tek-care nc150 and nc200 intercom nurse call systems

32
Tek-CARE ® NC150 and NC200 Intercom Nurse Call Systems UL ® 1069 Listed Operation, Installation and Service Manual Tek-CARE ® NC150 and NC200 series Intercom Nurse Call Systems are designed for nursing home or individual hospital ward use. The Tek-CARE ® NC150 and NC200 systems provide selective two-way audio and visual communication from master station to staff and patient stations, as well as emergency signaling and call indication from remote locations. Emergency calls are indicated by a rapid pulsing of all audible and visual signals associated with the calling station. Emergency calls take precedence over normal calls and can only be canceled at the point of origin. IL380 SECTION E Rev. 20 - 03/2011 Distributed by: Alpha Communications ® 42 Central Drive Farmingdale, NY 11735-1202 Phone: (631) 777-5500 Fax: (631) 777-5599 Website: www.AlphaCommunications.com Email: [email protected] TOLL-FREE Technical #: 1-800-666-4800

Upload: others

Post on 15-Mar-2022

4 views

Category:

Documents


0 download

TRANSCRIPT

Tek-CARE® NC150 and NC200Intercom Nurse Call Systems

UL® 1069 Listed

Operation, Installation and Service Manual

Tek-CARE® NC150 and NC200 series Intercom Nurse Call Systems are designed for nursinghome or individual hospital ward use. The Tek-CARE® NC150 and NC200 systems provideselective two-way audio and visual communication from master station to staff and patientstations, as well as emergency signaling and call indication from remote locations.Emergency calls are indicated by a rapid pulsing of all audible and visual signals associatedwith the calling station. Emergency calls take precedence over normal calls and can onlybe canceled at the point of origin.

IL380SECTION ERev. 20 - 03/2011

Distributed by:

Alpha Communications®

42 Central DriveFarmingdale, NY 11735-1202Phone: (631) 777-5500Fax: (631) 777-5599

Website:www.AlphaCommunications.com

Email:[email protected]

TOLL-FREE Technical #:1-800-666-4800

ii • IL380 Tek-CARE® NC150 & NC200 Manual Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

Operation, Installation and Service ManualCopyright © 2001–2011 TekTone® Sound & Signal Mfg., Inc., All rights reserved.

No part of this publication may be copied without the express written permission of TekTone® Sound & Signal Mfg., Inc. Thecontent of this manual is furnished for informational use only, is subject to change without notice, and should not be construed asa commitment by TekTone® Sound & Signal Mfg., Inc. TekTone® Sound & Signal Mfg., Inc. assumes no responsibility or liabilityfor any errors or inaccuracies that may appear in this documentation.

TekTone, the TekTone logo, Tek-Call, Tek-Care, Tek-Check-In, Tek-Com, Tek-Digicare, Tek-Door, Tek-Entry III, Tek-Guard, Tek-Micro, Tek-Micro II, Tek-MMARS II, TekNIOS, TekNIOS II, Tek-Paging, Tek-Phone, Tek-Safe, Tek-Select II, Tek-Sentry, Tek-Sound, Tek-Status, Tek-Trio and Tek-View are either registered trademarks or trademarks of TekTone® Sound & Signal Mfg., Inc.in the United States and/or other countries. All other trademarks are the property of their respective owners.

IL380 Tek-CARE® NC150 & NC200 Manual • iiiCopyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

A Word About ESD (Electrostatic Discharge) ....................................... iv

System Operating Instructions ...............................................................1NC150N, NC200N Master Stations ........................................................................... 1IR150B Staff Stations ................................................................................................ 3IR151B, IR152B Patient Stations .............................................................................. 5IR155B Patient Stations ............................................................................................. 5SF155B Emergency and SF156B Code Stations ....................................................... 5LI150B Duty Stations ................................................................................................. 5LI381 Corridor Lights ................................................................................................ 6LI382 & LI382LED Corridor Zone Lights ................................................................ 6

System Installation ...................................................................................7Installation Procedure ................................................................................................. 7Equipment Locations .................................................................................................. 7Wiring Installation ..................................................................................................... 8Housing Installation ................................................................................................... 9Wire Checkout .......................................................................................................... 10Wire Connections .................................................................................................... 10Connections Checkout .............................................................................................. 11System Test Instructions ........................................................................................... 11System Checkout and Testing .................................................................................. 11

System Maintenance Instructions ........................................................ 13NC150N, NC200N Master Stations ......................................................................... 13PK151A, PK152 Power & Control Units ................................................................ 14IR150B Staff and IR155B Patient Stations .............................................................. 14PK800A Secondary Power Supply ........................................................................... 14FZ151 In-Line Fuse Holder ...................................................................................... 14IR151B, IR152B Patient Stations ............................................................................ 15SF155B Emergency and SF156B Code Stations ..................................................... 15LI150B Duty Stations ............................................................................................... 15LI381 Corridor and LI382 Corridor Zone Lights ................................................... 15Replacement Parts .................................................................................................... 16

Illustrations & Wiring DiagramsFigure 1—NC150N and NC200N Control Locations ................................................ 2Figure 2—Duty, Staff, Patient, Emergency & Code Station Control Locations ........ 4Figure 3—Master Panel Housing Chart and Wall Cut-Out Details ......................... 8Figure 4—Panel Removal and Replacement ............................................................. 8Figure 5—Ring and Back Box for IR150B, IR151B, IR152B and IR155B ............. 9Figure 6—Ring and Back Box for SF155B, SF156B, LI150B,

LI381, LI382 and LI382LED .............................................................................. 9Figure 7—SS106 Transformer Installation ............................................................. 10Figure 8—NC150N, NC200N Selector Lamp/Switch

Lens, Filter and Lamp Replacement ................................................................. 13Figure 9—NC150N, NC200N Nurse Call Systems Notes and Electrical Ratings . 17Figure 10—Block Wiring Diagram without Zone Lamps ..................................... 18Figure 11—Block Wiring Diagram with Zone Lamps............................................ 19Figure 12—NC150N, NC200N Wiring Diagram ................................................... 20Figure 13—NC150N, NC200N, Two Stations in Parallel ....................................... 21Figure 14—PK153 Wiring Diagram with Smoke Detector .................................... 22Figure 15—PK153 Wiring Diagram with SF156B Code Station ........................... 23Figure 16—PK151A or PK152 to PK800A Interconnection .................................. 24Figure 17—SK151N Switch Board PCB Assembly ................................................ 25Figure 18—SF337C Cross Reference Diagram ....................................................... 26Figure 19—SF339 Cross Reference Diagram.......................................................... 27Figure 20—NC110N Hookup to NC150N, NC200N .............................................. 28

Table of Contents ————————————————————

iv • IL380 Tek-CARE® NC150 & NC200 Manual Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

What Is It? Static electricity is a result of triboelectric charging of two dissimilarnonconductive materials that are rubbed together, such as rubbing your feet on a carpet ona cold winter day or in a dry climate. The resulting charge is detected when you reach outto touch a doorknob or some other metallic object. The resulting discharge may only bestartling or, in severe cases, it may even be painful. The actual electrical charge is dependanton the materials being rubbed together, humidity, the rate of separation, and other factors.

What Can It Do? While this effect may be disturbing to humans, the effect on electronicequipment is often more serious, ranging from operational disruption to actual componentdamage. These effects result from the high voltages that may be developed. The simple actof walking across a carpet may develop as much as 30,000 volts, and changing a bed sheetmay create a charge of 100,000 volts or more. Such voltages readily cause arcing (thespark that can be observed when you grab a doorknob after walking across a carpet, etc.).The arcing is evidence of the discharge path. Due to the high voltage involved, the dischargecurrent can jump to any nearby metallic or non-metallic object. If the discharge is to orthrough an electronic device, such as the nurse call system, the operation of the device maybe affected. If the discharge current passes through internal components, these componentsmay be damaged or their operation degraded.

What Can We Do About It? The manufacturer of the nurse call equipment has alreadytaken steps to protect the equipment from electrostatic discharge (ESD) effects. However,since the cause is not in the equipment, but in the environment, further measures arerequired of the installer and the user to achieve complete protection.

