torelli za ucinke

Upload: alen123456

Post on 02-Jun-2018

219 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/10/2019 Torelli Za Ucinke

    1/180

    1/138

    Transient Overvoltages and Distance Protection:Problems and Solutions

    A thesis submitted in fulfillment of the requirements for the

    degree of Master of Engineering by Research

    Leonardo Torelli

    B.Eng. (Hons)

    School of Electrical and Computer Engineering

    RMIT University

    November 2010

  • 8/10/2019 Torelli Za Ucinke

    2/180

    2/138

    Table of Contents

    The Author .......................................................................................................................... 5

    Acknowledgement...............................................................................................................6

    Declaration .......................................................................................................................... 7

    Abbreviations ...................................................................................................................... 8

    Executive Summary ..........................................................................................................10

    1 Introduction .................................................................................................................. 11

    2 Neutral Earth Resistor and Transient Overvoltages .....................................................14

    2.1 Introduction ..........................................................................................................14

    2.2 Method of Earthing............................................................................................... 15

    2.3 Review of the Existing Body of Knowledge ........................................................16

    2.4 Design of the Experiment .................................................................................... 25

    2.4.1 The Software Package .................................................................................. 252.4.2 The Model .................................................................................................... 26

    2.4.3 The experimental design............................................................................... 27

    2.4.4 System Configuration ................................................................................... 29

    2.4.5 Simulation Characteristics ............................................................................ 31

    2.4.6 Model Components ...................................................................................... 32

    2.5 Simulation Results................................................................................................40

    2.5.1 Simulation 1 : Unloaded Line - Fault at the End of the Line ....................... 41

    2.5.2 Simulation 2 : Unloaded Line - Fault at the Beginning of the Line ............. 47

    2.5.3 Simulation 3 : Capacitor Bank. Fault at the End of the Line....................... 50

    2.5.4 Simulation 4 : Capacitor Bank. Fault at the Beginning of the Line ............. 56

    2.5.5 Simulation 5 : Light inductive Load. Fault at the End of the Line............... 59

    2.5.6 Simulation 6 : Energized 66/22kV Transformer Fault at the 66kV Bus. .... 62

    2.5.7 Overvoltages and Traveling Waves.............................................................. 63

    2.5.8 Impact of Time of Fault with the Overvoltage ............................................. 68

    2.5.9 Overvoltage Response on Phase a ,b and c .................................................. 72

    2.5.10 Overvoltage Harmonic Response ................................................................. 76

    2.6 Conclusion............................................................................................................78

    3 CVT and Transient Overvoltages ................................................................................. 80

    3.1 Overview .............................................................................................................. 80

  • 8/10/2019 Torelli Za Ucinke

    3/180

    3/138

    3.2 The CVT Model ..................................................................................................81

    3.3 Simulation Settings............................................................................................... 843.4 Simulation Results................................................................................................86

    3.5 CVT Conclusion .................................................................................................100

    4 Distance Protection Scheme ....................................................................................... 101

    4.1 Introduction ........................................................................................................101

    4.2 MHO Characteristics Theory ............................................................................. 107

    5 Transient Overvoltages and Distance Protection: Solutions ...................................... 111

    5.1 Introduction ........................................................................................................111

    5.2 Polarisation Techniques...................................................................................... 113

    5.3 Polarising Techniques ........................................................................................ 117

    5.4 CVT Techniques.................................................................................................119

    5.5 Setting Advice ....................................................................................................121

    6 Conclusion..................................................................................................................125

    6.1 Research Findings ..............................................................................................125

    6.2 Areas for Further Investigation........................................................................... 127

    7 References .................................................................................................................. 129

    Appendix A ..................................................................................................................... 133

    10th International Conference on Developments in Power System Protection, March

    2010, Manchester, UK -Abstract.....................................................................................133

    Appendix B ..................................................................................................................... 134

    Overvoltage StudyPSCAD Data .................................................................................. 134

    Appendix C ..................................................................................................................... 135

    Overvoltage studySteady State Voltage Data ............................................................. 135

    Appendix D ..................................................................................................................... 136

    Overvoltage Study- PSCAD Model ................................................................................ 136

    Appendix E......................................................................................................................137

    Voltage and Current as function of SIR.......................................................................... 137

  • 8/10/2019 Torelli Za Ucinke

    4/180

    4/138

    Appendix F......................................................................................................................138

    CVT Study

    PSCAD Data .............................................................................................138

  • 8/10/2019 Torelli Za Ucinke

    5/180

    5/138

    The Author

    My name is Leonardo Torelli. I have been working for fourteen years in power

    industry. I have worked in Italy in Utilities and in Australia in consulting firms. I am

    currently working at Hydro Tasmania Consulting and involved in Protection and

    Power System Analysis projects.

    It is not a surprise that the topic of this research goes across these two areas of

    electrical engineering. The aim of this study was, indeed, proving how important is

    the knowledge of power system analysis for Protection Engineers.

    As result of this study, I presented a paper at the 10th International Conference on

    Developments in Power System Protection, March 2010, Manchester, UK

    This research has given me the opportunity to expand my skills, challenging my

    knowledge and improved my analytical skills. I am committed to use this

    experience at RMIT University as starting point for further studies.

  • 8/10/2019 Torelli Za Ucinke

    6/180

    6/138

    Acknowledgement

    I thank Dr Selva Moorthy for his contribution, support and expert advice during this

    study. I have appreciated his sincere interest in my professional development and

    support of my personal life. Dr Moorthys feedback helped me to stay in line with

    my schedule and achieve the completion of this research.

    I would like to thank my former and existing colleagues at Hydro TasmaniaConsulting for their encouragement during this journey.

    Last, I would like to thank my three beautiful children, my family and friends for

    their warm and enthusiastic appreciation of my work.

    .

  • 8/10/2019 Torelli Za Ucinke

    7/180

    7/138

    Declaration

    I certify that except where due acknowledgement has been made, the work is that

    of the author alone; the work has not been submitted previously, in whole or in

    part, to qualify for any other academic award; the content of the thesis is the result

    of work which has been carried out since the official commencement date of the

    approved research program; and, any editorial work, paid or unpaid, carried out by

    a third party is acknowledged.

    .

    Leonardo Torelli

    Date

  • 8/10/2019 Torelli Za Ucinke

    8/180

    8/138

    Abbreviations

    The following terms are used in this thesis:

    ! HVDC - High Voltage Direct Current

    ! MHO relay - Distance relay with circular characteristic which passes through

    the origin of the R-X plane

    ! NER - Neutral Earth Resistor

    ! NEX - Neutral Earth Reactance

    ! PSCAD-EMTDC - Power system software package

    ! SIR- Source Impedance Ratio

    ! TRV- Transient Recovery Voltage

  • 8/10/2019 Torelli Za Ucinke

    9/180

  • 8/10/2019 Torelli Za Ucinke

    10/180

  • 8/10/2019 Torelli Za Ucinke

    11/180

    11/138

    1 Introduction

    Power systems are designed and operated to supply electrical energy to the

    customers in a safe, reliable and economical way. Faults represent one of the main

    challenges for the power system. Among all the types of faults, phase to ground

    faults represent the majority of the events, with records between 80 to 90 % of all

    faults. Ground faults are generated from insulation breakdown, atmospheric

    conditions and accidental contacts of birds or branches of trees with power lines.

    Therefore, these faults are transitory in nature.

    During this post fault initial period, the voltage change dramatically from a pre fault

    steady state value to a post fault steady state value. In addition, the voltage signal

    is disturbed by higher and lower frequency components. Therefore, transient

    overvoltages could affect the accuracy of the protection scheme. At the same time,

    the protection scheme should be able to operate in a fast manner to reduce the risk

    to personnel, equipment damage, and system stability.

    It is evident that achieving a short operating time and high accuracy of the

    protection scheme represents a major challenge for protection relay manufacturers

    and protection engineers. This research investigated the performance of modern

    digital distance relay during the transient overvoltages period which follows a

    ground fault.

    Initially, this study focused on power system analysis to have a clear understanding

    of the transient overvoltage phenomena. The overvoltage study was conducted

    using PSCAD-EMTC software package. The investigation was performed by using

    the experimental method that involves the scientific manipulation of the variables

    involved in the process and the systematic study of the behavior of the system.

    The study was conducted on a radial system using a neutral earth resistor, NER,

    as a method to earth the 66 kV network. However, the theory and the results

  • 8/10/2019 Torelli Za Ucinke

    12/180

    12/138

    obtained are largely applicable to higher transmission voltages and in power

    systems earthed via a neutral earth reactor, NEX.

    Following the transient overvoltages study, the research focused on the

    performance of five modern digital distance relays.

    In summary, the project objectives are as follow:

    ! Determine the characteristics of transient overvoltages generated by a

    phase to ground fault. This work should highlight the main factors that

    influence the voltage disturbances

    ! Analyze the characteristics of modern digital distance relays to determine if

    the transient overvoltages could affect the accuracy ad operating time of

    the protection relay

    ! Establish a method to predict the performance of the distance protection

    relay following a phase to ground fault

    ! Elaborate a list of setting advice that could enhance the application of the

    distance protection relay in relation to the transient overvoltages

    disturbance

    This study aimed to validate the existing body of knowledge, highlight new insight

    and views and determine new findings.

    The research is organised in six Sections:

    ! Section 2 -NER and Overvoltage

    ! Section 3 - NER and Capacitor Voltage Transformers

    ! Section 4- NER and Distance Protection

    ! Section 5- Distance Relay Applications

  • 8/10/2019 Torelli Za Ucinke

    13/180

    13/138

    In the last part of this study, Section 6, research conclusions and recommendations

    for areas of further investigations are also provided.

  • 8/10/2019 Torelli Za Ucinke

    14/180

  • 8/10/2019 Torelli Za Ucinke

    15/180

    15/138

    2.2 Method of Earthing

    The earthing of the power system involves the implementation of an electrical

    connection between the neutral point and the ground.

    Connection of the neutral to the earth can be done in several methods:

    ! Solidly earthing

    ! Neutral earth resistor, NER

    ! Neutral earth reactance, NEX

    ! Compensated earthing

    ! Ungrounded

    The type and size of the earthing system will affect the following system

    parameters [1-4]:

    ! Fault current

    ! Personnel safety

    ! System Protection

    ! Steady state overvoltage during ground faults

    ! Transient overvoltage during ground faults

    ! Thermal stress on the equipment

    ! Effect on communication circuit

    ! Harmonic current on neutral connection

    ! System stability

  • 8/10/2019 Torelli Za Ucinke

    16/180

  • 8/10/2019 Torelli Za Ucinke

    17/180

    17/138

    Transient overvoltages are produced by sudden changes in the electrical system

    as caused by lightning, faults or switching [6]. The method of earthing system doesnot have any effect on the system during normal operation [4]. However, during the

    transient period the method of earthing has an impact on the system response and

    magnitude of the transient overvoltage.

