Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong 523942, China Tel: +86 769 8593 5656 Fax: +86 769 8599 1080 Email: customerservice.dg@cn.bureauveritas.com Page 1 of 174 TEST REPORT NRS 097-2-1 VER.0 TEST REPORT NRS 097-2-1 Grid interconnection of embedded generation Part 2: Small-scale embedded generation Report reference number .............. : PVZA160707N051 Date of issue .......................... ……...: 2016-07-25 Total number of pages ........... ……...: 174 Testing laboratory name ............... : Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch Address ............................................ : No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong 523942, China Applicant's name............................ : Huawei Technologies Co., Ltd Address ............................................ : Administration Building, Headquarters of Huawei Technologies Co., Ltd., Bantian, Longgang District, Shenzhen, 518129, P.R.C Test specification Standard ........................................... : NRS 097-2-1:2010 Zertifikate ....................................... : Certificate of compliance Test report form number. ................. : NRS 097-2-1 Master TRF ...................................... : Bureau Veritas Consumer Products Services Germany GmbH Test item description ..................... : Grid-tied connected photovoltaic inverter Trademark ........................................ : Model / Type .................................... : SUN2000-36KTL, SUN2000-42KTL Ratings ............................................ : SUN2000-36KTL SUN2000-42KTL MPP DC voltage range [V] ............... : 480-850V or 580-850V 580-850V Input DC voltage range [V] ............... : 200-1000V, Max. 1100 Input DC current [A] ......................... : Max. 22,0 x 4 Output AC voltage [V] ...................... : 400, 3(N)~* + PE, or 480, 3~ + PE, 50Hz 480, 3~ + PE, 50Hz Output AC current [A] ....................... : Max. 57,8 x3 (400Vac) or max. 48,2Ax3 (480Vac) Max. 56,6 x3 Output power [VA] ............................ : Max. 40000 Max. 47000 * Choose whether to connect the neutral wire to the SUN2000-36KTL based on the application scenario.

Upload: others

Post on 10-Jul-2020

14 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 1 of 174 TEST REPORT NRS 097-2-1 VER.0

TEST REPORT

NRS 097-2-1 Grid interconnection of embedded generation

Part 2: Small-scale embedded generation

Report reference number .............. : PVZA160707 N051

Date of issue .......................... ……...: 2016-07-25

Total number of pages ........... ……...: 174

Testing laboratory name ............... : Bureau Ve ritas Shenzhen Co., Ltd. Dongguan Branch

Address ............................................ : No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong 523942, China

Applicant's name ............................ : Huawei Technologies Co., Ltd

Address ............................................ : Administration Building, Headquarters of Huawei Technologies Co., Ltd., Bantian, Longgang District, Shenzhen, 518129, P.R.C

Test specification

Standard ........................................... : NRS 097-2-1:2010

Zertifikate ...................................... . : Certificate of compliance

Test report form number. ................. : NRS 097-2-1

Master TRF ...................................... : Bureau Veritas Consumer Products Services Germany GmbH

Test item description ..................... : Grid-tied connected photovoltaic inverter

Trademark ........................................ :

Model / Type .................................... : SUN2000-36KTL, SUN2000-42KTL

Ratings ........................................... . : SUN2000-36KTL SUN2000-42KTL

MPP DC voltage range [V] ............... : 480-850V or 580-850V 580-850V

Input DC voltage range [V] ............... : 200-1000V, Max. 1100

Input DC current [A] ......................... : Max. 22,0 x 4

Output AC voltage [V] ...................... : 400, 3(N)~* + PE, or 480, 3~ + PE, 50Hz

480, 3~ + PE, 50Hz

Output AC current [A] ....................... : Max. 57,8 x3 (400Vac) or max. 48,2Ax3 (480Vac)

Max. 56,6 x3

Output power [VA] ............................ : Max. 40000 Max. 47000

* Choose whether to connect the neutral wire to the SUN2000-36KTL based on the application scenario.

Page 2: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 2 of 174 TEST REPORT NRS 097-2-1 VER.0

Testing Location ............................ : Bur eau Veritas Shenzhen Co., Ltd. Dongguan Branch

Address ............................................ : No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong 523942, China

Tested by (name and signature) ....................... :

Sean Tu

Approved by (name and signature) ....................... :

James Huang

Manufacturer’s name ..................... : Huawei Technologies Co., Ltd

Factory address ............................... : No.2 City Avenue, Songshan Lake Sci. & Tech. Industry Park, 523808 Dongguan, People’s Republic of China.

Document History

Date Internal reference Modification / Change / Sta tus Revision

2016-07-25 Sean Tu Initial report was written 0

Supplementary information:

Page 3: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 3 of 174 TEST REPORT NRS 097-2-1 VER.0

Test items particulars

Equipment mobility ........................... : Permanent connection

Operating condition .......................... : Continuous

Class of equipment .......................... : Class I

Protection against ingress of water .. : IP65 according to EN 60529

Mass of equipment [kg] .................... : 55,0

Test case verdicts

Test case does not apply to the test object ............................... : N/A

Test item does meet the requirement ................................ : P(ass)

Test item does not meet the requirement ................................ : F(ail)

Testing

Date of receipt of test item ............... : 2016-07-07

Date(s) of performance of test ......... : 2016-07-07 till 2016-07-22

General remarks: The test result presented in this report relate only to the object(s) tested. This report shall not be reproduced, except in full, without the written approval of the applicant.

”(see Annex #)" refers to additional information appended to the report. "(see appended table)" refers to a table appended to the report.

Throughout this report a comma is used as the decimal separator.

The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement of the PV-system. Therefore the values for tolerances given in EN 50438, Table 2 are used.

Tolerances on trip values tabel 2 EN50438: - Voltage: +/- 1% of the nominal voltage; - Frequency: +/- 0,5% of the nominal frequency - Clearance time: +/- 10%

This Test Report consists of the following document s:

1. Test Report

2. Annex No. 1 – EMC Test Report

3. Annex No. 2 – Datasheet of the relay

4. Annex No. 3 – Pictures of the units

5. Annex No. 4 – Test equipment list

Page 4: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 4 of 174 TEST REPORT NRS 097-2-1 VER.0

Copy of marking plate

Page 5: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 5 of 174 TEST REPORT NRS 097-2-1 VER.0

General product information: The units are three-phase The Solar inverter converts DC voltage into AC voltage. The input and output are protected by varistors to Earth. The unit is providing EMC filtering at the output toward mains. The unit does not provide galvanic separation from input to output (transformerless). The output is switched off redundant by the high power switching bridge and a two relays. This assures that the opening of the output circuit can operate in case of one error. SUN2000-36KTL(230/400Vac)

Page 6: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 6 of 174 TEST REPORT NRS 097-2-1 VER.0

SUN2000-36KTL(480Vac), SUN2000-42KTL:

Figure 1 Block digram

The internal control is redundant built. It consists of Microcontroller master DSP (U58) and slave DSP (U59).

The master DSP (U58) which can control the relays by switching signals; measures the voltage, frequency, AC current, DC-injection current, insulation resistance and residual current. In addition it tests the array isolation impedance and the RCMU circuit before each start up.

The slave DSP (U59) is user for detecting grid voltage, AC current, grid frequency and residual current, also can oen the relay, and communicate with Main DSP(U58) each other.

The unit provides two relays in series on each phase. When single-fault applied to one relay, an error code will appear on display panel, another redundant relay provides basic insulation maintained between the PV array and the mains. All the relays are tested before start up. Both DSP can open the relays.

The models SUN2000-36KTL and SUN2000-42KTL are identical to each other, the output power and voltage derated by software. Choose whether to connect the neutral wire to the SUN2000-36KTL based on the application scenario. If the rated output voltage of the SUN2000-36KTL is 400Vac, the MPP voltage range at full load is 480-850Vdc. If the rated output voltage is 480Vac, the MPP voltage range at full load is 580-850Vdc.

The product was tested on: Hardware version : V200R002 Software version : V200R002

Page 7: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 7 of 174 TEST REPORT NRS 097-2-1 VER.0

NRS 097-2-1:2010

Clause Requirement – Test Result – Remark Verdict

SECTION 4.1: Utility compatibility 4.1.1 General P 4.1.1.1 This clause describes the technical issues and the

responsibilities related to interconnecting an embedded generator to a utility network. Subclauses 4.1 and 4.2 are based on IEC 61727:2004.

Noticed. P

4.1.1.2 The quality of power provided by the embedded generator in the case of the on-site a.c. loads and the power delivered to the utility is governed by practices and standards on voltage, flicker, frequency, harmonics and power factor. Deviation from these standards represents out-of-bounds conditions. The embedded generator is required to sense the deviation and might need to disconnect from the utility network.

Noticed. P

4.1.1.3 All power quality parameters (voltage, flicker, frequency and harmonics) shall be measured at the PUC, unless otherwise specified (see annex A). The power quality shall comply with NRS 048-2. This implies that the combined voltage disturbances caused by the specific EG and other customers, added to normal background voltage disturbances, may not exceed levels stipulated by NRS 048-2. NOTE The frequency cannot be changed by an EG.

See appended table and Annex No. 1 – EMC Test Report.

P

4.1.1.4 The embedded generator’s a.c. voltage, current and frequency shall be compatible with the utility system in accordance with IEC 61727.

Noticed. P

4.1.1.5 The embedded generator shall be type approved, unless otherwise agreed upon with the utility (see annex A).

Noticed. P

4.1.1.6 The maximum size of the embedded generator is limited to the rating of the supply point on the premises.

Rely in the responsibility of the installer.

N/A

4.1.1.7 Embedded generators larger than 10 kW shall be of the three-phase type. NOTE This value refers to the maximum export potential of the generation device.

All inverters are three-phase type.

P

4.1.1.8 A customer with a multiphase connection shall split the embedded generator over all phases if the EG is larger than 6 kW. NOTE 1 Balancing phases in a multiphase embedded generator is deemed desirable. NOTE 2 In the case of long feeder spurs the maximum desired capacity of the EG might require approval by the utility and might result in the requirement for a three-phase connection.

Rely in the responsibility of the installer.

N/A

Page 8: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 8 of 174 TEST REPORT NRS 097-2-1 VER.0

NRS 097-2-1:2010

Clause Requirement – Test Result – Remark Verdict

SECTION 4.1: Utility compatibility 4.1.2 Normal voltage operating range P 4.1.2.1 In accordance with IEC 61727, utility-interconnected

embedded generators do not normally regulate voltage, they inject current into the utility. Therefore the voltage operating range for embedded generators is designed as protection which responds to abnormal utility network conditions and not as a voltage regulation function.

Derived from tests. P

4.1.2.2 The embedded generator shall synchronise (see 4.1.8) with the utility network before a connection is established. The embedded generator shall not control the voltage, unless agreed to by the utility (see annex A).

