transformer protection open lecture

Upload: daniel-delafuente

Post on 02-Apr-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/27/2019 Transformer Protection Open Lecture

    1/63

    Hands On Relay SchoolTransformer Protection Open Lecture

  • 7/27/2019 Transformer Protection Open Lecture

    2/63

    Hands On Relay SchoolTransformer

    Protection

    Open

    Lecture

    Class Outline Transformer protection overview Review transformer connections Discuss challenges and methods of current

    differential Protection

    Discuss other protective elements used in transformer protection

    Scott CooperEastern Regional Manager

    Manta Test

    Systems

    [email protected](727)415-5843

    204 37th Avenue North #281Saint Petersburg, FL 33704

  • 7/27/2019 Transformer Protection Open Lecture

    3/63

    Transformer Protection Overview Transformer Protection Zones

  • 7/27/2019 Transformer Protection Open Lecture

    4/63

    Types of ProtectionMechanical Protection

    Analysis of Accumulated Gases Looks for arcing byproducts

    Sudden Pressure Relays Orifice allows for normal thermal expansion/contraction. Arcing

    causing pressure waves in oil or gas space overwhelming the orifice and actuating the relay.

    Thermal Caused by overload, over excitation, harmonics and geo magnetically

    induced currents Hot spot temperature Top Oil LTC Overheating

  • 7/27/2019 Transformer Protection Open Lecture

    5/63

    Types of ProtectionRelay Protection

    Internal Short Circuit

    Phase: 87HS, 87T Ground: 87HS, 87T, 87GD

    System Short Circuit Back Up Protection

    Phase and Ground Faults Buses: 50, 50N, 51, 51N, 46 Lines: 50, 50N, 51, 51N, 46

  • 7/27/2019 Transformer Protection Open Lecture

    6/63

    Types of ProtectionRelay Protection

    Abnormal Operating Conditions Open Circuits: 46 Overexcitation: 24

    Undervoltage: 27 Abnormal Frequency: 81U Breaker Failure: 50BF, 50BFN

  • 7/27/2019 Transformer Protection Open Lecture

    7/63

    Phase DifferentialOverview

    What goes into a unit comes out of a unit

    Kirchoffs Law: The sum of the currents entering and leaving a junction is (should be) zero

    Straight forward concept, but not that simple in practice with transformers

    UNITI

    1I

    2

    I3

    I 1 + I 2 + I 3 = 0

  • 7/27/2019 Transformer Protection Open Lecture

    8/63

    Phase DifferentialOverview

    A host of issues presents itself to decrease security and reliability of transformer differential protection

    CT ratio caused current mismatch Transformation ratio caused current mismatch (fixed taps) LTC induced current mismatch Delta wye transformation of currents

    Vector group and current derivation issues Zero sequence current elimination for external ground faults on wye windings Inrush phenomena and its resultant current mismatch Harmonic content availability during inrush period due to point on wave

    switching (especially with newer transformers)

    Over excitation

    phenomena and

    its

    resultant

    current

    mismatch Internal ground fault sensitivity concerns

    Switch onto fault concerns CT saturation, remnance and tolerance

  • 7/27/2019 Transformer Protection Open Lecture

    9/63

    Compensation (2)

    Change in

    CT

    Ratio 1:1, Y-Y

    1:1, 3Y4:1, 3Y

    IA, IB, IC Ia, Ib, Ic

    IA'*4 = Ia'IB' * 4 = Ib'IC' * 4 = Ic'

    IA', IB', IC' Ia', Ib', Ic'

    Phase DifferentialOverview Transformer Basics

    Transformer Tap Calculation Per Unit Concept

  • 7/27/2019 Transformer Protection Open Lecture

    10/63

    Compensation (3)Transformer Ratio 2:1, Y-Y

    1:1, 3Y1:1, 3Y

    IA, IB, IC Ia, Ib, Ic

    IA' = Ia' / 2IB' = Ib' / 2IC' = Ic' / 2

    IA', IB', IC' Ia', Ib', Ic'

    Phase DifferentialOverview Transformer Basics

    Transformer Tap Calculation Per Unit Concept

  • 7/27/2019 Transformer Protection Open Lecture

    11/63

    Compensation (2)

    Change in

    CT

    Ratio

    IA, IB, IC Ia, Ib, Ic

    IA', IB', IC' Ia', Ib', Ic'

    Phase DifferentialOverview Transformer Basics

    Transformer Tap Calculation Per Unit Concept

    There must be an easier way..

