Page 1: Transducers - celsagermany.com · TRANSDUCERS Current and voltage transducers are applied for the measurement of sinusoidal alternating currents (Nominal-input current from 0,05 to

Transducers

energy management systems

06

Page 2: Transducers - celsagermany.com · TRANSDUCERS Current and voltage transducers are applied for the measurement of sinusoidal alternating currents (Nominal-input current from 0,05 to

Transducers

Page 3: Transducers - celsagermany.com · TRANSDUCERS Current and voltage transducers are applied for the measurement of sinusoidal alternating currents (Nominal-input current from 0,05 to

TRANSDUCERS

Configurable multifunctional transducers CPQT / CPQT13 page 6/1

MU for active/reactive power CPRNV page 6/3

MU for phase angle Phwd-MU page 6/7

MU for alternating current CIR page 6/9

MU for alternating voltage CUR page 6/11

MU for frecuency CFR page 6/13

MU for direct current DMI page 6/15

MU for direct voltage DMU page 6/15

MU for temperature DTV page 6/16

Limit relay GWS page 6/16

Limit relay GWR page 6/17

Isolating amplifier DTVU20 page 6/19

Page 4: Transducers - celsagermany.com · TRANSDUCERS Current and voltage transducers are applied for the measurement of sinusoidal alternating currents (Nominal-input current from 0,05 to

TRANSDUCERS

Current and voltage transducers are applied for the measurement of sinusoidal alternating

currents (Nominal-input current from 0,05 to 20A) and alternating voltages (Nominal input

voltages from 200 to 690 V). For higher currents or voltages transformers have to be con-

nected before. All transducers are able to snap on DIN rails.

Page 5: Transducers - celsagermany.com · TRANSDUCERS Current and voltage transducers are applied for the measurement of sinusoidal alternating currents (Nominal-input current from 0,05 to

6/1

MULTIFUNCTIONAL TRANSDUCER

CPQT is a configurable multi transducer for all electrical networks. Any of the

parameters can be linked to the 2 analog outputs.

The configuration is simple with the software “ConfigLQT” through the USB

port..

Configurable multifunctional transducer

Connections:

CPQT

Order informationDescription Output Article number

CPQT 2 Analog outputs 70051 - 1001

Technical DataInputs - Voltage

Input (Un) 100 – 400 V

Overload 1.5 x Un – continuously, 2 x Un – 10 s

Measuring range 0 – 500 V TRMS

Consumption Un x 1 mA / Phase

Frecuency 10…40….70…120 Hz

Inputs - Current

Input (Un) 1 – 5 A

overload 2 x In continuously, 10 x In 15 s, 40 x In 1 s

Measuring range 0 – 10 A TRMS

Load <0.05 VA / Phase

Aux. suppy

Universal current 24 – 250 VDC / 80 – 250 VAC

Consumption max 8 W

Outputs - Analog

Analog outputs 2

Range +/- 20 mA, Option: +/- 10 V

Load max 750 ohm (15V)

Response time < 100 ms

General Data

Accuracy class 0,2

Galvanic isolation Supply, in- and output are galvanically isolated

USB 1 pc for configuration

Temperature rangeOperation: -10 to +55 C° Storage -40 to +70 C°

Temperature coefficient < 0.1% / 10 C°

Test voltage 4 kV AC / min

Inputs Overvoltage cat. III

Outputs Overvoltage cat. II

Dimensions (w x h x d) 70 x 132 x 137 mm – DIN-rail

Weight approx. 0.5 kg

StandardSS-EN 60688SS-EN 601010 EN 61000-6-2 / -6-4 / -6-5

Page 6: Transducers - celsagermany.com · TRANSDUCERS Current and voltage transducers are applied for the measurement of sinusoidal alternating currents (Nominal-input current from 0,05 to

6/2

MULTIFUNCTIONAL TRANSDUCER

CPQT13 is a configurable multi transducer for all electrical networks. All of

the parameters can be linked to the 5 analog outputs.

There are 2 pulse outputs for kWh+ and kWh-.

The configuration is simple with the software “ConfigCPQT” through the USB

port.

Configurable multifunctional transducer

Connections:

CPQT13

Order informationDescription Output Article number

CPQT13 5 Analog outputs 70051 - 1000

Technical DataInputs - Voltage

Input (Un) 100 – 400 V

overload 1.5 x Un – continuously, 2 x Un – 10 s

Measuring range 0 – 500 V TRMS

Consumption Un x 1 mA / Phase

Frecuency 10…40….70…120 Hz

Inputs - Current

Input (Un) 1 – 5 A

Overload 2 x In continuously, 10 x In 15 s, 40 x In 1 s

Measuring range 0 – 10 A TRMS

Load <0.05 VA / Phase

Aux. suppy

Universal current 24 – 250 VDC / 80 – 250 VAC

Consumption max 8 W

Outputs - Analog

Number 5

Range +/- 20 mA, Option: +/- 10 V

Load max 750 ohm (15V)