What The Installer Can Do: In humid climates or in places where the relative humidity iskept at 65% or greater, there will likely be few problems with ESD. Where problems mayoccur the following measures can be taken.

• Ground all exposed metal surfaces. Grounding should be to a #16 gauge or largerconductor.

• Install nurse call system wiring in metal conduit. This conduit may be used to groundpanels.

• Use shielded cable for nurse call system station-to-station wiring. The use of openconductors invites inductive coupling of discharge currents, which can cause thesame problems as direct discharge currents.

• Ground your body before handling system components. This can be done by using awrist strap, or simply by contacting a grounded metal surface. Use caution to avoidhazardous voltages while grounded.

What The User Can Do: The most common generation of ESD in hospitals is due tochanging linen on hospital beds while the patient call cord or pillow speaker is still connectedto the nurse call system. The following precautions will help.

Remove the call cord or pillow speaker from the bed before changing the linen. It will benecessary for the nursing staff to discharge themselves by contacting a grounded metalobject before placing the call cord or pillow speaker back on the bed; otherwise a spark willjump to the nurse call equipment, causing the very damage they are trying to avoid. Toavoid a shock while discharging static electricity on the body, hold a metal object, such asa key, and use that object to contact the grounded surface.

This information is provided to make you aware of ESD problems so that precautions maybe taken to avoid damage and disruption of system operation.

A Word about ESD (Electrostatic Discharge)————————

IL380 Tek-CARE® NC150 & NC200 Manual • 1Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

This section provides complete operating instructions for all Tek-CARE® functions, aswell as reference drawings for use in locating and describing all controls. System operatorsmust read the following operating instructions concerning system equipment and the termsused in conjunction with the equipment.

NC150N, NC200N Master Stations

Refer to Figure 1 for locations, names, and functions of controls and indicators.

Answer Normal Calls:Normal calls are indicated by simultaneous operation of the following signals:

• Steady illumination of the associated station selector lamp which is marked toindicate call origin.

• Steady illumination of call lamp.

• Slowly pulsing audible tone. The audible call signal may be canceled for normal callsby pressing the TONE OFF button. The button will then illuminate to indicate the toneis silenced. Pressing the TONE OFF button when illuminated resets the call tone.

To establish conversation with the calling station, press the associated station selectorbutton. The remote station’s RESET lamp will illuminate. To speak to the caller, pressthe TALK button while speaking and release to listen.

When the conversation is complete, press the associated station selector button to releasethe station. The remote station’s RESET indicator will turn off. Normal calls placed froman IR155B Station must be canceled at the point of origin.

Answer Normal Calls Using Optional TA150N or TA200N Handset:To establish conversation with the calling station, press the associated station selectorbutton. The remote station’s RESET lamp will illuminate. To speak to the caller, lift thehandset from the cradle and begin normal two-way conversation. When the conversationis complete, press the associated station selector button to release the station. The remotestation’s RESET lamp will turn off. Replace the handset in the cradle. Normal callsplaced from an IR155B Station must be canceled at the point of origin.

Answer Emergency Calls:All emergency calls take precedence over any normal call signal. Emergency callsmust be answered in person and can only be canceled from point of origin. Emergencycalls are indicated by simultaneous operation of the following signals:

• Rapid flashing of the associated station selector lamp, which is marked to indicatecall origin.

• Rapid flashing of call lamp.

• Rapidly pulsing audible tone.

Answer Code Calls:All code calls take precedence over any normal or emergency call signal. Code callsmust be answered in person and can only be canceled from point of origin. Code callsare indicated by simultaneous operation of the following signals:

• Very rapid flashing of the associated station selector lamp (twice the rate ofemergency call), which is marked to indicate call origin.

• Very rapid flashing of call lamp (twice the rate of emergency call).

• Very rapidly pulsing audible tone (twice the rate of emergency call).

System Operating Instructions ——————————————

2 • IL380 Tek-CARE® NC150 & NC200 Manual Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

Figure 1—NC150N and NC200N Control Locations

1 – Duty Button: Transfers call tones from master station to a selected patientstation when pressed.

2 – Tone Off Button: Silences normal call tone when depressed.– Tone Off Lamp: Indicates tone silenced when illuminated.

3 – Call Button: Tone call to selected remote when pressed.– Call Lamp: Indicates incoming call when illuminated. Indicates emergency

call when flashing.

4 – Talk Button: Talk when pressed. Listen when released.

5 – Station Selector Buttons (PM150/4N): Establishes conversation path withassociated remote station when depressed.

– Station Selector Lamps: Indicates incoming call from associated remotewhen illuminated. Indicates emergency call from remote when flashing.

6 – Lamp Test Button (ST005D): Illuminates all lamps on panel when pressed.

7 – Telephone Handset (TA150N option): Lift from cradle to use for two-waycommunication.

8 – Telephone Handset (TA200N option): Lift from cradle to use for two-waycommunication.

9 – Group Call Button: Places call to all remote stations represented by row ofselector switches. Paging function only.

10 – Lamp Test Button: Illuminates all lamps on panel when pressed.

11 – Station Selector Buttons (PM200/20N): Establishes conversation path withassociated remote station when depressed.

– Station Selector Lamps: Indicates incoming call from associated remotestation when illuminated. Indicates emergency call from remote when flashing.

Call Tone IntercomVolumeControl

VolumeControl

NC150N, NC200NRear View of

Speaker/Control Panel

NC150N

8 1 2 3 4 9 10 11

NC200N

1 234 5 67

IL380 Tek-CARE® NC150 & NC200 Manual • 3Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

Call a Remote:• Locate the station selector button associated with the remote station to be called. Press

that selector button to establish a conversation path. The remote station’s RESET lampwill illuminate.

• Press the TALK button while speaking, and release button to listen. The remote areamay be monitored by selecting the remote station and releasing the TALK button.

• When conversation or monitoring is complete, press the station selector button torelease it. The remote station’s RESET lamp will turn off. NOTE: Normal andemergency calls will be received even while the NC150N or NC200N MasterStation is in use. The normal audible tone signal will be silenced, but theemergency tone and visual indicators will function as previously described.

Group Call Remote Stations (from NC200N only):• Locate the row of selector buttons for which group call is desired. Press the button

labeled GROUP CALL for that row. The remote stations’ RESET lamps will illuminate.Group call may be selected for only one row at a time.

• Press the TALK button while speaking. NOTE: Group call serves as a pagingfunction only. No reply will be heard.

• When paging or announcement is completed, press the GROUP CALL button so it isreleased. The remote stations’ RESET lamps will turn off.

Activate Nurse Follower Feature:• Press the DUTY button and the associated station selector button to which calls are to

be transferred. All incoming emergency and normal calls to the master station willbe directed to the remote station selected.

• Calls may be answered at the master station only. When answering an emergency ornormal call, depress the DUTY button to release it and follow procedures for answeringcalls as previously described. NOTE: Origination of a call will also be indicatedby associated corridor dome light, if installed.

Test Station Selector Lamp:Press lamp test button (one is included for each panel of station selector button/lamps).All station selector lamps on that panel should illuminate. (See NC150N, NC200NMaster Stations in the System Maintenance Instructions section for proper proceduresand precautions in replacing defective lamps.)

Improper Operation:• If the NC150N or NC200N Master Station fails to operate as described, contact

qualified maintenance personnel. There are no user replaceable parts on the NC150Nor NC200N Master Stations other than the station selector lamps.

• If a malfunction occurs during a call and causes a lack of indication of call origin onthe master station, first determine the origin of the call by observing which corridorlight and corridor zone light is illuminated, then inform qualified personnel.

IR150B Staff Stations

Refer to Figure 2 for locations, names and functions of controls and indicators.

Call the NC150N or NC200N Master Station: Press the CALL button. The call-placed lampwill illuminate to indicate call placement. When the call is answered, the call-placedlamp will go off and the IN USE LED will illuminate to indicate a communication pathhas been established to the master station. Speak in a normal voice.

System Operating Instructions

4 • IL380 Tek-CARE® NC150 & NC200 Manual Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

Figure 2—Duty, Staff, Patient, Emergency & Code Station Control Locations

1 – Call Button: Places a call when pressed.– Call Placed Lamp: Indicates a call is placed when illuminated.

