REFRIGERATION AND GLOBAL WARMING An Independent Review of the Role of HFC Refrigerants by March Consulting Group prepared for the European Fluorocarbon Technical Committee, a Sector Group of CEFIC /home/website/convert/temp/convert_html/5eb573c12636777925454662/document.doc

Upload: others

Post on 08-May-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

REFRIGERATION AND GLOBAL WARMING

An Independent Review of the Role of HFC Refrigerants

by March Consulting Group

prepared for the European Fluorocarbon Technical Committee,

a Sector Group of CEFIC

CONTENTS

SUMMARY..................................................................................................................................

/tt/file_convert/5eb573c12636777925454662/document.doc

September 1997

Page 2: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

1. INTRODUCTION....................................................................................................................

PART A BACKGROUND TO REFRIGERATION AND REFRIGERANTS

2. REFRIGERATION APPLICATIONS....................................................................................

3. SELECTING REFRIGERANTS..............................................................................................

PART B BACKGOUND TO GLOBAL WARMING ISSUES

4. THE IMPACT OF REFRIGERATION ON GLOBAL WARMING.......................................

5. INTERNATIONAL EFFORTS TO REDUCE GLOBAL WARMING IMPACT..................

PART C ANALYSIS OF GW IMPACT OF REFRIGERATION

6. OPPORTUNITIES TO REDUCE THE GW IMPACT OF REFRIGERATION.....................

/tt/file_convert/5eb573c12636777925454662/document.doc

Page 3: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

7. DIRECT EMISSION REDUCTION OPPORTUNITIES........................................................

8. ENERGY EFFICIENCY OPPORTUNITIES..........................................................................

9. SAFETY ISSUES.....................................................................................................................

10. END USE SECTOR REVIEW...............................................................................................

11. HISTORICAL AND FUTURE GLOBAL WARMING IMPACT........................................

APPENDIX 1 GLOSSARY OF TERMS …………………………………………………...25

APPENDIX 2 REFERENCES ………………………………………………………………26

/tt/file_convert/5eb573c12636777925454662/document.doc

Page 4: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

SUMMARY

1. This report presents a review of alternative options for refrigerants and examines ways in which the future global warming impact of refrigeration can be minimised.

2. The report was prepared by March Consulting Group at the request of the European Fluorocarbon Technical Committee during August/September 1997.

3. There is excellent potential for the refrigeration and air-conditioning user sectors to make a very positive contribution to solving the major environmental problem of global warming. The following figures show the global warming impact of EU refrigeration and air-conditioning systems expressed in Mtonnes CO2 equivalent.

Direct Impact Indirect Impact Overall Impact1990 actual 200 150 3502010 forecast 30 110 140% reduction 85% 25% 60%

4. This forecast reduction in the global warming impact of refrigeration can be achieved with widespread usage of HFC refrigerants.

5. The majority of other emitters of global warming gases are unable to make such a positive contribution. For example, the transport sector had EU global warming emissions of 220 GWP Mtonnes in 1990. However, it is estimated there will be an increase of 10% by 2010. This increase is because the growing number of vehicles and journeys outweighs improved energy efficiency.

6. There are three main refrigerant options currently available i.e. ammonia, hydrocarbons and HFCs. It is shown that each of these refrigerant options has a role to play in the future of refrigeration.

7. The various ways in which global warming emission reduction will be achieved are discussed. These include leakage and refrigerant charge reduction, improved energy efficiency and use of ammonia and hydrocarbons where appropriate.

8. HFC refrigerants are shown to be of vital importance for many refrigeration applications when safety considerations are taken into account.

9. When systems are properly designed to ensure low levels of refrigerant leakage and to maximise energy efficiency there is little or no difference between the global warming impact of ammonia, hydrocarbon or HFC systems. All can achieve considerable reductions in GW emissions when compared to the 1990 baseline.

10. Comparisons made in this report are based on the ‘real’ situation in 1990, when significant CFC and HCFC emissions were being made. Many publications ignore emissions of ozone depleting substances and hence give a false picture when comparing future emissions to the 1990 baseline.

March Consulting Group 1 EFCTC/CEFIC

Page 5: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

1. INTRODUCTION

Users of refrigeration are facing new choices with regard to selection of refrigerants because CFC and HCFC refrigerants are being phased out to protect the ozone layer. There is considerable confusion and controversy regarding the best choices, particularly when the environmental issue of global warming is taken into account. This report is intended to provide a balanced review of competing options in order to help users, designers and policy makers fully understand their relative benefits.

A key theme within this report is to examine the role of HFC refrigerants as alternatives. There is mounting pressure against these fluids from some environmental groups because it is claimed that refrigeration systems using HFCs have an excessive global warming impact. Is this pressure fair and how do HFCs compare to other options (and the CFC systems they are replacing)? Key factors that influence the global warming impact of refrigeration are discussed in order to identify the appropriate refrigerant for use in different applications.

The choice between competing refrigerants has always been complex. Nevertheless, there used to be fairly clear divisions between different types of refrigerant. CFCs and HCFCs were the refrigerant of choice for the vast majority of small and medium sized refrigeration systems (and many large ones). This was because of their excellent safety characteristics (non-toxic and non-flammable) and good materials compatibility (allowing use of copper components). Ammonia, a traditional refrigerant used for over 100 years, maintained a significant niche market in large industrial systems, particularly in the food and drink manufacturing industry and cold storage. Hydrocarbons were also used, but their market was restricted, mainly to large systems in certain petrochemical companies who were handling these highly flammable fluids within their manufacturing process.

What are the options for the future? Well over 95% of refrigeration applications use vapour compression refrigeration. Whilst other options such as absorption refrigeration and air cycle systems have a small market potential it is unlikely that there will be a significant move away from vapour compression cycles during the next 20 years. Hence, this document restricts itself to the options for vapour compression systems.

Currently, there are four main options that an end user can consider: HFCs, hydrocarbons (HCs), ammonia and elimination of the need for refrigeration. There are advantages and disadvantages for each. Some of the key issues include safety, cost (first cost and operating cost) and global warming impact. This report reviews refrigerant options and provides a logical and balanced framework to help users select the best one for them. Our general belief is that all four options are applicable in certain circumstances. The key issue is to identify what these circumstances are.

The report has been written to be of broad interest, both to those with relatively little refrigeration knowledge and to those with an in depth understanding of design issues. Hence, some background material is included early in the report followed by more detailed analysis. The document is split into three main parts. Part A, provides background to refrigeration and refrigerants. Part B gives background to global warming. Finally Part C analyses the global warming impact of refrigeration.

March Consulting Group 2 EFCTC/CEFIC

Page 6: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

2. REFRIGERATION APPLICATIONS

To properly understand the difficulties facing refrigeration systems designers it is important to be aware of the enormous range of applications. Refrigeration represents one of the most important energy-using utilities in all sectors of human activity: domestic, commercial and industrial. People often find it surprising that refrigeration and air-conditioning systems represent approximately 15% of EU electricity demand (Source - EEBPP 1). This makes it one of the largest definable electricity using groups (larger than, for example, lighting).