Response time < 100 ms

Outputs - Digital

Number 2 ,110 V AC/DC, 100 mA

Communication

Serial RS485

General Data

Accuracy class 0,2

Galvanic isolation Supply, in- and output are galvanically isolated

USB 1 pc for configuration

Temperature rangeOperation -10 to +55 C° Storage: -40 to +70 C°

Temperature coefficient < 0.1% / 10 C°

Test voltage 4 kV AC / min

Inputs Overvoltage cat. III

Outputs Overvoltage cat. II

Dimensions (w x h x d) 150 x 70 x 73 mm – DIN-rail

Weight approx. 0.5 kg

StandardSS-EN 60688SS-EN 601010 EN 61000-6-2 / -6-4 / -6-5

Page 7: Transducers - celsagermany.com · TRANSDUCERS Current and voltage transducers are applied for the measurement of sinusoidal alternating currents (Nominal-input current from 0,05 to

6/3

TRANSDUCERS FOR POWER

Available Versions

Single phasealternatingcurrent

3-phase 3-lines current 3-phase 4-lines current

balanced load unbalanced load balanced load unbalanced load

Active power CPR/1 w NV CPR/1 d NV CPR/2 NV CPR/1 NV CPR/3 NV

Reactive power CPR/1 wb NV CPR/1 db NV CPR/2 b NV CPR/1 b NV CPR/3 b NV

Description

This transducer is applied for measuring active and reactive power of sinu-

soidal current at a frequency of 50-60Hz. They can be directly connected to

rated input currents of 0,1 to 20A and to rated input voltages of 50 to 720

V. At higher currents and/or voltages they must be preceeded by AC measu-

rement transformers.

An auxiliary voltage supply always is required. If the measurement circuit vol-

tage does not vary more than ±10% this can be used as an auxiliary energy

supply. In this case with client specification an internal connection between

measurement voltage and auxiliary voltage contacts will be carried out.

FMode of operation

Current and voltage are galvanically insulated (5.2kV/1min), multiplied, in-

tegrated and converted into an output signal (current or voltage) linearly

proportional to the active or reactive power. The addition of letter "L" in

their denomination indicates a live-zero output signal (e.g. 4-20mA).

Symetric inputBipolar output

Transducers for active and reactive power

• Class 0,5

• For mounting on DIN rail (DIN EN 50 022) or for screw fixing with 2 cylinder-head screw M4

CPRNV

Output characteristic

Life-zero Standardoutput output

Page 8: Transducers - celsagermany.com · TRANSDUCERS Current and voltage transducers are applied for the measurement of sinusoidal alternating currents (Nominal-input current from 0,05 to

6/4

TRANSDUCERS FOR POWER

Dimensions of housing D10 (CPR/1w, ..1d, ..1, 1wb, ..1db, ..1bNV)

Dimensions of housing D20 (CPR/2, ..3, ..2b, ..3bNV)

Technical Data (according to DIN EN 60688)Typ 1) CPR ... NV

Output short-circuit and open-circuit protected

Current output 0-20 mA, 4-20mA

Limiting current none or approx. 22,5 mA

Open-circuit voltage ca. 30 V

Output load 0...750 Ω , 0...1000 Ω

Variation < 1 ppm/Ω

Voltage output 0-10 V or 2-10 V

Limiting current approx. 22,5 mA

Limiting voltage ca. 18 V

Output resistance < 30 Ω

Input

Current input Available nominal ranges

100mA ...20A5...120 %

Voltage inputAvailable nominal ranges

50...720 V 40...120 %

Frecuency 45...65 Hz

Excessive inputs continuos / short duration voltage input current input

120 %5-fold20-fold

Transmission

Accuracy class 0,5 0,2

Ripple (peak-to-peak) < 1 % < 0,4 %

Response time < 0,3 s < 0,6 s

Drift vs. temperature (0...45ºC) < 200 ppm/ºK

Drift vs. auxiliary supply < 20 ppm/V

Auxiliary supply voltageAC DC

90...110 %85...125 %

Nominal consumption

Measuring input < 1 W

Auxiliary supply input < 3 W

1) other values on request.

Order exampleProduct Input Output @ KW @ V

CPR/1wNV @/1A (Please indicate on the order) 0 ...20 mA Please indicate on the order Please indicate on the order

CPR/1dNV @/1A (Please indicate on the order) 4 ...20 mA Please indicate on the order Please indicate on the order

CPR/2NV @/1A (Please indicate on the order) 0 ...10 V Please indicate on the order Please indicate on the order

CPR/1NV @/1A (Please indicate on the order) 2 ...10 V Please indicate on the order Please indicate on the order

Order information for CPR...NV

Page 9: Transducers - celsagermany.com · TRANSDUCERS Current and voltage transducers are applied for the measurement of sinusoidal alternating currents (Nominal-input current from 0,05 to

