tip sheet on hvac system-2.0 march 2011(public)

Upload: ar-hussain-mojahid

Post on 06-Jul-2018

219 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/17/2019 Tip Sheet on HVAC System-2.0 March 2011(Public)

    1/12

    Heating, Ventilation and Air Conditioning (HVAC) accounts for a significant portion of a commercial building’s energy use and represents an opportunity for

    considerable energy savings. Tis ip Sheet acts as a primer on energy efficient

    HVAC systems and proven technologies and design concepts which can be used to

    comply with the HVAC provisions in Energy Conservation Building Code.

    ENERGY CONSERVATION

    BUILDING CODE TIP SHEET

    HVAC SYSTEM

    Version 2.0 — March, 2011

    Credits:

    E Source Technology Atlas

    US DOE’s Building Technologies Program

     Alliance to Save Energy 

    USAID ECO-III Project

    International Resources Group

    Phone: +91-11-4597 4597

    Fax: +91-11-2685 3114

    Email: [email protected]

    Keeping buildings cool

    in  hot climates has always  been a human concern. For

    millennia, people ingeniously applied anastonishing array of design features totheir shelters to avoid or reject unwantedheat. Windscoops, vents, cool towers,atria, shading, orientation, whitewash,night radiation – the whole panoply ofmodern passive techniques was inventedat least three thousand to ve thousandyears ago and developed to an impressivelevel of maturity. However, the inventionof refrigerative chiller by Willlis HavilandCarrier in 1902 changed the world and led

    to the abandoning of ancient and climateresponsive building architecture, as itcould cool any sort of boxy and sealedbuilding space and technically take care ofadverse hot climatic condit ions. From 1945onwards, refrigerative air-conditioningbecame the norm to maintain buildings ina narrow temperature range, irrespectiveof weather conditions.

     As the Cl imate Map of Ind ia (ECBC,2007) shows, most of India falls mainlyunder three climatic zones (hot-dry,

     warm-humid and composite) requir ing

    cooling of buildings for almost 6-8months to provide thermal comfort tothe occupants. All of this comes withsignicant energy consumption and

    costs. Both need to be addressed whiledesigning any building.

    HVAC systems have a signicant effect

    on the health, comfort, and productivityof occupants. Issues like user discomfort,improper ventilation, and poor indoor airqual ity are linked to HVAC system designand operation and can be improvedsignicantly by better system design.

     Thermodynamic processes takeplace between the human body andthe surrounding thermal environment.Our perception of thermal comfortand acceptance of indoor thermalenvironment is a result of the heat

    generated by metabolic processes and the

    adjustments that the human body makesto achieve a thermal balance betweenitself and the environment. Six factors

    that inuence the heat transfer betweenthe human body and the surroundingenvironment are shown in Table 1.

    Good HVAC design considers allthe inter-related building systems whilemanaging indoor air quality, energyconsumption, and thermal comfort.Optimizing the design requires that theHVAC designer and the architect addressthese issues early in the schematicdesign phase and continually improvesubsequent decisions throughout the

    design development process.

    Table 1: Thermal Comfort Parameters

    Parameters Significance

     Air Temperature Most important parameter for determining thermal comfort

    Mean Radiant Temperature

    Key factor in the perception of thermal discomfort resulting fromradiant asymmetry

    Relative Humidity Excessive dry or humid conditions are immediately perceived asuncomfortable

     Air Velocity Key factor in the perception of draft due to elevated air velocity

     Activity Level Poses a problem to designers if an indoor space has to be designed forpeople with different activity levels

    Clothing Resistance Important factor in the perception of thermal comfort; use of clothingto adjust to thermal environment is a good example of adaptive control.

    Source: Fanger, 1970 

      E  n  v  i  r  o  n  m  e  n  t  a  l

      P  e  r  s  o

      n  a  l

    Version 2.0 — March 20111

    ECBC TIP SHEET > HVAC System

  • 8/17/2019 Tip Sheet on HVAC System-2.0 March 2011(Public)

    2/12

    load operation penalties), large heatexchangers, low-friction duct layoutand sizing, low pressure drops in air-handling and piping components,and overall optimizat ion of the entireHVAC system can facil itate in mak ingthe system more efcient.

    6. Optimize the delivery system: Hugesavings are available from reducingthe velocity, pressure, and frictionlosses in ducts and piping. Theseimprovements can be captured withhigh-efciency fans, diffusers, andother components.

    7. Improve controls: Controls with betteralgorithms, sensors, signal delivery,user interface, simulators, and othermeasures can be applied to optimizeHVAC operation.

    8. Determining loads:  Projected loadfor new buildings can be analyzedaccurately by using ComputerSimulation. Hourly simulation modelsdesigned for energy analysis, calculatehourly cooling loads from detailedbuilding geometry, scheduling, andequipment data. Using actual weatherdata, it is possible to match a bui lding’senergy usage with actual utility billingdata. Computer Simulation can

    provide the best understanding of howa building will operate under differentscenarios from a combination ofdetailed end-use hourly simulation.

    3. Expand the comfort envelopewith reduced radiant heat load,increased air flow, less insulated furniture, more casual dress whereappropriate: These opportunities areless understood and deployed but havethe potential to save cooling loads. Inan indoor environment with xed air

    temperature, relative humidity, airspeed, and activity, an ofce workerin cotton trousers and half shirt (withan insulating value of 0.5 clo) will becomfortable at almost 3°C warmerthan the same person in a heavy two-piece business suit and accessories(with an insulating value of 1.0 clo).

     A 3°C increase in ins ide temperaturecan save signicant amount of energy.

    4. Apply non-vapor compressioncooling techniques:  They typicallyuse 20-30% as much energy per unitof cooling as conventional coolingequipment and can serve much orall of the load that remains after thebasic cooling load is reduced. Thesealternatives include natural ventilation

     with cool outside air, ground coupledcooling, night sky cooling, evaporativecooling, absorption cooling, anddesiccant systems fueled by naturalgas, waste heat, or solar energy (SeeBox 1).

    5. Serve the remaining load with high-efficiency refrigerative cooling: Moreefcient chillers, pumps, and fans,multiplexed chil lers (to minimize part-

     At times issue comes why shou ldbuildi ng developers and financiers carefor efficiency considerations, since theymay sell the building to someone elseor, if they retain ownership, pass alongthe operating costs to tenants. Reducingelectricity consumption through a highqualit y and high efficiency design could

    enhance the value of the building andits rent. Whichever developer firstcaptures the efficiency opportunity,therefore, can have a major competitiveadvantage.

     This outl ines an integrated strategytargeted for large buildings with a wholebuilding approach.

    Whole Building Approach

    1. Reduce cooling load by controllingunwanted heat gain:  As shownin Fig. 1, external heat gains can beavoided with architectural form, l ight-colored bui lding surfaces, vegetation,high performance windows, etc.Internal heat gains can be reducedby using more efcient buildingequipment (such as lights, computers,printers, copiers, servers, etc.), anddirect venting of spot heat sources.Load reduction not only saves energy,it allows HVAC equipment to besmaller, resulting in rst-cost savings.

     2. System interactions:  Cooling loadreduction should be approached inconcert with whole-building loadreduction measures for both coolingand heating systems. The objectivesof saving cooling and heating energymay be in conict or may supporteach other. For example, betterinsulation and efcient windows canreduce both loads while lighting loadreductions may increase heating loads.

    High-performance windows may bethe last step needed in eliminatingpart or all of the perimeter HVACequipment, while providing superiorradiant comfort in both summer and

     winter. To take advantage of load

     variat ions, it is critical that bui ldingHVAC systems be capable of reactingto the reduced loads. This requires

     variable capacity pumps and fans(or variable capacity compressor andcondenser units in case of packaged

    or split-systems) and reliable sensorsand controls to allow the equipmentto power down when loads drop. Fig. 1: Cooling Load Reduction Measures

    (Source: E Source Cooling Atlas)

    Window films reduce solar gain without

    sacrificing daylight or esthetics

    Plan for smaller cooling equipment and

    modified air handlers once internal and

    external load reduction measures are in place.

