"3ffcif ct'~OI E>~?JIOII ta~t4) tad;;fOl f@aldt UTrAI{ DAKSIiIN HAln'AfiA BLlU V'rrRA.N NIGAM Specification No. CSC-XX-R-II/DH/UH/P&D/2011-2012 TECHNICAL SPECIFICATION FOR 33 KV Control & Realy Panel Common Specifications Committee UHBVN & DHBVN Issue Morath: March 2012 . , (CSC approval date 26.09.2011) ( C:\Oocunenls And Settings\AdministratOfIDesktop\Specitication\CSC-XX-R-I-Doc Pa6:~ 1 of 16

Upload: others

Post on 11-Dec-2021

9 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: TECHNICAL SPECIFICATION FOR 33 KV Control Realy Panel

"3ffcif ct'~OI E>~?JIOII ta~t4) tad;;fOl f@aldt

UTrAI{ DAKSIiIN HAln'AfiA BLlU V'rrRA.N NIGAM

Specification No. CSC-XX-R-II/DH/UH/P&D/2011-2012

TECHNICAL SPECIFICATION

FOR

33 KV Control & Realy Panel

Common Specifications CommitteeUHBVN & DHBVN

Issue Morath: March 2012. ,(CSC approval date 26.09.2011)

(

C:\Oocunenls And Settings\AdministratOfIDesktop\Specitication\CSC-XX-R-I-Doc Pa6:~ 1 of 16

Page 2: TECHNICAL SPECIFICATION FOR 33 KV Control Realy Panel

~ ~ f>~?J101l firvR4T fadiilOI fZiror.Jr

tm:AIt D~ JI.t\JlY~ BLJU V'I:t'ItIlN NIfiAM

"TECHNICAL SPECIFICATION OF INDEPENDENT 33KV TRANSORMER AND FEEDERCONTROL AND RELAY PANELS FOR 33KV SUB STATION & FOR GROUP CONTROL OF2 Nos. OF 33!11 KV TRANSFORMERS

1. SCOPE:

The specification covers the design manufacture, testing before dispatch, supply &

delivery along with associated sundries to complete the job. A control and relay panel shall

include the following:

a) Protective and auxiliary relays required for the protection of transformers and lines.

b) Indicating instruments with necessary switches

c) Control switch for the remote control of 33 KV circuit breaker.. '.

- d) Supervision equipment

e) Mimic equipment

o Alarm equipment

g) Terminals, wiring ferrules, fuses, links and sundries to complete the job.

2. STANQARDS:

All material and equipment shall comply in every respect with the requirements of the .

latest edition of the relevant standards as specified here. Equipment meeting with any other

internationally recognised standards will be acceptable.

Protective relays IS: 3231

Indicating Instruments IS: 1248

Mimic colour shades IS: 1961

3. CLIMATIC CONDITIONS~The equipment/material to be supplied against this specification shall be suitable

for satisfactory operation under the following climatic Conditions

i) Location At various locations in the stateof Harvana

ii)- Max ambient temperature (deq.c) - 60iii) Min ambient air temperature (deg. c) ·--5iv) Max average daily ambient temperature (deq. c) 40v) ·/Max. yearly weighed average ambient 32

temperature (deQ. C) .vi) Max. altitude above mean sea level (Meters) 1000vii) Minimum Relative Humidity (%age ) 26viii) Max. Relative Humidity (%age) 95ix) AVQ. no of Rainy days! year 120x) AVQ. annual rainfall

,900mm

xi) Maximum wind pressure 195 KQ.lmm Sq.The equipment shall be for use in moderately hot and humid tropical climate, conducive to rustand fungus growth.C \Docl1JncnlsAncl Sdtings\Administralor\Desklop\Specificatioo\cSC-XX-R.J Doc Page 2 of 16

Page 3: TECHNICAL SPECIFICATION FOR 33 KV Control Realy Panel

~ ~ 6~<'.noll ~ tadOlOI ~

IJ'l"l:AIt D..AKSJmf 1IIdO'AR.A. BLlU Y'lTJUQr BlfuUI/'V/o.YaVN

L~tj

4. SYSTEM PARTICULARS AND AUXILIARY SUPPLIES:

4.1 33KV voltage supply will be 3 phase, 50 Hz.