6/5

TRANSDUCERS FOR POWER

Single phaseAC current

Active power

CPR/1 w NV

3-Phase Current 3-wires

Active power

balanced load

CPR/1 d NV

3-Phase Current 3-wires

Active power

unbalanced load

CPR/2 NV

3-Phase Current 4-wires

Active power

balanced load

CPR/1 NV

3-Phase Current 4-wires

Active power

unbalanced load

CPR/3 NV

Page 10: Transducers - celsagermany.com · TRANSDUCERS Current and voltage transducers are applied for the measurement of sinusoidal alternating currents (Nominal-input current from 0,05 to

6/6

TRANSDUCERS FOR POWER

Single phaseAC current

Reactive power

CPR/1 wb NV

3-Phase Current 3-wires

Reactive power

balanced load

CPR/1 db NV

3-Phase Current 3-wires

Reactive power

unbalanced load

CPR/2 b NV

3-Phase Current 4-wires

Reactive power

balanced load

CPR/1 b NV

3-Phase Current 4-wires

Reactive power

unbalanced load

CPR/3 b NV

Page 11: Transducers - celsagermany.com · TRANSDUCERS Current and voltage transducers are applied for the measurement of sinusoidal alternating currents (Nominal-input current from 0,05 to

6/7

TRANSDUCERS FOR PHASE ANGLE

Life-zero StandardOutput Output

Transducers for phase angle (COS φ)

• Class 0,5

• For mounting on DIN rail (DIN EN 50 022)

Description

The transducers Phwd-MU is used to convert and isolate the phase angle bet-

ween current and voltage of an AC and three-phase mains of balanced load

into a load-independent direct-current and direct voltage signal.

Conformity

This equipment conforms to the requirements of the Directive from the Council

of the European Community on the harmonisation of the member states re-

garding electromagnetic compatibility, EMC Directive 2004/108/EC, as

well as Low Voltage Directive 2006/95/EC.

Application

The measuring transducer Phwd-MU serve to convert and isolate the phase

angle between current and voltage of an AC and three-phase mains of ba-

lanced load into a load-independent direct-current and direct-voltage signal.

Function

The quantities to be measured will get via internal current transformers and

voltage divider to the null comparator. At the null comparator there is a rec-

tangular signal which is directly connected with the phase angle. A subse-

quent integrating step forms the direct-voltage mean value. This direct voltage

will be converted into a load-independent direct current and into an impres-

sed direct voltage. The galvanic separation between input and output signals

is effected by means of an optocoupler. The secondary amplifiers will supply

the load- independent direct current and direct-voltage signals. Both outputs

are no-load resistant and short-circuit proof. Any connection between both

outputs will be unacceptable. An auxiliary voltage will be required.

Phwd - MU

Characteristic lines: Output characteristics

4 - Quadrantal operation (Option)

cap.Received

ind.Supplied

cap.Supplied

ind.Received

Supplied Supplied

Received Received

cap.

cap.

ind.

ind.

Aux. supply

Current- impression

Voltage- impression

null-comparator

Page 12: Transducers - celsagermany.com · TRANSDUCERS Current and voltage transducers are applied for the measurement of sinusoidal alternating currents (Nominal-input current from 0,05 to

6/8

TRANSDUCERS FOR PHASE ANGLE

Connections

Dimensions

Technical Data (according to DIN EN 60688)Input

Input quantity Phase angle between sinusoidal current andvoltage in AC (or) three-phase systems

Rated value-60° - 0 - +60° electrical, cos phi 0,5 cap - 1 - 0,5 ind or-45,6 ° - 0 - +72,5 °electrical, cos phi 0,7 cap - 1 - 0,3ind

Rated voltage 100 V, 110 V, 230 V, 400 V, 500 V or 600 V(690 V in ground installation)

Rated current 1 A or 5 A , 0,3 VA

Rated frequency 50 Hz, 60 Hz or 400 Hz

Permanent overload voltage 1,2-fold, current 2-fold

Surge overload voltage 2-fold 1 sec., current 20-fold 1 sec.

Output

Output quantitiesproportional direct current and proportional direct voltage When using both outputs at the same time the voltage out-put must be charged with max. 1 mA.

Doble output0-20 mA/ 0-500 Ohm burden and 0-10 V max. 10 mA load, as well as 4-20 mA/0-500 Ohm burden and 2-10V max. 10 mA load, switchable at the front.

