transistorized inverter fr- 500 instruction manual …
TRANSCRIPT
S500TRANSISTORIZED INVERTER
Thank you for choosing this Mitsubishi Transistorized inverter.If this is the first time for you to use the FR-S500 series, please read throughthis instruction manual (basic) carefully and use the inverter safely.If you are going to use the inverter for higher-level applications, the FR-S500 instruction manual (detailed) [IB(NA)-0600027] is separately available from where you purchased the inverter or your Mitsubishi sales representative.
INSTRUCTION MANUAL (BASIC)FR-
FR-S520-0.1K to 3.7K(-R)(-C)FR-S520-0.1K to 3.7K-NA(R)FR-S520S-0.1K to 1.5K(-R)FR-S520S-0.2K to 1.5K-EC(R)
CONTENTS1. CONNECTION OF PERIPHERAL DEVICES ......................................22. INSTALLATION METHOD ..................................................................43. SPECIFICATIONS OF WIRING AND TERMINALS ............................54. OPERATION/CONTROL...................................................................155. ADJUSTMENT OF THE FREQUENCY SETTING
POTENTIOMETER AND INDICATOR ..............................................216. FUNCTION LIST ...............................................................................257. ERRORS AND PROTECTIVE FUNCTIONS.....................................378. SPECIFICATIONS.............................................................................409. OUTLINE DRAWINGS ......................................................................44Appendix 1 Instructions for Compliance with the European
Standards ...........................................................................46Appendix 2 Instructions for compliance with U.S. and Canadian
Electrical Codes..................................................................48
A - 1
This instruction manual (basic) provides handling information and precautions foruse of the equipment.Please forward this instruction manual (basic) to the end user.This instruction manual uses the International System of Units (SI). Themeasuring units in the yard and pound system are indicated in parentheses asreference values.
This section is specifically about safety mattersDo not attempt to install, operate, maintain or inspect the inverter until you haveread through this instruction manual (basic) and appended documents carefullyand can use the equipment correctly. Do not use the inverter until you have afull knowledge of the equipment, safety information and instructions.In this instruction manual (basic), the safety instruction levels are classified into"WARNING" and "CAUTION".
WARNINGAssumes that incorrect handling may cause hazardousconditions, resulting in death or severe injury.
CAUTIONAssumes that incorrect handling may cause hazardousconditions, resulting in medium or slight injury, or maycause physical damage only.
Note that even the CAUTION level may lead to a serious consequenceaccording to conditions. Please follow the instructions of both levels becausethey are important to personnel safety.
1. Electric Shock Prevention
WARNING! While power is on or when the inverter is running, do not open the front
cover. You may get an electric shock.! Do not run the inverter with the front cover removed. Otherwise, you may
access the exposed high-voltage terminals or the charging part of thecircuitry and get an electric shock.
! If power is off, do not remove the front cover except for wiring or periodicinspection. You may access the charged inverter circuits and get an electricshock.
! Before starting wiring or inspection, check for residual voltages with a meteretc. more than 10 minutes after power-off.
! Earth the inverter.! Any person who is involved in the wiring or inspection of this equipment
should be fully competent to do the work.! Always install the inverter before wiring. Otherwise, you may get an electric
shock or be injured.! Perform setting dial and key operations with dry hands to prevent an electric
shock.! Do not subject the cables to scratches, excessive stress, heavy loads or
pinching. Otherwise, you may get an electric shock.! Do not change the cooling fan while power is on.
It is dangerous to change the cooling fan while power is on.! When you have removed the front cover, do not touch the connector above
the 3-digit monitor LED display. Doing so can cause an electric shock.
A - 2
2. Fire Prevention
CAUTION! Mount the inverter to incombustible material. Mounting it to or near
combustible material can cause a fire.! If the inverter has become faulty, switch off the inverter power. A continuous
flow of large current could cause a fire.! Do not connect a resistor directly to the DC terminals P(+), N(−). This could
cause a fire.3. Injury Prevention
CAUTION! Apply only the voltage specified in the instruction manual to each terminal to
prevent damage etc.! Ensure that the cables are connected to the correct terminals. Otherwise,
damage etc. may occur.! Always make sure that polarity is correct to prevent damage etc.! While power is on and for some time after power-off, do not touch the inverter
or brake resistor as they are hot and you may get burnt.4. Additional instructionsAlso note the following points to prevent an accidental failure, injury, electricshock, etc.(1) Transportation and installation
CAUTION! When carrying products, use correct lifting gear to prevent injury.! Do not stack the inverter boxes higher than the number recommended.! Ensure that installation position and material can withstand the weight of the
inverter. Install according to the information in the Instruction Manual.! Do not operate if the inverter is damaged or has parts missing.! When carrying the inverter, do not hold it by the front cover or setting dial; it
may fall off or fail.! Do not stand or rest heavy objects on the inverter.! Check the inverter mounting orientation is correct.! Prevent screws, wire fragments, other conductive bodies, oil or other
flammable substances from entering the inverter.! Do not drop the inverter, or subject it to impact.
A - 3
CAUTION! Use the inverter under the following environmental conditions:
Ambienttemperature
-10°C to + 50°C (14°F to 122°F) (non-freezing)
Ambient humidity 90%RH or less (non-condensing)Storagetemperature
-20°C to +65°C (-4°F to 149°F) *
AmbienceIndoors (free from corrosive gas, flammable gas,oil mist, dust and dirt)
En
viro
nm
en
t
Altitude,vibration
Maximum 1000m (3280.80feet) above sea levelfor standard operation. After that derate by 3% forevery extra 500m (1640.40feet) up to 2500m(8202.00feet) (91%).5.9m/s2 or less (conforming to JIS C0911)
*Temperatures applicable for a short time, e.g. in transit.
(2) Wiring
CAUTION! Do not fit capacitive equipment such as power factor correction capacitor,
radio noise filter or surge suppressor to the output of the inverter.! The connection orientation of the output cables U, V, W to the motor will
affect the direction of rotation of the motor.
(3) Trial run
CAUTION! Check all parameters, and ensure that the machine will not be damaged by a
sudden start-up.
(4) Operation
WARNING! When you have chosen the retry function, stay away from the equipment as it
will restart suddenly after an alarm stop.! The [STOP] key is valid only when the appropriate function setting has been
made. Prepare an emergency stop switch separately.! Make sure that the start signal is off before resetting the inverter alarm. A
failure to do so may restart the motor suddenly.! The load used should be a three-phase induction motor only. Connection of
any other electrical equipment to the inverter output may damage theequipment.
! Do not modify the equipment.
A - 4
CAUTION! The electronic overcurrent protection does not guarantee protection of the
motor from overheating.! Do not use a magnetic contactor on the inverter input for frequent
starting/stopping of the inverter.! Use a noise filter to reduce the effect of electromagnetic interference.
Otherwise nearby electronic equipment may be affected.! Take measures to suppress harmonics. Otherwise power harmonics from the
inverter may heat/damage the power capacitor and generator.! When parameter clear or all clear is performed, each parameter returns to
the factory setting. Re-set the required parameters before starting operation.! The inverter can be easily set for high-speed operation. Before changing its
setting, fully examine the performances of the motor and machine.! In addition to the inverter's holding function, install a holding device to ensure
safety.! Before running an inverter which had been stored for a long period, always
perform inspection and test operation.
(5) Emergency stop
CAUTION! Provide a safety backup such as an emergency brake which will prevent the
machine and equipment from hazardous conditions if the inverter fails.
(6) Maintenance, inspection and parts replacement
CAUTION! Do not carry out a megger (insulation resistance) test on the control circuit of
the inverter.
(7) Disposing of the inverter
CAUTION! Treat as industrial waste.
(8) General instructionsMany of the diagrams and drawings in this instruction manual (basic) show theinverter without a cover, or partially open. Never run the inverter in this status.Always replace the cover and follow this instruction manual (basic) whenoperating the inverter.
1
Japanese Power Supply Harmonic Suppression GuidelineThe "harmonic suppression guideline for household appliances and general-purpose products" issued by the Ministry of International Trade and Industry inSeptember, 1994 applies to the FR-S500 series. By installing the FR-BEL or FR-BAL power factor improving reactor, this product complies with the "harmonicsuppression techniques for transistorized inverters (input current 20A or less)"established by the Japan Electrical Manufacturers' Association.
Product Checking and Parts IdentificationUnpack the inverter and check the capacity plate on the front cover and the ratingplate on the inverter side face to ensure that the product agrees with your orderand the inverter is intact.
Part names and plates
Front cover
Operation panel
Wiring cover
Serial number
Rating plate
Inverter type
FR - S520 - K -0.1
Capacity plate
Input rating
Output rating
Serial numberInverter type
Inverter type
R
Representsthe inverter capacity "kW ".
Standard structureSymbol Protective StructureNone
C
S520Symbol Voltage Class
Three-phase 200V classWith RS-485 communicationfunction
Totally enclosed structureIP40Only for Japanese version
S520S Single-phase 200V classNone
Symbol VersionJapanese specification
NA North Americanspecification
EC Europeanspecification
• Removal and reinstallation of the front coverRemove the front cover by pulling it towardyou in the direction of arrow.To reinstall, match the cover to the inverterfront and install it straight.
• Removal and reinstallation of the wiring coverThe cover can be removed easily by pulling ittoward you.To reinstall, fit the cover to the inverter alongthe guides.
FR-S520(S)-0.1K to 0.75K FR-S520(S)-1.5KFR-S520-2.2K, 3.7K
Wiring cover
2
< Type with RS-485 communication function >When using the RS-485 connector to wire thecable, you can cut off the lug of the wiring coverto wire it. (Cutting off the lug provides protectivestructure IP10.)
Lug
CAUTION
The connector above the operation panel is formanufacturer use. Do not touch it as doing somay cause an electric shock.
1. CONNECTION OF PERIPHERAL DEVICES1.1 Basic Configuration
Inverter
Use within the permissible power supply specifications of the inverter. (Refer to page 40.)
(MC)
(NFB) or
(ELB)
Earth (Ground)
Earth (Ground)
AC reactor(FR-BAL)
DC reactor(FR-BEL)
No-fuse breaker or earth leakage circuit breaker
Power supply
The breaker must be selected carefully since an in-rush current flows in the inverter at power-on.
Magnetic contactor
Do not use this magnetic contactor to start and stop the inverter. Doing so will cause the inverter life to be shorter.
Installation of reactorsThe reactors must be used when the power factor is to beimproved or the inverter is installed near a large power supplysystem (500kVA or more and wiring distance within 10m (32.81feet)).Make selection carefully.
Earth (Ground)To prevent an electric shock, always ground the motor and inverter.For reduction of induction noise from the power line of the inverter,it is recommended to wire the ground cable by returning it to the ground terminal of the inverter. (For details of noise reduction techniques, refer to the instruction manual (detailed).)
Devices connected to the outputDo not connect a power capacitor, surge suppressor or radio noise filter to the output side.
The inverter life is influenced by ambienttemperature. The ambient temperature should be as low as possible within the permissible range. (Refer to page 42.)
Wrong wiring might lead to inverter damage. The control signal lines must be kept fully away from the main circuit to protect them from noise. (Refer to page 5.)
