texas panhandle synchronous condenser solution

16
www.datcllc.com Texas Panhandle Synchronous Condenser Solution Presented to ERCOT Regional Planning Group April 22, 2014

Upload: berget

Post on 04-Feb-2016

72 views

Category:

Documents


1 download

DESCRIPTION

Texas Panhandle Synchronous Condenser Solution. Presented to ERCOT Regional Planning Group April 22, 2014. Outline. DATC Introduction Problem Description DATC Proposal DATC Advantages. Duke-American Transmission Company (DATC). - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Texas Panhandle Synchronous Condenser Solution

www.datcllc.com

Texas Panhandle Synchronous Condenser

Solution

Presented to ERCOT Regional Planning Group

April 22, 2014

Page 2: Texas Panhandle Synchronous Condenser Solution

www.datcllc.com

Outline

2

• DATC Introduction

• Problem Description

• DATC Proposal

• DATC Advantages

Page 3: Texas Panhandle Synchronous Condenser Solution

www.datcllc.com

Duke-American Transmission Company (DATC)

• DATC is a 50/50 joint venture, formed in April 2011 to pursue transmission development on a national scale

• Founded on a vision of transmission as the key to efficient power markets

• Committed to developing projects that deliver a strong portfolio of reliability, economic and public policy benefits

• Publically announced projects and assets:– DATC Midwest Portfolio – new transmission line projects in Iowa, Wisconsin, Illinois, Indiana and Ohio

– Zephyr Power Transmission – planned 500 kV HVDC transmission line from Wyoming to California

– Path 15 – DATC owns 72 percent of the transmission service rights the 500 kV transmission line in central California

• Strategic focus on ERCOT, Texas and SPP as areas of high potential

– Interest in pursuing a variety of platforms for transmission development including partnerships, greenfield, and acquisitions

3

Page 4: Texas Panhandle Synchronous Condenser Solution

www.datcllc.com

Overview of Duke Energy Corporation (NYSE: DUK)

4

• Headquartered in Charlotte, NC

• 150+ years of service

• ~ 30,000 employees

• $50 Billion market cap

• 57,200 MW of generating capacity

• 85% regulated franchise utilities and 15% commercial enterprises

Page 5: Texas Panhandle Synchronous Condenser Solution

www.datcllc.com

Duke Energy Texas Presence

6

Wind Solar Battery Office

Offices in Houston and AustinOver 100 employees in Texas

950 MW operating generationSweetwater Windpower Project, Nolan County

283 MW 2003 (2007)

Ocotillo Windpower Project, Howard County

59 MW (2008)

Notrees Windpower Project, Ector & Winkler Counties

153 MW (2009)

Blue Wing Solar Power Project, San Antonio

14 MW (2010)

Notrees Battery Storage Project, Winkler County

36 MW (2012)

Los Vientos I Windpower Project, Willacy County

200 MW (2012)

Los Vientos II Windpower Project, Willacy County

202 MW (2012)

Page 6: Texas Panhandle Synchronous Condenser Solution

www.datcllc.com

Overview of American Transmission Company

7

• First multi-state stand alone transmission utility in U.S.

– Formed in 2001

– Privately held with diverse ownership made up of investor-owned utilities, municipalities and cooperatives

• Tremendous growth since formation

– Over $3.3B in assets in 2012

– Largest transmission owner in MISO

Page 7: Texas Panhandle Synchronous Condenser Solution

www.datcllc.com

ATC Municipalities, IOUs, and Co-ops

8

ATC has 29 owners, including several cooperatives

Page 8: Texas Panhandle Synchronous Condenser Solution

www.datcllc.com 9

PREZ Problem Statement• Original CREZ plan called for ~5.5 GW of capacity in Panhandle, but

reactive support equipment initially installed for ~2.4 GW.

• Panhandle transmission, remote from ERCOT load and synchronous generation, is stability constrained.

• Panhandle Renewable Energy Zone (PREZ) study has determined additional transmission upgrades are required to support generation located in the panhandle when GI queue reaches 3,000 MW financial commitment.

• PREZ study (phase 1) recommends additional transmission and 200 MVAR of reactive support be installed initially (1,650 MVAR ultimately) in the panhandle area in the form of synchronous condensers1 due to their superior inertia and fault current characteristics.