Options

4 Quadrant Operation for AC or three phase current with two-sided energy directionFrequency control a value of 0-5 Hz bis 0-10 kHz“ Open-collector” NPN, max. 30 V 100 mA resilient, Pulse/ pause 50/50 % Square wave signal 5 V, max. 10 mA load, pulse /

break 50/50 %

Dynamic system behaviour

Accuracy +/- 0,5 % (linear to the angular degrees)

Current range 4-200 % of the rated current

Current influence < 0,5 % for 0,15 up to a twice rated current

Voltage influence < 0,1 % for +/- 10 % of rated voltage

Frequency influence < 0,1 % with difference frequency 10 Hz

Temperature range -15 up to + 20 up to +30 bis +55 °C

Temperature influence < 0,2 % at 10 K

Influence of Aux. none

Load influence none

External magneticfield influence none (up to 400 A/m)

Residual ripple < 30 mVss

Response time < 400 ms

Open-circuit voltage max. 24 V

Current limitation max. 2-fold in case of saturation

Aux. suppy 230 V AC +/- 20 %, 45-65 Hz, 2,5 VA

Option110 V AC +/i 20 %, 45-65 Hz, 2,5 VA24 V DC, -15 % up to + 25 %, 2 W, (EMV DIN EN 61326 Class A)

Wide range aux. supply (Option)

6-30 VAC + DC or 36-265 VAC + DC, 2 VA,(EMV DIN EN 61326 Class A)

Weight Standard type 200 g

Regulations

EMV DIN EN 61326

Mechanical strength DIN EN 61010 Part 1

Electric security

DIN EN 61010 part 1Housing all insulated, protection class II,at a working voltage up to 300V (network to neutral con-ductor) degree of pollution 2, overvoltage category CAT IIIat a working voltage up to 600V (network to neutral con-ductor) degree of pollution 2, overvoltage category CAT II

Accuracy, overload DIN EN 60688

Separation DIN EN 61010 Part 1, 3,52 kV 50 Hz 10 sec.

Air gaps and creep distance DIN EN 61010 Part 1

System protection DIN EN 60529 Housing IP30, terminal IP20

Connections DIN 43807

Order information for Phwd-MU

Order exampleProduct Input

Output

Phwd-MU 380 V / 5 A 4 ...20 mA / 37º - 0 - 53º

Phwd-MU 110 V / 5 A 4 ...20 mA / 60º - 0 - 60º

Page 13: Transducers - celsagermany.com · TRANSDUCERS Current and voltage transducers are applied for the measurement of sinusoidal alternating currents (Nominal-input current from 0,05 to

6/9

TRANSDUCERS FOR ALTERNATING CURRENT

CIR

Technical Data (according to DIN EN 60688)Typ 1) CIR CIR/IOutput short-circuit and open-circuit protected short-circuit and open-circuit protectedCurrent output 0 ...20 mA 4 ...20 mALimit current none or approx. 22,5 mA approx. 22,5 mAOpen-circuit voltage approx. 30V approx. 30VOutput load 0 - 750 Ω 0 - 750 ΩVariation < 50% < 1ppm/ΩVoltage output 0 ...10V 0 ...10VLimiting current none or approx. 22,5 mA < 30 ohmLimiting voltage approx. 18V approx. 18VOutput resistance 500 Ω < 30 ΩInput 1A or 5A (Please indicate on the order) 1A or 5A (Please indicate on the order)Working range 50 ...120% 5 ...120%Frequency of input quantity 45 ...55 Hz. (Opt. 55-65Hz) 45 ...65 Hz.

Excessiv inputs (overload)continuos short duration (1s)Voltage inputCurrent Input

120 %

2 fold20 fold

120 %

5 fold20 fold

Accuracy class 0,5 0,5

Ripple (peak-to-peak)100 Ω: <6%750 Ω: <1%

< 1%

Response time100 Ω: <0,4s750 Ω: <0,8s

< 0,15s

Drift vs. temperature (0 ...45ºC)

Drift vs. Aux. suppy

< 1%

---< 200ppm/ºK< 20ppm/V

Aux. suppy 2)

AC

DC

passive------

external aux. suppy50 ...110%50 ...125%

Nominal consumption measuring input

Nominal consumption aux. suppy input3W---

1W3W

1) other values on request. 2.) According to DIN EN 60688 a nominal range of use from 80...120% (for AC) and 85...125% (for DC) is required. 50...120% or 50...125% is valid in consideration of the decre-sead load capability according to the auxiliary supply diagrams.

Application

The transducers are to be applied for the measurement of alternating currents

(Nominal input currents 1 or 5 A).

Mode of operation

The input value is being galvanically insulated (5 kV / 1 min), rectified (ave-

raging) and transformed into a proportional, graven direct current.

The CIR doesn’t require any auxiliary supply. The type CIR/I is active (Output

4...20 mA) and requires some auxiliary supply of 230V AC or 24V DC.

Design

The small design of measuring converts with a width of only 22,5 mm is reali-

zed , as well, by a precise selection of components, as by a precise coordi-

nation of components and circuits, geared to power requirements and

warming. The low power loss allows mounting of any quantity of transducers

side by side, within the operating temperature range, without need to consi-

der of minimum distances.