4.2 Wherever the neutral is provided on the power transformer, the same will be solidly

earthed.

4.3 A.C. supply at the 33KV sub-station for which the C&R panels against this

specification are required will be415/240 Volts, 3 phase, 4wire, 50Hz:!:3% variation.

4.4 D.C. supply available at the sub stations for which the C&R panel against this

specification are required will be 24 Volts, 2 wire available from the sub-station battery.

The supply may have 2: 10% variation:

5. TEST SHEETS:

Guaranteed test sheets as per Annexure 'A' will be submitted by the tenderer alongwith

the tender. Relevant literature will be supplied for proper appreciation of the offered

equipment.

6. SPARE PARTS:

The cost of the following items may" be quoted separately so that: the same be

purchased as spares, if considered necessary.

6.1 Triple pole IDMTL type over current relay with instantaneous attachments, non-

directional combined over current and earth fault relay, auxiliary relays (used in the

alarm scheme) semaphore relays used.on the panel.

6.2 Control handle used on the panel for the remote control of circuit breake.r.

6.3 Ammeter & Voltmeterused on the panel:

6.4 INDICATING LAMPS, BELL BUZZER:

At list of spare parts recommended for 5 years of normal operation shall be furnished

with the tender. Actual quantities to be ordered shall be determined by the purchaser.

7. DEPARTURE FROM SPECIFICATION:

Sh~uld the tenderer wishes to depart from the provision of this specification either on

account of manufacturing practice or for any other reason, he will draw special attention to the

proposed points of departure in his tender and submit such full information, drawing and

specifications as will enable the merit of his proposal to be appreciated.

In the event of supplier's drawings, specifications and tables etc., disagreeing with this

specification during the execution of contract, this specification shall be held binding unless the

departures have been fully recorded and agreed upon by purchaser as required above.

C \DoculTk:JluArdScnmgslAdminLslral~top\Speclfjc.lllon\CSC-XX-R-11Joc Page 3 of 16

Page 4: TECHNICAL SPECIFICATION FOR 33 KV Control Realy Panel

~ ~ f>~ZJlOII ~ fi'Jd<>lOI ~

UlTAa D~ IWO"ANA BIJLI V'I:raAR BI6IdI

8. DRAWING:In addition to any other drawings which the tenderer may like to enclose to explain the

merits of his proposal, the following drawings shall be enclosed with the tender in quadruplicate:

i) Major dimensional drawing of each of the three types of C & R panel.

ii) Feeder circuit protection scheme.

iii) Transformer circuit protection scheme in respect of both types of transformers C &R

panel.

Within 15days after the date of issue of firm order together with other essential technical

particulars( by the purchaser), the supplier shall furnish 4 copies each of the

dimensional drawings, schematic drawings and wiring drawings of C&R panels for.

purchaser's approval, enabling him to determine that the design proposed can be

satisfactorily fabricated. The purchaser shall have the right to require the supplier to

make any other change in the design, which may be necessary in his opinion to make

. the equipment conform to the stated provisions of the specification without additional~- .cost tQJhe purchaser. Approval by the purchaser of the supplier's drawings shall not be

held to relieve the supplier of any part of the contract ebligation to meet all the

requirements of this specification. .

9. ILLUSTRATEDAND PRINTEDLITERATURE:

Two copies each of the descriptive and printed literature in respect of al.1instruments

switches and relays used on the offer~d.panels shall be supplied alongwith the tender.

10. PLACE OF MANUFACTURE& INSPECTION:

The tenderer shall state in his tender the place(s) of manufacture, testing and inspection

of the various portions of the work included in the tender,

The purchaser or his duly authorized agency shall have access to the supplier's works

at any time during working hours for the purpose of inspecting the manufacture of material,

equipment etc., and the supplier shall provide the necessary facilities for inspection.

