technical specification for stationary vrla-gel … bae opzv block.pdfbae secura opzv block...

2
BAE SECURA OPzV BLOCK Technical Specification for Stationary VRLA-GEL-Block Batteries 1. Application BAE SECURA OPzV BLOCK batteries belong to the highest EUROBAT classification for maintenance-free lead-acid batteries: >12 years long life. In applications with high requirements of operational safety and autonomy times of 1 h to more than 10 h, the BAE SECURA OPzV BLOCKs are the right choice. They are used as stand-by power sources in telecommunications, in microwave radio systems, emergency lighting and other equipments. 2. Types, capacities, dimensions, weights Type C 10 h C 5h C 3h C 1h C 8h R i I k Length Width Height Weight 20 °C 20 °C 20 °C 20 °C 25 °C 1) 2) (L) (W) (H) Ah Ah Ah Ah Ah mV kA mm mm mm kg U e V/cell 1.80 1.77 1.75 1.67 1.75 12 V 1 OPzV 50 60 53 48 35 60 17.47 0.73 272 205 385 43.0 12 V 2 OPzV 100 110 99 89 68 109 9.55 1.34 272 205 385 52.0 12 V 3 OPzV 150 167 149 135 103 166 6.74 1.91 380 205 385 74.2 6 V 4 OPzV 200 224 200 181 137 222 2.66 2.42 272 205 385 51.0 6 V 5 OPzV 250 281 251 227 172 279 2.24 2.87 380 205 385 65.0 6 V 6 OPzV 300 337 301 273 207 335 1.94 3.31 380 205 385 73.8 2 V 12 OPzV 600 674 600 543 413 668 0.29 7.33 205 272 385 51.0 2 V 15 OPzV 750 844 750 681 517 832 0.24 8.81 205 380 385 65.0 2 V 18 OPzV 900 1,010 905 819 622 1,000 0.21 10.18 205 380 385 73.8 1, 2) Internal resistance R i and short circuit current I k according to IEC 60896-21 Height (H) is the maximum height between container bottom and top of the bolts in assembled condition. All values given in the table correspond to 100 % DOD without voltage drop of connectors. Please consider item 6. 12 V 1 OPzV 50 to 12 V 3 OPzV 150 6 V 4 OPzV 200 to 6 V 6 OPzV 300 2 V 12 OPzV 600 to 2 V 18 OPzV 900 3. Terminal positions

Upload: others

Post on 10-Sep-2020

13 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Technical Specification for Stationary VRLA-GEL … BAE OPzV Block.pdfBAE Secura OPzV BLOCK Technical Specification for Stationary VRLA-GEL-Block Batteries 1. Application BAE Secura

BAE Secura OPzV BLOCK Technical Specification for Stationary VRLA-GEL-Block Batteries

1. Application BAESecuraOPzVBlOckbatteriesbelongtothehighestEUROBATclassification

formaintenance-freelead-acidbatteries:>12yearslonglife. Inapplicationswithhighrequirementsofoperationalsafetyandautonomytimes

of1htomorethan10h,theBAESecuraOPzVBlOcksaretherightchoice.Theyareusedasstand-bypowersourcesintelecommunications,inmicrowaveradiosystems,emergencylightingandotherequipments.

2. Types, capacities, dimensions, weights

Type c10h c5h c3h c1h c8h Ri Ik length Width Height Weight 20°c 20°c 20°c 20°c 25°c 1) 2) (l) (W) (H) Ah Ah Ah Ah Ah mV kA mm mm mm kg Ue V/cell 1.80 1.77 1.75 1.67 1.75

12V1OPzV50 60 53 48 35 60 17.47 0.73 272 205 385 43.012V2OPzV100 110 99 89 68 109 9.55 1.34 272 205 385 52.012V3OPzV150 167 149 135 103 166 6.74 1.91 380 205 385 74.2 6V4OPzV200 224 200 181 137 222 2.66 2.42 272 205 385 51.06V5OPzV250 281 251 227 172 279 2.24 2.87 380 205 385 65.06V6OPzV300 337 301 273 207 335 1.94 3.31 380 205 385 73.8 2V12OPzV600 674 600 543 413 668 0.29 7.33 205 272 385 51.02V15OPzV750 844 750 681 517 832 0.24 8.81 205 380 385 65.02V18OPzV900 1,010 905 819 622 1,000 0.21 10.18 205 380 385 73.81,2)InternalresistanceRiandshortcircuitcurrentIkaccordingtoIEc60896-21Height(H)isthemaximumheightbetweencontainerbottomandtopoftheboltsinassembledcondition.Allvaluesgiveninthetablecorrespondto100%DODwithoutvoltagedropofconnectors.Pleaseconsideritem6.