    Power demand, power generated and system configuration vary continuously with

    time. Therefore the power system always changes from one steady state to

    another steady state. In this very short periods current and voltages may reach

    dangerous values for the equipment and the insulation of the system.

    Overvoltages are often classified according to their duration in two groups [7, 8]:

    ! Temporary Overvoltage above 200 ms

    ! Transient Overvoltage below 200 ms

    Alternatively, overvoltages can be classified according to their origin:

    ! External overvoltage caused by atmospheric phenomena as lighting and

    electrostatic charges

    ! Internal overvoltage generated within the power systems

    This type of disturbances are also classified according to the frequency of the two

    major overvoltage components [9]:

    ! Power frequency overvoltage

    ! Natural frequency overvoltage of a short duration superimposed on the

    power frequency overvoltage

    The sum of the power and natural frequency overvoltage is the voltage recorded in

    the field. This voltage is commonly defined as a transient overvoltage.

  • 8/10/2019 Torelli Za Ucinke

    18/180

    18/138

    The overvoltage component with a power frequency does not theoretically have

    any decaying component and it often termed as steady state overvoltage. Instead,the short duration component usually decays in less than 100 ms. Above all; the

    magnitude of the overall overvoltage is of greatest interest for the impact on the

    planning, design and financial cost of the power system.

    A fault in the power system can be represented and analysed as the closing of a

    switch in the electrical system. This change in the power system develops a new

    redistribution of stored energy in the system [6]. Phase to ground faults represent

    the majority of faults in the power system. These types of faults are produced by

    atmospheric condition, mechanical breakdown of the insulation, objects such as

    birds or branches or trees in contact with the overhead line and poles or structures.

    Recent statistics conducted by protection relay manufacturers found that these

    types of faults represent between 80 and 90 % of the faults in a given power

    system [3, 4, 10]. A large majority of these faults involving overhead lines also

    have transient characteristics and, therefore, self extinguish in a short period of

    time.

    When a phase to ground fault occurs, an overvoltage can be measured in the

    system during the fault itself or after clearing [10]. The maximum transient

    overvoltage is obtained by adding the peak of the temporary overvoltage at power

    frequency overvoltage at 50Hz sinusoidal pattern to the transient overvoltage

    which usually has a higher frequency. This relation is based on the worst case

    scenario with the assumptions that the two components will have maximum peak

    values at the same time. This is plausible because of the different time frames.Power frequency peak lasts long in the context of high frequency oscillations.

    The magnitude of the power frequency overvoltage is strictly related to the

    characteristic parameters of the system. This overvoltage can be calculated using

    the symmetrical components theory. Considering some system simplification as

    necessary, this engineering technique produces accurate results. The fundamental

    frequency voltage, which is also referred to the steady state overvoltage, is absent

  • 8/10/2019 Torelli Za Ucinke

    19/180

    19/138

    in a solidly earthed system. In an ungrounded system the overvoltage reaches the

    maximum value of !3=1.732. In this latter case, the phase to ground voltage isequal to the phase to phase voltage.

    Application of the neutral earth resistor as a method of grounding increases the

    fundamental frequency overvoltage from none to a maximum of 1.732 for the

    insulated system.

    Between these two boundaries of the overvoltage measured in the system, the

    institution of Electrical and Electronic Engineers established an arbitrary limit of

    the overvoltage measured, which is named effective grounding[11].

    The effective grounding term indicates that, during a ground fault, the voltage on

    the healthy phases will not exceed 80 % of the maximum line to line voltage. The

    term effective grounding is commonly used in the power industry as a point of

    reference for the design of the earthing system and sizing of the neutral

    impedance. Therefore a power system can be effectively grounded or

    ineffectively grounded. In other words, in a 66kV subtransmission system, thephase to ground voltage during fault condition will be:

  • 8/10/2019 Torelli Za Ucinke

    20/180

    20/138

    V Nominal

    Vph-ph=66kV

    Vph-g = 66kV/!3=38.1 kV

    Solidly Grounded System

    Vph-g fault= 66/ !3 = 38.1 kV

    Effective grounding System

    Vph-g fault= 66 * 0.8= 52.8 kV

    Ungrounded System

    Vph-g fault= 66kV

    The main advantage of having an effective grounded system is limiting the

    overvoltage magnitude which has a direct impact on the cost of the system. For

    instance, the required insulation medium can be reduced with direct benefits to the

    cost of the electrical equipment. This advantage is a key factor for the design of

    subtransmission and transmission power systems.

    The effective grounding system is nowadays considered the best compromise

    between reducing the phase to ground fault and keeping the overvoltages at a

    reasonable level. Therefore the effective grounding is the preferred solution for the

  • 8/10/2019 Torelli Za Ucinke

    21/180

    21/138

    higher voltages in countries where the power system is grounded via an

    impedance[4] .

    How to achieve an effective grounded system? IEEE Recommended Practice for

    Grounding of Industrial and Commercial Power Systems states the required

    system conditions:

    ! The system must be grounded through a sufficient low impedance such

    that for all system conditions the ratio of zero sequence reactance to

    positive sequence reactance is positive and equal or less than ( X0/X1"3)

    and

    ! the ratio of zero sequence resistance to positive-sequence reactance is

    positive and less than 1( R0/X1

  • 8/10/2019 Torelli Za Ucinke

    22/180

    22/138

    ! 20

    1

    0"

    X

    X, which is inherently met in resistance grounding and with delta

    star power transformers [12], unless the power system is earthed via a

    large reactor

    From the system conditions stated above, it can be derived that the size of neutral

    earth resistor or neutral earth reactor is not critical by itself for the magnitude of the

    overvoltage. The relation with other system parameters determines the magnitude

    of the overvoltage. The above conditions also highlights that unplanned increase of

    the size of the resistor will increase the value of the overvoltage due to the fault

    clearing restrike.

    Besides, the system conditions show that the reactance of the overall zero

    sequence network shall be inductive and not capacitive.

    These system conditions aim to limit transient overvoltages and, at the same time,

    reduce the phase to ground fault current between 10 and 25 % of the steady state

    fault current [9]. The lower level is dictated by the minimum current requirement for

    relay operation. Nowadays with modern digital relays, this requirement could be

    reconsidered. The 25 % upper level takes into consideration the resistor cost in

    comparison to the reactive option.

    Plots of power frequency overvoltage following faults as a function of different

    system parameters or system parameters or ratios of system parameters have

    been published and are available in the existing literature[9].

    Existing studies on overvoltage and impact of the neutral earth resistor on the

    measured overvoltages are based on field testing, software simulation and

    theoretical analysis.

    First researches on transient overvoltages during faults were conducted before the

    Second World War. Overvoltages were analytically determined and tested using

  • 8/10/2019 Torelli Za Ucinke

    23/180

    23/138

    miniature models[9] . Maximum peak voltages were recorded mainly between 3

    and 4 pu with 20 % above 4 pu. The researchers also considered current choppingproduced by the circuit breakers and restrike phenomena known as transient

    recovery voltage, usually abbreviated as TRV. Overvoltage calculations and tests

    using miniature system have also been conducted by other researchers[6, 8].

    These papers provide a complete explanation of the maximum overvoltage in

    relation to system parameters and formed the basis for future IEEE standards.

    Measurements of overvoltages following a fault were performed in the distribution

    network in the 10kV Croatian distribution network[13]. The system was earthed

    using the NER. Maximum overvoltage factors are below 2 pu and minimum

    variations are recorded for different values of the resistor. A transient software

    program was used to validate the results.

    It is possible to determine the maximum transient overvoltage by applying the RLC

    circuit analysis and the use of symmetrical components. [14]. Generalized plots

    which took into consideration the damping effect of the resistor were also

    produced.

    An overall indication of the effect of the resistor is defined by:

    020 XR " circuit is oscillatory

    020 XR $ critical damped

    020 XR # over damped

    Recent studies usually apply the traveling waves theory. In line with this theory,

    modern transient software packages also avoid the use of lumped elements [15].

    Lumped elements representation is adequate for steady state analysis but give

    inaccurate results in transient studies. In the latter studies, where travel time of the

    electromagnetic waves and the energy exchange between capacitance and

    inductance must be taken into consideration, traveling waves theory is the most

  • 8/10/2019 Torelli Za Ucinke

    24/180

    24/138

    accurate method for the computation of the overvoltages along the transmission

    line.

    Fault generated traveling waves propagates not only on the overhead line to line.

    but also line to earth with different propagation parameters [16]. A phase to ground

    fault can be represented as disturbance that generates current and voltage

    traveling waves on a subtransmission line. At each point of discontinuity the

    traveling waves will be refracted and reflected according to the surge impedance

    characteristic of the line [17].It is possible to represent the large number of forward

    and backwards waves and determine the maximum overvoltage generated as a

    function of time by using the Bewley Lattice diagram. However, there are also

    some other considerations which must be dealt with which include mutual coupling

    with other conductors and wave shape distortion experienced along the

    transmission line.

    It is important to point out that overvoltage studies and traveling wave application

    mainly focus on switching and lightning transients [16]. However, overvoltages

    produced by switching episode can be used as a reference for this type of study.

    To conclude, what overvoltage magnitude can be developed under a ground fault?

    From the existing literature it can be inferred generally that the maximum

    overvoltages following a phase to ground fault are below 3 pu [18-20]. Maximum

    overvoltage can instead reach 4.1 pu with trapped charges on the line as in the

    case of switching a capacitor bank connected on the line [19].

  • 8/10/2019 Torelli Za Ucinke

    25/180

    25/138

    2.4 Design of the Experiment

    2.4.1 The Software Package

    Usually, software packages are used to facilitate transient overvoltage studies. In

    fact, these investigations involve complex and time consuming computation that

    can be achieved with sufficient accuracy with software packages.

    PSCAD-EMTDC is a state of the art software package developed using the wave

    propagation theory first published by DR Hernmann W Dommel in the transaction

    of IEEE Power Apparatus and Systems in 1969. based on this paper another two

    transient analysis software packages well known in the industry, EMTP and, later,

    the ATP software package [21] were developed.

    PSCAD is a very powerful and flexible graphical interface that uses the EMTDC

    simulation program. The first version of PSCAD was produced by Denis Woodford

    to model and simulate the high voltage DC system in Canada. The software is now

    developed and maintained by the Manitoba HVDSC Research Centre and is

    continually upgraded to incorporate the latest validated research.

