temperature control using analog pid controller

Upload: niravikukadiya

Post on 16-Oct-2015

148 views

Category:

Documents


7 download

DESCRIPTION

Temperature Control Using Analog PID Controller. Project Report for Final Year Engineering Students.The objective of our project is maintaining the temperature constant in a particular area using analog PID controller.

TRANSCRIPT

  • 1 | P a g e

    TEMPERATURE CONTROL USING ANALOG PID CONTROLLER

    Project report submitted in partial fulfillment of the requirements

    For the award of the degree of

    BACHELOR OF TECHNOLOGY

    IN

    ELECTRICAL AND ELECTRONICS ENGINEERING

    By

    P.BHARGAVA (08241A0261)

    B.PRASANNA KUMAR (08241A0283)

    J.RAMESH BABU (08241A0290

    S.VENKATESH (08241A02B3)

    Under the guidance of

    Ms. K. Sireesha

    Assistant Professor

  • 2 | P a g e

    Department of Electrical and Electronics Engineering

    GOKARAJU RANGARAJU INSTITUTE OF ENGINEERING & TECHNOLOGY,

    BACHUPALLY, HYDERABAD-72

    2012

  • 3 | P a g e

    GOKARAJU RANGARAJU INSTITUTE OF ENGINEERING AND TECHNOLOGY

    Hyderabad, Andhra Pradesh.

    DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

    C E R T I F I C A T E

    This is to certify that the project report entitled TEMPERATURE CONTROL USING ANALOG PID CONTROLLER that is being submitted by

    P.BHARGAVA, B.PRASANNA KUMAR , J.RAMESH BABU, S.VENKATESH in partial fulfillment for the

    award of the Degree of Bachelor of Technology in Electrical and Electronics

    Engineering to the Jawaharlal Nehru Technological University is a record of bonafide work carried out by him under my guidance and supervision. The results embodied in this project report have not

    been submitted to any other University or Institute for the award of any Post graduation degree.

    Prof P.M.Sharma Ms. K.Sireesha Dr. S.N.Saxena

    HOD, EEE Assistant Professor, EEE Dept. Professor, Coordinator,

    GRIET, Hyderabad GRIET, Hyderabad EEE Dept.

    (Internal Guide) G.R.I.E.T, Hyderabad

  • 4 | P a g e

    ACKNOWLEDGEMENT

    This is to place on record my appreciation and deep gratitude to the persons without whose

    support this project would never seen the light of day.

    We wish to express my propound sense of gratitude to Mr. P. S. Raju, Director, G.R.I.E.T for his

    guidance, encouragement, and for all facilities to complete this project.

    We have immense pleasure in expressing my thanks and deep sense of gratitude to my guide

    Ms K.Sireesha, Asst. Professor, Department of Electrical Engineering, G.R.I.E.T for his guidance

    throughout this project.

    We are also thankful to Mr.Chakravarthi, Assoc. Professor, Department of Electrical Engineering,

    G.R.I.E.T who help.ed us a large wit his excellent guidance.

    We also express our sincere thanks to Prof.P.M.Sharma, Head of the Department, G.R.I.E.T for

    extending his help.

    We express our gratitude to Dr. S.N. Saxena, Professor, Department of Electrical and

    Electronics Engineering, Coordinator, Project Review Committee, G.R.I.E.T for his valuable

    recommendations and for accepting this project report.

    Finally we express our sincere gratitude to all the members of faculty and my friends who

    contributed their valuable advice and helped to complete the project successfully.

    P.BHARGAVA (08241A0261)

    B.PRASANNA KUMAR (08241A0283)

    J.RAMESH BABU (08241A0290)

    S.VENKATESH (08241A02B3)

  • 5 | P a g e

    ABSTRACT

    The objective of our project is maintaining the temperature constant in a particular area

    using analog PID controller. The motivation for doing this project is the fact that

    temperature control has become an integral part of any control system operating in a

    temperature sensitive environment Whatever the process or the parameter (temp, flow,

    speed, ..) the principles of control are similar. Input and output signals are specified in this

    project are analog. Control of a process is achieved by means of a closed loop circuit. One

    of the primary purposes of using feedback in control system is to reduce the sensitivity of

    the system to parameter variations.The project deals with a simple aspect of giving

    information about the controlling of temperature in a furnace. In this project we are

    developing a system, which can control temperature of a furnace automatically. The furnace

    temperature is compared with the value set by the user and if the temperature goes beyond

    the Preset temperature then heater will get off and if temperature goes below the set value

    then heater gets on.In this project we tried to control the temperature of surrounding area of

    the bulb.Initially the input voltage of the system for a particular temperature at bulb is noted

    and it is taken as reference or set point and that temperature is maintained constant using

    analog pid controller with the help of heat sensor LM35 whose output is fed back to the

    input as feed back.

  • 6 | P a g e

    CONTENTS

    Chapter

    No.

    Name Of The Chapter

    Page No.