12V1OPzV50to12V3OPzV150 6V4OPzV200to6V6OPzV300 2V12OPzV600to2V18OPzV900

3. Terminal positions

Page 2: Technical Specification for Stationary VRLA-GEL … BAE OPzV Block.pdfBAE Secura OPzV BLOCK Technical Specification for Stationary VRLA-GEL-Block Batteries 1. Application BAE Secura

12/2

012

480

4035

Tec

hnica

l deta

ils m

ay b

e sub

ject t

o alt

erati

ons.

Technical Specification for BAE Secura OPzV BLOcK

4. DesignPositiveelectrode tubular-platewithwovenpolyestergauntletandsolidgridsinacorrosion-resistant PbcaSn-alloyNegativeelectrode grid-plateinPbcaSn-alloywithlong-lifeexpandermaterialSeparation microporousseparatorElectrolyte sulphuricacidwithadensityof1.24kg/l,fixedasGElbyfumedsilicacontainerandlid highimpactSAN(Styrol-Acrylic-Nitrile),greycoloured(colourmayvaryslightlyfrom givenimage),Ul-94rating:HB onrequestalsoinABS(Acrylonitrile-Butadiene-Styrene),Ul-94rating:V-0Blockswithblindcells 4V,6V,8V,10VValve onevalvepercellwithflamearrestor,openingpressureapprox.120mbarPole-bushing 100%gas-andelectrolyte-tight,sliding,plasticcoated“Panzerpol”kindofpole M10brassinsertionconnectors flexibleinsulatedcoppercableswithcross-sectionof25,35,50,70,95or120mm², onrequest:insulatedsolidcopperconnectorswithcross-section90,150or300mm²connectorscrew M10,steel,insulated,withmeasuringpointkindofprotection IP25regardingEN60529,touchprotectedaccordingtoVBG4Horizontaloperation PleaseuseBAEspecialtypeOPzV“horizontal”.Theconstructionandproductionof thistypeisadaptedtothehorizontaloperation.

5. ChargingIU-characteristic Imaxwithoutlimitation U=2.25V/cell±1%,between10°cand45°c(50°Fand113°F)inthemonthly average,DU/DT=-0.003V/cellperkbelow10°c(50°F)Floatcurrent 20-30mA/100Ahc10Boostcharge U=2.33to2.40V/cell,timelimitedchargingtimeupto92% 6hwith1.5xI10initialcurrent,2.25V/cell,50%c10discharged

6. Discharge characteristicsReferencetemperature 20°c(68°F)Initialcapacity accordingtoIEc60896-21:95%atthe1stcycle,100%atthe5thcycleDepthofdischarge(DOD) normallyupto80%Deepdischarges morethan80%DODordischargesbeyondfinaldischargevoltages(dependenton dischargecurrent)havetobeavoided

7. MaintenanceEvery6months checkbatteryvoltage,pilotblockvoltages,temperaturesEvery12months recordbatteryandblockvoltagesandtemperatures

8. Operational dataclassificationaccordingtoEUROBAT 12yearsandlonger-longlifeServicelife 18yearsinstand-byoperation,floatat20°cto25°c(68°Fto77°F)Maintenance-free notoppingupduringlifeIEc60896-21cycles >1,500Self-discharge approx.2%permonthat20°c(68°F)Batterytemperature -20°cto45°c(-4°Fto113°F) recommended10°cto30°c(50°Fto86°F) shorttime45°cto55°c(113°Fto131°F)Deepdischargerecovery verygoodStandard DIN40744Testsaccordingto IEc60896-21,-22Safetystandard,ventilation EN50272-2,Ventilationrequirementsarereducedto20%comparedtothosefor ventedbatteriesofthesamecapacity.Transport BatteriesarenotsubjecttoADR(roadtransport),iftheconditionsofSpecial Provisions598and238(chapter3.3)areobserved. BAEcells/batteriesareconformtotheIMDG-code,thereforetheseproductsareno dangerousgoodsonseatransport.

BAEBatterienGmbHWilhelminenhofstraße69/7012459BerlinGermany

Tel.:+49(0)3053001-661Fax:+49(0)3053001-667E-Mail:[email protected]