11. TESTS:

The following tests shall be carried out at the manufacturer's works after complete

assemble of control and relay panel board and the test report of such tests supplied in

quadruplicate for approval of CGM/MM, DHBVN I UHBVN before despatch of equipment: -

i) Checking of wiring circuits and their continuity.

ii) , One minute applied voltage test for all equipment on panels and wiring.

iii) Insulation resistance of complete wiring, circuit by circuit with all equipments

mounted on the panel.

iv) Checking the operation of protective relays.C\Documents And SeltmgMdministrator\DesktoplSpecific.:Jlion'CSC.XX.R.[ Doc Page 4 of 16

Page 5: TECHNICAL SPECIFICATION FOR 33 KV Control Realy Panel

~ ~ e>PolZIIOII ~ fadi:(Oi ~

tTrT::Idl DAKSBINIIAlO'ANA BIJU lfI'rRAN .sI6IdI

All instruments, auxiliary relays and protective relays used on the panels shall comply

with the latest edition of relevant Indian/Other internationally acceptable standards and routine

test certificates for the same supplied and got approved from the purchaser.

Type test reports relating to all protective relays as per relevant standards shall be

submitted by the tenderers alongwith their tender for reference of the purchaser.

The type test reports should not be more than five years old reckoned from the date of

bid opening. The type tests should be got carried out from the Govt./Govt. approved NABL

accredited test house as per relevant ISS.

Immediately after finalisation of the programme of acceptance/routine testing, the

supplier shall give sufficient advance intimalion (at least 15 days notice for Indians suppliers and

30 days notice for Foreign supplier) to the purchaser to enable him to depute his representative

for Witnessingthe tests.

12. FAKEINSPECTION CALL

The manufacturer shall be responsible to pay penalty of -Rs 20,0007- for each

occasion at which the fake inspection call hasbeen made or the material is rejected during

testing/inspection by the authorized agency/representative of the Nigam. This penalty would

be in addition to the expenses incurred by the Nigam in deputing the Inspecting Officer,

carrying out such inspection

13. INSTRUCTION BOOKLETS:

Operating, testing, commissioning and maintenance instructions in English.language

covering all the protective and auxiliary relays and instrumenisshall be put under a common

cover and six such sets shall be supplied free of cost at least one month before despatch of the

C&R panel.

13. REPRODUCIBLEDRAWINGS:The supplier shall supply one set of full size reproducible of dimensional drawings,

schernalicdrawinqs and wiring diagrams of the three types of control and relay panels against

the contract either on tracing cloth or on synthetic paper enabling easy multiplication of prints as

and when required by the purchaser. The supplier will also supply six sets of drawings for each

type of C&R panels, each set consisting of dimensional schematic and wiring diagrams of the

panels.

14. PACKING AND TRANSPORT:The supplier shall be responsible for suitable packing of all the material and marking on

the consignment so as to avoid any damage during the transport and storage and to ensure

correct despatch to the destination.

C:l.l:>ocumCits And SettmgsIAdministratorl.Dc:sJdop\Sp«irICaILOO\cSC-XX-R-l.Doc Page 5 of 16

Page 6: TECHNICAL SPECIFICATION FOR 33 KV Control Realy Panel

"3OCT ~ 6~l1lOIi ~ tad;>tOI taor.Jr

U1T.AIt DAKSIDN IlARYANA BIJIJ V'.(n:tiU M6AM

15. MARKING:The following particulars shall be marked distinctly and permanently on every relay

preferably in a position visible from the front.

(a) Manufacturers name or the make by which he may be identified.

(b) Manufacturer's type reference.

(c) Ratedcurrent, rated voltage or both.

(d) Frequency.

(e) Particularsof auxiliary equipment.

(f) Setting indication.

(9) Manufacturer's serial Number.

(h) Countryof manufacture.-

Relays must be marked with ISI certification mark.

Meters shall have markings as per ISS 1248-1983 or latest version thereof/equivalent

IEC.

