CB503 VENTILATION & AIR CONDITIONING 3 TOPIC 3 : DISTRICT COOLING SYSTEM NAZRIZAM BINTI AB. WAHAB [email protected] 017-612 5556 PSA/ CB503/ PNNAZZ

Upload: pnnazz

Post on 12-Jan-2015

10.041 views

Category:

Education


10 download

DESCRIPTION

Understand about DCS

TRANSCRIPT

Page 1: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

CB503VENTILATION & AIR CONDITIONING 3

TOPIC 3 : DISTRICT COOLING SYSTEM

NAZRIZAM BINTI AB. [email protected]

017-612 5556

Page 2: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

Page 3: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

1. Palm District Cooling

2. Qatar Cool Overview

3. District Cooling System Installation and Overview in Baltimore (Q3)

Page 4: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

GENERAL DESCRIPTIONS/ DEFINITIONS OF DISTRICT COOLING SYSTEM

• District Cooling Systems (DCS) is a system which distribute chilled water or other media, usually provided from a dedicated cooling plant, to multiple buildings for air conditioning or other uses.

OR• District Cooling System (DCS) can be defined as

centralized production and distribution of chilled water from a cooling plant to residential, commercial and industrial facilities trough a network of underground pipes.

Page 5: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

OBJECTIVE OF DCS

To centralized production of chilled water by using district

cooling plant. The generated chilled water will then be

channeled to various building blocks thru pre-

insulated seamless

underground pipes.

Page 6: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

WHAT IS DISTRICT COOLING?

1. DC means the centralized production and distribution of cooling energy. Chilled water is delivered via an underground insulated pipeline to office, industrial and residential buildings to cool the indoor air of the buildings within a district. Specially designed units in each building then use this water to lower the temperature of air passing through the building's ACS.

2. The output of one cooling plant is enough to meet the cooling-energy demand of dozens of buildings. DC can be run on electricity or natural gas, and can use either regular water or seawater. Along with electricity and water, DC constitute a new form of energy service.

Page 7: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

3. DC is measured in refrigeration ton (RT) which is equivalent to 12000 BTU's per hour. RT is the unit measure for the amount of heat removed. RT is defined as the heat absorbed by one ton of ice (2000 pounds) causing it to melt completely by the end of one day (24 hours).

4. DCS can replace any type of ACS, but primarily compete with air-cooled reciprocating chiller systems serving large buildings which consume large amounts of electricity. This ACS is subject to a difficult operating environment, including extreme heat, saline humidity and windborne sand. Over time, performance, efficiency and reliability suffer, leading to significant maintenance costs and ultimately to equipment replacement.

WHAT IS DISTRICT COOLING?

Page 8: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

HISTORY OF DISTRICT COOLING

1. The oldest district heating system was created in the early 14th century in Chaudes-Aigues Cantal - a village in France. This system distributed warm water through wooden pipes and it is still in use today.

2. The first commercial district heating system was created by Birdsill Holly in Lockport, New York in 1877. Holly used the boiler as the central heat source and built a loop consisting of steam pipes, radiators, and even condensate return lines. His system started off with 14 customers. Only 3 years later, it served several factories as well as residential customers and had extended to a 3-mile loop.

3. District cooling also has its roots in the 19th century. It was introduced as a scheme to distribute clean, cool air to houses through underground pipes. The first known district cooling system began operations at Denver's Colorado Automatic Refrigerator Company in late 1889. In the 1930's, large district cooling systems were created for Rockefeller Centre in New York City and for the U.S. Capital Buildings in Washington, D.C.

Page 9: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

HOW DISTRICT COOLING WORKS?

1. Chilled water is produced in a central plant and distributed via a system of pipes that can run underground, on the surface or over rooftops.

2. Inside the buildings, these transmission pipes are normally connected to a conventional air handling unit or fan coil that allows the water to chill the air passing through.

3. This means multiple chiller units placed locally are no longer required.

4. Once the required thermal energy has been extracted from the cold water, this water is returned to the central plant to be re-chilled and re-circulated through the closed-loop piping system.

5. This cooling system is more flexible and also operates with higher efficiency under all load conditions than traditional chillers.