3
Selection of peripheral devices (Selection changes with thepower supply input specifications of the inverter.) FR-S520-0.1K to 3.7K(-R)(-C) FR-S520-0.1K to 3.7K-NA(R)
Cables (mm2)(*2)
MotorOutput
(kW(HP))
InverterType
No-FuseBreaker
(NFB*1) orEarth
LeakageCircuitBreaker(ELB)
PowerFactor
ImprovingAC
Reactor
PowerFactor
ImprovingDC
Reactor
MagneticContactor
(MC) R, S, T U, V, W
0.1(1/8)
FR-S520-0.1K
30AF/5ATFR-BAL-0.4K (*3)
FR-BEL-0.4K (*3)
S-N10 2 2
0.2(1/4)
FR-S520-0.2K
30AF/5ATFR-BAL-0.4K (*3)
FR-BEL-0.4K (*3)
S-N10 2 2
0.4(1/2)
FR-S520-0.4K
30AF/5ATFR-BAL-
0.4KFR-BEL-
0.4KS-N10 2 2
0.75(1)
FR-S520-0.75K
30AF/10ATFR-BAL-
0.75KFR-BEL-
0.75KS-N10 2 2
1.5(2)
FR-S520-1.5K
30AF/15ATFR-BAL-
1.5KFR-BEL-
1.5KS-N10 2 2
2.2(3)
FR-S520-2.2K
30AF/20ATFR-BAL-
2.2KFR-BEL-
2.2KS-N11,S-N12
2 2
3.7(5)
FR-S520-3.7K
30AF/30ATFR-BAL-
3.7KFR-BEL-
3.7KS-N20 3.5 3.5
FR-S520S-0.1K to 1.5K(-R) FR-S520S-0.2K to 1.5K-EC(R)
Cables (mm2)(*2)
MotorOutput
(kW(HP))
InverterType
No-FuseBreaker
(NFB*1) orEarth
LeakageCircuitBreaker(ELB)
PowerFactor
ImprovingAC
Reactor
PowerFactor
ImprovingDC
Reactor
MagneticContactor
(MC) R, S<L1, N>
U, V, W
0.1(1/8)
FR-S520S-0.1K
30AF/5ATFR-BAL-0.4K (*3)
FR-BEL-0.4K (*3)
S-N10 2 2
0.2(1/4)
FR-S520S-0.2K
30AF/10ATFR-BAL-0.4K (*3)
FR-BEL-0.4K (*3)
S-N10 2 2
0.4(1/2)
FR-S520S-0.4K
30AF/10ATFR-BAL-
0.75K (*3)FR-BEL-
0.75K (*3)S-N20 2 2
0.75(1)
FR-S520S-0.75K
30AF/15ATFR-BAL-1.5K (*3)
FR-BEL-1.5K (*3)
S-N20 2 2
1.5(2)
FR-S520S-1.5K
30AF/20ATFR-BAL-2.2K (*3)
FR-BEL-2.2K (*3)
S-N21 2 2
*1 Choose the NFB type to meet the power supply capacity.*2 The size of the cable indicated assumes the wiring length of 20m (65.62feet).*3 The power factor may be slightly lower.
4
2. INSTALLATION METHOD2.1 Installation of the Inverter
When containing two or more inverters, install them in parallel and provide cooling measures.
Leave enough clearances and provide cooling measures.
Enclosure surface mounting Mounting inside enclosure
Fix the front cover and wiring cover after removing them.
• Install the inverter under the following conditions.
Vertical mounting
Vertical
Ambient temperature and humidity
Temperature: -10°C to 50°C (14°F to 122°F)Humidity: 90%RH maximum
Enough clearances
10cm(3.94inch) or more1cm
(0.39inch) or more
10cm(3.94inch) or more
1cm(0.39inch) or more
These clearances are also necessaryfor changing the cooling fan. (1.5K or more)
• The inverter consists of precision mechanical and electronic parts. Never installor handle it in any of the following conditions as doing so could cause anoperation fault or failure.
Direct sunlightHigh temperature, high humidity
Oil mist, flammable gas, corrosive gas, fluff, dust, etc.
Horizontal placement
Transportation byholding front coveror dial
Vertical mounting(When mounted inside enclosure)
Mounting to combustible material
Vibration (5.9m/s or more)2
5
3. SPECIFICATIONS OF WIRING AND TERMINALS3.1 Terminal connection diagram (Japanese version)
FR-S520-0.1K to 3.7K (-R) (-C)
Power factor improving DC reactor(FR-BEL: Option)
3-phase ACpower supply
NFBRST
PCExternal transistor common
24VDC power supplyContact input common (source)
STF
STR
RH
RM
RL
SD
Forward rotation start
Reverse rotation start
Middle
High
Low
Frequency setting signals (Analog)
10 (+5V)
22
3
1
4 to 20mADC (+) 4 (4 to 20mADC)
Frequencysettingpotentiometer1/2W1k(*4)
RUN
SE
Running
FM
SD
Control input signals(No voltage input allowed)
Jumper: Remove this jumper when FR-BEL is connected.
Motor
IM
Ground
Alarmoutput
A
B
C
UVW
P1
P
N
(+) (-)
Earth (Ground)Grounding resistance 100 maximumGrounding cable size: 2mm2
Selected
Multi-speed selection
Operation status outputContact input common
5 (Common)
Open collectoroutput common
Current input (-)
MC
Opencollectoroutputs
Calibration resistor (*2)
SINK
SOURCE
RS-485 Connector (*1)
Inverter
Main circuit terminal, Control circuit input terminal, Control circuit output terminal
0 to 5VDC0 to 10VDC
Indicator1mA full-scaleAnalog meter(Digital indicator)
1mA
(*3)
When using current input as the frequency setting signal, set "4" in any of Pr. 60 to Pr. 63 (input terminal function selection) and assign AU (current input selection) to any of terminals RH, RM, RL and STR.
Take care not to shortterminals PC-SD.
Remarks*1 Only the type with RS-485 communication function*2 Not needed when the setting dial is used for calibration. Used when
calibration must be made near the frequency meter for such a reason as aremote frequency meter. However, the frequency meter needle may notdeflect to full-scale if the calibration resistor is connected. In this case, usethis resistor and setting dial together.
*3 You can switch between the sink and source logic positions. For details, referto the instruction manual (detailed).
*4 When the setting potentiometer is used frequently, use a 2W1kΩ potentiometer.CAUTION
Keep the signal cables more than 10cm (3.94inches) away from the power cables.
6
FR-S520S-0.1K to 1.5K (-R) (-C)
Power supply
NFB
RS
Motor
IM
Earth(Ground)
UVW
MC
Remarks• To ensure safety, connect the power input to the inverter via a magnetic
contactor and earth leakage circuit breaker or no-fuse breaker, and use themagnetic contactor to switch power on-off.
• The output is three-phase 200V.
7
3.1.1 Layout and wiring of main circuit terminals FR-S520-0.1K, 0.2K, 0.4K, 0.75K (-R) (-C) FR-S520-1.5K, 2.2K, 3.7K (-R) (-C)
P1
U V W
IM
R S T
R S T
N P
Jumper
Powersupply
Motor
P1
Jumper
R S T U V W
IM
N P
Powersupply
Motor
FR-S520S-0.1K, 0.2K, 0.4K, 0.75K (-R) FR-S520S-1.5K (-R)
P1
U V W
IM
N P
R S
Jumper
Powersupply
Motor
P1
U V W
IM
N P
R S
Jumper
Powersupply
Motor
Screw size: M3.5 Recommended cable size:
2mm2 (14 AWG) Crimping terminal: 2-3.5 Screw tightening torque: 1.2 N⋅m Overall wiring length:
100m (328.08feet) maximum *CAUTION
If the wiring length of the 0.1K or 0.2K is30m (98.43feet) or more, reduce thecarrier frequency to 1kHz.
Screw size: M4 Recommended cable size:
2mm2 (14 AWG) (1.5K, 2.2K)3.5mm2 (12 AWG) (3.7K)
Crimping terminal:2-4 (1.5K, 2.2K), 5.5-4 (3.7K)
Screw tightening torque: 1.5N⋅m Overall wiring length:
100m (328.08feet) maximum *
* When automatic torque boost is selected in Pr. 98 "automatic torque boost selection(motor capacity)": 30m (98.43feet) maximum.
CAUTION• The power supply cables must be connected to R, S, T. If they are connected
to U, V, W, the inverter will be damaged. (Phase sequence need not bematched.)(For use with a single-phase power supply, the power supply cables must beconnected to R and S.)
• Connect the motor to U, V, W.Turning on the forward rotation switch (signal) at this time rotates the motorcounterclockwise when viewed from the load shaft.
8
3.2 Terminal connection diagram (North America version) FR-S520-0.1K to 3.7K-NA (R)
Earth (Ground)Grounding resistance 100 maximumGrounding cable size: 2mm2
Power factor improving DC reactor(FR-BEL: Option)
3-phase ACpower supply
NFBRST
PCExternal transistor common
24VDC power supplyContact input common (source)
STF
STR
RH
RM
RL
SD
Forward rotation start
Reverse rotation start
Middle
High
Low
Frequency setting signals (Analog)
10 (+5V)
22
3
1
4 to 20mADC (+) 4 (4 to 20mADC)
Frequencysettingpotentiometer1/2W1k(*3)
RUN
SE
Running
Control input signals(No voltage input allowed)
Jumper: Remove this jumper when FR-BEL is connected.
Motor
IM
Earth(Ground)
Alarmoutput
A
B
C
UVW
P1
P
N
Selected
Multi-speed selection
Operation status outputContact input common
5 (Common)
Open collectoroutput common
Current input (-)
MC
Opencollectoroutputs
SINK
SOURCE
Inverter
Main circuit terminal, Control circuit input terminal, Control circuit output terminal
0 to 5VDC0 to 10VDC
(*2)
When using current input as the frequency setting signal, set "4" in any of Pr. 60 to Pr. 63 (input terminal function selection) and assign AU (current input selection) to any of terminals RH, RM, RL and STR.
RS-485 Connector (*1)
AM
5
(+)
(-)
Analog signal output(0 to 5VDC)
Take care not to shortterminals PC-SD.
Remarks*1 Only the type with RS-485 communication function*2 You can switch between the sink and source logic positions. For details, refer
to the instruction manual (detailed).*3 When the setting potentiometer is used frequently, use a 2W1kΩ potentiometer.
CAUTIONKeep the signal cables more than 10cm (3.94inches) away from the power cables.
9
3.2.1 Layout and wiring of main circuit terminals FR-S520-0.1K, 0.2K, 0.4K, 0.75K-NA (R) FR-S520-1.5K, 2.2K, 3.7K-NA (R)
P1
U V W
IM
R S T
N P
Jumper
Powersupply
Motor
P1
Jumper
R S T U V W
IM
N P
Powersupply
Motor
Screw size: M3.5 Recommended cable size:
2mm2 (14 AWG) Crimping terminal: 2-3.5 Screw tightening torque: 1.2 N⋅m Overall wiring length:
100m (328.08feet) maximum *CAUTION
If the wiring length of the 0.1K or 0.2K is30m (98.43feet) or more, reduce thecarrier frequency to 1kHz.
Screw size: M4 Recommended cable size:
2mm2 (14 AWG) (1.5K, 2.2K)
3.5mm2 (12 AWG) (3.7K) Crimping terminal:
2-4 (1.5K, 2.2K), 5.5-4 (3.7K) Screw tightening torque: 1.5N⋅m Overall wiring length:
100m (328.08feet) maximum *
* When automatic torque boost is selected in Pr. 98 "automatic torque boost selection(motor capacity)": 30m (98.43feet) maximum.
CAUTION• The power supply cables must be connected to R, S, T. If they are connected
to U, V, W, the inverter will be damaged. (Phase sequence need not bematched.)