1 Synchronous Condensers are generators that operate like a motor to supply inertial response, reactive support, and frequency response - synchronized with the grid, requiring no fuel, and produce zero emissions.

Page 9: Texas Panhandle Synchronous Condenser Solution

www.datcllc.com 10

PREZ Upgrade Requirements

• Synchronous condensers located at Windmill and Ogallala stations in all 3 PREZ planning scenarios

• Synchronous condensers and linear upgrades required concurrently

Page 10: Texas Panhandle Synchronous Condenser Solution

www.datcllc.com

PREZ Upgrade Plan

11

Page 11: Texas Panhandle Synchronous Condenser Solution

www.datcllc.com

DATC Solution•Project Phoenix is the DATC response to ERCOT’s identified need for reactive support in the Texas panhandle to facilitate wind generation interconnection currently in the queue with confirmed financial commitment to build.

•DATC proposes to install repowered generators from the Duke fleet operated as Synchronous Condensers at Windmill Substation and/or other ERCOT locations to supply the needed reactive power.

•DATC is eligible to offer and own this solution to ERCOT under ERCOT Nodal Protocol 3.11.2 (3) which states, “ERCOT shall attempt to meet these reliability criteria as economically as possible and shall actively identify economic projects to meet this goal.”

•If endorsed by ERCOT, a PUCT CCN application will follow.

12

Page 12: Texas Panhandle Synchronous Condenser Solution

www.datcllc.com

Duke Preferred Synchronous Condenser InventoryUnit Manufacturer MVA

CapabilityMVAR Capability Retirement

1 Westinghouse 192 155 / -116 March 2014

2 GE 288 205 / -125 May 2015

3 Westinghouse 512 379 / -256 May 2015

4 Westinghouse 105 103 / -76 April 2016

5 GE 145 115 / -67 April 2016

6 GE 145 115 / -67 April 2016

7 Westinghouse 156 144 / -94 April 2016

8* Westinghouse 496 320 / -250 October 2013

9* GE 128 101 / -59 April 2013

10* Westinghouse 297 250 / -130 September 2012

11* GE 150 100 / -65 April 2012

12* GE 160 110 / -80 October 2012

* Recently rewound

13

Page 13: Texas Panhandle Synchronous Condenser Solution

www.datcllc.com

DATC Proposal

•DATC is also amenable to collaborating with ERCOT on ERCOT’s preference of available Duke units.

14

Proposal Units to be Repowered

Capability MVAR

Cost

A #10#12

Total

250 / -130110 / -80360 / -210

$39M

B #10#8

Total

250 / -130320 / -250570 / -380

$41M

Page 14: Texas Panhandle Synchronous Condenser Solution

www.datcllc.com

DATC Solution Advantages•DATC provides a cost advantage over all other incumbent providers due to full depreciation ($0 book value) of Duke generators to be repowered.

•Anticipate 20-30% savings over new Synchronous Condenser equipment.

•Duke retired generator inventory is immediately available providing a time advantage over new equipment long lead time delivery.

•DATC Proposal B can satisfy PREZ Phase 2 reactive reinforcement requirements at Windmill thereby avoiding approximately $88M additional cost.

•DATC Synchronous Condenser solution is “repeatable” at other ERCOT locations requiring reactive support.

15

Page 15: Texas Panhandle Synchronous Condenser Solution

www.datcllc.com 16

Duke / ATC Strengths Applicable To the TX Panhandle

• Large fleet of retired and soon to be retired units and spare parts inventory

• History of operating generation and transmission providing a unique skill set in ERCOT when considering synchronous condensers as transmission assets

• Supply chain economies of scale

• Expert in planning, designing, and constructing transmission lines, substations, generating plants, and related infrastructure

• History of reliable interconnection and operations in the ERCOT system

• History of meeting stakeholder expectations

Page 16: Texas Panhandle Synchronous Condenser Solution

Contact Information

www.datcllc.comJeff Peterson

713-375-0709

[email protected]

Bob Burner

704-382-6889

[email protected]

Mark Bruce

512-810-1516

[email protected]