    1

    2

    3

    4

    INTRODUCTION

    PID CONTROLLER THEORY

    2.1 P - Characteristics

    2.2 I - Characteristics

    2.3 D - Characteristics

    2.4 PID - Characteristics

    2.5 Importance Of Temperature Control

    2.6 Advantage Of PID Controller For Temperature

    Control

    CONTROL LOOP BASICS

    PROJECT OVERVIEW

    4.1 Op Amp IC741

    4.1.1 Description

    4.2 Temperature Sensor LM35

    4.2.1 Description

    9

    11

    12

    14

    16

    18

    20

    21

    23

    26

    28

    29

  • 7 | P a g e

    5

    6

    4.3 Relay RAS0510

    4.3.1 Description

    4.4 Bridge Rectifier BR 68

    4.4.1 Description

    4.5 Voltage Regulators 7915 7815 7015

    4.5.1 Description

    PHYSICALLY IMPLEMENTING OF PID CONTROLLER

    5.1 Ideal versus Standard PID Form

    5.2 Loop Tuning

    5.2.1 Stability

    5.2.2 Optimum Behaviour

    5.2.3 Manual Tuning

    DESCRIPTION OF PROJECT KIT

    6.1 Design Of Panel Board

    6.2 Panel Board Circuit

    6.3 Working Of The Panel

    6.3.1 Power Circuit

    6.3.2 PID Circuit

    6.3.3 Sensor Circuit

    30

    31

    33

    34

    36

    37

    40

    41

    45

    46

  • 8 | P a g e

    7

    8

    9

    CONCLUSION

    FUTURE SCOPE OF PID CONTROLLER

    8.1 Improvements

    8.1.1 Feed Fprward

    8.1.2 Other Improvements

    BIBILOGRAPHY

    9.1 APPENDIX

    9.1.1 Appendix A

    9.1.2 Appendix B

    9.1.3 Appendix C

    9.1.4 Appendix D

    9.1.5 Appendix - E

    48

    50

    51

    52

    54

  • 9 | P a g e

    CHAPTER 1

    INTRODUCTION

  • 10 | P a g e

    The PID controller is the most common form of feedback. It was an essential

    element of early governors and it became the standard tool when process control emerged in the

    1940s. In process control today, more than 95% of the control loops are of PID type, most loops

    are actually PI control. PID controllers are today found in all areas where control is used. The

    controllers come in many different forms. There are standalone systems in boxes for one or a few

    loops, which are manufactured by the hundred thousands yearly. PID control is an important

    ingredient of a distributed control system. The controllers are also embedded in many special

    purpose control systems. PID control is often combined with logic, sequential functions,

    selectors, and simple function blocks to build the complicated automation systems used for

    energy production, transportation, and manufacturing. Many sophisticated control strategies,

    such as model predictive control, are also organized hierarchically. PID control is used at the

    lowest level; the multivariable controller gives the set points to the controllers at the lower level.

    The PID controller can thus be said to be the bread and butter t of control engineering. It is an important component in every control engineers tool box. PID controllers have survived many changes in technology, from mechanics and pneumatics to microprocessors

    via electronic tubes, transistors, integrated circuits. The microprocessor has had a dramatic

    influence on the PID controller. Practically all PID controllers made today are based on

    microprocessors. This has given opportunities to provide additional features like automatic

    tuning, gain scheduling, and continuous adaptation. To accurately control process temperature

    without extensive operator involvement, a temperature control system relies upon a controller,

    which accepts a temperature sensor such as a thermocouple or RTD as input. It compares the

    actual temperature to the desired control temperature, or set point, and provides an output to a

    control element. The controller is one part of the entire control system, and the whole system

    should be analyzed in selecting the proper controller.

    The following items should be considered when selecting a controller:

    1. Type of input sensor (thermocouple, RTD) and temperature range 2. Type of output required (electromechanical relay, SSR, analog output) 3. Control algorithm needed (on/off, proportional, PID) 4. Number and type of outputs (heat, cool, alarm, limit)

  • 11 | P a g e

    CHAPTER 2

    PID CONTROLLER THEORY

  • 12 | P a g e

    2.1 P CHARACTERISTICS (Proportional term)

    The proportional term produces an output value that is proportional to the current error

    value. The proportional response can be adjusted by multiplying the error by a constant Kp,

    called the proportional gain.

    The proportional term is given by:

    Proportional - To handle the immediate error, the error is multiplied by a constant P (for "proportional"), and added to the controlled quantity. P is only valid in the band over which a

    controller's output is proportional to the error of the system. For example, for a heater, a

    controller with a proportional band of 10 C and a set point of 20 C would have an output of

    100% at 10 C, 50% at 15 C and 10% at 19 C. Note that when the error is zero, a proportional

    controller's output is zero

    A high proportional gain results in a large change in the output for a given change in the error.

    If the proportional gain is too high, the system can become unstable (see the section on loop

    tuning). In contrast, a small gain results in a small output response to a large input error, and a

    less responsive or less sensitive controller. If the proportional gain is too low, the control action

    may be too small when responding to system disturbances. Tuning theory and industrial practice

    indicate that the proportional term should contribute the bulk of the output change.