     Thermostats and controls should accommodate

    load reduction.

    Green roofs help in lowering the Roof

     Temperature

     Trees block solar radiation and provide

    cooling benefit through

    evapotranspiration

    Automatic louvers, fixed louvers, andsolar screens block solar radiation

    Movable awnings provide

    shade

    South

    Insulating the roof helps

    decrease heat conduction to the

    inside of the building

    Structural overhangs,

    lightshelves reduce solar

    gain

    Light-colored roof coatings reflect

    solar radiation and reduce

    conduction potential

    Spectrally selective

    glazings let light in

    but keep heat out

    Version 2.0 — March 2011 2ECBC TIP SHEET > HVAC System

  • 8/17/2019 Tip Sheet on HVAC System-2.0 March 2011(Public)

    3/12

    Evaporative Cooling

    E vaporat ive cool ing is an ancient ai rconditioning technique that is growing

    in popularity due to increased interest in

    energy efficiency, reduced peak demand,

    improved indoor air quality, and non-

    CFC cooling. Evaporative coolingtypically uses less than one-fourth

    the energy of vapor-compression air-

    conditioning systems, while using no

    more water than a power plant uses to

    produce the electricity needed for the

    same amount of vapor-compression

    cooling. The cost of an evaporative

    cooling system may be higher than a

     vapor compress ion chil ler system, but

    payback is typically 1-5 years depending

    on climate.

     The most common ty pe of di rect

    evaporative cooler uses a cellulose fiber

    pad, permeable to both water and air,

     which has water pumped into its top edge.

     As the ai r passes through the wetted

    pad, water evaporates, taking heat from

    the air, and the air cools adiabatically to

    balance the heat it has lost to evaporation.

    Indirect evaporative coolers (See

    Fig. 2) eliminate the problem of

    increasing the moisture content of the

    air that enters the conditioned space

    by using a heat exchanger. In an air-to-

    air heat exchanger system, secondary(exhaust) air flows through one side of

    the heat exchanger where it is sprayed

     with water and cooled by evaporat ion.

     The bui lding supply ai r f lows through the

    other side of the heat exchanger where

    it is sensibly cooled by the evaporative

    cooled secondary air. Because of the heat

    exchanger, the effectiveness of indirect

    evaporative cooling is reduced to about

    65-75 %, but it has wider applicability to

    climates where increased air humidity is

    unwelcome.

    Desiccant Heat Recovery

    Properties of desiccants materials to readily

    attract water and thus dehumidify air can

    be used in HVAC applications to reduce

    cooling loads, improve chiller efciency,

    and widen the applicability of evaporative

    cooling, while providing improved indoorair quality and eliminating the use of

    CFC refrigerants. In combination with

    evaporative cooling, desiccant cooling can

    eliminate refrigerative air conditioning in

    many climates.

     A conventional cooling system

    dehumidies bypassing the supply air across

    a cooling coil that is cold enough to condense

     water vapor. This dehumidication requires

    a colder coil than would be required for

    sensible cooling alone, often doubling energy

    requirements at typical low-load conditions

     where it is necessary to dehumidify but not

    cool. Often in these conditions, the air is

    cooled for dehumidication and then must

    be reheated for comfortable supply. With

    desiccants, dehumidication takes place

    independently of sensible cooling. In large

    buildings, desiccants can reduce HVAC

    electricity use by 30-60 %. Fig. 3 shows

    how the desiccant wheel alternately passes

    through two separate airstreams; one to be

    dehumidied and used in the building, and

    one to regenerate the desiccant with warm,

    dry air.

    Ground Source Heat Pump:

     Water-loop heat pump (WLHP) systems

    have captured a small (3 to 4%) but slowly

    growing percentage of the U.S. commercial

    cooling market and have good potential in

    India as well.

    Ground coupled systems provide

    passive heating and cooling by using the

    ground as a heat source or a heat sink.

     There are two basic variet ies.

    • Groundwater-source heat pumps

    (GWHPs) draw water from wells, lakes,

    or other reservoirs of groundwater, passthe water through an open loop, and

    discharge it back to the environment.

    • Ground-source closed-loop heat pumps

    (GSHPs)  system use a pump and

    ground-coupled heat exchanger to

    provide a heat source and heat sink for

    multiple GSHPs within the building.

    Absorption CoolingOn the surface, the idea of using an

    open ame or steam to generate cooling

    might appear contradictory, but the

    idea is actually very elegant. Instead of

    mechanically compressing a gas (as occurs

     with a vapor-compression refrigeration

    cycle), absorption cooling relies on a

    thermochemical “compressor.” Absorption

    cooling is more common today than most

    people realize. Large, high-efciency,

    double-effect absorption chillers using

     water as the refrigerant dominate the

     Japanese commercial air-conditioning

    market. While less common in India,

    interest in absorption cooling is growing,

    largely as a result of high electricity tariffs

    and growing availability of natural gas on a

    commercial basis.

     Absorption cool ing is most frequent ly

    used to air-condition large commercial

    buildings. Absorption cooling equipment

    on the market ranges in capacity from

    less than 10 tons to over 1,500 tons (35 to

    5,300 kW). Coefcients of performance

    range from about 0.7 to 1.2, and electricityuse ranges from 0.004 to 0.04 kW/ton of

    cooling. Absorption chillers may make

    sense in the following situations:

    • Electric demand charges are high

    • Electricity use rates are high

    • Natural gas prices are favorable

    • Utility and manufacturer rebates exist

     The potential of absorption cool ing

    systems to use waste heat can greatly

    improve their economics. Indirect-

    red chillers use steam or hot water astheir primary energy source, and they

    lend themselves to integration with on-

    site power generation or heat recovery

    from incinerators, industrial furnaces, or

    manufacturing equipment. Indirect-red,

    double-effect absorption chillers require

    steam at around 190°C and 900 kPa, while

    the less efcient (but also less expensive)

    single-effect chillers require hot water or

    steam at only 75-132 °C. High-efciency,

    double-effect absorption chillers are more

    expensive than electric-driven chillers.

     They requ ire larger heat exchangersbecause of higher heat rejection loads; this

    translates directly into h igher costs.

    Non Refrigerative Technological Options in HVAC System

    Conditioned airHeat Exchanger

    Supply Fan

    Secondary

    air Fan

    Secondary Air 

    Wetted pad of other direct

    evaporating media

    Pump Reservoir

    Outdoor Air

    Fig. 2: Indirect Evaporative Cooler

    (Source: E Source Cooling Atlas)

    Heater

     To Out side

    Outside Air

    Desiccant WheelDehumidified

    Supply Air

    Partition separates heated

    exhaust air from supply air

    Fig. 3: Solid Desiccant Wheels

    (Source: E Source Cooling Atlas)

    Box 1

    Version 2.0 — March 2011 3ECBC TIP SHEET > HVAC System

  • 8/17/2019 Tip Sheet on HVAC System-2.0 March 2011(Public)

    4/12

     Air System Balancing: Adjusting airowrates through air distribution systemdevices, such as fans and diffusers,by manually adjusting the position ofdampers, splitter vanes, extractors, etc.,or by using automatic control devices,

    such as constant air volume or variable air volume boxes.

    Boiler:  A self-contained low-pressureappliance for supplying steam or hot

     water. A packaged boiler includes factory-built boilers manufactured as a unit orsystem, disassembled for shipment, andreassembled at the site.

    Coefficient Of Performance (COP) –Cooling:  the ratio of the rate of heatremoval to the rate of energy input,in consistent units, for a completerefrigerating system or some specicportion of that system under designatedoperating conditions

    Coefficient Of Performance (COP) –Heating:  the ratio of the rate of heatdelivered to the rate of energy input,in consistent units, for a complete heatpump system, including the compressorand, if applicable, auxiliary heat, underdesignated operating conditions

    Constant Volume System:  A space-conditioning system that delivers a xedamount of air to each space. The volume ofair is set during the system commissioning.