• Connect the motor to U, V, W.Turning on the forward rotation switch (signal) at this time rotates the motorcounterclockwise when viewed from the load shaft.
<When single-phase power input is provided for three-phase power input inverter(NA version only)>• Reduce the output current.
FR-S520-"K-NA inverter 0.1 0.2 0.4 0.75 1.5 2.2 3.7Rated output current (A) 0.4 0.8 1.5 2.5 4.0 5.0 7.0Power supply capacity (kVA) 0.4 0.8 1.5 2.5 4.5 5.5 9.0AC input power (kW) 1.1 6.4 4.5 6.4 11.2 12.9 17.4
• Set m9 (Pr. 637) "current detection filter".Setting "801" in the manufacturer setting parameter C8 enables you to set them9 parameter.
CAUTIONParameters other than m9 can also be made to be displayed, but never alterthese since they are manufacturer setting parameters.
m9 Setting Description0 Single-phase power input
- - -(Factory setting) Three-phase power input
CAUTIONAlways return the C8 parameter to 0 (factory setting) after you have finished thesetting of m9.
10
3.3 Terminal connection diagram (European version) FR-S520S-0.2K to 1.5K-EC (R)
Earth (Ground)Grounding resistance 100 maximumGrounding cable size: 2mm2
Power factor improving DC reactor(FR-BEL: Option)
Power supply
NFBL1N
PCExternal transistor common
24VDC power supplyContact input common (source)
STF
STR
RH
RM
RL
SD
Forward rotation start
Reverse rotation start
Middle
High
Low
Frequency setting signals (Analog)
10 (+5V)
22
3
1
4 to 20mADC (+) 4 (4 to 20mADC)
Frequencysettingpotentiometer1/2W1k(*3)
RUN
SE
Running
Control input signals(No voltage input allowed)
Jumper: Remove this jumper when FR-BEL is connected.
Motor
IM
Earth(Ground)
Alarmoutput
A
B
C
UVW
P1
Selected
Multi-speed selection
Operation status outputContact input common
5 (Common)
Open collectoroutput common
Current input (-)
MC
Opencollectoroutputs
SINK
SOURCE
Inverter
Main circuit terminal, Control circuit input terminal, Control circuit output terminal
0 to 5VDC0 to 10VDC
(*2)
When using current input as the frequency setting signal, set "4" in any of Pr. 60 to Pr. 63 (input terminal function selection) and assign AU (current input selection) to any of terminals RH, RM, RL and STR.
RS-485 Connector (*1)
AM
5
(+)
(-)
Analog signal output(0 to 5VDC)
Take care not to shortterminals PC-SD.
Remarks*1 Only the type with RS-485 communication function*2 You can switch between the sink and source logic positions. For details, refer
to the instruction manual (detailed).*3 When the setting potentiometer is used frequently, use a 2W1kΩ potentiometer.• The output is three-phase 200V.
CAUTION• Keep the signal cables more than 10cm (3.94inches) away from the power cables.• To ensure safety, connect the power input to the inverter via a magnetic
contactor and earth leakage circuit breaker or no-fuse breaker, and use themagnetic contactor to switch power on-off.
11
3.3.1 Layout and wiring of main circuit terminals FR-S520S-0.2K, 0.4K, 0.75K-EC (R)
P1
U V W
IM
+-
L1 N
Powersupply
Motor
Jumper
Screw size: M3.5 Recommended cable size: 2mm2 (14 AWG) Crimping terminal: 2-3.5 Screw tightening torque: 1.2 N⋅m Overall wiring length: 100m (328.08feet) maximum *
CAUTIONIf the wiring length of the 0.2K is 30m (98.43feet) or more, reduce the carrier frequencyto 1kHz.
FR-S520S-1.5K-EC (R)
P1
U V W
IM
+-
L1 N
Jumper
Powersupply
Motor
Screw size: M4 Recommended cable size:2mm2 (14 AWG) Crimping terminal: 2-4 Screw tightening torque: 1.5N⋅m Overall wiring length: 100m (328.08feet) maximum *
Remarks* When automatic torque boost is selected in Pr. 98 "automatic torque boost
selection (motor capacity)": 30m (98.43feet) maximum.
CAUTION• For power input wiring, connect L1 to R/L1 of the terminal block and N to
S/L2 of the terminal block.• Connect the motor to U, V, W.
Turning on the forward rotation switch (signal) at this time rotates the motorcounterclockwise when viewed from the load shaft.
• Do not connect the power supply to U, V and W.
12
3.4 Main Circuit3.4.1 Explanation of main circuit terminals
Symbol Terminal Name DescriptionR, S, T* AC power input Connect to the commercial power supply.U, V, W Inverter output Connect a three-phase squirrel-cage motor.
N <->DC voltagecommon
DC voltage common terminal. Not isolated from the powersupply and inverter output.
P <+>, P1Power factorimproving DCreactor connection
Remove the jumper from across terminals P <+> -P1 andconnect the optional power factor improving DC reactor (FR-BEL).
Earth (Ground)For grounding the inverter chassis.Must be earthed.
* R, S, <L1, N> terminals for single-phase power input.
CAUTION< > Terminal names in parentheses are those of the EC version.
3.5 Control Circuit3.5.1 Explanation of control circuit terminals
Symbol Terminal Name Description
STFForward rotationstart
Turn on the STF signalto start forward rotationand turn it off to stop.
A stop command is given if STFand STR signal turn ON at the
STRReverse rotationstart
Turn on the STF signalto start reverse rotationand turn it off to stop.
same time.
Con
tact
inpu
t
RHRMRL
Multi-speedselection
You can select multiple speeds byshorting any of terminals RH, RMand RL signal.The priorities of the speedcommands are in order of jog,multi-speed setting (RH, RM, RL,REX) and AU.
The terminal functionchanges with thesetting of inputterminal functionselection (Pr. 60 toPr. 63). (*4)
SD(*1)
Contact inputcommon (sink)
Common terminal for contact inputs (terminals STF, STR,RH, RM, RL) and indicator connection (terminal FM).Isolated from terminals 5 and SE.
PC(*1)
External transistorcommon
24VDC powersupply
Contact inputcommon (source)
When connecting the transistor output (open collectoroutput) of a programmable controller (PLC) etc., connectthe positive external power supply for transistor output tothis terminal to prevent a malfunction due to leakagecurrent. It can be used as a 24V 0.1A DC power supplyacross PC-SD terminals. Acts as the common terminal ofthe contact input signals when source logic is selected.
10Frequency settingpower supply
5VDC, permissible load current 10mA.
2Frequencysetting(Voltage signal)
Inputting 0 to 5VDC (0 to 10V) provides the maximumoutput frequency at 5V (10V) and makes input and outputproportional.Use Pr. 73 "0 to 5V, 0 to 10V selection" to switch between5V and 10V.Input resistance 10kΩ. Maximum permissible input voltage20V.
Inpu
t si
gnal
s
Fre
que
ncy
sett
ing
4Frequencysetting(Current signal)
Input 4 to 20mA DC. Factory-adjusted to be 0Hz at 4mAand 60Hz <50Hz for EC version> at 20mA. Maximumpermissible input current 30mA. Input resistanceapproximately. 250Ω.Turn ON signal AU for current input.Use any of Pr. 60 to Pr. 63 (input terminal functionselection) to set the AU signal.
13
Symbol Terminal Name Description
Inpu
t si
gnal
s
5Frequencysetting inputcommon
Common terminal for the frequency setting signals(terminals 2, 4) and indicator connection (terminal AM).Isolated from terminals SD and SE. Do not connect thisterminal to the ground.
ABC
Alarm output
1 contact output which indicates that theprotective function of the inverter isactivated to stop output. 230V 0.3A AC,30V 0.3A DC. No conduction across B-C(conduction across A-C) when alarm(error) state.Conduction across B-C (no conductionacross A-C) when normal. (*6)
Ope
n co
llect
or
RUN Inverter running
Low when the inverter output frequencyis the starting frequency or higher(factory-set to 0.5Hz and changeable),and High during stop or DC injectionbrake operation (*2). Permissible load24V 0.1A DC
The terminalfunctionchanges with thesetting of outputterminal functionselection(Pr. 64, Pr. 65).(*5)
SE Open collectorcommon
Common terminal for inverter running terminal RUN.Isolated from terminals 5 and SD.
Pul
seF
M<
Japa
nes
e>
For meter
Factory setting of output item:FrequencyPermissible load current 1mA1440 pulses/s at 60Hz
Out
put
sign
als
Indi
cato
rA
nalo
gA
M<
NA
, E
C>
Analog signaloutput
One selected from outputfrequency and motorcurrent is output.The output signal isproportional to themagnitude of eachmonitoring item. Factory setting of output item:
FrequencyOutput signal 0 to 5VDCPermissible load current 1mA
Com
mun
icat
ion
RS-485connector(*3)
Using the parameter unit connection cable (FR-CB201 to205), the parameter unit (FR-PU04) can be connected.Communication operation can be performed using RS-485.
*1. Do not connect terminals SD and PC each other or to the ground.For sink logic, terminal SD acts as the common terminal of contact input. For sourcelogic, terminal PC acts as the common terminal of contact input.
*2. Low indicates that the open collector output transistor is on (conducts). High indicatesthat the transistor is off (does not conduct).
*3. Compatible with only the type having the RS-485 communication function. For details,refer to the separately available instruction manual (detailed).
*4. RL, RM, RH, RT, AU, STOP, MRS, OH, REX, JOG, RES, X14, X16, (STR) signalselection
*5. RUN, SU, OL, FU, RY, Y12, Y13, FDN, FUP, RL, LF, ABC signal selection*6. For compatibility with the European Directive (Low Voltage Directive), the operating
capacity of relay output (A, B, C) should be 30V, 0.3A DC.
14
3.5.2 Arrangement and wiring of control circuit terminalsPC SE RUN 10 2 5 4
SD STF STR RL RM RHSD
A B C
....Japanese version
....NA, EC versionFM
<AM>
Loosen the terminal screw and insert the cable into the terminal. Screw size: M3 (A, B, C terminals), M2 (other than on the left)
Tightening torque: 0.5N⋅m to 0.6N⋅m (A, B, Cterminals)0.22N⋅m to 0.25N⋅m (other thanthe above)
CAUTION
Undertightening can cause cable disconnectionor malfunction. Overtightening can cause a shortcircuit or malfunction due to damage to thescrew or unit.
Con
trol
circ
uit t
erm
inal
blo
ck
Cable size: 0.3mm2 to 0.75mm
2
Screwdriver: Small flat-blade screwdriver(Tip thickness: 0.4mm (0.02inches)/tip width: 2.5mm (0.10inches))
Wire the stripped cable after twisting it to prevent it from becoming loose.In addition, do not solder it.*
Cable stripping size
A, B, C terminals
Other than the above
(mm (inches))
6 (0.24)
5 (0.20)
*For the bar terminal, refer to the instruction manual (detailed).
3.5.3 Connection to RS-485 connector (only the inverter with RS-485communication function)
(1) When connecting the parameter unit (FR-PU04)Use the optional FR-CB2 .
(2) RS-485 communicationUse the RS-485 connector to perform communication operation from apersonal computer etc. By connecting the RS-485 connector to a computersuch as a personal computer, Factory Automation or other computer, by thecommunication cable, you can operate/monitor the inverter and read/write theparameter values using user programs. For further details, refer to theinstruction manual (detailed).• Standard with which RS-485 connector conforms: EIA Standard RS-485• Transmission format : Multi-drop link• Communication speed: Maximum 19200 bps• Overall extension : 500m (1640.42feet)
CAUTION
Do not plug the connector to a computer LAN board, fax modem socket,telephone modular connector etc. As they are different in electricalspecifications, the inverter may be damaged.
