9 18.7 20180.00 21.4 17.8 30.4 22.0 28.7 0.81 1.06

19 34.7 19.2 18990.00 21.5 17.5 29.9 21.6 28.2 0.81 1.06

20 33.1 18.8 18485.00 20.9 19.3 33.1 23.9 31.2 0.81 1.06

21 30.2 18.3 17165.00 20.1 22.1 37.8 27.3 35.6 0.81 1.06

22 29.5 17.7 17280.00 19.5 24.1 41.1 29.7 38.8 0.81 1.06

23 27.7 17.2 16595.00 18.8 26.3 44.9 32.4 42.4 0.81 1.06

24 26.5 17.2 16300.00 18.6

Total (kWh) 278.4 476.0 343.7 449.0 10.5 13.8

Average (kW) 21.4 36.6 26.4 34.5 0.81 1.06

51

Appendix 4: Energy Consumption in a Typical Adelaide Summer Day

ACAD-BSG 12th of Dec.

Time

Dry-bulb temp (°C)

Wet-bulb temp (°C)

Entering air

humidity ratio

(g/kg)

Leaving air dry-

bulb temp (°C)

Cooling capacity for various air flow

rate (kW) EER for various air flow rate (-)

Electricity consumed for

various air flow rate (kW)

9360 16000 9360 16000 9360 16000

1 15.8 13.9 9.12 14.2

2 15 13.6 9.13 13.8

3 14 13.1 9.02 13.2

4 13.4 12.5 8.66 12.6

5 13.6 12.1 8.17 12.3

6 15.2 12.2 7.61 12.7

7 17.8 13 7.35 13.7

8 21 14.2 7.30 15.2

9 24.4 15.6 7.44 16.9

10 27.6 16.8 7.50 18.4 27.4 46.9 33.8 44.2 0.81 1.06

11 30.0 17.8 7.71 19.6 23.5 40.3 29.1 38.0 0.81 1.06

12 31.4 18.6 8.13 20.5 20.7 35.4 25.6 33.4 0.81 1.06

13 32.0 19.1 8.52 21.0 19.1 32.6 23.5 30.7 0.81 1.06

14 32.0 19.4 8.91 21.3 18.2 31.2 22.5 29.4 0.81 1.06

15 31.7 19.3 8.90 21.2 18.7 31.9 23.0 30.1 0.81 1.06

16 31.1 18.9 8.63 20.7 20.0 34.2 24.7 32.3 0.81 1.06

17 30.3 18.2 8.08 20.0 22.3 38.1 27.6 36.0 0.81 1.06

18 29.4 17.5 7.60 19.3 24.6 42.1 30.4 39.7 0.81 1.06

19 28.2 16.9 7.37 18.6 26.9 45.9 33.2 43.3 0.81 1.06

20 26.7 16.5 7.52 18.0

21 24.8 16.3 8.07 17.6

22 22.9 16 8.51 17.0

23 21.5 15.7 8.74 16.6

24 20.9 15.2 8.43 16.1

Total (kWh) 221.5 378.6 273.4 357.2 8.1 10.6

Average (kW) 22.1 37.9 27.3 35.7 0.81 1.06

52

Appendix 4 (Cont…)

ACDB-ADEL 7th of Dec.

Time

Dry-bulb temp (°C)

Wet-bulb temp (°C)

Entering air

humidity ratio

(g/kg)

Leaving air dry-

bulb temp (°C)

Cooling capacity for various air flow

rate (kW) EER for various air flow rate (-)

Electricity consumed for

various air flow rate (kW)