    Economizer, Water-side:  A system by which the supply air of a cooling systemis cooled indirectly with water that is itselfcooled by heat or mass transfer to theenvironment with the use of mechanicalcooling.

    Economizer, Air-side: A duct and damperarrangement and automatic control systemthat together allow a cooling system tosupply outdoor air to reduce the need formechanical cooling during mild or cold

     weather.

    Energy Efficiency Ratio (EER): Performanceof room ACs smaller chillers and rooftopunits is frequently measured in EERrather than kW/ton. EER is calculatedby dividing a chil ler’s cooling capacity (in

    Btu/h) by its power input (in watts) at full-load conditions. The higher the EER, themore efcient the unit.

    Heat Pump:  A heat pump consists ofone or more factory-made assemblies thatnormally include indoor conditioning coil,compressor, and outdoor coil, includingmeans to provide a heating function. Heatpumps provide the funct ion of air heating

     with controlled temperature, and mayinclude the functions of air cooling, aircirculation, air cleaning, dehumidifying,or humidifying.

    Hydronic System Balancing:  Adjusting water ow rates through hydronicdistribution system devices, such aspumps and coils, by manually adjustingthe position of valves, or by usingautomatic control devices, such as owcontrol valves.

    kW/ton Rating:  Commonly referred toas efciency, but actually power inputto compressor motor divided by tons ofcooling produced, or kilowatts per ton(kW/ton). Lower kW/ton indicates higherefciency.

    Integrated Part-Load Value (IPLV): This metric attempts to capture a morerepresentative “average” chiller efciencyover a representative operating range. Itis the efciency of the chiller, measured

    in kW/ton, averaged over four operatingpoints, according to a standard formula.

    Outdoor Air : Air taken from outdoorsand not previously circulated in thebuilding. For the purposes of ventilation,outdoor air is used to ush out pollutantsproduced by the building materials,occupants and processes.

    Part-Load Performance:  For Waterchill ing packages covered by this standard,

    the IPLV shall be calculated as follows:Determine the part-load points. Usethe following equation to calculate theIPLV.

    IPLV = 0.01A + 0.42B + 0.45C + 0.12D

    For COP and EER:

     Where: A=COP or EER at 100%

      B=COP or EER at 75%  C=COP or EER at 50%  D=COP or EER at 25%

    For kW/ton:

    IPLV:

    0.01 0.42 0.45 0.12 A B C D

    + + +

    1

     Where:  A=kW/ton at 100%  B=kW/ton at 75%  C=kW/ton at 50%  D=kW/ton at 25%

     The weighting factors have been basedon the weighted average of the mostcommon building types and operationusing average weather in 29 U.S. cities,

     with and without air side economizers.

    Return Air:  Air from the conditionedarea that is returned to the conditioningequipment for reconditioning. The airmay return to the system through a seriesof ducts, plenums, and airshafts.

    Seasonal Energy Efficiency Ratio(SEER): SEER is a measure of equipmentenergy efciency over the cooling season.It represents the total cooling of a centralair-conditioner or heat pump (in kWh)during the normal cooling season ascompared to the total electric energyinput consumed during the same period.

    Supply Air:  Air being conveyed toa conditioned area through ducts orplenums from a heat exchanger ofa heating, cooling, absorption, or

    evaporative cooling system. Supply airis commonly considered air delivered toa space by a space-conditioning system.Depending on space requirements, thesupply may be either heated, cooled orneutral.

    Tons: One ton of cooling is the amountof heat absorbed by one ton of ice meltingin one day, which is equivalent to 12,000Btu/h or 3.516 thermal kW.

    Variable Air Volume (VAV) System: Aspace conditioning system that mainta inscomfort levels by varying the volumeof conditioned air. This system deliversconditioned air to one or more zones. Theduct serving each zone is provided with amotorized damper that is modulated by asignal from the zone thermostat.

     Zone: A space or group of spaces withina building with heating and coolingrequirements that are sufcientlysimilar so that desired conditions

    (e.g., temperature) can be maintainedthroughout using a single sensor (e.g.,thermostat or temperature sensor).

    Key Technical Terms

    Version 2.0 — March 2011 4ECBC TIP SHEET > HVAC System

  • 8/17/2019 Tip Sheet on HVAC System-2.0 March 2011(Public)

    5/12

    Air-Conditioner Basics

    Basic components of the system includean evaporator, compressor, condenser(air-cooled or water cooled), and anexpansion device, similar to that ofa domestic refrigerator. A refrigerantcirculates in these components (Fig. 4).It vaporizes in the evaporator absorbing

    the heat from the warm room air drawnacross the evaporator coil. This cools anddehumidies the air. The compressorraises the pressure and temperature ofthe refrigerant vapors. The condensercondenses the refrigerant and transformsthe high pressure vapor into highpressure liquid. Heat is rejected viaoutside air drawn across the condenser.

     The expansion device transformsthe high pressure high temperatureliquid refrigerant to low pressure lowtemperature mixture of refrigerantliquid and vapor. The refrigerant goesto the evaporator, and the cooling cyclecontinues.

    Types of Air-Conditioners

     The most common types of air-conditioners are room air-conditioners,packaged air-conditioners, and centralair-conditioners. Fig. 5 shows marketshare of different types of vaporcompression HVAC systems (residentialand commercial) in India.

    Unitary and split air-conditioners:  These air-conditioners cool rooms ratherthan the building. They provide coolingonly when needed. These air-conditionersare less expensive to operate than centralunits, even though their efciency isgenerally lower than that of central air-conditioners.

    In a split-system air-conditioner,an outdoor metal cabinet contains the

    condenser and compressor, and an indoorcabinet contains the evaporator. In manysplit-system ai r-conditioners, this indoorcabinet also contains an electr ic heater orthe indoor part of a heat pump.

    Packaged air-conditioners:  In apackaged air-conditioner, the evaporator,

    condenser, and compressor are all locatedin one cabinet, which usually is placed ona roof or on a concrete slab adjacent tothe building. This type of air-conditioneris typical in small commercial buildingsand also in residential buildings. Airsupply and return ducts come fromindoors through the building’s exterior

     wal l or roof to connect with the packagedair-conditioner, which is usually locatedoutdoors. Packaged air-conditionersoften include electric heating coils or anatural gas furnace. This combinationof air-conditioner and central heatereliminates the need for a separate furnaceindoors.

    Central air-conditioners:  In central air-conditioning systems, cooling is generatedin a chiller and distributed to air-handlingunits or fan-coil units with a chi lled watersystem. This category includes systems

     with air-cooled chil lers as wel l as systems with cooling towers for heat rejection (SeeBox 2).

    Heating Systems Types

    Heating systems can be classied fairly well by the heating equipment type. Theheating equipment used in commercial

    buildings include boilers (oil and gas),furnaces (oil, gas, and electric), heatpumps, and space heaters.

    Boiler-based heating systems havesteam and/or water piping to distributeheat. The heated water may serve preheatcoils in air handling units, reheat coils,and local radiators. Systems that circulate

     water or a uid are cal led hydron icsystems. Additional uses are for heatingof service water and other process needs,depending on the building type. Somecentral systems have steam boilers ratherthan hot water boilers because of theneed for steam for conditioning needs(humidiers in air-handling units) orprocess needs (sterilizers in hospitals,direct-injection heating in laundries anddishwashers, etc.).

     The remaining heat ing systems heatthe space directly and require litt le or nodistribution. These include heat pumpsand space heaters.

    ECBC Requirements

     The Energy Conservation Bui ldingCode (ECBC) covers several prescriptiverequirements for HVAC systems includingrequirements for economizer, duct andpipe insulation, controls optimization,and system balancing.