2 – Reset Button: Cancels the call when pressed.– In Use LED: Indicates station is in use when illuminated.

3 – Call Placed Lamp: Indicates a call is placed when illuminated.

4 – Call Cord Jack: Receptacle for SF301A or SF302 call cord.

5 – Plug: Connects call cord to patient station when plugged intocall cord jack.

6 – Call Button: Places a call when pressed, if cord is connectedto patient station.

7 – In Use LED: Indicates station is in use when illuminated.

8 – Reset Switch: Cancels the call when pushed to the left.

9 – Call Cord: Places a call when pulled.

10 – Call Placed Lamp: Indicates a call is placed when flashing.

11 – Call/Cancel Switch: Places a call when pulled down. Cancelsthe call when pushed up.

12 – Call Placed Lamp: Indicates a normal call is placed whenilluminated. Indicates an emergency call when flashing.

13 – Tone Off Switch: Silences normal audible tone signal whenpushed down.

RESET CALL 3

4

2

IR151B Patient Station

RESET CALL

1

2

IR150B Staff Station

IR152B Patient Station

RESET CALL3

4

2

CALL

Tone Off

12

13

LI150B Duty Station

CODEEMERGENCY

10

11

SF155B Emergency & SF156B Code Stations

5

6

SF301A Call Cord

SF302 Call Cord

IR155B Patient Station

RESET CALL

3

9

78

IL380 Tek-CARE® NC150 & NC200 Manual • 5Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

Cancel a Call: Press the RESET button. CALL PLACED lamp will go off.

Improper Operation: Contact qualified service personnel if the station does not operate asdescribed. There are no user serviceable parts on the IR150B Staff Station.

IR151B, IR152B Patient Stations

Refer to Figure 2 for locations, names and functions of controls and indicators.

Call a Nurse: Press the CALL button located on the end of the call cord. The CALL PLACED

lamp will illuminate to indicate call placement. When the nurse answers, the CALL

PLACED lamp will go off and the IN USE LED will illuminate to indicate that a commu-nication path has been established with master station. When the nurse speaks, reply ina normal voice. NOTE: If the call cord is pulled from its receptacle, a call will beplaced automatically and cannot be canceled until the call cord is replaced in thereceptacle.

Cancel a Call: Press the RESET button. The CALL PLACED lamp will go off.

Improper Operation: If the patient station does not operate as described, contact qualifiedservice personnel. There are no user serviceable parts on the IR151B, IR152B PatientStations other than call cords.

IR155B Patient Stations

Refer to Figure 2 for locations, names and functions of controls and indicators.

Call A Nurse: Pull the cord. The CALL PLACED lamp will illuminate to indicate call place-ment. When the nurse answers, the CALL PLACED lamp will go off and the IN USE LEDwill illuminate to indicate that a communication path has been established with themaster station. When the nurse speaks, reply in a normal voice.

Cancel a Call: Call must be canceled at the point of origin. Push the RESET switch to theleft. The CALL PLACED lamp will go off.

Improper Operation: If the station does not operate as described, contact qualified servicepersonnel. There are no user serviceable parts on the IR155B Patient Station.

SF155B Emergency and SF156B Code Stations

Refer to Figure 2 for locations, names and functions of controls and indicators.

Call a Nurse: Pull the call cord, or slide the call/cancel switch down. The CALL PLACED

lamp will flash. Wait for the nurse.

Cancel a Call: Push the call/cancel switch up. The CALL PLACED lamp will go off.

Improper Operation: If the call station does not operate as described, contact qualifiedservice personnel. There are no user serviceable parts on the SF155B Emergency Calland SF156B Code Call Stations.

LI150B Duty Stations

Refer to Figure 2 for locations, names and functions of controls and indicators.

Emergency Calls: Emergency calls are indicated by a flashing CALL PLACED lamp and arapidly pulsing audible tone. The audible tone signal cannot be silenced by the TONE

OFF switch.

System Operating Instructions

6 • IL380 Tek-CARE® NC150 & NC200 Manual Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

System Operating Instructions

Normal Calls: Normal calls are indicated by steady illumination of the CALL PLACED lampand a slowly pulsing audible tone. Push the TONE OFF switch down to silence the audibletone signal. Push the TONE OFF switch up to turn the audible tone signal on.

Improper Operation: If the call station does not operate as described, contact qualifiedservice personnel. There are no user serviceable parts on the LI150B Duty Station.

LI381 Corridor Lights

Emergency Calls: Emergency calls are indicated by rapid flashing of the corridor lightthat is associated with the calling station.

Code Calls: Code calls are indicated by very rapid flashing of the corridor light that isassociated with the calling station.

Normal Calls: Normal calls are indicated by steady illumination of the corridor light thatis associated with the calling station.

Improper Operation: If corridor light does not operate as described, contact qualifiedservice personnel. There are no user serviceable parts on the LI381 Corridor Lightsother than lamps.

LI382. LI382LED Corridor Zone Lights

Emergency Calls: Emergency calls are indicated by rapid flashing of the red corridor zonelight associated with the zone or area from which an emergency call has been placed.

Code Calls: Code calls are indicated by very rapid flashing of the designated corridor zonelight associated with the zone or area from which a code call has been placed.

Normal Calls: Normal calls are indicated by steady illumination of the white corridorzone light associated with the zone or area from which a normal call has been placed.

Concurrent Emergency and Normal Calls: If an emergency and normal call are placed inthe same zone at the same time, the red lamp connected to the emergency station fromwhich a call was placed will flash rapidly, while the white lamp associated with thenormal call will maintain a steady illumination.

Improper Operation: If corridor zone light does not operate as described, contact quali-fied service personnel. There are no user serviceable parts on the LI382 Corridor ZoneLights other than lamps. There are no user serviceable parts on the LI382LED Corri-dor Zone Lights.

IL380 Tek-CARE® NC150 & NC200 Manual • 7Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

System Installation ———————————————————

Installation Procedure

• Read the following instructions concerning system equipment and determine instal-lation methods before proceeding.

• Determine equipment locations.• Install wiring.• Install housing.• Check wires.• Connect equipment.• Check connections.

Equipment Locations

NC150N, NC200N Master Stations: Locate NC150N or NC200N Master Station withineasy reach of operating personnel. Do not exceed operating temperature of 10–30°C.

IR150B Staff Stations: Locate IR150B stations where convenient to operate, but not in thesame room as the NC150N or NC200N Master Station. Do not exceed operating tem-perature range of 10–40°C.

IR151B, IR152B, IR155B Patient Stations: Locate patient stations where convenient foroperation. Do not exceed operating temperature range of 10–40°C.

SF155B Emergency Switch: Locate emergency stations where convenient for operation.Avoid areas where direct contact with water may occur. The SF155B includes a 6' longpull cord permitting installation high enough to provide easy operation by the nurseand by seated or prone patients. The SF155B may be used without the cord as a pull-down actuated switch.

SF156B Code Switch: Locate code stations where convenient for operation. Avoid areaswhere direct contact with water may occur.

LI150B Duty Stations: Locate duty stations as needed and where convenient for opera-tion. Location should provide for unobstructed visibility of the call indicator.

LI381 Corridor Lights: Locate corridor lights in the corridor above or beside the door ofthe associated room. Location should provide for unobstructed visibility of the corridorlight in both directions.

LI382, LI382LED Corridor Zone Lights: Locate corridor zone lights in the corridor areanearest the nurses central monitoring station. Location should provide for unobstructedvisibility of each corridor zone light from the central location.

SF301, SF302 Call Cords: Insert call cord plugs into the associated station jacks as indi-cated on the stations. Call cords provided are 6' or 10' in length.

PK151A, PK152 Power & Control Units: Locate the PK151A or PK152 and IH151NJunction Box in an accessible area. Do not exceed operating temperature range of 10–30°C. Location should provide for convenient cable runs to remote and master stations.Cable run from the PK151A or PK152 to the NC150N or NC200N Master Station mustnot exceed 100'.

PK800A Secondary Power Supply: Locate the PK800A in an accessible area within 2 feetof the PK151A or PK152 that it is to be connected to. Do not exceed operating tempera-ture range of 10–30°C. The PK800A is for use in applications that exceed the currentload capacity of the PK151A or PK152 (1 amp). The PK800A allows the current load tobe increased to 3 amps. The FZ151 Fuse Assembly must be located between the PK800Aand the PK151A or PK152. See Figure 16 for actual FZ151 connection points.