Refrigeration applications range enormously in size and temperature level. A domestic refrigerator has a cooling load of a few hundred watts whereas large industrial systems can have loads in excess of 10 MW. Small systems contain less than 100g of refrigerant whereas large ones can contain many tonnes. Temperatures range from specialist cryogenic applications (below -150oC), through a wide variety of industrial and food chain requirements between -40oC and 10oC, to air-conditioning and heat pump applications at temperatures of 20oC and above. Some refrigeration systems can be operated in restricted locations where only trained personnel are present. Other systems, such as those for supermarkets and building air-conditioning, operate where there are numerous untrained members of the public. All these variations lead to widely differing refrigeration system designs. Because of the wide variety of circumstances in which refrigeration is used, there is no single refrigerant that suits all applications; there is a need for various refrigerants with different properties.

The main requirements for refrigeration systems fall into four distinct groups:

The food and drink chain, including agricultural, manufacturing, storage, transport, retailing and domestic requirements.

Other industrial processes, including applications in sectors such as chemicals, pharmaceuticals and electronics.

Comfort conditioning, including domestic, commercial and industrial buildings

Mobile air-conditioning in cars and other vehicles.

In this short report we cannot give an adequate description of the full variety of applications and designs. However, it is worth noting that most very small systems (such as domestic refrigerators and small commercial units like icemakers, small retail displays etc) are based on hermetic designs. These are factory built units using only welded or brazed joints. They contain very small refrigerant charges and suffer very little from leakage. Larger systems usually require some or all of construction to be carried out on site and there are numerous pipe joints and seals required. Refrigerant charge is much higher and the chance of refrigerant leakage is significant.

It is also useful to distinguish between ‘Distributed Systems’ that circulate the refrigerant itself to cool a building or a process and ‘Secondary Refrigerant Systems’ that incorporate a secondary fluid to transmit cooling to the user (often water or an ‘anti-freeze’ solution). Secondary refrigerant systems have the advantages that they can reduce the quantity of primary refrigerant required and allow it to be contained within a limited physical area such as a plant room. This considerably limits the

March Consulting Group 3 EFCTC/CEFIC

Page 7: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

potential for leakage and eases safety problems if flammable or toxic refrigerants are used. However, there will usually be an energy penalty, because of the need to pump the secondary refrigerant and to account for the extra temperature difference between the primary and secondary circuits.

One can attempt to quantify the size of the refrigeration market in a number of different ways including number of systems, quantity of refrigerant used and energy consumption. The following estimates are based on References EC DGIII, UK DoE 1, UK DoE 2 and March Consulting Group estimates.

In terms of number of systems the domestic sector is totally dominant, with some 200 million systems in use in the EU. This compares with about 30 million small systems for retailing and air-conditioning and about 2 million larger systems for supermarkets, large buildings and industrial applications. However, if we analyse the quantity of refrigerant contained within all these systems or the annual energy consumption a quite different picture will be obtained. In terms of refrigerant quantities the supermarket, industrial and air-conditioning sectors become the most important, with domestic systems being the 4th largest segment. Figure 1 gives an approximate breakdown of the EU refrigerant bank in terms of end use sectors.

The various fluorocarbons including CFCs, HCFCs (and more recently HFCs) represent in the region of 80 to 85% of the total EU refrigerant bank. Ammonia represents a further 10 to 15%. Hydrocarbons have historically represented a very small proportion of the total bank, probably in the region of 1 to 2%. Recent growth in the market for hydrocarbons in the domestic and small refrigeration field will have caused this to grow but the total is currently less than 3% of the EU bank.

March Consulting Group 4 EFCTC/CEFIC

Page 8: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

3. SELECTING REFRIGERANTS

As already discussed the process of refrigerant selection is quite complex. This is because there are a significant number of parameters that need to be assessed and few available fluids ‘score well’ on all of them. The key parameters include the following:

Thermodynamic performance - for the required evaporating and condensing temperature levels the fluid should be able to provide energy efficient performance (i.e. a high coefficient of performance or COP).

Appropriate operating pressures - the evaporating pressure should not be too low and the condensing pressure should not be too high (under the relevant operating temperatures). Ideally the evaporating pressure should be higher than atmospheric pressure and condenser pressure should be below around 20 bar(g).

Compressor size - the thermophysical properties for the fluid should result in as small a compressor as possible

Toxicity - the fluid should be of zero or low toxicity

Flammability - the fluid should be non-flammable and non-explosive.

Materials compatibility - the fluid should be compatible with various materials used in the construction of a refrigeration plant (e.g. pipes, vessels, gaskets, seals etc).

Oil compatibility - the fluid should perform well with available lubricating oils.

Stability - the fluid should remain stable throughout many years of operation and must not chemically react with system components, lubricating oil and contaminants.

Cost - the fluid should have reasonable cost.

Ozone Depletion Potential - the fluid should have a zero ODP.

Global Warming Potential - the fluid should have a zero or low GWP.

Prior to the Montreal Protocol, CFCs and HCFCs were the obvious choice for many applications. Whilst they were not the cheapest refrigerants to buy (e.g. ammonia was less than 25% of the price of CFCs) they led to plants with minimum ‘total ownership cost’. They had good materials compatibility and it was easy to deal with safety issues. CFCs can no longer be selected because of their high ODP. In the future we should only consider zero ODP fluids and we also need to ensure minimum global warming impact. In simplistic terms this may seem to suggest fluids with zero or low GWP are best. However, as we shall see later in this report, the use of a fluid with a higher intrinsic GWP does not necessarily lead to the highest overall global warming impact.

Bearing in mind the list of issues described on the previous page it is useful to examine the advantages and disadvantages of the four main refrigerant options listed in the introduction.

March Consulting Group 5 EFCTC/CEFIC

Page 9: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

Ammonia

Ammonia is a refrigerant that has been used since the very earliest days of vapour compression refrigeration. It has good thermodynamic properties for systems operating with evaporating temperatures above about -50oC and with condensing temperatures below about +40oC. Ammonia is not an appropriate refrigerant for very low temperature applications (below –50oC). Ammonia has good compatibility with mineral lubricating oils and excellent stability over long system lifetimes. It is one of the cheapest available refrigerants in terms of cost per kilogram. The environmental properties are excellent, as the fluid has zero ODP and zero GWP.

The main drawbacks of ammonia are toxicity, flammability and materials compatibility. The fluid is highly toxic and causes severe risk to humans when significant leakage occurs. The dangers are particularly significant if untrained personnel are involved, as the noxious fumes can create panic. Ammonia is flammable in certain concentrations, although it is actually relatively hard for a fire or explosion to occur. On the more practical side ammonia is incompatible with copper which restricts the materials that can be used for plant construction. All copper and brass components must be avoided and ammonia systems are constructed mainly with steel components. For small plants this can add significantly to the cost.

HFCs

HFCs also have good thermodynamic properties and the added advantage over ammonia that they are a family of fluids with different operating pressures. Hence, HFCs can be used across a wider range of application temperatures and can be more carefully selected to optimise system efficiency. Most HFCs have very low toxicity and zero flammability and they have excellent materials compatibility. Hence they do not suffer some of the drawbacks of ammonia.