Page 10: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

ADVANTAGES OF DISTRICT COOLING SYSTEM

1. Improve efficiency of energy

2. Protect environment

3. Save space

4. Improve urban view

5. Re-use the heat from exhaust system

6. Prevent disaster

7. Reduce manpower for operation

and maintenance

Page 11: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

WHY IS DISTRICT COOLING ENVIRONMENTAL FRIENDLY?

District cooling helps the environment by increasing

energy efficiency and reducing environmental emissions including air

pollution, the greenhouse gas (GHG) carbon dioxide

(CO2) and ozone-destroying refrigerants. District cooling

can reduce annual CO2 emissions by about 1 ton for every ton of district cooling

refrigeration demand served.

Page 12: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

DISTRICT COOLING SYSTEM

VSCONVENTIONAL REFRIGERANT SYSTEM

Page 13: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

Page 14: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

Page 15: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

Page 16: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

Page 17: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

TYPE OF REFRIGERANTS FOR DCP

• Brine, and propylene-glycol are the famous examples used in DCP.

• Known as “secondary cooling media”, it is not really a refrigerant.

• This type of heat transfer media is used for delivering cool temperature from air conditioner evaporator, to cooling coils.

• These are used in very large air conditioning system, or “district cooling”.

• The reasons are, to keep the maintenance cost, safety risk, and compressor breakdown, low.

Page 18: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

APPLICATION OF DISTRICTCOOLING

SYSTEM IN

MALAYSIA

Page 19: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

DCS IN MALAYSIA

Since 1997, chilled water and electricity have been supplied to airport facilities from the Chiller Plant. Shinryo Corp. contracted with 35,000 RT designed chilled water capacity. Current installed capacity consists of 12 nos. 2500 RT double effect steam absorption chillers. Owner: Gas District Cooling (M)

Sdn BhdDate of Completion: Mar 1997

1. Kuala Lumpur International Airport

Page 20: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

DCS IN MALAYSIA

Putrajaya area was developed for the transfer of the capital city Kuala Lumpur in Malaysia. Plant started to supply chilled water to the government office complex in 1999. Plant capacity was 27,500 RT which included 2 nos. of 1250 RT ECC, integrated chilled water storage system, 5nos. of 2500 RT SAC and 5 nos. of 1500 RT DFC.Owner: Gas District Cooling (M)

Sdn BhdDate of Completion: Dec 2000

2. Putrajaya Precinct 1 DCS Plant

Page 21: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

• The District Cooling System in Bangsar supplies chilled water to a district that comprises :– The Cygal Hotel and the Cygal Towers A &B– The Atlas Towers A to F– Menara Telekom and Wisma Telekom– Tenaga Head Quarters (TNB)

• Objective :– To take advantage of the lower electricity tariff

during the night, the Cristopia Thermal Energy Storage System (STL) is used with the purpose of storing thermal energy during the night for use during the day.     

DCS IN MALAYSIA

3. Bangsar District Cooling Plant

Page 22: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

• Characteristics :– The plant consists of 5 centrifugal chillers (3500 kW each)

working in conjunction with 5 cylindrical STL steel tanks of 380 m³ (3.80 m diameter, 35 m long).

– Two conventional water chillers are used for the base load.– Each brine chiller operates with one STL and one heat

exchanger to provide brine at 3.3°C at the primary side of the heat exchanger.

– Each loop (5) operates independently of the others. – The chillers and the STL's can be operated singularly and

separately or in any combination to cater for the demand, and the decision for their operating status during the day is based on the objective of minimizing the use of the chillers and depleting the energy stored.

DCS IN MALAYSIABangsar District Cooling Plant

Page 23: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

• Technical Data :– Daily Cooling Energy Consumption : 450,000 kWh– Maximum Cooling Demand : 40,000 kW– Cooling Energy Stored : 110,000 kWh– STL Storage Volume : 1,900 m³– Number of Tanks : 5 nos

• Technical Advantages :– Smaller chiller capacity – Smaller heat rejection plant – Reduced maintenance – Efficient and reliable system – Increase of the plant life time – Flexible system available for efficient energy management

DCS IN MALAYSIABangsar District Cooling Plant

Page 24: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

• Financial Advantages :– Saving on operating costs, maintenance, demand

charge and off peak consumption– Lower initial investment

• Projects Credits– Customer : Bangsar Energy Systems SDN BHD

(subsidiary of TNEC)– Consultant: KJ Engineering– Installing Company: KJ Engineering

DCS IN MALAYSIABangsar District Cooling Plant

Page 25: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

DCS IN MALAYSIA4. UKM District Cooling Plant

– Completed and operational in 1998

– District cooling plant serving 10 faculties within the University.