15
4. OPERATION/CONTROL<Control panel>The operation panel cannot be removed from the inverter.
Used to give the forward rotationoperation command. Use Pr. 17 to set reverse rotation.
Turns on/flickers* to indicate operation.
RUN
PUEXT
MODE SET
RUN
PU
EXT
STOPRESET
+-
Lit to indicate the PU operation mode.
Shows the frequency, parameter number, etc.
EXT indicationLit to indicate the external operation mode.
Setting dialUsed to change the frequencysetting and parameter values.This dial cannot be removed.
Used to switch between thePU and external operationmode. (Change the Pr. 79value to use the combinedmode.)
PU/EXT key
RUN key
STOP/RESET keyUsed to stop operation or reset an alarm.
SET keyUsed to define each setting.
Used to change the setting mode.MODE key
*RUN indication On: Indicates that forward rotation operation is being performed. Slow flickering (1.4 s cycle): Indicates reverse rotation. Fast flickering (0.2 s cycle) : Indicates that operation is not
RUN being performed but the key was pressed or the start command was given.
RUN indication
PU indication
3-digit monitor LED
<Basic operation> (Factory setting)
Parameter setting
MODE
Alarm history
MODE
PUEXT
Press PU/EXT key.
Turn settingdial to match frequency.
SET
Press SET key.
[Operation panel is used for operation]
PUEXT
Press PU/EXTkey.
Turn setting dial untildesired parameternumber appears.
SET
Press SET key to show present setting.
[Parameter setting change]
Turn settingdial to changevalue.
SET
Press SET keyto completesetting.
Monitor/frequency setting
MODE
Press MODEkey.
Return
After setting is complete,
press key once to show alarm history, or twice to show frequency setting screen.
MODE
Frequency setting has been written and completed!!
and frequency flicker.
RUNPress to start.STOP
RESETPress to stop.
Press MODEkey.
Press MODEkey.
16
4.1 Setting the Frequency to Perform Operation(Example: Performing Operation at 30Hz)
1. Screen at power-onThe monitor display appears.
PUEXT
2. Press the key to choose the PU operation mode.
PUEXT
Flicker ... Frequency setting complete!!
SET
3. Turn the setting dial to show the frequency you want to set. The frequency flickers for about 5 seconds.
4.
5.
6.To change the set frequency, perform the operation in above steps 3 and 4.(Starting from the previously set frequency.)
7.
RUN
Press the key to stop.STOPRESET
SET
RUN
RUN
PU
EXT
RUN
PU
EXTPU indication is lit.
RUN
PU
EXT
While the value is flickering, press the key to set the frequency.
RUN
PU
EXT
3 s later
Flickers for about 5 s
STOPRESET
SETIf you do not press the key, the value flickers for about 5 seconds and the displaythen returns to 0.0 (monitor display).At this time, return to "Step 3" and set the frequency again.
DisplayOperation
After the value has flickered forabout 3 seconds, the displayreturns to 0.0 (monitor display).Press the key to start operation.
Operation cannot be performed at the set frequency ... Why? Did you carry out step 4 within 5 seconds after step 3? (Did you press the
SET key within 5 seconds after turning the dial?)
Setting of higher than 60Hz cannot be made ... Why? Check to see if the Pr. 1 "maximum frequency" setting is 60Hz.
The frequency does not change by turning the dial ... Why? Check to see if the operation mode selected is the external operationmode.
Remarks
Pressing the setting dial shows the set frequency.• The setting dial can also be used like a potentiometer to perform operation.
Set Pr. 30 "extended function display selection" to "1" (extended functionparameter valid) and Pr. 53 "frequency setting operation selection" to "1"(setting dial potentiometer mode). Press the RUN key, turn the dial, and setthe frequency. After turning the setting dial, the frequency setting is changed
without pressing the SET key.(For an operation example, refer to the instruction manual (detailed).)
17
4.2 Setting the Parameters4.2.1 Example: Changing the Pr. 7 setting from "5s" to "10s"(For parameter details, refer to the instruction manual (detailed).)
1. Confirm the RUN indication and operation mode indication. The inverter must be at a stop. The inverter must be in the PU operation mode. (Press the key.)
2. Press the key to choose the parameter setting mode.
MODE
MODE
PUEXT
SET
5. Turn the setting dial until the desired value appears.Example: To change setting from "5" to "10"
6. Press the key to set the value.SET
MODE
RUN
PU
EXT
Flicker ... Parameter setting complete!!
3. Turn the setting dial until the desired parameter number appears.Example: Pr. 7 "acceleration time"
By turning the setting dial , you can read another parameter.
SETPress the key to show the setting again.
SETPress the key twice to show the next parameter.
DisplayOperation
The parameternumber read previously appears.
SET4. SET
After parameter setting is complete, press the key once to show the alarmhistory or twice to return to the monitor display. To change the setting of anotherparameter, perform the operation in above steps 3 to 6.
Press the key to read the
currently set value.Example: "5" (factory setting) appears.
Error display? • If write was performed with "1" set in Pr. 77
• If the operation panel does not have the write precedence (only forthe type with RS-485 function)
• If write was performed during operation• If write was performed in the external operation mode
Remarks• If the setting has not been changed, the value does not flicker and the next
parameter number appears.• Either step 1 or 2 may be carried out first.• Convenient usage
You can read the parameter number and set value in order without needing
to choose the parameter setting mode in steps 1 and 2 and press the SET
key after showing the desired parameter number.
18
4.2.2 Example: Changing the Pr. 30 setting from "0" to "1"(The extended parameters are made valid by setting "1" in Pr. 30 "extendedfunction display selection". Refer to page 27 for the extended function parameterlist and to the instruction manual (detailed) for details.)
After parameter setting is complete, press the key once to show the alarm history or twice to return to the monitor display. To change the setting of another parameter, perform the operation in above steps 3 to 6.
1.
2.MODE
Press the key to choose the parameter setting mode.
MODE
SET
SET
3.
5.
4. SET
6. Press the key to set the value.SET
MODE
RUN
PU
EXT
Flicker ... Parameter setting complete!!
Turn the setting dial to change it to the set value of .
By turning the setting dial , you can read another parameter.
SETPress the key to show the setting again.
SETPress the key twice to show the next parameter.
Press the key to read the currently set value. (factory setting) appears.
Confirm the RUN indication and operation mode indication. The inverter must be at a stop. The inverter must be in the PU operation mode. (Press the key.)PU
EXT
Operation Display
" "
" "
The parameternumber read previously appears.
Turn the setting dial until (Pr. 30) appears.
Error display?
• If the operation panel does not have the write precedence (only forthe type with RS-485 communication function)
• If write was performed during operation• If write was performed in the external operation mode
Remarks
If the setting has not been changed, the value does not flicker and the nextparameter number appears.
19
4.3 Clearing the ParametersPOINT
• The clear parameter CLr is an extended parameter. Set "1" in Pr. 30 and turnthe dial to show it. (Refer to page 18.)
• The parameters can be cleared by setting "1" in CLr "parameter clear".
3. Turn the setting dial until CLr "clear" appears. The Pr. 30 value must be "1". (Refer to steps 3 to 6 on page 18 for the parameter setting method.)
SET
5.
SET
1. RUN
PU
EXT
2.MODE
Press the key to choose the parameter setting mode.
MODE
4. Press the key to show "0".SET
Turn the setting dial to change it to "1".
6. Press the key.SET
Flicker ... Parameter clear complete!!
Confirm the RUN indication and operation mode indication. The inverter must be at a stop. The inverter must be in the PU operation mode. (Press the key.)PU
EXT
Operation Display
The parameternumber read previously appears.
By turning the setting dial , you can read another parameter.
SETPress the key to show Pr. 0 ( ).
CLr Setting Description0 Not executed.
1Parameter clear *1(Calibration parameters C1 to C7 are not cleared.)
10All clear *2(All set values including those of calibration parametersC1 to C7 are returned to factory settings.)
*1. Parameters are not cleared when "1" is set in Pr. 77 "parameter write disableselection".Pr. 75 "reset selection/PU stop selection", Pr. 38, Pr. 39, Pr. 53, Pr. 60 toPr. 65, Pr. 99, calibration parameters C1 to C7 and communicationparameters n13, 15 are not cleared.
*2. Pr. 75 "reset selection/PU stop selection" and communication parameter n13"PU language switching" are not cleared.
20
4.4 Monitoring the Output CurrentPOINT
The output current appears while the SET key is pressed in the monitor mode.
2.SET
3.
1.
Independently of whether the inverter is running in any operation mode or at a stop, the output current appears while the key is pressed.SET
Release the key to return to the output frequency monitor mode.
SET
(1.0A)
Press the key to choose the output
frequency monitor mode.
MODE
Hold down
Operation Display
Remarks
When Pr. 52 = "1", the output current is displayed in the monitor mode and the
output frequency appears while the SET key is pressed.
21
5. ADJUSTMENT OF THE FREQUENCY SETTINGPOTENTIOMETER AND INDICATOR
• Related parameters
Parameter Name Setting Range Factory Setting<EC Version>
38 Frequency setting voltage gain frequency 1 to 120Hz 60Hz <50Hz>39 Frequency setting current gain frequency 1 to 120Hz 60Hz <50Hz>C2 Frequency setting voltage bias frequency 0 to 60Hz 0HzC3 Frequency setting voltage bias 0 to 300% 0%*C4 Frequency setting voltage gain 0 to 300% 96%*C5 Frequency setting current bias frequency 0 to 60Hz 0HzC6 Frequency setting current bias 0 to 300% 20%*C7 Frequency setting current gain 0 to 300% 100%*
* Settings may differ because of calibration parameters.
Ou
tpu
t fr
eq
ue
ncy
(H
z)
Frequency setting voltage signal
Factory setting
5V or 10V0V
Frequency setting current signal
Factory setting
20mA4mA*C3(0% ) Pr.73 C4(100% )
60Hz<50Hz>( )Pr.39
0Hz
C6(20% ) C7(100% )
0HzC2( )
60Hz<50Hz>Pr.38( )
C5( ) Ou
tpu
t fr
eq
ue
ncy
(H
z)(Across terminals2-5)
(Across terminals4-5)
* Pr. 73 "0-5V/0-10V selection" changes the specifications of terminal "2".
POINT• Bias setting for 0 to 5VDC (0 to 10VDC) input: Use the calibration parameter
C2, C3 for setting.• Gain setting for 0 to 5VDC (0 to 10VDC) input: Use Pr. 38, calibration
parameter C4 for setting.• Bias setting for 4 to 20mADC input: Use calibration parameter C5, C6 for setting.• Gain setting for 4 to 20mADC input: Use Pr. 39, calibration parameter C7 for
setting.(For 4 to 20mADC input, set "4" in any of Pr. 60 to Pr. 63 (input terminalfunction selection) and assign AU (current input selection) to any of terminalsRH, RM, RL and STR.
5.1 Changing the Output Frequency Setting of theFrequency Setting Potentiometer(Bias and gain of frequency setting voltage (current))
POINT• Pr. 38, Pr. 39 and calibration parameters "C1 to C7" can be made to be read
by setting "1" (extended function parameter valid) in Pr. 30 "extendedfunction display selection".