  • 7/27/2019 Transformer Protection Open Lecture

    12/63

    Transformer Tap Calculation Per Unit Concept

    Phase DifferentialOverview

    Transformer Basics

    100MVAIN

    100MVAOUT

  • 7/27/2019 Transformer Protection Open Lecture

    13/63

  • 7/27/2019 Transformer Protection Open Lecture

    14/63

    Transformer Tap Calculation Per Unit Concept

    Phase DifferentialOverview

    Transformer Basics

    Each measured current is divided by the winding Tap. The

    result is a percent of rating. These percent of ratings can becompared directly.

  • 7/27/2019 Transformer Protection Open Lecture

    15/63

    AB connected delta wye transformer

    Phase DifferentialOverview

    Transformer Basics

  • 7/27/2019 Transformer Protection Open Lecture

    16/63

    a

    b

    c -b

    Subtracting Vectors: Subtract from reference phase vector theconnected non-polarity vectorin our example I a-Ib

    Can be repeated for B & C, or you can assume 120 and 240displacement from A for B&C respectively

    I b I c and I c I a would be the vectors

    Phase DifferentialOverview

    Transformer Basics

  • 7/27/2019 Transformer Protection Open Lecture

    17/63

    AC connected delta wye transformer

    Ia Ia

    Ib Ib

    IcIc

    Ia

    Ib

    Ic

    Ia-Ic

    Ib-Ia

    Ic-Ib

    Ia

    Ia-IcIb

    Ic

    Ib-Ia

    Ic-Ib

    Phase DifferentialOverview

    Transformer Basics

  • 7/27/2019 Transformer Protection Open Lecture

    18/63

  • 7/27/2019 Transformer Protection Open Lecture

    19/63

    Angular Displacement Conventions: ANSI YY, @ 0; Y , Y @ X1 lags H1 by 30

    ANSI makes life easy

    Euro designations use 30 increments of LAG from the X1 bushing to the H1 bushings

    Dy11=X1 lags H1 by 11*30 =330 or, H1 leads X1 by 30

    Think of a clock each hour is 30 degrees0

    6

    39

    8

    7

    10

    11 1

    2

    5

    4

    Dy1 = X1 lags H1 by 1*30 = 30, orH1 leads X1 by 30 (ANSI std.)

    Phase DifferentialOverview

    Transformer Basics

  • 7/27/2019 Transformer Protection Open Lecture

    20/63

    US Standard Dy Example: H1 (A) leads X1 (a) by 30 Currents on H bushings are delta quantities

    a

    b

    c A

    B

    C

    Assume 1:1 transformer

    Phase DifferentialOverview Transformer Basics

  • 7/27/2019 Transformer Protection Open Lecture

    21/63

    Assume 1:1 transformer

    a

    b

    c

    AB

    C

    Phase DifferentialOverview Transformer Basics

    US Standard Yd Example:H1 (a) leads X1 (A) by 30Currents on X bushings are delta quantities

  • 7/27/2019 Transformer Protection Open Lecture

    22/63

    Phase DifferentialOverview

    Applied with variable percentage slopes to accommodate CT saturation and CT ratio errors

    Applied with inrush and over excitation restraints

    Set with at least a 20% pick up to accommodate CT performance

    Class C CT; +/ 10% at 20X rated

    If unit is LTC, add another +/ 10%

    May not be sensitive enough for all faults (low level, ground faults near neutral)

  • 7/27/2019 Transformer Protection Open Lecture

    23/63

    CT ratios and tap settings are selected to account for:

    Transformer ratios If delta or wye connected CTs are

    applied

    Delta increases ratio by 1.73 Delta CTs must be used to filter zero

    sequence current on all wye transformer windings

    Dy transformer connections compensated by yd CT connections to make the currents apples to apples.

    Phase DifferentialEM

    Relay

    Application

  • 7/27/2019 Transformer Protection Open Lecture

    24/63

    Zero sequence elimination: In EM relays with wye connected transformers, delta connected CTs are used to remove the ground current.

