TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING PSCAD AND MATLAB SITI NUR BAIZURA ABU BAKAR Thesis submitted in fulfillment of the requirements for the award of the degree of Bachelor of Electrical Engineering ( Power System ) Faculty of Electrical & Electronics Engineering UNIVERSITI MALAYSIA PAHANG DECEMBER 2010

Upload: dodieu

Post on 21-Apr-2018

223 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER …umpir.ump.edu.my/2100/1/Siti_Nur_Baizura_Abu_Bakar_(_CD_5337_).pdf · TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING

TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING PSCAD AND MATLAB

SITI NUR BAIZURA ABU BAKAR

Thesis submitted in fulfillment of the requirements for the award of the degree of Bachelor of Electrical Engineering ( Power System )

Faculty of Electrical & Electronics EngineeringUNIVERSITI MALAYSIA PAHANG

DECEMBER 2010

Page 2: TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER …umpir.ump.edu.my/2100/1/Siti_Nur_Baizura_Abu_Bakar_(_CD_5337_).pdf · TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING

ii

“All the trademark and copyrights use herein are property of their respective owner.

References of information from other sources are quoted accordingly; otherwise the

information presented in this report is solely work of the author.”

Signature : ………………

Author : SITI NUR BAIZURA BINTI ABU BAKAR

Date : 30 NOVEMBER 2010

Page 3: TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER …umpir.ump.edu.my/2100/1/Siti_Nur_Baizura_Abu_Bakar_(_CD_5337_).pdf · TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING

ii

ACKNOWLEDGEMENT

In the name of ALLAH s.w.t, most gracious, most merciful

The thesis has been an extremely arduous yet enriching and satisfying

experience for me. I would like to acknowledge profusely all those who have been a

part of this experience without whom I could not have completed the undertaken

task. Firstly I would like to thank my research advisor, Miss Lailatul Niza

Muhammad to whom I am greatly indebted for engineering guidance. I am fortunate

to have her as my advisor and am deeply appreciative of her considerate personality.

She has been the main source of motivation in pursuing my research ideas.

Mr. Redzuan Ahmad is an excellent teacher and has sparked my interest in

power systems through his course “Power System Distribution & High Voltage”. I

extend my heartfelt gratitude to my parent and friend for their constant support and

motivation to pursue my thesis successfully.

Finally, I like to thank to all my friends and those who help me in completing

this project and to my parents for their never ending supports.

May God repay all of your kindness.

Page 4: TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER …umpir.ump.edu.my/2100/1/Siti_Nur_Baizura_Abu_Bakar_(_CD_5337_).pdf · TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING

ii

ABSTRACT

Power utilities have facing challenges due to increase load demands caused

by rapid industries growth over years. One of the problems is the voltage instability

in power system. Voltage stability is the ability of the system to maintain the voltage

magnitude under normal condition and also under heavy stressed condition. Voltage

instability is the power system that did not have the ability to meet reactive power

demand. This will lead to a voltage collapse in the system. This project will present

the performance of STATCOM installation in nine bus test system. A load flow

analysis is conducted in order to obtain the power flow magnitudes, voltage levels

and power losses in the distribution system. In addition, this project is to study the

effectiveness of STATCOM by injecting at the critical location bus in the system.

Thus, STATCOM that acts as a controller will regulate the terminal voltage and

correcting the fault in transmission line of power system network.

Page 5: TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER …umpir.ump.edu.my/2100/1/Siti_Nur_Baizura_Abu_Bakar_(_CD_5337_).pdf · TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING

iii

ABSTRAK

Tenaga utiliti menghadapi cabaran akibat peningkatan tuntutan beban kerana

pertumbuhan pesat industri selama bertahun-tahu. Salah satu sebab adalah ketidak

stabilan voltan. Tegangan kestabilan adalah kemampuan sistem untuk

mempertahankan besarnya tegangan pada keadaan biasa dan juga dalam keadaan

stres berat. Punca ketidakstabilan voltan adalah sistem kuasa tidak memiliki

kemampuan untuk memenuhi permintaan kuasa reaktif. Hal ini akan menyebabkan

jatuhnya voltan dalam sistem. Tesis ini akan menyajikan keberkesanan pemasangan

STATCOM di sembilan ujian sistem bas. Analisis aliran kuasa dilakukan dalam

rangka untuk mendapatkan besaran aliran daya, tahap voltan dan kerugian daya

dalam sistem pengedaran. Projek ini adalah untuk mengkaji keberkesanan

STATCOM oleh suntikan di lokasi bas kritikal dalam sistem. Dengan demikian,

STATCOM bertindak sebagai pengawal akan menetapkan voltan terminal dan

perbaikan kesalahan dalam saluran penghantaran rangkaian sistem tenaga.