8 • IL380 Tek-CARE® NC150 & NC200 Manual Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

SS100 24 VAC 100 VA Transformer: Locate the SS100 within 3 feet of the PK800ASecondary Power Supply. Do not exceed operating temperature range of 10–30°C.

Wiring Installation

Run wiring conduit from corridor light to corridor light and terminate at the PK151A orPK152 Power & Control Unit. Limit each run to 15 corridor lights, 16 stations and 500feet of wire. Refer to Wiring Diagrams section for additional connection and cablinginformation, starting with Figure 10. Select conduit size to accommodate the followingcables:

• 4 cond. #18 common to all stations (except LI150B Duty Stations). Add 2 cond. #18common if LI382 or LI382LED Corridor Zone Lights are used.

• 2 cond. #22 selective for each IR150B, IR151B, IR152B and IR155B Station in thesystem. Shielded cable must be used.

• 1 cond. #22 selective for each SF155B Emergency Station or SF156B Code Stationnot used in conjunction with a patient station.

• 4 cond. #18 to one LI150B Duty Station.

System Installation

Panel Removal: First remove theself-tapping metal screws located inthe top U-channel just above eachpanel. Then lift up on panel to clearbottom channel. After removal,adequate space is available to graspand remove the remaining panels.

Panel Replacement: Insert top ofpanel into top channel, push panel inat bottom, and release. Panel shouldfall into place in bottom channel.Replace self-tapping metal screws.

Figure 4—Panel Removaland Replacement

Figure 3—Master Panel Housing Chart and Wall Cut-Out Details

Housing Wall OpeningFlush Surface Width (B) Height

OH202 OH302 8.5" 16.25"OH203 OH303 12.5" 16.25"OH204 OH304 16.5" 16.25"OH205 OH305 20.5" 16.25"

16"

B

3.75"

Finished Wall

4" min.

16.25"

B

In masonry walls, install 0.5"×4" woodfillers at top and bottom of opening forhousing attachment.

B

Finished Floor

66"

16.25"

IL380 Tek-CARE® NC150 & NC200 Manual • 9Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

System Installation

Housing Installation

NC150N Master Station:Flush Wall Mounting: Provide wall cutout as shown in Figure 3. Remove panels fromframe as shown in Figure 4. Fit back box and frame assembly into prepared opening.Fasten assembly into place using screws provided in back box. Back box must beTekTone® OH200 Series. Replace panels using the procedure as shown in Figure 4.

Surface Mounting: Remove panels from frame as shown in Figure 4. Fasten box andframe assembly to wall through holes provided in back of box. Use suitable fasteners.Back box must be TekTone® OH300 Series. Replace panels using the procedure asshown in Figure 4.

NC200N Master Station: Desk Mounting: Use TekTone® IH200N series Desk Cabinets.

IR150B, IR151B, IR152B, IR155B Staff and Patient Stations: Ring and back box mustbe UL® approved. Install the back box (Steel City #H3BD with Steel City #3GC plasterring or exact equivalent) as shown in Figure 5 for each station in system. If a smallerback box is desired, use ARCO #2GB with ARCO #3GC ring. Minimum dimensions ofthe back box to be not less than 8.6"×4.5"×2.5". Minimum clearance from live parts onthe station to dead metal parts to be not less than 0.5".

SF155B Emergency and SF156B Code Stations: Install single gang ring (or single gangring/double gang box) as shown in Figure 6 for each emergency or code station insystem. Ring and back box must be UL® approved. Minimum dimensions of back boxto be not less than 4"×4"×1.5". Minimum opening on ring to be not less than 1.75"×2.75".Minimum clearance from live parts on station to dead metal parts to be not less than0.5".

LI150B Duty Stations: Install single gang ring (or single gang ring/double gang box) asshown in Figure 6 for each duty station. Ring and back box must be UL® approved.Minimum dimensions are the same as for the SF155B Emergency Station previouslylisted.

LI381 Corridor Lights and LI382 Corridor Zone Lights: Install double gang ring (ordouble gang ring and box) as shown in Figure 6 for each corridor light in system. Ringand back box must be UL® approved. Minimum dimensions of back box to be not lessthan 4"×4"×1.5". Minimum opening on ring to be not less than 2.75"×2.75". Mini-mum clearance from live parts of station to dead metal parts to be not less than 0.5".

Figure 5—Ring and Back Box for IR150B, IR151B,IR152B and IR155B

Figure 6—Ring and Back Box for SF155B, SF156B,LI150B, LI381, LI382 and LI382LED

Install ring with panel mounting holes at top and bottom, as shown.

10 • IL380 Tek-CARE® NC150 & NC200 Manual Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

System Installation

LI382LED Corridor Zone Light: Install standard one- or two-gang box with one- or two-gang ring as shown in Figure 6 for each corridor light in system. Ring and back boxmust be UL® approved. Minimum clearance from live parts of station to dead metalparts to be not less than 0.5".

PK151A or PK152 Power & Control Unit, IH151N Junction Box: Fasten IH151N Junc-tion Box to wall using suitable fasteners. Mount PK151A or PK152 inside junctionbox. Any alternate junction box must be UL® approved. Minimum dimensions of junc-tion box must be not less than 12"×12"×4". Minimum clearance from live parts to deadmetal parts on housing must be 1".

Install SS106 Transformer in junction box as shown in Figure 7. Do not connecttransformer primary to power source until entire installation is completed and checkedfor shorts and grounds.

Install transformer connection box as shown in Figure 7. Transformer box must beUL® approved. Minimum dimensions must be not less than 1.75"×3.75"×1.5". Thejunction box, transformer and power & control unit are also available preassembledfrom the factory as part number IH151NK.

PK800A Secondary Power Supply: Fasten PK800A Secondary Power Supply to wall us-ing suitable fasteners.

SS100 24 VAC 100 VA Transformer: Fasten SS100 24 VAC 100 VA Transformer to wallusing suitable fasteners. Do not connect transformer primary to power source untilentire installation is completed and has been checked for shorts and grounds.

Wire Checkout

Use an ohmmeter or other continuity checking device to test wires for shorts or grounds. Ifshorts or grounds are encountered, find and correct the problem before continuing. Makesure minimum number of conductors needed for all of the equipment being used in thesystem are available.

Figure 7—SS106 Transformer Installation

IL380 Tek-CARE® NC150 & NC200 Manual • 11Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

System Installation

Wire Connections

Use crimp-style connectors for all wire connections. Do not use wire nuts.

NC150N, NC200N Master Stations: No internal wiring is necessary for the NC150N andNC200N Master Stations.

IR150B, IR151B, IR152B, IR155B Staff and Patient Stations: Connect wires as shownin Figure 12.

SF155B Emergency Stations: Connect wires as shown in Figure 12.

SF156B Code Stations: Connect wires as shown in Figure 15.

LI150B Duty Stations: Connect wires as shown in Figure 12.

LI381 Corridor Lights, LI382 and LI382LED Corridor Zone Lights: Connect wires asshown in Figure 12.

PK151A, PK152 Power & Control Unit: Connect wires as shown in Figure 12. Alsoconnect secondary from the SS106 Transformer (24 VAC, 30 VA connections) to thePK151A or PK152 as shown in Figure 12. Do not connect transformer primary topower source until entire installation is completed and has been checked for shorts andgrounds.

PK800A Secondary Power Supply: Connect wires as shown in Figure 16.

SS100 24 VAC 100 VA Transformer: Connect wires as shown in Figure 16. Do not con-nect transformer primary to power source until entire installation is completed and hasbeen checked for shorts and grounds.

Connections Checkout

Recheck all connections to equipment. If all wires and connections are satisfactory, connectprimary coil of SS106 Transformer to source of 117 VAC 60 Hz (40 watts max.) andoperation of system can be checked according to System Test Instructions next in thissection.

System Test Instructions

Before proceeding with a system test, set all stations to normal conditions as follows:

NC150N and NC200N Master Stations: All push buttons should be in the OUT position. Adepressed button may be released by pressing the button and then releasing it.