  • 13 | P a g e

    Plot of PV vs time, for three values of Kp (Ki and Kd held constant)

    Because a non-zero error is required to drive the controller, a pure proportional controller

    generally operates with a steady-state error, referred to as droop. Droop is proportional to the

    process gain and inversely proportional to proportional gain. Droop may be mitigated by adding

    a compensating bias term to the set point or output, or corrected by adding an integral term

  • 14 | P a g e

    2.2 I CHARACTERISTICS ( Integral term)

    Integral - To learn from the past, the error is integrated (added up) over a period of time, and

    then multiplied by a constant I (making an average), and added to the controlled quantity. A

    simple proportional system either oscillates, moving back and forth around the set point because

    there's nothing to remove the error when it overshoots, or oscillates and/or stabilizes at a too low

    or too high value. By adding a proportion of the average error to the process input, the average

    difference between the process output and the set point is continually reduced. Therefore,

    eventually, a well-tuned PID loop's process output will settle down at the set point. As an

    example, a system that has a tendency for a lower value (heater in a cold

    environment), a simple proportional system would oscillate and/or stabilize at a too low value

    because when zero error is reached P is also zero thereby halting the system until it again is too

    low.

    The integral term accelerates the movement of the process towards setpoint and eliminates the

    residual steady-state error that occurs with a pure proportional controller. However, since the

    integral term responds to accumulated errors from the past, it can cause the present value

    to overshoot the set point value

    Integrator Circuit

    If a capacitor is used as the feedback element in the inverting amplifier, shown in figure 21, the

    result is an integrator. An intuitive grasp of the integrator action may be obtained from the

    statement under the section, Current Output, that current through the feedback loop charges the capacitor and is stored there as a voltage from the output to ground. This is a voltage input

    current integrator.

  • 15 | P a g e

    Plot of PV vs time, for three values of Ki (Kp and Kd held constant)

    The contribution from the integral term is proportional to both the magnitude of the error

    and the duration of the error. The integral in a PID controller is the sum of the instantaneous

    error over time and gives the accumulated offset that should have been corrected previously. The

    accumulated error is then multiplied by the integral gain ( ) and added to the controller output.

    The integral term is given by:

  • 16 | P a g e

    2.3 D CHARACTERISTICS (Derivative Term)

    Derivative - To handle the future, the first derivative (the slope of the error) over time is

    calculated, and multiplied by another constant D, and also added to the controlled quantity. The

    derivative term controls the response to a change in the system. The larger the derivative term,

    the more rapidly the controller responds to changes in the process's output. Its D term is the

    reason a PID loop is also sometimes called a "predictive controller." The D term is reduced when

    trying to dampen a controller's response to short term changes. Practical controllers for slow

    processes can even do without D term. More technically, a PID loop can be characterized as a

    filter applied to a complex frequency-domain system. This is useful in

    order to calculate whether it will actually reach a stable value. If the values are chosen

    incorrectly, the controlled process input can oscillate, and the process output may never stay at

    the set point.

    The derivative term slows the rate of change of the controller output. Derivative control

    is used to reduce the magnitude of the overshoot produced by the integral component and

    improve the combined controller-process stability. However, the derivative term slows

    the transient response of the controller. Also, differentiation of a signal amplifies noise and thus

    this term in the controller is highly sensitive to noise in the error term, and can cause a process to

    become unstable if the noise and the derivative gain are sufficiently large. Hence an

    approximation to a differentiator with a limited bandwidth is more commonly used. Such a

    circuit is known as a phase-lead compensator.

    Differentiator Circuit

    Using a capacitor as the input element to the inverting amplifier, figure 22, yields a

    differentiator circuit. Consideration of the device in figure 23 will give a feeling for the

    differentiator circuit. Since the inverting input is at ground potential:

  • 17 | P a g e

    Plot of PV vs time, for three values of Kd (Kp and Ki held constant)

  • 18 | P a g e

    The derivative of the process error is calculated by determining the slope of the error over

    time and multiplying this rate of change by the derivative gain . The magnitude of the

    contribution of the derivative term to the overall control action is termed the derivative gain,

    .

    The derivative term is given by.

    2.4 PID CHARACTERISTIC (PID Term)

    A proportionalintegralderivative controller (PID controller) is a generic control

    loop feedback mechanism (controller) widely used in industrial control systems a PID is the

    most commonly used feedback controller. A PID controller calculates an "error" value as the

    difference between a measured process variable and a desired set point. The controller attempts

    to minimize the error by adjusting the process control inputs.

    The PID control scheme is named after its three correcting terms, whose sum constitutes the

    manipulated variable (MV). The proportional, integral, and derivative terms are summed to

    calculate the output of the PID controller. Defining as the controller output, the final form

    of the PID algorithm is:

    where

    Kp: Proportional gain, a tuning parameter

    Ki: Integral gain, a tuning parameter

    Kd: Derivative gain, a tuning parameter

    : Error

    t: Time or instantaneous time (the present)

  • 19 | P a g e

    The PID loop adds positive corrections, removing error from the process's controllable

    variable (its input). Differing terms are used in the process control industry: The "process

    variable" is also called the "process's input" or "controller's output." The process's output is also

    called the "measurement" or "controller's input." This "up a bit, down a bit" movement of the

    process's input variable is how the PID loop automatically finds the correct level of input for the

    process. "Turning the control knob" reduces error, adjusting the process's input to keep the

    process's measured output at the set point. The error is found by subtracting the measured

    quantity from the set point. "PID" is named after its three correcting calculations, whose sum

    constitutes the output of the PID controller.