Transducers for alternating current

• Class 0,5

• For mounting on DIN rail (DIN EN 50022-35)

• only 22,5mm width

• Load resistance up to 1000 Ohm @ 20mA

Page 14: Transducers - celsagermany.com · TRANSDUCERS Current and voltage transducers are applied for the measurement of sinusoidal alternating currents (Nominal-input current from 0,05 to

6/10

TRANSDUCERS FOR ALTERNATING CURRENT

Connection diagrams

Current output

Voltage output

DimensionsOrder exampleProduct Input Output Aux. suppy

CIR 1A 0 ...20 mA ---

CIR 5A 0 ...10 V ---

CIR/I 1A 0 ...10 V 24 V DC

CIR/I 5A 4 ...20 mA 230 V AC

Order information for CIR

Output

Input

Output

Input

Output

Input

Output

Input

Output

Input

Output

Input

Aux. supply 230V AC Aux. supply 24V DC

Aux. supply 230V AC Aux. supply 24V DC

Page 15: Transducers - celsagermany.com · TRANSDUCERS Current and voltage transducers are applied for the measurement of sinusoidal alternating currents (Nominal-input current from 0,05 to

6/11

TRANSDUCERS FOR ALTERNATING VOLTAGE

CUR

Description

The transducers are to be applied for the measurement of alternating voltages

(Nominal input voltages 100 to 690 V). Please indicate the exact voltage

on the order. For higher voltage transformers to be inserted before.

Mode of operation

The input value is being galvanically insulated (5 kV / 1 min), rectified (ave-

raging) and transformed into a proportional, graven direct current. The CUR

doesn’t require any auxiliary supply. The type CUR/I is active (Output 4...20

mA) and requires some auxiliary supply of 230V AC or 24V DC

Design

The small design of measuring converts with a width of only 22,5 mm is reali-

zed , as well, by a precise selection of components, as by a precise coordi-

nation of components and circuits, geared to power requirements and

warming. The low power loss allows mounting of any quantity of transducers

side by side, within the operating temperature range, without need to consi-

der of minimum distances.

Transducers for alternating voltage

• Class 0,5

• For mounting on DIN rail (DIN EN 50022-35)

• only 22,5mm width

• Load resistance up to 1000 Ohm @ 20mA

Technical Data (according to DIN EN 60688)Typ 1) CUR CUR/IOutput short-circuit and open-circuit protected short-circuit and open-circuit protectedCurrent output 0 ...20 mA 4 ...20 mALimit current none or approx. 22,5 mA approx. 22,5 mAOpen-circuit voltage approx. 30V approx. 30VOutput load 0 - 750 Ω 0 - 750 ΩVariation < 50% < 1ppm/ΩVoltage output 0 ...10V 0 ...10VLimiting current none or approx. 22,5 mA < 30 ohmLimiting voltage approx. 18V approx. 18VOutput resistance 500 Ω < 30 ΩInput 100 ... 720V (Please indicate on the order) 100 ... 720V (Please indicate on the order)Working range 50 ...120% 5 ...120%Frequency of input quantity 45 ...55 Hz. (Opt. 55-65Hz) 45 ...65 Hz.

Excessiv inputs (overload)continuos short duration (1s)Voltage inputCurrent Input

120 %

2 fold20 fold

120 %

5 fold20 fold

Accuracy class 0,5 0,5

Ripple (peak-to-peak)100 Ω: <6%750 Ω: <1%

< 1%

Response time100 Ω: <0,4s750 Ω: <0,8s

< 0,15s

Drift vs. temperature (0 ...45ºC)

Drift vs. Aux. suppy

< 1%

---< 200ppm/ºK< 20ppm/V

Aux. suppy 2)

AC

DC

passive------

external aux. suppy50 ...110%50 ...125%

Nominal consumption measuring input

Nominal consumption aux. suppy input3W---

1W3W

1) other values on request. 2.) According to DIN EN 60688 a nominal range of use from 80...120% (for AC) and 85...125% (for DC) is required. 50...120% or 50...125% is valid in consideration of the decre-sead load capability according to the auxiliary supply diagrams.

Page 16: Transducers - celsagermany.com · TRANSDUCERS Current and voltage transducers are applied for the measurement of sinusoidal alternating currents (Nominal-input current from 0,05 to

6/12

TRANSDUCERS FOR ALTERNATING VOLTAGE

Dimensions

Connections diagrams

Current output

Voltage output

Order exampleProduct Input Output Aux. suppy

CUR 500V 0 ...20 mA ---

CUR 500V 0 ...10 V ---

CUR/I 500V 0 ...20 mA 230V AC

CUR/I 500V 0 ...10 V 24V DC

Order information for CUR

Output

Input

Output

Input

Output

Input

Output

Input

Output

Input

Output

Input

Aux. supply 230V AC Aux. supply 24V DC

Aux. supply 230V AC Aux. supply 24V DC

Page 17: Transducers - celsagermany.com · TRANSDUCERS Current and voltage transducers are applied for the measurement of sinusoidal alternating currents (Nominal-input current from 0,05 to

6/13

TRANSDUCERS FOR FREQUENCY

Description

The transducer series CFRNV are to be applied for measuring frequencies in

a range 40 to 70Hz (to be specified). Rated input voltages are from 50 to

720V. The dynamic range goes from 20 to 120%

Mode of operation

The input value is being galvanically insulated (5kV/1min), a frequency

proportional value is calculated and this is converted into a proportional

and load-independent DC current (or DC voltage). Auxiliary supply is re-

quired, standard 24VDC or 230VAC.