See appended table. P

4.1.3 Flicker The operation of the embedded generator, in conjunction with other existing and future loads at the same point of connection, shall not cause flicker levels to increase beyond the levels specified in NRS 048-2.

See appended table and Annex No. 1 – EMC Test Report.

P

4.1.4 DC injection The static power converter of the embedded generator shall not inject d.c. current exceeding 1 % of the rated a.c. output current into the utility a.c. interface under any operating condition in accordance with IEC 61727. This relates specifically to embedded generators where the static power converter has no simple separation from the utility network (e.g. inverters that are transformer-less).

See appended table. P

4.1.5 Normal frequency operating range An embedded generator that operates in parallel with the utility system shall operate within the frequency trip limits defined in 4.2.2.3.3.

See appended table. P

Page 9: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 9 of 174 TEST REPORT NRS 097-2-1 VER.0

NRS 097-2-1:2010

Clause Requirement – Test Result – Remark Verdict

SECTION 4.1: Utility compatibility 4.1.6 Harmonics and waveform distortion

(in accordance with IEC 61727) P

4.1.6.1 Only devices that inject low levels of current and voltage harmonics will be accepted; the higher harmonic levels increase the potential for adverse effects on connected equipment.

See appended table and Annex No. 1 – EMC Test Report.

P

4.1.6.2 Acceptable levels of harmonic voltage and current depend upon distribution system characteristics, type of service, connected loads or apparatus, and established utility practice.

See appended table and Annex No. 1 – EMC Test Report.

P

4.1.6.3 The embedded generator output shall have low current-distortion levels to ensure that no adverse effects are caused to other equipment connected to the utility system.

See appended table and Annex No. 1 – EMC Test Report.

P

4.1.6.4 Total harmonic current distortion shall be less than 5 % at rated generator output in accordance with IEC 61727. Each individual harmonic shall be limited to the percentages listed in table 1.

See appended table and Annex No. 1 – EMC Test Report.

P

4.1.7 Power factor The embedded generator shall not inject reactive power into the utility network, while the drain of reactive power shall be limited to a power factor of 0,9. These limits apply, unless otherwise agreed upon with the utility (see annex A).

See appended table. P

4.1.8 Synchronization P 4.1.8.1 The embedded generator shall synchronize with the

utility network before the parallel connection is made. Derived from tests. P

4.1.8.2 Automatic synchronization equipment shall be the only method of synchronization.

Derived from tests. P

4.1.8.3 The limits for the synchronizing parameters for each phase are

a) frequency difference: 0,3 Hz, b) voltage difference: 5 % = 11,5 V per phase, and c) phase angle difference: 20°.

Derived from tests. P

Page 10: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 10 of 174 TEST REPORT NRS 097-2-1 VER.0

NRS 097-2-1:2010

Clause Requirement – Test Result – Remark Verdict

SECTION 4.2: Safety and protection 4.2.1 General

The safe operation of the embedded generator in conjunction with the utility network shall be ensured at all times.

Noticed. P

4.2.2 Safety disconnect from utility network P 4.2.2.1 General

The embedded generator shall automatically and safely disconnect from the grid in the event of an abnormal condition. Abnormal conditions include

a) network voltage or frequency out-of-bounds conditions,

b) loss-of-grid conditions, and d.c. current injection threshold exceeded.

Derived from tests. P

4.2.2.2 Disconnection switching unit P 4.2.2.2.1 The embedded generator shall be equipped with a

disconnection switching unit which separates the embedded generator from the grid due to the above abnormal conditions. The disconnection unit may be integrated into one of the components of the embedded generator (for example the PV utility-interconnected inverter) or may be an independent device installed between the embedded generator and the utility interface.

The transformer less inverter provides two relays in series for each line.

P

4.2.2.2.2 The disconnection switching unit shall be able to operate under all operating conditions of the utility network.

The disconnection switching unit was tested according the single fault safety of the VDE0126-1-1. See appended table.

P

4.2.2.2.3 A failure within the disconnection switching unit shall lead to disconnection and indication of the failure condition.

See appended table. P

4.2.2.2.4 A single failure within the disconnection switching unit shall not lead to failure to disconnect. Failures with one common cause shall be taken into account and addressed through adequate redundancy.

The disconnection switching unit was tested according the single fault safety of the VDE0126-1-1. See appended table.

P

Page 11: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 11 of 174 TEST REPORT NRS 097-2-1 VER.0

NRS 097-2-1:2010

Clause Requirement – Test Result – Remark Verdict

SECTION 4.2: Safety and protection 4.2.2.2.5 The disconnection switching unit shall disconnect from

the network by means of two series switches. Each switch shall be separately rated to the embedded generator’s nominal power output. At least one of the switches shall be an electromechanical switch while the second switch may be part of the existing solid state switching circuits of a utility-interconnected static power converter. The electromechanical switch shall disconnect the embedded generator on the neutral and the live wire(s). NOTE 1 The switching unit need not disconnect its sensing circuits. NOTE 2 A mains-excited induction generator requires only a single disconnection switch as the generator requires excitation from the utility network to operate. NOTE 3 A static power converter without simple separation should make use of two series-connected electromechanical disconnection switches.

The transformer less inverter provides two relays in series for each line.

P

4.2.2.2.6 The fault current breaking capacity of the disconnecting switch shall be appropriately sized for the application.

See Annex No. 2 – Datasheet of the relay.

P

Page 12: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 12 of 174 TEST REPORT NRS 097-2-1 VER.0

NRS 097-2-1:2010

Clause Requirement – Test Result – Remark Verdict

SECTION 4.2: Safety and protection 4.2.2.3 Overvoltage, undervoltage and frequency P 4.2.2.3.1 General

Abnormal conditions can arise on the utility system and requires a response from the connected embedded generator. This response is to ensure the safety of utility maintenance personnel and the general public, and also to avoid damage to connected equipment. The abnormal utility conditions of concern are voltage and frequency excursions above or below the values stated in this clause. The embedded generator shall disconnect if these conditions occur.

See appended table. P

4.2.2.3.2 Overvoltage and undervoltage The embedded generator shall cease to energize the utility distribution system should the network voltage deviate outside the conditions specified in table 2. This applies to any phase of a multiphase system. The system shall sense abnormal voltage and respond. The following conditions shall be met, with voltages in r.m.s. and measured at the PUC. NOTE All discussions regarding system voltage refer to the nominal voltage. The purpose of the allowed time delay is to ride through short-term disturbances to avoid excessive nuisance tripping. The generator does not have to cease to energize if the voltage returns to the normal utility continuous operating condition within the specified trip time. A customer with a multiphase connection and a single-phase embedded generator above 3 kW shall monitor all phases for out-of-bounds voltage conditions. The EG shall be disconnected if an out-of-bounds voltage condition is detected on any of the phases.

See appended table. P

4.2.2.3.3 Overfrequency and underfrequency The embedded generation system shall cease to energize the utility network when the utility frequency deviates outside the specified conditions. When the utility frequency is outside the range of 47,5 Hz and 52 Hz, the system shall cease to energize the utility line within 0,5 s in accordance with EA Engineering Recommendation G83/1-1: Amendment 1-June 2008. The purpose of the allowed range and time delay is to allow continued operation for short-term disturbances and to avoid excessive nuisance tripping in weak utility system conditions. The plant does not have to cease to energize if the frequency returns to the normal utility continuous operating condition within the specified trip time.

See appended table. P

Page 13: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 13 of 174 TEST REPORT NRS 097-2-1 VER.0

NRS 097-2-1:2010

Clause Requirement – Test Result – Remark Verdict

SECTION 4.2: Safety and protection 4.2.2.4 Prevention of islanding P 4.2.2.4.1 A utility distribution network can become de-energized

for several reasons: for example, a substation breaker that opens due to a fault condition or the distribution network might be switched off for maintenance purposes. Should the load and (embedded) generation within an isolated network be closely matched, then the voltage and frequency limits may not be triggered. If the embedded generator control system only made use of passive voltage and frequency out-of-bounds detection, this would result in an unintentional island that could continue beyond the allowed time limits.

See appended table. P

4.2.2.4.2 In order to detect an islanding condition, the embedded generator shall make use of at least one active islanding detection method. An active islanding detection method intentionally varies an output parameter and monitors the response or it attempts to cause an abnormal condition at the utility interface to trigger an out-of-bounds condition. If the utility supply is available, the attempt to vary an output parameter or cause an abnormal condition will fail and no response will be detected. However, if the utility supply network is de-energized, there will be a response to the change which can be detected. This signals an island condition to the embedded generator upon detection of which the embedded generator shall cease to energize the utility network within a specific time period.

See appended table. P

4.2.2.4.3 Active islanding shall be detected in all cases where the EG interfaces with the utility network through one or more static power converters.

See appended table. P

4.2.2.4.4 Synchronous generators, power-factor corrected induction generators and self-excited induction generators shall use an islanding detection method acceptable to the utility (e.g. rate-of-change-of-frequency or voltage vector shift detection). Mains-excited induction generators are not required to be fitted with such islanding detection capabilities.

See appended table. P

4.2.2.4.5 This section of NRS 097-2 requires that an islanding condition shall cause the embedded generator to cease to energize the utility network within 2 s, irrespective of connected loads or other embedded generators. The embedded generator shall comply with the requirements of IEC 62116 (ed. 1). NOTE Prevention of islanding measures are only considered on the embedded generator side, i.e. no utility installed anti-islanding measures are considered.

See appended table. P

4.2.2.4.6 The embedded generator shall physically disconnect from the utility network in accordance with the requirements in 4.2.2.2.

The transformer less inverter provides two relays in series for each line. Derived from tests.

P

Page 14: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 14 of 174 TEST REPORT NRS 097-2-1 VER.0

NRS 097-2-1:2010

Clause Requirement – Test Result – Remark Verdict

SECTION 4.2: Safety and protection 4.2.2.5 DC current injection

The static power converter of the embedded generator shall not inject d.c. current greater than 1 % (see IEC 61727:2004) of the rated a.c. output current into the utility interface under any operating condition. The EG shall cease to energize the utility network within 500 ms if this threshold is exceeded.

See appended table. P

4.2.3 Response to utility recovery After a voltage or frequency out-of-range condition that has caused the embedded generator to cease energizing the utility network, the generator shall not re-energize the utility network for 60 s after the utility service voltage and frequency have recovered to within the specified ranges.

See appended table. P

4.2.4 Isolation P 4.2.4.1 The embedded generator shall provide a means of

isolating from the utility interface in order to allow for safe maintenance of the EG. The disconnection device shall be a double pole for a single-phase EG, a three-pole for a three-phase delta-connected EG, and a four-pole for a three-phase star-connected EG. The grid supply side shall be wired as the source.

Disconnecting device is not integral part of the unit. The installation instructions specify a disconnection device for the final installation. The correct assembling is part of the installer.

N/A

4.2.4.2 The breaking capacity of the isolation circuit-breaker closest to the point of utility connection shall have a minimum fault current level of 6 kA in accordance with SANS 60947-2.