    The software allows one to model an electrical circuit, run a simulation, analyze the

    results and manage the data information in an efficient way. The software package

    is provided with an equipment library, but also allows the creation of new models

    and building a personal equipment library. It is used by consulting engineers,equipment manufacturers and laboratories for planning and design of power

    systems.

    Typical projects involve transient stability, dynamic stability, relay coordination,

    transformer saturation, insulation coordination studies, HVDC studies, harmonic

    studies, power electronics studies and optimisation of controller parameters.

    Further information is located on the website http://www.pscad.com

    http://www.pscad.com/
  • 8/10/2019 Torelli Za Ucinke

    26/180

  • 8/10/2019 Torelli Za Ucinke

    27/180

    27/138

    Steady state overvoltage for a given value of the neutral earth resistor was

    calculated by applying symmetrical components theory. Factor K2 and K0 wereused to determine fault currents and steady state overvoltages[4].

    Z2/Z1K2 $

    Z0/Z1K0 $

    Where:

    Z1= Positive system impedance

    Z2= Negative system impedance

    Z0= Zero system impedance

    The factor K0 gives us a prompt understanding of the power frequency overvoltage

    on the healthy phases during a ground fault.

    The factor K2 is assumed to be 1. If the fault occurs close to the generator the

    factor K2 may increase to 1.4 [4].

    Knowing the steady state overvoltage and the total overvoltage, the transient

    component can be calculated with:

    Natural Frequency V = Measured Overvoltage - Power Frequency V

    2.4.3 The experimental design

    The most relevant factors that influence the overvoltage magnitude during phase to

    ground faults are as follow:

  • 8/10/2019 Torelli Za Ucinke

    28/180

    28/138

    ! Method of earthing

    ! Type of fault

    ! System configuration

    ! Number of earthing points and location in respect to the fault location

    ! Electrical parameters of the equipment

    ! Size of the neutral earth resistor

    ! Location of the fault

    ! Time of the fault applied

    ! Type of subtransmission network as underground cables and overhead

    lines have different electrical characteristics

    ! Type of overhead line

    ! Length of the line

    ! Fault impedance

    Each variable was analyzed in order to determine the most critical and relevant

    factors to be used in this research. In the end, the study was based on thefollowing five factors:

    ! System configuration

    ! Type of faults

    ! Size of the neutral earth resistor

  • 8/10/2019 Torelli Za Ucinke

    29/180

    29/138

    ! Location of the fault

    ! Time of the fault

    2.4.4 System Configuration

    Four system configurations were selected. These configurations were considered

    the most likely configurations to produce the highest overvoltages during a ground

    fault [5, 14]:

    66kV Subtransmission Line

    T

    #1 #2RL

    Resis

    +

    Figure 2.1: Overhead line with no load at the end of the line model

    66kV Subtransmission Line

    T

    #1 #2RL

    Resis

    +30 [MVAR]

    Figure 2.2: Overhead line with capacitor bank at the end of the line

  • 8/10/2019 Torelli Za Ucinke

    30/180

  • 8/10/2019 Torelli Za Ucinke

    31/180

    31/138

    Faults were simulated at the beginning and at the end of line.

    Time of fault

    Considering the symmetry of the alternating voltage cycle, the samples were

    selected only on one half cycle. As one semi cycle at 50Hz takes 10 ms, 21 sample

    spaced 0.5 ms apart were selected.

    Line length

    Line lengths were set to 100, 10 and 0.2 km.

    These line lengths are based on the minimum, maximum and typical line length in

    the Victorian Network. Typical subtransmission lines vary between 10-20 km in the

    urban area around Melbourne and increase to 30-40 km in the country area. In

    Victoria the maximum line length is about 80 Km. The line length of 100 km reflects

    the need to investigate the system in the worst case scenario.

    2.4.5 Simulation Characteristics

    In this study no randomization factor is applied as the chance of biasing the results

    in a software simulation is considered negligible. Therefore, simulation studies

    were conducted in a logical order to maximize the efficiency of the work.

    The simulations were conducted using PSCAD multiple run function. This software

    tool allows completion of complex studies in an efficient manner by manipulating

    variables sequentially and automatically. PSCAD Multiple Run tool can run and

    modulate up to six variables.

  • 8/10/2019 Torelli Za Ucinke

    32/180

    32/138

    Maximum instantaneous voltage peak was recorded for each run and on each

    phase. Only the maximum overvoltage among the three phases was selected forthe maximum overvoltage record.

    Duration of the run time was set to 0.6 s with fault start at 0.4 s plus selected time

    delay. The end time of the fault was 0.1 s with clearing fault at the first zero

    crossing intersection of the fault current.

    According to the Nyquist_Shannon Sampling Theorem, to avoid aliasing and

    incorrect representation of the selected variable, sampling rate should be at least

    double of the variable frequency to be represented. PSCAD recommends that 50s

    for the time step of the process and computation would be sufficient. However,

    time step resolution was reduced to 20 s to capture transient components up to

    25 kHz [22].

    Sampling rate=20 s

    Frequency rate= 1/T=106/20= 50kHz

    2.4.6 Model Components

    Source

    The source represents the power system which is upstream the 220/66 kV power

    transformer in the substation. The voltage source selected from the PSCAD library

    enabled to specify the positive, negative and zero-sequence impedance.

    The impedance value is selected to produce a three fault current of 30 kA on the

    220 kV bus at the substation. Positive impedance is equal to negative impedance.

    Zero impedance was set to be equal to the positive sequence impedance to allow

    for a phase to ground fault level equal to the three phase fault level.

    The X/R ratio was set to 10.

  • 8/10/2019 Torelli Za Ucinke

    33/180

    33/138

    The control system for the output voltage was set using the Fixed Controlfunction

    offered by PSCAD software package. Through several trial and error experimentsthis type of control produced a model behavior very similar to an infinite bus. This

    setting enhances the robustness of the source model in respect to disturbances on

    a lower voltage level. It is assumed that the impact of the overvoltage on the 66 kV

    radial line is limited on the higher transmission network.

    In summary:

    Source Type = Three Phase Voltage-Source Model 3

    MVA = 100 MVA

    Vph- Vph = 220 kV

    Frequency = 50 Hz

    Time constant = 0.06 s

    Z1=Z2=Z0= 4.23 Ohm

    Z1 angle= 84.289 deg

    Voltage Fixed Control

    Es = 220 kV

    Ph = 0.0 deg

    Frequency = 50 Hz

    Transformer

    The two winding 220/66 kV power transformer connects the transmission system to

    the subtransmission system.

  • 8/10/2019 Torelli Za Ucinke

    34/180

    34/138

    Often substation have more than one transformer operating in parallel with the bus

    tie on the 220 kV closed and on the 66 kV bus open or closed according to systemrequirement, the fault level in the system and the rating of the equipment. To

    simplify the study the model represents only one transformer.

    Winding connection of the transformer is delta on the HV side and star on the LV

    side. Tap changer operation is disabled

    The transformer is represented in PSCAD according to the classical approach of

    the transformer theory. Magnetising current is represented as well as core

    saturation placed on the HV side. In PSCAD the HV side is the closest winding to

    the core of the transformer.

    Hysteresis losses in the transformer core are included. Copper losses are disabled

    to reduce the number of nodes in the system. Considering that a typical X/R for a

    power transformer of 100 MVA and 220/66 kV is above 30, this simplification was

    considered acceptable.

    TRANSFORMER DATA:

    3 Phase

    2 Winding Transformer

    MVA Rating: 100.0 MVA

    Freq= 50 Hz,

    V ph-ph primary= 220 kV

    Vph-ph secondary= 66kV

    No Load Losses= 0.01 pu

  • 8/10/2019 Torelli Za Ucinke

    35/180

    35/138

    Copper Losses=0.0 pu.

    Positive Sequence Reactance= 0.15 pu.

    Saturation enabled simulated on primary winding

    Air core reactance= 0.3 pu

    In Rush Decay Time Constant= 0.03 pu.

    Knee Point Voltage: 1.25 pu

    Time to release Flux Clipping=0.1s

    Magnetising Current= 0.02 pu.

    Overhead line

    In electromagnetic simulation studies there are two main methods to representtransmission lines[21]:.

    ! Simplified studies generally rely on the PI Section model

    ! Distributed transmission line, which is most suited for transient line response

    modeling using a digital computer. This method was used for this study

    PSCAD operates applying the traveling wave theory but also implementing mutual

    coupling between conductors and wave shape attenuation produced by the

    transmission line. Transmission lines under PSCAD transient software packages

    are modeled using one of the three traveling wave models:

    ! Bergeron Model

    ! Frequency Dependent Mode Model

  • 8/10/2019 Torelli Za Ucinke

    36/180

    36/138

    ! Frequency Dependent Phase Model

    The Frequency Dependent Phase Model was selected for this study as is the most

    accurate model. This model is a distributed RLC traveling wave model, which

    incorporates the frequency dependence of all parameters in the model. This model

    is recommended by the PSCAD Users Guide for this type of study.

    The overhead line parameters are based on a typical 66 kV line as represented in

    Victoria.

    Conductor Data

    400 mm2 aluminum

    Conductor Resistance= 0.071 Ohm/km

    Conductor Geometric Mean Radius 0.00982 m

    Capacitor bank

    The capacitor bank is implemented in Simulation 3 and 4. The capacitor bank is

    connected at the end of the line to produce maximum peak value of the system

    response during the transient period. The capacitance value was set under the

    assumption that the load on the overhead line is 60 MVA with a power factor of

    0.707.

    Load Current = S/ ( !3 * V ) = 60 *106 / !3 * 66000 )= 524.8 A

    P = S * PF = 52.42 MW

    If PF is 0.707

    Power angle = 45 degrees

  • 8/10/2019 Torelli Za Ucinke

    37/180

  • 8/10/2019 Torelli Za Ucinke

    38/180

  • 8/10/2019 Torelli Za Ucinke

    39/180

    39/138

    Phase to ground and phase to phase to ground the fault were simulated. Current

    interruption was simulated at 0 current crossing to avoid any overvoltage related tomagnetic field being trapped in the circuit. This type of overvoltage is usually

    referred as current chopping[3].

    Fault resistance is set to zero to evaluate the impact of the neutral earth resistor by

    itself.

    In summary:

    Fault Type = Phase to ground and phase to phase to ground

    Fault start =0.4 s to fault 0.410 s

    Fault length =0.1 s

    Fault ON resistance = 0.01 ohm

    Fault OFF resistance = 106ohm

    Current Chopping limit= 0 kA

  • 8/10/2019 Torelli Za Ucinke

    40/180

    40/138

    2.5 Simulation Results

    Simulation results are organized according to the six system configuration and

    related simulations.