The bias/gain of the frequency setting voltage (current) may be adjusted in any ofthe following methods:1) Changing the highest frequency
22
2) Adjusting the deviation of the highest frequency from the Pr. 38 (Pr. 39) setting.2)-1 Make adjustment with a voltage applied directly across terminals 2-5 (with
a current flowing across terminals 4-5)2)-2 Make adjustment at any point without a voltage applied across terminals 2-
5 (without a current flowing across terminals 4-5) (For the setting method,refer to the instruction manual (detailed).)
Changing example When you want to use the 0 to 5VDC input frequency settingpotentiometer to change the 5V-time frequency from 60Hz to50Hz
POINT• Pr. 38 is an extended function parameter. Pr. 30 must be set to "1".
(Refer to page 18.)• Change Pr. 38 "frequency setting voltage gain frequency" to 50Hz.
1) Changing the highest frequency.
3. Turn the setting dial until the parameter number 38 "frequency setting voltage gain frequency" appears.
4. SETPress the key to show the currently set value. (60Hz)
SET
5. Turn the setting dial to change the set value to "50.0". (50Hz)
2.MODE
6.Flicker ... Parameter setting complete!!
Press the key to set the value.SET SET
1. Confirm the RUN indication and operation mode indication. The inverter must be at a stop. The inverter must be in the PU operation mode. (Press the key.)PU
EXT
MODEPress the key to choose theparameter setting mode.
Pr. 30 must be set to "1". (For the parameter setting method, refer to steps 3 to 6 on page 18.)
By turning the setting dial , you can read another parameter.SETPress the key to show the setting again.
SETPress the key twice to show the next parameter.
RUN
PU
EXT
The parameternumber read previously appears.
Operation Display
The monitor/frequency setting indication cannot be changed to just 50Hz... Why?
The calibration parameter C4 "frequency setting voltage gain" value mustbe set. (Refer to page 23.)
RemarksTo change the value to more than 60Hz <50Hz>, Pr. 1 "maximum frequency"must be set to more than 60Hz <50Hz>.
23
Changing example Changing the calibration parameter C4 "frequency settingvoltage gain"
POINTThe calibration parameter C4 is an extended function parameter. Pr. 30 must beset to "1".
2) Adjusting a deviation of the highest frequency from the Pr. 38 (Pr. 39) setting.2)-1 Making adjustment with a voltage applied directly across terminals 2-5
(with a current flowing across terminals 4-5)
Turn the setting dial until " "
DisplayOperationRUN
PU
EXT
1.
PUEXT(Press the key.)
Confirm the RUN indication and operationmode indication.
The inverter must be at a stop.The inverter must be in the PU operationmode.
3.MODE
2. MODE
SET4. SETPress the
7.123
45 6
7
8
9
10
*
*The value is nearly 100 (%) in the maximum position of the potentiometer.
8. Press the key to set the value.SET SET
*
Flicker ... Parameter setting complete!!
5. Turn the setting dial until thecalibration parameter C4"frequency setting voltage gain"appears.
6. SETSET
Analog voltage analog-to-digital conversion value (%) across terminals 2-5
Press the key to show theanalog voltage analog-to-digitalconversion value (%).
(Adjustment complete)*The value is nearly 100 (%) in the maximum position of the potentiometer.
Apply a 5V voltage.(Turn the external potentiometerconnected to across terminals2-5 to the maximum (any position).)
Press the key to choose theparameter setting mode.
By turning the setting dial , you can read another parameter.SETPress the key to return to the " " indication (step 4).
SETPress the key twice to show the next parameter ( ).
CAUTION
(For details, refer to steps 3 to 6 on page 18.)Pr. 30 must be set to "1".
key to show " "
The parameternumber read previously appears.
appears.
When adjusting Pr. 38
After performing operation in step 7, do not touch the setting dial until completion of calibration.
The frequency meter (indicator) connected to across terminals FM-SD (AM-5) does notindicate just 50Hz ... Why?
The calibration parameter C1 "FM (AM) terminal calibration" value must be set. (Refer topage 24.)
When write is performed, an error ( ) is displayed. The gain and bias frequency settings are close.
24
5.2 Adjustment (Calibration) of the Frequency Meter(Indicator)
Changing example Deflecting the meter (Analog indicator) to full-scale (AcrossFM-SD: 1mA, across AM-5: 5V) at 60Hz
POINT• The calibration parameters "C1" can be made to be read by setting "1" (extended
function parameter valid) in Pr. 30 "extended function display selection".• Set the value of the calibration parameter C1 "FM (AM) terminal calibration".
MODE
5.
6. Press the key to enable setting. SETSET
RUN
PU
EXT
4.SET
9. SET
Flicker ... Parameter setting complete!!
SET
7. RUN
PU
EXT
RUNRUN
+
-
8.
2. MODE
Pr. 30 must be set to "1".(For details, refer to steps 3 to 6 on page 18.)
3. Turn the setting dial to show" " .
Operation Display1. Confirm the RUN indication and operation
mode indication.The inverter must be at a stop.
Press the key to show SET
" " .
The parameternumber read previously appears.
By turning the setting dial , you can read another parameter.
SETPress the key to return to the " " indication (step 4).
SETPress the key twice to show the next parameter ( ).
Press the key to choose theparameter setting mode.
Turn the setting dial until thecalibration parameter C1 "FM (AM)terminal calibration" appears.
Press the key to start theinverter. (The motor need not beconnected.)
Press the key.Setting is complete.
Turn the setting dial to adjust the indicator needle to the desired position.
Analog indicator
Remarks• Depending on the set value, it may take some time for the needle to move.• If "1" is set in Pr. 30 "extended function display selection", the calibration parameter
C1 "FM (AM) terminal calibration" can also be set in the external operation mode.
POINTBy setting the Pr. 54 "FM (AM) terminal function selection" value, preset Pr. 55"frequency monitoring reference" or Pr. 56 "current monitoring reference" to therunning frequency or current value at which the output signal is 1440 pulses/s (5V).At 1440 pulses/s (5V), the meter generally deflects to full-scale.
25
6. FUNCTION LIST6.1 Basic Function Parameter List
Pa-rame-
terName Indica-
tionSettingRange
MinimumSetting
Increments
FactorySetting
<EC Version>
CustomerSetting
0 Torque boost 0 to 15% 0.1% 6%
1 Maximum frequency 0 to 120Hz 0.1Hz 60Hz <50Hz>
2 Minimum frequency 0 to 120Hz 0.1Hz 0Hz
3 Base frequency 0 to 120Hz 0.1Hz 60Hz <50Hz>
4Multi-speed setting(high speed) 0 to 120Hz 0.1Hz 60Hz <50Hz>
5Multi-speed setting(middle speed) 0 to 120Hz 0.1Hz 30Hz
6Multi-speed setting(low speed) 0 to 120Hz 0.1Hz 10Hz
7 Acceleration time 0 to 999s 0.1s 5s
8 Deceleration time 0 to 999s 0.1s 5s
9Electronic thermalO/L relay 0 to 50A 0.1A Rated output
current
30Extended functiondisplay selection 0, 1 1 0
79Operation modeselection 0 to 4, 7, 8 1 0
Remarks• The extended function parameters are made valid by setting "1" in Pr. 30
"extended function display selection". (Refer to page 18)• The decimal places of a value of 100 or more (3 digits or more) cannot be set
to be displayed.
6.2 Explanation of the Basic Function ParametersFor details, refer to the instruction manual (detailed) separately available.
Pr. 0 "torque boost" Pr. 1 "maximum frequency",Pr. 2 "minimum frequency"
• Clamp the upper and lower limits ofthe output frequency.
Pr.1
Pr.2
Frequency settin
Minimum frequency
Maximum frequency
Out
put f
requ
ency
5V(10V)
(20mA) etc.
• Allows the motor torque in the lowspeed range to be adjustedaccording to the load.Make adjustment when stallprevention is operated when starting.
• When a constant-torque motor isused, set the following value:• 0.1K to 0.75K ......6%• 1.5K to 3.7K ........4%
Setting range
Base frequency
0
100%
Output frequency
Pr.0
Pr.3
Out
put v
olta
ge
26
Pr. 3 "base frequency" Pr. 4 "multi-speed setting (high speed)"Pr. 5 "multi-speed setting (middle speed)"Pr. 6 "multi-speed setting (low speed)"
• Set the base frequency (referencefrequency at rated motor torque)within the range 0 to 120Hzaccording to the motor.
Pr. 7 "acceleration time",Pr. 8 "deceleration time"
• You can select any speed (RH, RM,RL) by simply changing the externalcontact signal.
RH RM RLHigh speed ON OFF OFF
Middle speed OFF ON OFFLow speed OFF OFF ON
• Each speed (frequency) can be setto any value within the range 0 to120Hz if the inverter is running.
• The extended functions enablesetting of up to 15 speeds.
Pr. 9 "electronic thermal O/L relay"
• As the acceleration time, set thetime taken to reach theacceleration/deceleration referencefrequency in Pr. 20 from 0Hz, andas the deceleration time, set thetime taken to reach 0Hz from thePr. 20 value.
Acceleration time Deceleration time
Pr.20
Pr.7 Pr.8
0Hz Out
put
freq
uenc
y
Pr. 30 "extended function displayselection"
• Set this parameter whenshowing/setting the extendedfunction parameters.Setting Description
0 Only basic functions are displayed.1 All parameters are displayed.
• You can set a current value forprotection of the motor from overheat.Normally, set the rated motor current at50Hz as it is.
• At the setting of 0A, motor protectiondoes not function. (The output transistorprotection of the inverter functions.)
• When connecting multiple motors to theinverter, provide external thermal relaysto individual motors.
• For the 0.1K to 0.75K, this value isfactory-set to 85% of the rated invertercurrent.
Pr. 79 "operation mode selection"• The inverter has two different operation modes: operation under control of
external signals and operation from the PU (setting dial, RUN key). You canuse either or both operation modes.
Setting Description
0PU (setting dial, RUN key) operation or external operation can be selected by the
PUEXT key.
1 Only PU (setting dial, RUN key) operation may be performed.2 Only external operation may be performed.
Running frequency Start signal
3 • Setting made by setting dial• Multi-speed selection• 4 to 20mA (Made valid when AU signal turns on)
External terminal(STF/STR)
Running frequency Start signal4
External terminal signals (multi-speed, 0 to 5VDC, etc.) RUN key
7 PU operation interlock(Switching to PU operation mode is enabled/disabled by turning MRS signal ON/OFF)
8 Operation mode external signal switching (disabled during operation)Turn X16 signal ON/OFF to choose operation mode.
27
6.3 EXTENDED FUNCTION PARAMETER LISTSetting "1" in Pr. 30 "extended function display selection" makes the extended functionparameters valid. (Refer to the separately available instruction manual (detailed).)Parameter
Indica-tion
Name Outline
FactorySetting
<ECVersion>
For parameters 0 to 9, refer to the basic function parameters.