Rely in the responsibility of the installer and is stated in the installation instruction of the manufacturer.

N/A

4.2.4.3 This disconnection device does not need to be accessible to the utility.

P

4.2.5 Earthing P 4.2.5.1 The electrical installation shall be earthed in accordance

with SANS 10142-1. The earthing requirements for different embedded generation configurations in conjunction with the customer network are described in annex B for the most common earthing systems.

Rely in the responsibility of the installer.

N/A

4.2.5.2 The embedded generator shall be protected by an earth leakage unit. The embedded generator shall not be connected to any of the customer network earth leakage protection units.

Rely in the responsibility of the installer.

N/A

Page 15: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 15 of 174 TEST REPORT NRS 097-2-1 VER.0

NRS 097-2-1:2010

Clause Requirement – Test Result – Remark Verdict

SECTION 4.2: Safety and protection 4.2.5.3 Utility-interconnected inverters without simple

separation shall make use of earth leakage circuit-breakers which are able to respond to d.c. fault currents including smooth d.c. fault currents (i.e. without zero crossings) unless the inverter can exclude the occurrence of d.c. leakage currents through its circuit design1). NOTE The earth leakage unit may also fulfil the requirement of the all-pole disconnection device as stated in 4.2.4. 1) The appropriate earth leakage unit should be selected to accommodate the higher leakage current of inverters without transformers to avoid nuisance tripping.

The inverter was tested according IEC 62109-1 for the residual current device (RCD) or monitoring (RCM).

P

4.2.6 Short -circuit protection The embedded generator shall have short-circuit protection in accordance with IEC 60364-7-712. The short-circuit characteristics for rotating generators shall be supplied to the utility.

Rely in the responsibility of the installer and is stated in the installation instruction of the manufacturer.

N/A

4.2.7 Labelling P 4.2.7.1 A label on the distribution board of the premises where

the embedded generator is connected, shall state: “ON-SITE EMBEDDED GENERATION (EG) CONNECTED. THE EG IS FITTED WITH AN AUTOMATIC DISCONNECTION SWITCH WHICH DISCONNECTS THE EG IN THE CASE OF UTILITY NETWORK DE-ENERGIZATION.”

Rely in the responsibility of the installer and is stated in the installation instruction of the manufacturer.

N/A

4.2.7.2 The label shall be permanent, coloured red, and with white lettering of height at least 8 mm.

Noticed. N/A

Page 16: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 16 of 174 TEST REPORT NRS 097-2-1 VER.0

Test overview:

NRS 097-2-1:2010

Clause Test Result

1 Response to protection operation - fault condition tests (according VDE0126-1-1:2006) P

4. Type test :

4.1.3 Voltage fluctuations and Flicker P

4.1.4 Monitoring of DC-Injection P

4.1.5 Normal frequency operating range (see 4.2.2.3.3 below) P

4.1.6 Harmonics and waveform distortion P

4.1.7 Power factor P

4.2.2.3.2 Voltage monitoring P

4.2.2.3.3 Frequency monitoring P

4.2.2.4 Prevention of islanding P

Page 17: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 17 of 174 TEST REPORT NRS 097-2-1 VER.0

Test Results

1. Response to protection operation - fault conditi on tests

P

ambient temperature (°C) : 24,9

model/type of power supply : AC: 61511 DC: 62150h-1000s

manufacturer of power supply : Chroma

rated markings of power supply : AC: 0-300V, 45kw DC: 0-1000V,15A

component No. fault

test condition test time

fuse No.

fault condition result

AC DC AC DC Relay K5, contacts(C)

Short before start-up

480V 0A

720V 0,01A

10 Min, -- 480V 0A

720V 0,01A

PV inverter can not start-up. Error message: "400" (System Fault )

Relay K8, contacts(C)

Short before start-up

480V 0A

720V 0,01A

10 Min, -- 480V 0A

720V 0,01A

PV inverter can not start-up. Error message: "400" (System Fault )

Relay K6, contacts(B)

Short before start-up

480V 0A

720V 0,01A

10 Min, -- 480V 0A

720V 0,01A

PV inverter can not start-up. Error message: "400" (System Fault )

Relay K9, contacts(B)

Short before start-up

480V 0A

720V 0,01A

10 Min, -- 480V 0A

720V 0,01A

PV inverter can not start-up. Error message: "400" (System Fault )

Relay K7, contacts(A)

Short before start-up

480V 0A

720V 0,01A

10 Min, -- 480V 0A

720V 0,01A

PV inverter can not start-up. Error message: "400" (System Fault )

Relay K10, contacts(A)

Short before start-up

480V 0A

720V 0,01A

10 Min, -- 480V 0A

720V 0,01A

PV inverter can not start-up. Error message: "400" (System Fault )

Relay monitoring circuit, Q5, G-S

short before start-up

480V 0A

720V 0,01A

10 Min, -- 480V 0A

720V 0,01A

PV inverter can not start-up. Error message: "400" (System Fault )

Relay monitoring circuit, R144

open before start-up

480V 0A

720V 0,01A

10 Min, -- 480V 0A

720V 0,01A

PV inverter can not start-up. Error message: "400" (System Fault )

Relay monitoring circuit, R146

Short before start-up

480V 0A

720V 0,01A

10 Min, -- 480V 0A

720V 0,01A

PV inverter can not start-up. Error message: "400" (System Fault )

Relay monitoring circuit, C28

short before start-up

480V 0A

720V 0,01A

10 Min, -- 480V 0A

720V 0,01A

PV inverter can not start-up. Error message: "400" (System Fault )

PV array insulation resistance monitoring, Q3026, C to E

Short before start-up

480V 0A

720V 0,01A

10 Min, -- 480V 0A

720V 0,01A

PV inverter can not start-up. Error message: "313" (Array Insulation Resistance Fault)

Page 18: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 18 of 174 TEST REPORT NRS 097-2-1 VER.0

component No.

fault test condition test

time fuse No.

fault condition result

AC DC AC DC PV array insulation resistance monitoring, K3001

Short before start-up

480V 0A

720V 0,01A

10 Min, -- 480V 0A

720V 0,01A

PV inverter can not start-up. Error message: "313" (Array Insulation Resistance Fault)

PV array insulation resistance monitoring, D3045

short before start-up

480V 0A

720V 0,01A

10 Min, -- 480V 0A

720V 0,01A

PV inverter can not start-up. Error message: "313" (Array Insulation Resistance Fault)

PV array insulation resistance monitoring, R3216

Open before start-up

480V 0A

720V 0,01A

10 Min, -- 480V 0A

720V 0,01A

PV inverter can not start-up. Error message: "313" (Array Insulation Resistance Fault)

PV array insulation resistance monitoring, R3615

Short before start-up

480V 0A

720V 0,01A

10 Min, -- 480V 0A

720V 0,01A

PV inverter can not start-up. Error message: "313" (Array Insulation Resistance Fault)

PV array insulation resistance monitoring, R3084

Open before start-up

480V 0A

720V 0,01A

10 Min, -- 480V 0A

720V 0,01A

PV inverter can not start-up. Error message: "313" (Array Insulation Resistance Fault)

PV array insulation resistance monitoring, R3138

Open before start-up

480V 0A

720V 0,01A

10 Min, -- 480V 0A

720V 0,01A

PV inverter can not start-up. Error message: "313" (Array Insulation Resistance Fault)

PV array insulation resistance monitoring, R3088

Short before start-up

480V 0A

720V 0,01A

10 Min, -- 480V 0A

720V 0,01A

PV inverter can not start-up. Error message: "313" (Array Insulation Resistance Fault)

PV array insulation resistance monitoring, R3088

Open before start-up

480V 0A

720V 0,01A

10 Min, -- 480V 0A

720V 0,01A

PV inverter can not start-up. Error message: "313" (Array Insulation Resistance Fault)

AC voltage and frequency monitoring, R112

open 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. Error message: "301" (Grid Voltage Abnormal)

AC voltage and frequency monitoring, R2690

short 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. Error message: "301" (Grid Voltage Abnormal)

AC voltage and frequency monitoring, R2692

open 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. Error message: "301" (Grid Voltage Abnormal)

Page 19: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 19 of 174 TEST REPORT NRS 097-2-1 VER.0

component No.

fault test condition test

time fuse No.

fault condition result

AC DC AC DC AC voltage and frequency monitoring, U118, pin 2 – pin 3

short 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. Error message: "301" (Grid Voltage Abnormal)

AC voltage and frequency monitoring, R2864

short 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. Error message: "301" (Grid Voltage Abnormal)

AC voltage and frequency monitoring, C1036

short 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. Error message: "301" (Grid Voltage Abnormal)

AC voltage and frequency monitoring, U118, Vcc - GND

short 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. Error message: "301" (Grid Voltage Abnormal)

DC injection current monitoring, U123, pin Vc to GND

short 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. R345 damaged. Error message: "202" (Invert Module Fault )

DC injection current monitoring, U14, pin Voutput to GND

short 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. Error message: "202" (Invert Module Fault )

DC injection current monitoring, R2431

short 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. Error message: "202" (Invert Module Fault )

DC injection current monitoring, R2428

open 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. Error message: "202" (Invert Module Fault )

DC injection current monitoring, U123, pin 2 – pin3

short 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. Error message: "202" (Invert Module Fault )

DC injection current monitoring, R2757

open 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. Error message: "202" (Invert Module Fault )

DC injection current monitoring, C1015

short 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. No display.

Page 20: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 20 of 174 TEST REPORT NRS 097-2-1 VER.0

component No.

fault test condition test

time fuse No.

fault condition result

AC DC AC DC RCMU detect, R221

short 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. Error message: "318" (Residual Current )

RCMU detect, R1830

Open 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. Error message: "318" (Residual Current )

RCMU detect, R1831

Open 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. Error message: "318" (Residual Current )

RCMU selt-test, R1201

Open 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. Error message: "318" (Residual Current )

RCMU selt-test, Q9, G - S

short 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. Error message: "318" (Residual Current )

RCMU selt-test, C750

short 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. Error message: "318" (Residual Current )

Slave CPU(U58), 3,3V power

Increase to protection

480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. No display.

Slave CPU(U58), 3,3V power

Decrease to protection

480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. No display.

CPLD(U51), 3,3V power

Increase to protection

480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. No display.

CPLD(U51), 3,3V power

Decrease to protection

480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. No display.

CPLD(U51) Any signal interrupted from DPS 1

480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. No display.

CPLD(U51) Any signal interrupted from DPS 2

480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. No display.

Watchdog, U72, Vcc - GND

short 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. No display.

OSC1 Clock, VDD - GND

short 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. No display.

OSC1 Clock, R188

Open 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. No display.

OSC1 Clock, R387

Open 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. No display.

Page 21: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 21 of 174 TEST REPORT NRS 097-2-1 VER.0

component No.

fault test condition test

time fuse No.

fault condition result

AC DC AC DC OSC2 Clock, VDD - GND

short 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. No display.