C.\Documt."llls And Sct{ingslAdminislIalor\Dcsktop\SJXX:ification\CSC.XX.R-I.Doe Page 6 of 16

Page 7: TECHNICAL SPECIFICATION FOR 33 KV Control Realy Panel

~ ~ e>~<11011 ~ fi'.tdCilOI furorUlTK DAK$IJlj Hln"ANA BIJLI Y'lTRiU tmiItM

PART-II TECHNICAL PARTICULARS

1. GENERAL DESCRIPTION OF CONTROL & RELAY PANEL:The control and relay panel shall consist of separate cubicle with side covers made of

sheet steel and complete with internal wiring, terminals, ferrules and illumination with door

operated 'OFF' and 'ON' switch. The cubicle shall be suitable for floor mounting with its bottom

open and shall be completely dust and vermin proof. The cubicle shall be of suitable height with

adequate depth and width so as to afford comfortable working area inside the panel for testing

staff. Each cubicle shall be fitted with flush mounted steel hinged door and lock at the back and

all the equipments (control, supervisory, metering and protective) will be mounted in front. The

supply shall include the channel base, suitable grouting bolts, nuts, locknuts, washers etc.

alongwith the panels.

The individual panels shall have provision for extension at both ends so as to form a

board as per the requirement.

SUPERVISION SCHEME:Each of the control and relay panel against the specification shall be fitted with the

following supervision lamps: -

Circuit breaker close:Circuit breaker open:Auto-trip:Trip circuit healthy:(Monitor~g both whenBreaker IS OFF/ON)All lamps except circuit breaker close and circuit breaker open indicating lamps shall berated for 24 volt D.C. The lamps shall have low wattage consumption and shall provide acomfortable viewing.Circuit breaker close and circuit breaker open indication lamps will be suitable for 220VAC. Glass/plastic lens of appropriate colour shall be screwed into the front of the lamp.toov.An engraved label indicating the purpose of the lamp shall be provided with each lamp.

. .ln the initial supply 20% of the lamps actually used on the switch board and 10% of lamplenses of various colours shall be supplied loose to serve as spares.ALARM SCHEME:

2.

Red.Green.Amber.White.

3.

a) Alarm scheme for trip alarm due to electrical faults:Trip commands due to operation of protective relays including Buchholz relay and

winding temperature trip contacts will actuate bell and will be cancelled by the circuit

breaker control handle. Auto trip lamp will glow on the panel and there will be flag

indication on the concerned protective relay/auxiliary relay of the panel.

C\Docum.:nlsAnd Sdhf\gMdmUli.stn.tor'olXs",op\Spa:irlCalion'CSC~XX-R-I.Doc Page 7 of 16

Page 8: TECHNICAL SPECIFICATION FOR 33 KV Control Realy Panel

~ ~ 6~<.11011 ~ fOdClOI faOJ<JJ

U1"(AR DAKSIIIk 1lAln"A.NA. BIJLI VI:rRIlN MtiIlM

b) Alarm scheme for non trip alarm:This scheme will conform to the following:i) The closing of an initiating contact shall actuate a buzzer and will be

accompanied by a flag indication on the concerned auxiliary relay.

ii) The closing of an initiating contact shall glow a lamp, which will not reset until the

fault has cleared.

iii) It shall be possible to silence the buzzer by pressing 'accept' push button,. If

after canceling the alarm but before resetting thevisuat signal, the same fault

persists the buzzer shall be suppressed.

iv) If after canceling the alarm but before resetting the visual signal some other fault

takes place then the alarm accompanied by the flag indication on the concemed

auxiliary relay shall take place.

v) If after canceling the alarm and after resetting the visual signal, the same fauit

reappears or some other fault takes place, the alarm flag indication and non-trip

lamp indication shall reappear as usual:

vi) The non-trip alarm. acceptance shall be by means of a push button and resetting

.ot visual signal may also be done through a push button.

vii) Means shall be provided for test checking the alarm and lamp circuits.

viii) The equipment shall be suitable for 24 D.C. operation.

3.1 Four ways for the annunciation of non-trip alarm on transformer panels with the following

description shall be provided:

TRASFORMER PANELS:

1) .Buchholz alarm-._-

2) Winding temperature alarm

3) Oil temperature alarm

4) OLTC oil surge relay & low oilalarm

3.2 Four ways for annunciation of trip & alarm on TIF panels with following description shall

.be provided:

I) Buchholz trip

2) Winding temperature trip

3) Oil temperature trip.