Characteristic line

f1 = lower measuring frequency(can’t be used for the determination oferror limit).

f2 = upper measuring frequency (final value of measuring range for deter-mination of the error limit).

CFRNV

Transducers for frecuency

• only 22,5mm width

• Load resistance up to 1000 Ohm @ 20mA

Connections diagrams

Aux. supply 230V ACOutput: 0(4) - 20mA

Aux. supply 230V ACOutput: 0(2) - 10 V

Aux. supply 230V ACOutput: 0(4) - 20mA

Aux. supply 230V ACOutput: 0(2) - 10 V

Page 18: Transducers - celsagermany.com · TRANSDUCERS Current and voltage transducers are applied for the measurement of sinusoidal alternating currents (Nominal-input current from 0,05 to

6/14

TRANSDUCERS FOR FREQUENCY

Dimensions

Technical Data (according to DIN EN 60688)Typ 1) CFRNV

Output short-circuit and open-circuit protected

Current output 0-20 mA

Limiting current none or approx. 22,5 mA

Open-circuit voltage ca. 30 V

Output load 0...750 Ω , 0...1000 Ω

Variation < 1 ppm/Ω

Voltage output 0-10 V or 2-10 V

Limiting current none or approx. 22,5 mA

Limiting voltage approx. 18 V

Output resistance < 30 Ω

Input

Measuring range45...55Hz; 47...53Hz;55...65Hz; 57...63Hz;45...65Hz;

Voltage input 50...720 V

Available nominal ranges 20...120 %

frecuency 40...70 Hz

Excessive inputs continuos / short duration voltage input

120 %2-fold

Transmission

Accuracy class 0,5 0,2

Ripple (peak-to-peak) < 1 % < 0,4 %

Response time < 0,4 s < 0,8 s

Drift vs. temperature (0...45ºC) < 1% < 0,5 %

Auxiliary supply voltage

AC DC

90...110 %85...125 %

Nominal consumption

Measuring input < 1 W

Auxiliary supply input < 3 W

1) other values on request.

Order exampleProduct Measuring range Input Output Aux. suppy

CFRNV 45-55 Hz 100V 4 ...20 mA 230V AC

CFRNV 55-65 Hz 230V 4 ...20 mA 230V AC

CFRNV 45-65 Hz 220V 0 ...20 mA 220V AC

CFRNV 47-53 Hz 100V 0 ...20 mA 24V DC

Order information for CFRNV

Page 19: Transducers - celsagermany.com · TRANSDUCERS Current and voltage transducers are applied for the measurement of sinusoidal alternating currents (Nominal-input current from 0,05 to

6/15

TRANSDUCERS FOR DIRECT CURRENT / VOLTAGE

Technical DataInput Strom DC(0,01 - 15 A)* Protection class housing IP 30

Output All standard signals** Max. consumption 2 W

Max. burden 750 Ω Width 22,5 mm

Auxiliary voltage supply 20 - 250 V AC/DC Lenght 80 mm

Fuse max. 16 A Height 79 mm

Ambient temperature -10 – +65 °C Material of housing PA

Storage temperature -40 – +70 °C Colour Green

Connection wire square size 1,5 qmm Weight 90 - 120 gr.

Protection class terminals IP 10 Class 0,5

* Input current has to be indicated for ordering Transducer is completly galvanic insulated.

** Output signal has to be indicated for ordering

Dimensions DMI / DMU Connections DMI / DMU

Order information for DMI

DMI (Transducers for direct current)

DMU (Transducers for direct voltage)

Technical DataInput Voltage DC (0,01 - 500 V)* Protection class housing IP 30

Output All standard signals** Max. consumption 2 W

Max. burden 1000 Ω Width 22,5 mm

Auxiliary voltage supply 20 - 250 V AC/DC Lenght 80 mm

Fuse max. 16 A Height 79 mm

Ambient temperature -10 – +65 °C Material of housing PA

Storage temperature -40 – +70 °C Colour Green

Connection wire square size 1,5 qmm Weight 90 - 120 gr.

Protection class terminals IP 10 Class 0,5

* Input current has to be indicated for ordering Transducer is completly galvanic insulated.