OSC2 Clock, R190

Open 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. No display.

AD Multiplexer, U4, VDD - GND

Short 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. Error message: "200" (DC Bus Voltage Fault )

AD Multiplexer, U4, R140

open 480V 19,2A

720V 22,6A

10 Min, -- 480V 0A

720V 0,01A

PV inverter disconnected from grid immediately. Error message: "200" (DC Bus Voltage Fault )

Note: The errors in the control circuit simulate that the safety is even under one error ensured. Test result refers to test report PV160317N006. The tests had been performed on the SUN2000-42KTL is valid for the SUN2000-36KTL, since it is identical in hardware and software construction.

Page 22: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 22 of 174 TEST REPORT NRS 097-2-1 VER.0

4.1.3 Voltage fluctuation and flicker

P

Test conditions: Maximum permissible voltage fluctuation (expressed as a percentage of nominal voltage at 100 % power) and flicker as per EN 61000-3-3

Starting Stopping Running

Limit 3,3% 3,3% Pst=1,0 Plt=0,65

Test value * * * *

inverter >16A

Limit dc% = 3,3 Pst=1,0 Plt=0,65

Test value See below

L1 phase_SUN2000-36KTL(400Vac)

L2 phase_SUN2000-36KTL(400Vac)

Page 23: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 23 of 174 TEST REPORT NRS 097-2-1 VER.0

L3 phase_SUN2000-36KTL(400Vac)

L1 phase_SUN2000-36KTL(480Vac)

L2 phase_SUN2000-36KTL(480Vac)

Page 24: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 24 of 174 TEST REPORT NRS 097-2-1 VER.0

L3 phase_SUN2000-36KTL(480Vac)

L1 phase_SUN2000-42KTL

L2 phase_SUN2000-42KTL

Page 25: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 25 of 174 TEST REPORT NRS 097-2-1 VER.0

L3 phase_SUN2000-42KTL

Note: *The stationary deviance of dc% is more relevant than the dynamic deviance of dmax at starting and stopping. Mains Impedance according EN61000-3-11: Rmax = 0,24 Ω; jX max= 0,15 Ω @50Hz (|Zmax| = 0,472 Ω) for single phase inverter use also R n = 0,16 Ω; jX n= 0,1 Ω Calculation of the maximum permissible grid impedance at the point of common coupling based on dc: Zmax = Zref * 3,3% / dc(Pn) The tests should be based on the limits of the EN 61000-3-11 for more than 16A.

Page 26: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 26 of 174 TEST REPORT NRS 097-2-1 VER.0

4.1.4 DC-Injection (4.2.2.5 DC current injection)

P

Test conditions: UN = 230Vac; Uinput =700Vdc;

Rated Power: 100%

Test result: SUN2000-36KTL(400Vac)

DC Injection (A) Limits Trip Time L1 (ms)

Trip Time L2 (ms)

Trip Time L3 (ms)

+1,0A IDC:>1% than disconnection within 0,5 sec

424 413 429

-1,0 A IDC:>1% than disconnection within 0,5 sec 419 458 447

Test result: SUN2000-42KTL

DC Injection (A) Limits Trip Time L1 (ms)

Trip Time L2 (ms)

Trip T ime L3 (ms)

+1,0A IDC:>1% than disconnection within 0,5 sec

441 461 492

-1,0 A IDC:>1% than disconnection within 0,5 sec 448 391 468

Note: A dc-current of greater than 1% of Iac nom cause a disconnection time of max. 0,5s

Page 27: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 27 of 174 TEST REPORT NRS 097-2-1 VER.0

Negative DC-Injection:SUN2000-36KTL(400Vac)

Positive DC-Injection: SUN2000-36KTL(400Vac)

Page 28: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 28 of 174 TEST REPORT NRS 097-2-1 VER.0

Negative DC-Injection:SUN2000-42KTL

Positive DC-Injection: SUN2000-42KTL

Page 29: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 29 of 174 TEST REPORT NRS 097-2-1 VER.0

4.1.4 Monitoring of permanent DC-Injection

P

Test result:SUN2000 -36KTL(400Vac) IEC61727 Limit : 1% of Inom (522mA) Output power: 25% 50% 100%

max test value phase 1: -67,9 -48,7 -45,1 max test value phase 2: 89,2 89,7 89,4 max test value phase 3: 74,3 -70,8 -98,9

Note: Testing must be performed according to WI 10.4.-03.doc rev D. The internal temperature of the EUT must be stabilized. No temperature drift of more than 2K within 1 hour is allowed.

Page 30: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 30 of 174 TEST REPORT NRS 097-2-1 VER.0

Test result:SUN2000 -36KTL(480Vac) IEC61727 Limit: 1% of Inom (433mA) Output power: 25% 50% 100%

max test value phase 1: -36,7 78,7 61,9 max test value phase 2: 84,3 70,0 71,8 max test value phase 3: -98,6 -52,5 51,3

Note: Testing must be performed according to WI 10.4.-03.doc rev D. The internal temperature of the EUT must be stabilized. No temperature drift of more than 2K within 1 hour is allowed.

Page 31: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 31 of 174 TEST REPORT NRS 097-2-1 VER.0

Test result:SUN2000 -42KTL IEC61727 Limit: 1% of Inom (505mA) Output power: 25% 50% 100%

max test value phase 1: -66,0 -72,8 -81,6 max test value phase 2: 82,9 73,9 68,5 max test value phase 3: -92,5 81,4 92,6

Note: Testing must be performed according to WI 10.4.-03.doc rev D. The internal temperature of the EUT must be stabilized. No temperature drift of more than 2K within 1 hour is allowed.

Page 32: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 32 of 174 TEST REPORT NRS 097-2-1 VER.0

4.1.6 Harmonics and waveform distortion

P

SUN2000-36KTL(400Vac) Normal ambient (EN 61 000-3-12)

Output power 100% Watts_[kW] 13,361/13,326/13,335

Vrms_[V] 231,52/231,49/231,51

Arms_[A] 57,725/57,574/57,595

Frequency_[Hz] 50,00

THD 1,239%/1,227%/1,287% Harmonics Current Magnitude (A) % of Fundamental Phase Harmonic Current

Limits (%) L1 L2 L3 L1 L2 L3

1st 57,712 57,562 57,580 99,992 99,992 99,992 Three Phase -- 2nd 0,210 0,133 0,248 0,363 0,232 0,430 Three Phase 1% 3rd 0,040 0,060 0,033 0,070 0,104 0,057 Three Phase 4% 4th 0,101 0,065 0,134 0,175 0,112 0,232 Three Phase 1% 5th 0,315 0,359 0,359 0,546 0,624 0,624 Three Phase 4% 6th 0,022 0,030 0,019 0,038 0,052 0,032 Three Phase 1% 7th 0,192 0,190 0,208 0,333 0,329 0,362 Three Phase 4% 8th 0,017 0,032 0,044 0,029 0,056 0,076 Three Phase 1% 9th 0,033 0,034 0,037 0,057 0,060 0,064 Three Phase 4% 10th 0,029 0,031 0,037 0,050 0,053 0,064 Three Phase 0,5% 11th 0,313 0,292 0,283 0,543 0,507 0,492 Three Phase 2% 12th 0,027 0,014 0,033 0,047 0,024 0,057 Three Phase 0,5% 13th 0,255 0,260 0,262 0,442 0,451 0,456 Three Phase 2% 14th 0,015 0,027 0,030 0,026 0,046 0,052 Three Phase 0,5% 15th 0,015 0,021 0,025 0,026 0,036 0,043 Three Phase 2% 16th 0,019 0,024 0,038 0,033 0,042 0,066 Three Phase 0,5% 17th 0,184 0,180 0,162 0,318 0,313 0,282 Three Phase 1,5% 18th 0,016 0,028 0,023 0,028 0,048 0,040 Three Phase 0,5% 19th 0,179 0,181 0,175 0,310 0,314 0,304 Three Phase 1,5% 20th 0,021 0,027 0,018 0,036 0,047 0,031 Three Phase 0,5% 21th 0,019 0,016 0,017 0,033 0,029 0,030 Three Phase 1,5% 22th 0,026 0,020 0,025 0,046 0,035 0,043 Three Phase 0,5% 23th 0,114 0,115 0,103 0,198 0,201 0,180 Three Phase 0,6% 24th 0,022 0,017 0,020 0,038 0,029 0,035 Three Phase 0,5% 25th 0,141 0,137 0,137 0,245 0,238 0,238 Three Phase 0,6% 26th 0,022 0,015 0,020 0,039 0,027 0,035 Three Phase 0,5% 27th 0,023 0,016 0,015 0,041 0,028 0,026 Three Phase 0,6% 28th 0,020 0,016 0,019 0,035 0,027 0,034 Three Phase 0,5% 29th 0,086 0,091 0,085 0,149 0,158 0,148 Three Phase 0,6% 30th 0,021 0,015 0,022 0,036 0,026 0,039 Three Phase 0,5% 31th 0,101 0,100 0,102 0,175 0,174 0,177 Three Phase 0,6% 32th 0,020 0,019 0,022 0,035 0,032 0,039 Three Phase 0,5% 33th 0,020 0,019 0,019 0,035 0,033 0,033 Three Phase 0,6% 34th 0,019 0,020 0,019 0,032 0,035 0,033 Three Phase N/A 35th 0,072 0,076 0,071 0,124 0,133 0,124 Three Phase N/A 36th 0,019 0,017 0,019 0,033 0,029 0,033 Three Phase N/A 37th 0,071 0,070 0,070 0,123 0,121 0,122 Three Phase N/A 38th 0,018 0,019 0,016 0,031 0,033 0,028 Three Phase N/A 39th 0,017 0,017 0,016 0,030 0,030 0,028 Three Phase N/A 40th 0,017 0,019 0,022 0,030 0,033 0,038 Three Phase N/A

Page 33: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 33 of 174 TEST REPORT NRS 097-2-1 VER.0

SUN2000-36KTL(480Vac)

Normal ambient (EN 61 000-3-12) Output power 100%

Watts_[kW] 13,370/13,332/13,451

Vrms_[V] 278,50/278,48/278,62

Arms_[A] 48,016/47,882/48,285

Frequency_[Hz] 50,00

THD 1,251%/1,265%/1,186% Harmonics Current Magnitude (A) % of Fundamental Phase Harmonic Current