IR150B Staff Station: If the CALL PLACED lamp is illuminated, press the RESET button toreset it.

IR151B, IR152B Patient Stations: Insert a call cord in each call cord jack. If the CALL

PLACED lamp is illuminated, press the RESET button to reset it.

IR155B Patient Stations: If the call cord has been pulled, reset the station by pushing thereset switch to the left.

SF155B Emergency or SF156B Code Stations: If the pull cord has been pulled, or theswitch had been pulled down, reset the station by pushing the switch up.

LI150B Duty Stations: Push the TONE OFF switch up.

12 • IL380 Tek-CARE® NC150 & NC200 Manual Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

System Installation

System Checkout and Testing

IR151B, IR152B, IR155B Patient Stations: Test patient stations one at a time. Initiate acall on each patient station: Press the button on the end of the call cord for IR151B andIR152B Patient Stations (test both circuits on IR152B stations). Pull the call cord on theIR155B.

Check for operation of the following signals:• The CALL PLACED lamp on the patient station should be illuminated.• The LI381, LI382 or LI382LED Corridor Light near the room entrance should be

illuminated.• On the NC150N or NC200N Master Station, the call lamp should be illuminated and

the associated station selector lamp (marked to identify the calling station) should beilluminated. A slowly repeating audible call tone should be heard. The normal calltone may be silenced by the TONE OFF button, which should be illuminated to indicatetone silencing.

• On all LI150B Duty Stations, the CALL PLACED lamp should be illuminated, and aslowly repeating audible call tone should be heard. The normal call tone may besilenced by the TONE OFF switch.

Reset the call at the patient station: Press the RESET button on IR151B and IR152BStations. Push the RESET switch to the left on IR155B Stations. All signals should becanceled.

Test the intercom function:• Initiate a call on each station as previously described.• On the master station, select the calling station by pressing the illuminated station

selector button and check for the following:1. The STATION SELECTOR lamp should be canceled.2. The CALL lamp should turn off.3. The audible call tone should be canceled.4. The remote station’s IN USE LED should be illuminated.

• Press the CALL button and the TALK button on the master station. An electronic calltone should be heard at the master station and at the patient station.

• Press the TALK button and speak in a normal voice. Release the button to hear the reply.• At the patient station, the CALL PLACED lamp should turn off, and the IN USE LED

should be illuminated.• When voice communication is heard, reply in a normal voice.• Return all controls to the normal position.

On each IR150B Staff Station, test operation the same as with the IR151B Patient Station,except place a call using the CALL button instead of a call cord.

On each SF155B Emergency or SF156B Code station (one at a time), slide the callswitch down, and then check the following signals:• The CALL PLACED lamp should be flashing.• The LI381, LI382 or LI382LED Corridor Light near the room entrance should be

flashing.• On the master station, the CALL lamp should be flashing, the associated station

selector lamp (marked to identify calling station) should be flashing, and anintermittent audible call tone should be heard. The TONE OFF button must not cancelthe emergency code call tone.

On all LI150B Duty Stations, check the following signals:• The CALL PLACED lamp should be flashing.• The rapidly pulsing audible call tone should be heard. The TONE OFF switch must not

cancel the emergency call tone.

IL380 Tek-CARE® NC150 & NC200 Manual • 13Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

System Maintenance Instructions —————————————Most of the equipment and parts used in the NC150N and NC200N Nurse Call Systemsare not user serviceable and cannot be replaced or repaired by the end user. Equipmentmust be repaired by qualified service personnel only. Parts which are user serviceable arelisted in the following sections and their replacement explained.

NC150N, NC200N Master Stations

There are several user serviceable parts in the NC150N and NC200N Master Stations.Only one of these parts is electrically operated. The user serviceable parts and replacementprocedures are explained below.

Refer to Figure 8 to identify replacement switch parts. A full list of replacement parts andnumbers appears in the Replacement Parts section.

Selector Lamp/Switch Lens Replacement:• Remove lens by squeezing top and bottom together and pulling away from panel.• Replace with same color lens by pushing new lens towards panel. The lens should

snap into place on the selector lamp/switch knob with a noticeable click.

Selector Lamp/Switch Filter Identification:• Remove lens by squeezing top and bottom together and pulling away from panel.• Remove white filter by lifting it out of selector lamp/switch knob.• Identify filter by room number or other means using dry transfer lettering, labels, or

other similar methods. Be sure identified filter is replaced in knob so that letteringis readable right side up.

Defective Lamp Replacement:• Remove lens and filter by method described above.• Using needle-nosed pliers, tweezers or similar tool, pull lamp out of socket by

gripping lamp at sides and moving it from side to side as it is pulled away from thepanel. WARNING: Do not squeeze too tightly, or it will break.

• Replace lamp by holding with tool and pushing into socket. Be sure lamp is turnedso that the base is lined up with the slot in the socket. Lamp must be pushed in belowthe level of the filter.

• Push test button to make sure lamp has been placed in socket properly. If lamp doesnot light, try pressing more firmly into socket. If lamp still does not light, repeat stepsabove with new lamp until one works properly.

• Replace lens and filter in lamp/switch knob as previously described.

Figure 8—NC150N, NC200NSelector Lamp/Switch Lens,

Filter and Lamp Replacement1

2

3

4

1 – Lens

2 – Filter

3 – 24V Lamp

4 – Switch Knob

14 • IL380 Tek-CARE® NC150 & NC200 Manual Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

System Maintenance Instructions

Defective Handset Replacement:• To remove handset from panel, grip end of modular plug on the handset cord firmly

and squeeze until cord is easily pulled straight away from panel.• To replace handset, hold end of plug on the handset cord, squeeze and push straight

into jack on panel. Release and plug will click into place.• To test handset, initiate a call to a remote station. The handset should operate as

described above.

PK151A, PK152 Power & Control Units

There are no user serviceable parts in the PK151A and PK152 Power & Control Units.Notify qualified service personnel for repair or replacement.

IR150B Staff and IR155B Patient Stations

There are no user serviceable parts on these stations. Notify qualified service personnel forrepair or replacement.

PK800A Secondary Power Supply

The only user serviceable part is a 4A, 125 VAC fuse (1.25"×0.25").

• Disconnect power to the associated SS100 transformer. If the SS100 is hard wired,locate the associated breaker and turn it off. If a means cannot be established toremove power to the SS100, then contact qualified service personnel and do notproceed further. The SS106 powering the associated PK151A or PK152 should alsobe powered down in the same fashion.

• Once power has been disconnected, firmly grasp the black fuse holder knob on theside of the PK800A, push in and rotate it counterclockwise. Pull out on the knob andthe fuse will be exposed.

• Remove the fuse and insert the new fuse. Reinsert fuse holder knob. Restore powerto the system.

For repair or replacement of any other parts, contact qualified service personnel. A list ofreplacement parts and numbers appears in the Replacement Parts section.

FZ151 In-Line Fuse Holder

The only user serviceable part is a 4A, 125 VAC fuse (1.25"×0.25").

• Disconnect power to the associated SS100 transformer. If the SS100 is hard wired,locate the associated breaker and turn it off. If a means cannot be established toremove power to the SS100, then contact qualified service personnel and do notproceed further. The SS106 powering the associated PK151A or PK152 should alsobe powered down in the same fashion.

• Once power has been removed, firmly grasp both ends of the fuse holder, push in androtate in opposite directions. Pull out on both ends and the fuse will be exposed.

• Remove the fuse and insert the new fuse. Put fuse holder back together and verify thatboth pieces are interlocked. Restore power to the system.

For repair or replacement of any other parts, contact qualified service personnel. A list ofreplacement parts and numbers appears in the Replacement Parts section.

IL380 Tek-CARE® NC150 & NC200 Manual • 15Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

System Maintenance Instructions

IR151B, IR152B Patient Stations

The only user serviceable part on these stations is the call cord. To replace:

• To remove the call cord, grip end of plug firmly and pull straight away from patientstation.

• To replace the call cord, hold by end of plug and push straight into call cord jack onpatient station.

• To test, push the button at the end of the call cord. The CALL PLACED lamp shouldilluminate. Push the RESET button to cancel the call.