    Phase DifferentialEM Relay Application

  • 7/27/2019 Transformer Protection Open Lecture

    25/63

    Settings compensate for the following: Transformer ratio CT ratio

    Vector quantities Which vectors are used Where the 1.73 factor (3) is applied

    When examining line to line quantities on delta connected transformer windings and CT windings

    Zero sequence current filtering for wye windings so the differential quantities do not occur from external ground faults

    Phase DifferentialDigital

    Relay

    Application

  • 7/27/2019 Transformer Protection Open Lecture

    26/63

    Angular displacement (IEC and SEL) IEC (Euro) practice does not

    have a standard like ANSI Most common connection is

    Dy11 (low lead high by 30!) Obviously observation of

    angular displacement is extremely important when paralleling transformers!

    *1

    *1

    *2

    *2

    *1 = ANSI std. @ 0

    *2 = ANSI std. @ X1 lag H1 by 30 ,or high lead low by 30

    Phase DifferentialDigital Relay Application

  • 7/27/2019 Transformer Protection Open Lecture

    27/63

    Digital Relay Application

    All wye CTs shown, most can retrofit legacy delta CT applications

  • 7/27/2019 Transformer Protection Open Lecture

    28/63

    Benefits of Wye CTs Phase segregated line currents

    Individual line current oscillography Currents may be easily used for overcurrent

    protection and metering Easier to commission and troubleshoot Zero sequence elimination performed by

    calculation

  • 7/27/2019 Transformer Protection Open Lecture

    29/63

    Zero sequence elimination: In digital relays with wye connected transformers and wye connected CTs, ground current must be removed from the differential calculation.

    3I 0 = [I a + I b + I c]I0 = 1/3 *[I a + I b + I c]

    Used where filtering is

    required, such as wyewinding with wye CTs

    Phase DifferentialDigital Relay Application

  • 7/27/2019 Transformer Protection Open Lecture

    30/63

    Typical Transformer Inrush Waveform

    2nd and 4thHarmonicsDuringInrush

    Phase DifferentialDigital Relay Application

  • 7/27/2019 Transformer Protection Open Lecture

    31/63

    Harmonically Restrained Differential Element Inrush Detection and Restraint

    Inrush occurs on transformer energizing as the core magnetizes Sympathy inrush occurs from adjacent transformer(s) energizing, fault

    removal, allowing the transformer to undergo a low level inrush Characterized by current into one winding of transformer, and not out

    of the other winding(s) This causes the differential element to pickup Use inrush restraint to block differential element during inrush period

    Phase DifferentialDigital Relay Application

  • 7/27/2019 Transformer Protection Open Lecture

    32/63

    Inrush Detection and Restraint 2nd harmonic restraint has been employed for years Gap detection has also been employed As transformers are designed to closer tolerances, both 2nd harmonic

    and low current gaps in waveform have decreased

    If 2

    nd

    harmonic restraint

    level

    is

    set

    too

    low,

    differential

    element

    may

    be blocked for internal faults with CT saturation (with associated harmonics generated)

    Phase DifferentialDigital Relay Application

  • 7/27/2019 Transformer Protection Open Lecture

    33/63

    Inrush Detection and Restraint 4 th harmonic is also generated during inrush Odd harmonics are not as prevalent as Even harmonics during inrush Odd harmonics more prevalent during CT saturation Use 4 th harmonic and 2nd harmonic together

    M3310/M 3311 relays use RMS sum of the 2nd

    and 4th

    harmonic as inrush restraint Result: Improved security while not sacrificing reliability

    Phase DifferentialDigital Relay Application

  • 7/27/2019 Transformer Protection Open Lecture

    34/63

  • 7/27/2019 Transformer Protection Open Lecture

    35/63

    0.5

    1.0

    1.5

    2.0

    0.5 1.0 1.5 2.0

    87T Pick Up

    87T Pick Upwith 5th Harmonic Restraint

    Slope 1

    Slope 2

    Slope 2Breakpoint

    TRIP

    RESTRAIN

    Phase DifferentialDigital Relay Application

  • 7/27/2019 Transformer Protection Open Lecture

    36/63

    87T Pick Up Class C CTs, use 20%

    LTC, add 10% Magnetizing losses, add 1% 0.3 to 0.4 pu typically setting

    Slope 1 Used for low level currents Typically set for 25%

    Slope 2 breakpoint

    Typically set at 2X rated current This setting assumes that any current over 2X rated is a

    through fault or internal fault, and is used to desensitize the element against unfaithful replication