    Equipment Efficiency

    HVAC equipment are required to meet orexceed minimum efciency requirementsmentioned in ECBC 5.2.2. Powerconsumption ratings for unitary air

    conditioners, split systems and packagedair conditioners are referred to BIS codes(See Table 2, 3 and 4). Cooling systemsnot included are referred to ASHRAE90.1 – 2004. Single zone unitary systemsare covered as well as multiple zone airand water systems. The more complex thesystem, the more requirements apply tothat system: a single-zone unitary systemhas fewer requirements than a complexsystem made up of chillers, boilers, andfan coil units.

    For natural ventilation requirements,

    buildings are required to follow thedesign guidelines provided for natural

     ventilation in the National Bui ldingCode of India, 2005 [ECBC 5.2.1].

    Discharge Line

    Compressor

    Suction Line

    Evaporator

    Condenser

    Expansion DeviceLiquid Line

    A

    B

    C

    D

    Rejected Hot Air

    (Outside)

    Ambient Air

    (Refrigerant Vapour)

    (Refrigerant Vapour)

    Refrigerant

    Warm Room Air

    Cooled Air

    Fig. 4: Air Conditioner Basics

    Fig. 5: Market Share of Different Types

    of AC Units in India

    (Source: 2007 Sales Data fom EmersonClimate Technology)

    Water

    Chiller11%

    VRF Chiller 1%

    Room AC

    69%

    Ducted/

    Package

    AC 19%

    Version 2.0 — March 2011 5ECBC TIP SHEET > HVAC System

  • 8/17/2019 Tip Sheet on HVAC System-2.0 March 2011(Public)

    6/12

    1. Plan ahead:  It makes sense to startplanning early to al low sufcient time to

    evaluate various scenarios and to identifya comprehensive system approach which

    best meets budgetary and facility needs.

     2. Buy only as much chiller as you need: Reduce building loads and improve air-

    side distribution before sizing the chiller.

    Buying more cooling than you need not

    only costs money for equipment, it also

    increases monthly utility bills.

    3. Use computer simulations to model thebuilding throughout the year: Designs

    should include chillers that operate mostefciently under part-load conditions that

    most chillers spend most of their time

    satisfying (typically 40 to 70% load).

    4.  Maximize system efficiency:  Coolingtower fans and condenser and chilled water pumps should be considered

    along with chiller energy consumption.

    Chiller efciency increases with higher-

    temperature chilled water and lower-

    temperature condenser water (called

    lower “lift”).

    5. Select unequally sized machines formultiple chiller installations:  Select

    one machine small enough to meet light

    loads efciently and the others to meet

    larger loads efciently. Start additionalchillers only when the chillers that

    already are running are near full capacity.

    6. Obtain competitive bids:  There areoften good reasons to stay with the same

    brand of chiller—maintenance, otherequipment in the facility, existing service

    relationships, etc. However, for such a

    major purchase it makes sense to obtain

    bids from more than one manufacturer.

     All manufacturers have “sweet spots”— 

    sizes at which their equipment is most

    efcient.

    7.  Monitor the system on an ongoingbasis:  Monitor compressor power and

    cooling load to determine whether or

     when attention wil l be needed, and to

    allow optimal system operation.

    Top Issues to Consider When Buying a Chiller Box 3

    Overview

     A chiller is essentially a packaged vaporcompression cooling machine. The chi llerrejects heat either to condenser water (inthe case of a water-cooled chiller) or toambient air (in the case of an air-cooled

    chiller). Fig. 6 shows the different loops ofheat transfer in a chilled water system. Atypical chi ller is rated between 15 to 1000tons (53 to 3,500 kW) in cooling power.

     Water-cooled chil lers incorporate theuse of cooling towers which improve heatrejection more efciently at the condenserthan air-cooled chillers. For a water-cooled chiller, the cooling tower rejectsheat to the environment through directheat exchange between the condenser

     water and cooling air. For an air-cooledchiller, condenser fans move air through

    a condenser coil. As heat loads increase, water-cooled chillers are more energyefcient than air-cooled chillers.

    Type of Chillers

    Chillers are classied according to

    compressor type. Electric chillers forcommercial comfort cooling havecentrifugal, screw, scroll, or reciprocatingcompressors. Centrifugal and screwchillers have one or two compressors.Scroll and reciprocating chillers are built

     with mult iple, smaller compressors.

    • Centrifugal chillers are the quiet,

    efcient, and reliable workhorses of

    comfort cooling. Although centrifugal

    chillers are available as small as 70 tons,

    most are 300 tons or larger.

    • Screw chillers are up to 40% smaller and

    lighter than centrifugal chillers, so are

    becoming popular as replacement chillers.

    • Scroll compressors are rotary positive-

    displacement machines, also fairly new

    to the comfort cooling market. These

    small compressors are efcient, quiet,

    and reliable. Scroll compressors are madein sizes of 1.5 to 15 tons.

    Chiller Efficiency

    Chiller efciency is rated in kW/ton (orCOP) for larger machines and EER orCOP for smaller machines (See Fig. 7).Efciencies are measured at peak loadand at IPLVs. The concept of the “mostefcient chiller” makes sense only incontext of the facility to be cooled. If achiller operates 90% of the time at 60%load and very rarely at 90-100 % load,then the most efcient chiller for thatapplication is the one with the lowest kW/ton at 60% load, regardless of peak loadkW/ton.

    Chiller Basics

    Fig. 6: Process Diagram of a Chilled Water Air-Conditioning System

    (Source: E Source Cooling Atlas)

    Supply air fan Chilled water

    pumpCompressor

    Condenser

    pumpCooling tower

    fan

    AirWaterRefrigerantWaterAir

    Cooling coil Evaporator Condenser Cooling tower

    In this figure, thermal energy moves from left to right

    as it is extracted from the space and exp elled into the

    outdoors through five loops of heat transfer:

    • Indoor air loop. In the left most loop, indoor air is

    driven by the supply air f an through a cooling coil,

    where it transfers its heat to chilled water. The cool

    air then cools the building space.

    • Chilled water loop. Driven by the chilled water

    pump, water returns from the cooling coil to the

    chiller’s evaporator to be re-cooled.

    • Refrigerant loop. Using a phase-change refrigerant,

    the chiller’s compressor pumps heat from the

    chilled water to the condenser water.

    • Condenser water loop. Water absorbs heat from the

    chiller’s condenser, and the condenser water pump

    sends it to the cooling tower.

    • Cooling tower loop. The cooling tower’s fan drives

    air across an open flow of the hot condenser water,

    transferring the heat to the outdoors.

    Box 2

    Standard High-efficiency

    0.90

    0.800.75

    0.70 0.700.65

    0.60

    0.48

    0.8

    0.6

    0.4

    0.2

    0

    Typical chiller performance

    Chillers are getting more efficient

     Thank s to desi gn adva nces, new chi llers a re far m ore effic ient

    than their predecessors, even though CFC -free refriger ants

    are less efficient than CFC refrigerants.

    pre-1973

    Year manufactured

    1980 1990 1997

    ig. 7: Trend in Chillers Efficiency

    (Source: E Source Cooling Atlas)

       E   f     c   i  e  n  c  y  a   t

       F  u   l   l   L  o  a   d

       (   k   W   /   t  o  n   )

    Version 2.0 — March 2011 6ECBC TIP SHEET > HVAC System

  • 8/17/2019 Tip Sheet on HVAC System-2.0 March 2011(Public)

    7/12

    are often called hydronic, and steam-

    based systems are called steam systems,both of which use a piping system tocirculate water or steam.

    Forced hot air systems are morecommon than hydronic or steam heatingsystems because they cost much lessto install. However, hydronic systemsperform better than forced hot air becausethey leak less heat, are easier to insulate,make almost no noise, can be easily zonedand can provide more even temperatures.Hydronic systems also do a much better

    job of serving a radiant heating system. The energy efciency of a d istr ibutionsystem depends largely on the design andinstallation quality. Duct distributionsystems are prone to the most signicantlosses—especially if the ducts are poorlysealed and/or installed outside the“thermal envelope” of the building (inan unconditioned attic, for example).Hydronic systems are typically installed

     within condit ioned or “buffered” spaceslike an uncondit ioned basement. In eithercase, it is important to insulate ducts/

    hot water pipes that are in unconditionedspaces.