On the negative side HFCs have a significant GWP; if they are to be responsibly used it is essential that emissions should be minimal. They are relatively expensive fluids although this usually is only an issue in large refrigeration systems. They are not compatible with conventional mineral lubricating oils and it has been necessary for new synthetic oils to be developed for HFC refrigeration systems. This development has been successfully completed.

Hydrocarbons

As with ammonia and HFCs, hydrocarbons have good thermodynamic properties and as they form a family of fluids, there can be good selection over a relatively wide range of application temperatures. Hydrocarbon refrigerants have low toxicity and good materials compatibility. They also have good environmental properties with zero ODP and very low GWP.

The key drawback to HCs is their very high flammability. Any significant leakage could lead to a fire or an explosion. For this reason, hydrocarbons have historically been restricted to use in petrochemical facilities that are handling these flammable fluids as part of the main manufacturing process. More widespread application requires very careful attention to flammability safety issues.

March Consulting Group 6 EFCTC/CEFIC

Page 10: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

Elimination of refrigeration

This fourth option is always worth considering when developing plans for a new refrigeration plant. If refrigeration can be eliminated there are obvious and significant environmental benefits. No refrigerant fluid is used so the GWP is irrelevant. More importantly, no energy is used hence there may be a significant reduction in the overall global warming impact. There are numerous examples of elimination of refrigeration, ranging from use of ambient free cooling, to reductions in load from better process integration to completely new approaches to processing (e.g. use of irradiated food instead of refrigerated food).

The clear disadvantage of this option is the relatively narrow applicability. For the vast majority of current refrigeration applications, whilst there may be some good opportunities for cooling load reduction, complete elimination of mechanical refrigeration is often impossible.

This option is not often given the attention it deserves. In many cases the elimination (or reduction) of a refrigeration load not only saves energy, but also saves capital cost!

Options for Different Sized Refrigeration Systems

Relating the general characteristics of refrigerants, as described above, to the main refrigeration applications it is possible to draw up general rules for the usability of refrigerants. Table 1 outlines the results of such a comparison. It should be noted that the four categories of refrigeration chosen simplify what is a much more complex picture. The dividing lines between these categories may not always be obvious. It should also be noted that if capital cost is irrelevant, the safety issues that make ammonia and hydrocarbons difficult to use could be overcome. Bearing these points in mind, Table 1 provides a useful ‘feel’ for the cost-effective use of refrigerants.

Table 1 General Applicability of Refrigerants (for cost-effective and safe usage)

Refrigeration Application Category Ammonia HCs HFCs

1. Very Small Systemse.g. domestic refrigerators, icemakers, through the wall a/c.Hermetic systems, very low refrigerant charge.

2. Distributed Systems used in public arease.g. supermarkets, split system a/c, small cold stores.Refrigerant charge larger and leaks affect untrained people.

3. Distributed Systems used in restricted arease.g. food factories, cold stores.Usually large industrial systems.

4. Secondary Refrigerant Systemse.g. water chillers, glycol chillers. Refrigerant in restricted plant room with no public access.

March Consulting Group 7 EFCTC/CEFIC

Page 11: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

4. THE IMPACT OF REFRIGERATION ON GLOBAL WARMING

Many volumes have been written on the mechanics of global warming. Simply stated: radiation from the sun hits the Earth and some is re-emitted into the atmosphere as infrared radiation. When the infrared light tries to leave the atmosphere, some of it gets reflected back to the Earth by the greenhouse gases. This trapped energy then warms the planet.

There are many greenhouse gases, some of which are naturally occurring such as water, carbon dioxide and methane. The natural global warming process ensures the earth keeps itself warm enough for human habitation. The problem is that humans are adding more and more carbon dioxide into the atmosphere by burning fossil fuels for power, transportation and industry. We have also added other man-made greenhouse gases, such as nitrous oxides (NOx) and fluorocarbons (FCs).

There is a growing acceptance in the international community that action is required to reverse the growth in the emission of greenhouse gases. However, it is also recognised that this must be achieved without causing intolerable human hardship and the triggering of a world-wide recession through draconian legislation. It is thus important to target the areas where the largest reductions can be achieved with least impact to human activity.

Contributors to Global Warming

In 1990 there were four main man-made greenhouse gases: CO2, Methane, NOx and FCs. CO2 was by far the largest single contributor. Before 1990, when the environmental effects of FC emissions were not fully understood, FCs were responsible for the second largest contribution to the total. Figure 2 shows the relative impact of the four gases. The data includes emissions of CFCs and HCFCs. (Source AFEAS).

The Role of Fluorocarbons in Global Warming

Clearly, from the 1990 emissions figures much attention was required to target the emissions of fluorocarbons. They were used for a variety of processes due to their excellent physical properties and safety record. Major uses included: aerosols, foams, solvents and refrigerants. Refrigerants accounted for only 15% of the 1990 emissions of fluorocarbons (hence 4% of all GW emissions). Since this date much effort has been made by the industry both through self-regulation and Government intervention to reduce this figure. The progress made within the European Union over the last five years has been enormous as is shown in Figure 3. (Source ICI)

March Consulting Group 8 EFCTC/CEFIC

Page 12: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

Enormous progress has thus been made in reducing the usage of fluorocarbons (with an 82% fall in GWPtonnes between 1990 and 1995). Most of this improvement is from the aerosol, solvent and foam sectors, although there has also been a useful contribution from refrigeration. By the year 2010, EU emissions of both CFCs and HCFCs are likely to be almost eliminated. The use of HFCs should be confined to the sectors where performance, safety and cost factors dictate that they are still the best option. This may include refrigeration, medical aerosols and foam production. The chemical and user industries must remain vigilant that less crucial applications (such as the proposed self-cooling drink can) are not allowed to develop.

The Indirect Impact of Refrigeration on Global Warming

As we have seen, carbon dioxide is the main greenhouse gas. This gas is the product of combustion for all fossil fuels currently used for energy generation. Any assessment of the impact of refrigeration on global warming must consider not only the direct effect of refrigerant emissions, but also the indirect effect of the carbon dioxide emissions resulting from the energy required to operate the refrigeration system. The sum of the direct and indirect emissions is known as the Total Equivalent Warming Impact (TEWI). Indirect emissions from refrigeration systems are estimated to represent 3% of 1990 GW emissions (Source EEBPP 1 and March Consulting Group estimates). It is important to understand the relative magnitude of the direct versus the indirect impact. Figure 4 shows the relative 1990 contributions from three distinct types of refrigeration appliance. (Source Greenpeace 1)

Figure 4 TEWI Comparison for 3 Refrigeration Applications, 1990

Domestic Refrigerator Commercial Air Conditioning Car Air Conditioning

It can clearly be seen that, for 1990 domestic refrigerator designs, maximum benefit can be gained by targeting energy efficiency improvements. For car air-conditioning, great strides are needed in reducing the direct impact of the refrigerant leakage.

March Consulting Group 9 EFCTC/CEFIC

Page 13: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

5. INTERNATIONAL EFFORTS TO REDUCE GLOBAL WARMING IMPACT

Legislative/Governmental Initiatives

To fully appreciate the options that Governments can adopt to limit the impact of global warming it is helpful to compare the processes that are currently being followed with regard to both ozone depletion and global warming.

