PERFORMANCE TEST REPORT

Rendered to:

THERMACOTE, INC.

PRODUCT: ThermaCote® Air Barrier Coating

Report No: B0780.01-106-31

Report Date: 08/08/11

Expiration Date: 07/15/15

Architectural Testing

130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com

Page 2: Therma cote air barrier test final report  astm e 2178

PERFORMANCE TEST REPORT

Rendered to:

THERMACOTE, INC.

1369 Herrington Road

Lawrenceville, Georgia 30044

Report No: B0780.01-106-31

Test Dates: 07/11/11

Through: 07/15/11

Report Date: 08/08/11

Expiration Date: 07/15/15

Product: ThermaCote® Air Barrier Coating

Project Summary: Architectural Testing, Inc. was contracted by ThermaCote, Inc. to evaluate

the air permeance of their ThermaCote® air barrier coating. The product description, test

procedure and test results are reported herein. The average results from testing are presented in

the chart below.

ASTM E 2178 - Air Permeance

Parameter Test Results

Calculated Air Permeance at 25 Pa 0.000004 L/Pa·m2·s

Calculated Air Permeance at 50 Pa 0.000004 L/Pa·m2·s

Calculated Air Permeance at 75 Pa 0.000005 L/Pa·m2·s

Calculated Air Permeance at 100 Pa 0.000005 L/Pa·m2·s

Calculated Air Permeance at 150 Pa 0.000006 L/Pa·m2·s

Calculated Air Permeance at 300 Pa 0.000006 L/Pa·m2·s

Test Method: The test specimens were evaluated in conformance with the following method

without deviation. ASTM E 2178-03, Standard Test Method for Air Permeance of Building Materials.

Product Description: ThermaCote provided to Architectural Testing five nominal 48" x 48" x

1/2" (122 cm x 122 cm x 1.3 cm) ThermaCote® air barrier coated Dens-glass sections and one

nominal 48" x 48" x 1/2" (122 cm x 122 cm x 1.3 cm) uncoated Dens-glass section. The

ThermaCote® air barrier was applied at a 40 mil wet thickness and dried to a 30 to 35 mil dry

thickness. It is white in color and has a nominal basis weight of 5 lbs/gal. The sections were

tested as-received with the exception of cutting the sections to 42.5" x 42.5" (108 cm x 108 cm).

Architectural Testing

130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com

Page 3: Therma cote air barrier test final report  astm e 2178

B0780.01-106-31

Page 2 of 4

Test Procedure and Test Results: The results are reported in the following tables. All

specimen conditioning and test conditions were at standard laboratory conditions.

ASTM E 2178 - Air Permeance

Each test specimen was placed coating side up (exterior) on top of the test chamber (ICN

004933) and then sealed to the test chamber utilizing duct tape and 4 mil thick polyethylene

sheeting. The resulting test area was 1 meter x 1 meter (39.3" x 39.3").

The test specimen was then tested at preset air pressures ranging from 25 Pa to 300 Pa. Upon

completion of the cycle, the polyethylene sheet was sliced and peeled away from the test

specimen's surface. The test specimen was tested again at preset air pressures ranging from 25

Pa to 300 Pa. Refer to the photos in Appendix A. The actual pressure and flow values are

presented in Appendix B, and the air permeance graph appears in Appendix C.

ThermaCote® Air Barrier Coated Dens-glass

Air

Pressure,

Pa

Measured Flow Rate, L/(s·m2)

Test Specimen

1 2 3 4 5

25 0.00011 0.00019 0.00020 0.00005 0.00018

50 0.00024 0.00006 0.00023 0.00017 0.00026

75 0.00064 0.00046 0.00020 0.00042 0.00013

100 0.00056 0.00090 0.00031 0.00038 0.00026

150 0.00084 0.00149 0.00136 0.00063 0.00106

300 0.00207 0.00241 0.00281 0.00192 0.00170

ThermaCote® Air Barrier Coated Dens-glass

Air Pressure,

Pa

Calculated Flow Rate,

L/(s·m2)

Calculated Air Permeance,

L/(Pa·m2·s)

25 0.0001 0.000004

50 0.0002 0.000004

75 0.0004 0.000005

100 0.0005 0.000005

150 0.0008 0.000006

300 0.0019 0.000006

Architectural Testing

Page 4: Therma cote air barrier test final report  astm e 2178

B0780.01-106-31

Page 3 of 4

Test Procedure and Test Results: (Continued)

Dens-glass (One Specimen)

Air Pressure,

Pa

Calculated Flow Rate,

L/(s·m2)

Calculated Air Permeance,

L/(Pa·m2·s)

25 0.0027 0.000106

50 0.0055 0.000111

75 0.0085 0.000114

100 0.0116 0.000116

150 0.0179 0.000119

300 0.0374 0.000125

Data sheets, representative samples of test specimens, a copy of this report, or other pertinent

project documentation will be retained by Architectural Testing, Inc. for a period of four years

from the original test date. At the end of this retention period such materials shall be discarded

without notice and the service life of this report by Architectural Testing will expire. Results

obtained are tested values and were secured by using the designed test methods. This report does

not constitute certification of this product nor an opinion or endorsement by this laboratory. It is

the exclusive property of the client so named herein and relates only to the specimens tested.