4) OLTC oil surge relay trip.

N.B.: 33 kV transformer panels meant for the group control of 2 Nos. 33/11 kV transformers

shall be provided with necessary auxiliary relays for independent annunciation of the non-trip

alarms (such as Buchhloz's alarm, winding temperature & Oil temperature alarm, OLTC Oil

C"\DocumC'ltsAnd Sctting:Mdministraror\Dc:slctoplSpccification\cSC-XX-R-I.Ooc Page 8 of 16

Page 9: TECHNICAL SPECIFICATION FOR 33 KV Control Realy Panel

./

"3ifi,f ~ E>~211011 taJl&'t fadil/Ol ~

IJlTAR DAKSHIN IIAIO'ANA BlJU YItVtN l'miAM

surge relay & Low Oil alarm etc)., trip (such as Buchhloz's trip, winding temperature, Oil

temperature trip & OLTC Oil surge relay trip etc.) conditions of transformer.

4. MIMIC SCHEME:4.1 Suitably painted mimic diagram will be reproduced on the panels. Automatic semaphore

indication for indicating OPEN and CLOSE position of circuit breakers, isolators and

earth switches shall be suitably incorporated in the mimic diagram as per Sketch-

I(enclosed). The operating coil of the semaphore relays shall be suitable for use on

24VD.C.

4.1 Following colour scheme shall be used for mimic representation on the panels against

this specification:

Vottaqe panel Colour Shade No. (accordinq to ISS-1961)33KV Brilliant green 22111KV Sional 537

5. METERING SCHEME:

. Voltmeters & Ammeters on all_the panels against the specification shall be of square,

flush mounting type. The line panels shall be mounted with both voltmeter & ammeter,

. whereas the transformer panel shall have only the ammeter. . . .

5.1 . Voltmeter shall be accompanied by a suitable selector switch facilitating the·

measurement of voltage between phase to phase and between phase to neutral.. The

voltmeter coil shall be rated for 110 Volts between phase to phase obtainable from the

secondary of potential transformers. The instrument shall be of moving iron spring

controlled type grade 'A' classification with an accuracy class of 1 and shall conform to

IS: 1248- 1983, IS:2419-1963 (latest version there of) or relevant BIS, IEC or ASA

standard.

5.2.1 Suitably sealed ammeter to cover CTs ratio shown in sketch-I shall be accompanied by

a selector switch facilitating the rneasurementof phase currents as well as the

unbalanceq current in the neutral. The ammeter coil shall be rated for 5 Amp. The

instrument shall be of moving iron spring controlled type of industrial grade 'A'

classification with an accuracy class 1 and shaHconform to IS: 1248-1983, IS: 2419-

1963 (latest versionthereof) or relevant BIS/I.E.C or ASA standard

6. CONTROL SCHEME AND CONTROL SWITCHES:It shall be possible to close the breaker from the control room. For this purpose control

switches with built in key free locks having pistol grip type or handles of the spring return to

neutral position type with alarm (cancellation) contacts shall be provided for operation of circuit

breakers.

C;\Documc:nlsAnd SdtlllgMwmnistraronlxsl1op'Spetifit.allon\cSC-XX-R.tDoc Page 9 of 16

Page 10: TECHNICAL SPECIFICATION FOR 33 KV Control Realy Panel

~ ~f$tOI e;~2I101l fBJlt4) tOd~OI Potolat

uTTAIt DAKSlfIl( BAIO.'ANA ULlLI Y'rntAN NItiAM

7. PROTECTION SCHEME:7.1 TRANSFORMER PANELS:

Triple pole over current relay IDMTL type with high set elements For Over Current

protection a triple pole inverse definite minimum time lag over Current relay with a setting range of 50%-

200% (of 5Amp Rating) and also fitted with high set elements of 500%-2000% of 5A for instantaneous

clearance of faults within the transformer(s) shall be provided on each of the transformer control and

relay panel.