Ozone depletion issues are being addressed through the Montreal Protocol. The MP process is based on fluid production bans. In developed countries many ozone depleting substances are already subject to a production ban. Usage of existing material is allowed and the MP does not curb emissions of existing ozone depleting substances. The rationale behind this legislative process is that emissions will fall towards zero as the production ban begins to have an impact. The largest users of ozone depleting substances were highly emissive (e.g. aerosol, flexible foam and solvent applications) and the production ban process has quickly driven such users to switch to alternative materials.

Global warming issues are being addressed through the Framework Convention on Climate Change. The FCCC is quite different in nature to the MP. The process relies on control of emission of global warming substances. The reason for this different approach is obvious: the main global warming gas is carbon dioxide and it would be impractical to consider a ban on the man-made production/emission of this gas.

In the case of HFCs there is a danger of these two mechanisms becoming confused. The current users of HFCs (and many HFC policy makers) were previously affected by the Montreal Protocol. Because of familiarity with the MP mechanism there is a natural reaction to mistakenly consider a ban on HFC production. This is quite illogical; it is the emission of HFCs that should be considered not the production.

It should also be noted that the FCCC is comparing global warming emissions in 1990 with those in the future. However, the FCCC ignores 1990 emissions of substances being banned under the MP. In 1990 the refrigeration sector had significant global warming impact through leakage of CFC and HCFC refrigerants. Taking these into account, it can be shown that the sector can make large reductions in global warming impact, providing the care being taken to limit emissions of HFCs is continued.

Voluntary Initiatives

The refrigeration user industry and chemical producers are conscious of the fact that the historical use of CFCs and HCFCs was profligate, both for refrigeration and other applications. Before the adverse environmental effects were identified, wastage and leakage were the norm and use for highly emissive applications such as general aerosols was accepted. These groups agree that this attitude cannot be allowed to continue for HFCs. Because HFCs have a high GWP it is essential that they be used responsibly and that all efforts are made to minimise emissions. Highly emissive applications should not be allowed unless the benefits to society outweigh the contribution to GW; emissive use of HFCs for medical aerosols is a good example.

March Consulting Group 10 EFCTC/CEFIC

Page 14: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

6. OPPORTUNITIES TO REDUCE THE GLOBAL WARMING IMPACT OF REFRIGERATION

In 1990, refrigeration and air-conditioning systems represented approximately 7% of all greenhouse gas emissions from the EU: 4% through emissions of CFCs and HCFCs and 3% through indirect emission of CO2. This contribution is significant and stresses how important it is for refrigeration users to reduce their 1990 global warming impact.

These figures emphasise that it is the TEWI of a refrigeration system that must be reduced. Addressing the issues of energy efficiency, refrigerant charge and refrigerant leakage rates will have far more impact than simply considering the GWP of the refrigerant chosen. In the remaining sections we shall consider in detail the potential for minimising the impact of emissions from the refrigeration sector.

Mechanisms for Reducing Global Warming Impact

There are a number of ways in which the GW impact of refrigeration systems can be reduced. These give the opportunity for refrigeration users to make the largest single improvement to GW emissions of any end use sector. Rather than wasting effort attacking the use of HFC refrigerants, one should encourage the refrigeration industry to make the far greater gains possible by applying a more ‘holistic’ approach. Tackling the following areas will lead to major improvements:

Reduction in Leakage. Historical FC leakage levels are unacceptably high in many application areas. There is potential to reduce current average leakage rates by at least 30% - 40%. The potential is particularly good for distributed systems.

Reduction in System Charge. Using systems with much lower refrigerant charge can lead to further emission reductions. By using secondary refrigerant systems in appropriate applications charge can be reduced by up to 90%.

Energy Efficiency Improvements. Levels of efficiency in 1990 were relatively low. Savings of at least 25% can be cost effectively achieved.

Reduction in Fluorocarbon GWP. The average GWP of HFCs being used to replace CFCs is much lower (e.g HFC 134a has a GWP of 1300 compared to the fluid it replaces, CFC 12 with a GWP of 8100)

Reduction in Use of FCs. As described in Section 3, there are options to use ammonia, HCs and to eliminate refrigeration altogether. These should be adopted wherever it is appropriate.

Weighed against these areas for improvement, it should not be forgotten that there is potential for some growth in the market size for certain applications of refrigeration, particularly car and domestic/commercial air conditioning. The following sections will review in turn, the opportunities for emissions reduction in each of the refrigeration sectors. Balanced against this, the safety implications of switching to flammable refrigerants and the relative lack of experience of the use of these refrigerants will also be discussed.

March Consulting Group 11 EFCTC/CEFIC

Page 15: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

7. DIRECT EMISSION REDUCTION OPPORTUNITIES

The impact that any refrigerant will have on global warming is solely dependent on whether it is released to the atmosphere. If a “perfect” system could be produced in which leakage to the atmosphere never occurred and if the refrigerant was totally recycled at the end of it’s working life then the GW impact would be zero irrespective of the refrigerant GWP. Whilst such perfection is impossible, direct emission rates can be reduced substantially from current levels. Emissions should be minimised for all refrigerant options; if HFCs are used this is to prevent GW, whereas if ammonia or HCs are used low emissions are crucial for safe operation.

There are three basic opportunities for reducing direct GW emissions:

Reduction of annual leakage rate.

Reduction of refrigerant charge.

Improved rate of recovery on system disposal.

The rate of leakage is highly dependent on the type of application and design considered. Domestic refrigerators and other small hermetic systems are factory built using only welded or brazed joints and hence leakage is minimal. They also contain very small refrigerant charges. Historical leakage rates are only about 1% of the refrigerant charge per year. There is little potential to improve this leakage rate or to reduce the refrigerant charge. For small hermetic systems there is an opportunity to improve the rate of recovery at the end of system life or to use hydrocarbon refrigerants in place of HFCs. However, energy usage represents about 98% of the TEWI of an HFC 134a refrigerator and it is this impact that requires most attention.

Larger systems fall into two main categories involving either distributed use of refrigerant or more confined use of refrigerant in a "central plant". The potential for leakage in distributed systems is particularly significant as they usually involve numerous pipe joints and valves which have to be fitted on site. Distributed systems usually contain a relatively high specific refrigerant charge (i.e. the ratio of quantity of refrigerant (kg) to cooling duty (kW)). There are numerous examples of distributed system ranging from small split system air-conditioning units, through supermarket systems to large industrial plants used in food manufacture and cold storage. Historical leakage rates from distributed systems using fluorocarbons are high. A typical 1990 supermarket system loses 30% of the refrigerant charge per year and the specific refrigerant charge is high because of the length of distribution pipework required. It is interesting to note that leakage rates from distributed ammonia systems tend to be lower because steel pipework is used (which is less prone to certain types of leakage problem than copper pipework) and continual effort is made to limit leakage of this highly toxic refrigerant.

Central plants fall between the leakage rates of small hermetic systems and the distributed systems described above. These plants are substantially factory built, with higher levels of manufacturing quality control available than for site erected systems. Specific refrigerant charge has the potential to be lower than equivalent distributed systems, although many older designs (using flooded shell and tube evaporators) actually have a quite high specific refrigerant charge. Modern evaporator designs,

March Consulting Group 12 EFCTC/CEFIC

Page 16: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

especially plate heat exchangers, can lead to significant reductions in the specific refrigerant charge of a central plant. Historical leakage rates from central plants have typically been in the region of 10% per year. Significant potential exists for reduction in leakage rates from both distributed and central systems.