Page 6: TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER …umpir.ump.edu.my/2100/1/Siti_Nur_Baizura_Abu_Bakar_(_CD_5337_).pdf · TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING

vii

TABLE OF CONTENTS

CHAPTER TITLE PAGE

DECLARATION ii

DEDICATION iii

ACKNOWLEGMENT iv

ABSTRACT v

ABSTRAK vi

TABLE OF CONTENTS vii

LIST OF TABLES ix

LIST OF FIGURES x

LIST OF ABBREVIATIONS xii

LIST OF APPENDICES xiii

1.0 INTRODUCTION

1.1 Overview of the project 1

1.2 Objectives 2

1.3 Problem Statement 2

1.4 Scope of Work

1.5 Thesis Outline

1.6 Gantt Chart

3

3

4

2.0 LITERATURE REVIEW

2.1 Power Flow 5

2.2 FACTS

2.2.1 Theory and control of STATCOM

6

9

Page 7: TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER …umpir.ump.edu.my/2100/1/Siti_Nur_Baizura_Abu_Bakar_(_CD_5337_).pdf · TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING

viii

3.0

2.2.1.1 STATCOM Main Circuit Configurations

2.2.1.1 Advantages of STATCOM

2.3 Formula and Equation

2.3.1 Conversion of per-unit to actual value

2.3.2 Six-pulse STATCOM

2.4 Summary

METHODOLOGY

10

11

12

12

13

14

3.1 Introduction

3.2 Test Systems

3.3 Analysis Approach

3.3.1 Flow Chart

3.4 Software Involve in Analysis

3.4.1 PSCAD

3.4.1.1 Six Pulse STATCOM

3.4.1.2 Voltage Control Loop

3.4.1.3 SPWM Control

3.4.1.4 Firing Pulses

3.4.2 MATLAB

3.4.2.1 MATPOWER

3.4.2.2 M-Files

3.5 Summary

15

15

17

18

19

19

20

23

25

26

27

27

28

28

4.0 RESULT AND DISCUSSION

4.1 Introduction

4.2 Four Bus Test System

4.2.1 Load Flow Analysis

4.2.1.1 Steady State Analysis

4.3 STATCOM Placement

4.4 Nine Bus Test System

4.4.1 Load Flow Analysis

4.4.1.1 Steady State

4.5 STATCOM Placement

4.6 Summary

29

29

32

32

36

42

44

44

47

53

Page 8: TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER …umpir.ump.edu.my/2100/1/Siti_Nur_Baizura_Abu_Bakar_(_CD_5337_).pdf · TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING

ix

5.0 CONCLUSION AND RECOMMENDATIONS

5.1 Conclusion

5.2 Future Recommendation

54

54

55

REFERENCES 56

APPENDICES 59

Page 9: TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER …umpir.ump.edu.my/2100/1/Siti_Nur_Baizura_Abu_Bakar_(_CD_5337_).pdf · TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING

ix

LIST OF TABLES

TABLE NO. TITLE PAGE

1 Gantt Chart for PSM 1 4

2 Gantt Chart for PSM 2 4

3 Data of 4 Bus Test Systems from input data of

MATPOWER 4.02

16

4 Conversion of per unit value to actual value 30

5 Voltage level for IEEE 4 bus system without

STATCOM

33

6 Load Flow Result in MATLAB 33

7 Load Flow Result in PSCAD 34

8 Voltage level for 4 bus system with STATCOM 39

9 Power flow of bus system by adding the STATCOM 40

10 Voltage level for IEEE 9 in MATLAB 44

11 The load flow in MATLAB of 9 bus system 45

12 Load flow analysis result in PSCAD of 9 bus system 45

13 Power Losses Comparison between MATLAB and

PSCAD

46

14 Voltage level for 9 bus system with STATCOM 49

15 Power flow of bus system with STATCOM

installation

50

Page 10: TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER …umpir.ump.edu.my/2100/1/Siti_Nur_Baizura_Abu_Bakar_(_CD_5337_).pdf · TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING

x

LIST OF FIGURES

FIGURE NO TITLE PAGE

2.1 A three phase converter bridge-the basic building block

of a VSC

7

2.2 A VSC interfaced to a transmission line- P&Q exchange 8

2.3 A Static synchronous compensator operated in inductive

and capacitive mode

10

2.4 Multipulse Converter Diagram 11

2.5 Cascade multilevel converter diagram 11

3.1 Six-pulse STATCOM 20

3.2 IEEE 4 bus system with implementation of STATCOM 21

3.3 Basic STATCOM control scheme 23

3.4 Voltage Control Loop 24

3.5 Generation of triangular waveforms for STATCOM 25

3.6 Generation of sine waveforms for STATCOM 26

3.7 Interpolated Firing Pulses component for STATCOM. 27

3.8 MATLAB Software 27

4.1 Modeling of IEEE 4 bus test system in PSCAD 31

4.2 Per-unit bus voltage, V1 without STATCOM 35

4.3 Per-unit bus voltage, V2 without STATCOM 35

4.4 Per-unit bus voltage, V3 without STATCOM 35

4.5 Per-unit bus voltage, V4 without STATCOM 36

4.6 IEEE 4 bus system with STATCOM at bus 3 38

4.7 Graph of voltage at each bus 40

4.8 Graph of Reactive Power Losses 41

4.9 Graph of Real Power Losses 41

Page 11: TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER …umpir.ump.edu.my/2100/1/Siti_Nur_Baizura_Abu_Bakar_(_CD_5337_).pdf · TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING

xi

4.10 IEEE 9 bus system in PSCAD 43

4.11 IEEE 9 bus system with STATCOM at bus 9 48

4.12 Graph of voltage at each bus 50

4.13 Graph of real power losses 51

4.14 Graph of reactive power losses 51

4.15(a) STATCOM performance of Active Power 52

4.15(b) STATCOM performance of Reactive Power 52

4.15(c) STATCOM performance of DC Voltage 52

Page 12: TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER …umpir.ump.edu.my/2100/1/Siti_Nur_Baizura_Abu_Bakar_(_CD_5337_).pdf · TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING

xii

LIST OF ABBREVIATIONS

AI - Artificial Intelligence

DM - Decision Maker

DC - Direct Current

FIS - Fuzzy Inference System

GA - Genetic Algorithms

L - Low Voltage

MV - Medium Voltage

SA - Simulated Annealing

TS - Tabu Search

TNB - Tenaga Nasional Berhad

Page 13: TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER …umpir.ump.edu.my/2100/1/Siti_Nur_Baizura_Abu_Bakar_(_CD_5337_).pdf · TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING

xiii

LIST OF APPENDICES

APPENDIX TITLE PAGE

A Data Form 4 Bus Test Systems from Input Data of MATPOWER 4.02

59

B Result For 4 Bus Test System from MATLAB 60

C Voltage bus level Meter Reading for Load Flow Analysis of

4-bus Test System

61

D Real and Reactive Power Meter Reading for Load Flow

Analysis of 4-bus Test System

62

E Data Form 9 Bus Test Systems from Input Data of MATPOWER 4.02

63

F Result For 9 Bus Test System from MATLAB 64

G Voltage bus level Meter Reading for Load Flow Analysis of 9-bus Test System

(Before STATCOM installed)

65

H Voltage bus level Meter Reading for Load Flow Analysis of 9-bus Test System

(After STATCOM installed)

66

I Real Power Meter Reading for Load Flow Analysis of 9-bus Test System (Before STATCOM installed)

67

J Real Power Meter Reading for Load Flow Analysis of 9-bus Test System (After STATCOM installed)

68

K Reactive Power Meter Reading for Load Flow Analysis of 9-bus Test System (Before STATCOM installed)

69

L Reactive Power Meter Reading for Load Flow Analysis of 9-bus Test System (Before STATCOM installed)