9360 16000 9360 16200 9360 16000

1 22.2 14.6 7.24 15.7

2 21.6 14.2 7.05 15.3

3 20.8 13.8 6.95 14.9

4 20.7 13.7 6.89 14.8

5 20.6 13.6 6.83 14.7

6 21 13.3 6.35 14.5

7 21.5 13.8 6.67 15.0

8 22.6 14.1 6.53 15.4

9 24.3 15 6.81 16.4

10 26 15.2 6.34 16.8

11 27.9 15.8 6.23 17.6 30.0 51.3 37.0 48.4 0.81 1.06

12 29.5 16.6 6.49 18.5 27.0 46.2 33.4 43.6 0.81 1.06

13 31.2 17 6.26 19.1 25.1 43.0 31.0 40.5 0.81 1.06

14 32.2 17.4 6.33 19.6 23.6 40.3 29.1 38.0 0.81 1.06

15 32.6 17 5.69 19.3 24.5 41.8 30.2 39.5 0.81 1.06

16 32.5 17.7 6.57 19.9 22.6 38.7 27.9 36.5 0.81 1.06

17 31.8 17.6 6.73 19.7 23.2 39.7 28.7 37.5 0.81 1.06

18 31.4 18.2 7.63 20.2 21.8 37.2 26.9 35.1 0.81 1.06

19 29.7 17.1 7.00 19.0 25.6 43.7 31.6 41.3 0.81 1.06

20 28.6 16.7 6.98 18.5 27.2 46.5 33.6 43.9 0.81 1.06

21 26.6 15.5 6.42 17.2

22 26.8 15.6 6.45 17.3

23 26.2 14.9 5.92 16.6

24 26.5 14.5 5.37 16.3

Total (kWh) 250.7 428.5 309.4 404.2 8.1 10.6

Average (kW) 25.1 42.8 30.9 40.4 0.81 1.06

53

Appendix 5: Industry Contact List

The authors acknowledge the cooperation of the major evaporative air conditioning system

manufacturers listed below in providing technical specifications of their products and additional

information which was included in the report. The information was gathered from the companies‘

websites and directly through the contact persons listed below:

1. Air Group Australia

Website: http://www.airgroup.com.au/ Contact Person: Mr Michael Woodhouse E-mail: [email protected] Telephone: +61 8 9218 8888

2. Seeley International Website: http://www.seeley.com.au/ Contact Person: Mr Paul Schwarz E-mail: [email protected] Telephone: +61 8 8275 3265

3. Climate Technologies Website: http://www.climatetechnologies.com.au Contact Person: Mr Richard Calaby E-mail: [email protected] Telephone: +61 8 8307 5100

4. Carrier Website: http://www.brivis.com.au Contact Person: Mr Theo Karamanis E-mail: [email protected]

54

Appendix 6: Glossary of terms

Air change: the replacement of a quantity of air in a volume within a given period of time. This

is expressed in number of changes per hour. If a house has 1 air change per hour, all the air in the

house will be replaced in a 1-hour period.

Air change per hour (ach): a unit that denotes the number of times a house exchanges its entire

volume of air with outside air in an hour.

Air Flow: Measures the flow of air, often in CFMs. This should be carefully balanced to ensure

maximum cooling efficiency and optimal operation.

Air, ambient: surrounding air.

Air, saturated: moist air in which the partial pressure of water vapour equals the vapour

pressure of water at the existing temperature. This occurs when dry air and saturated water

vapour co-exist at the same dry-bulb temperature.

Air, standard: dry air at a pressure of 101.325 kPa at a temperature of exactly 20 °C. Under

these conditions, the density is 1.2041 kg/m3.

ASHRAE: The American Society of Heating Air Conditioning and Refrigeration Engineers.

Bleed Rate: The flow rate of water leaving the evaporative cooler sump, and which is replaced

with cleaner inlet water. Used to control the build-up of dust and minerals in the sump water.

CFM: Cubic feet per minute. Typical English measurement for the flow rate from a fan.

Collector, solar: a device for capturing solar energy, ranging from ordinary windows to

complex mechanical devices.

Combustion air: the air required to provide adequate oxygen for fuel burning appliances in the

building. The term ‗combustion air‘ is often used to refer to the total air requirement of a fuel

burning appliance including both air to support the combustion process and air to provide

chimney draft (dilution air).