    Simulation results data is attached in Appendix B.

    Each simulation result Section contains two graphs. The first plot summarizes the

    main objective of this investigation which is the maximum overvoltage as a function

    of the reduced fault current. The fault current was calculated by applying the

    symmetrical components theory as illustrated in Appendix B.

    The second plot highlights the specific weight of the transitory overvoltage

    component in respect to the steady state overvoltage component. Power frequency

    overvoltage was subtracted from the measured overvoltage only if the recorded

    maximum overvoltage took place during the fault and not at fault clearing. After

    fault clearing, the power frequency overvoltage can be considered absent as the

    three phases are now connected to a symmetrical voltage source.

    Additional investigations were also performed on the following topics:

    ! Overvoltages and traveling waves

    ! Influence of the fault time

    ! Overvoltage response on healthy and faulty phases

    ! Frequency spectrum analysis

  • 8/10/2019 Torelli Za Ucinke

    41/180

    41/138

    2.5.1 Simulation 1 : Unloaded Line - Fault at the End of the Line

    TABLE 2-1SIMULATION 1 RESULTS

    Line Length= 100km

    NER(Ohm)

    MaxMeasuredV from

    PSCAD(kV)

    Iph-g withNER/ Iph-g

    solidlyearthed K0

    V Meas /

    NominalVoltage

    Power

    FrequencyV (pu)

    Natural

    Frequency V(pu)

    0 126.216 1.000 1.0 2.342 1.002 2.3425 124.898 0.977 1.1 2.318 1.103 2.31810 126.607 0.946 1.3 2.349 1.204 2.34915 128.809 0.909 1.5 2.390 1.296 2.39020 128.021 0.867 1.8 2.376 1.378 2.37625 129.201 0.824 2.0 2.398 1.448 2.398

    30 131.007 0.782 2.3 2.431 1.507 2.43135 131.669 0.740 2.6 2.443 1.555 2.44340 132.052 0.700 2.9 2.450 1.596 2.45045 132.457 0.663 3.2 2.458 1.629 2.45850 132.599 0.628 3.6 2.461 1.656 2.461100 103.588 0.394 6.8 1.922 1.763 1.922550 112.552 0.082 36.0 2.089 1.757 0.3321000 122.539 0.045 65.4 2.274 1.747 0.5271000000 140.632 0.000 65217.4 2.610 1.736 0.873

    Line Length=10km0 90.447 1.000 1.0 1.678 1.006 1.6785 99.668 0.882 1.7 1.850 1.412 1.850

    10 100.711 0.705 3.0 1.869 1.647 1.86915 99.279 0.561 4.3 1.842 1.745 1.84220 99.031 0.457 5.7 1.838 1.783 0.05425 96.724 0.383 7.1 1.795 1.797 -0.00330 96.071 0.328 8.5 1.783 1.802 -0.01935 95.465 0.286 9.8 1.772 1.802 -0.03040 95.437 0.253 11.2 1.771 1.800 -0.02945 95.512 0.227 12.6 1.772 1.797 -0.02550 95.526 0.206 14.0 1.773 1.794 -0.021100 94.901 0.105 27.9 1.761 1.771 -0.010

  • 8/10/2019 Torelli Za Ucinke

    42/180

    42/138

    NER(Ohm)

    Max

    MeasuredV fromPSCAD(kV)

    Iph-g withNER/ Iph-gsolidlyearthed K0

    V Meas /NominalVoltage

    PowerFrequencyV (pu)

    NaturalFrequency V(pu)

    550 101.180 0.019 153.0 1.878 1.740 0.1371000 107.676 0.011 278.1 1.998 1.736 0.2621000000 120.050 0.000 278041.7 2.228 1.736 0.491

    Line Length=0.2km0 76.644 1.000 0.9 1.422 1.011 1.4225 86.617 0.806 2.3 1.607 1.358 1.607

    10 92.223 0.564 4.4 1.711 1.455 0.25715 95.204 0.415 6.5 1.767 1.478 0.28820 96.245 0.324 8.6 1.786 1.822 -0.03625 96.587 0.264 10.8 1.792 1.817 -0.02530 96.206 0.223 12.9 1.785 1.810 -0.02535 96.501 0.192 15.1 1.791 1.804 -0.013

    40 96.337 0.169 17.2 1.788 1.798 -0.01045 96.163 0.151 19.3 1.784 1.792 -0.00850 95.991 0.136 21.5 1.781 1.788 -0.007100 94.486 0.068 42.9 1.753 1.763 -0.010

    550 96.337 0.012 236.1 1.788 1.738 0.0501000 102.533 0.007 429.2 1.903 1.735 0.167

    1000000 118.593 0.000 429200.4 2.201 1.736 0.464

    Configuration 1- Fault at the of the line- No load- Measured Overvoltage

    0.0

    0.5

    1.0

    1.5

    2.0

    2.5

    3.0

    0.00.10.20.30.40.50.60.70.80.91.0

    Ifault/I ph-g solidly earthed (pu)

    Overvoltage(pu)

    L=100km

    L = 10km

    L= 0.2km

    Figure 2.5: Configuration 1 Measured overvoltage result

  • 8/10/2019 Torelli Za Ucinke

    43/180

  • 8/10/2019 Torelli Za Ucinke

    44/180

    44/138

    explained using the factor K0=Z0/Z1. The implementation of the resistor will

    increase Z0. As the neutral impedance has a bigger impact on the factor K0, in theshortest line the expected steady state overvoltage has a bigger increase

    The results show that the maximum overvoltages recorded in the simulation with a

    line length of 10km are similar to the results obtained from the simulation with a

    line length of 0.2km. This characteristic is recorded throughout the study. We can

    explain this characteristic by referring to the overvoltage plots as function of system

    parameters of IEEE standards[18]. The different line length does not have a

    particular impact on the Xco/X1. For both line lengths, the ratio is larger than 100 .

    Beyond this value the expected overvoltage is considered constant.[6].

    Xsource= 0.0087 pu

    X Tx= 0.15 pu

    X line=0.0088 Ohm/km

    C= 9.4 nF/Km

    Line length 10km

    Xc = 1/(2f C )/ 10 = 1/( 2* 50 * 9.4 10-9)/ 10 = 33879 Ohm

    X1= Xsource+ Xtx + X line = 0.0087 + 0.15 + 0.088 ( 10km) = 0.2467 pu

    Z base = 484 Ohm

    Xc in pu = Xc value/ Z base= 33879/484= 70 pu

    Ratio Xco/X1= 70/ 0.2467= 283.7

    Line length 0.2km

  • 8/10/2019 Torelli Za Ucinke

    45/180

    45/138

    Xc = 1/(2f C )/0.2 = 1/( 2* 50 * 9.4 10-9)/ 0.2 = 1693996 Ohm

    X1= Xsource+ Xtx + X line( 0.2km) = 0.0087 + 0.15 + 0.0018 = 0.1605 pu

    Z base = 484 Ohm

    Xc in pu = Xc value/ Z base= 636/484= 3500 pu

    Ratio Xco/X1= 3500/ 0.1605= 21806

    Line length 100 km

    Xc = 1/(2f C )/0.2 = 1/( 2* 50 * 9.4 10-9)/ 100 = 3387.9 Ohm

    X1= Xsource+ Xtx + X line( 100km) = 0.0087 + 0.15 + 0.88 = 0.1605 pu

    Z base = 484 Ohm

    Xc in pu = Xc value/ Z base= 3387.9/484= 7 pu

    Ratio Xco/X1= 7/ 0.1605= 43.6

    The Xco/X1 ratio for line length of 100km is also proved to be below 100.

    Therefore, the line will produce a higher overvoltage.

  • 8/10/2019 Torelli Za Ucinke

    46/180

    46/138

    Configuration 1- Fault at the of the line- No load- Transient Overvoltage Contribution

    -0.5

    0.0

    0.5

    1.0

    1.5

    2.0

    2.5

    3.0

    0.00.10.20.30.40.50.60.70.80.91.0

    Ifault/I ph-g solidly earthed (pu)

    Overvoltage(pu)

    L=100km

    L = 10km

    L= 0.2km

    Figure 2.6: Configuration 1 Transient overvoltage component

    Figure 2.6 shows the contribution of the transient overvoltage to the maximum

    recorded overvoltage.

  • 8/10/2019 Torelli Za Ucinke

    47/180

    47/138

    2.5.2 Simulation 2 : Unloaded Line - Fault at the Beginning of the Line

    TABLE 2-2SIMULATION 2 RESULTS

    Line Length= 100km

    NER(Ohm)

    MaxMeasuredV from

    PSCAD(kV)

    Iph-g withNER/ Iph-g

    solidlyearthed K0

    V Meas /

    NominalVoltage

    Power

    FrequencyV (pu)

    Natural

    FrequencyV (pu)

    0 72.597 1.000 0.9 1.347 1.011 1.3475 94.147 0.804 2.4 1.747 1.361 1.747

    10 99.371 0.561 4.4 1.844 1.456 1.84415 101.219 0.412 6.6 1.878 1.479 1.87820 102.529 0.321 8.7 1.903 1.488 1.90325 103.542 0.262 10.9 1.921 1.817 0.10430 104.549 0.220 13.1 1.940 1.810 0.13035 106.192 0.190 15.2 1.971 1.803 0.167

    40 107.291 0.167 17.4 1.991 1.797 0.194

    45 108.035 0.149 19.6 2.005 1.792 0.21350 108.486 0.134 21.7 2.013 1.788 0.226100 111.955 0.068 43.4 2.078 1.763 0.315550 110.022 0.012 238.7 2.042 1.738 0.3041000 111.633 0.007 434.0 2.072 1.735 0.3361000000 111.941 0.000 433986.8 2.077 1.736 0.341

    Line Length=10km0 72.781 1.000 0.9 1.351 1.011 1.3515 91.485 0.804 2.4 1.698 1.361 1.698

    10 97.134 0.561 4.4 1.802 1.456 1.802

    15 97.917 0.412 6.6 1.817 1.479 0.33820 97.710 0.321 8.7 1.813 1.488 0.32525 97.291 0.262 10.9 1.805 1.817 -0.01230 96.880 0.220 13.1 1.798 1.810 -0.01235 96.520 0.190 15.2 1.791 1.803 -0.012

    40 96.212 0.167 17.4 1.785 1.797 -0.01245 95.950 0.149 19.6 1.781 1.792 -0.01250 95.727 0.134 21.7 1.776 1.788 -0.011100 94.570 0.068 43.4 1.755 1.763 -0.008