Transport refrigeration systems and mobile air-conditioning face extra problems from the leakage perspective because of significant levels of vibration and the effect of impact with small objects like grit and stones. In countries where salt is applied to roads to prevent freezing there is the added potential problem of corrosion. Historically mobile air-conditioners, particularly those built and used in the USA have had a very poor leakage record with annual leakage of 50% to 100% of refrigerant charge. Private discussions with a major European car manufacturer indicate that there is enormous potential for improving this historical position. They indicate that a well designed system can achieve leakage rates of about 2% per year.

With the exception of small hermetic systems it is clear from the description above that there is significant potential to reduce annual leakage rates and specific refrigerant charge in many areas of refrigeration application. This potential can be achieved at relatively low cost by applying a number of "common sense" design and maintenance principles to the industry. A few examples of key areas for attention include:

reducing large leaks from distributed systems that currently use over-stressed copper pipework

reducing the gradual leakage that occurs from systems that use flared compression joints to connect pipework

improving the design of valves to reduce leakage through valve stem seals

improving the design of compressors to avoid shaft seal leakage

improving management techniques to detect leaks early and to ensure that they are quickly repaired.

Whilst the technical potential for leakage reduction is excellent there needs to be some process put in place to ensure that this potential is achieved. This could either be through voluntary agreement or legislation. Although leakage from refrigeration systems has improved during the last five years, it appears that current legislation is not strong enough to encourage more effective and widespread improvement.

It is interesting to note that a number of refrigerant leakage Codes of Practice have been recently published by organisations in the refrigeration industry (e.g. the UK Institute of Refrigeration published such a code in 1996, source: IOR). A voluntary agreement between the UK refrigeration industry and UK Government concerning use of HFCs in refrigeration quotes this Code of Practice as the basis for leakage standards. The ‘Responsible Refrigeration’ concept being promoted by chemical companies and the refrigeration industry encourages this type of action. Nevertheless, there is still a lot of room for improvement. Bearing in mind the excellent potential it may be appropriate for HFC emission standards to be legislated as is the case in the Netherlands.

March Consulting Group 13 EFCTC/CEFIC

Page 17: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

8. ENERGY EFFICIENCY OPPORTUNITIES

As discussed in previous sections of this report the energy efficiency of refrigeration systems represents a key opportunity for reducing global warming impact. Data for 1990 showed that energy usage represented approximately 45% of the total TEWI for refrigeration. If the opportunities to reduce direct emissions, described in Section 7, are adopted then the need for energy efficiency becomes even more significant.

There is really excellent scope for the improvement of the efficiency of refrigeration systems. In many existing systems 20% can be saved at relatively low cost. The overall technical potential may be as high as 40%. This scope has been well understood for many years. Whilst there are some signs of efficiency improvements over the last five years, there is still a massive untapped potential. (Sources: there are a number of useful publications discussing refrigeration efficiency issues. The following paragraphs make use of examples and data from various UK documents including EEBPP 2, 3, 4, 5, 6 and UK DoE 3).

When comparing the relative benefits of using HFCs, ammonia or HCs is it important to establish how much the selection of the refrigerant can affect the energy efficiency? There is a lot of evidence to show that differences between the main refrigerant options only have a secondary influence on energy efficiency. Refrigerants do exhibit varying thermodynamic performance and hence energy efficiency, but there are a number of other issues that are of far more importance to refrigeration plant efficiency. Ironically, in many of the publications extolling the virtues of alternative refrigerants little attention has been given to general opportunities for improving energy efficiency.

Refrigeration Efficiency Opportunities

The opportunities for improving the efficiency of refrigeration systems can be sub- divided into the following five groups:

1. Reduction of cooling demand. When considering any new refrigeration application the essential first step is to review the cooling demand and make every effort to reduce the size of the cooling load. There are numerous ways to do this. In a domestic refrigerator, insulation thickness can be increased. In a building air-conditioning system efforts can be made to shade the building from solar gain or to use free cooling at those times of the year when ambient temperatures are low enough. In many refrigeration applications auxiliary loads such as evaporator fans, refrigerant pumps and cold store lighting can be better designed and controlled to reduce power input. It is surprising how many refrigeration systems are built without a proper review of these cooling load reduction opportunities. The overall technical potential for reducing cooling demands is probably in excess of 25%.

2. Improved system design. Once the cooling load has been minimised there are usually numerous system options available to the plant designer. Historically, many high efficiency design options have been ignored or overlooked. A particularly common mistake is to design a plant to be efficient at the ‘design point’ (maximum cooling load under summer time operating conditions). Most systems actually spend much of the time running with lower cooling loads and cooler ambient conditions, but rarely does the design enable performance to be optimised at all these different conditions. Another common design fault is to

March Consulting Group 14 EFCTC/CEFIC

Page 18: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

oversize the system, leading to poor part load efficiency. Many existing plants employ very poor control systems and these can have a great influence on efficiency. There are numerous other system design opportunities such as use of sophisticated cycles (e.g. two stage systems) and use of techniques such as thermal storage. The overall technical potential for improved system design is probably in excess of 20%.

3. Improved component design and selection. The individual components in a refrigeration system require careful selection if efficiency is to be optimised. The most important opportunity is compressor efficiency. Many existing plants utilise compressors of relatively poor efficiency. Improvements of 10% can often be made at no extra cost. Use of extra evaporator or condenser surface area can often be a worthwhile investment. Other detailed issues such as pipe line and valve pressure drop, defrost system design, oil separation effectiveness etc. all have an influence on efficiency. The overall technical potential for improved component design and selection is probably in excess of 15%.

4. Improved operation and maintenance practices. Even if a plant is designed to have very high efficiency there is no guarantee that this level of performance will be achieved during the operating life of the equipment. Because refrigeration systems are relatively complex many end users find it difficult to ensure that efficient operation is maintained. When existing refrigeration systems are carefully analysed by experts it is the norm to find significant opportunities for efficiency improvements. These can usually be achieved by small changes in operating practice (such as better compressor sequencing or temperature control) or improved maintenance (such as ensuring no build up of non-condensable gases in the condenser or reducing excessive frost on evaporators). Very few refrigeration systems have sufficient metering to allow proper energy efficiency analysis to be carried out on a regular basis. For example, compressors are rarely fitted with kWh meters. The overall technical potential for improved operation and maintenance practices is probably in excess of 20%.

5. Optimum selection of refrigerant. As discussed in the introduction to this section there are differences between the thermodynamic performance of different refrigerant fluids. Whilst these could in theory lead to significant differences in efficiency, it should be noted that few fluids would reach the market if their performance was significantly worse than competing options. For a wide range of refrigeration applications one would not expect more than about a 5% difference in efficiency between ammonia or the most appropriate HFC or hydrocarbon.

It is clear from the description given above that there are really excellent opportunities for refrigeration users to make energy efficiency improvements. What is of crucial importance to the refrigerant selection process is to note that refrigerant properties are one of five areas for potential improvement of energy efficiency and that they represent the smallest of these opportunities. Hence, when assessments are made of the potential to reduce indirect GW impact, the selection of the refrigerant itself has little overall influence.