    The PID controller calculation (algorithm) involves three separate constant parameters, and

    is accordingly sometimes called three-term control: the proportional,

    the integral and derivative values, denoted P, I, and D. Heuristically, these values can be

    interpreted in terms of time: P depends on the present error, Ion the accumulation of past errors,

    and D is a prediction of future errors, based on current rate of change. The weighted sum of these

    three actions is used to adjust the process via a control element such as the position of a control

    valve, or the power supplied to a heating element.

  • 20 | P a g e

    Some applications may require using only one or two actions to provide the appropriate

    system control. This is achieved by setting the other parameters to zero. A PID controller will be

    called a PI, PD, P or I controller in the absence of the respective control actions. PI controllers

    are fairly common, since derivative action is sensitive to measurement noise, whereas the

    absence of an integral term may prevent the system from reaching its target value due to the

    control action.

    2.5 IMPORTANCE OF TEMPERATURE CONTROL

    Temperature control is so important because it not only keeps all substances and food items at set

    temperatures but it also means that the business is operating completely legally, and its

    surprising how temperature can have so much of an effect when it comes to the law.

    Manual temperature control is often used, but now theres an even easier way of achieving the

    same results wireless temperature monitoring. This is a lot more convenient and hassle-free

    than more conventional methods, so businesses should always consider investing in a wireless

    system (such as that provided by Kelsius) for complete peace of mind.

  • 21 | P a g e

    2.6 ADVANTAGE OF PID CONTROLLER FOR TEMPERATURE

    The different cases are discussed below:

    The P controller shows a relatively high maximum overshoot , a long settling

    time as well as a steady-state error .

    The I controller has a higher maximum overshoot than the P controller due to the slowly

    starting I behaviour, but no steady-state error.

    The PI controller fuses the properties of the P and I controllers. It shows a maximum

    overshoot and settling time similar to the P controller but no steady-state error.

    The real PD controller to with has a smaller maximum overshoot due to the

    'faster' D action compared with the controller types mentioned under a) to c). Also in this

    case a steady-state error is visible, which is smaller than in the case of the P controller.

    This is because the PD controller generally is tuned to have a larger gain due to the

    positive phase shift of the D action. For the results shown in Figure the gain for the P

    controller is and for the PD controller . The plant has a gain

    of .

    The PID controller to with fuses the properties of a PI and PD controller. It

    shows a smaller maximum overshoot than the PD controller and has no steady state error

    due to the I action.

    The qualitative concepts of this example are also relevant to other type of plants with delayed

    proportional behaviour. This discussion has given some first insights into the static and dynamic

    behaviour of control loops.

  • 22 | P a g e

    Figure Behaviour of the normalised controlled variable for step

    disturbance at the input to the plant ; for different

    types of controllers

  • 23 | P a g e

    CHAPTER 3

    CONTROL LOOP BASICS

  • 24 | P a g e

    A familiar example of a control loop is the action taken when adjusting hot and cold

    faucets (valves) to maintain the water at a desired temperature. This typically involves the

    mixing of two process streams, the hot and cold water. The person touches the water to sense or

    measure its temperature. Based on this feedback they perform a control action to adjust the hot

    and cold water valves until the process temperature stabilizes at the desired value.

    The sensed water temperature is the process variable or process value (PV). The desired

    temperature is called the set point (SP). The input to the process (the water valve position) is

    called the manipulated variable (MV). The difference between the temperature measurement and

    the set point is the error (e) and quantifies whether the water is too hot or too cold and by how

    much.

    After measuring the temperature (PV), and then calculating the error, the controller decides when

    to change the tap position (MV) and by how much. When the controller first turns the valve on, it

    may turn the hot valve only slightly if warm water is desired, or it may open the valve all the

    way if very hot water is desired. This is an example of a simple proportional control. In the event

    that hot water does not arrive quickly, the controller may try to speed-up the process by opening

    up the hot water valve more-and-more as time goes by. This is an example of an integral control

    Making a change that is too large when the error is small is equivalent to a high gain controller

    and will lead to overshoot. If the controller were to repeatedly make changes that were too large

    and repeatedly overshoot the target, the output would oscillate around the set point in either a

    constant, growing, or decaying sinusoid. If the oscillations increase with time then the system is

    unstable, whereas if they decrease the system is stable. If the oscillations remain at a constant

    magnitude the system is marginally stable.

    In the interest of achieving a gradual convergence at the desired temperature (SP), the controller

    may wish to damp the anticipated future oscillations. So in order to compensate for this effect,

    the controller may elect to temper its adjustments. This can be thought of as a derivative control

    method.

