Transformer Protection Simulation User Manual Hardware and Relay Configuration Guide Nicholas Kilburn 17/05/22 This manual details the configurations and methods to replicate the Transformer Protection Simulation developed as a part of the SEL Protection and Monitoring thesis project of 2013.

Upload: vonhan

Post on 10-Mar-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Transformer Protection Simulation User Manualresearchrepository.murdoch.edu.au/21662/3/Transformer... · Web viewSet the Phase Overcurrent pickup elements to be 10% on the nominal

Transformer Protection Simulation User Manual

Hardware and Relay Configuration Guide

Nicholas Kilburn

6/05/23

This manual details the configurations and methods to replicate the Transformer Protection Simulation developed as a part of the SEL Protection and Monitoring thesis project of 2013.

Page 2: Transformer Protection Simulation User Manualresearchrepository.murdoch.edu.au/21662/3/Transformer... · Web viewSet the Phase Overcurrent pickup elements to be 10% on the nominal

ContentsHardware Configuration........................................................................................................................2

Relay Configuration...............................................................................................................................3

Hardware...........................................................................................................................................3

Configuration.....................................................................................................................................3

Simulation Operation............................................................................................................................7

Appendix...............................................................................................................................................9

Page 3: Transformer Protection Simulation User Manualresearchrepository.murdoch.edu.au/21662/3/Transformer... · Web viewSet the Phase Overcurrent pickup elements to be 10% on the nominal

Hardware Configuration

Figure 1 - Lab-Volt Simulation SLD

Connect the Lab-Volt Equipment as per the diagram in Figure 1. For the Primary CTs use the 2.5:5 ratio For the Secondary CTs use the 1:5 ratio Ensure the CTs are not shorted, i.e. the associated switches are set off. For the load set the per phase resistance to 686Ω, set all resistor switches on Connect the grounding points to the neutral of the power supply to avoid earth-leakage

tripping of the three-phase main supply.

See the appendix images for visual representation of this simulation connections structure and a larger version of Figure 1.

Page 4: Transformer Protection Simulation User Manualresearchrepository.murdoch.edu.au/21662/3/Transformer... · Web viewSet the Phase Overcurrent pickup elements to be 10% on the nominal

Relay Configuration

Hardware

Figure 2 - Relay Connections

Connect the relay I/O terminals as illustrated in Figure 2 Ensure that the connections to the interconnection panel match those leading to the Lab-

Volt systemo Z01 to Z12 inputs for the CT secondarieso A05 to A08 are the outputs for breaker controlo A09 to A12 provide the inputs for breaker monitoring

Make sure the correct power is connected to A01 and A02, 120V approximately.

ConfigurationStep 1. To configure the relay first open the AcSELerator Quickset application, connect the

relay to the PC serial communication port and establish a connection as detailed in the “AcSELerator Quickset User Manual”.

Step 2. Once this is complete open the settings editor either directly from the relay or from the local database, if a new settings editor is established then all configuration settings will need to be addressed.

Step 3. Ensure that the configuration settings are configured as follows (Table 1); adjust as necessary for any changes in simulation configuration.

a. If simulation has been modified, follow steps 1 through 4 in the Simulation Operation section before proceeding to step 4.

b. These configurations fit the original simulation as designed in 2013.

Page 5: Transformer Protection Simulation User Manualresearchrepository.murdoch.edu.au/21662/3/Transformer... · Web viewSet the Phase Overcurrent pickup elements to be 10% on the nominal

Table 1 - Default Simulation Relay Configuration

Level 1 Level 2 Level 3 Level 4/5 Name SettingGlobal

General PHROT ABCFNOM 50DATE_F DMY

FAULT51P1P OR 51P2P OR 51G1P OR 51G2P OR 51N1P OR TRIP

Event MessengerEMP N

Settings Group Selection

SS1 1Synchronized Phasor Measurement

EPMU NBreaker Failure

52ABF NThrough-Fault Monitor

THFLTD NInput Debounce

Slot AIN101D 100IN102D 100

Group 1Set 1

ConfigurationMVA OFFICON NW1CT DELTACTR1 1W2CT WYECTR2 1

Transformer Differential ElementsE87 NTAP1 4.76TAP2 3.04O87P 0.387AP 0.1587AD 5SLP1 25SLP2 70IRS1 3U87P 6PCT2 15PCT4 15PCT5 35

Page 6: Transformer Protection Simulation User Manualresearchrepository.murdoch.edu.au/21662/3/Transformer... · Web viewSet the Phase Overcurrent pickup elements to be 10% on the nominal

TH5P OFFHRSTR YHBLK N

Overcurrent ElementsWinding 1Phase Overcurrent

50P11P 1.1250P11D 0.150P11TC 150P12P OFF50P13P OFF50P14P OFF

Negative Sequence Overcurrent50Q11P 0.150Q11D 0.250Q11TC 1

Winding 2Phase Overcurrent

50P21P 1.5650P21D 0.150P21TC 150P22P OFF50P23P OFF50P24P OFF

Residual Overcurrent50G21P 0.150G21D 0.150G21TC 150G22P OFF

Negative Sequence Overcurrent50Q21P 0.150Q21D 0.250Q21TC 150Q22P OFF

Time Overcurrent Elements51P1P OFF51G1P OFF51Q1P OFF51P2P OFF51G2P OFF51Q2P OFF

Trip and Close LogicTDURD 0TRXFMR 87R OR 87UREMTRIP 0ULTRXFMR NOT (87R OR 87U)