This report may not be reproduced, except in full, without the written approval of Architectural

Testing, Inc.

For ARCHITECTURAL TESTING, INC.:

Dawn M. Chaney - Senior Technician Gary Hartman, P.E. - Director

Components / Materials Testing Components / Materials Testing

DMC:dmc/nlb

Attachments (pages) This report is complete only when all attachments listed are included.

Appendix A - Photographs (1)

Appendix B - ASTM E 2178 Test Specimen Actual Pressure and Flow Values (3)

Appendix C - ASTM E 2178 Air Permeance Graph (1)

Architectural Testing

Page 5: Therma cote air barrier test final report  astm e 2178

B0780.01-106-31

Page 4 of 4

Revision Log

Rev. # Date Page(s) Revision(s)

0 08/08/11 N/A Original report issue.

This report produced from controlled document template ATI 00231, revised 03/06/07.

Architectural Testing

Page 6: Therma cote air barrier test final report  astm e 2178

B0780.01-106-31

APPENDIX A

Photographs

Architectural Testing

Page 7: Therma cote air barrier test final report  astm e 2178

B0780.01-106-31

Photo No. 1

ASTM E 2178 Air Permeance

Tare in Progress

Photo No. 2

ASTM E 2178 Air Permeance

Test Specimen Testing in Progress

Architectural Testing

Page 8: Therma cote air barrier test final report  astm e 2178

B0780.01-106-31

APPENDIX B

ASTM E 2178 Test Specimen Actual Pressure and Flow Values

Architectural Testing

Page 9: Therma cote air barrier test final report  astm e 2178

B0780.01-106-31

Test Specimen 1 - ThermaCote® Air Barrier Coated Dens-glass

Date/Time Target Pressure,

Pa

Actual Pressure,

Pa

Actual Flow,

L/s

Tare (Leakage)

07/12/2011 10:45 25 24.92455 0.00029

07/12/2011 10:56 50 50.10990 0.00062

07/12/2011 11:11 75 75.16397 0.00071

07/12/2011 11:19 100 99.88657 0.00114

07/12/2011 11:26 150 150.24756 0.00157

07/12/2011 11:32 300 300.77225 0.00306

Test

07/12/2011 12:00 25 25.00184 0.00040

07/12/2011 12:08 50 50.22964 0.00086

07/12/2011 12:15 75 75.19346 0.00135

07/12/2011 12:20 100 99.80757 0.00170

07/12/2011 12:26 150 150.19123 0.00241

07/12/2011 12:31 300 300.83413 0.00513

Test Specimen 2 - ThermaCote® Air Barrier Coated Dens-glass

Date/Time Target Pressure,

Pa

Actual Pressure,

Pa

Actual Flow,

L/s

Tare (Leakage)

07/14/2011 16:29 25 24.95045 0.00052

07/14/2011 16:41 50 50.09985 0.00081

07/14/2011 16:53 75 75.32018 0.00104

07/14/2011 17:00 100 100.31703 0.00140

07/14/2011 17:07 150 150.33978 0.00208

07/14/2011 17:13 300 300.94031 0.00446

Test

07/14/2011 17:43 25 24.89140 0.00071

07/14/2011 17:56 50 50.21873 0.00087

07/14/2011 18:08 75 75.31141 0.00150

07/14/2011 18:15 100 99.66525 0.00230

07/14/2011 18:20 150 150.20947 0.00357

07/14/2011 18:25 300 301.25547 0.00687

Architectural Testing

Page 10: Therma cote air barrier test final report  astm e 2178

B0780.01-106-31

Test Specimen 3 - ThermaCote® Air Barrier Coated Dens-glass

Date/Time Target Pressure,

Pa

Actual Pressure,

Pa

Actual Flow,

L/s

Tare (Leakage)

07/13/2011 15:20 25 24.96613 0.00059

07/13/2011 16:30 50 50.11638 0.00099

07/13/2011 16:37 75 74.69483 0.00180

07/13/2011 16:44 100 100.08071 0.00239

07/13/2011 16:54 150 150.10729 0.00276

07/13/2011 17:00 300 300.66027 0.00559

Test

07/13/2011 17:27 25 24.87580 0.00079

07/13/2011 17:40 50 50.23313 0.00122

07/13/2011 17:48 75 75.08199 0.00200

07/13/2011 17:55 100 99.89595 0.00270

07/13/2011 18:00 150 150.29750 0.00412

07/13/2011 18:06 300 301.06125 0.00840

Test Specimen 4 - ThermaCote® Air Barrier Coated Dens-glass

Date/Time Target Pressure,

Pa

Actual Pressure,

Pa

Actual Flow,

L/s

Tare (Leakage)