    If a controller starts from a stable state at zero error (PV = SP), then further changes by the

    controller will be in response to changes in other measured or unmeasured inputs to the process

    that impact on the process, and hence on the PV. Variables that impact on the process other than

    the MV are known as disturbances. Generally controllers are used to reject disturbances and/or

    implement set point changes. Changes in feed water temperature constitute a disturbance to the

    faucet temperature control process.

    In theory, a controller can be used to control any process which has a measurable output (PV), a

    known ideal value for that output (SP) and an input to the process (MV) that will affect the

    relevant PV. Controllers are used in industry to regulate temperature, pressure, flow rate

    ,chemical composition, speed and practically every other variable for which a measurement

    exists

    Consider a typical process control system. For a particular example let us look at an open tank,

    which supplies a process, say, a pump, at its output. The tank will require a supply to maintain its

    level (and therefore the pumps positive suction head) at a fixed predetermined point. This

    predetermined level is referred to as the set point (SP) and it is also the controlled quantity of the

    system. Clearly whilst the inflow and outflow are in mass balance, the level will remain constant.

    Any difference in the relative flows will cause the level to vary. How can we effectively control

  • 25 | P a g e

    this system to a constant level? We must first identify our variables. Obviously there could be a

    number of variables in any system, the two in which we are most interested are: The controlled

    variable - in our example this will be level. The manipulated variable . the inflow or outflow

    from the system. If we look more closely at our sample system (Figure 1), assuming the level is

    at the set point, the inflow to the system and outflow are

    balanced. Obviously no control action is required whilst this status quo exists. Control action is

    only necessary when a difference or error exists between the set point and the measured level.

    Depending on whether this error is a positive or negative quantity, the appropriate control

    correction will be made in an attempt to restore the process to the set point. Henceforth, the error

    will always take the form of:

    Error = Set point . Measured Quantity

    OR

    e = SP - M

  • 26 | P a g e

    CHAPTER 4

    PROJECT OVERVIEW

  • 27 | P a g e

    List of Components used in the project (Panel Board)

    Op Amp IC741

    Temperature Sensor LM35

    Relays RAS0510

    Bridge Rectifier BR 68

    Voltage Regulators 7915 7815 7015

  • 28 | P a g e

    4.1 Op Amp IC741

    DECRIPTION

    An operational amplifier ("op-amp") is a DC-coupled high-gain electronic voltage amplifier with

    a differential input and, usually, a single-ended output. An op-amp produces an output voltage

    that is typically hundreds of thousands times larger than the voltage difference between its input

    terminals.

    Operational amplifiers had their origins in analog computers where they were used in many

    linear, non-linear and frequency-dependent circuits. Characteristics of a circuit using an op-amp

    are set by external components with little dependence on temperature changes or manufacturing

    variations in the op-amp itself, which makes op-amps popular building blocks for circuit design.

    Op-amps are among the most widely used electronic devices today, being used in a vast array of

    consumer, industrial, and scientific devices. Many standard IC op-amps cost only a few cents in

    moderate production volume; however some integrated or hybrid operational amplifiers with

    special performance specifications may cost over $100 US in small quantities.[citation needed]

    Op-

    amps may be packaged as components, or used as elements of more complex integrated circuits.

    The op-amp is one type of differential amplifier. Other types of differential amplifier include

    the fully differential amplifier (similar to the op-amp, but with two outputs), the instrumentation

    amplifier (usually built from three op-amps), the isolation amplifier (similar to the

    instrumentation amplifier, but with tolerance to common-mode voltages that would destroy an

    ordinary op-amp), and negative feedback amplifier (usually built from one or more op-amps and

    a resistive feedback network) .

  • 29 | P a g e

    4.2 Temperature Sensor LM35

    Description

    An analog temperature sensor is pretty easy to explain, its a chip that tells you what the ambient

    temperature is!

    These sensors use a solid-state technique to determine the temperature. That is to say, they dont

    use mercury (like old thermometers), bi metallic strips (like in some home thermometers or

    stoves), nor do they use thermistors (temperature sensitive resistors). Instead, they use the fact as

    temperature increases, the voltage across a diode increases at a known rate. (Technically, this is

    actually the voltage drop between the base and emitter - the V be - of a transistor. By precisely

    amplifying the voltage change, it is easy to generate an analog signal that is directly proportional

    to temperature. There have been some improvements on the technique but, essentially that is how

    temperature is measured.

  • 30 | P a g e

    Because these sensors have no moving parts, they are precise, never wear out, don't need

    calibration, work under many environmental conditions, and are constant between sensors and

    readings. Moreover they are very inexpensive and quite easy to use

    These stats are for the temperature sensor in the Ad a fruit shop, the Analog Devices TMP36 (-40

    to 150C). Its very similar to the LM35/TMP35 (celsius output) and LM34/TMP34 (farenheit

    output). The reason we went with the '36 instead of the '35 or '34 is that this sensor has a very

    wide range and doensn't require a negative voltage to read sub-zero temperatures. Otherwise, the

    functionality is basically the same.