– Energy conservation award winning plant for Retrofitting Category

– Chiller plant capacity of 3,700 RT (13.0 MWr)

– Thermal storage capacity of 11,300 RTH

Page 26: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

5. Malaysia Institute of Nuclear Technology

– Completed and operational in 2001

– Chiller plant capacity of 1,500 RT (5.3 MWr)

– Thermal storage capacity of 6,000 RTH

DCS IN MALAYSIA

Page 27: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

6. Serdang Hospital– Completed and

operational in 2002– 600 bed hospital– Chiller plant

capacity of 2,800 RT (9.8 MWr)

– Thermal storage capacity of 6,000 RTH

DCS IN MALAYSIA

Page 28: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

7. KLCC Cogeneration Plant Upgrading

– Completed and operational in 2005

– Upgrading of additional 12,000 RT (42.2 MW) to cater additional load and energy optimization solution

– Thermal storage capacity of 45,000 RTH

DCS IN MALAYSIA

Page 29: Topic 3 District Cooling System

8. Putrajaya Precint 1 (P1)– Completed and operational in 2008– Retrofit existing plant by additional 12,000 RT (42.2

MW) to a more reliable system– Thermal storage capacity of 48,000 RTH

DCS IN MALAYSIA

PSA/ CB503/ PNNAZZ

Page 30: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

9. MBSA (Shah Alam Municiple)

– Completed and operational in 2006

– District cooling plant serving Shah Alam including the Selangor Council building

– Upgrading of additional 2,400 RT (8.4 MW) to convert existing plant to District Cooling Plant

– Thermal storage capacity of 45,000 RTH

DCS IN MALAYSIA

Page 31: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

10. 1 Borneo– Completed and

operational in 2008– Chiller plant capacity

of 5,700 RT (20.0 MWr)

– Thermal storage capacity of 16,800 RTH

DCS IN MALAYSIA

Page 32: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

11. Institute Jantung Negara (IJN)– Completed end 2008– Chiller plant capacity of 1,200 RT (4.22 MWr)– Thermal storage capacity of 7,100 RTH

DCS IN MALAYSIA

Page 33: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

DCS COMPONENTS• A typical DCS comprises the following components:

1. Central Chiller Plant– generate chilled water for cooling purposes

2. Distribution Network–distribute chilled water to buildings

3. User Station– interface with buildings' own air-

conditioning circuits.

Page 34: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

1. Central Chiller Plant

– Chilled water is typically generated at the central chiller plant by compressor driven chillers, absorption chillers or other sources like ambient cooling or “free cooling” from deep lakes, rivers, aquifers or oceans.

– Groups of large and energy-efficient water-cooled chillers are usually installed in a central chiller plant to take advantage of the economy of scale and the cooling demand diversity between different buildings within a district.

– Sea water condensers or fresh water cooling towers can be utilized to reject waste heat from the central chillers.

Page 35: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

2. Distribution Network

– District chilled water is distributed from the cooling source(s) to the user stations through supply pipes and is returned after extracting heat from the building’s secondary chilled water systems.

– Pumps distribute the chilled water by creating a pressure differential between the supply and return lines.

Page 36: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

3. User Station

– The interface between the district cooling system and the building cooling system is commonly referred to as user station.

– The user station usually comprise of air handling units, heat exchanger and chilled water piping in the building.

– A user station is required in each user's building to connect the DCS distributed chilled water pipe to the building.

– Inside the user station, devices called heat exchangers are installed to transfer heat between the chilled water supply of DCS and the air-conditioning system of the user building.

– The user station could be designed for direct or indirect connection to the district cooling distribution system.

– With direct connection, the district cooling water is distributed within the building directly to terminal equipment such as air handling and fan coil units, induction units, etc.