March Consulting Group 15 EFCTC/CEFIC

Page 19: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

9. SAFETY ISSUES

When selecting a refrigerant, safety issues cannot be overlooked. The major drawbacks of HFC alternatives are the safety characteristics. Ammonia is highly toxic and slightly flammable; HCs are highly flammable. The small potential for TEWI improvement through use of zero/low GWP refrigerants must be offset against additional safety risks. It is striking that little research has been published regarding the relative risks of HFCs, HCs and ammonia.

Table 2 illustrates some of the characteristics of different refrigerants from a safety perspective. The toxicity rating is given in terms of the Occupational Exposure Limit (OEL). The 1000 ppm limit on non-toxic substances is to prevent any danger of suffocation due to oxygen displacement. Flammability properties are characterised by the concentration limits in which combustion can take place and by the auto-ignition temperature. The very low concentration that is required to sustain combustion with iso-butane is an indication of the high level of flammability of hydrocarbons. Most HFC refrigerants are non-flammable, as illustrated by HFC 134a. However, HFC 32 has been included to illustrate that some are flammable. In most situations HFC 32 is used in a mixture with other HFCs. The mixtures are carefully formulated to ensure zero flammability throughout their full operating range and in leakage situations.

Table 2 Toxicity and Flammability Characteristics of Certain Refrigerants

Refrigerant Toxicity Rating

OEL, ppmFlammability Ratings

Flammability limits% concentration in air

Auto-ignitionTemperature oC

Ammonia 25 15 to 28% 630Iso-Butane 1000 1.8 to 8.5% 460HFC 134a 1000 Non-flammableHFC 32 1000 12.7 to 33.4% 648

The risk of a fatality from ammonia refrigeration systems is estimated to be at least 1.5 per million installations per year (Source - IEA). If the 30 million commercial and industrial refrigeration systems estimated to be in the EU were all operated on ammonia this could result in an additional 50 fatalities each year. This assumes that accident rates remain the same as those in historical data. If there is much more widespread use of ammonia it is likely that the accident rate would rise because of the lack of experience of ammonia use in both the refrigeration contracting and end user sectors.

There is little published data on the risk factors related to HC refrigerants as they are not currently in widespread use. It is reasonable to assume that the safety record for HCs used in domestic refrigeration and small hermetic units should be good as long as stringent quality control is maintained, since the actual refrigerant charge is very low. However, even a risk factor 100 times better than that for ammonia systems could still result in a number of fatalities in the EU due to the high number of units in use. For larger systems, with higher refrigerant charge and greater risk of leakage, risks are likely to be even higher than for ammonia because of the high flammability.

March Consulting Group 16 EFCTC/CEFIC

Page 20: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

There is also little published data for risks related to HFCs, but some is available on use of CFCs and HCFCs. These have led to some fatalities over the years, mainly due to suffocation. This is a risk with any inert gas; e.g. engineers have died in confined areas that are full of refrigerant vapour. The number of fatalities reported is far lower than for ammonia systems, even though there are significantly more FC systems in use. The risk of fatalities with FCs is several orders of magnitude lower than for ammonia (source IEA).

Track Record and Experience with Installations

There is inadequate contractor and end user experience to cope with a rapid mass switch away from FCs to ammonia or HCs. For example, in the UK there is a Refrigerant Handlers Register that proves the competence of technicians operated by the Air-conditioning and Refrigeration Industry Board. They currently have 2350 technicians registered to handle HFCs and only 100 registered for ammonia (4% of the total). A rapid switch to ammonia or HCs would entail a massive requirement for re-training. Calor Gas, a supplier of HCs has trained over 3000 engineers in the UK. However, there are few non-domestic HC installations, so the majority of these will have had no further experience with HCs. There is even less ammonia or HC experience amongst engineers in end-user companies – particularly in non-industrial organisations. The use of inexperienced operators on toxic/flammable systems could considerably raise the accident rate.

Suitability of refrigerants to different systems

Given the safety issues raised above, a responsible approach to the substitution of FCs with flammable or toxic refrigerants is clearly required. Table 1 on page 7 summarises a logical framework for cost effective and safe refrigerant application.

For Very Small Systems ammonia cannot easily be used because of materials compatibility problems. Selection of HCs is a reasonable option; safety risks should be small as only a small refrigerant charge is used and leakage is minimal. However, caution should be exercised as little track record of performance yet exists and maintenance contractors have limited hands-on experience.

For Distributed Systems used in public areas great care is required since leakage rates are high and untrained people are in an area of potential leakage. Ammonia and HCs are not appropriate (and sometimes not allowed by safety codes, source BS 1). If HFCs are used it is essential that sufficient investment is made in leakage prevention.

For Distributed Systems used in restricted areas there is more flexibility as staff can be trained what to do if a major leak occurs. Ammonia or HFCs can be considered for this type of system. The high flammability of HCs makes them inappropriate in ‘normal’ working areas such as food production halls. They may be applicable in special situations, such as outdoor distributed systems in petrochemical works.

For Secondary Refrigerant Systems it is reasonable to consider any of the three main options as safety issues are easier to deal with in a single plant room with restricted access. However, before there could be widespread use of ammonia or HCs in new secondary refrigerant application areas such as supermarkets it is essential that the contractor experience issues discussed above be addressed.

March Consulting Group 17 EFCTC/CEFIC

Page 21: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

10. END USE SECTOR REVIEW

Each sector of the refrigeration market has unique characteristics that define the potential for reducing the global warming impact. To simplify analysis it is useful to consider six distinct sectors of the refrigeration market, namely: domestic; small commercial (e.g. shops, pubs, hotels) large commercial (supermarkets); industrial; building air-conditioning; mobile air-conditioning. In each sector it is possible to estimate the GW impact of a number of scenarios that incorporate the opportunities introduced in Section 6. The scenarios used in this report are as follows:

Scenario 1. Baseline estimate of 1990 GW emissions (defined as 100)

Scenario 2. Easy reductions in leakage (direct emissions)

Scenario 3. Scenario 2 + easy reductions in energy efficiency (indirect emissions)

Scenario 4. Scenario 3 + further investment in both leakage prevention and energy efficiency

Scenario 5. Scenario 4 + widespread substitution of FCs with ammonia or HCs.

It is important to note that Scenarios 2 and 3 can be applied to existing systems, through ‘retrofit’ investments whereas Scenarios 4 and 5 are only cost effective when applied to new (or replacement) systems.

Sector 1 Domestic Refrigeration

Domestic refrigeration systems are hermetically sealed units, thus leakage rates are low. In 1990 only 4% of the total TEWI was due to the direct impact of the CFC 12 refrigerant used. HFC 134a has a GWP that is less than 20% of the GWP of CFC 12, hence direct emissions from HFC refrigerators are only about 1% of the total (assuming no change in efficiency). The energy efficiency of the unit is of crucial importance. A recent report (Source Greenpeace 2) outlined the following potential areas for reducing emissions from domestic refrigerators and freezers:

Improvement Potential Saving (%)

Increasing insulation 30More Efficient Compressor 15Enlarge Condensing Area 5Redesign Evaporator 5-10Improve Control Thermostat 4-6Door Gasket Improvement 3Use HCs instead of HFCs 1

This data clearly shows the excellent efficiency opportunities and the small impact of refrigerant substitution. Also, data from Energy Labels used on domestic refrigerators and freezers (required by EC Regulations) show enormous variation of efficiency for currently available models. The best category uses 60% less energy than the worst.

