transformer oil specifications
TRANSCRIPT
TRANSFORMER OIL SPECIFICATIONS
BYCENTRAL INSULATING OIL TESTING LABORATORY
TRANSFORMER OIL SPECIFICATIONS
• NEW OIL:
• An unused mineral insulating oils intended to use in transformers for insulation and cooling purpose.
• IS-335/1993 – Specification for uninhibited
new insulating oils.
• IS-12463/1988 – Specification for inhibited
mineral insulating oils.
TRANSFORMER OIL SPECIFICATIONS
• IEC -60296/2003 – Specification for unused mineral insulating oils for transformers and switchgear. This standard cover both uninhibited and inhibited oils.
• ASTM – D3487/2000- Standard Specification for Mineral Insulating Oil used in Electrical apparatus. This standard also covers both uninhibited and inhibited oils.
TRANSFORMER OIL SPECIFICATIONS
• Unused Mineral Insulating oils filled in New transformers
• IS – 1866/2000 – Code of Practice for Electrical Maintenance and supervision of Mineral Insulating oil in Equipment.
(Refer Table.1 for limiting values of various parameters)
• IEC – 60422/1998 – Supervision and maintenance guide for mineral insulating oils in electrical equipment.
TRANSFORMER OIL SPECIFICATIONS
• In service Mineral Insulating oils:
• IS – 1866/2000 – Code of Practice for Electrical Maintenance and supervision of Mineral Insulating oil in Equipment.
(Refer Table.2 for limiting values of various parameters)
TRANSFORMER OIL SPECIFICATIONSIS-335/1993
• Appearance ------------• Density at 29.5˚C (Max)• Kinematic Viscosity (Max)
1) at 27˚C ------------------
2) at 40˚C ------------------• IFT at 27˚C (Min) ---------• Flash Point (Min) ---------• Pour Point (Max) ---------• Neutralization Value
1) total Acidity (Max) ----
2) Inorganic acidity ------• Corrosive Sulphur -------
• Clear and transparent• 0.89 g/cm2
• 27 cSt• Under consideration• 0.04 N/m• 140˚C• -6˚C
• 0.03 mg KOH/gm• Nil• Non-corrosive
TRANSFORMER OIL SPECIFICATIONSIS-335/1993
• Electric Strength (BDV) 1) New unfiltered Oil(Min) 2) After filteration (Min)
• Dielectric dissipation factor (tan δ)at 90˚C(max)
• Specific resistance (Resistivity)
1) at 90˚C (Min) 2) at 27˚C (Min)• Oxidation Stability 1) Acidity (max) 2) total sludge (max)
• 30 KV (rms)• If the above value is not
attained, the oil shall be filtered to 60 KV (rms)
• 0.002
• 35 x 1012 ohm-cm• 1500 x 1012 ohm-cm
• 0.4 mg KOH/gm• 0.1 % by weight
TRANSFORMER OIL SPECIFICATIONSIS-335/1993
• Ageing characteristics
a) Resistivity (Min)
1) at 27˚C
2) at 90˚C
b) Tanδ at 90˚C (Max)
c) Total acidity (Max)
d) Total sludge (Max)• Presence of Oxidation
inhibitor
• Water content• SK value
• 2.5 x 1012 ohm-cm• 0.2 x 1012 ohm-cm• 0.20• 0.05 mg KOH/gm• 0.05 % by weight• The oil shall contain
natural anti oxidant additives.
• 50 ppm• Under consideration
TRANSFORMER OIL SPECIFICATIONSIS-1866/2000-Recommended Limits of Unused Mineral Oil filled in New
Transformer
Property Highest voltage of Equipment (KV)
<72.5 72.5-170 >170
Appearance Clear, Free from sediment and suspended matter
Density at 29.5˚C (g/cm2),Max 0.89 0.89 0.89
Viscosity at 27˚C (cSt),Max 27 27 27
Flash Point (˚C),Min 140 140 140
Pour Point (˚C),Max -6 -6 -6
Total acidity(mgKOH/gm),Max 0.03 0.03 0.03
Water content (ppm), Max 20 15 10
IFT at 27˚C (mN/m),Min 35 35 35
Tanδ at 90˚C, Max 0.015 0.015 0.010
Resistivity at 90˚C(x10e12ohm-cm),Min
6 6 6
BDV (KV),Min 40 50 60
TRANSFORMER OIL SPECIFICATIONSIS-1866/2000-Violation Limits for in service oils
Property Highest voltage of Equipment (KV)
<72.5 72.5-170 >170
Appearance Clear and without visual contaminations
Water content (ppm), Max No Free water 40 20
BDV (KV),Min 30 40 50
Total acidity(mgKOH/gm),Max 0. 3 0. 3 0. 3
IFT at 27˚C (mN/m),Min 15 15 15
Resistivity at 27˚C(x10e12ohm-cm),Min
1 1 1
Resistivity at 90˚C(x10e12ohm-cm),Min
0.1 0.1 0.1
Tanδ at 90˚C, Max 1.0 1.0 0.2
Flash Point (˚C),Min Maximum decrease of 15˚C from initial value
Sediment and sludge No sediment or precipitable sludge should be detected. Results below 0.02% by mass may be neglected.
TRANSFORMER OIL SPECIFICATIONSIS-1866/2000-Frequency of testing
Property Frequency of testing
Appearance In conjunction with other Quantitative tests
Water content After filling or refilling prior to energizing, then after three and 12 months, subsequently along with DGA
BDV After filling or refilling prior to energizing, then yearly
Total acidity Yearly
IFT After filling or refilling prior to energizing, then yearly
Resistivity After filling or refilling prior to energizing, then yearly
Tanδ After filling or refilling prior to energizing, then yearly
Flash Point Yearly
Sediment and sludge Yearly
TRANSFORMER OIL SPECIFICATIONSIS-1866/2000-Recommended Actions
Property Recommended Actions
Appearance As dictated by other tests
Water content Check Source of water and consider reconditioning
BDV Recondition the oil or alternatively, if more economical or other tests dictate replace oil
Total acidity Replace or reclaim oil
IFT Replace or reclaim oil
Resistivity Replace or reclaim oil
Tanδ Replace or reclaim oil
Flash Point Replace the oil, equipment may require inspection
Sediment and sludge Where sediment is detected recondition the oil
TRANSFORMER OIL SPECIFICATIONSIS-1866/2000-Classification of oils in service.
• Group 1:
This group contains oils that are in satisfactory condition for continued use. The frequency can be followed as described earlier.
TRANSFORMER OIL SPECIFICATIONSIS-1866/2000-Classification of oils in service.
• Group 2:
This group contains oils that requires reconditioning for further service. (Low BDV and High water content). The frequency can be followed as described earlier after reconditioning.
TRANSFORMER OIL SPECIFICATIONSIS-1866/2000-Classification of oils in service.
• Group 3:
This group contains oils in poor condition that it can restore satisfactory properties only after reclaiming. Insulating oils this group should be reclaimed or replaced depending on economic considerations.
TRANSFORMER OIL SPECIFICATIONSIS-1866/2000-Classification of oils in service.
• Group 4:
This group contains oils, in such poor state that it is technically advisable to dispose of them.
TRANSFORMER OIL SPECIFICATIONSIEC -60296 – General Specification
• Functional Properties: Viscosity, Pour point, Water content, BDV,
Density, Tanδ.• Stability Properties: Appearance, Acidity, IFT, corrosive Sulfur,
Antioxident additive• Performance Properties: Oxidation Stabillity, Sludge• HSE Properties: Flash Point, PCB content, PCA content