For restricted earthfault protection to 33KV winding of the power transformer, an

instantaneous balanced earth fault relay shall be provided on each of the transformer C& R panel.

The relay shall have a setting range of 10%-40% of 5Amp. & shall be complete with 50Hz circuit &

stabilizing resistance.

Note:

R.E.F. protection is not required for the transformer having capacity 5 MVA & below.

7.2 LINE PANEL:Triple pole combined over current and earth fault relay:-Triple pole combined over current and earth fault relay consisting of outer two over current

elements having setting range 50% to 200% of 5Amp having IDMTL characteristics and inner earth fault

element having setting range of 20-80% of 5Amp having IDMTL characteristic shall be provided on

. each of the 33KV line panel.

7.3· TRANSFORMER DIFFERENTIAL PROTECTIOIN (For Capacity 10 MVA & above):The relay shall

i) Be triple pole numerical type.

ii) Have 3 instantaneous high set differential units.

iii) .Have second harmonic restraint or other inrush proof feature and be stable under normal

. over fluxing condition.

iv) Have fifth harmonic by pass filter or similar other arrangement to prevent mal-operation of

the relay under operating conditions.

v) Be suitable for rated current of 5A and include necessary ICTs for ratio & phase angle

correction.

vi) Have operating current setting sufficiently low (15% or less) so as to cover practically the

whole of the transformer against all types otfaults.

vii) Have adjustable bias setting range of 20-50%. Have maximum operating time of 30milli

seconds at 5 items the rated current.

viii) Be provided with necessary terminal & links to measure current in restraining circuits & in

the operating circuits of all the phases under load without making any wiring changes.

ix) Display.resolution of differential/pickup current should be 0.01A (10 MA).

8. SMALL WIRING:

8.1 All the wiring shall be of switchboard type consisting of single tinned annealed copper

C:\DoCUTlents And Settiogs\Administrator\Desk1op\Specificatioo\CSC-XX-R-I.Ooc Page 10 of 16

Page 11: TECHNICAL SPECIFICATION FOR 33 KV Control Realy Panel

conductor insulated with polyvinyl chloride insulation suitable for 660 volts service and in

accordance with IS: 732-1963 (latest version thereof).

8.2 The wiring of the following circuits shall be not less than the size specified below:

CTs and PTs circuits: 2.5 mm sq

Control alarm, supervision circuits: 1.5 mm sq.8.3 All wires will be continuous from one terminal to the other and also will have no tee- junction

enroute. At the terminal connections, washers shall be interposed between terminals and

holding nuts. All holding nuts shall be secured by locking nuts.

8.4 Bus wires shall be fully insulated and run separately. Fuses and links shall be provided to

enable all the circuits in a panel to be isolated from the bus wire. Wherever practicable all

circuits in which the voltage exceeds 125 volts shall be kept physically separated from the

remaining wiring. The function of each circuit shall be marked on the associated terminal

board.

8.5 All wiring diagrams for the control and relay panel shall be drawn as viewed from the back of

. the cubicle and shall be in accordance witl+..lSS;. 375-1963 (latest version thereof). Multicore

cable tails shall be so bound to its cable that each wire may be traced without difficulty.

9 TERMINAL BOARDS:9.1 Terminals block connectors built from cells of moulded dielectric and brass stud inserts shall

be provided for terminating the outgoing ends .of the panel wiring and the corresponding

tail ends of Control Cables. Insulating barriers shall be provided between adjacent connections.

The height of barriers and spacing between terminals shall be such as to give adequate

.protection while allowing easy access to terminals.

9.2 Terminal blocks shall be suitable for 660 Volts service and for connection with both

copper and aluminum wires.

10. CONTROL AND RELAY CUBICLES

i) The Control and Relay Cubicles shall be made of Sheet Steel of thickness not less than 10

SWG (3.251 mm) for the base frame, door frame, front & Rear portions of Cubicle & not less

than 14 SWG (2.032 rnrn) for doors, side.fop & bottom portions, in place of sheet metal of 2

rnm thickness.

ii) The main REF and differential relays should only be of make AREVA ! ABB ! SIEMENS!