Page 7: Transformer Protection Simulation User Manualresearchrepository.murdoch.edu.au/21662/3/Transformer... · Web viewSet the Phase Overcurrent pickup elements to be 10% on the nominal

CFD1 1

TR150P11T OR 50G11T OR 50Q11T OR NOT LT02 AND SV04T OR OC1

ULTRIP1NOT ( 50P11P OR 50G11P OR 50Q11P OR 51A1 )

52A1 NOT IN101CL1 SV03T AND NOT LT02 OR CC1ULCL1 TRIP1 OR TRIPXFMRCFD2 1

TR250P21T OR 50G21T OR 50Q21T OR NOT LT02 AND SV04T OR OC2

ULTRIP2NOT ( 50P21P OR 50G21P OR 50Q21P OR 52A2 )

52A2 NOT IN102CL2 SV03T AND NOT LT02 OR CC2ULCL2 TRIP2 OR TRIPXFMR

Logic 1Outputs

Slot AOUT101FS YOUT101 HALARM OR SALARMOUT102FS NOUT102 TRIP1 OR TRIPXFMROUT103FS NOUT103 TRIP2 OR TRIPXFMR

Notes:

NOT of elements 52A1 and 52A2 is to account for the NC contract from the control relays feeding the Breaker status monitor.

Element E87 will need to be enabled (Y) to allow the settings to be modified to avoid settings download errors.

Protective Functionality can be disabled by setting the required XXXX1P overcurrent elements to OFF.

Step 4. Once the configurations are confirmed, the settings can be downloaded to the relay

through selection of the Send Active Settings button .

Page 8: Transformer Protection Simulation User Manualresearchrepository.murdoch.edu.au/21662/3/Transformer... · Web viewSet the Phase Overcurrent pickup elements to be 10% on the nominal

Simulation OperationThe process described should result in the configuration settings defined in Table 1, assuming no changes to the simulation have been made.

1. Ensure all protective functionality is disabled by setting all XXXXXP overcurrent elements to OFF and disable differential protection.

2. Check that all fault inducing switches or buttons are in their off positions, this can causea. Nominal configuration errors, orb. Trip the three-phase earth-leakage breaker (any ground fault).

3. Turn on the DC control relays power supply; the three-phase contactors in the transmission grid should close.

4. Set the Lab-Volt Power supply to 50% and turn on. 5. Use the Relay HMI Phaosr and Differential Elements windows to record nominal CT

secondary current readings for all phases and the nominal differential elements.a. Use this data to establish the pickup levels for Phase Overcurrent and Differential

Protection.i. Set the Phase Overcurrent pickup elements to be 10% on the nominal

metered current, as seen by the relay. For Residual and Negative-Sequence Elements set the Pickup to the smallest permissible without causing trip conditions during nominal operation.

ii. The configuration of time delays is entirely up to the user. b. Calculate the TAP elements using the following formula:

TAPn= MVA×1000√3×VWDG×CTR

×C , Where:

i. C=1 ( for wye ) or √3 ( for Delta )ii. MVA=Maximum transformer power Ratingiii. VWDG=Line-to-line winding voltage (kV)iv. ¿ ,CTR=CT ratio setting

c. This calculation, using the actual values will produce results that will result in errors, to avoid this multiply the results by a suitable factor to bring these calculations into a configurable range.

i. Adjust any settings that become erroneous as a result of this calculation to avoid download errors.

ii. More details of this process can be observed within the Thesis Report in sections 6.2.3 and 7.5.2.

6. Enable the required protective functions and download new settings to the relay.7. Connect the required power to the Universal Fault Module and connect the Line-to-Line

Fault, series connected with an available contact output, across two phases of the load or any other point in the simulation.

8. Power the Lab-Volt system (still at 50%) and DC control relay power supply. 9. Begin fault testing by conducting any number of the following:

a. Depressing the initiate fault button on the Universal Fault Moduleb. Disconnecting a phase of the Load

Page 9: Transformer Protection Simulation User Manualresearchrepository.murdoch.edu.au/21662/3/Transformer... · Web viewSet the Phase Overcurrent pickup elements to be 10% on the nominal

c. Temporarily increase the three-phase Power Supply (greater than 50%)d. Initiate faults on the Faultable Transformer Module. e. At this stage do not introduce a fault to ground

i. The three-phase earth-leakage circuit breaker will trip disconnecting the power to the Lab-Volt system before the relay has a chance to respond to the fault.

10. After the introduction of a fault the relay will respond and trip the appropriate contactors, the front panel will:

a. Describe the type of faultb. Indicate the winding to generate the faultc. Visually indicate which breakers have opened as a result

The response will vary depending on which fault mechanism was utilised and what protective functionality was enabled during the fault event.

11. To re-close the three-phase contactors push the desired and illuminated reset button on the control relay panel. The relay should reset the trip condition and allow the contactors to remain closed.

a. On occasion the relay may instantaneously re-open the contactor(s) upon reset attempt; this usually happens as a result of residual currents within the Delta transformer and can be resolved by holding the reset button for an extended period to allow the system to settle before the relay can generate a trip condition.

b. This occurrence can also be avoided by introducing a delayed tripping response, to account for the system settling or any remaining start-up transient currents within the delta winding.

12. The use of the EVENT, SUM and EVE DIF1 commands in the terminal command window will provide fault event metering data and before, during and after metering screenshots detailing the fault generation and relay response. This is the easiest mechanism to observe the nature of the induced faults and their impact upon the system.

13. After simulations are complete turn off all power supplies for the Lab-Volt system, then turn off relay at rear mains switch.