    4.3 Relays RAS0510

  • 31 | P a g e

    Description

    A relay is an electrically operated switch. Many relays use an electromagnet to operate a

    switching mechanism mechanically, but other operating principles are also used. Relays are used

    where it is necessary to control a circuit by a low-power signal (with complete electrical isolation

    between control and controlled circuits), or where several circuits must be controlled by one

    signal. The first relays were used in long distance telegraph circuits, repeating the signal coming

    in from one circuit and re-transmitting it to another. Relays were used extensively in telephone

    exchanges and early computers to perform logical operations.

    A type of relay that can handle the high power required to directly control an electric motor or

    other loads is called a contactor. Solid-state relays control power circuits with no moving parts,

    instead using a semiconductor device to perform switching. Relays with calibrated operating

    characteristics and sometimes multiple operating coils are used to protect electrical circuits from

    overload or faults; in modern electric power systems these functions are performed by digital

    instruments still called "protective relays" .

    4.4 Bridge Rectifier BR 68

  • 32 | P a g e

    FEATURES

    Low cost

    This series in UL recognized under component

    index, file number E127707

    High forward surge current capacity

    Ideal for printed circuit board

    High isolation voltage from case to leads

    High temperature soldering guaranteed:

    260OC / 10 seconds, at 5 lbs. (2.3kg) tension.

    MECHANICAL DATA

    Technology: Cell with vacuum soldered

    Case: Molded plastic body

    Terminal: Lead solderable per MIL-STD-202E

    method 208C

    Polarity: Polarity symbols marked on case

    Mounting: Thru hole for #10 screw, 5 in-lbs torque max.

    Weight: 0.13 ounce, 3.66 gram

    MAXIMUM RATINGS AND ELECTRICAL CHARACTERISTICS

    Ratings at 25OC ambient temperature unless otherwise specified

    Single Phase, half wave, 60Hz, resistive or inductive load

    For capacitive load derate current by 20%

    4.5 Voltage Regulators 7915 7815 7015

  • 33 | P a g e

    Description

    A voltage regulator is an electrical regulator designed to automatically maintain a

    constantvoltage level. A voltage regulator may be a simple "feed-forward" design or may

    include negative feedback control loops. It may use an electromechanical mechanism, or

    electronic components. Depending on the design, it may be used to regulate one or

    more AC or DC voltages.

    Electronic voltage regulators are found in devices such as computer power supplies where they

    stabilize the DC voltages used by the processor and other elements. In automobile alternators and

    central power station generator plants, voltage regulators control the output of the plant. In

    anelectric power distribution system, voltage regulators may be installed at a substation or along

    distribution lines so that all customers receive steady voltage independent of how much power is

    drawn from the line.

  • 34 | P a g e

    CHAPTER 5

    PHYSICALLY IMPLEMENTING OF PID CONTROLLER

  • 35 | P a g e

    In the early history of automatic process control the PID controller was implemented as a

    mechanical device. These mechanical controllers used a lever, spring and a mass and were often

    energized by compressed air. These pneumatic controllers were once the industry standard.

    Electronic analog controllers can be made from a solid-state or tube amplifier, a capacitor and

    a resistance. Electronic analog PID control loops were often found within more complex

    electronic systems, for example, the head positioning of a disk drive, the power conditioning of a

    power supply, or even the movement-detection circuit of a modern seismometer. Nowadays,

    electronic controllers have largely been replaced by digital controllers implemented

    with microcontrollers or FPGAs.

    Most modern PID controllers in industry are implemented in programmable logic

    controllers (PLCs) or as a panel-mounted digital controller. Software implementations have the

    advantages that they are relatively cheap and are flexible with respect to the implementation of

    the PID algorithm. Variable voltages may be applied by the time proportioning form of Pulse-

    width modulation (PWM) a cycle time is fixed, and variation is achieved by varying the

    proportion of the time during this cycle that the controller outputs +1 (or 1) instead of 0. On a

    digital system the possible proportions are discrete

    e.g., increments of .1 second within a 2 second cycle time yields 20 possible steps: percentage

    increments of 5% so there is a discretization error, but for high enough time resolution this

    yields satisfactory performance

    5.1 Ideal versus Standard PID Form

    The form of the PID controller most often encountered in industry, and the one most relevant to

    tuning algorithms is the standard form. In this form the Kp gain is applied to the Iout,

    and Dout terms, yielding:

    Where

    Ti is the integral time

    Td is the derivative time

  • 36 | P a g e

    In this standard form, the parameters have a clear physical meaning. In particular, the

    inner summation produces a new single error value which is compensated for future and past

    errors. The addition of the proportional and derivative components effectively predicts the error

    value at Td seconds (or samples) in the future, assuming that the loop control remains unchanged.

    The integral component adjusts the error value to compensate for the sum of all past errors, with

    the intention of completely eliminating them in Ti seconds (or samples). The resulting

    compensated single error value is scaled by the single gain .

    In the ideal parallel form, shown in the controller theory section the gain parameters are

    related to the parameters of the standard form through and This parallel form, where the

    parameters are treated as simple gains, is the most general and flexible form. However, it is also

    the form where the parameters have the least physical interpretation and is generally reserved for

    theoretical treatment of the PID controller. The standard form, despite being slightly more

    complex mathematically, is more common in industry.