EASUN REYROLLE. However, the Auxiliary and 2 Nos. Over Current + Earth Faulty relays

may be of JVS make, but the same should be numerical type.

iii) The C&R Panels should be of standard-dimensions as under:-

Depth =Height of switch Board above base frame =Height of base frame =

610 mm.

2210 mm.

102 mm.

C:\Ooo.rnents And Settings\Admi'listJatot\Oesktop\Specification\CSC-XX-R.J.Ooc Page 11 of 16

Page 12: TECHNICAL SPECIFICATION FOR 33 KV Control Realy Panel

11. FERRULES, SPACE HEATERS AND SAFETY EARTHING:

11.1 Ferrules engraved with some number and letters as indicated in the connection and wiring

diagram shall be provided on the terminal ends of all wires for easy identification of circuits

for inspection and maintenance.

11.2 Tubular space heaters suitable for connection to the single phase 230 Volts A.C. supply

complete with switches shall be provided at the bottom of each control and relay panel to

prevent condensation of moisture.

11.3 Earthing of current free metallic parts or metallic bodies of the equipment mounted on the

switchboard shall be done with copper conductor of suitable size.

12. CHALLENGE CLAUSE

The material offered/received after the inspection by the authorized inspecting officer may

again be subjected to the test for losses or any other parameter from any Testing House/in-

house technique of the NiqarnS the results if found deviating un-acceptable or not complying to

approved GTP's the bidder shall arrange to supply the replacement within thirty (30) days of

such detection at his cost including to & fro transportation. In addition to this penalty @10% of

cost of the inspected lot of material shall be imposed.

13. ~WARRANTEE PERIOD

The supplier shall be responsible to. replace, free of cost, with no transportation or

insurance cost to the Purchaser, up to destination, the whole or any part of the material which in

normal and proper use proves the defective in quality or workmanship; subject to the condition

that the defect is noticed within 1.8 months from the date of receipt of material in stores or 12

months from the date of commissioning whichever period may expire earlier. The consignee or.

any other officer of Nigam actually using the material will give prompt notice of each such defect

to the supplier. The replacement shall be effected by the supplier within a reasonable time, but

not, in any case, exceeding 45 days. The supplier shall, also, arrange to remove the defective

within a reasonable period, but not exceeding 45 days from the date of issue of notice in respect

thereof, failing which, the purchaser reserve the right to dispose of defective material in any

manner considered fit by him (Purchaser), at the sole risk and cost of the supplier. . Any sale

proceeds of the defective material after meeting the expenses incurred on its custody, disposal

handlmq.etc., shall however-be credited to the-supplier'saccount and set off against any

outstanding dues of the purchaser against the supplier. The warranty for 12/18 months shall be

one time

GM I(P&O) GM (PO)Member Secy DHBVNUHBVN

FA & CAO FA & CAO CGM(MM) (MM) (PO&C)UHBVN OHBVN UHBVN

CE (PO)DHBVN

Director(Projects)DHBVN

Director(Projects)UHBVN

C:\OoCUT1ents And Settings\Administrator\Oeslctop\$pecification\CSC-XX-R-I.00c Page 12 of 16

Page 13: TECHNICAL SPECIFICATION FOR 33 KV Control Realy Panel

rad~OI Potaldt

PART III

PANEL DETAILS

A. TRANSFORMER PANLES:

I. Protection scheme as per para 7.1

II. A multi contact auxiliary relay suitable for 24 V D.C. for inters tripping purposes ..

III. The provision of supervision scheme, alarm scheme, mimic scheme, metering scheme andcontrol scheme on this panel shall conform to applicable items of paras 2,3,4,5, & 6respectively.

B LINE PANEL:

I. Protection scheme as per para 7.2

II. -T1re=provision of supervision scheme, alarm scheme, mimic scheme, metering and controlscheme on this panel shall conform to applicable items of pares 2,3,4,5 & 6 respectively.