70

Page 14: TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER …umpir.ump.edu.my/2100/1/Siti_Nur_Baizura_Abu_Bakar_(_CD_5337_).pdf · TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING

1

CHAPTER 1

INTRODUCTION

1.1 Overview of the project

Heavy industries and electrical utilizes facing a number of challenges and

problems that is related to reactive power. These heavy industrial applications can

cause phenomena and problem such as voltage unbalance, distortion or flicker on the

electric grid. For electrical utilities, it may be confronted with phenomena of voltage

sags, poor power factor or even voltage instability. Reactive power control can

resolve these issues. The ultimate objective of the transmission system is to deliver

electric power reliably and economically from generators to loads. Power systems

are extremely complex, large beside has ever-changing structures that must respond

continuously real-time. The electricity should be produced and should be delivered

instantly when is demanded by a load. The system should carry out as economically

as possible, with transactions and sales monitored accurately.

To overcome this problem, a new technology was develop to replace the

mechanical control. The FACTS controllers have the ability of enhancing

transmission system control, reliability, and operation, and also improve the

distribution-system power quality. Static Synchronous Compensator (STATCOM) is

one of the FACTSs’ families. Over the last two decades, advancements in static

reactive compensation technology based on VSC concepts have produced significant

benefits. STATCOM systems offer rapid response to system events, improved

voltage and power system stabilization and enhanced reliability.

Page 15: TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER …umpir.ump.edu.my/2100/1/Siti_Nur_Baizura_Abu_Bakar_(_CD_5337_).pdf · TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING

2

1.2 Objective

The purpose of this project are:

i. to simulate STATCOM model IEEE 4 and IEEE 9 bus power system

network using PSCAD software.

ii. to analyze the performance of the IEEE 4 and IEEE 9 bus power

system network with and without STATCOM applied.

iii. to model STATCOM in IEEE 4 and IEEE 9 bus power system

network.

1.3 Problem Statement

Nowadays, the increasing of power demand and loads especially non linear

loads making the power system network become complex to operate. The system

becomes insecure with large power flows without adequate control. To overcome

these issues, STATCOM controllers is introduced to the power system. Ideally, these

new controllers should be able to control voltage level and improve system’s stability

by applying at the critical location.

1.4 Scope of Project

The scope of this project is focusing on:

i. modeling STATCOM in IEEE 4 and IEEE 9 bus power system

network

ii. simulation on the model using PSCAD.

iii. analyze and compare the performance of IEEE 4 and IEEE 9 bus

system with and without STATCOM.

Page 16: TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER …umpir.ump.edu.my/2100/1/Siti_Nur_Baizura_Abu_Bakar_(_CD_5337_).pdf · TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING

3

1.5 Thesis Outline

The thesis is organized into five chapters. The brief outline of each chapter is presented as below:

Chapter 1 contained about overviewed of overall of this project, objective of

doing this project, scope of project description, and the problem statement regarding

to this research.

Chapter 2 consist of literature review that been read. It contains of review of

the technical paper written by expertise that have been taken from website and also

books. Literature review is crucial for every thesis not only to support the proposed

title but also for guidelines and references on the conducted thesis.

Chapter 3 represent about the analysis approach that involve in this research.

It also included the procedures and the tools that used in the analysis which are

PSCAD and MATLAB.

Chapter 4 states the result and the analysis made from the research and the

discussion during the research done. Every result from the simulation are stated,

analyzed and explained briefly.

Chapter 5 contains the conclusion of overall project by state the final result

that gained from the project. Future recommendations also stated in order to improve

this project in the future undertakings

Page 17: TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER …umpir.ump.edu.my/2100/1/Siti_Nur_Baizura_Abu_Bakar_(_CD_5337_).pdf · TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING

4

1.6 Gantt Chart

Table 1: Gantt Chart for PSM 1

Table 2: Gantt Chart for PSM 2

Page 18: TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER …umpir.ump.edu.my/2100/1/Siti_Nur_Baizura_Abu_Bakar_(_CD_5337_).pdf · TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING

5

CHAPTER 2

LITERATURE REVIEWS

2.1 Power Flow

Load flow studies are performed using computer software that simulates

actual steady-state power system operating conditions, enabling the evaluation of bus

voltage profiles, real and reactive power flow and losses. Conducting a load flow

study using multiple scenarios helps ensure that the power system is adequately

designed to satisfy the performance criteria. A properly designed system helps

contain initial capital investment and future operating costs [1]. Load flow studies are

commonly used to investigate:

i. the component or circuit loading

ii. the bus voltage profiles

iii. the real and reactive power flow

iv. the power system losses

v. the proper transformer tap settings

The goal of a power flow study is to obtain complete voltage angle and

magnitude information for each bus in a power system for specified load and

generator real power and voltage conditions. Once of this information is known, real

and reactive power flow on each branch as well as generator reactive power output

can be analytically determined. Due to the nonlinear nature of this problem,

numerical methods are employed to obtain a solution that is within an acceptable

Page 19: TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER …umpir.ump.edu.my/2100/1/Siti_Nur_Baizura_Abu_Bakar_(_CD_5337_).pdf · TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING

6

tolerance. The solution to the power flow problem begins with identifying the known

and unknown variables in the system. The known and unknown variables are

dependent on the type of bus. A bus without any generators connected to it is called a

Load Bus. With one exception, a bus with at least one generator connected to it is

called a Generator Bus. The exception is one arbitrarily-selected bus that has a

generator. This bus is referred to as the Slack Bus [1].

For assessing the impact of the STATCOM in controlling the grid voltage,

power flow study is necessary. Moreover, in the planning stage, to determine the

ratings of the STATCOM, among others, repeated load flow studies are carried out.

Also, in a stability study, load flow solution is required to establish the initial

operating point. Thus, power flow studies are indeed one of the most fundamental

studies necessary to be carried out before implementing any STATCOM in a power

system [2].

2.2 FACTS

FACTS is stand for Flexible AC Transmission System. FACTS is an

evolving technology based solution envisioned to help the utility industry to deal

with changes in the power delivery business. FACTS is defined by the IEEE as “a

power electronic based system and other static equipment that provide control of one

or more AC transmission system parameters to enhance controllability and increase

power transfer capability [3].

FACTS provide high speed and precise control of one or more AC system

parameters within synchronous AC system, thereby greatly enhancing the value of

AC transmission assets. These parameters include voltages, impedances, phase

angle, currents, reactive power and active power [4].

There are three widely known FACTS controllers, namely as STATCOM,

SSSC and UPFC. All of these controllers have a converter based which is Voltage-

Source Converters (VSC). A basic building block of any VSC is the three phase

Page 20: TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER …umpir.ump.edu.my/2100/1/Siti_Nur_Baizura_Abu_Bakar_(_CD_5337_).pdf · TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING

7

converter bridge. One is commonly known configuration for a three phase bridge is

shown in Figure 2.1. The bridge has two DC terminals indicated by “+” sign and “-”

sign in the Figure 2.1 and three AC terminals “~” in the mid points of the converter

legs. By controlling the states of switches in the legs we can produce arbitrary

voltage waveforms at the AC terminals [5].

Figure 2.1: A three phase converter bridge-the basic building block of a Voltage

Source Converters [5].

When a VSC is interfaced to a transmission system it has to operate at the

line frequency and to produce a balanced set of sinusoidal voltages. Therefore, a

VSC coupled to the transmission system has only two control degrees of freedom; it

can vary the magnitude and the phase angle of its output voltage relative to the

system voltage [5].

These two control degrees of freedom can be mapped to exchange active and

reactive power with the transmission system. The amount of exchanged reactive

power is limited only by the current capacity of the converter switches, while the

active power coupled to (from) the line has to be supplied from (delivered to ) the

DC terminals, as shown symbolically in Figure 2.2 [5].

+

-

Page 21: TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER …umpir.ump.edu.my/2100/1/Siti_Nur_Baizura_Abu_Bakar_(_CD_5337_).pdf · TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING

8

Figure 2.2: A VSC interfaced to a transmission line- P and Q exchange.

Among the main functions of FACTS devices that can enhance the flexibility

and increase the security of a power system are [5]:

i. phase shifting: this is realized by injecting a voltage in series into the

power system.

ii. voltage support by means of shunt device.

iii. line impedance adaption by means of series devices.