For repair or replacement of any other parts, contact qualified service personnel. A list ofreplacement parts and numbers appears in the Replacement Parts section.

SF155B Emergency and SF156B Code Stations

There are no user serviceable parts on these stations. Notify qualified service personnel forrepair or replacement.

LI150B Duty Stations

There are no user serviceable parts on these stations. Notify qualified service personnel forrepair or replacement.

LI381 Corridor and LI382 Corridor Zone Lights

• To remove cover, grip firmly by sides, and pull cover away from plate.

• To remove bulb, make sure that no call is placed, then push bulb in towards plate.Turn bulb counterclockwise and pull bulb out of socket. On LI382, remove red bulbcover before removing bulb.

• To replace bulb, hold by glass part and push metal end into socket. When resistanceis encountered, turn bulb clockwise until it falls into socket. (Metal part should bebelow the top of the socket.) Push bulb again and turn clockwise until bulb stopsturning, and then release. On LI382, replace red bulb cover. Be sure to place bulbcover over the same bulb from which it was removed.

• To test light, place call at the associated station. If light still does not work, repeatsteps above until corridor lamp and/or corridor zone lamps function properly.

• To replace cover, reverse instructions for removal.

16 • IL380 Tek-CARE® NC150 & NC200 Manual Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

System Maintenance Instructions

Replacement Parts

Part No. Description Used ForFZ010 4A Fuse PK800A Secondary Power Supply and FZ151 Fuse Asst.LI014 24V Lamp NC150N, NC200N Control and Selector Module LampsLI028 28V Lamp LI381, LI382 Corridor LightsRP021 Blank Filter NC150N, NC200N Selector Button LabelRP022 Orange Lens NC150N, NC200N Call and Selector ButtonsRP024 Green Lens NC150N, NC200N Talk ButtonRP027 Clear Lens NC150N, NC200N Duty ButtonRP028 Yellow Lens NC150N, NC200N Tone Off ButtonRP037A Red Bulb Cover LI382 Corridor Zone LightsSF301 Call Cord IR151B, IR152BSF302 Dual Call Cord IR151B, IR152BTA150N Handset NC150N Master StationTA200N Handset NC200N Master Station

IL380 Tek-CARE® NC150 & NC200 Manual • 17Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

Electrical Ratings (Maximum):NC150N/NC200N Master Station ................ 24 VDC, .36 ampsPK151A Power & Control Unit ........24 VAC, 60 Hz, 1.25 ampsPK152 Power & Control Unit ..........24 VAC, 60 Hz, 1.25 ampsIR150B Staff Station .................................... 24 VDC, .09 ampsIR151B Patient Station ................................ 24 VDC, .09 ampsIR152B Patient Station ................................ 24 VDC, .09 ampsIR155B Patient Station ................................ 24 VDC, .09 ampsSF155B Emergency Station ........................ 24 VDC, .03 ampsSF156B Code Station .................................. 24 VDC, .06 ampsLI150B Duty Station ..................................... 24 VDC, .03 ampsLI381 Corridor Light ..................................... 24 VDC, .06 ampsLI382 Corridor Zone Light .......................... 24 VDC, .068 ampsLI382LED Corridor Zone Light..................... 24 VDC, .08 ampsPK800A Secondary Power Supply ...................24 VAC, 60 Hz

Wiring Notes:1. Selector switch shown is representative of both NC150N and NC200N

Master Stations.

2. Terminal identifications shown are not in actual order.

3. Main supply circuit: Connect to 117 VAC, 60 Hz (40 watts max). Use18 gauge wire minimum. SS106 Transformer rating is 24 VAC, 30 VA max.

4. Use shielded cable if not in a metal conduit. If shielded cable is used, shielddrain wire replaces conductor connected to Terminal C on TALK/LISTEN switchmodule.

5. All wiring is #18 gauge unless otherwise specified.

6. System wire description:

C = Audio commonR = Normal callP = +24 VDCQ = Emergency commonX = Audio selectiveL = Lamp wire selective

Figure 9—NC150N, NC200N Nurse Call SystemsNotes and Electrical Ratings

18 • IL380 Tek-CARE® NC150 & NC200 Manual Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

Figure 10—Block Wiring Diagram without Zone Lamps

Trunk Cable4 #18. These conductors are common to all rooms. (NOT

individual home runs.) Maximum 15 corridor lights, 16stations and 500' per run.

Point Pair2 #22 shielded per room, home run to the master. Shield

not required if run in metal conduit. Shield must becontinuous (no physical gaps) to IR station.

If shielded wire is used, the shield replaces the “C” lineon each station (terminated at “C” terminal); and theshield can be ground at master end only.

If metal conduit is used, the conduit must be continuous(no physical gaps); it must contain only intercom wiring;and it should not be ground at multiple locations.

MASTER STATION

PK151N / PK151A / PK152POWER & CONTROL UNIT

6 #18

POINTPAIRS TRUNK

(4 #18)

SS106TRANSFORMER

2 #18

IR

STATIONSERIES

SF

STATIONSERIES

SF

STATIONSERIES

SF

STATIONSERIES

IR

STATIONSERIES

DOMELIGHT

DOMELIGHT

TRUNK &POINT PAIR

TRUNK &POINT PAIR

SF

STATIONSERIESDOME

LIGHTTRUNK &

POINT PAIR

IR

STATIONSERIES

3 #22 plus

DOMELIGHT

TRUNK &POINT PAIR

IR

STATIONSERIES

SF

STATIONSERIESDOME

LIGHTTRUNK &

POINT PAIR

3 #22

4 #22 plus 4 #22 4 #22

4 #22 plus 3 #22 plus

4 #22 plus

TRUNK CABLEPOINT PAIR

SYSTEMTO

MASTER

4 #18

<OVERHEAD VIEW OF HOSPITAL CORRIDOR>

SF

STATIONSERIES

SF

STATIONSERIES

IR

STATIONSERIESDOME

LIGHTTRUNK &

POINT PAIR

4 #22 plus 4 #22 plus 3 #22 plus

4 #22 POINT PAIR

POINT PAIR POINT PAIR

POINT PAIR

POINT PAIR POINT PAIR POINT PAIR

POINT PAIR

100'MAX

Drawing Name & Number: IL380 NC150N NC200N Block Diagram 1 Rev3 100610 1

IL380 Tek-CARE® NC150 & NC200 Manual • 19Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

Trunk Cable6 #18 (4 #18 + 2 #18 for zone pair). The two additional conductors

extend from zone lamp through corridor. These conductors arecommon to all rooms. (NOT individual home runs.) Maximum 15corridor lights, 16 stations and 500' per run.

Point Pair2 #22 shielded per room, home run to the master. Shield

not required if run in metal conduit. Shield must becontinuous (no physical gaps) to IR station.

If shielded wire is used, the shield replaces the “C”line on each station (terminated at “C” terminal); andthe shield can be ground at master end only.

If metal conduit is used, the conduit must be continuous(no physical gaps); it must contain only intercom wiring;and it should not be ground at multiple locations.

Figure 11—Block Wiring Diagram with Zone Lamps

TRUNK CABLEPOINT PAIR

SYSTEM

ZONELAMP

TO

MASTER

<OVERHEAD VIEW OF HOSPITAL CORRIDOR>

IR

STATIONSERIES

SF

STATIONSERIES

SF

STATIONSERIES

SF

STATIONSERIES

IR

STATIONSERIES

DOMELIGHT

DOMELIGHT

SF

STATIONSERIESDOME

LIGHT

IR

STATIONSERIES

4 #22 plus

DOMELIGHTTRUNK &

POINT PAIR

IR

STATIONSERIES

SF

STATIONSERIESDOME

LIGHT

4 #22

6 #22 plus 5 #22

6 #22 plus 4 #22 plus

6 #22 plus 5 #22 5 #22

4 #183 #18

6 #18

ONE TRUNK COMMON, "P" PLUSTWO ZONE LIGHT COMMONS

SF

STATIONSERIES

SF

STATIONSERIES

IR

STATIONSERIESDOME

LIGHT

6 #22 plus 6 #22 plus 4 #22 plus

ZONE PAIR,

TRUNK &POINT PAIR

ZONE PAIR,

TRUNK &POINT PAIR

TRUNK &POINT PAIR

TRUNK &POINT PAIR

TRUNK &POINT PAIR

MASTER STATION

PK151N / PK151A / PK152POWER/CONTROL UNIT

6 #18

POINTPAIRS

TRUNK(4 #18)

SS106TRANSFORMER

2 #18

POINT PAIR

POINT PAIR POINT PAIR

POINT PAIR

POINT PAIR POINT PAIR POINT PAIR

POINT PAIR

100' MAX.