10 DC injection brakeoperation frequency 3Hz
11 DC injection brakeoperation time 0.5s
12 DC injection brakevoltage
Set the timing of switching to DC injectionbrake (0 to 120Hz), the time to apply DCinjection brake (0 to 10s), and the brakingtorque at DC injection brake start (0 to 15%).(Set Pr. 12 to 4% when a constant-torquemotor is used.) 6%
13 Starting frequency
Frequency which is output by the inverter firstat a start and gives great influence to thestarting torque. About 1 to 3Hz for vertical liftapplications, or up to 5Hz to the maximum. Forother than vertical lift applications, factorysetting of about 0.5Hz is recommended.0 to 60Hz
0.5Hz
14 Load patternselection
Choose the output frequency and output voltagepatterns according to the application (loadcharacteristic).0: For constant-torque loads (when relatively large
torque is needed at low to high speeds)1: For variable-torque loads (for applications
where torque is small at low speed, e.g. fansand pumps)
2: For vertical lifts (for elevators at reverse rotationboost of 0%)
3: For vertical lifts (for elevators at forward rotationboost of 0%)
0
15 Jog frequency 5Hz
16 Jog acceleration/deceleration time
Speed command (0 to 120Hz) andacceleration/deceleration slope (0 to 999s) forjog (inching) operation 0.5s
17 RUN key rotationdirection selection
The RUN key of the operation panel can be usedto choose the direction of rotation for operation.0: forward rotation, 1: reverse rotation
0
19Base frequencyvoltage
Indicates the magnitude of the output voltage atthe base frequency (Pr. 3).888: 95% of power supply voltage- - -: Same as power supply voltage0 to 500V, 888, - - -
- - -<888>
20Acceleration/decelerationreference frequency
Indicates the frequency to be referenced foracceleration from or deceleration to 0Hz in thetime set in Pr. 7 "acceleration time" or Pr. 8"deceleration time".1 to 120Hz
60Hz<50Hz>
28
Parameter
Indica-tion
Name Outline
FactorySetting
<ECVersion>
21 Stall preventionfunction selection 0
22 Stall preventionoperation level
Stall prevention is a function designed tosuspend a frequency increase duringacceleration or suspend a frequency decreaseduring deceleration if the preset current (0 to200%) is exceeded, in order to prevent anovercurrent alarm.Pr. 21 allows you to select whether to use stallprevention or not according to theacceleration/deceleration status.If the Pr. 22 value is set to 170% or more,torque will not be developed.In that case, set "1" in Pr. 21.
150%
23
Stall preventionoperation levelcompensationfactor at doublespeed
Used to reduce the stall prevention level at orabove the base frequency.Setting other than "- - -" specifies the current levelat 120Hz which is lower than the Pr. 22 value ofthe stall prevention level at base frequency.0 to 200%, - - -
- - -
24 Multi-speed setting(speed 4)
- - -
25 Multi-speed setting(speed 5)
- - -
26 Multi-speed setting(speed 6)
- - -
27Multi-speed setting(speed 7)
Setting other than "- - -" specifies speeds 4 to 7.By combining ON and OFF of the contactsignals (RH, RM, RL signals), the runningspeed can be changed step-by-step.
RH RM RLON ON
ON
ONONON
ON ON
ON
Speed 4
Speed 5
Speed 6
Speed 7
OFF
OFF
OFF
0 to 120Hz, - - -- - -
28Stall preventionoperation reductionstarting frequency
You can reduce the stall prevention level in thehigh frequency range.0 to 120Hz
60Hz<50Hz>
29 Acceleration/deceleration pattern
Used to determine the frequency changingpattern at acceleration/deceleration.0: Linear acceleration/deceleration1: S-pattern acceleration/deceleration A
(e.g. machine tool spindle applications)2: S-pattern acceleration/deceleration B
(e.g. load collapse preventing applicationsfor conveyors and so on)
0
For parameter 30, refer to the basic function parameters.31 Frequency jump 1A - - -32 Frequency jump 1B - - -33 Frequency jump 2A - - -34 Frequency jump 2B - - -35 Frequency jump 3A - - -36 Frequency jump 3B
Set the frequency range you want to evadeduring constant-speed operation to avoidresonance with a machine.0 to 120Hz, - - -
- - -
37 Speed display
You can convert the frequency monitor/setfrequency of the operation panel into the loadspeed and display it. Setting 0 shows the outputfrequency, and setting 0.1 to 999 shows the loadspeed. (Set the speed for 60Hz operation.)0, 0.1 to 999
0
29
Parameter
Indica-tion
Name Outline
FactorySetting
<ECVersion>
38Frequency settingvoltage gainfrequency
You can set as desired the magnitude (slope) ofthe output frequency to the external frequencysetting voltage signal (0 to 5V or 0 to 10V).1 to 120Hz
60Hz<50Hz>
39Frequency settingcurrent gainfrequency
You can set as desired the magnitude (slope)of the output frequency to the externalfrequency setting current signal (4 to 20mA).1 to 120Hz
60Hz<50Hz>
40Start-time groundfault detectionselection
Set whether a ground fault is to be detected ornot at a start.0: Not detected1: Detected
0<1>
41Up-to-frequencysensitivity
You can adjust the ON range of the up-to-frequency signal (SU) to be output when theoutput frequency reaches the runningfrequency. You can use this function to ensurethat the running frequency has been reachedor use it as the operation start signal etc. forrelated equipment.Use Pr. 64 or Pr. 65 to assign the terminalused for SU signal output.0 to100%
10%
42Output frequencydetection
Set the reference value at which the signal(FU) is output when the output frequency risesto or above a certain value. This function canbe used for electromagnetic brake operation,open signal, etc.Use Pr. 64 or Pr. 65 to assign the terminalused for the FU signal.0 to 120Hz
6Hz
43Output frequencydetection forreverse rotation
Set the reference value at which the signal(FU) is output when the output frequency risesto or above a certain value. This function isvalid for reverse operation.0 to 120Hz, - - -
- - -
44Secondacceleration/deceleration time
Second function for the acceleration/deceleration time set in Pr. 7 or Pr. 8.0 to 999s
5s
45 Seconddeceleration time
Second function for the deceleration time setin Pr. 8.0 to 999s, - - -
- - -
46 Second torqueboost
Second function for the torque boost set inPr. 0.0 to 15%, - - -
- - -
47 Second V/F(base frequency)
Second function for the base frequency set inPr. 3.0 to 120Hz, - - -
- - -
48 Output currentdetection level
Set the level at which the output currentdetection signal (Y12) is output.0 to 200%
150%
49Output currentdetection signaldelay time
When the output current is at or above the outputcurrent detection level (Pr. 48) for longer than thisperiod (Pr. 49), the output current detection signal(Y12) is output.0 to 10s
0s
30
Parameter
Indica-tion
Name Outline
FactorySetting
<ECVersion>
50 Zero currentdetection level
Set the level at which the zero currentdetection signal (Y13) is output.0 to 200%
5%
51Zero currentdetection time
When the output current is at or below the zerocurrent detection level (Pr. 50) for longer than thisperiod (Pr. 51), the zero current detection signal(Y13) is output.0.05 to 1s
0.5s
52Control paneldisplay dataselection
You can choose the data displayed on theoperation panel.0: Output frequency1: Output current100: Set frequency during stop/output
frequency during operation
0
53Frequency settingoperation selection
You can use the setting dial like apotentiometer to perform operation.0: Setting dial frequency setting mode1: Setting dial potentiometer mode
0
54FM (AM) terminalfunction selection
You can choose the indicator connected to theFM (AM) terminal.0: Output frequency monitor1: Output current monitor
0
55Frequencymonitoringreference
Set the reference value of frequency monitoring.0 to 120Hz
60Hz<50Hz>
56 Current monitoringreference
Set the reference value of current monitoring.0 to 50A
Ratedoutputcurrent
57Restart coastingtime - - -
58 Restart cushiontime
At power restoration after an instantaneouspower failure, you can restart the inverter withoutthe motor being stopped (with the motorcoasting).The inverter begins to restart after this period(Pr. 57) has elapsed after power restoration.The inverter does not restart by setting "- - -"."0" setting generally does not pose a problem butyou can adjust the time (0 to 5s, - - -) accordingto the magnitude of the load.When the restart coasting time (Pr. 57) haselapsed, the output voltage is risen gradually.Set this cushion time (0 to 60s).Operation may be performed generally at thefactory setting, but you can adjust the timeaccording to the magnitude of the load.
1s
59Remote settingfunction selection
You can set the remote setting function whichis used when the operation panel is away fromthe control box, for example.0: Without remote setting function1: With remote setting function
With frequency setting storage function2: With remote setting function
Without frequency setting storage function
0
31
ParameterIndica-
tionName Outline Factory
Setting
60RL terminal functionselection 0
61 RM terminalfunction selection
1
62 RH terminalfunction selection
2
63 STR terminalfunction selection
You can choose the following input signals:0: RL (multiple low-speed operation command)1: RM (multiple middle-speed operation
command)2: RH (multiple high-speed operation command)3: RT (second function selection)4: AU (current input selection)5: STOP (start self-holding selection)6: MRS (output stop)7: OH (external thermal relay input)8: REX (15 multi-speed selection)9: JOG (jog operation selection)10: RES (reset)14: X14 (PID control valid terminal)16: X16 (PU operation/external operation
switching)- - -: STR (reverse rotation start (may be
assigned to only STR terminal))
- - -
64RUN terminalfunction selection 0
65A, B, C terminalfunction selection
You can choose the following output signals:0: RUN (inverter running)1: SU (up-to-frequency)3: OL (overload warning)4: FU (output frequency detection)11: RY (operation ready)12: Y12 (output current detection)13: Y13 (zero current detection)14: FDN (PID lower limit signal)15: FUP (PID upper limit signal)16: RL (PID forward/reverse rotation signal)98: LF (minor failure output)99: ABC (alarm output)
99
66 Retry selection
You can choose the retry alarm to be activatedwhen the protective function is activated.0: OC1 to 3, OV1 to 3, THM, THT, GF, OHT,
OLT, PE, OPT1: OC1 to 3, 2: OV1 to 3, 3: OC1 to 3, OV1 to 3
0
67 Number of retries atalarm occurrence
You can set the number of retries to be madewhen the protective function is activated.0: No retry1 to 10: Without alarm output during retry
operation101 to 110: With alarm output during retry
operation
0
68 Retry waiting time
You can set the waiting time from when theprotective function is activated until a retry ismade.0.1 to 360s
1s
69Retry count displayerase
You can display the cumulative number ofsuccessful restarts made by retries when theprotective function is activated.0: Cumulative count erase
0
32
ParameterIndica-
tionName Outline Factory
Setting
70 Soft-PWM setting
You can choose whether Soft-PWM control isto be exercised or not.When Soft-PWM is valid, you can change themetallic motor tone into an unoffendingcomplex tone.0: Soft-PWM invalid1: Soft-PWM valid
1
71 Applied motor
Set the motor to be used.0: Thermal characteristic for Mitsubishi
standard motor1: Thermal characteristic for Mitsubishi
constant-torque motor
0
72PWM frequencyselection
You can change the PWM carrier frequency.Increasing this value reduces the tone, butincreases noise and leakage current.The setting is in [kHz].0: 0.7kHz, 15: 14.5kHz0 to 15
1
73 0-5V/0-10Vselection
You can set the input voltage specification ofterminal "2".0: For 0 to 5VDC input1: For 0 to 10VDC input
0
74 Input filter timeconstant
Valid for eliminating noise of the frequencysetting circuit.A larger set value increases the time constant.
1
75Reset selection/PUstop selection
You can choose the function of the STOP
RESET keyon the operation panel.0: Reset normally enabled/PU stop key disabled
(In other than PU and combined operation modes)1: Enabled at reset alarm occurrence only/
PU stop key disabled(In other than PU and combined operation modes)
14: Reset normally enabled/normallydecelerated to stop
15: Enabled at alarm occurrence only/normallydecelerated to stop
14
76 Cooling fanoperation selection
You can control the operation of the coolingfan built in the inverter. (Operates in power-onstatus.)0: The fan normally operates at power-on of
the inverter.1: The fan is normally on during inverter
operation. The fan switches on/offaccording to the temperature during a stopof the inverter whose status is monitored.