Conditioned space: Space within a building which is provided with positive heat and/or cool

supply, or which has heated and/or cooled air or surfaces, or where required, with humidification

or dehumidification means, so as to be capable of maintaining a space condition falling within

the comfort zone set forth in the ASHRAE Handbooks.

Conductivity: the quantity of heat that will flow through one square metre of material, one

Metre thick, in one second, when there is a temperature difference of 1ºC between its surfaces.

Cooling Capacity: A measure of the ability of a unit to remove heat from an enclosed space.

COP: Coefficient of Performance of a heat pump means the ratio of the rate of useful heat

output delivered by the complete heat pump unit (exclusive of supplementary heating) to the

corresponding rate of energy input, in consistent units and under operating conditions.

Cooling Pads: Otherwise known as cool media. Pads that are found in an evaporative cooler;

water is directed onto these pads and fresh, outside air is pulled through the moist pads where it

is cooled by evaporation and circulated through an area.

Density: the mass of a substance, expressed in kilograms per cubic metre.

Design conditions: Specified environmental conditions, such as temperature and light intensity,

required to be produced and maintained by a system and under which the system must operate.

Direct radiation: the component of solar radiation that comes directly from the sun without

being diffused or reflected.

Dry bulb temperature: the temperature of a gas of mixture or gases indicated by an accurate

thermometer after correction for radiation.

Duct: A main trunk or branch round or rectangular tube, normally installed for air distribution of

heating and/or cooling air conditioning systems and which depends on a blower for air

circulation.

Ducted system: A ducted system is one that provides cooling to multiple rooms through a series

of ducts, which are usually installed in the roof.

55

Energy: The capacity for doing work taking a number of forms that may be transformed from

one into another, such as thermal (heat), mechanical (work), electrical and chemical in

customary units, measured in kilowatt-hours (kWh) or British thermal units (Btu).

Energy efficiency: The more efficient use of energy in order to reduce economic costs and

environmental impacts. Using less energy/electricity to perform the same function.

Energy efficiency Ratio (EER): The ratio of net equipment cooling capacity in Btu/h to total

rate of electric input in watts (W) under designated operating conditions. If the output capacity in

Btu/h is converted to watts (to create consistent units) the result is equal to the cooling COP

(EER X 3.41 = COP.)

Energy Star: Energy Star qualified appliances and air conditioners meet strict energy efficiency

guidelines set by the EPA and the U.S. Department of Energy and use at least 10% less energy

than conventional models.

Evaporation: phase change of a material from liquid to vapour at a temperature below the

boiling point of the liquid. Cooling occurs during the process of evaporation.

Evaporative Air-cooling: Lowering of the dry-bulb temperature as air moves over a water

surface.

Evaporative cooling: A heat removal process in which water vapour is added to air, increasing

its humidity while lowering its temperature. The total amount of heat in the air stays constant,

but is transferred from sensible heat in the air to latent heat in the moisture. In the process of

changing from liquid to vapour (evaporating), the water must absorb large amount of heat.

Evaporative cooling, Direct: a cooling process where the warm and dry air moves through a

wetted medium to evaporate moisture in the air. The cool humid air is then used to cool a place.

Evaporative cooling, Indirect: a cooling process where the evaporative process is remote from

the conditioned space. The cooled air is then used to lower the temperature of the building

surface, such as in a roof spray, or is passed through a heat exchanger to cool indoor air. The

indirect process has the advantage of lowering temperatures without adding humidity to the air,

thus extending the climate conditions and regions in which evaporate cooling is effective.

Geothermal: Literally, the heat of the earth. Where this heat occurs close to the earth's surface,

and is able to maintain a temperature in the surrounding rock or water at or above 150 degrees C,

it may be tapped to drive steam turbines.

Heat exchanger: a device usually consisting of a coiled arrangement of metal tubing used to

transfer heat through the tube walls from one fluid to another.

Heat pump: a thermodynamic device that transfers heat from one medium to another; the first

medium cools while the second warms up.

Human thermal comfort: Human thermal comfort is defined by ASHRAE as the state of mind

that expresses satisfaction with the surrounding environment (ASHRAE Standard 55).