  • 8/10/2019 Torelli Za Ucinke

    48/180

    48/138

    NER(Ohm)

    Max

    MeasuredV fromPSCAD(kV)

    Iph-g withNER/ Iph-gsolidlyearthed K0

    V Meas /NominalVoltage

    PowerFrequencyV (pu)

    NaturalFrequencyV (pu)

    550 108.220 0.012 238.7 2.008 1.738 0.2701000 112.946 0.007 434.0 2.096 1.735 0.3611000000 119.533 0.000 433986.8 2.218 1.736 0.482

    Line Length=0.2km0 67.090 1.000 0.9 1.245 1.011 1.2455 91.473 0.804 2.4 1.697 1.361 1.697

    10 97.117 0.561 4.4 1.802 1.456 0.34615 97.898 0.412 6.6 1.817 1.479 0.33820 97.681 0.321 8.7 1.813 1.488 0.32525 97.272 0.262 10.9 1.805 1.817 -0.01230 96.861 0.220 13.1 1.797 1.810 -0.01335 96.501 0.190 15.2 1.791 1.803 -0.01340 96.193 0.167 17.4 1.785 1.797 -0.01245 95.931 0.149 19.6 1.780 1.792 -0.01250 95.708 0.134 21.7 1.776 1.788 -0.012100 94.570 0.068 43.4 1.755 1.763 -0.008550 108.314 0.012 238.7 2.010 1.738 0.272

    1000 112.946 0.007 434.0 2.096 1.735 0.3611000000 113.404 0.000 433986.8 2.104 1.736 0.368

    Configuration 2- Fault at the bus- No load- Measured Ov ervoltage

    0.0

    0.5

    1.0

    1.5

    2.0

    2.5

    0.00.10.20.30.40.50.60.70.80.91.0

    Ifault/I ph-g solidly earthed (pu)

    Overvoltage(p

    u)

    L=100km

    L = 10kmL= 0.2km

    Figure 2.7- Configuration 2 Measured overvoltage result

  • 8/10/2019 Torelli Za Ucinke

    49/180

  • 8/10/2019 Torelli Za Ucinke

    50/180

    50/138

    2.5.3 Simulation 3 : Capacitor Bank. Fault at the End of the Line

    TABLE 2-3SIMULATION 3 RESULTS

    Line Length= 100km

    NER(Ohm)

    MaxMeasuredV fromPSCAD(kV)

    Iph-g withNER/ Iph-gsolidlyearthed K0

    V Meas /NominalVoltage

    PowerFrequencyV (pu)

    NaturalFrequencyV (pu)

    0 187.403 1.000 1.0 3.478 1.002 2.4765 185.285 0.977 1.1 3.438 1.102 2.33610 184.351 0.946 1.3 3.421 1.204 2.21715 184.572 0.909 1.5 3.425 1.296 2.12920 185.656 0.867 1.8 3.445 1.378 2.06725 187.384 0.824 2.0 3.477 1.448 2.02930 189.670 0.782 2.3 3.520 1.507 2.01335 192.279 0.740 2.6 3.568 1.555 2.01340 195.097 0.700 2.9 3.620 1.596 2.025

    45 199.190 0.663 3.2 3.696 1.629 2.06850 203.527 0.628 3.6 3.777 1.656 2.121100 245.786 0.394 6.8 4.561 1.763 2.798550 406.039 0.082 36.0 7.535 1.757 5.7781000 453.542 0.045 65.4 8.416 1.747 6.6691000000 526.382 0.000 65217.4 9.768 1.732 8.036

    Line Length=10km0 110.323 1.000 1.0 2.047 1.006 1.0415 123.489 0.882 1.7 2.292 1.412 0.87910 127.826 0.705 3.0 2.372 1.647 0.72515 128.511 0.561 4.3 2.385 1.745 0.64020 124.144 0.457 5.7 2.304 1.783 0.52125 154.689 0.383 7.1 2.871 1.797 1.07330 160.269 0.328 8.5 2.974 1.802 1.17235 164.680 0.286 9.8 3.056 1.802 1.25440 168.268 0.253 11.2 3.123 1.800 1.32345 171.273 0.227 12.6 3.178 1.797 1.38150 173.731 0.206 14.0 3.224 1.794 1.430100 186.406 0.105 27.9 3.459 1.771 1.688

  • 8/10/2019 Torelli Za Ucinke

    51/180

    51/138

    NER(Ohm)

    Max

    MeasuredV fromPSCAD(kV)

    Iph-g withNER/ Iph-gsolidlyearthed K0

    V Meas /NominalVoltage

    PowerFrequencyV (pu)

    NaturalFrequencyV (pu)

    550 198.797 0.019 153.0 3.689 1.740 1.9491000 200.148 0.011 278.1 3.714 1.736 1.9781000000 182.224 0.000 278041.7 3.381 1.736 1.645

    Line Length=0.2km0 109.095 1.000 0.9 2.024 1.011 1.0145 135.208 0.806 2.3 2.509 1.358 1.151

    10 135.715 0.564 4.4 2.518 1.455 1.06415 127.208 0.415 6.5 2.361 1.478 0.88220 148.710 0.324 8.6 2.760 1.822 0.93725 152.521 0.264 10.8 2.830 1.817 1.01330 162.300 0.223 12.9 3.012 1.810 1.20235 166.755 0.192 15.1 3.094 1.804 1.29140 170.288 0.169 17.2 3.160 1.798 1.36245 173.169 0.151 19.3 3.213 1.792 1.42150 175.588 0.136 21.5 3.258 1.788 1.471100 188.724 0.068 42.9 3.502 1.763 1.739550 200.208 0.012 236.1 3.715 1.738 1.977

    1000 201.435 0.007 429.2 3.738 1.735 2.0031000000 203.044 0.000 429200.4 3.768 1.736 2.031

    Configuration 3- Fault at the end of the line- Cap Bank connected at the end of the line- Measured

    Overvoltage

    0.0

    2.0

    4.0

    6.0

    8.0

    10.0

    12.0

    0.00.10.20.30.40.50.60.70.80.91.0

    Ifault/I ph-g solidly earthed (pu)

    Overvoltage(pu)

    L=100km

    L = 10km

    L= 0.2km

    Figure 2.9: Configuration 3 Measured overvoltage result

  • 8/10/2019 Torelli Za Ucinke

    52/180

    52/138

    Configuration 3- Fault at the end of the line- Cap Bank connected at the end of the line-

    Transient Overvoltage Contribution

    0.0

    1.0

    2.0

    3.0

    4.0

    5.0

    6.0

    7.0

    8.0

    9.0

    0.00.10.20.30.40.50.60.70.80.91.0Ifault/I ph-g so lidly earthed (pu)

    Overvoltage(pu)

    L=100km

    L = 10km

    L= 0.2km

    Figure 2.10: Configuration 3 Transient overvoltage component

    The dangerous effects of capacitor switching are well known in the engineering

    field [23]. The results obtained with this simulation show that, following a fault in the

    network with no or small loads and a capacitor bank connected to the grid

    represent a danger to the insulation of the power system.

    The overvoltages measured in this simulation are the highest of the entire study

    reported here. The results are in line with previous studies [5, 14] except for

    results obtained with line length of 100 km . This is due to the combination of the

    following system parameters:

    !

    Length of the line

    ! NER size

    These parameters affect the3

    00 XC

    R " transient overvoltages condition. If this

    condition is not met, dangerous fault restrikes are generated [9]. Is it worth noting

    that field experience of arcing ground fault above 7 pu are quite rare as the

    insulation of the power system usually breaks down between 6 to 7 pu [9]

  • 8/10/2019 Torelli Za Ucinke

    53/180

    53/138

    Line length impact is shown in Figure 2.9 and 2.10. Instead, to review the impact of

    the NER size further simulations were performed. Four snapshots with a NER of10, 100, 1000 and 1000000 Ohm were taken as shown in Figures 2.11 to 2.14.

    -80

    -60

    -40

    -20

    0

    20

    40

    60

    80

    100

    Voltage

    (kV)

    Vs

    Figure 2.11: Configuration 3 Transient overvoltage Snapshot with NER of 10 Ohms

    -300

    -200

    -100

    0

    100

    200

    300

    VV

  • 8/10/2019 Torelli Za Ucinke

    54/180

    54/138

    Figure 2.14: Configuration 3 Transient overvoltage Snapshot with NER of 1000000 Ohms

    The graphs show that the increase of the resistor will increase the transient

    overvoltages.

    The dangerous transient overvoltages are also due to the conservative approach in

    selecting the size of the capacitor bank. A further simulation is conducted to

    validate this theory. A smaller capacitor bank of 15 MVA was used for the analysis.

    Configuration 3- Line Length 100km- Comparison between 30MVAR and 15MVAR Capacitor BankResults- Measured Overvoltage

    0.0

    2.0

    4.0

    6.0

    8.0

    10.0

    12.0

    0.00.10.20.30.40.50.60.70.80.91.0

    Ifault/I ph-g solidly earthed (pu)

    Overvoltage(pu)

    15MVAR

    30MVAR

    Figure 2.15: Configuration 3 30 and 15 MVAR Cap bank overvoltage comparison

  • 8/10/2019 Torelli Za Ucinke

    55/180

    55/138

    The system response with a smaller capacitor gives a result which is acceptable

    and in line with previous studies [5, 19]. Maximum overvoltage with the insulatedsystem is 4.1 pu.