07/14/2011 9:32 25 25.08723 0.00049

07/14/2011 9:41 50 49.95190 0.00098

07/14/2011 9:56 75 75.15843 0.00109

07/14/2011 10:06 100 99.70693 0.00157

07/14/2011 10:13 150 150.10712 0.00220

07/14/2011 10:19 300 300.11211 0.00428

Test

07/14/2011 10:42 25 24.93511 0.00054

07/14/2011 10:58 50 50.17297 0.00115

07/14/2011 11:06 75 75.34601 0.00151

07/14/2011 11:11 100 100.23488 0.00195

07/14/2011 11:18 150 150.30560 0.00283

07/14/2011 11:23 300 299.90749 0.00620

Architectural Testing

Page 11: Therma cote air barrier test final report  astm e 2178

B0780.01-106-31

Test Specimen 5 - ThermaCote® Air Barrier Coated Dens-glass

Date/Time Target Pressure,

Pa

Actual Pressure,

Pa

Actual Flow,

L/s

Tare (Leakage)

07/14/2011 13:42 25 24.94185 0.00031

07/14/2011 13:49 50 50.11502 0.00083

07/14/2011 13:56 75 75.35206 0.00134

07/14/2011 14:01 100 100.05182 0.00178

07/14/2011 14:08 150 150.16388 0.00233

07/14/2011 14:13 300 300.96597 0.00468

Test

07/14/2011 14:35 25 24.96247 0.00049

07/14/2011 14:41 50 50.09218 0.00109

07/14/2011 14:48 75 74.70821 0.00147

07/14/2011 14:55 100 99.88947 0.00204

07/14/2011 15:02 150 149.43003 0.00339

07/14/2011 15:07 300 301.07761 0.00638

Dens-glass

Date/Time Target Pressure,

Pa

Actual Pressure,

Pa

Actual Flow,

L/s

Tare (Leakage)

07/11/2011 10:47 25 25.02477 0.00029

07/11/2011 10:55 50 50.18558 0.00065

07/11/2011 11:03 75 74.96898 0.00129

07/11/2011 11:09 100 100.15596 0.00168

07/11/2011 11:14 150 150.48943 0.00243

07/11/2011 11:20 300 300.61331 0.00512

Test

07/11/2011 11:33 25 25.30250 0.00290

07/11/2011 11:45 50 50.11604 0.00654

07/11/2011 11:54 75 74.72474 0.00962

07/11/2011 12:03 100 99.71980 0.01285

07/11/2011 12:18 150 150.28932 0.02123

07/11/2011 12:25 300 299.80326 0.04159

Architectural Testing

Page 12: Therma cote air barrier test final report  astm e 2178

B0780.01-106-31

APPENDIX C

ASTM E 2178 Air Permeance Graph

Architectural Testing

Page 13: Therma cote air barrier test final report  astm e 2178

0 50 100 150 200 250 300 350

Target Pressure (pa)

0

0.5

1

1.5

2

2.5

3

Flo

w R

ate

(L/s

), *0

.001

Sample #338 Measured Rate

Sample #341 Measured Rate

Sample #342 Measured Rate

Sample #343 Measured Rate

Sample #344 Measured Rate

Calculated Flow Rate

Air Permeance Test Results

Product Name: ThermaCote Air Barrier

Product Type: Air Barrier

Description:

Test Start: 7/12/2011 10:45:56 AM

Test Complete: 7/14/2011 6:56:19 PMWeight:

Thickness:

Sample Area (m2): 1

TargetPressure

(pa)

% DifferenceMeasured To

Calculated(Min-Max)

MaxMeasuredFlow Rate

(L/s)

Calculated AirPermeance(L/Pa-m2-s)

MinMeasuredFlow Rate

(L/s)

CalculatedFlow Rate

(L/s)

0.0000040.000125.00 0.0001 0.0002 +106.19%-48.45%

0.0000040.000250.00 0.0001 0.0003 +16.12%-73.20%

0.0000050.000475.00 0.0001 0.0006 +75.22%-64.41%

0.0000050.0005100.00 0.0003 0.0009 +74.13%-49.70%

0.0000060.0008150.00 0.0006 0.0015 +76.72%-25.28%

0.0000060.0019300.00 0.0017 0.0028 +44.38%-12.65%

Q = CA(DP)n

Q = 0.0000020*1.00(DP)1.2068778

r2 = 0.7838328

Printed: July 15, 2011 8:05AM Architectural Testing Page: 1 of 3

Page 14: Therma cote air barrier test final report  astm e 2178

B0780.01-106-31

Error Analysis: In compliance with Section 9.4 an error analysis shall be performed that includes an examination

of the sources of error, an evaluation of systematic errors and propagation of error, and the resulting value of error

on air flow values through the material tested. Regression analysis yielded a lower correlation than the method

allows. The primary contributing factor is believed to be the test specimens themselves. The substrate and the

coating application method may result in samples which are non-homogenous.

Archi tectura l Test ing