    5.2 Loop Tuning

    Tuning a control loop is the adjustment of its control parameters (proportional band/gain,

    integral gain/reset, derivative gain/rate) to the optimum values for the desired control response.

    Stability (bounded oscillation) is a basic requirement, but beyond that, different systems have

    different behavior, different applications have different requirements, and requirements may

    conflict with one another.

    A PID controller needs to be tuned (PID gains set to appropriate values for your specific

    system) to function properly. The performance of your control system is defined by a set of

    measurements made when applying a specific input step function as the set point command

    variable (going from 0 to 100% of the output value instantaneously) and then measuring the

    response of the process variable. These measurements are shown in the graph of a systems

    response to a step input below

    When tuning your controller, you may desire an over-damped, critically damped, or under-

    damped system. In most robotics applications overshoot is unacceptable and may cause damage

    to the system. Most robotics systems are over-damped so that they never overshoot their setpoint.

    The goal of tuning such systems, then, is decreasing the rise-time and steady-state error to

    achieve the best possible performance

    PID tuning is a difficult problem, even though there are only three parameters and in

    principle is simple to describe, because it must satisfy complex criteria within the limitations of

    PID control. There are accordingly various methods for loop tuning, and more sophisticated

    techniques are the subject of patents; this section describes some traditional manual methods for

    loop tuning.

    Designing and tuning a PID controller appears to be conceptually intuitive, but can be hard

    in practice, if multiple (and often conflicting) objectives such as short transient and high stability

  • 37 | P a g e

    are to be achieved. Usually, initial designs need to be adjusted repeatedly through computer

    simulations until the closed-loop system performs or compromises as desired.

    Some processes have a degree of non-linearity and so parameters that work well at full-load

    conditions don't work when the process is starting up from no-load; this can be corrected by gain

    scheduling (using different parameters in different operating regions). PID controllers often

    provide acceptable control using default tunings, but performance can generally be improved by

    careful tuning, and performance may be unacceptable with poor tuning.

    5.2.1 Stability

    If the PID controller parameters (the gains of the proportional, integral and derivative terms)

    are chosen incorrectly, the controlled process input can be unstable, i.e., its output diverges, with

    or without oscillation, and is limited only by saturation or mechanical breakage. Instability is

    caused by excess gain, particularly in the presence of significant lag.

    Generally, stabilization of response is required and the process must not oscillate for any

    combination of process conditions and set points, though sometimes marginal stability (bounded

    oscillation) is acceptable or desired

    5.2.2 Optimum Behaviour

    The optimum behavior on a process change or set point change varies depending on the

    application.

    Two basic requirements are regulation (disturbance rejection staying at a given set point)

    and command tracking (implementing set point changes) these refer to how well the

    controlled variable tracks the desired value. Specific criteria for command tracking include rise

    time and settling time. Some processes must not allow an overshoot of the process variable

    beyond the set point if, for example, this would be unsafe. Other processes must minimize the

    energy expended in reaching a new set point

  • 38 | P a g e

    5.2.3 Manual Tuning

    If the system must remain online, one tuning method is to first Ki set Ki and Kd values to

    zero. Increase the Kp until the output of the loop oscillates, then the Kp should be set to

    approximately half of that value for a "quarter amplitude decay" type response. Then

    increase until Ki any offset is corrected in sufficient time for the process. However, too

    much Ki will cause instability. Finally, increase Kd, if required, until the loop is acceptably quick

    to reach its reference after a load disturbance. However, too much Kd will cause excessive

    response and overshoot. A fast PID loop tuning usually overshoots slightly to reach the set point

    more quickly; however, some systems cannot accept overshoot, in which case an over-

    damped closed-loop system is required, which will require a Kp setting significantly less than

    half that of the Kp setting causing oscillation

    Effects of increasing a parameter independently

    Parameter Rise time Overshoot Settling time Steady-state error Stability

    Decrease Increase Small change Decrease Degrade

    Decrease[4]

    Increase Increase Decrease

    significantly Degrade

    Minor

    decrease

    Minor

    decrease

    Minor

    decrease No effect in theory

    Improve

    if small

  • 39 | P a g e

    CHAPTER 6

    DESCRIPTION OF PROJECT KIT

  • 40 | P a g e

    6.1 Design Of Panel Board

  • 41 | P a g e

  • 42 | P a g e

  • 43 | P a g e

  • 44 | P a g e

    6.2 Panel Board Circuit

  • 45 | P a g e

    6.3 Working Of The Panel

    6.3.1 Power Circuit

    It consists of Transformer, bridge rectifier ,Voltage regulators namely 7815 and 7915 followed

    by filter circuit. The transformer used is 230/36 volts. Bridge rectifier used is BR68 .The AC

    supply voltage of 230 is fed to the transformer which whose out put is 36V AC. This 36V is fed

    to the BR68 rectifier which converts the voltage from AC to DC. This voltage obtained is filtered

    using capacitors. The Output from the filter is fed to the regulators 7915 and7815 whose output

    is +15 Volts and -15Volts respectively. This is used as +Vcc and Vee for an Operational

    amplifiers used in the circuit.