  • 8/10/2019 Torelli Za Ucinke

    56/180

    56/138

    2.5.4 Simulation 4 : Capacitor Bank. Fault at the Beginning of the Line

    TABLE 2-4SIMULATION 4 RESULTS

    Line Length= 100km

    NER

    (Ohm)

    MaxMeasuredV fromPSCAD

    (kV)

    Iph-g withNER/ Iph-gsolidly

    earthed K0

    V Meas /Nominal

    Voltage

    PowerFrequency

    V (pu)

    NaturalFrequency

    V (pu)0 73.660 1.000 0.9 1.367 1.011 1.3675 102.229 0.804 2.4 1.897 1.361 1.89710 110.677 0.561 4.4 2.054 1.456 2.05415 120.455 0.412 6.6 2.235 1.479 2.23520 139.620 0.321 8.7 2.591 1.488 2.59125 156.662 0.262 10.9 2.907 1.817 2.90730 171.647 0.220 13.1 3.185 1.810 3.18535 185.697 0.190 15.2 3.446 1.803 3.44640 198.103 0.167 17.4 3.676 1.797 3.67645 209.035 0.149 19.6 3.879 1.792 3.879

    50 219.140 0.134 21.7 4.067 1.788 4.067100 282.383 0.068 43.4 5.240 1.763 5.240550 373.638 0.012 238.7 6.934 1.738 6.9341000 431.569 0.007 434.0 8.009 1.735 8.0091000000 553.568 0.000 433986.8 10.272 1.736 10.272

    Line Length=10km0 73.885 1.000 0.9 1.371 1.011 0.3605 104.589 0.804 2.4 1.941 1.361 0.58010 115.953 0.561 4.4 2.152 1.456 0.69615 126.137 0.412 6.6 2.341 1.479 0.86220 129.761 0.321 8.7 2.408 1.488 0.92025 140.232 0.262 10.9 2.602 1.817 0.78530 143.196 0.220 13.1 2.657 1.810 0.84735 147.174 0.190 15.2 2.731 1.803 0.92840 151.560 0.167 17.4 2.812 1.797 1.01545 155.590 0.149 19.6 2.887 1.792 1.09550 158.744 0.134 21.7 2.946 1.788 1.158100 173.853 0.068 43.4 3.226 1.763 1.463550 185.633 0.012 238.7 3.445 1.738 1.707

  • 8/10/2019 Torelli Za Ucinke

    57/180

  • 8/10/2019 Torelli Za Ucinke

    58/180

  • 8/10/2019 Torelli Za Ucinke

    59/180

    59/138

    2.5.5 Simulation 5 : Light inductive Load. Fault at the End of the Line.

    TABLE 2-5SIMULATION 5 RESULTS

    Line Length= 100km

    NER(Ohm)

    MaxMeasured

    V fromPSCAD(kV)

    Iph-g with

    NER/ Iph-gsolidlyearthed K0

    V Meas /NominalVoltage

    PowerFrequencyV (pu)

    NaturalFrequency V (pu)

    0 123.996 1.000 1.0 2.301 1.002 2.3015 121.497 0.977 1.1 2.255 1.102 2.25510 127.242 0.946 1.3 2.361 1.204 2.36115 124.414 0.909 1.5 2.309 1.296 2.30920 125.584 0.867 1.8 2.330 1.378 2.33025 126.472 0.824 2.0 2.347 1.448 2.34730 127.242 0.782 2.3 2.361 1.507 2.36135 127.753 0.740 2.6 2.371 1.555 2.371

    40 128.210 0.700 2.9 2.379 1.596 2.37945 128.382 0.663 3.2 2.382 1.629 2.38250 128.563 0.628 3.6 2.386 1.656 2.386100 125.448 0.394 6.8 2.328 1.763 2.328550 106.256 0.082 36.0 1.972 1.757 0.2151000 114.514 0.045 65.4 2.125 1.747 0.378

    1000000 131.252 0.000 65217.4 2.436 1.732 0.704

    Line Length=10km0 89.031 1.000 1.0 1.652 1.006 1.6525 98.999 0.882 1.7 1.837 1.412 1.837

    10 99.542 0.705 3.0 1.847 1.647 1.84715 98.172 0.561 4.3 1.822 1.745 1.82220 97.019 0.457 5.7 1.800 1.783 0.01725 95.755 0.383 7.1 1.777 1.797 -0.02130 95.531 0.328 8.5 1.773 1.802 -0.02935 95.024 0.286 9.8 1.763 1.802 -0.03840 94.367 0.253 11.2 1.751 1.800 -0.04945 94.358 0.227 12.6 1.751 1.797 -0.04650 94.180 0.206 14.0 1.748 1.794 -0.046100 93.855 0.105 27.9 1.742 1.771 -0.029

  • 8/10/2019 Torelli Za Ucinke

    60/180

    60/138

    550 99.236 0.019 153.0 1.841 1.740 0.101

    NER(Ohm)

    MaxMeasuredV fromPSCAD(kV)

    Iph-g withNER/ Iph-gsolidlyearthed K0

    V Meas /NominalVoltage

    PowerFrequencyV (pu)

    NaturalFrequency V (pu)

    1000 109.857 0.011 278.1 2.039 1.736 0.3021000000 241.638 0.000 278041.7 4.484 1.736 2.748

    Line Length=0.2km0 74.717 1.000 0.9 1.387 1.011 1.3875 85.939 0.806 2.3 1.595 1.358 1.595

    10 91.418 0.564 4.4 1.696 1.455 0.24215 94.402 0.415 6.5 1.752 1.478 0.27320 95.404 0.324 8.6 1.770 1.822 -0.05225 95.743 0.264 10.8 1.777 1.817 -0.04030 95.531 0.223 12.9 1.773 1.810 -0.03735 95.640 0.192 15.1 1.775 1.804 -0.02940 95.477 0.169 17.2 1.772 1.798 -0.02645 95.301 0.151 19.3 1.768 1.792 -0.02450 95.131 0.136 21.5 1.765 1.788 -0.022100 94.017 0.068 42.9 1.745 1.763 -0.019550 97.021 0.012 236.1 1.800 1.738 0.062

    1000 107.684 0.007 429.2 1.998 1.735 0.2631000000 126.718 0.000 429200.4 2.351 1.736 0.615

    Configuration 5- Fault at the of end the line- Inductive Load connected at the end of the

    line- Measured Overvoltage

    0.0

    0.5

    1.0

    1.5

    2.0

    2.5

    3.0

    3.5

    4.0

    4.5

    5.0

    0.00.10.20.30.40.50.60.70.80.91.0

    Ifault/I ph-g solidly earthed (pu)

    Overvoltage(pu) L=100km

    L = 10km

    L= 0.2km

    Figure 2.18: Configuration 1 Measured overvoltage result

  • 8/10/2019 Torelli Za Ucinke

    61/180

    61/138

    Configuration 5- Fault at the end of the line- Inductive Load connected at the end of the line-

    Transient Overvoltage Contribution

    -0.5

    0.0

    0.5

    1.0

    1.5

    2.0

    2.5

    3.0

    0.00.10.20.30.40.50.60.70.80.91.0

    Ifault/I ph-g solidly earthed (pu)

    Overvoltage(pu)

    L=100km

    L = 10km

    L= 0.2km

    Figure 2.19: Configuration 5 Transient overvoltage component

    Maximum overvoltages recorded are similar to the results from Simulation 1. It is

    likely that this inductive load was not large enough to produce any relevant impact

    on the overvoltages. Therefore, not further analysis was conducted using the

    results of this system configuration.

  • 8/10/2019 Torelli Za Ucinke

    62/180

    62/138

    2.5.6 Simulation 6 : Energized 66/22kV Transformer Fault at the 66kV

    Bus.

    TABLE 2-6SIMULATION 61 RESULTS

    NER(Ohm)

    MaxMeasuredV fromPSCAD(kV)

    Iph-g withNER/ Iph-gsolidlyearthed K0

    V Meas /NominalVoltage

    PowerFrequencyV (pu)

    NaturalFrequency V (pu)

    0 54.929 1.000 0.9 1.017 1.011 0.0065 91.224 0.804 2.4 1.692 1.361 0.33110 96.846 0.561 4.4 1.792 1.456 0.33615 97.661 0.412 6.6 1.812 1.479 0.33320 97.464 0.321 8.7 1.806 1.488 0.31825 97.053 0.262 10.9 1.800 1.817 -0.01730 96.646 0.220 13.1 1.793 1.810 -0.01735 96.287 0.190 15.2 1.788 1.804 -0.01640 95.982 0.167 17.4 1.786 1.798 -0.01245 95.721 0.149 19.6 1.776 1.792 -0.01650 95.499 0.134 21.7 1.772 1.788 -0.016

    100 94.343 0.068 43.4 1.763 1.763 0.000550 93.211 0.012 238.7 1.729 1.738 -0.0091000 93.089 0.007 434.0 1.727 1.735 -0.0081000000 92.838 0.000 433986.8 1.723 1.732 -0.009

    Configuration 6- Fault at the bus- Tx 30 MVA delta/star at the bus- Measured Overvoltage

    0.0

    0.2

    0.4

    0.6

    0.8

    1.0

    1.2

    1.4

    1.6

    1.8

    2.0

    0.00.10.20.30.40.50.60.70.80.91.0

    Ifault/I ph-g solidly earthed (pu)

    Overvoltage(pu)

    Figure 2.20: Configuration 6 Measured overvoltage result

  • 8/10/2019 Torelli Za Ucinke

    63/180

    63/138

    Configuration 6- Fault at the bus- Tx 30 MVA at the bus-

    Transient Overvoltage Contribution

    -0.1

    0.0

    0.1

    0.1

    0.2

    0.2

    0.3

    0.3

    0.4

    0.4

    0.00.10.20.30.40.50.60.70.80.91.0

    Ifault/I ph-g solidly earthe d (pu)

    Overvoltage(pu)

    Figure 2.21: Configuration 6- Transient overvoltage result

    Overvoltages recorded in this study are relatively lower than in the other

    simulations. Maximum overvoltage reaches a maximum of 1.8pu as phase to

    ground fault decreases below 0.6 pu.

    Please note that the transient overvoltage component disappears as the phase to

    ground fault decreases below 0. 25 pu. Therefore, for high resistor values the

    overvoltages are only produced by the power frequency voltage.

    No further analysis was conducted using the data from this simulation

    2.5.7 Overvoltages and Traveling Waves

    This section documents the propagation of the voltage traveling waves along the

    transmission line. A series of snapshots are presented to describe the behavior of

    the overvoltages using the data from Simulation 1 No load at the end of the line-

    and with the line length of 100 km

  • 8/10/2019 Torelli Za Ucinke

    64/180

    64/138

    Bus Current,Bus Voltage : Graphs

    Time ... 0.3850 0.3900 0.3950 0.4000 0.4050 0.4100 0.4150 0.4200 0.4250 0.4300

    -1.50

    -1.00

    -0.50

    0.00

    0.50

    1.00

    1.50

    Current(kA)

    Is

    -100

    -80

    -60

    -40

    -20

    0

    20

    40

    60

    80

    Voltage

    (kV)

    Vs

    Figure 2.22: Configuration 1 - Maximum Overvoltage - Phase to Ground Fault NER 0 Ohm

    Snapshots were recorded at fault inception and fault clearing time. The graph also

    shows that the transient overvoltage at higher frequency is superimposed on a

    lower frequency overvoltage. The overvoltage has a period of 0.7 ms which is

    equivalent to a frequency of 1400 Hz. The high frequency component decays inapproximately 10ms.

    Traveling waves are triggered at the same time on both healthy phases and travel

    on the conductors. The steps pattern of the transient overvoltage is the effect of the

    traveling waves that reflect back and forward between the two ends of the line.