    Small commercial buildings typicallyuse constant volume rooftop HVAC units,

    Controls

    Controls determine how HVAC systemsoperate to meet the design goals of comfort,efciency, and cost-effective operation. TheECBC requires that all HVAC equipment(>28 kW cooling and/or >7 kW heatingcapacity) be controlled with a timeclockcapable of retaining programming forat least 10 hours, controlling varyingschedules. [ECBC 5.2.3]

     Al l heating and cooling systems arerequired to be temperature controlled[ECBC 5.2.3]. Each zone must be

    controlled by an individual temperaturecontroller. A temperature of dead band of 3ºC (5ºF )

    is required for equipment that suppliesboth heating and cooling. Thermostatsmust also prevent simultaneous heatingand cooling. [ECBC 5.2.3.2].

    Distribution System

    Distribution systems carry a heating orcooling medium to condition the space.

     The two most common mediums are airand water. Air-based systems are often

    “forced air” because they use a fan topush the air from the furnace or air-conditioner through the duct work to theconditioned space. Water-based systems

    and a simple duct layout for circulatingconditioned air. They are generally “un-engineered” systems and it is acknowledgedby the construction industry that rst-cost dominates construction practices.

     This leads to short cuts in construct ionpractices and/or the use of lower-gradematerials. In the case of duct work

    this shows up as sloppy connections,inexpensive leaky diffusers, and low-gradeduct tapes. With respect to the HVACequipment this leads to installations andservice techniques that produce degradedequipment performance.

     The ECBC requ ires insu lat ing ductsand pipelines to reduce energy losses inheating and cooling distribution systems.Insulation exposed to weather is requi redto be protected by aluminum sheet metal,painted canvas, or plastic cover. Cellula rfoam insulation needs to be protectedas described above, or be painted with

     water reta rdant paint .

    Duct sealing: Duct sealing applies tosupply and return duct work and to plenumsthat are formed by part of the buildingenvelope. Proper duct sealing ensures thatcorrect quantities of heated or cooled airis delivered to the space, and not be lostto unconditioned spaces or the outdoorsthrough leaks in the ducts. This may beone of the most important conservation

    features to check. A properly sealed ductsystem will increase the comfort and lowerthe energy use of the bui lding. Some areasto be sealed include:

    • Longitudinal seams are joints orientedin the direction of air ow.

    •  Transverse joints are connections of twoduct sections orientated perpendicularto airow.

    • Duct wall penetrations are openingsmade by any screw or fastener.

    • Spiral lock joints in round and at oval

    duct need not be sealed.

    Pipe insulation: To minimize heat losses,the Code requires that piping of heatingand cooling systems, (including the storagetanks,) must be insulated. The Codespecies required R-values of insulationfor heating and cooling systems based onthe operating temperature of the system.

     These are as shown in Table 5 and Table 6.

    Air System Balancing

     Air balancing is a smal l part of the building

    commissioning process. Commissioninginvolves the functional testing of allcomponents of an HVAC system toinsure proper operation. Commissioning

    Table 2: Power Consumption Rating for Packaged Air Conditioners-Under TestConditions

    Cooling Capacity Maximum Power Consumption

    in Watts

    Watts Tons of Refrigeration Water Cooled Air Cooled

    10,000 3 3,750 4,750

    17,500 5 6,000 7,000

    26,250 7.5 9,000 10,000

    35,000 10 11,500 13,500

    52,000 15 17,000 20,000

    Source: Code No.: IS 8148: 2003

    Table 3: Power Consumption Ratingsfor Unitary Air Conditioners – Under

    Test Conditions

    Rated Cooling

    Capacity

    Maximum

    Power

    (kcal/h) kW Consumption

    (kW)

    1,500 1.7 1.1

    2,250 2.6 1.43,000 3.5 1.6

    3,750 4.4 2.0

    4,500 5.2 2.4

    6,000 7.0 3.2

    7,500 8.7 4.25

    9,000 10.5 5.2

    Source: Code No.: IS 1391 (Part-1): 1992(amendment No. 2 Dec.2006)

    Table 4: Power Consumption Ratingsfor Split Air Conditioners – Under Test

    Conditions

    Rated Cooling

    Capacity

    Maximum

    Power

    (kcal/h) kW Consumption

    (kW)

    3 000 3.5 1.7

    4 500 5.2 2.6

    6 000 7.0 3.4

    7 500 8.7 4.5

    9 000 10.5 5.4

    Source: Code No.: IS 1319 (Part-2): 1992(amendment No. 2 Dec.2006)

    Version 2.0 — March 2011 7ECBC TIP SHEET > HVAC System

  • 8/17/2019 Tip Sheet on HVAC System-2.0 March 2011(Public)

    8/12

    is a systematic process of vericationand documentation—from the designphase to a minimum of one year after theconstruction—that all systems performin accordance with design documentationand intent, and in accordance with theoperational needs. The air-balancingportion of the commissioning process is

    usually done at the completion of a newconstruction project.

     Air balancing should verify damperoperation and adjust settings to deliverthe designed airow to each zone. Itis important that some balancing bedone prior to occupancy for severalreasons. Some equipment has minimum

    airow requirements across the coils toavoid compressor damage. Generallybefore project acceptance the buildingowner would like to know that comfortconditions could be maintained in thebuilding before occupancy, particularlyin the warmer and cooler months. Thisdoes not necessarily need to be a detailed

    room-by-room investigation. The totalsupply, return, and outside airowquantities should be measured for eachair handl ing system. A detailed balance isoften done before occupancy because itis much easier to do measurements whenthe building is unoccupied.

     The ECBC requires that air systems bebalanced in a manner to rst minimizethrottling losses; then for fans > 0.75kW (1.0 HP) the fan speed needs to beadjusted to meet design ow conditions.[ECBC 5.2.5.1.1]. Refer Box 4 for moreinformation on air handl ing units.

    Overview

    On an annual basis, continuously operatingair distribution fans can consume moreelectricity than chillers or boilers, whichrun only intermittently. High-efciencyair distribution systems can substantiallyreduce fan power required by an HVACsystem, resulting in dramatic energy

    savings. Because fan power increases atthe square of air speed, delivering a largemass of air at low velocity is a far moreefcient design strategy than pushingair through small ducts at high velocity.Supplying only as much air as is needed tocondition or ventilate a space through theuse of variable-air-volume systems is moreefcient than supplying a constant volumeof air at all times.

     The largest gains in efciency forair distribution systems are realized

    in the system design phase duringnew construction or major retrots.Modications to air d istribution systems

    are difcult to make in existing build ings,except during a major renovation.

    Design options for improving airdistribution efciency include:

    •  Variable-air-volume (VAV) systems•  VAV diffusers• Low-pressure-drop duct design• Low-face-velocity air handlers

    • Fan sizing and variable-frequency-drive (VFD) motors

    • Displacement ventilation systems. Air-handling systems deliver fresh

    outside air to disperse contaminantsand provide free cooling, transportheat generated or removed by space-conditioning equipment, and create airmovement in the space also being served,deliver heated or cooled air to conditionedair to conditioned spaces (See Fig. 8).Passive or natural air transport systems

    have the highest efciency, and successful,modern examples of this approach aresteadily accumulating. For buildingsthat require mechanical ventilation,innovative design approaches and amethodical examination of the entire airsystem can greatly improve efciency andeffectiveness. Air-handling efficiency: Te energyrequired to move air is:

    Energy =Efciency 

    Flow x Pressure x Duty Factor

     Al l four of these factors can bemanipulated to reduce the energyconsumption of the system.

    Flow: Air ow has a dominant effect onenergy consumption because it shows uptwice in the energy equation: as the rstterm and as a squared function in thesecond term (pressure).