FACTS controllers can be connected to the system in the number of ways [5];

i. In shunt, the preferred way to meet equipment isolation requirements

(one end of the device is referenced to ground) and from the stand

point of protection from system short circuit currents.

ii. In series, which has the disadvantages mention above, but only

requires relatively low voltage ratings; technological solutions have

been develop to solve problems associated with insulating the

equipment from ground and the full potential of series connections

can now be exploited.

iii. With both shunt and series elements, such as in the UPFC.

Page 22: TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER …umpir.ump.edu.my/2100/1/Siti_Nur_Baizura_Abu_Bakar_(_CD_5337_).pdf · TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING

9

2.2.1 Theory and control of STATCOM

The Static Synchronous Compensator (STATCOM) is based on the principal

that a voltage source inverter generates a controllable AC voltage source behind a

transformer reactance so that the voltage difference across the reactance produces

active and reactive power exchange between the STATCOM and the transmission

network [6]. The STATCOM is a shunt reactive power compensating electronic

device that generates AC voltage, which intern causes a current of variable

magnitude at the point of connection. This injected current is almost in quadrature

with the line voltage, thereby emulating an inductive or a capacitive reactance at the

point of connection with the transmission line. The functionality of the STATCOM

model is verified by regulating the reactive current flow through it. This is useful to

generate or absorb reactive power for regulating the line voltage of the bus where the

STATCOM is connected [7].

A STATCOM installation plays an important role in power industries to

improve the stability of the system. STATCOM in it basis is one DC-AC voltage

source convertor having one storage unit energy, usually a DC capacitor. It operating

as Synchronous Voltage Source (SVS) that connected to the line through a coupling

transformer. STATCOM has a dynamic performance far exceeding the other Var

Compensators [8].

Figure 2.3 demonstrates a simplified diagram of the STATCOM with an

inverter voltage source, E and a tie reactance, Xtie connected to an ac system with

voltage source, Vth and a Thevenin reactance, Xth. When the converter voltage is

greater than the system voltage, the STATCOM “sees” an inductive reactance

connected at its terminal. Hence, the system “sees” the STATCOM as a capacitive

reactance and the STATCOM is operating in a capacitive mode [7]. The current

flows from the STATCOM to the AC system, and the device generates reactive

power. In this case, the system draws capacitive current that leads by and angle of

90° the system voltage, assuming that the converter losses are equal to zero [9].

Page 23: TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER …umpir.ump.edu.my/2100/1/Siti_Nur_Baizura_Abu_Bakar_(_CD_5337_).pdf · TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING

10

Figure 2.3: A static synchronous compensator operated in inductive and capacitive

mode [10]

2.2.1.1 STATCOM Main Circuit Configurations

There are two types of STATCOM main circuit configuration which are

multipulse converter and multilevel converter [8].

In the multipulse converter, the 3-phase bridges are connected in parallel on

the DC side as shown in Figure 2.4. The bridges are magnetically coupled via a

zigzag transformer. The transformer is usually arranged in order to make the bridges

appear in series viewed from the AC sides. Each windings of the transformer is phase

shifted. This is to eliminate selected harmonics and produce a multipulse output

voltage. Pulse Width Modulation (PWM) is applied to improve the harmonics

content, at the expense of higher switching and snubber loss, plus reduced the

fundamental of var rating [8].

Page 24: TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER …umpir.ump.edu.my/2100/1/Siti_Nur_Baizura_Abu_Bakar_(_CD_5337_).pdf · TESTING OF STATCOM MODEL IN IEEE 0 BUS POWER SYSTEM NETWORK USING

11

Figure 2.4: Multipulse Converter Diagram [8].

Figure 2.5 shows the multilevel converter configuration consists of three

different configurations which are Diode-clamped converter, Flying Capacitor

Converter and Cascade Converter. A cascade converter is constructed by standard H-

bridges in series. Apart from other designs, cascade multilevel converter eliminates

clamping diode, flying capacitors or zigzag transformer. Thus, its requires least

components used and low cost are involved. Larger dc-side capacitors are required

compared to the diode clamped and flying capacitor converter under balanced

condition but it provides separate phase control to support significant voltage

unbalance [8].

Figure 2.5: Cascade multilevel converter diagram [8]

2.2.1.2 Advantages of STATCOM

STATCOM has many advantages over the other compensators. The

advantages of STATCOM can be summarized such as[10]:

i. it has short term overload capability of ~20%