    Phase DifferentialDigital Relay Application

  • 7/27/2019 Transformer Protection Open Lecture

    37/63

    Slope 2 Typically set at 70%

    Inrush Restraint (2nd

    and 4th

    harmonic) Typically set from 15 20% Employ cross phase averaging blocking for security

    Over excitation Restraint (5 th harmonic) Typically set at 30% Raise 87T pick up to 0.60 pu during overexcitation No cross phase averaging needed, as overexcitation is

    symmetric on the phases

    Phase DifferentialDigital Relay Application

  • 7/27/2019 Transformer Protection Open Lecture

    38/63

    Unrestrained 87H Pick Up Typically set at 810pu rated current

    This value should be above maximum possible inrush current and lower than the CT saturation current

    C37.91, section 5.2.3, states 10pu an acceptable value Can use data captured from energizations to fine tune the

    setting

    Phase DifferentialDigital Relay Application

  • 7/27/2019 Transformer Protection Open Lecture

    39/63

    CT Issues:

    Remnance :

    Residual magnetism

    that

    causes

    dc

    saturation

    of

    the

    CTs

    Saturation : Error signal resulting from too high a primary current combined with a large burden

    Tolerance : Class C CTs are rated +/ 10% for currents x20 of nominal Thru faults and internal faults may reach those levels depending on ratio

    selected

    Phase DifferentialDigital Relay Application

  • 7/27/2019 Transformer Protection Open Lecture

    40/63

    CT Issues (cont.) Best defense is to use high Class C voltage levels

    C400, C800 These have superior characteristics against saturation and relay/wiring burden

    Use low burden relays

    Digital systems

    are

    typically

    0.020

    ohms

    Use a variable percentage slope characteristic to desensitize the differential element when challenged by high currents that may cause replication errors

    Phase DifferentialDigital Relay Application

  • 7/27/2019 Transformer Protection Open Lecture

    41/63

    Point on Wave Considerations During Energization As most circuit breakers are ganged three pole, each phase is closed at a

    different angle resulting in less harmonics on one phase and more on the others

    Low levels of harmonics may not provide inrush restraint for affected phase security risk!

    Most modern relays employ some kind of cross phase averaging scheme to compensate for this issue Provides security if any phase has low harmonic content during inrush or overexcitation This can occur depending on the voltage point on wave when the transformer is energized for a

    given phase Cross phase averaging uses the average of harmonics on all three phases to determine level

    Phase DifferentialDigital Relay Application

  • 7/27/2019 Transformer Protection Open Lecture

    42/63

    Improved Ground Fault Sensitivity: 87T element is typically set with 20 40% pick up This is to accommodate Class C CT accuracy

    during a fault plus the effects of LTCs That leaves 20 40% of the winding not covered for

    a ground fault Employ a ground differential element to improve

    sensitivity (87GD)

    Phase DifferentialDigital Relay Application

  • 7/27/2019 Transformer Protection Open Lecture

    43/63

  • 7/27/2019 Transformer Protection Open Lecture

    44/63

    Switch onto Fault (cont): Employ 87HS to protect winding that is first energized 87HS is set above inrush current If fault is near the bushing end of the winding, the current will be higher

    than inrush Typically 912 pu thru current

    87HS does not employ harmonic restraint Fast tripping on high current faults

    Phase DifferentialDigital Relay Application

    d ff l

  • 7/27/2019 Transformer Protection Open Lecture

    45/63

    Use 87GD I A + I B + I C = 3I 0

    If fault is internal, opposite polarity

    If fault is external, same polarity

    IG

    I A

    IB

    IC

    Ground DifferentialDigital Relay Application

    G d Diff i l

  • 7/27/2019 Transformer Protection Open Lecture

    46/63

    IG

    I A

    IB

    IC

    IG

    I A

    IB

    IC

    Internal External

    Ground DifferentialDigital Relay Application

  • 7/27/2019 Transformer Protection Open Lecture

    47/63

    G d Diff ti l

  • 7/27/2019 Transformer Protection Open Lecture

    48/63

    IG

    I A

    IB

    IC

    3I0IG

    Residual currentcalculated fromindividual phasecurrents. ParalleledCTs shown toillustrate principle.