  • 8/10/2019 Torelli Za Ucinke

    65/180

    65/138

    Bus Current,Bus Voltage : Graphs

    Time ... 0.5050 0.5075 0.5100 0.5125 0.5150 0.5175 0.5200 0.5225 0.5250 0.5275

    -1.50

    -1.00

    -0.50

    0.00

    0.50

    1.001.50

    Current(kA)

    Is

    -100

    -75

    -50

    -25

    0

    25

    50

    75

    100

    125

    Voltage

    (kV)

    Vs

    Figure 2.23: Configuration 1- Snapshot of after clearing overvoltage- Phase to Ground Fault NER

    0 Ohm

    Transient overvoltage superimposed on the power frequency voltage has a

    frequency of 590 Hz. Maximum overvoltage appears on the phase which has the

    highest voltage at the clearing time. The overvoltage is produced by the energy

    stored in the electric field of the capacitance that will discharge at fault clearing

    time.

  • 8/10/2019 Torelli Za Ucinke

    66/180

    66/138

    Bus Current,Bus Voltage : Graphs

    Time ... 0.490 0.500 0.510 0.520 0.530 0.540 0.550

    -1.50

    -1.00

    -0.50

    0.00

    0.50

    1.001.50

    Current(kA)

    Is

    -100

    -50

    0

    50

    100

    150

    Voltage

    (kV)

    Vs

    Figure 2.24: Configuration 1- Snapshot of Maximum Overvoltage- Phase to Phase to Ground Fault

    NER 0 Ohm

    In the phase to phase ground fault the maximum overvoltage is recorded at the

    fault clearing time. Frequency of the superimposed transient overvoltage is 590 Hz

    as in the phase to ground faults. The overvoltages on each phase have the same

    frequency. This transient overvoltage decays after 30ms.

  • 8/10/2019 Torelli Za Ucinke

    67/180

  • 8/10/2019 Torelli Za Ucinke

    68/180

    68/138

    As the NER approaches 50 Ohm, the pattern of the plots remains similar to plots

    with NER equal to 0 Ohm. Overvoltage frequencies are 590 Hz in all three phases.

    Bus Current,Bus Voltage : Graphs

    Time ... 0.4000 0.4050 0.4100 0.4150 0.4200 0.4250

    -0.100

    -0.050

    0.000

    0.050

    0.100

    0.150

    0.200

    Current(kA)

    Is

    -125

    -100

    -75

    -50

    -25

    0

    25

    50

    75

    100

    Voltage

    (kV)

    Vs

    Figure 2.27: Configuration 1- Snapshot of Maximum Overvoltage- Phase to Ground Fault NER

    1000 Ohm

    The large size of the resistor now makes the phase to ground fault as the most

    prominent overvoltage. Traveling waves are visible in the current and voltage plots.

    2.5.8 Impact of Time of Fault with the Overvoltage

    This investigation highlights the relation between the time of fault and the

    amplitude of the measured overvoltage. Plots are divided into phase to ground fault

    and phase to phase to ground fault.

  • 8/10/2019 Torelli Za Ucinke

    69/180

    69/138

    Simulation 1- Measured Overvoltage

    Ph-g fault- All Data Plot

    0

    0.5

    1

    1.5

    2

    2.5

    3

    0 50 100 150 200 250 300 350

    Sample

    Overvoltag L=100km

    L=10km

    L=0.2km

    Solidly Earthed

    SystemInsulated

    System

    Figure 2.28: Configuration 1- All Data Plot

    Simulation 2- Measured Overvoltage

    Ph-g Fault- All Data Plot

    0

    0.5

    1

    1.5

    2

    2.5

    0 50 100 150 200 250 300 350

    Sample

    Overvoltag L=100km

    L=10km

    L=0.2km

    Solidly Earthed

    SystemInsulated

    System

    Figure 2.29: Configuration 2 All Data Plot

    Simulation 3- Measured Overvoltage

    Ph-g Fault- All Data Plot

    0

    2

    4

    6

    8

    10

    12

    0 50 100 150 200 250 300 350

    Sample

    Overvoltag L=100km

    L=10km

    L=0.2km

    Solidly Earthed

    SystemInsulated

    System

    Figure 2.30: Configuration 3 All data plot

  • 8/10/2019 Torelli Za Ucinke

    70/180

    70/138

    Simulation 4- Measured Overvoltage

    Ph-g Fault- All Data Plot

    0

    2

    4

    6

    8

    10

    12

    0 50 100 150 200 250 300 350

    Sample

    Overvoltag L=100km

    L=10km

    L=0.2km

    Solidly Earthed

    SystemInsulated

    System

    Figure 2.31: Configuration 4- All data plot

    Simulation 1- Measured OvervoltagePh-Ph-G Fault- All Data Plot

    0

    0.5

    1

    1.5

    2

    2.5

    3

    0 50 100 150 200 250 300 350

    Simulation

    Overvoltage(pu)

    Series1

    Series2

    Series3Solidly EarthedSystem

    InsulatedSystem

    Figure 2.32: Configuration 1- All data plot

    Simulation 2- Measured OvervoltagePh-Ph-G Fault- All Data Plot

    0

    0.5

    1

    1.5

    2

    2.5

    0 50 100 150 200 250 300 350

    Simulation

    Overvoltage(pu)

    L=100km

    L=10km

    L=0.2kmSolidly Earthed

    System

    InsulatedSystem

    Figure 2.33: Configuration 2 All data plot

  • 8/10/2019 Torelli Za Ucinke

    71/180

    71/138

    Simulation 3- Measured OvervoltagePh-Ph-G Fault- All Data Plot

    0

    0.5

    1

    1.5

    2

    2.5

    3

    3.5

    4

    4.5

    5

    0 50 100 150 200 250 300 350

    Simulation

    Overvoltage(pu)

    L=100km

    L=10km

    L=0.2kmSolidly E arthedSystem

    InsulatedSystem

    Figure 2.34: Configuration 3- All data plot

    Simulation 4- Measured Overvoltage

    Ph-Ph-G Fault- All Data Plot

    0

    1

    2

    3

    4

    5

    6

    7

    8

    0 50 100 150 200 250 300 350

    Simulation

    Overvoltage(pu)

    L=100km

    L=10km

    L=0.2kmSolidly EarthedSystem

    InsulatedSystem

    Figure 2.35: Configuration 3 All data plot

    These graphs are produced by using the maximum overvoltage recorded on each

    simulation. It is reminded that 11 simulations were performed for each NER sizeconfiguration. Besides, 1 ms additional delay time was applied on each simulation.

    Points were plotted sequentially, starting on the simulation with a NER of 0 Ohm to

    the maximum value of the NER, which corresponds to the insulated system.

    In these eight plots, Figure 2.28 to Figure 2.35, it is possible to recognize the 15

    peaks related to the 15 resistor sizes used in the simulations.

  • 8/10/2019 Torelli Za Ucinke

    72/180

    72/138

    Phase to ground faults for transmission line of 10 and 0.1km showed a smoother

    pattern with lower peak values. Only in Simulation 2 there is an irregularity in themaximum overvoltage. Overall, the maximum overvoltage in the phase to ground

    fault is therefore less dependent on the time of fault.

    Phase to ground fault maximum overvoltages show a similar pattern across the

    three different subtransmission line lengths. Maximum overvoltages appear only for

    a brief period of time and at the same time in all the three line lengths.

    The 8 plots also show similar results for simulations conducted with

    subtransmission line of 10km and 0.1km.

    These graphs confirm that time of fault is relevant in determining the maximum

    overvoltage during phase to phase to ground faults.

    2.5.9 Overvoltage Response on Phase a ,b and c

    The section investigates the relationship between faults and different overvoltage

    responses on each phase.

    This study was conducted only for subtransmission line of 100km in the simulation

    1, 2, 3 and 4. Graphs are divided in phase to ground faults and phase to phase to

    ground faults.

    On PSCAD software package phase to ground fault takes place on phase a and

    phase to phase to ground fault takes place on phases a and b.

  • 8/10/2019 Torelli Za Ucinke

    73/180

    73/138

    Simulation 1-Measured Overvoltage

    Phase Comparison-Phase to Ground Fault- L=100km

    0

    0.5

    1

    1.5

    2

    2.5

    3

    0 50 100 150 200 250 300 350

    Simulation

    Overvoltage(pu)

    Phase a

    Phase b

    Phase c

    Solidly Earthed

    System

    Insulated

    System

    Figure 2.36: Configuration 1 Phase comparison

    Simulation 2-Measured Overvoltage

    Phase Comparison-Phase to Ground Fault- L=100km

    0

    0.5

    1

    1.5

    2

    2.5

    0 50 100 150 200 250 300 350

    Simulation

    Overvoltage(p)

    Phase a

    Phase b

    Phase c

    Solidly Earthed

    System

    Insulated

    System

    Figure 2.37: Configuration 2 Phase comparison

    Simulation 3-Measured Overvoltage

    Phase Comparison-Phase to Ground Fault- L=100km

    0

    2

    4

    6

    8

    10

    12

    0 50 100 150 200 250 300 350

    Simulation

    Overvoltage(pu)

    Phase a

    Phase b

    Phase c

    Solidly Earthed

    System

    Insulated

    System

    Figure 2.38: Configuration 3 Phase comparison

  • 8/10/2019 Torelli Za Ucinke

    74/180

    74/138

    Simulation 4-Measured OvervoltagePhase Comparison-Phase to Ground Fault- L=100km

    0

    2

    4

    6

    8

    10

    12

    0 50 100 150 200 250 300 350

    Simulation

    Overvoltage(pu)

    Phase a

    Phase b

    Phase c

    Solidly EarthedSystem

    InsulatedSystem

    Figure 2.39: Configuration 4 Phase comparison

    Simulation 1-Measured Overvoltage

    Phase Comparison-Phase to Phase to Ground Fault- L=100km

    0

    0.5

    1

    1.5

    2

    2.5

    3

    0 50 100 150 200 250 300 350

    Simulation

    Overvoltage(pu)

    Phase a

    Phase b

    Phase c

    Solidly Earthed

    System

    InsulatedSystem

    Figure 2.40: Configuration 1 Phase comparison

    Simulation 2-Measured Overvoltage

    Phase Comparison-Phase to Phase to Ground Fault- L=100km

    0

    0.5

    1

    1.5

    2

    2.5

    0 50 100 150 200 250 300 350

    Simulation

    Overvoltage(pu)

    Phase a

    Phase b

    Phase c

    Solidly Earthed

    System

    Insulated

    System

    Figure 2.41: Configuration 2 Phase comparison

  • 8/10/2019 Torelli Za Ucinke

    75/180

  • 8/10/2019 Torelli Za Ucinke

    76/180

    76/138

    As noted in Section 2.4.9, the plots for the phase to phase to ground faults show

    that the time of fault is a key element to determine in which phase the maximumovervoltage is recorded.