March Consulting Group 18 EFCTC/CEFIC

Page 22: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

It is reasonable to assume a minimum potential of 40% improvement in efficiency for domestic refrigeration. Scenarios 2 and 3 show little emission improvement because there are few ‘retrofit’ opportunities with existing units. Scenario 4 shows a massive improvement due to efficiency. With further development of technology there may be potential for at least another 10% improvement in Scenario 4. Scenario 5 only shows a further 1% improvement.

Sector 2. Small Commercial Refrigeration

This category includes a wide range of equipment found in retail premises. Examples include chilled and frozen display cases in food shops and petrol garages, small cold stores in hotels and restaurants, cellar coolers and bottle coolers in pubs and bars etc. Many of these small commercial systems are factory built hermetic units. They have similar characteristics to domestic systems i.e. small refrigerant charge, low leakage and good potential for energy efficiency. The larger systems in this category (e.g. cold stores, cellar coolers and display cases in larger shops) are of a ‘distributed refrigerant’ design (see Table 1 in Section 3).

These systems have a large refrigerant charge and are constructed on site. The potential for leakage is quite considerable. Historical leakage levels are high and there is good potential for leakage reduction (2). Energy efficiency can be significantly improved through both technical and management measures (3). Further improvements for leakage and energy efficiency are likely for new systems (4). A move away from HFCs gives only a small improvement, because distributed systems must use HFCs (5).

Sector 3. Large Commercial (Supermarket) Refrigeration

Large supermarkets are one of the most important refrigeration sub-sectors. A modern supermarket uses 2 large distributed refrigerant systems, for low temperature and chilled requirements. Refrigerant is piped to numerous display cases in the store and to small cold stores in non-public areas. Refrigerant charge can be in excess of 1 tonne and there are long runs of copper pipework connecting the display cases to the plant room. Historical leakage levels have been very high and there is plenty of potential for improvements to both leakage and energy efficiency.

This is a sector where it could well be possible to achieve reduced emissions by switching to secondary refrigeration systems. The use of a secondary refrigerant loop

March Consulting Group 19 EFCTC/CEFIC

Page 23: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

will considerably reduce systems charge and % annual leakage rates. It will also ensure that the public is not exposed to a risk of a refrigerant leak. However, it may lead to lower efficiency, as the secondary loop will necessitate extra pumping power.

The options for improvement are detailed opposite. Replacement with HFCs and less leaky systems (2), is the least expensive option. Energy efficiency improvements of around 25% should be achievable with existing types of system (3). Optimised secondary loop systems with lower refrigerant charge and with lower leakage, using HFCs (4) or ammonia (5) give excellent potential. Again this demonstrates that it is the indirect emissions which are the most important to address, particularly once leakage is reduced

Sector 4. Industrial Refrigeration

This is another large and important refrigeration sub-sector. It includes a wide range of designs and applications, many of which are in the food, drink, chemicals and pharmaceuticals industries. The sector was the only one to make use of ammonia and HCs prior to 1990. There is a mixture of distributed refrigerant and central chillers/secondary refrigerant systems in use. Distributed ammonia systems containing several tonnes of refrigerant are not uncommon in the food and cold storage industries. This illustrates that safety issues can be addressed in an industrial environment where staff can be trained how to react if a large ammonia leak occurs.

Whilst the leakage performance of existing ammonia and HC systems is already reasonable, many industrial FC systems have high levels of leakage which could be improved (2). Energy saving potential is good for all categories of plant (3). There is some scope for additional efficiency and leakage improvements for new plant (4). A move away from HFCs is also possible (5). The industrial sector also has a number of significant opportunities for cooling load elimination or load reduction.

Sector 5. Building Air Conditioning

This large sector includes very small systems in houses and offices, larger

March Consulting Group 20 EFCTC/CEFIC

Page 24: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

distributed refrigerant systems (mostly used in offices, hotels etc.) and central chilled water systems.

Average leakage rates in 1990 were around 16% per annum. Starting from this 1990 baseline (1), leakage rate can be reduced to 4% per annum representing current practice (2). Efficiency is also an area where big improvements can be made. Some easy improvements are achievable (3). Leakage can be reduced to 1% in best practice situations and considerable further efficiency gains made (4). Finally, in some cases where safety considerations allow, a shift away from HFCs is also possible (5).

Sector 6. Mobile Air Conditioning

At present mobile air conditioning has a very poor environmental performance. The fuel consumption of a car with a/c is increased by 15-25%. It is estimated that around 30% of the refrigerant is lost each year (Source - EU Report). Discussions with a major European car manufacture determined that current systems are approximately 50% less leaky than those in use in 1990. However, whilst a well maintained and cleaned car may expect to retain its refrigerant charge for around 8 years, one exposed to corrosion from road salt can lose its charge after as little as two years.

Efforts are being made to improve both leakage (2) and efficiency (3), but improvements will be offset by the likely increase in market for these systems. Safety issues may preclude the use of flammable refrigerants. Corrosion from road salt and accident damage may limit the scope for further leakage reduction (4). Tests on the suitability of CO2 as a refrigerant are currently being conducted. It is likely that CO2 systems would be heavier and less efficient than HFC systems, thus a move away from HFCs may increase the indirect emissions.(5)

March Consulting Group 21 EFCTC/CEFIC

Page 25: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

11. HISTORICAL AND FUTURE GLOBAL WARMING IMPACT

In this final section we combine the results of the sectoral analysis in Section 10, to present the potential for GW emission reduction in refrigeration and air-conditioning.

Great care must be taken when analysing historic emissions figures. Retrospective figures for greenhouse gas emissions paint a very confusing picture, since CFCs and HCFCs are often ignored. The rationale for this is that the substances are being banned from use under the Montreal Protocol and 1990 usage is not relevant. This is a very questionable approach and disguises the real improvements made in the refrigeration (Source IIR). Ignoring the CFC/HCFC contribution to the 1990 baseline is no more logical than ignoring fuel usage from a type of vehicle no longer allowed under safety legislation!

Since 1990, all the FC user industries have made great strides in reducing emissions of greenhouse gases. The GW emissions of FCs produced in the EU, expressed in Mtonnes CO2 equivalent, fell from 1100 in 1990 to just 200 in 1995.

Direct Emissions from Refrigeration

By implementing the technical improvements outlined in this document, the refrigeration industry will be able to reduce the direct emissions impact of refrigeration by almost a factor of ten by the year 2010. Figure 11 shows the potential fall in direct emissions for all refrigeration and air-conditioning systems based on Scenarios 4 and 5 described in Chapter 10.