Limits (%) L1 L2 L3 L1 L2 L3

1st 48,012 47,879 48,280 99,992 99,992 99,993 Three Phase -- 2nd 0,048 0,079 0,058 0,100 0,164 0,120 Three Phase 1% 3rd 0,088 0,075 0,076 0,182 0,157 0,157 Three Phase 4% 4th 0,119 0,115 0,025 0,248 0,241 0,051 Three Phase 1% 5th 0,109 0,142 0,106 0,227 0,297 0,219 Three Phase 4% 6th 0,017 0,038 0,030 0,035 0,080 0,063 Three Phase 1% 7th 0,127 0,131 0,125 0,265 0,274 0,259 Three Phase 4% 8th 0,027 0,032 0,019 0,057 0,068 0,039 Three Phase 1% 9th 0,029 0,043 0,027 0,061 0,091 0,057 Three Phase 4% 10th 0,039 0,031 0,020 0,081 0,064 0,041 Three Phase 0,5% 11th 0,304 0,299 0,300 0,633 0,625 0,622 Three Phase 2% 12th 0,019 0,014 0,022 0,041 0,030 0,045 Three Phase 0,5% 13th 0,261 0,263 0,261 0,544 0,549 0,541 Three Phase 2% 14th 0,023 0,023 0,020 0,048 0,048 0,042 Three Phase 0,5% 15th 0,025 0,027 0,021 0,052 0,056 0,044 Three Phase 2% 16th 0,034 0,028 0,018 0,070 0,059 0,037 Three Phase 0,5% 17th 0,202 0,203 0,189 0,421 0,423 0,391 Three Phase 1,5% 18th 0,015 0,014 0,014 0,032 0,030 0,030 Three Phase 0,5% 19th 0,173 0,168 0,175 0,360 0,351 0,362 Three Phase 1,5% 20th 0,020 0,019 0,017 0,041 0,039 0,035 Three Phase 0,5% 21th 0,017 0,014 0,016 0,035 0,030 0,034 Three Phase 1,5% 22th 0,031 0,026 0,017 0,065 0,055 0,036 Three Phase 0,5% 23th 0,136 0,137 0,129 0,282 0,286 0,266 Three Phase 0,6% 24th 0,019 0,014 0,016 0,040 0,030 0,033 Three Phase 0,5% 25th 0,127 0,119 0,123 0,265 0,249 0,254 Three Phase 0,6% 26th 0,021 0,018 0,017 0,043 0,038 0,035 Three Phase 0,5% 27th 0,017 0,021 0,016 0,035 0,044 0,033 Three Phase 0,6% 28th 0,024 0,022 0,016 0,050 0,046 0,034 Three Phase 0,5% 29th 0,086 0,091 0,087 0,179 0,190 0,180 Three Phase 0,6% 30th 0,015 0,027 0,013 0,032 0,056 0,026 Three Phase 0,5% 31th 0,081 0,079 0,082 0,170 0,165 0,169 Three Phase 0,6% 32th 0,018 0,028 0,013 0,038 0,058 0,027 Three Phase 0,5% 33th 0,017 0,025 0,013 0,036 0,053 0,027 Three Phase 0,6% 34th 0,020 0,021 0,013 0,041 0,044 0,026 Three Phase N/A 35th 0,056 0,057 0,055 0,117 0,119 0,115 Three Phase N/A 36th 0,017 0,014 0,011 0,035 0,030 0,024 Three Phase N/A 37th 0,044 0,038 0,045 0,092 0,079 0,093 Three Phase N/A 38th 0,022 0,014 0,012 0,045 0,030 0,026 Three Phase N/A 39th 0,023 0,014 0,012 0,049 0,029 0,025 Three Phase N/A 40th 0,030 0,013 0,012 0,063 0,028 0,026 Three Phase N/A

Page 34: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 34 of 174 TEST REPORT NRS 097-2-1 VER.0

SUN2000-42KTL

Norm al ambient (EN 61 000-3-12) Output power 100%

Watts_[kW] 15,693/15,635/15,659

Vrms_[V] 278,73/278,69/278,76

Arms_[A] 56,309/56,109/56,183

Frequency_[Hz] 50,00

THD 1,134%/1,178%/1,160% Harmonics Current Magnitude (A) % of Fundamental Phase Harmonic Cur rent

Limits (%) L1 L2 L3 L1 L2 L3

1st 56,304 56,106 56,177 99,993 99,993 99,993 Three Phase -- 2nd 0,044 0,155 0,131 0,078 0,277 0,233 Three Phase 1% 3rd 0,083 0,054 0,079 0,147 0,097 0,140 Three Phase 4% 4th 0,163 0,178 0,205 0,290 0,317 0,365 Three Phase 1% 5th 0,146 0,161 0,148 0,259 0,288 0,263 Three Phase 4% 6th 0,016 0,044 0,039 0,028 0,078 0,069 Three Phase 1% 7th 0,148 0,168 0,137 0,262 0,300 0,244 Three Phase 4% 8th 0,027 0,028 0,018 0,047 0,049 0,031 Three Phase 1% 9th 0,028 0,049 0,032 0,050 0,088 0,056 Three Phase 4% 10th 0,040 0,024 0,029 0,071 0,043 0,052 Three Phase 0,5% 11th 0,300 0,295 0,292 0,534 0,525 0,519 Three Phase 2% 12th 0,031 0,018 0,022 0,056 0,032 0,040 Three Phase 0,5% 13th 0,261 0,260 0,265 0,463 0,464 0,472 Three Phase 2% 14th 0,039 0,034 0,037 0,070 0,060 0,066 Three Phase 0,5% 15th 0,022 0,021 0,019 0,038 0,037 0,034 Three Phase 2% 16th 0,044 0,036 0,042 0,078 0,065 0,075 Three Phase 0,5% 17th 0,194 0,193 0,182 0,345 0,343 0,325 Three Phase 1,5% 18th 0,016 0,018 0,018 0,028 0,033 0,032 Three Phase 0,5% 19th 0,179 0,176 0,181 0,318 0,314 0,322 Three Phase 1,5% 20th 0,021 0,025 0,023 0,037 0,045 0,041 Three Phase 0,5% 21th 0,017 0,016 0,021 0,030 0,028 0,037 Three Phase 1,5% 22th 0,035 0,027 0,038 0,063 0,048 0,067 Three Phase 0,5% 23th 0,143 0,147 0,135 0,255 0,262 0,241 Three Phase 0,6% 24th 0,022 0,019 0,021 0,039 0,034 0,038 Three Phase 0,5% 25th 0,134 0,130 0,133 0,238 0,232 0,237 Three Phase 0,6% 26th 0,025 0,025 0,019 0,044 0,044 0,035 Three Phase 0,5% 27th 0,020 0,022 0,023 0,035 0,039 0,041 Three Phase 0,6% 28th 0,032 0,025 0,028 0,056 0,044 0,050 Three Phase 0,5% 29th 0,100 0,105 0,100 0,178 0,186 0,178 Three Phase 0,6% 30th 0,022 0,018 0,020 0,039 0,032 0,036 Three Phase 0,5% 31th 0,099 0,094 0,097 0,177 0,168 0,173 Three Phase 0,6% 32th 0,021 0,019 0,020 0,037 0,035 0,036 Three Phase 0,5% 33th 0,016 0,019 0,018 0,028 0,034 0,032 Three Phase 0,6% 34th 0,022 0,023 0,020 0,038 0,041 0,036 Three Phase N/A 35th 0,073 0,077 0,075 0,129 0,137 0,133 Three Phase N/A 36th 0,016 0,023 0,015 0,029 0,041 0,027 Three Phase N/A 37th 0,066 0,063 0,066 0,118 0,112 0,117 Three Phase N/A 38th 0,018 0,021 0,019 0,033 0,037 0,035 Three Phase N/A 39th 0,015 0,019 0,017 0,027 0,034 0,031 Three Phase N/A 40th 0,019 0,019 0,019 0,034 0,034 0,034 Three Phase N/A

Page 35: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 35 of 174 TEST REPORT NRS 097-2-1 VER.0

4.1.7 Power factor

P

Test result:SUN2000-36KTL(400Vac)

Test conditions:

Output power Test voltage (Vac)

~10% ~25% ~50% ~75% ~100%

400V

0,9955c 0,9994c 0,9997c 0,9998c 0,9999c

Test result:SUN2000-36KTL(480Vac)

Test conditions:

Output power Test voltage (Vac)

~10% ~25% ~50% ~75% ~100%

480V

0,9946c 0,9994c 0,9998c 0,9998c 0,9999c

Test result:SUN2000-42KTL

Test conditions:

Output power Test voltage (Vac)

~10% ~25% ~50% ~75% ~100%

480V

0,9959c 0,9996c 0,9998c 0,9999c 0,9999c

Note: *The PV system shall have a lagging power factor greater than 0,9 when the output is greater than 50% of the rated inverter output power. The letter “i” is short for “inductive” and indicates inductive power factor. In case of capacitive power factor the letter “c” is used instead.

Page 36: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 36 of 174 TEST REPORT NRS 097-2-1 VER.0

4.2.2.3.2 Overvoltage and undervoltage P

Test result:SUN2000-36KTL(400Vac) L1 phase

First Level Test conditions: Output power: 18,0kW

Frequency: 50Hz

Under Voltage Over Voltage Parameter Voltage Time (ms) Voltage Time (ms)

Limit 195,5V <= 2,0s

253,0V <= 2,0s

Trip value 196,0V 255,6V Disconnection time

203V to 191V 1468 1492 1488 203V to

258V 1496 1480 1488

Reconnection time

min. 60s 60s min. 60s 60s

Second Level Test conditions: Output power: 9,0kW

Frequency: 50Hz

Under Voltage Over Voltage Parameter Voltage Time (ms) Voltage Time (ms)

Limit 115,0V <= 200ms

276,0V <= 160ms

Trip value 116,2V 278,1V Disconnection time

230V to 110V 180 179 189 230V to

280V 137 135 147

Reconnection time min. 60s 61s min. 60s 60s

L2 phase

First Level Test conditions: Output power: 18,0kW

Frequency: 50Hz

Under Voltage Over Voltage Parameter Voltage Time (ms) Voltage Time (ms)

Limit 195,5V <= 2,0s

253,0V <= 2,0s

Trip value 194,7V 253,3V Disconnection time

203V to 191V 1492 1480 1480 203V to

258V 1484 1488 1488

Reconnection time min. 60s 60s min. 60s 61s

Second Level Test conditions: Output power: 9,0kW

Frequency: 50Hz

Under Voltage Over Voltage Parameter Voltage Time (ms) Voltage Time (ms)

Limit 115,0V <= 200ms

276,0V <= 160ms

Trip value 115,4V 275,5V Disconnection time

230V to 110V 183 192 190 230V to

280V 148 151 137

Reconnection time min. 60s 61s min. 60s 61s

Page 37: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 37 of 174 TEST REPORT NRS 097-2-1 VER.0

L3 phase

First Level Test conditions: Output power: 18,0kW

Frequency: 50Hz

Under Voltage Over Voltage Parameter Voltage Time (ms) Voltage Time (ms)