Humidity: water vapour within a given space.

HVAC: mechanical system for heating, ventilating and air-conditioning that controls

temperature, humidity, and air quality.

Inverter: An "inverter" system is one with a variable speed compressor. This means that the air

conditioner can adjust its power output to suit the amount of cooling required at the time, which

usually results in an energy saving.

Kilowatt (kW): A kilowatt (abbreviation: kW) is 1000 watts and is a measure of cooling

capacity. It is also a measure of electrical input.

Kilowatt hour (kWh): A kilowatt hour (abbreviation: kWh) is the common unit of measure for

electrical energy consumption over time.

Multi-split system: A multi-split system is a split system that has a single outdoor unit

connected to multiple indoor units. It is possible to operate these systems independent of each

other or at the same time. These systems are best suited to cooling multiple rooms.

56

Portable air conditioner: Portable air conditioners are usually small in capacity, and may be

either refrigerated or evaporative. Normally the only installation they require is to be plugged

into an electrical outlet - if this is the case, they can be used without needing a licensed

contractor to install them. Some portable air conditioners may require hoses to be run to an

outside space (typically through a window) for water to drain and/or for heat to escape, as a

result they may not be suited to all applications.

Pressure: the normal force exerted by a homogenous liquid or gas, per unit area, on the wall of

container.

Pressure difference: the difference in pressure between the volume of air enclosed by the

building envelope and the air surrounding the envelope.

Psychrometric Chart: Graphic representation of the properties of moist air. Gives the readings

of DB, WB, and dew point temperatures, enthalpy, specific volume, RH, and water vapour

content. Enables one to graphically see cause and effect when the quality of air is changed.

Refrigerant: The working fluid in a vapour compression refrigerated air-conditioner.

Refrigerated system: A refrigerated system uses a refrigerant to take heat from the indoor space

and reject it outside.

Relative humidity: the percentage of water vapour in the atmosphere relative to the maximum

amount of water vapour that can be held by the air at a given temperature.

Reverse cycle: A reverse cycle system is one that can change modes to provide either heating or

cooling.

Saturation Effectiveness: A ratio of the change in dry-bulb temperature divided by the

difference between the outside air dry-bulb and the wet-bulb temperature. Used to predict the

discharge performance of an evaporative air cooler.

Seasonal Energy Efficiency Ratio, SEER: Air conditioners are given a SEER rating by the

industry. The value represents the average cooling output per unit input electrical energy

consumed during a cooling season.The higher the SEER rating, the greater the efficiency. An air

conditioning unit that has a rating of SEER 10 is 25% more efficient than one with a rating of 8.0.

Specific heat: a measure of the ability of a material to store heat. Specifically, the quantity of

heat required to raise the temperature of unit mass of a substance by one degree. (kJ/kg °C ).

Vapour Compression: Mechanical refrigeration that uses a refrigerant i.e. chilled water or

direct expansion (DX) of the refrigerant working fluid.

Variable Speed Drive (VSD): A device which when added to a device like a centrifugal fan or a

pump, can control the speed and output of the device. Variable speed drives are often referred to

as variable frequency drive (VFD) which is a common method of controlling fan speed.

Ventilation: The process of supplying or removing air by natural or mechanical means to or

from any space. Such air may or may not have been conditioned.

Ventilation (natural): air flow through and within a space stimulated by either the distribution

of pressure gradients around a building, or thermal forces caused by temperature gradients

between indoor and outdoor air.

Watt (W): a measure of power commonly used to express heat loss or heat gain, or to specify

electrical equipment. It is the power required to produce energy at the rate of one joule per

second.

Wet-bulb temperature: the air temperature measured using a thermometer with a wetted bulb

moved rapidly through the air to promote evaporation. The evaporating moisture and changing

phase lowers the temperature measured relative to that measured with a dry bulb. Wet bulb

temperature accounts for the effects of moisture in the air. It can be used along with the dry-bulb

temperature on a psychrometric chart to determine relative humidity.