It is clear that the potential is excellent in both cases. Under Scenario 4, which assumes widespread use of HFCs an 85% reduction is possible. The total direct GW emissions of refrigerant from the EU, expressed in Mtonnes CO2 equivalent, would fall from around 200 in 1990 to just 30 by 2010. Scenario 5, based on almost complete substitution of FCs with ammonia and HCs gives a 98% reduction. However, HFCs will not be replaceable in all cases, due to safety or efficiency constraints. Taking indirect emissions into account (see figure 13) there is little difference between the GW impact of Scenarios 4 and 5.

March Consulting Group 22 EFCTC/CEFIC

Page 26: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

Indirect Emissions from Refrigeration

The indirect emissions due to refrigeration are also likely to fall over this period, but by a smaller amount. The technical improvements outlined in Section 8 are capable of reducing energy requirements by at least 50%. However, this saving must be balanced against the likely increase in the market for refrigeration systems, particularly in the commercial and car air conditioning sectors. In total, an indirect emissions reduction of around 25% by the year 2010 seems likely. Figure 12 below shows no difference between the indirect emissions for Scenarios 4 or 5. The impact of refrigerant selection is regarded as negligible on energy efficiency. There are many ‘market uptake’ assumptions built in to our efficiency estimates which would potentially have a much larger impact on overall indirect emissions than the energy efficiency differences attributable to use of the alternate refrigerants.

Overall Potential for Refrigeration and Air-conditioning

Combining the direct and indirect effects we can see the overall potential for refrigeration GW impact in Figure 13.

March Consulting Group 23 EFCTC/CEFIC

Page 27: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

The figure clearly illustrates the excellent overall potential. It also emphasises the relatively small difference between Scenarios 4 and 5.

Comparison with an Energy Using Sector

The reduction potential for refrigeration and air-conditioning is particularly impressive when viewed in comparison to likely emissions over the next 20 years from other sectors such as transport.

From 1990 to 1994, the period for which figures are available, only two sectors, refrigeration and fossil fuel electricity generation have made major reductions in greenhouse gases emitted. Emissions from industry has remained broadly constant, whilst the emissions from the transport sector rise inexorably. Figure 14 details the predicted contributions from transport in the EU. These figures are extrapolated from UK Government predictions for the UK (Source UK Climate Change). It is assumed that trends in UK transport emissions broadly mirror those of the EU as a whole.

Whilst significant efficiency improvements are expected in transport, the GW emissions from transport continue to rise due to market growth. For refrigeration, which will also experience some market growth, GW emissions are predicted to fall rapidly, mainly due to improvements in leakage rates and improvements in the energy efficiency of the systems.

Conclusions

By the year 2010, the contribution of refrigeration to total global warming emissions may have fallen from 7% in 1990 to just under 3%. This assumes that total emissions due to human activity can be stabilised at 1990 levels, a situation that is still not clear. This large reduction assumes widespread use of HFC refrigerants. It will be achieved through the sensible use of efficient refrigeration systems and the selection of the most appropriate, safe and energy efficient refrigerant for each application.

March Consulting Group 24 EFCTC/CEFIC

Page 28: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

APPENDIX 1 GLOSSARY OF TERMS

CFC Chlorofluorocarbon, a member of the FC family containing only chlorine, fluorine and carbon.

Distributed systems Refers to refrigeration systems in which the primary refrigerant is circulated around a building, factory or process to deliver cooling.

FC Fluorocarbons - a family of chemicals manufactured by replacing hydrogen atoms in HC molecules with fluorine or chlorine

GWP Global warming potential, compared to the GWP of CO2 which is defined as 1. All GWP figures used in this report are based on the 100 year time horizon.

GWP tonnes A measure of global warming impact obtained by multiplying the tonnes of emission of a gas by its GWP.

Hermetic system Refers to a hermetically sealed refrigeration system with an all welded construction. There are no gaskets or rotating seals.

HC Hydrocarbons - a family of chemicals containing hydrogen and carbon.

HCFC Hydrochlorofluorocarbon, a member of FC family containing hydrogen, chlorine, fluorine and carbon.

HFC Hydrofluorocarbon, a member of the FC family containing only hydrogen, fluorine and carbon.

ODP Ozone Depletion Potential, compared to ODP of CFC11 which is defined as 1.

OEL Occupational exposure limit, a measurement of toxicity based on the concentration level permissible in areas with long term human occupation.

Secondary systems Refers to refrigeration systems in which a secondary fluid such as water or glycol solution is cooled by a primary refrigerant and then circulated around a building, factory or process to deliver cooling.

Specific refrigerant charge The ratio of the quantity of refrigerant contained in a system divided by the cooling duty (kg/kW).

March Consulting Group 25 EFCTC/CEFIC

Page 29: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

APPENDIX 2 REFERENCES

AFEAS “Energy and Global Warming Impacts of CFC Alternative Technologies”, AFEAS and US DoE, 1991

BS 1 BS 4434 “Safety and environmental aspects in the design construction and installation of refrigerating appliances and systems”, British Standards Institute, 1995

EC DGIII “HCFCs and their alternatives in the European Union”, EC DGIII Report, 1997

EEBPP 1 UK DoE Energy Efficiency Best Practice Programme (EEBPP), Refrigeration Market Strategy Report, 1992

EEBPP 2 UK DoE EEBPP, Good Practice Guide 36, “Commercial Refrigeration: Energy Efficient Operation and Maintenance”

EEBPP 3 UK DoE EEBPP, Good Practice Guide 37, “Commercial Refrigeration: Energy Efficient Design”

EEBPP 4 UK DoE EEBPP, Good Practice Guide 42, “Industrial Refrigeration: Energy Efficient Operation and Maintenance”

EEBPP 5 UK DoE EEBPP, Good Practice Guide 44, “Industrial Refrigeration: Energy Efficient Design”

EEBPP 6 UK DoE EEBPP, Good Practice Guide 59, “Energy efficient design and operation of refrigeration compressors”

EU Report Workshop on EU Policies and Measures on Climate Change 29 May 1997. - Paper on EU Reduction Potential of Fluorocarbons - p6.

Greenpeace 1 “Hydrocarbons and Other Progressive Answers to Refrigeration” - Proceedings of the 1995 International CFC and Halon Alternatives Conference, Washington DC, October 1995. p19

Greenpeace 2 ibid p114 -117

ICI Report by McCulloch & Midgeley 1997

IEA International Energy Agency Heat Pump Programme, Report No HPP AN 20 1

IIR International Institute of Refrigeration, 12th Informatory note on fluorocarbons and refrigeration, 1997

IOR UK Institute of Refrigeration, Refrigerant Emissions Code of Practice, 1996

UK Climate Change Climate Change The UK Programme - pub HMSO (Her Majesty’s Stationary Office) 1997.

UK DoE 1 CFCs in the UK Refrigeration and Air-conditioning Industry, HMSO, 1992

March Consulting Group 26 EFCTC/CEFIC

Page 30: Template for the creation of standard format March …€¦ · Web viewTemperature oC Ammonia 25 15 to 28% 630 Iso-Butane 1000 1.8 to 8.5% 460 HFC 134a 1000 Non-flammable HFC 32 1000

/tt/file_convert/5eb573c12636777925454662/document.doc

UK DoE 1 UK Use and Emissions of Selected Halocarbons, SF6 and NF3, HMSO, 1996

March Consulting Group 27 EFCTC/CEFIC