Limit 195,5V <= 2,0s

253,0V <= 2,0s

Trip value 195,0V 253,4V Disconnection time

203V to 191V

1488 1484 1488 203V to 258V

1492 1492 1488

Reconnection time min. 60s 61s min. 60s 61s

Second Level Test conditions: Output power: 9,0kW

Frequency: 50Hz

Under Voltage Over Voltage Parameter Voltage Time (ms) Voltage Time (ms)

Limit 115,0V <= 200ms

276,0V <= 160ms

Trip value 116,2V 275,1V Disconnection time

230V to 110V 194 174 187

230V to 280V 145 144 158

Reconnection time min. 60s 62s min. 60s 61s

Page 38: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 38 of 174 TEST REPORT NRS 097-2-1 VER.0

Under Voltage First Level:L1 phase

Over voltage First Level L1 phase

Page 39: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 39 of 174 TEST REPORT NRS 097-2-1 VER.0

Under Voltage Second Level L1 phase

Over voltage Second Level L1 phase

Page 40: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 40 of 174 TEST REPORT NRS 097-2-1 VER.0

Under Voltage First Level:L2 phase

Over voltage First Level L2 phase

Page 41: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 41 of 174 TEST REPORT NRS 097-2-1 VER.0

Under Voltage Second Level L2 phase

Over voltage Second Level L2 phase

Page 42: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 42 of 174 TEST REPORT NRS 097-2-1 VER.0

Under Voltage First Level:L3 phase

Over voltage First Level L3 phase

Page 43: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 43 of 174 TEST REPORT NRS 097-2-1 VER.0

Under Voltage Second Level L3 phase

Over voltage Second Level L3 phase

Page 44: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 44 of 174 TEST REPORT NRS 097-2-1 VER.0

Test result:SUN2000-42KTL

L1 phase

First Level Test conditions: Output power: 21,0kW

Frequency: 50Hz

Under Voltage Over Voltage Parameter Voltage Time (ms) Voltage Time (ms)

Limit 408,0V <= 2,0s

528,0V <= 2,0s

Trip value 408,4V 530,3 V Disconnection time

413V to 403V

1480 1480 1472 413V to 403V

1488 1480 1488

Reconnection time min. 60s 79s min. 60s 75s

Second Level Test conditions: Output power: 10,0kW

Frequency: 50Hz

Under Voltage Over Voltage Parameter Voltage Time (ms) Voltage Time (ms)

Limit 240V <= 200ms

576V <= 160ms

Trip value 240,5V 577,5V Disconnection time

480V to 235V 197 186 198

480V to 235V 146 150 142

Reconnection time min. 60s 75s min. 60s 80s

L2 phase

First Level Test conditions: Output power: 21,0kW

Frequency: 50Hz

Under Voltage Over Voltage Parameter Voltage Time (ms) Voltage Time (ms)

Limit 408,0V <= 2,0s

528,0V <= 2,0s

Trip value 407,4V 530,0 V Disconnection time

413V to 403V

1475 1475 1476 413V to 403V

1496 1484 1492

Reconnection time min. 60s 80s min. 60s 79s

Second Level Test conditions: Output power: 10,0kW

Frequency: 50Hz

Under Voltage Over Voltage Parameter Voltage Time (ms) Voltage Time (ms)

Limit 240V <= 200ms

576V <= 160ms

Trip value 240,3V 576,8V Disconnection time

480V to 235V 199 178 193

480V to 235V 148 146 140

Reconnection time min. 60s 79s min. 60s 74s

Page 45: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 45 of 174 TEST REPORT NRS 097-2-1 VER.0

L3 phase

First Level Test conditions: Output power: 21,0kW

Frequency: 50Hz

Under Voltage Over Voltage Parameter Voltage Time (ms) Voltage Time (ms)

Limit 408,0V <= 2,0s

528,0V <= 2,0s

Trip value 406,8V 528,8 V Disconnection time

413V to 403V

1495 1483 1495 523V to 533V

1491 1479 1471

Reconnection time min. 60s 76s min. 60s 75s

Second Level Test conditions: Output power: 10,0kW

Frequency: 50Hz

Under Voltage Over Voltage Parameter Voltage Time (ms) Voltage Time (ms)

Limit 240V <= 200ms

576V <= 160ms

Trip value 240,0V 275,1V Disconnection time

480V to 235V 184 197 199

480V to 580V 159 153 147

Reconnection time min. 60s 75s min. 60s 81s

Page 46: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 46 of 174 TEST REPORT NRS 097-2-1 VER.0

Under Voltage First Level:L1 phase

Over voltage First Level L1 phase

Page 47: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 47 of 174 TEST REPORT NRS 097-2-1 VER.0

Under Voltage Second Level L1 phase

Over voltage Second Level L1 phase

Page 48: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 48 of 174 TEST REPORT NRS 097-2-1 VER.0

Under Voltage First Level:L2 phase

Over voltage First Level L2 phase

Page 49: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 49 of 174 TEST REPORT NRS 097-2-1 VER.0

Under Voltage Second Level L2 phase

Over voltage Second Level L2 phase

Page 50: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 50 of 174 TEST REPORT NRS 097-2-1 VER.0

Under Voltage First Level:L3 phase

Over voltage First Level L3 phase

Page 51: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 51 of 174 TEST REPORT NRS 097-2-1 VER.0

Under Voltage Second Level L3 phase

Over voltage Second Level L3 phase

Page 52: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 52 of 174 TEST REPORT NRS 097-2-1 VER.0

4.2.2.3.3 Overfrequency and underfrequency

P

Test:SUN2000-36KTL(400Vac)

Test conditions: Any output power level

Under frequency Over frequency

Parameter Frequency (Hz) Time (ms) Frequency

(Hz) Time (ms)

Output Voltage ~85%UN ~UN ~110%UN ~85%UN ~UN ~110%UN

Limit 47,50Hz 500ms 500ms 500ms 52,00Hz 500ms 500ms 500ms

Trip value 47,49 47,49 47,50 52,00 52,01 52,01

Disconnection time (ms)

48,00Hz to 47,00Hz 485 479 473 51,50Hz to

52,50Hz 480 483 471

Reconnection time min. 60s 61s min. 60s 61s

Test:SUN2000-42KTL

Test conditions: Any output power level

Under frequency Over frequency

Parameter Frequency (Hz) Time (ms) Frequency

(Hz) Time (ms)

Output Voltage ~85%UN ~UN ~110%UN ~85%UN ~UN ~110%UN

Limit 47,50Hz 500ms 500ms 500ms 52,00Hz 500ms 500ms 500ms

Trip value 47,49 47,50 47,50 52,01 52,01 52,01

Disconnection time (ms)

48,00Hz to 47,00Hz 471 488 473 51,50Hz to

52,50Hz 487 478 476

Reconnection time min. 60s 76s min. 60s 75s

Note: For under-frequency testing the applied frequency is varied from fn down to fth-low -0,1 Hz in steps of 0,025 Hz with a time duration per step exceeding the configured disconnection time. The operate value is the value of the applied frequency at switch the protection function trips and shall be within fth-low ± 0,05 Hz. For over-frequency testing the applied frequency is varied from fn up to fth-high + 0,1 Hz in steps of 0,025 Hz with a time duration per step exceeding the configured disconnection time. The operate value is the value of the applied frequency at which the protection function trips and shall be within fth-high ± 0,05 Hz.. The oscilloscope pictures below show the measured worst case disconnection times.

Page 53: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 53 of 174 TEST REPORT NRS 097-2-1 VER.0

Under Frequency:SUN2000-36KTL(400Vac)

Over Frequency: SUN2000-36KTL(400Vac)

Page 54: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 54 of 174 TEST REPORT NRS 097-2-1 VER.0

Under Frequency:SUN2000-42KTL

Over Frequency: SUN2000-42KTL

Page 55: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 55 of 174 TEST REPORT NRS 097-2-1 VER.0

4.2.2.4: Preventing of islanding (Islanding protect ion, Condition A)

P

Test reult:SUN2000-42KTL

Test conditions

Frequency: 50+/-0,1Hz UN=230+/-3Vac

RLC consumes inverter real power within +/- 3% Distortion factor of chokes < 3%

Quality =1

Disconnection limit 2s

No PEUT 1)

(% of EUT rating)

Reactive load (% of

QL in 6.1.d) 1)

PAC 2) (% of

nominal)

QAC 3)

(% of nominal)

Run on Time (ms)

PEUT

(kW per phase)

Qf VDC

(V) Remarks4)

1 100 100 0 0 362 14,027 1,005 778 Test A at BL

2 100 100 -10 -10 170 14,027 1,060 778 Test A at IB

3 100 100 -10 -5 231 14,027 1,089 778 Test A at IB

4 100 100 -10 0 177 14,027 1,117 778 Test A at IB

5 100 100 -10 +5 195 14,027 1,145 778 Test A at IB

6 100 100 -10 +10 169 14,027 1,172 778 Test A at IB

7 100 100 -5 -10 208 14,027 1,004 778 Test A at IB

8 100 100 -5 -5 274 14,027 1,032 778 Test A at IB

9 100 100 -5 0 183 14,027 1,058 778 Test A at IB

10 100 100 -5 +5 187 14,027 1,085 778 Test A at IB

11 100 100 -5 +10 172 14,027 1,110 778 Test A at IB

12 100 100 0 -10 316 14,027 0,954 778 Test A at IB

13 100 100 0 -5 252 14,027 0,980 778 Test A at IB

14 100 100 0 +5 465 14,027 1,030 778 Test A at IB

15 100 100 0 +10 299 14,027 1,055 778 Test A at IB

16 100 100 +5 -10 238 14,027 0,908 778 Test A at IB

17 100 100 +5 -5 285 14,027 0,933 778 Test A at IB

18 100 100 +5 0 416 14,027 0,958 778 Test A at IB

19 100 100 +5 +5 244 14,027 0,981 778 Test A at IB

20 100 100 +5 +10 260 14,027 1,004 778 Test A at IB

21 100 100 +10 -10 232 14,027 0,867 778 Test A at IB

22 100 100 +10 -5 283 14,027 0,891 778 Test A at IB

23 100 100 +10 0 217 14,027 0,914 778 Test A at IB

24 100 100 +10 +5 220 14,027 0,937 778 Test A at IB

25 100 100 +10 +10 239 14,027 0,959 778 Test A at IB

Page 56: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 56 of 174 TEST REPORT NRS 097-2-1 VER.0

Parameter at 0% per phase L= 17,340 mH R= 5,470 Ω C= 585,89 µF IAC fundamental current at

balance condition L1: 278 mA L2: 196 mA L3: 223 mA

Note: RLC is adjusted to min. +/-1% of the inverter rated output power 1) PEUT: EUT output power 2) PAC: Real power flow at S1 in Figure 1. Positive means power from EUT to utility. Nominal is the 0 % test condition value. 3) QAC: Reactive power flow at S1 in Figure 1. Positive means power from EUT to utility. Nominal is the 0 % test condition value. 4) BL: Balance condition, IB: Imbalance condition. Condition A: EUT output power PEUT = Maximum 5) EUT input voltage 6) = >90% of rated input voltage range 5) Maximum EUT output power condition should be achieved using the maximum allowable input power. Actual output power may exceed nominal rated output. 6) Based on EUT rated input operating range. For example, If range is between X volts and Y volts, 90 % of range =X + 0,9 × (Y – X). Y shall not exceed 0,8 × EUT maximum system voltage (i.e., maximum allowable array open circuit voltage). In any case, the EUT should not be operated outside of its allowable input voltage range.