     The energy required to move airthrough a ducted system increases withthe cube of the ow rate. This important

    relationship, known as the “cube law,”points to a meticulous and comprehensiveexamination of required ow as the start ofdesigning an efcient air-handling system.

    Pressure:  The pressure a fan must workagainst depends on two primary factors:the ow and duct design features such asdiameter, length, surface treatment, andimpediments such as elbows, lters, andcoils. Typical pressure losses are on the orderof 2 to 6 inches water gauge (wg); an efcient

    system operates at less than 1.5” wg.

    Duty factor:  A fan’s duty factor is thenumber of hours per year that it operates,sometimes presented as a percentage.Many large fans spin at full speedcontinuously (8,760 hours per year).Using simple or complex controls, dutyfactors can often be reduced to about3,000 hours per year or less by limitingfan operation to occupied periods.

    Efficiency: The mechanical efciency of

    the fan and its drive system, can typicallybe raised from the 40 to 60% range to themid - 80 % range.

    Most of the air in commercial buildings is

    recirculated (returned) through the space. Only

    about 10 percent is exhausted and replaced with

    outside air.

      S  u  p  p

      l  y  A  i  r   1

     0 0  %

      R e  t  u  r

      n  A  i  r   1

     0 0  %

     O u  t s  i d e

      A  i r  1

     0 %

    R  e c  i  r  c  u l  a t  e d   A i  r  

     9 0 % Exhaust Air

    10%

    Fig. 8: Air Flow and its Make Up

    (Source: E Source Cooling Atlas)

    Air Handling Unit Concepts Box 4

    Table 5: Insulation of Heating Systems

    Heating System

    Designed Operating Temperature of Piping Insulation with Minimun R-value (m2·K/W)

    60°C and above 0.74

     Above 40°C and below 60°C 0.35

    Table 6: Insulation of Cooling Systems

    Cooling SystemDesigned Operating Temperature of Piping Insulation with Minimun R-value (m2·K/W)

    Below 15°C 0.35

    Refrigerant Suction Piping

    Split System 0.35

    Version 2.0 — March 2011 8ECBC TIP SHEET > HVAC System

  • 8/17/2019 Tip Sheet on HVAC System-2.0 March 2011(Public)

    9/12

    Overview (US DOE, 2008)

    Building commissioning is a systematicprocess of ensuring that a buildingperforms in accordance with the designintent, contract documents, and theowner’s operational needs. Due to the

    sophistication of building designs and thecomplexity of building systems constructedtoday, commissioning is necessary, butnot automatically included as part of thetypical design and construction process.Commissioning is critical for ensuring thatthe design developed through the whole-building design process is successfullyconstructed and operated.

    Building commissioning includes thefollowing:

    • Systematically evaluating all piecesof equipment to ensure that they are

     working according to specications. This includes measuring temperaturesand ow rates from all HVAC devicesand calibrating all sensors to a knownstandard.

    • Reviewing the sequence of operationsto verify that the controls are providingthe correct interaction betweenequipment.

    In particular, building commissioningactivities include:

    • Engaging a commissioning authority

    and team• Documentation• Verication procedures, funct ional

    performance tests, and validation•  Training.

    Commissioning HVAC systems iseven more important in energy-efcientbuildings because equipment is less likelyto be oversized and must therefore runas intended to maintain comfort. Also,HVAC equipment in better performingbuildings may require advanced control

    strategies. Commissioning goes beyondthe traditional HVAC elements. Moreand more buildings rely on parts of theenvelope to ensure comfort.

    Commissioning includes evaluatingthe building elements to ensure thatshade management devices are in place,glazing is installed as specied, air-leakage standards have been met—theseare the static elements of the building.Commissioning can also evaluate otherclaims about the construction materialssuch as Volatile Organic Compounds

    (VOCs) emission content and durabilit y.Continuous commissioning ensures

    that the building operates as efciently

    as possible while meeting the occupants’comfort and functional needs throughoutthe life of the building. It is worth notingthat Continuous commissioning is differentfrom building operation and maintenance.

    Benets of building commissioning

    include:• Energy savings and persistence ofsavings

    • Improved thermal comfort with properenvironmental control

    • Improved indoor air quality • Improved operation and maintenance with documentation

    • Improved system function that easesbuilding turn-over from contractor toowner.

    Commissioning Cost

    Building owners are nding that theenergy, water, productiv ity, and operationalsavings resulting from commissioningoffset the cost of implementing a buildingcommissioning process. Recent studiesin the U.S. indicate that on averagethe operating costs of a commissionedbuilding range from 8 to 20% below thatof a non-commissioned building. Theone-time investment in commissioning atthe beginning of a project may result inreduced operating costs that will last the

    life of the building. The cost of commissioning is

    dependent upon many factors includinga building’s size and complexity, and

     whether the project consists of newconstruction or building renovation. Ingeneral , the cost of commissioning a newbuilding ranges from 0.5% to 1.5% of thetotal construction cost. For an existingbuilding, never before commissioned,the cost of retro-commissioning canrange from 3% to 5% of the total

    operating cost. For HVAC and ControlSystems, cost of commissioning rangesfrom 1.5 to 2.5% of mechanical systemcost.

    Testing, Adjusting, and

    Balancing (Nolfo, 2001)

     Testing, Adjusting, and Balancing (TAB)refers to the process whereby a systemor a component must rst be testedto determine its operating state, thenadjusted, and nally balanced to producethe desired results and performance in

    accordance with the design documents. The primary objective of carrying out the TAB function is to help the system to work

    properly by balancing the uid ows totheir correct proportion and in the processidentify design and installation errors, ifthey exist, to ensure the performance ofthe HVAC system. Some key issues thata rm undertaking TAB functions must

    address are listed below:

    1. Identification of a TraverseLocation:  To ensure that accuratemeasurements of airflows insideducts can be obtained. Thisinformation is then used by HVACcontrol system to regulate the flowof air and optimize system operation.

     2. Determining Outside Air Quantity: If supply and return airflow aremeasured accurately, outside airflowcould easily be determined from thefollowing Equation:  Q 

    supply  = Q 

    return +Q 

    outside

    3. Duct Leakage: A good duct traversecan also be used to determine ductleakage.

    4. Determining Pump Flow: Like measuringairflow on a fan, pump flowmeasurements can sometimes besuspect. Most TAB technicians will

    determine flow by measuring thedifferential pressure between pumpdischarge and pump suction. Byusing the manufactu rer’s pump curveand the pressure measurements, thetechnician can estimate total flow.

    5. Sizing Balancing Valves:  Abalancing device is similar to acontrol device and should be sizedaccordingly. Balancing devices shouldbe sized based on the design pressure

    difference at that part of the system.

    6. Fan and Pump Curves: Manufacturers’performance curves are graphicrepresentations of measuredperformance under laboratoryconditions. The combination ofeld measurements and associatedcalculations can be plotted on the fancurve. If accurate, careful, thoughtfulmeasurements can be taken, themeasured data usually matches thepublished data within the normal

    tolerances of the performance tests.

    Building Commissioning and System Balancing Box 5

    Version 2.0 — March 2011 9ECBC TIP SHEET > HVAC System

  • 8/17/2019 Tip Sheet on HVAC System-2.0 March 2011(Public)

    10/12

    Role of Temperature and

    Humidity

     The inuence of the indoor thermalenvironment on thermal comfort is widelyrecognized. Even in laboratory settings

     with uniform clothing and activ ity levels,

    it is not possible to satisfy more than 95%of occupants by providing a single uniformthermal environment (Fanger 1970)because thermal preferences vary amongpeople. Despite the signicant attentionplaced on thermal comfort by buildingprofessionals, dissatisfaction with indoorthermal conditions is the most commonsource of occupant complaints in ofcebuildings (Federspiel 1998).