** Output signal has to be indicated for ordering

Order exampleProduct

InputMeasuring range from .. to ...A DC

Output

DMI 0 - 5 A DC 4 ...20 mA

DMI 0 - 10 A DC 0 ...20 mA

DMI 0 - 6 A DC 0 ...10 V

Order information for DMU

Order exampleProduct

InputMeasuring range from .. to ...V DC

Output

DMU 0 - 150 V DC 4 ...20 mA

DMU 0 - 100 mV DC 0 ...20 mA

DMU 0 - 20 V DC 0 ...10 V

Page 20: Transducers - celsagermany.com · TRANSDUCERS Current and voltage transducers are applied for the measurement of sinusoidal alternating currents (Nominal-input current from 0,05 to

6/16

TRANSDUCERS FÜR TEMPERATUR / GRENZWERTRELAIS

Dimensions DTV / GWS Connections DTV / GWS

DTV (Transducers for temperature)

Technical DataInput PT100/1000/Thermocouple*)* Protection class housing IP 30

Output All standard signals** Max. consumption 2 W

Max. burden 1000 Ω Width 22,5 mm

Auxiliary voltage supply 20 - 250 V AC/DC Lenght 109 mm

Fuse max. 16 A Height 108 mm

Ambient temperature -10 – +65 °C Material of housing PA

Storage temperature -40 – +70 °C Colour Green

Connection wire square size 1,5 qmm Weight 110 gr.

Protection class terminals IP 10 Class 0,1

* Input current has to be indicated for ordering Transducer is completly galvanic insulated.

** Output signal has to be indicated for ordering

GWS (Limit relay)

Technical DataInput Current/Voltage AC/DC* Protection class housing IP 30

Output 1 change over switch** Max. consumption 2 W

Max. burden 250 V 5 A AC Width 22,5 mm

Auxiliary voltage supply 20 - 250 V AC/DC Lenght 110 mm

Fuse max. 16 A Height 100 mm

Ambient temperature -10 – +65 °C Material of housing PA

Storage temperature -40 – +70 °C Colour Green

Connection wire square size 1,5 qmm Weight k.A-

Protection class terminals IP 10 Class 0,1

* Input current/voltage has to be indicated for ordering Transducer is completly galvanic insulated.

** 2 insulated change over switches on request

Order information for DTV

Order example

Product InputInputMeasuring rangefrom .. to...A DC

Wire Output

DTV PT100 0 - 100 ºC 3+4 - wire 4 ...20 mA

DTV PT1000 -30 ... +30 ºC 3 - wire 0 ...10 V

DTV Thermocouple 0 - 200 ºC - 0 ...20 mA

Order information for GWS

Order example

ProductInputCurrent/voltageAC/DC

InputMeasuring rangefrom .. to ...V DC

Output* Onrequest: with 2 insul-taed change over switches

GWS alternating current 0 - 1 A AC 1 change

GWS direct voltage 0 - 100 mV DC 1 change

GWS direct current 4 - 20 mA2 insulated changeover switches

Page 21: Transducers - celsagermany.com · TRANSDUCERS Current and voltage transducers are applied for the measurement of sinusoidal alternating currents (Nominal-input current from 0,05 to

6/17

LIMIT RELAY

Description

The electronical limit value relay type GWR is applied to control direct current

or alternating current as well as direct voltage or alternating voltage. The AC

variables of any curve shape are measured as r.m.s values.

Conformity

This equipment conforms to the requirements of the Directive from the Council

of the European Community on the harmonisation of the member states re-

garding electromagnetic compatibility, EMC Directive 2004/108/EC, as

well as Low Voltage Directive 2006/95/EC.

Application

The limiting values are adjustable in steps of 1 % by means of coding swit-

ches. The delay in response as well as closed-circuit and open-circuit current

principles can be selected. The instantaneous switching condition of the out-

put relay is indicated by means of light-emitting diodes. The limit value relays

are installed in a housing of 22,5 mm of breadth and can be mounted on

DIN-rail. They are extremely solid and do not dispose of any mechanically

movable parts except the output relay. Thus they are very suitable for hard

operating conditions.

Limit relay

• Switching accuracy +/- 1%

• Type GMA with digital display and programing on request)

• For mounting on DIN rail (DIN EN 50 022 - 35)

Dimensions

Connections

GWR

Page 22: Transducers - celsagermany.com · TRANSDUCERS Current and voltage transducers are applied for the measurement of sinusoidal alternating currents (Nominal-input current from 0,05 to

6/18

LIMIT RELAY

Technical Data (according to DIN EN 60688)Input

Input quantity

direct current or direct voltage, alternating current or alter-nating volta-ge; the AC variables of any curve shape (up tocrest factor 4) are measured as root mean square in therange of DC + AC 40 to 1000 Hz

Setting of the limitvalue

0-99% in steps of 1%

Relay point 1 change-over contact

Functional displayred LED lights up in case of relay drop-outgreen LED lights up in case of relay pick up

Testing voltage4 kV between measurement input and relay as well asaux.voltage

Switching operation

Switching accuracy +/- 1 % of the final value of the measurement range

Hysteresis approx. 4 % of the limit value

Delay in response adjustable between 0,1 and 10 sec.

Switching conditions closed-circuit or open-circuit current principle, optional

Temperature range -15 to +20 up to +30 up to +55 °C

Temperature effect < 0,1 % at 10 K

Overload capacibilityvoltage input: fivefold (750 V max.)current input: twofold, permanent, 20-fold 1 sec. (50 Amax.)