Page 57: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 57 of 174 TEST REPORT NRS 097-2-1 VER.0

Disconnection at Pac 0% and Qac5% reactive load and 100% nominal power

Page 58: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 58 of 174 TEST REPORT NRS 097-2-1 VER.0

4.2.2.4: Preventing of islanding (Islanding protect ion, Condition B)

P

Test reult:SUN2000-42KTL

Test conditions

Frequency: 50+/-0,1Hz UN=230+/-3Vac

RLC consumes inverter real power within +/- 3% Distortion factor of chokes < 3%

Quality =1

Disconnection limit 2s

No PEUT 1)

(% of EUT rating)

Reactive load (% of

QL in 6.1.d) 1)

PAC 2) (% of

nominal)

QAC 3)

(% of nominal)

Run on Time (ms)

PEUT

(kW per

phase)

Qf VDC

(V) Remarks4)

12 66 66 0 -5 166 9,167 0,977 690 Test B at IB

13 66 66 0 -4 178 9,167 0,982 690 Test B at IB

14 66 66 0 -3 206 9,167 0,987 690 Test B at IB

15 66 66 0 -2 240 9,167 0,992 690 Test B at IB

16 66 66 0 -1 297 9,167 0,997 690 Test B at IB

2 66 66 0 0 342 9,167 1,002 690 Test B at BL

17 66 66 0 1 296 9,167 1,007 690 Test B at IB

18 66 66 0 2 258 9,167 1,012 690 Test B at IB

19 66 66 0 3 255 9,167 1,017 690 Test B at IB

20 66 66 0 4 247 9,167 1,022 690 Test B at IB

21 66 66 0 5 224 9,167 1,027 690 Test B at IB

Parameter at 0% per phase L= 27,25 mH R= 8,37 Ω C= 390,58 µF IAC fundamental current at

balance condition L1: 242 mA L2: 159 mA L3: 189 mA

Note: RLC is adjusted to min. +/-1% of the inverter rated output power 1) PEUT: EUT output power 2) PAC: Real power flow at S1 in Figure 1. Positive means power from EUT to utility. Nominal is the 0 % test condition value. 3) QAC: Reactive power flow at S1 in Figure 1. Positive means power from EUT to utility. Nominal is the 0 % test condition value. 4) BL: Balance condition, IB: Imbalance condition. Condition B: EUT output power PEUT = 50 % – 66 % of maximum EUT input voltage 5) = 50 % of rated input voltage range, ±10 % 5) Based on EUT rated input operating range. For example, If range is between X volts and Y volts, 90 % of range =X + 0,9 × (Y – X). Y shall not exceed 0,8 × EUT maximum system voltage (i.e., maximum allowable array open circuit voltage). In any case, the EUT should not be operated outside of its allowable input voltage range.

Page 59: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 59 of 174 TEST REPORT NRS 097-2-1 VER.0

Disconnection at P AC 0% and Q AC 0% reactive load and 66% nominal power

Page 60: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 60 of 174 TEST REPORT NRS 097-2-1 VER.0

4.2.2.4: Preventing of islanding (Islanding protect ion, Condition C)

P

Test result:SUN2000-42KTL

Test conditions

Frequency: 50+/-0,1Hz UN=230+/-3Vac

RLC consumes inverter real power within +/- 3% Distortion factor of chokes < 3%

Quality =1

Disconnection limit 2s

No PEUT 1)

(% of EUT rating)

Reactive load (% of

QL in 6.1.d) 1)

PAC 2) (% of

nominal)

QAC 3)

(% of nominal)

Run on Time (ms)

PEUT

(W) Qf VDC

(V) Remarks4)

22 33 33 0 -5 167 4,546 0,976 602 Test C at IB

23 33 33 0 -4 175 4,546 0,981 602 Test C at IB

24 33 33 0 -3 175 4,546 0,986 602 Test C at IB

25 33 33 0 -2 196 4,546 0,991 602 Test C at IB

26 33 33 0 -1 277 4,546 0,996 602 Test C at IB

3 33 33 0 0 298 4,546 1,001 602 Test C at BL

27 33 33 0 1 265 4,546 1,006 602 Test C at IB

28 33 33 0 2 245 4,546 1,011 602 Test C at IB

29 33 33 0 3 209 4,546 1,016 602 Test C at IB

30 33 33 0 4 207 4,546 1,021 602 Test C at IB

31 33 33 0 5 189 4,546 1,026 602 Test C at IB

Parameter at 0% per phase L= 55,65 mH R= 16,88 Ω C= 195,77 µF IAC fundamental current at

balance condition L1: 168 mA L2: 217 mA L3: 172 mA

Note: RLC is adjusted to min. +/-1% of the inverter rated output power 1) PEUT: EUT output power 2) PAC: Real power flow at S1 in Figure 1. Positive means power from EUT to utility. Nominal is the 0 % test condition value. 3) QAC: Reactive power flow at S1 in Figure 1. Positive means power from EUT to utility. Nominal is the 0 % test condition value. 4) BL: Balance condition, IB: Imbalance condition. Condition C: EUT output power PEUT = 25 % – 33 % 5) of maximum EUT input voltage 6) = <10 % of rated input voltage range 5) Or minimum allowable EUT output level if greater than 33 %. 6) Based on EUT rated input operating range. For example, If range is between X volts and Y volts, 90 % of range =X + 0,9 × (Y – X). Y shall not exceed 0,8 × EUT maximum system voltage (i.e., maximum allowable array open circuit voltage). In any case, the EUT should not be operated outside of its allowable input voltage range.

Page 61: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 61 of 174 TEST REPORT NRS 097-2-1 VER.0

Disconnection at PAC 0% and QAC 0% reactive load an d 33% nominal power

Page 62: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 62 of 174 TEST REPORT NRS 097-2-1 VER.0

4.2.2.4: Preventing of islanding (Islanding protect ion, Condition A)

P

Test reult:SUN2000-36KTL(400Vac)

Test conditions

Frequency: 50+/-0,1Hz UN=230+/-3Vac

RLC consumes inverter real power within +/- 3% Distortion factor of chokes < 3%

Quality =1

Disconnection limit 2s

No PEUT 1)

(% of EUT rating)

Reactive load (% of

QL in 6.1.d) 1)

PAC 2) (% of

nominal)

QAC 3)

(% of nominal)

Run on Time (ms)

PEUT

(kW per phase)

Qf VDC

(V) Remarks4)

1 100 100 0 0 443 12,133 1,004 768 Test A at BL

2 100 100 -10 -10 230 12,133 1,058 768 Test A at IB

3 100 100 -10 -5 217 12,133 1,087 768 Test A at IB

4 100 100 -10 0 222 12,133 1,115 768 Test A at IB

5 100 100 -10 +5 198 12,133 1,143 768 Test A at IB

6 100 100 -10 +10 182 12,133 1,170 768 Test A at IB

7 100 100 -5 -10 259 12,133 1,002 768 Test A at IB

8 100 100 -5 -5 239 12,133 1,030 768 Test A at IB

9 100 100 -5 0 244 12,133 1,057 768 Test A at IB

10 100 100 -5 +5 260 12,133 1,083 768 Test A at IB

11 100 100 -5 +10 177 12,133 1,108 768 Test A at IB

12 100 100 0 -10 313 12,133 0,952 768 Test A at IB

13 100 100 0 -5 252 12,133 0,978 768 Test A at IB

14 100 100 0 +5 417 12,133 1,029 768 Test A at IB

15 100 100 0 +10 301 12,133 1,053 768 Test A at IB

16 100 100 +5 -10 254 12,133 0,907 768 Test A at IB

17 100 100 +5 -5 244 12,133 0,932 768 Test A at IB

18 100 100 +5 0 473 12,133 0,956 768 Test A at IB

19 100 100 +5 +5 277 12,133 0,980 768 Test A at IB

20 100 100 +5 +10 367 12,133 1,003 768 Test A at IB

21 100 100 +10 -10 232 12,133 0,866 768 Test A at IB

22 100 100 +10 -5 226 12,133 0,889 768 Test A at IB

23 100 100 +10 0 227 12,133 0,913 768 Test A at IB

24 100 100 +10 +5 247 12,133 0,935 768 Test A at IB

25 100 100 +10 +10 241 12,133 0,957 768 Test A at IB

Page 63: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 63 of 174 TEST REPORT NRS 097-2-1 VER.0

Parameter at 0% per phase L= 13,80 mH R= 4,36 Ω C= 731,57 µF IAC fundamental current at

balance condition L1: 178 mA L2: 166 mA L3: 123 mA

Note: RLC is adjusted to min. +/-1% of the inverter rated output power 1) PEUT: EUT output power 2) PAC: Real power flow at S1 in Figure 1. Positive means power from EUT to utility. Nominal is the 0 % test condition value. 3) QAC: Reactive power flow at S1 in Figure 1. Positive means power from EUT to utility. Nominal is the 0 % test condition value. 4) BL: Balance condition, IB: Imbalance condition. Condition A: EUT output power PEUT = Maximum 5) EUT input voltage 6) = >90% of rated input voltage range 5) Maximum EUT output power condition should be achieved using the maximum allowable input power. Actual output power may exceed nominal rated output. 6) Based on EUT rated input operating range. For example, If range is between X volts and Y volts, 90 % of range =X + 0,9 × (Y – X). Y shall not exceed 0,8 × EUT maximum system voltage (i.e., maximum allowable array open circuit voltage). In any case, the EUT should not be operated outside of its allowable input voltage range.