Drawing Name & Number: IL380 NC150N NC200N Block Diagram 2 Rev3 100610 1

20 • IL380 Tek-CARE® NC150 & NC200 Manual Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

Fig

ure

12—

NC

150N

, NC

200N

Wir

ing

Dia

gra

m

SW

ITC

H M

OD

ULE

UN

JE

J D R R P T1 N Q E

P F VQ L

P X C 1 2 3

Red

Whi

te

R PC

omm

onW

ires

Q

See

SS

106

PK

151N

/ P

K15

1A /

See

Not

e3

TALK

/LIS

TEN

EN

CLO

SU

RE

MA

STE

R S

T ATI

ON

NC

150N

/200

N

EN

CLO

SU

RE

EQ

UIP

ME

NT

CE

NTR

AL

SE

LEC

TOR

MO

DU

LE

TER

MIN

AL

MO

DU

LE

LI38

1

N Q

J D P E

IR15

0N/1

51N

/152

N/1

53N

/155

N

LI38

1

NO

TES

1. S

elec

tor s

witc

h m

odul

e sh

own

is re

pres

enta

tive

of N

C15

0N m

aste

r sta

tion.

3. M

ain

supp

ly c

ircui

t: c

onne

ct to

117

VA

C, 6

0 H

z (4

0 w

atts

max

.).

U

se 1

8 ga

uge

wire

min

imum

. SS

106

Tran

sfor

mer

ratin

g is

24

VA

C, 3

0 V

A m

inim

um.

2 . T

erm

inal

iden

tific

atio

ns s

how

n ar

e no

t in

actu

al o

rde r

.

4. U

se s

hiel

ded

cabl

e if

not i

n a

met

al c

ondu

it. If

shi

elde

d ca

ble

is u

sed,

NO

. 22

NO

. 18

NO

. 18

LI38

2 or

LI3

82LE

D

SF1

51N

SF1

53N

G

T 2PS

F155

B

LI38

1

LI38

1

BR

OW

N (P

)

RE

D (Q

)

OR

AN

GE

(F)

YE

LLO

W (V

)

GR

EE

N (L

)

BLU

E (N

.U.)

BR

OW

N (P

)

RE

D (Q

)

OR

AN

GE

(F)

YE

LLO

W (V

)

GR

EE

N (L

)

BLU

E (N

.U.)

P L YC XR

R L N

BR

OW

N (P

)

RE

D (Q

)

OR

AN

GE

(F)

YE

LLO

W (V

)

GR

EE

N (L

)

BLU

E (N

.U.)

C

CD

PP

1N

O. 1

8

LL

XL

LX

LL

XL

LX

XXX

X

shie

ld w

ire re

plac

es c

ondu

ctor

con

nect

ed to

ter

min

al C

on

talk

/Lis

ten

mod

ule

on N

C15

0N.

5. U

se 1

8 ga

uge

wire

for o

ptio

nal L

I382

, LI3

82LE

D z

one

lIght

wiri

ng.

SH

IELD

ED

SE

E N

OTE

4

Cha

ssis

gro

und

Not

e 5

SF1

55B

SF1

55B

& IR

157N

LI15

0N/L

I150

B

Sta

nd A

lone

Con

figur

atio

nC

ombi

ned

Con

figur

atio

n

Com

bine

d C

onfig

urat

ion

Com

bine

d C

onfig

urat

ion

IR15

0B/1

51B

/152

B/1

55B

Pow

er &

Con

trol U

nit

PK

152

IL38

0 N

C15

0N N

C20

0N W

iring

Rev

11 0

3041

1 1

Zone

Lig

ht

IL380 Tek-CARE® NC150 & NC200 Manual • 21Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

Fig

ure

13—

NC

150N

, NC

200N

, Tw

o S

tati

on

s in

Par

alle

l

Sw

itch

Mod

ule

UN

JE

J D R R P T1 Q E

Red

Wh i

te

RC

omm

onW

ires

QSee

SS

106

TALK

/LIS

TEN

Mas

ter S

tatio

n E

nclo

sure

NC

150N

/200

NC

entra

l Equ

ipm

ent

SE

LEC

TOR

MO

DU

LE

T ER

MIN

AL

MO

DU

LE

N Q

J D P E

IR15

0N/1

51N

/152

N/1

53N

/155

N

NO

TES

1. S

elec

tor s

witc

h m

odul

e sh

own

is re

pres

enta

tive

of N

C15

0N m

aste

r sta

tion.

3. M

ain

supp

ly c

ircui

t: C

onne

ct to

117

VA

C, 6

0 H

z (4

0 w

atts

max

.). U

se 1

8 ga

uge

wire

min

imum

.

SS

106

Tran

sfor

mer

ratin

g is

24

VA

C, 3

0 V

A m

inim

um.

2. T

erm

inal

iden

tific

atio

ns s

how

n ar

e no

t in

actu

al o

rder

.

4. U

se s

hiel

ded

cabl

e if

not i

n a

met

al c

ondu

it. If

shi

elde

d ca

ble

is u

sed,

shi

eld

wire

repl

aces

No.

22

No.

18

No.

18

LI38

2, L

I382

LED

T2PS

F155

B

LI38

1

BR

OW

N (P

)

RE

D (Q

)

OR

AN

GE

(F)

YE

LLO

W (V

)

GR

EE

N (L

)B

LUE

(N.U

.)

P YC XRP L YC XR

C

CD

PP

1N

o. 1

8

LL

XL

LX

LL

XL

LX

XXX

X

cond

ucto

r con

nect

ed to

ter

min

al C

on

talk

/Lis

ten

mod

ule

on N

C15

0N.

5. U

se 1

8 ga

uge

wire

for o

ptio

nal L

I382

, LI3

82LE

D z

one

lIght

wiri

ng.

Shi

elde

d, S

ee N

ote

4 Cha

ssis

gro

und

Not

e 5

LI15

0N/L

I150

B

Com

bine

d C

onfig

urat

ion

Com

bine

d C

onfig

urat

ion

IR15

0N/1

51N

/152

N/1

53N

/155

N

NO

TE: D

iode

s ar

e 1N

4003

type

.

IL38

0 IL

381

NC

150N

NC

200N

2 S

tatio

ns P

aral

lel R

ev5

0303

11 1

Enc

losu

re

See

Not

e 3

P

N

L

PK

151N

/ P

K15

1A /

Pow

er &

Con

trol U

nit

PK

152

Zone

Lig

ht

22 • IL380 Tek-CARE® NC150 & NC200 Manual Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

Fig

ure

14—

PK

153

Wir

ing

Dia

gra

m w

ith

Sm

oke

Det

ecto

r

EN

CLO

SU

RE

MA

STE

R S

TATI

ON

NC

150N

/200

N

EN

CLO

SU

RE

EQ

UIP

ME

NT

CE

NTR

AL

LI38

2 or

LI3

82LE

D

Com

bine

d C

onfig

urat

ion

J D R R P T 1 N Q E

24V

AC

SS

106

PK

151N

/ P

K15

1A /

PK

152

N QT2P

Pow

er &

Con

trol U

nit

E2 D2

E1

D1

P1

P N J1 J2

PK

153

P1

Con

trol u

nit

E J PD

LI15

0N

V

LI15

0B

V R P Q

N.O

.

N.O

.N

.C. W

HIT

E

RE

D

SF1

55B

LI38

1

BR

OW

N (P

)

RE

D (Q

)

OR

AN

GE

(F)

YE

LLO

W (V

)

GR

EE

N (L

)

BLU

E (N

.U.)

Com

bine

d C

onfig

urat

ion

N.O

.N

.C.