– An indirect connection utilizes one or multiple heat exchangers in between the district system and the building system.

Page 37: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

A. Mechanical

1. Centrifugal Chillers

2. Condenser water Pumps

3. Chilled Water Primary Pumps

4. Chilled Water Secondary Pumps

5. Cooling Towers

6. Make up water pumps for Cooling Towers

7. Chemical Dosing system for Cooling Towers

8. Chemical Dosing system for chilled water network

9. R.O Plant for blow down water re-claim

10. Water Storage Tank for Cooling Towers / Fire Pumps

11. Blow Down Storage Tank

12. Thermal Storage Tanks

DISTRICT COOLING PLANT EQUIPMENT

Page 38: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

B. Electrical

1. 11 kV Switchgear (3.3 kV if applicable)

2. 11kV Capacitor banks

3. 11 kV / 400 Ton Transformers (11 kV / 3.3 kV Transformers if applicable)

4. H.V Cables and containment systems

5. UPS / Battery Charger for 11 kV vacuum circuit breakers

6. L.V Switchgear

7. Motor control centres

8. L.V capacitor banks

DISTRICT COOLING PLANT EQUIPMENT

Page 39: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

C. Control Systems

1. Building Management System (BMS) or CMS (Plant Control Management System).

2. PLC System for data control

3. System Data server

4. Operator work stations

5. Energy work station

DISTRICT COOLING PLANT EQUIPMENT

Page 40: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

Cooling Tower Cooling Tower Fan & Motor

Page 41: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

Typical Thermal Storage Tank Thermal Storage Tank

Page 42: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

Air Cooled Chiller Water Cooled Chiller Module

Page 43: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

Fan Coil Unit AHU Unit

Page 44: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

Motor Control Center 11kV Switchgear

Page 45: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

CONTROL SYSTEMS

Control System SCADA System Projector Screen

Page 46: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

HEAT EXCHANGER (HE)

• HE are used to transfer heat from one medium to another, such as from steam to hot water, or from water at a higher temperature to water at a lower temperature.

• Two basic types of HE :– Shell and tube type– Plate type

Page 47: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

1. SHELL-AND-TUBE TYPE (STT)

– The STT of HE consists of a bundle of tubes in the shell.

– Primary medium is either steam or water, which flows in the shell.

– Secondary medium is always water, which flows through the tubes.

– The tubes are partitioned to allow single or multiple passes to increase the temperature and the heat transfer.

HEAT EXCHANGER (HE)

Page 48: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

2. PLATE TYPE (PT)

– PT HE composed of multiple, thin, slightly separated plates that have very large surface areas and fluid flow passages for heat transfer.

– This stacked-plate arrangement can be more effective, in a given space, than the STT.

– Advances in gasket and brazing technology have made the plate-type heat exchanger increasingly practical.

– Large HE of this type are called plate-and-frame; when used in open loops, these heat exchangers are normally of the gasket type to allow periodic disassembly, cleaning, and inspection.

– There are many types of permanently bonded plate heat exchangers, such as dip-brazed and vacuum-brazed plate varieties, and they are often specified for closed-loop applications such as refrigeration.

– PT HE also differ in the types of plates that are used, and in the configurations of those plates.

– Some plates may be stamped with "chevron" or other patterns, where others may have machined fins and/or grooves.

HEAT EXCHANGER (HE)

Page 49: Topic 3 District Cooling System

PSA/ CB503/ PNNAZZ

SHELL-AND-TUBE TYPE (STT)

Page 50: Topic 3 District Cooling System
Page 51: Topic 3 District Cooling System

TASBIH KIFARAH

د�ك� م� ب�ح� و� م الله� ان�ك� ب�ح� س��ن�ت� أ إ�ال �ل�ه� إ ال� أ�ن� د� ه� أ�ش�

�ل�ي�ك� إ �ت�و�ب� أ و� ك� ر� ت�غ�ف� س� أ�

(Maha Suci Engkau Ya Allah dan Segala Puji BagiMu, aku bersaksi bahawa tiada Tuhan

melainkan Engkau, aku memohon keampunan dan taubat daripada Engkau)