     Air temperature and humidity alsoinuence perceptions of the quality ofindoor air and the level of complaintsabout non-specic build ing-related healthsymptoms (often called sick buildingsyndrome symptoms). Relative humiditiesbelow approximately 25% have beenassociated with complaints of dry skin,nose, throat, and eyes. At high humidities,discomfort will increase due substantiallyto an increase of skin moisture. The upperhumidity limits of ASHRAE’s thermalcomfort zone vary with temperature fromapproximately 60% RH at 26°C to 80%RH at 20°C.

    Sick Building Syndrome

     The most common health symptomsattributed by building occupants to theirindoor environments are non-specichealth symptoms that do not indicate aspecic disease, such as irr itation of eyes,nose, and skin, headache, fatigue, chesttightness, and difculty breathing. Thesesymptoms are commonly called sickbuilding syndrome symptoms. In somebuildings, the symptoms coincide with

    periods of occupancy in the building.Buildings within which occupantsexperience unusually high levels ofthese symptoms are sometimes called“sick” buildings. On average, occupantsof sealed air-conditioned buildingsreport more symptoms than occupantsof naturally ventilated buildings. Moststudies have found that lower indoorair temperatures are associated withfewer non-specic health symptoms.Symptoms have been reduced throughpractical measures such as increased

     venti lat ion, decreased temperature, andimproved cleaning of oors and chairs(Mendell 1993).

    Impact of IEQ on Health and

    Productivity

    Some characteristics of the indoorenvironment, such as temperaturesand lighting quality, may also inuence

     worker performance without impacting

    health. In many businesses, such asofce work, worker salaries plus benetsdominate total costs; therefore, very smallpercentage increases in productivity,even a fraction of one percent, are oftensufcient to justify expenditures forimprovements that increase productivity.

    In a critical review and analysis ofexisting scientic information, Fisk andRosenfeld (1997) have developed estimatesof the potential to improve productivityin the U.S. through changes in indoorenvironments. The review indicates thatbuilding and HVAC characteristics areassociated with prevalences of acuterespiratory infections and with al lergy andasthma symptoms and non-specic healthsymptoms. From analyses of existingscientic literature and calculations usingstatistical data, the estimated potentialannual nationwide (for the US) benetsof improvements in IEQ include thefollowing:

    •  A 10% to 30% reduction in acuterespiratory infections and allergy and

    asthma symptoms.•  A 20% to 50% reduction in acute non-

    specic health symptoms (commonlyreferred to as Sick Building Syndrome)

    •  A 0.5% to 5% increase in theperformance of ofce work.

    •  Associated annual cost savings andproductivity gains of $30 billion to$170 billion.

    Tips to Ensure Good

    IEQ While Designing and

    Commissioning HVAC

    systems

     Assure Quality of Intake Air  Assuring adequate qual ity of intake airis essential. Outside air intakes shouldnot be located near strong sources ofpollutants such as combustion stacks,sanitary vents, busy streets, loading docks,parking garages, standing water, coolingtowers, and vegetation. The outside airintake must be separated sufcientlyfrom locations where ventilation airis exhausted to prevent signicant re-

    entrainment of the exhaust air. Incomingair should be ltered to remove particles.

     The recommended minimum part icle

    ltration efciencies vary among IAQ and ventilation standards and guidelines.

     Maintain Min. Ventilation Rates The minimum venti lation rates speciedin the applicable code requirements

    should be maintained or exceeded. TheHVAC system should be designed sothat rates of outside air intake can bemeasured using practical measurementtechniques. In buildings with variableair volume (VAV) ventilation systems,special controls may be needed to ensureminimum outside air intake into the

     AHU is maintained during operation.

    Recirculation of Indoor Air Recirculation of indoor air is standardpractice in some countries, such as India,and discouraged in other countriessuch as those of Scandinavia. When airis recirculated, it should be ltered toremove particles. However, lters areoften used only to prevent soiling andfouling of the HVAC equipment. Theselters have a very low efciency forrespirable-size particles (smaller than 2.5micrometers). Use of lters that exceedminimum requirements is an optionto improve IAQ, often with a small ornegligible incremental cost.

     Maintenance of the HVAC SystemRegular preventative maintenanceof the HVAC system is necessary toassure proper delivery of outside airthroughout the building and to limitgrowth of microorganisms in the system.Elements of periodic maintenance thatare important for maintaining good IEQinclude changing of lters, cleaning ofdrain pans and cooling coils, checks offan operation, and checks of operation of

    dampers that inuence air ow rates.

    Integrated Approach to IEQ  The IEQ performance of a bui ldingalso depends on the interactions amongbuilding design, building materials,and building operation, control, andmaintenance. Therefore, an integrated or

     whole building approach is recommendedto maximize IEQ. Such an integratedapproach may focus on the following:

    • IEQ targets or objectives;• Occupancy and indoor pollutant

    sources and pollutant sinks and their variat ion over time;

    • Building and HVAC design.

    Indoor Environment Quality Box 6

    Version 2.0 — March 2011 10ECBC TIP SHEET > HVAC System

  • 8/17/2019 Tip Sheet on HVAC System-2.0 March 2011(Public)

    11/12

    happens, the highest efciencies arepossible in the system, which translatesinto reduced pumping costs.

    ECBC requires hydronic systems to beproportionately balanced in a manner torst minimize throttling losses; then thepump impeller must be trimmed or pumpspeed adjusted to meet the design ow

    Hydronic System Balancing

     A balanced hydronic system is one thatdelivers even ow to all the devices onthat piping system. Each component hasan effective equal length of pipe on thesupply and return. And when a systemis balanced, all of the pressure dropsare correct for the devices. When that

    conditions. [ECBC 5.2.5.1.2] The ECBCallows the following exceptions to thehydronic system balancing requirement:

    • Pump motors of 7.5 kW (10 HP) or less,and

    •  When throttling results in no greaterthan 5% of the nameplate HP draw, or2.2 kW (3 HP), whichever is greater.

    Reduce cooling load •  About half of the cooling load in an

    inefcient building comes from solar

    gain and l ighting, so careful treatment of

    these two sources of heat gain can yield

    impressive savings.

    •  Well-designed building form and

    orientation can maximize daylighting and

    natural ventilation, while minimizing

    unwanted solar gain and the need for

    electric lighting.

    •  Appropriate envelope materials,

    including advanced solar control

    glazing, insulation, venting, and

    light-colored façades and roofs can

    signicantly reduce cooling loads and

    enhance comfort.

    • Landscaping and vegetation can cost

    effectively reduce heat gain and provide

    evapotranspiration cooling while

    enhancing esthetics.

    •  Well-designed load reduction measures may

    allow cooling or heating equipment to bedownsized or even eliminated, thus reducing

    capital cost as well as operating cost.

    System sizing • Operating cost for an HVAC system

    of a given size will not fall linearly with

    cooling load, because most of the cooling

    systems are less efcient at low loads than

    they are in upper range of their capacity.

     To fully capture operating cost savings as

     well as the capital cost savings from the

    load reduction, a smaller HVAC systemmatched carefully to the load prole

    should be installed or retrotted. At the

     very least, this should mean fewer tons of

    cooling plant. In some cases it may mean

    smaller ducts, pipes, pumps, fans, and

    other auxiliaries.

    • In addition to reducing energy

    consumption and costs, right sizing of

    HVAC Systm:

    • Reduces noise.

    • Lowers rst costs for both equipment

    and installation.

    • Reduces equipment footprint.• Controls moisture and improve

    indoor air quality.

    Chillers• Chiller efciencies have improved

    in recent years because of better heattransfer (more surface area throughmore and/or enhanced tubes). Keepthese surfaces clean to maintain highefciency, either through automaticor annual cleaning. A control systemcan monitor heat exchanger approachtemperatures and sound an alarm

     when increasing temperatures indicatefouling.

    • Select the chiller and cooling systems which minimize energy consumption ofthe building throughout the year. Mostchillers spend most hours at 40 to 70percent load, not at design conditions.

     Air handing units• An efcient air system works from

    the end-user upstream. Reducingow requirements by minimizing

    internal and external heat gains offerspotential ly deep cube-law savings.