C:\Ooctments And Settilg:s\Admristrator\Oeslctop\Spe<:ification\CSC-XX-R-IDoc Pag~13 of 16

Page 14: TECHNICAL SPECIFICATION FOR 33 KV Control Realy Panel

ANNEXUR-'A'GUARANTEED TECHNICAL PARTICULARS OF 33 KV TRASFORMER AND FEEDER CONTROLAND RELAY PANEL & FOR GROUP CONTROL OF 2 Nos. OF 33/11 KV TRANSFORMERS.

I. Indicating instruments:1. Make

2. Type

3. Size

4. VA burden

a) Current Coil

b) Potential Coil

5. Power consumption

a) Current Coil

b) Potential coil

6. IS standard grade of accuracy

7. Range of dial

8. Limits of error in effective range

9. Calibration for

a) CT ratio

b) PT ratio

10. Finish

11. Short time overloads capacity.

12. Descriptive leaflet reference Nos. submitted.

13. Type & make of selector.switch for ammeter.II Circuit breaker control switches:

1. Make:

2. Type:

3. Type of handle provided:

4. No. of position:

5. No. of contacts.

a) Normally closed

b) Normally opened.

6. Whether spring return to neutral or stay put type?

7. Type of lock provided.

8. Descriptive leaflet number submitted.

III. Semaphore indicator (for circuit breaker, isolator & earth switch)

1. Make

2. Type

3. Diameter of the disc.

C;\DoclXIlents And SettngslAaninistralor\Oesktop\Speci1icatioflICSC-XX-R-I.Doc Pdg~ 14of 16

Page 15: TECHNICAL SPECIFICATION FOR 33 KV Control Realy Panel

~ <l>tmOI 6~<JIOII iaJl<.4l tad;>tOl .Pot<JIJt

ITITAl{ D.AKSIiIIJ IIAIO'ANA BIJLI ~ l!IItiAM

"4. Operating voltage

5. Burden

6. Whether latch-in type or supply failure type.

7. Descriptive leaflet number submitted.IV. Indicating Lamps:

1 Make

2 Type

3 Operating voltage.

4 Size of lens.

5 Wattage of the lamp.

6 Descriptive leaflet number submitted.V _ Switch Board Wiring

1 Insulation of wiring.

2 Wiring conductor size and its material. 3 Size of wiring conductor for:

a. CT circuits.

b. PT circuits.

c. D.C. supply circuits.

d. Other circuits.

4 Size of earthing bar for safety-earthing.

5 Type of terminals used in wiring the panel.VI Over Current & earth fault relay:

Make.

2 Type. of relay.

3. Current-coil rating.

3. Tap. range.

4. Range of high set elements (wherever applicable)

6. VA burden:

a. At highest Tap.

b. At lowest Tap.

7 Trip contact rating.

8 Descriptive leaflet Nos. submitted.VII Auxiliary Relays:

1. Make.

2. Type.

3. Capacity of co~tacts

a. Continuously.

b. For 3 seconds.

4. Operating coil VA burden.

C:\Doctrnents And Seffi1gs\AdministJator\Desktop\Specification\CSC4XX-R-I.00c Page IS of 16

Page 16: TECHNICAL SPECIFICATION FOR 33 KV Control Realy Panel

fOd;]lO I taJalCH

5 Voltage operated or current operated.

6. Number of normally open contacts.

7. Number of normally closed contacts.

8. Contacts hand or self reset type.

9. Descriptive leaflet number submitted.VIII. Restricted Earth Fault Relay:

1. Make

2. Type of relay.

3. Current coil rating.

4. Setting range

5. VA burden:

.. ' " a. At highest tap

b. At lowest tap

6. Descriptive leaflet number submitted.IX. TRANSFORMER DIFFERENTIAL RELAY.

1. Make.

2. Type.

3. Minimum differential current at which relay operations.

4. Range & steps of bias setting.

5. Operating time at twice the relay setting.

6. VA burden ofthe relay.

7. Descriptive leaflet No.

C:\OoctmentsAnd Setlngs\Administrator\Oes.ktop\Specification\CSC-XX·R~.Ooc Page16 of 16