Page 64: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 64 of 174 TEST REPORT NRS 097-2-1 VER.0

Disconnection at Pac 5% and Qac0% reactive load and 100% nominal power

Page 65: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 65 of 174 TEST REPORT NRS 097-2-1 VER.0

4.2.2.4: Preventing of islanding (Islanding protect ion, Condition B)

P

Test reult:SUN2000-36KTL(400Vac)

Test conditions

Frequency: 50+/-0,1Hz UN=230+/-3Vac

RLC consumes inverter real power within +/- 3% Distortion factor of chokes < 3%

Quality =1

Disconnection limit 2s

No PEUT 1)

(% of EUT rating)

Reactive load (% of

QL in 6.1.d) 1)

PAC 2) (% of

nominal)

QAC 3)

(% of nominal)

Run on Time (ms)

PEUT

(kW per

phase)

Qf VDC

(V) Remarks4)

12 66 66 0 -5 242 7,368 0,977 640 Test B at IB

13 66 66 0 -4 246 7,368 0,982 640 Test B at IB

14 66 66 0 -3 239 7,368 0,987 640 Test B at IB

15 66 66 0 -2 245 7,368 0,992 640 Test B at IB

16 66 66 0 -1 256 7,368 0,997 640 Test B at IB

2 66 66 0 0 296 7,368 1,002 640 Test B at BL

17 66 66 0 1 263 7,368 1,007 640 Test B at IB

18 66 66 0 2 262 7,368 1,012 640 Test B at IB

19 66 66 0 3 297 7,368 1,017 640 Test B at IB

20 66 66 0 4 290 7,368 1,022 640 Test B at IB

21 66 66 0 5 275 7,368 1,027 640 Test B at IB

Parameter at 0% per phase L= 25,13 mH R= 7,18 Ω C= 489,62µF IAC fundamental current at

balance condition L1: 192 mA L2: 175 mA L3: 198 mA

Note: RLC is adjusted to min. +/-1% of the inverter rated output power 1) PEUT: EUT output power 2) PAC: Real power flow at S1 in Figure 1. Positive means power from EUT to utility. Nominal is the 0 % test condition value. 3) QAC: Reactive power flow at S1 in Figure 1. Positive means power from EUT to utility. Nominal is the 0 % test condition value. 4) BL: Balance condition, IB: Imbalance condition. Condition B: EUT output power PEUT = 50 % – 66 % of maximum EUT input voltage 5) = 50 % of rated input voltage range, ±10 % 5) Based on EUT rated input operating range. For example, If range is between X volts and Y volts, 90 % of range =X + 0,9 × (Y – X). Y shall not exceed 0,8 × EUT maximum system voltage (i.e., maximum allowable array open circuit voltage). In any case, the EUT should not be operated outside of its allowable input voltage range.

Page 66: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 66 of 174 TEST REPORT NRS 097-2-1 VER.0

Disconnection at P AC 0% and Q AC -0% reactive load and 66% nominal power

Page 67: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 67 of 174 TEST REPORT NRS 097-2-1 VER.0

4.2.2.4: Preventing of islanding (Islanding protect ion, Condition C)

P

Test result:SUN2000-36KTL(400Vac)

Test conditions

Frequency: 50+/-0,1Hz UN=230+/-3Vac

RLC consumes inverter real power within +/- 3% Distortion factor of chokes < 3%

Quality =1

Disconnection limit 2s

No PEUT 1)

(% of EUT rating)

Reactive load (% of

QL in 6.1.d) 1)

PAC 2) (% of

nominal)

QAC 3)

(% of nominal)

Run on Time (ms)

PEUT

(W) Qf VDC

(V) Remarks4)

22 33 33 0 -5 185 3,858 0,977 512 Test C at IB

23 33 33 0 -4 208 3,858 0,983 512 Test C at IB

24 33 33 0 -3 232 3,858 0,988 512 Test C at IB

25 33 33 0 -2 227 3,858 0,993 512 Test C at IB

26 33 33 0 -1 245 3,858 0,998 512 Test C at IB

3 33 33 0 0 244 3,858 1,003 512 Test C at BL

27 33 33 0 1 274 3,858 1,008 512 Test C at IB

28 33 33 0 2 317 3,858 1,013 512 Test C at IB

29 33 33 0 3 676 3,858 1,018 512 Test C at IB

30 33 33 0 4 235 3,858 1,023 512 Test C at IB

31 33 33 0 5 214 3,858 1,028 512 Test C at IB

Parameter at 0% per phase L= 45,61 mH R= 13,71 Ω C= 244,00 µF IAC fundamental current at

balance condition L1: 186 mA L2: 197 mA L3: 188 mA

Note: RLC is adjusted to min. +/-1% of the inverter rated output power 1) PEUT: EUT output power 2) PAC: Real power flow at S1 in Figure 1. Positive means power from EUT to utility. Nominal is the 0 % test condition value. 3) QAC: Reactive power flow at S1 in Figure 1. Positive means power from EUT to utility. Nominal is the 0 % test condition value. 4) BL: Balance condition, IB: Imbalance condition. Condition C: EUT output power PEUT = 25 % – 33 % 5) of maximum EUT input voltage 6) = <10 % of rated input voltage range 5) Or minimum allowable EUT output level if greater than 33 %. 6) Based on EUT rated input operating range. For example, If range is between X volts and Y volts, 90 % of range =X + 0,9 × (Y – X). Y shall not exceed 0,8 × EUT maximum system voltage (i.e., maximum allowable array open circuit voltage). In any case, the EUT should not be operated outside of its allowable input voltage range.

Page 68: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 68 of 174 TEST REPORT NRS 097-2-1 VER.0

Disconnection at Pac 0% and Qac 3% reactive load an d 33% nominal power

Page 69: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 69 of 174 TEST REPORT NRS 097-2-1 VER.0

Annex 1 EMC Test Report

Page 70: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 70 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 71: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 71 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 72: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 72 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 73: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 73 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 74: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 74 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 75: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 75 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 76: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 76 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 77: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 77 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 78: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 78 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 79: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 79 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 80: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 80 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 81: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 81 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 82: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 82 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 83: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 83 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 84: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 84 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 85: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 85 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 86: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 86 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 87: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 87 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 88: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 88 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 89: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 89 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 90: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 90 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 91: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 91 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 92: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 92 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 93: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 93 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 94: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 94 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 95: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 95 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 96: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 96 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 97: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 97 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 98: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 98 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 99: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 99 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 100: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 100 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 101: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 101 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 102: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 102 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 103: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 103 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 104: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 104 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 105: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 105 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 106: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 106 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 107: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 107 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 108: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 108 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 109: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 109 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 110: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 110 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 111: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 111 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 112: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 112 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 113: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 113 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 114: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 114 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 115: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 115 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 116: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 116 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 117: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 117 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 118: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 118 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 119: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 119 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 120: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 120 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 121: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 121 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 122: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 122 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 123: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 123 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 124: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 124 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 125: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 125 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 126: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 126 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 127: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 127 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 128: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 128 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 129: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 129 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 130: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 130 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 131: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 131 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 132: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 132 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 133: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 133 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 134: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 134 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 135: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 135 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 136: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 136 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 137: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 137 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 138: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 138 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 139: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 139 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 140: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 140 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 141: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 141 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 142: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 142 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 143: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 143 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 144: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 144 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 145: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 145 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 146: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 146 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 147: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 147 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 148: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 148 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 149: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 149 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 150: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 150 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 151: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 151 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 152: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 152 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 153: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 153 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 154: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 154 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 155: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 155 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 156: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 156 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 157: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 157 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 158: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 158 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 159: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 159 of 174 TEST REPORT NRS 097-2-1 VER.0

Page 160: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 160 of 174 TEST REPORT NRS 097-2-1 VER.0

Annex 3 Pictures of the unit

Page 161: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 161 of 174 TEST REPORT NRS 097-2-1 VER.0

Enclosure front

Enclosure back

Page 162: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 162 of 174 TEST REPORT NRS 097-2-1 VER.0

Enclosure bottom

Interior view:

Page 163: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 163 of 174 TEST REPORT NRS 097-2-1 VER.0

Internal view-1

Internal view-2

Page 164: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 164 of 174 TEST REPORT NRS 097-2-1 VER.0

Internal view-3

Internal view-4

Page 165: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 165 of 174 TEST REPORT NRS 097-2-1 VER.0

Internal view-5

Internal view-6

Page 166: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 166 of 174 TEST REPORT NRS 097-2-1 VER.0

AC output board - component side:

AC output board board - solder side

Page 167: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 167 of 174 TEST REPORT NRS 097-2-1 VER.0

Main power board - component side

Main power board - solder side

Page 168: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 168 of 174 TEST REPORT NRS 097-2-1 VER.0

DC input board - component side

DC input board - solder side

Page 169: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 169 of 174 TEST REPORT NRS 097-2-1 VER.0

DC EMI board - component side

DC EMI board - solder side

Page 170: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 170 of 174 TEST REPORT NRS 097-2-1 VER.0

Interface board - component side

Interface board - solder side

Page 171: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 171 of 174 TEST REPORT NRS 097-2-1 VER.0

Monitoring board - component side

Monitoring board - solder side

Page 172: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 172 of 174 TEST REPORT NRS 097-2-1 VER.0

Control board - component side

Control board - solder side

Page 173: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 173 of 174 TEST REPORT NRS 097-2-1 VER.0

Annex 4 Test equipment list

Page 174: TEST REPORT NRS 097-2-1 - SegenSolar · The NRS 097-2-1 refers to the IEC 61727 and the IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement

Report No.: PVZA160707N051

Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch

No. 34, Chenwulu Section, Guantai Rd., Houjie Town, Dongguan City, Guangdong

523942, China

Tel: +86 769 8593 5656 Fax: +86 769 8599 1080

Email: [email protected] Page 174 of 174 TEST REPORT NRS 097-2-1 VER.0

Test location: Bureau Veritas Shenzhen Co., Ltd. Dongguan Branch Dates of per formance test: 2016-07-07 to 2016-07-22

Equipment Internal No. Manufacturer Type Serial No. Last Calibration

Power Analyzer A4080002DG YOKOGAWA WT3000 91M210852 Mar. 07, 2016

AC Source A7040019DG Chroma 61512 61512000439 Monitored by Power Analyzer

AC Source A7040020DG Chroma 61512 61512000438 Monitored by Power Analyzer

AC Source SCGJ276 Chroma 6560 656038001201 Monitored by Power Analyzer

DC Simulation Power Supply A7040015DG Chroma 62150H-1000S 62150EF00488 Monitored by

Power Analyzer DC Simulation Power Supply A7040016DG Chroma 62150H-1000S 62150EF00490 Monitored by

Power Analyzer

RLC Load A7150027DG Qunling ACLT-3803H 93VOO2869 Monitored by Power Analyzer

Four Channel Digital Phosphor Oscilloscope

A4089003DG Tektronix DPO4104B C010624 Oct. 16, 2015

ScopeCorder A4089017DG YOKOGAWA DL850 91N726247 Sep. 11, 2015 Oscilloscope probel

A4089008DG Tektronix TPP1000 C008230 Dec. 22, 2015

Oscilloscope probel A4089009DG Tektronix TPP1000 C008231 Dec. 22, 2015

Oscilloscope probel A4089010DG Tektronix TPP1000 C008228 Dec. 22, 2015

Oscilloscope probel A4089011DG Tektronix TPP1000 C008229 Dec. 22, 2015

Current transducer A1060007DG YOKOGAWA CT200 1130700012 Dec. 08, 2015 Current transducer A1060008DG YOKOGAWA CT200 1130700017 Nov. 21, 2015 Current transducer A1060009DG YOKOGAWA CT200 1130700019 Nov. 21, 2015 Current transducer A1060010DG YOKOGAWA CT200 1130700016 Dec. 08, 2015