Sm

oke

Det

ecto

rS

mok

e D

etec

tor

SW

ITC

H M

OD

ULE

UN

JE

TALK

/LIS

TEN

SE

LEC

TOR

MO

DU

LE

T ER

MIN

AL

MO

DU

LE

CD

PP

1

LL

XL

LX

LL

XL

LX

XXX

X

IR15

0B/1

51B

/152

B/1

55B

C

NO

TES

:1.

Thi

s dr

awin

g to

be

used

as

a su

pple

men

t to

the

stan

dard

NC

150N

/200

N w

iring

dia

gram

and

wiri

ng n

otes

.2.

The

NC

150N

/200

N p

rovi

de o

nly

anci

llary

ann

unci

atio

n of

fire

sig

nals

.

Cha

ssis

gro

und

SF1

55B

LI38

1

BR

OW

N (P

)

RE

D (Q

)

OR

AN

GE

(F)

YE

LLO

W (V

)

GR

EE

N (L

)

BLU

E (N

.U.)

Com

bine

d C

onfig

urat

ion

IR15

0B/1

51B

/152

B/1

55B

SF1

55B

BR

OW

N (P

)

RE

D (Q

)

OR

AN

GE

(F)

YE

LLO

W (V

)

GR

EE

N (L

)

BLU

E (N

.U.)

IL38

0 P

K15

3 W

iring

Rev

10 0

1141

1 1

IR15

0B/1

51B

/152

B/1

55B

SF1

55B

BR

OW

N (P

)

RE

D (Q

)

OR

AN

GE

(F)

YE

LLO

W (V

)

GR

EE

N (L

)

BLU

E (N

.U.)

IL380 Tek-CARE® NC150 & NC200 Manual • 23Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

Fig

ure

15—

PK

153

Wir

ing

Dia

gra

m w

ith

SF

156B

Co

de

Sta

tio

n

EN

CLO

SU

RE

MA

STE

R S

TAT I

ON

NC

150N

/200

N

EN

CLO

SU

RE

EQ

UIP

ME

NT

CE

NTR

AL

LI38

2 or

LI3

82LE

D

Com

bine

d C

onfig

urat

ion

J D R R P T1 N Q E

2 4V

AC

SS

106

PK

151A

/ P

K15

2

N QT2P

Pow

er/C

ontro

l uni

t

E2 D2

E1

D1

P1

P N J1 J2

PK

153

P1

Con

trol u

nit

E J PD

LI15

0N

V

LI15

0B

V R P Q

WH

ITE

RE

D

SF1

55B

LI38

1

BR

OW

N (P

)

RE

D (Q

)

OR

AN

GE

(F)

YE

LLO

W (V

)

GR

EE

N (L

)

BLU

E (N

.U.)

Com

bine

d C

onfig

urat

ion

NO

TES

:

SW

ITC

H M

OD

ULE

UN

JE

TALK

/LIS

TEN

SE

LEC

TOR

MO

DU

LE

TER

MIN

AL

MO

DU

LE

CD

PP

1

LL

XL

LX

LL

XL

LX

XXX

X

IR15

0N/1

51N

/152

N/1

53N

/155

N

P F VQ LGP L YC XR

IR15

0B/1

51B

/152

B/1

55B

SF1

51N

SF1

53N

C

LI38

1

Sm

oke

dete

ctor

BR

OW

N (P

)

RE

D (Q

)

OR

AN

GE

(F)

YE

LLO

W (V

)

GR

EE

N (L

)

BLU

E (N

.U.)

SF1

56B

LI38

1

Sta

nd A

lone

Con

figur

atio

nS

tand

Alo

ne C

onfig

urat

ion

N.O

.N

.C.

SF1

56B

BR

OW

N (P

)

RE

D (Q

)

OR

AN

GE

(F)

YE

LLO

W (V

)

GR

EE

N (L

)

BLU

E (N

.U.)

P F VQ LG

SF1

56

1. T

his

draw

ing

to b

e us

ed a

s a

supp

lem

ent t

o th

e st

anda

rdN

C15

0N/2

00N

wiri

ng d

iagr

am a

nd w

iring

not

es.

2. T

he N

C15

0N/2

00N

pro

vide

onl

y an

cilla

ry a

nnun

ciat

ion

of fi

re s

igna

ls.

Cha

ssis

gro

und

IL38

0 P

K15

3 W

iring

2 R

ev8

0114

11 1

24 • IL380 Tek-CARE® NC150 & NC200 Manual Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

Fig

ure

16—

PK

151A

or

PK

152

to P

K80

0A In

terc

on

nec

tio

n

J D R R P T1 N Q E

24V

AC

SS

100

PK

800A

N QT2P

Pow

er s

uppl

yP

K15

1A /

PK

152

Con

trol u

nit

Fuse

Ass

y.

Mou

nt w

ithin

2 fe

et o

f eac

h ot

her.

Not

e:

T1 a

nd T

2 in

puts

whe

n in

terc

onne

ctin

g P

K80

0AS

econ

dary

Pow

er S

uppl

y!

Do

not c

onne

ct S

S10

6 Tr

ansf

orm

er to

PK

151A

/PK

152

Gro

und

Gro

und

Gro

und

Gro

und

24V

AC

24V

AC

24V

DC

24V

DC

24V

DC

5VD

C

5VD

C

5VD

C

To m

aste

r

To fi

eld

IL38

1 P

K15

1A P

K80

0A In

terc

onne

ctio

n R

ev5

0301

11

J D E P N R Q P

4A F

ast-B

low

INLI

NE

All

wiri

ng s

how

n is

18-

gaug

e.

IL380 Tek-CARE® NC150 & NC200 Manual • 25Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

Figure 17—SK151N Switch Board PCB Assembly

26 • IL380 Tek-CARE® NC150 & NC200 Manual Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

Bro

wn

Red

Ora

nge

Yel

low

Gre

en

Blu

e

on s

tatio

n

P Not

use

d

Q QLV

7 pi

n co

nnec

tor

Pur

ple

F NO

TE: B

oth

jum

pers

on

back

of s

tatio

nne

ed to

be

in u

p po

sitio

n!

DR

AW

ING

#: IL

380

IL38

1 S

F337

C W

IRIN

G R

EV

1 09

1603

1

EM

ER

GE

NC

Y

Not

e: B

oth

Ora

nge

& B

lue

wir

es a

re

conn

ecte

d to

"Q

" co

mm

on

and

mus

t be

conn

ecte

d to

geth

er.

Fig

ure

18—

SF

337C

Cro

ss R

efer

ence

Dia

gra

m

IL380 Tek-CARE® NC150 & NC200 Manual • 27Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

Bro

wn

Red

Ora

nge

Yel

low

Gre

en

Blu

e

on s

tatio

n

P Not

use

d

Q QLV

7 pi

n co

nnec

tor

Pur

ple

F

NO

TE: B

oth

jum

pers

on

back

of s

tatio

nne

ed to

be

in u

p po

sitio

n!

Bro

wn

Red

Ora

nge

Yel

low

Gre

en

Blu

e

on s

tatio

n

P Not

use

d

Q QLV

7 pi

n co

nnec

tor

Pur

ple

F

NO

TE: B

oth

jum

pers

on

back

of s

tatio

nne

ed to

be

in u

p po

sitio

n!

DR

AW

ING

#: IL

380

IL38

1 S

F339

WIR

ING

RE

V3

0916

03 1

Not

e: B

oth

Ora

nge

& B

lue

wir

es a

re

conn

ecte

d to

"Q

" co

mm

on

and

mus

t be

conn

ecte

d to

geth

er.

Fig

ure

19—

SF

339

Cro

ss R

efer

ence

Dia

gra

m

28 • IL380 Tek-CARE® NC150 & NC200 Manual Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.

Figure 20—NC110N Hookup to NC150N, NC200N

MODULE

J D E E1

L L L L

N N P P

CONTROL

ENCLOSUREMASTER STATION

NC110N

SELECTOR MODULE

TERMINAL MODULE

D

J

E

N

PK151A / PK152

L

L

L

TOSELECTIVE LAMP

WIRE ONNC150N, NC200N

NC150N, NC200NTO

PK151A / PK152NC110NTO

N

P

IL381 NC110N NC150N NC200N Hookup Rev2 100110 1

#22

#18

#18

PK and NC150N/NC200Nmust not exceed 100'.

Total wire distance between