    0

    90

    180

    270

    IG

    -3I O

    Ground DifferentialDigital Relay Application

    Ground Differential

  • 7/27/2019 Transformer Protection Open Lecture

    49/63

    0

    90

    180

    270

    IG

    -3I O

    Ground DifferentialDigital Relay Application

    Other Transformer Protection

  • 7/27/2019 Transformer Protection Open Lecture

    50/63

    Fuses Small transformers (

  • 7/27/2019 Transformer Protection Open Lecture

    51/63

    Hside over current elements:

    Protection against heavy prolonged through faults Transformer Category by nameplate capacity IEEE Std. C57.109 1985 Curves

    Other Transformer ProtectionOver current Elements

  • 7/27/2019 Transformer Protection Open Lecture

    52/63

  • 7/27/2019 Transformer Protection Open Lecture

    53/63

    Th h F l

  • 7/27/2019 Transformer Protection Open Lecture

    54/63

    Through Fault

    Category 2

    Th h F lt

  • 7/27/2019 Transformer Protection Open Lecture

    55/63

    Through Fault

    Category 3

    Through Fault

  • 7/27/2019 Transformer Protection Open Lecture

    56/63

    Through Fault

    Category 4

    Other Transformer Protection

  • 7/27/2019 Transformer Protection Open Lecture

    57/63

    Xside Over Current Elements

    Used to protect against un cleared faults downstream

    of the transformer May consist of phase

    and ground elements

    Coordinated with line protection off the bus Failed Breaker

    5151G

    Over current Elements

    Other Transformer Protection

  • 7/27/2019 Transformer Protection Open Lecture

    58/63

    Xside Over Current Elements: Negative sequence over

    current used to protect against unbalanced loads & open conductors

    Easy to coordinate46

    Over current Elements

    Other Transformer Protection

  • 7/27/2019 Transformer Protection Open Lecture

    59/63

    Overexcitation:

    Responds to overfluxing; excessive v/Hz

    Continuous operational limits ANSI C37.106 & C57.12

    1.05 loaded, 1.10 unloaded

    Inverse curves typically available for values over the continuous allowable maximum

    Over current Elements

    Other Transformer Protection

  • 7/27/2019 Transformer Protection Open Lecture

    60/63

    Causes: Generating Plants

    Excitation system runaway

    Sudden loss of load Operational issues (reduced frequency)

    Static starts Pumped hydro starting Rotor warming

    Transmission Systems Voltage and Reactive Support Control Failures

    Capacitor banks ON when they should be OFF Shunt reactors OFF when they should be ON Generator unit transformer connected to long line with

    no load (Ferranti effect) Runaway LTCs

    Over current Elements

    Overexcitation Curve

  • 7/27/2019 Transformer Protection Open Lecture

    61/63

    Overexcitation Curve

    This is typically how the apparatus manufacturer specs it

    Overexcitation Curve

  • 7/27/2019 Transformer Protection Open Lecture

    62/63

    Overexcitation Curve

    This is how protection engineers enter the v/Hz curve into a protective device

    References:ANSI / IEEEC37 91 Guide for Protective Relay Applications for Power Transformers

  • 7/27/2019 Transformer Protection Open Lecture

    63/63

    ANSI/ IEEEC37.91, Guide for Protective Relay Applications for Power TransformersANSI/IEEE C57.12, Standard General Requirements for Liquid Immersed Distribution, Power and Regulating TransformersProtective Relaying: Principals and applications, Third Edition By J. Lewis Blackburn and Thomas J. DominDigital Transformer Protection from Power Plants to Distribution Substations, CJ MozinaGeneral Electric Transformer Connections including Autotransformer Connections GET2J, Dec, 1970

    87T

    50

    51 51G

    High Side Low Side