1
77Parameter writedisable selection
You can choose whether to enable or disableparameter write.0: Write is enabled only during a stop in the
PU operation mode1: Write disabled (except some parameters)2: Write during operation enabled (external
mode and during operation)
0
78Reverse rotationprevention selection
You can prevent trouble during reverseoperation due to false input of the start signal.0: Both forward rotation and reverse rotation enabled1: Reverse rotation disabled2: Forward rotation disabled
0
For parameter 79, refer to the basic function parameters.
33
ParameterIndica-
tionName Outline Factory
Setting
80 Multi-speed setting(speed 8) - - -
81 Multi-speed setting(speed 9) - - -
82 Multi-speed setting(speed 10) - - -
83 Multi-speed setting(speed 11) - - -
84 Multi-speed setting(speed 12) - - -
85 Multi-speed setting(speed 13) - - -
86 Multi-speed setting(speed 14) - - -
87 Multi-speed setting(speed 15)
Setting other than "- - -" specifies speeds 8 to 15.By combining ON and OFF of the contactsignals (RH, RM, RL, REX signals), the runningspeed can be changed step-by-step.Use Pr. 63 to assign the REX signal.
RH RM RL
ON
ONON
ON
REX
ON
ONONON
ON ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Speed 8
Speed 9
Speed 10
Speed 11
Speed 12
Speed 13
Speed 14
Speed 15
OFF
OFF
OFF
OFF OFF OFF
OFF
OFF
OFF
OFF
OFF
OFF
0 to 120Hz, - - - - - -
88 PID action selectionUsed to choose the operation of PID control.20: PID reverse action,21: PID forward action
20
89 PID proportionalband
Used to set the proportional band for PID control.0.1 to 999%, - - - 100%
90 PID integral time Used to set the integral time for PID control.0.1 to 999s, - - - 1s
91 PID upper limit Used to set the upper limit value for PID control.0 to 100%, - - - - - -
92 PID lower limit Used to set the lower limit value for PID control.0 to 100%, - - - - - -
93 PID action set pointfor PU operation
Used to set the PID action set point for PU operation.0 to 100% 0%
94 PID differential time Used to set the differential time for PID control.0.01 to 10s, - - - - - -
95 Rated motor slipUsed to set the rated motor slip to make slipcompensation.0 to 50%, - - -
- - -
96 Slip compensationtime constant
Used to set the response time of slip compensation.0.01 to 10s 0.5s
97Constant-output regionslip compensationselection
Used to choose whether slip compensation ismade or not in the constant-output region.0, - - -
- - -
98Automatic torqueboost selection(Motor capacity)
You can set the motor capacity and exerciseautomatic torque boost control."- - -" specifies V/F control.Set the motor capacity used.• The motor capacity should be equal to or
one rank lower than the inverter capacity.• The number of motor poles should be 2, 4 or
6. (Only 4 poles for constant-torque motor)• Single-motor operation (one motor run by
one inverter) should be performed.• Wiring length from inverter to motor should
be within 30m (98.43feet).When using a constant-torque motor, set "1" inPr. 71.<Example> For 1.5kW, set "1.5".0.1 to 3.7kW, - - -
- - -
99 Motor primaryresistance
You can set the motor's primary resistance value.(Normally, this parameter need not be set.)0 to 50Ω, - - -
- - -
34
CalibrationParameter
Indica-tion
Name OutlineFactorySetting
C1(FM:900)(AM:901)
FM (AM) terminalcalibration
You can calibrate the indicator connected toacross terminals FM-SD (AM-5).
C2
(902)
Frequency settingvoltage biasfrequency
You can set as desired the magnitude (slope)of the output frequency to the externalfrequency setting voltage signal (0 to 5V or 0to 10V). (Bias frequency)0 to 60Hz
0Hz
C3
(902)Frequency settingvoltage bias
Used to adjust the analog-to-digital convertedvoltage value of the frequency set incalibration parameter C4. (Bias %)0 to 300%
0%*
C4
(903)Frequency settingvoltage gain
Used to adjust the analog-to-digital convertedvoltage value of the frequency set in Pr. 38.(Gain %)0 to 300%
96%*
C5
(904)
Frequency settingcurrent biasfrequency
You can set as desired the magnitude (slope)of the output frequency to the externalfrequency setting current signal (4 to 20mA).0 to 60Hz
0Hz
C6
(904)Frequency settingcurrent bias
Used to adjust the analog-to-digital convertedvoltage value of the frequency set incalibration parameter C5. (Bias %)0 to 300%
20%*
C7
(905)Frequency settingcurrent gain
Used to adjust the analog-to-digital convertedvoltage value of the frequency set in Pr. 39.(Gain %)0 to 300%
100%*
C8(269) Parameter for manufacturer setting. Do not set.
CLr Parameter clear
0: Not executed1: Initialization of parameters other than
calibration values (parameter clear)10: Initialization of parameters including
calibration values (all clear)
0
ECL Alarm history clear0: Not cleared1: Alarm history clear
0
*Settings may differ because of calibration parameters.
35
• Parameters which can be read on only the type having the RS-485communication function. (When the parameter unit (FR-PU04) is used,operation from the operation panel is not accepted.)
Communi-cation
ParameterIndica-
tion
Name Outline
FactorySetting<NA, ECVersion>
n1
(331)Communicationstation number
Set the station number for communicationfrom the RS-485 connector.0 to 31: Specify the station number of theinverter.
0
n2
(332)Communicationspeed
48: 4800bps96: 9600bps192: 19200bps
192
n3
(333) Stop bit length
0: Stop bit length 1 bit/data length 81: Stop bit length 2 bits/data length 810: Stop bit length 1 bit/data length 711: Stop bit length 2 bits/data length 7
1
n4
(334)Parity checkpresence/absence
0: Absent1: With odd parity check2: With even parity check
2
n5
(335)
Number ofcommunicationretries
Set the permissible number of retries atoccurrence of a data receive error. "- - -"specifies that the inverter does not come to analarm stop if a communication error occurs.0 to 10, - - -
1
n6
(336)Communicationcheck time interval
Set the interval of communication check time.If a no-communication status persists forlonger than the permissible time, the inverterwill come to an alarm stop.0: No communication0.1 to 999s- - -: Check suspended
0s<- - ->
n7
(337) Wait time setting
Set the waiting time from when data istransmitted to the inverter until response ismade.0 to 150ms- - -: Set in communication data
- - -
n8
(338)Operationcommand write
You can choose whether the operationcommand is given by the computer or externalterminal.0: Command write from computer1: Command write from external terminal
0
n9
(339)Speed commandwrite
You can choose whether the speed commandis given by the computer or external terminal.0: Command write from computer1: Command write from external terminal
0
n10
(340)Link start modeselection
You can choose the operation mode at power-on or at power restoration after instantaneouspower failure. Set "1" to select the computerlink operation mode.0: Mode set in Pr. 79 is established.1: Started in computer link mode.
0
36
Communi-cation
ParameterIndica-
tion
Name Outline
FactorySetting<NA, ECVersion>
n11
(341) CR/LF selection0: Without CR/LF1: With CR, without LF2: With CR/LF
1
n12(342)
E2PROM write
selection
0: Write to RAM and E2PROM
1: Write to RAM only0
n13
(145)PU displaylanguage
0: Japanese1: English2: German3: French4: Spanish5: Italian6: Swedish7: Finish
0<1>
n14(990)
PU buzzer soundcontrol
0: Without sound, 1: With sound 1
n15
(991)PU contrastadjustment
0 (bright)
63 (dark)58
n16
(992)
PU main displayscreen dataselection
0: Selectable between output frequency andoutput current100: Set frequency (during stop)Output frequency (during operation)
0
n17
(993)
PU disconnectiondetection/PUsetting lock
0: Without PU disconnection error/PUoperation valid
1: Error at PU disconnection/PU operation valid10: Without PU disconnection error/
PU operation invalid
0
For details of the program, etc., refer to the instruction manual (detailed)separately available.
Remarks
The parameter numbers within parentheses are those for use of the parameterunit (FR-PU04). Pr. stands for a parameter number.
37
7. ERRORS AND PROTECTIVE FUNCTIONS7.1 About Errors (Definitions)When an alarm occurs in the inverter, the protective function is activated to bringthe inverter to an alarm stop and the PU display automatically changes to any ofthe following error (alarm) indications.For details, refer to the instruction manual (detailed) which is separately available.(1) Major failures
Control PanelIndication
Function Name Definition
(OC1)Overcurrent cut-off duringacceleration
The inverter output current rose to orabove about 200% of the rated invertercurrent during acceleration.
(OC2)Overcurrent cut-off duringconstant speed
The inverter output current rose to orabove about 200% of the rated invertercurrent during constant-speed operation.
(OC3)Overcurrent cut-off duringdeceleration
The inverter output current rose to orabove about 200% of the rated invertercurrent during deceleration.
(OV1)Regenerative overvoltagecut-off during acceleration
Excessive regenerative energy or surgevoltage occurred during acceleration.
(OV2)Regenerative overvoltagecut-off during constantspeed
Excessive regenerative energy or surgevoltage occurred during constant speed.
(OV3)Regenerative overvoltagecut-off during decelerationor stop
Excessive regenerative energy or surgevoltage occurred during deceleration orstop.
(THM)Motor overload cut-off(Electronic thermalovercurrent protection) (*1)
Overload or reduced cooling capabilityduring low-speed operation
(THT)Inverter overload cut-off(Electronic thermalovercurrent protection) (*1)
Current more than 150% of the ratedoutput current flew and overcurrent shut-offdid not occur.
(FIN) Fin overheat Temperature rise of the heat sink.
(GF)Start-time output sideground fault overcurrentprotection (*2)
Ground fault occurred on the inverter'soutput side.
(OHT) External thermal relay (*3)External thermal relay provided forprotection from overheat was actuated(contact open).
(OLT) Stall prevention (overload)Stall prevention was activated to drop therunning frequency to 0. (OL appears whilestall prevention is activated.)
(OPT) Communication error
Communication errors occurredconsecutively more than the permissiblenumber of retries when the RS-485connector is used and communicationparameter n5 = "- - -". RS-485 communication error occurred. Communication was broken for a periodset in communication parameter n6.(Only for the type with RS-485 function.)
(PE) Parameter error Error occurred in the parameter stored.
38
Control PanelIndication
Function Name Definition
(PUE) PU disconnected
PU was disconnected when communicationparameter n17 = "1".This function is valid for only the type withRS-485 communication function.
(RET) Retry countOperation could not be resumed properlywithin the preset number of retries.
(CPU) CPU errorArithmetic operation of the built-in CPUdoes not end within the predetermined time.
*1. Resetting the inverter initializes the internal thermal integral data of theelectronic overcurrent protection.
*2. Activated only when "1" is set in Pr. 40 "start-time ground fault detectionselection".
*3. Activated only when any of Pr. 60 to Pr. 63 (input terminal functionselection) is set to OH.
(2) Minor failuresControl Panel
IndicationFunction Name Definition
(FN) Fan troubleThe cooling fan built in the inverter failed(stopped).
Remarks
In this product, the cooling fan does not start until the start signal ( RUN key,STF, STR signal) turns on. (Refer to Pr. 76 "cooling fan operation selection".)
(3) WarningsControl Panel
IndicationFunction Name Definition
(OL)Stall prevention(overcurrent) (*4)
Current more than 150% of the ratedinverter current flew in the motor andoperation is being performed to prevent theinverter from resulting in overcurrent shut-off.