    2.5.10 Overvoltage Harmonic Response

    A further analysis was conducted on the frequency spectrum of the transient

    overvoltage. The study was done using the Fast Fourier Transform (FFT) function,

    which determine the harmonic magnitude and phase of the input signal as a

    function of time[21].

    Base frequency was set to 12.5 Hz to detect noise elements lower than power

    frequency voltage.

    Here below few snapshots of the healthy and faulty phases for a phase to ground

    fault following a fault are provided. Snapshots were captured after 10 ms fault

    injection.

    Referring to the graphs left hand side spectrum refers to 12.5 Hz component and

    right hand side spectrum refers to 322.5 HZ noise element. The number in the plot

    frame refers to the voltage magnitude in the first frequency band, 12.5 Hz.

    Ea60.0

    0.0

    [1] 1.79434

    Figure 2.44: Configuration 1 Harmonic analysis NER 0 ohmsafter 10ms

  • 8/10/2019 Torelli Za Ucinke

    77/180

    77/138

    Ea60.0

    0.0

    [1] 3.50508

    Figure 2.45: Configuration 1 Harmonic analysis NER 5 ohmsafter 10ms

    Ea60.0

    0.0

    [1] 6.13753

    Figure 2.46: Configuration 1 Harmonic analysis NER 50 ohmsafter 10ms

    From the graphs we can observe that voltage noise appears at frequencies higher

    and lower values in respect of the power frequency voltage The major components

    are in the band close to 50 Hz. Components with lower magnitude, less than 3 %

    of nominal voltage, are visible on high frequency up to 300 Hz.

    The harmonics were recorded on the healthy phase. The graphs show that thenoise is not limited to odd harmonics. Therefore, filtering this natural frequency

    component could be problematic and slow down the information process of the

    digital relays.

  • 8/10/2019 Torelli Za Ucinke

    78/180

    78/138

    2.6 Conclusion

    1. Results obtained from this study are in line with the existing literature and

    previous studies in this field. Maximum overvoltages are below 2.5 pu for a

    ground fault in an unloaded subtransmission line and below 4 pu in an

    unloaded line with a capacitor bank connected at the end of the line

    2. Maximum overvoltage is influenced by the power system parameters. The

    size of the neutral earth resistor itself does not give a clear indication of the

    system response and expected maximum overvoltage during a ground fault

    3. Increasing the size of the neutral earth resistor controls the maximum

    overvoltage on unloaded line as the resistor has a positive impact in limiting

    the natural frequency overvoltage until the fault current is equal to 10 % of

    the fault current with a solidly earthed system

    4. The limitation of the transitory overvoltage component is strictly connected

    to the increase of the ratio R0/X0 until the R0

  • 8/10/2019 Torelli Za Ucinke

    79/180

    79/138

    analysis and related transient studies should be carefully considered for

    long subtransmission lines as is usually done for transmission lines

    8. There is also a consistent similarity of results for line length of 10km and

    0.2km. This characteristic should be taken into consideration to optimize the

    work during planning and design activities for short and medium length

    subtransmission lines

    9. Transient overvoltages appear in the faulty and healthy phases. There is a

    relation between time of fault and location where the maximum overvoltages

    takes place

    10. There is not a strong relation between the time of fault and the magnitude of

    the maximum overvoltage during phase to ground faults. Relation between

    the magnitude of the maximum overvoltage and the time of fault is only

    relevant on the phase to phase to ground faults

    11. Considering the overvoltage component at higher frequency, this study

    shows that beyond the debate of effective or non effective grounding, design

    of the neutral earth resistors could safely aim to limit the ground fault current

    to 0.1pu of the fault current in a solidly earthed system without

    compromising the insulation level of the system

  • 8/10/2019 Torelli Za Ucinke

    80/180

    80/138

    3 CVT and Transient Overvoltages

    3.1 Overview

    Capacitive voltage transformer, CVT, represents the most common method of

    voltage source for the impedance protection relays installed for transmission and

    subtransmission power systems.

    Until few years ago the use of the CVT was limited to extra high voltage system. In

    recent years the use of the CVT has become more popular even for applicationwith nominal voltage down to 33kV (as applied by Energex and Ergon in

    Queensland) due the lower capital cost compared to the traditional voltage

    transformer, VT. CVTs also offer the advantage to couple power line carrier to

    inject teleprotection signals between substations.

    During a fault, ideally, the low voltage source provided by the CVT should be an

    exact copy of the primary voltage. Unfortunately this is not the reality. CVT

    contains a large number of stored energy components which must charge and

    discharge during voltage changes [24-29]. The transfer of energy between

    capacitances and inductances within the CVT requires some time to take place.

    Therefore, the CVT introduces some transients that affect the magnitude and

    shape of the voltage signal.

    CVT creates some problems to the distance relays especially during faults that

    severely depress the voltage at the relay location. Faults located at the beginning

    of the protected line can bring the voltage down to few percents of the nominal

    voltage and this could affect accuracy and operating time of the relay.

    This section aims to investigate the CVT transient response during phase to

    ground fault and the impact that this disturbance can have on the distance relay.

  • 8/10/2019 Torelli Za Ucinke

    81/180

  • 8/10/2019 Torelli Za Ucinke

    82/180

    82/138

    The tuning reactor is required to cancel out the value of the capacitive divider at

    the system frequency [24] . Therefore, the reactor prevents the phase shiftbetween the voltage signal at the transmission line and the voltage fed to the relay.

    The size of the reactor is tuned for the system frequency of 50 Hz. In this study the

    reactor is 111 H.

    Voltage transformer

    The voltage transformer reduces the voltage from 10-15 kV to a voltage suitable for

    the relay which is usually 100 or 110 V. Copper and iron losses were taken into

    consideration by adding in the CVT model a resistance of 2000 Ohm.

    Ferroresonance Suppression Circuit

    The ferroresonance suppression circuit is installed in the low voltage side of the

    voltage transformer to prevent dangerous overvoltages due to the saturation of the

    iron core of the step down transformer.

    Two types of ferroresonance suppression circuits are normally used by CVT

    manufacturers [24, 25, 27]:

    ! Active ferroresonance suppression circuit

    ! Passive ferroresonance suppression circuit

    The active ferroresonance suppression circuit consists of a parallel tuning circuit in

    series with a damping resistor. The LC parallel circuit behaves as an open circuit at

    the nominal power frequency to prevent shunt current flowing through the circuit.

    During transient condition the tuning circuit will decrease the impedance to the

    value of the damping resistor. The resistor will attenuate the energy of the transient

    surge [24]

  • 8/10/2019 Torelli Za Ucinke

    83/180

    83/138

    The passive ferroresonance suppression circuit has a resistor, a saturable inductor

    and air gap loading resistor. In normal condition the voltage is not high enough toflash the air gap. During transient conditions, the air gap will flash over through the

    resistor and will attenuate the transient energy.

    Existing literature and previous study demonstrated that the passive

    ferroresonance circuit has better transient performance than the active device [24,

    25, 27, 28, 31, 32]. However, as the study aims to test the CVT under the worst

    case scenario, the active suppression circuit was implemented.

    Device Data

    R= 77379 Ohms

    C=29 nF

    L=111 H

    CVT Burden

    The burden connected at the end of the circuit represents the static or numerical

    digital relays. Modern relays have a small burden. Typically the burden is below 5

    VA .

    The value of the burden is 1000 Ohms

  • 8/10/2019 Torelli Za Ucinke

    84/180

    84/138

    3.3 Simulation Settings

    Fault time

    System faults can happen at any time. Considering the two voltage magnitude end

    range, the fault could take place at 0 voltage or at maximum voltage. Fault at zero

    voltage are less common than faults at the maximum voltage. In fact, this type of

    fault could only happen during lightning or close of the circuit breaker on fault

    condition. Faults at the maximum voltage usually take place when insulation failure

    occurs and are statistically more likely to happen.

    Simulations were conducted with fault at zero crossing of the primary voltage. At

    this time the energy store in the capacitor is at the maximum and this condition will

    generate the worst voltage transient conditions. The sudden change in the system

    will release the energy stored in the active elements of the CVT creating the worst

    transient overvoltage condition. These voltage oscillations are composed of lowerand higher frequency components.

    Network and Source Settings

    66 kV subtransmission line model is as per the model used in Section 1

    (Overvoltage). The line model was set to 2 km and 10 km. Short lines were

    selected to increase the source impedance ratio, SIR, and testing the performance

    of the CVT with a higher SIR. It is reminded that SIR is the ration between the

    source impedance and the line impedance at the relay point.

  • 8/10/2019 Torelli Za Ucinke

    85/180

    85/138

    The source impedance was set to determine a starting SIR of 1 and 10 without the

    implementation of the NER. Then, the neutral earth resistor was increased toobtain the desired SIR.

    To conclude, four network models were investigated:

    ! 10km line length- SIR of 1( No NER), 5, 10, 20, 30 and 60

    ! 10km line length- SIR of 10( No NER), 20, 30 and 60

    ! 2 km line length- SIR of 1( No NER), 5, 10, 20, 30 and 60

    ! 10km line length- SIR of 10( No NER), 20, 30 and 60

  • 8/10/2019 Torelli Za Ucinke

    86/180

    86/138

    3.4 Simulation Results

    Simulations results are provided in Appendix D and summarised in the graphs here

    below:

    Transient Overvoltage- 10km line- Initial SIR 1

    0.00

    5.00

    10.00

    15.00

    20.0025.00

    30.00

    35.00

    40.00

    45.00

    50.00

    10 30 50 70

    Time (ms)

    Overvoltage(pu) SIR 1

    SIR 5

    SIR 10

    SIR 20

    SIR 30

    SIR 60

    Figure 3.1: Peak overvoltage after fault- Initial SIR 1- Line length 10 km

    Transient Overvoltage- 10km line- Initial SIR 10

    0.00

    5.00

    10.00

    15.00

    20.00

    25.00

    30.00

    35.00

    40.00

    45.00

    50.00

    10 30 50 70

    Time (ms)

    Overvoltage(pu)

    SIR 10

    SIR 20

    SIR 30

    SIR 60

    Figure 3.2: Peak overvoltage after fault- Initial SIR 10- Line length 10 km

  • 8/10/2019 Torelli Za Ucinke

    87/180