Switching capacibility max. 8 A, 250 V, 2000 VA

Auxiliary voltage 230 V AC ± 15 %, 45-65 Hz, 2,5 VA

Optional110 V AC ± 15 %, 45-65 Hz, 3 VA24 V DC, -15 % up to +25 %, 2,5 W, (EMC DIN EN 61326 class A)

Wide range aux. sup-ply

6-30 V AC + DC or 36-265 V AC + DC, 2 VA, (EMC DIN EN 61326 class A)

Measuring range

Alternating/direct cur-rent AC+DC effective

Adjustable Internal resistantfrom to

10 A 0,1 A 9,9 A 0,006 Ohm

5 A 0,05 A 4,95 A (5A =100 %) 0,012 Ohm

1 A 0,01 A 0,99 A 0,06 Ohm

100 mA 1 mA 99 mA 0,6 Ohm

10 mA 0,1 mA 9,9 mA 6 Ohm

20 mA (just direct-current DC) 0,2 mA 19,8 mA (20 mA=100 %) 3 Ohm

4 - 20 mA (just direct-current DC) 4 mA 19,84 mA (20 mA=100 %) 3 Ohm

Alternating/direct vol-tage AC+DC effective

Adjustable Internal resistantfrom to

500 V 5 V 495 V 1 MOhm

100 V 1 V 99 V 1 MOhm

10 V 0,1 V 9,9 V 100 kOhm

1 V 0,01 V 0,99 V 10 kOhm100 mV (just direct-voltageDC)

1 mV 99 mV 1 kOhm

4 - 20 mA (just direct-voltageDC)

0,6 mV 59,4 mV (60 mV=100 %) 1 kOhm

Vorschriften

EMC DIN EN 61326

Mechanical strength DIN EN 61010 Part 1

Electrical security

DIN EN 61010 part 1housing all insulated, protection class II, at a working vol-tage up to 300V (network to neutral conductor) degree ofpollution 2, overvoltage category CAT III, at a working vol-tage up to 600V (network to neutral conductor) degree of pollution 2, overvoltage category CAT II

Order information for GWR

Order example

ProductInputMeasuring range from .. to ...A DC

Aux. suppy

GWR 0 - 100mV 230 V AC

GWR 4 - 20 mA DC 230 V AC

Page 23: Transducers - celsagermany.com · TRANSDUCERS Current and voltage transducers are applied for the measurement of sinusoidal alternating currents (Nominal-input current from 0,05 to

6/19

UNIVERSAL ISOLATING AMPLIFIER

Application

The universal isolating amplifier DTVU20 is applied for transforming standard

signals. It can be used in complex measuring and control circuits, process

data acquisition systems, data-loggers and multiplex. In remote control sy-

stems detectors and sensors, which are connected on central points by long

leads, can be isolated.

Selection of input-ranges is made by the frontside-switch at the DTVU20. The

different outputs are selected by connecting to the relevant clamps. Input, au-

xiliary and output are galvanic separated (3-way-separation). Isolation-vol-

tage is 2kV. The DTVU20 can work with input of 0-10 V, 0-20 mA or 4-20

mA. The output can be selected of 0-10 VDC, 2-10 VDC, 0-20 mA or 4-20

mA.

Technical DataAuxiliary supply 24-230 V AC/DC

Consumption 2,8 VA

Ambient temperature -10 to +65 °C

Storage temperature - 40 to +70º C

Protection class housing IP30

Housing Polyamid, for mounting on DIN rail(DIN EN 5022-35

Weight approx.105 g

RegulationsEN 60204-1/ VDE 0113VDE 0110/ IEC 664EMC according EN 50081-1 and 50082-2

Input resistence V=20 kΩ / V, I:50 Ω

Output 4-20 mA, 0-20 mA, 0-10 V, (burden max. 1000 Ohm)

Accuracy 0,1º%

Position of switch Input Output

0-0 0-20mA/0-10V 0-20mA/0-10V0-0 4-20mA/2-10V 4-20mA/2-10V 4-0 4-20mA/2-10V 0-20mA/2-10V 0-4 0-20mA/0-10V 4-20mA/0-10V

Output signal ± 6%Offset adjustment

Dimensions

Connections

Universal isolating amplifier

• For standard signals – with wide range power supply

• For mounting on DIN rail (DIN EN 50 022 - 35

DTUV20

Order information for DTVU20

Order exampleProduct

Position ofswitch

Input Output

DTVU20 0 - 0 0 - 20 mA / 0 - 10V 0 - 20mA / 0 - 10V

DTVU20 0 - 0 4 - 20 mA / 2 - 10V 4 - 20 mA / 2 - 10V

DTVU20 4 - 0 4 - 20 mA / 2 - 10V 0 - 20 mA / 2 - 10V

DTVU20 0 - 4 0 - 20 mA / 0 - 10V 4 - 20 mA / 0 - 10V

Page 24: Transducers - celsagermany.com · TRANSDUCERS Current and voltage transducers are applied for the measurement of sinusoidal alternating currents (Nominal-input current from 0,05 to