  • 46 | P a g e

    6.3.2 PID Circuit

    This circuit consists of op amps, voltage regulators, Potentiometers, Diode and Relay. The

    Voltage regulator is used to give an input to the op amp. The op amp is use to design the

    proportional ,integral and derivative analog controller.. The input to the op amp consist of two

    voltages . one is the variable voltage fed from the sensor as feedback and other is the fixed value

    taken as reference. The difference between these two inputs is taken as error. The error is fed to

    proportional ,integral and derivative block. Where the error is multiplied with proportional gain

    in P block and error is multiplied after integrating in I block and the error is multiplied after

    differentiating in D block. The output of these three blocks or circuits is added up using a

    summer circuit. The output of the summer circuit is fed to the diode IN4007 .The diode is

    connected in series with the relay. The output terminals of the relay is connected to the bulb.

    6.3.3 Sensor Circuit

    The sensor used is LM35 which is a heat sensor consisting of three terminals such as input

    output and ground respectively .this sensor is output is amplified using op amp and the output is

    fed as feed back to the input terminal of op amp which is compared with the reference value and

    the error is calculated.

  • 47 | P a g e

    CHAPTER 7

    CONCLUSION

  • 48 | P a g e

    Now a days temperature control has become an integral part of any control system operating in a

    temperature sensitive environment. Input and output signals are specified in this project is

    analog. Control of a process is achieved by means of a closed loop circuit. One of the primary

    purposes of using feedback in control system is to reduce the sensitivity of the system to

    parameter variations.The project deals with a simple aspect of giving information about the

    controlling of temperature in a furnace. In this project we have developed a system which

    controls the temperature of a furnace. Here we used a bulb in the place of a heater or furnace and

    tried to control the temperature of the surroundings of the bulb using heat sensor LM35 . The

    output of the sensor is fed back as input to the system as feed back. Here we used analog PID

    controller to control the temperature.The gains are to be tuned manually.But use the softwares

    (like labview) apt control is possible.

  • 49 | P a g e

    CHAPTER 8

    FUTURE SCOPE OF PID CONTROLLER

  • 50 | P a g e

    8.1 Improvements

    8.1.1 Feed-forward

    The control system performance can be improved by combining the feedback (or closed-loop)

    control of a PID controller with feed-forward (or open-loop) control. Knowledge about the

    system (such as the desired acceleration and inertia) can be fed forward and combined with the

    PID output to improve the overall system performance. The feed-forward value alone can often

    provide the major portion of the controller output. The PID controller can be used primarily to

    respond to whatever difference or error remains between the setpoint (SP) and the actual value of

    the process variable (PV). Since the feed-forward output is not affected by the process feedback,

    it can never cause the control system to oscillate, thus improving the system response and

    stability.

    For example, in most motion control systems, in order to accelerate a mechanical load under

    control, more force or torque is required from the prime mover, motor, or actuator. If a velocity

    loop PID controller is being used to control the speed of the load and command the force or

    torque being applied by the prime mover, then it is beneficial to take the instantaneous

    acceleration desired for the load, scale that value appropriately and add it to the output of the PID

    velocity loop controller. This means that whenever the load is being accelerated or decelerated, a

    proportional amount of force is commanded from the prime mover regardless of the feedback

    value. The PID loop in this situation uses the feedback information to change the combined

    output to reduce the remaining difference between the process setpoint and the feedback value.

    Working together, the combined open-loop feed-forward controller and closed-loop PID

    controller can provide a more responsive, stable and reliable control system.

    8.1.2 Other improvements

    In addition to feed-forward, PID controllers are often enhanced through methods such as

    PID gain scheduling (changing parameters in different operating conditions), fuzzy

    logic or computational verb logic. Further practical application issues can arise from

    instrumentation connected to the controller. A high enough sampling rate, measurement

    precision, and measurement accuracy are required to achieve adequate control performance.

    Another new method for improvement of PID controller is to increase the degree of freedom by

    using fractional order. The order of the integrator and differentiator add increased flexibility to

    the controller.

  • 51 | P a g e

    CHAPTER 9

    BIBILOGRAPHY

  • 52 | P a g e

    www.wekipedia.com, http://en.wikipedia.org/wiki/PDI

    PID controller http://en.wikipedia.org/wiki/PID_control

    Texas Instruments, Op Amps and Comparators - Don't Confuse Them, SLOA067, Bruce Carter, 09/06/2001

    R. J. Widlar, Super Gain Transistors for ICs, IEEE Journal of Solid-State Circuits

  • 53 | P a g e

    9.1 Appendixes

    9.1.1 Appendix A

  • 54 | P a g e

    9.1.2 Appendix B

  • 55 | P a g e

    9.1.3 Appendix C

  • 56 | P a g e

    9.1.4 Appendix D

  • 57 | P a g e

    9.1.5 Appendix E

  • 58 | P a g e