    • Matching air supply continuously tocooling and ventilation loads using a

     Variable Air Volume (VAV) systemprovides the best system efciency.

    •  Arranging air zones logical ly is keyto making VAV systems efcientand effective. VAV boxes should begrouped to serve areas with similarcooling and ventilation loads (forexample, combine core ofces for

    one zone, south perimeter ofces foranother, and so on).• Measuring fan power is critical to

    ensure energy savings with VAVsystems.

    • Displacement air distribution canefciently provide excellent air qualityand heat removal by moving a large massof air slowly, instead of conventionalturbulent induction systems that moveless air at higher speed.

    • Exhaust air fans are a v iable alternativeto return air fans. They have lower

    power requirements, move less air,avoid redundancy, and expel their fanheat from the building.

    Duct layout 

    • HVAC duct layout must have a gooddesign that is planned early in theconstruction process and understoodby the designer and HVAC contractor.

    •  The duct system must be properlyinstalled with the correct amount ofairow. Every joint and bend in theduct system affects the efciency ofthe system.

    •  The duct system must be air sealed,insulated and appropriately sized.

    Operation and maintenance

    • Maintain chilled water systems withDT up to 9°C to increase the overallenergy efciency of chilled waterproduction and distribution.

    • Incorporate variable speed drives forpumps and fans to efciently meetpartial load requirements.

    • Use of thermal energy storage systems

    in places where cooling plays a majorrole in peak electricity demand and offpeak grid energy rate is considerablylower than the peak time rate.

    • Have demand control ventilation forhigh occupancy spaces. Use of CO

    sensors in spaces that have varyingpeople density loads.

    • Plug leakages in ducts and plenums bysealing of all the joints. Ensure goodduct work quality, workmanship, ductsealing, functionality of dampers, duct

    cleanliness and testing.• Use building management system(BMS) to improve energy efciency.It helps in optimizing the run timeof equipment at desired levels ofefciency to maintain building insidetemp, humidity, air quality etc withinset limits.

    • Reduce face velocities at coils toincrease heat transfer efciency andreduce condensate entrainment

    • Deploy indoor air quality monitoringand controls system to monitor CO

    and volatile organic compound levels.

    Technical Tips for Efficient HVAC System Box 7

    Version 2.0 — March 2011 11ECBC TIP SHEET > HVAC System

  • 8/17/2019 Tip Sheet on HVAC System-2.0 March 2011(Public)

    12/12

    For more information:

    Dr. Ajay Mathur, BEE ([email protected])

    Dr. Archana Walia, USAID ([email protected])

    Mr. Aalok Deshmukh, ECO-III Project([email protected])

    Developed by USAID ECO-III Project Team:

    Technical Contents: Satish Kumar, Ravi Kapoor, and Anurag Bajpai

    Editing: Ravi KapoorLayout Design: Meetu Sharma 

    Printing Coordination: Vidhi Kapoor

    Scale Control in Water

    Circuit

    In a water-cooled air-conditioning system,heat is rejected from the refrigerant tothe cooling water in the condenser. Theimpurities in the cooling water circuitget accumulated, and thus the scales anddeposits are built up in the condenser tubes,creating scaling problems on the condenserheat transfer surfaces. This reduces the heattransfer efciency of the condenser andthus increases chiller energy consumption.

     The ECBC requires [ECBC 5.2.6.2] use ofsoft water for condensers and chilled watersystems to reduce scale formation.

    Economizers  An economizer is a collect ion of dampers,sensors, actuators, and logic devices thattogether decide how much outside air tobring into a building (See Fig. 9). Whenthe outdoor temperature and humidity aremild, economizers save energy by coolingbuildings with outside air instead of byusing refrigeration equipment to coolrecirculated air.

     A properly operati ng economizer can

    cut energy costs by as much as 10 percentof a building’s total energy consumption,depending mostly on local climate andinternal cooling loads. ECBC requiresan economizer for cooling systems over1,200 liters/sec (2,500 cfm) fan capacity

    Energy savings can be achieved bycontrolling the uid ow rate in hydronicsystems. Very often demand on thesesystems is not 100% of the design ow rate.Controls capable of reducing pump ratescut energy costs by modulating the owto meet demand. The ECBC addresses

     Variable Flow Hydronic Systems [ECBC5.3.2] in several ways. First, by requiringthat pump ow rates be controllable toeither 50% of the design or the minimumrequired by the equipment manufacturerfor proper operation of the chillers orboilers. Second, the ECBC requires thatcirculation pumps ≥ 3.7 kW (5 HP) in

     water-cooled air-conditioning units orheat pumps contain a two-way automaticisolation valve to shut off the condenser

     water ow when the compressor is notoperating [ECBC 5.3.2.2].

     Third ly, the ECBC requires pumpmotors in all hydronic systems ≥ 3.7 kW(5 HP) shall be controlled with variablespeed drives [ECBC 5.3.2.3]. Whilethrottling reduces the ow, the motoris still running at full speed and workseven harder as it has to work against a

    restriction. By reducing the speed of themotor, the variable speed drive ensuresreduction in energy consumption whilemaintain ing the required ow.

    and with a cooling capacity > 22 kW[ECBC 5.3.1.1].

    Referencesa. E Source (1997): E Source Technology

     Atlas Series- Volume II: Cooling, Boulder,

    CO, USA.

    b. Energy Conservation Building Code,

    Ministry of Power, Indian, May 2007.

    c. Fanger, P. O. (1970): Thermal comfort

    analysis and applications in environmental

    engineering. McGraw-Hill, New York.

    d. Federspiel, C.C. (1998) “Statistical analysis

    of unsolicited thermal sensation complaints

    in commercial buildings”, ASHRAE

     Transactions 104(1): 912-923

    e. Fisk, W.J. and Rosenfeld, A.H. (1997)

    “Estimates of improved productivity andhealth from better indoor environments”,

    Indoor Air 7(3): 158-172.

    f. Mendell, M.J. (1993) “Non-specic health

    symptoms in ofce workers: a review and

    summary of the epidemiologic literature”,

    Indoor Air 3(4): 227-236.

    g. Nolfo, A.P. (2001): A Primer on Testing,

     Adjusting and Balancing, ASHRAE

     Journal , May 2001.

    h. US Department of Energy (2008): Building

     Technologies Program Web Site (http://

     www.eere.energy.gov/buildings/).i. USGBC (2004): The Treatment by LEED

    of the Environmental Impact of HVAC

    Refrigerants, LEED TSAC Task Force,

     Washington, DC (http://www.usgbc.org/

    docs/)

     The lack of a direct relationship between the

    Global Warming Potential (GWP) and the

    Ozone Depletion Potential (ODP) creates

    a challenge in developing a rating system

    that allows the two environmental factors to

    be considered together, as they should be in

    evaluating the environmental impact of an

    HVAC system. In the absence of perfect or

    ideal refrigerant we should follow a ‘trade-

    off’ approach to identify a better combination

    of HVAC equipment and its refrigerants to

    facilitate optimum environmental impact in

    terms of GWP and ODP per unit of cooling

    capacity.Refrigerant ODP GWP Application

    CFC-11 1 4600 Centrifugal chillers

    CFC-12 0.82 10600 Freezers, chillers, air conditioners

    HFC-410A 0 2000 Air conditioning  

    HCF-134a 0 1600 CFC-12 replacement

    HCFC-123 0.012 120 CFC-11 replacement

    Environmental Tips (Source: USGBC, 2004) Box 8

     Logic ControllerOutdoor

     Temperature

    Sensor

    Outside Air

    Damper

    LinkageMotorized

    Actuator

    Motorized

    Actuator

    Linkage

    Return-Airdamper

    Supply Air

    Cooling

    Coil

    Heating

    Coil

    Mixed Air

    Return Air

    Outside Air

    Key

    InformationFlow

    Air

    Flow

    Fig. 9: The Components of an Economizer

    (Source: E Source Cooling Atlas)

    Version 2.0 — March 2011 12ECBC TIP SHEET > HVAC System