telcoasis iase evaporative cooling systems · munters indirect air-side economizer (iase) has the...
TRANSCRIPT
Munters Indirect Air-Side Economizer (IASE) has the potential to outperform current cooling strategies while offering some key system advantages. With over 35 years of experience in air-to-air heat exchangers and evaporative cooling, Munters advanced cooling systems provide the desired cooling results using significantly less energy than standard air conditioning.
The TelcOasis™ IASE uses an indirect evaporative cooling system to cool the return air. Munters indirect evaporative cooler is constructed of patented polymer tubes, elliptical in shape, and sealed into headers at both ends. The tubes are flexible and shed mineral scale deposits that form during the evaporation process. Water is sprayed over the exterior of the tubes while the warm data center air flows through the inside of the tubes. The data center air never comes in contact with water. Supply fan motors are equipped with variable speed controls allowing the supply airflow from the unit to be capable of matching the airflow of the IT equipment fans. A standard touch screen model is offered to the Telecom and IT industry to cover most central office, point of presence and switch gear/server/computer room applications.
Munters TelcOasis™ units consume less peak power compared to conventional cooling systems, enabling Telecom customers to free up electrical power for their core business. These outdoor units do not occupy valuable indoor white space and can be located on the roof or on the exterior perimeter of the building.
The TelcOasis™ 10k unit is the ideal choice for retrofitting projects as the weight and the footprint were designed to replace conventional R-22 rooftop package units.
TelcOasis™ IASE Evaporative Cooling SystemsIndirect Air-Side Economizer designed for Mission Critical facilities
TelcOasis™ IASE benefits:
• 4 times less energy consumption than conventional cooling
• Environmentally friendly
• BacNet compatible controls
• Regional utility rebates may apply to reduce TCO
• Lower peak power usage
• Small footprint
Product guideTelcOasis™ 10k Cooling for Telecommunications
Munters Corporation, Data Center Division Phone +1 800 843 5360 / E-mail [email protected] / munters.com
All enquires to:
Munters Corporation Tel: (800) 843-5360 E-mail: [email protected]
www.munters.com
Features• R-410a refrigerant
• Indirect evaporative cooler using flexible,
scale shedding polymer tubes
• Packaged DX system
• One piece shipment
• Low noise
• Simple touch screen controls
• Regional utility rebates may apply
Built in redundant features
• 2 x supply fans
• 2 x scavenger fans
• 2 x compressors
• 2 x methods of water supply
Munters vs Conventional Cooling for a room with 63 kW IT load in San Francisco CAAnnual Energy Consumption
Conventional Cooling 252,288 kWh
Munters IASE 68,018 kWh
Percentage of annual hours in a typical year (TMY2) where IASE satisfies 100% of Data Cooling needs Percentage of Total Tonnage picked up by IEC during ASHRAE 0.4% WB Design Condition
Note: Return air temp = 90°F (32°C) Supply air temp = 70°F (21°C )
San Francisco 94% 79%
Denver 98% 79%
Los Angeles 83% 74%
Boston 82% 61%
Calgary 100% 100%
Toronto 87% 54%
Effectiveness
TelcOasis™ 10k
Cooling Capacity10,000 cfm17,000 m3/h
Delta T (°F–°C)
TR kW
15–8.3 13.5 47
20–11.1 18.0 63
25–13.9 22.5 79
Footprint
13’5 “ x 7’8”4.1m x 2.3m
Operating Modes1. Winter – Dry mode2. Summer – Wet mode3. Summer Extreme – Wet mode with DX for trimming
DualSupplyFans
Return Air Supply Air
Return Air
Supply Air