(oL)Stall prevention(overvoltage)
Regenerative energy of the motor becameexcessive and operation is beingperformed to stop the frequency fromdecreasing to prevent overvoltage shut-off.
(PS)PU stop (Stopped with PUSTOP key)
Pr. 75 "PU stop selection" had been setand a stop was made by pressing the STOP
RESET
key of the operation panel or parameterunit (FR-PU04) during operation in theexternal operation mode.
(UV) UndervoltagePower supply voltage of the inverterdropped.
(Err) During reset During inverter reset (RES signal is ON)
* 4. The stall prevention operation current may be set to any value. It is factory-set to 150%.
39
(4) Write errorsControl Panel
IndicationFunction Name Definition
(Er1) Write disable error
• Write was performed with "1" set inPr. 77.
• Frequency jump setting rangeoverlapped.
• Parameter write was performed thoughthe operation panel does not have thewrite precedence. (Only the type havingRS-485 communication function)
(Er2)Write-while-runningerror/mode designationerror
Write was performed during operation.Write was performed in the externaloperation mode.
(Er3) Calibration errorAnalog input bias and gain calibrationvalues are too close.
• Major failure: When the protective function is activated, the inverter output isshut-off and an alarm output is provided.
• Minor failure: When the protective function is activated, the output is not shut-off. The minor failure signal can be output by making parametersetting. (Set "98" in Pr. 64 or Pr. 65 (output terminal functionselection).)
7.2 Inverter ResetPerforming any of the following operations resets the inverter. Note thatperforming reset clears (erases) the internal thermal integral value of theelectronic overcurrent protection and the number of retries.
Operation 1 ...... Using the operation panel, perform reset with the STOPRESET key.
(Enabled only when the inverter protective function is activated(major failure))
Operation 2 ...... Switch power off once, then on again.Operation 3 ...... Turn on the reset signal (RES).
(Assign this signal to any of Pr. 60 to Pr. 63.)
40
8. SPECIFICATIONS8.1 Ratings(1) 3-phase 200V power supply
Japanese versionFR-S520-0.1K to 3.7K(-R)(-C)
NA versionFR-S520-0.1K to 3.7K-NA(R)
Model FR-S520-"K(-R)(-C) 0.1 0.2 0.4 0.75 1.5 2.2 3.7kW 0.1 0.2 0.4 0.75 1.5 2.2 3.7
Applicable motor capacity (*1)HP 1/8 1/4 1/2 1 2 3 5
Rated capacity (kVA) (*2) 0.3 0.5 1.0 1.6 2.8 4.0 6.6Rated current (A) 0.8 1.4 2.5 4.1 7.0 10 16.5Overload capacity (*3) 150% 60s, 200% 0.5s (Inverse-time characteristics)O
utpu
t
Voltage (*4) Three-phase 200 to 240V 50Hz/60HzRated input ACvoltage/frequency
Three-phase 200 to 240V 50Hz/60Hz
Permissible AC voltage fluctuation 170 to 264V 50Hz/60HzPermissible frequency fluctuation Within ±5%
Pow
er s
uppl
y
Power supply equipment capacity(kVA) (*5)
0.4 0.7 1.2 2.1 4.0 5.5 9
Protective structure (JEM1030)Enclosed type (IP20). IP40 for totally-enclosed structureseries.
Cooling system Self-cooling Forced air cooling
Approximate weight (kg (lbs))0.5
(1.1)0.5
(1.1)0.8
(1.76)0.9
(1.98)1.5
(3.3)1.5
(3.3)2.1
(4.62)*1. The applicable motor capacity indicated is the maximum capacity
applicable for use of the Mitsubishi 4-pole standard motor.*2. The rated output capacity indicated assumes that the output voltage is 230V.*3. The % value of the overload capacity indicates the ratio of the overload
current to the inverter's rated output current.For repeated duty, allow time for the inverter and motor to return to orbelow the temperatures under 100% load.
*4. The maximum output voltage does not exceed the power supply voltage.You can set the maximum output voltage to any value below the powersupply voltage.
*5. The power supply capacity changes with the values of the power supplyside impedances (including those of the input reactor and cables).
41
(2) Single-phase 200V power supply Japanese versionFR-S520S-0.1K to 1.5K(-R)
EC versionFR-S520S-0.2K to 1.5K-EC(R)
Model FR-S520S-"K(-R) 0.1 0.2 0.4 0.75 1.5kW 0.1 0.2 0.4 0.75 1.5
Applicable motor capacity (*1)HP 1/8 1/4 1/2 1 2
Rated capacity (kVA) (*2) 0.3 0.5 1.0 1.6 2.8Rated current (A) 0.8 1.4 2.5 4.1 7.0Overload capacity (*3) 150% 60s, 200% 0.5s (Inverse-time characteristics)O
utpu
t
Voltage (*4) Three-phase 200 to 240V 50Hz/60HzRated input AC voltage/frequency Single-phase 200 to 240V 50Hz/60HzPermissible AC voltage fluctuation 170 to 264V 50Hz/60HzPermissible frequency fluctuation Within ±5%
Pow
er s
uppl
y
Power supply equipment capacity(kVA) (*5)
0.5 0.9 1.5 2.5 4.4
Protective structure (JEM1030) Enclosed type (IP20).
Cooling system Self-coolingForced
aircooling
Approximate weight (kg (lbs))0.5
(1.1)0.6
(1.32)0.8
(1.76)1.0
(2.2)1.5
(3.3)*1. The applicable motor capacity indicated is the maximum capacity
applicable for use of the Mitsubishi 4-pole standard motor.*2. The rated output capacity indicated assumes that the output voltage is 230V.*3. The % value of the overload capacity indicates the ratio of the overload
current to the inverter's rated output current.For repeated duty, allow time for the inverter and motor to return to orbelow the temperatures under 100% load.
*4. The maximum output voltage does not exceed the power supply voltage.You can set the maximum output voltage to any value below the powersupply voltage.
*5. The power supply capacity changes with the values of the power supplyside impedances (including those of the input reactor and cables).
42
8.2 Common Specifications
Control methodSelectable between Soft-PWM control and high carrierfrequency PWM control, V/F control or automatic torque boostcontrol selectable.
Output frequency range 0.5 to 120Hz (starting frequency variable between 0 and 60Hz)
Frequency settingresolution
5VDC input: 1/500 of max. set frequency, 10V, 4 to 20mADCinput: 1/1000 of max. set frequency. Digital input: 0.1Hz (lessthan 100Hz), 1Hz (100Hz or higher)
Frequency accuracy
Analog input: Within ±1% of max. output frequency (25°C ± 10°C(77°F ± 18°F))Digital input: Within ±0.5% of set output frequency (When settingdial is used)
Starting torque 150% (at 6Hz) under automatic torque boost control
Acceleration/deceleration time setting
0, 0.1 to 999s (may be set individually for acceleration anddeceleration), linear or S-pattern acceleration/decelerationmode selectable.
Regenerative(*2)
0.1K, 0.2K....150%, 0.4K, 0.75K.....100%, 1.5K .....50%,2.2K, 3.7K....20%Braking
torqueDC braking
Operation frequency (0 to 120Hz), operation time (0 to 10s),operation voltage (0 to 15%)
Input signal
Frequency setting signal (0 to 5(10)VDC), 4 to 20mA, digitalsetting with dial, start signal, alarm reset, multi-speedselection, second function selection, output stop, current inputselection, external thermal relay input, start self-holdingselection, jog signal, PID control valid, PU operation-externaloperation switching.
Operational function
Maximum and minimum frequency settings, frequency jumpoperation, external thermal relay input selection, automaticrestart after instantaneous power failure, forward/reverserotation prevention, slip compensation, operation modeselection, PID control, computer link operation (RS-485) (*3)
Running status
1 open collector signal can be selected from among inverterrunning, up-to-frequency, frequency detection, overloadwarning, zero current detection, output current detection, PIDupper limit, PID lower limit, PID forward/reverse rotation,operation ready, minor failure and alarm. 1 contact output (1contact, 230V 0.3AAC, 30V 0.3ADC) signal can be selected.
Japanese1 signal can be selected from output frequency and motorcurrent.Pulse train output (1440 pulses/s, 1mA full scale)O
utpu
t si
gnal
Formeter
NA, EC1 signal can be selected from output frequency and motorcurrent.Analog output (0 to 5VDC, 1mA full scale)
Con
trol
spe
cific
atio
ns
Protective/warningfunction
Overcurrent shut-off (during acceleration, deceleration,constant speed), regenerative overvoltage shut-off (duringacceleration, deceleration, constant speed), overload shut-off(electronic overcurrent protection), fin overheat, fan failure(*4), stall prevention, start-time output side ground faultprotection (*5), external thermal relay (*6), PU disconnection(*3), retry count excess, communication error (*3), CPU error,undervoltage (*1)
43
Ambient temperature-10°C to +50°C (14°F to 122°F) (non-freezing)(-10°C to +40°C (14°F to 104°F) for totally-enclosed structurefeature)
Ambient humidity 90%RH max. (non-condensing)Storage temperature -20°C to +65°C (-4°F to +149°F)
AtmosphereIndoors (without corrosive gas, flammable gas, oil mist, dustand dirt etc.)E
nvir
onm
ent
Altitude/vibrationMax. 1000m (3280.80feet) above seal level, 5.9m/s2 or less(conforms to JIS C 0911)
*1. When undervoltage occurs, no alarm output is provided but the output isshut off. After power restoration, the inverter may be run as it is. Dependingon the running status (e.g. load magnitude), however, overcurrent,regenerative overvoltage or other protection may be activated at powerrestoration. (In external operation mode.)
*2. The magnitude of braking torque indicates the short-duration averagetorque (which changes with the motor loss) developed when the motoralone is decelerated from 60Hz in the shortest period, and is not continuousregenerative torque. Deceleration made from a high speed above the basefrequency will reduce the value of average deceleration torque.
*3. This function is valid for only the type with RS-485 communication function.*4. Compatible with only the product having the built-in cooling fan.*5. Activated only when "1" is set in Pr. 40 "start-time ground fault detection
selection".*6. Activated only when external thermal relay input (OH) is selected in any of
Pr. 60 to Pr. 63 (input terminal function selection).
44
9. OUTLINE DRAWINGS0.1K, 0.2K, 0.4K, 0.75K
φ5 hole
68 (2.68)6 (0.24) 56 (2.20) 6 (0.24)
5 (0.20)
128
(5.0
4)5
(0.
20)
118
(4.6
5)
- +
5 (0
.20)
18.5(0.73) D1
4 (0.16)D2
D
Rating plate
Capacity
0.1K, 0.2K
0.4K
0.75K 132.5 (5.22)
112.5 (4.43)
80.5 (3.17)
D
·3-phase 200V power supply
62 (2.44)
42 (1.65)
10 (0.39)
D1
52 (2.05)
52 (2.05)
52 (2.05)
D2
Capacity
0.1K, 0.2K
0.4K
0.75K 162.5 (6.40)
142.5 (5.61)
80.5 (3.17)
D
·Single-phase 200V power supply
62 (2.44)
42 (1.65)
10 (0.39)
D1
82 (3.23)
82 (3.23)
52 (2.05)
D2
(Unit: mm (inches))
45
Capacity
1.5K, 2.2K
3.7K 170 (6.69)
108 (4.25)
W
·3-phase 200V power supply
158 (6.22)
96 (3.78)
W1
142.5 (5.61)
135.5 (5.33)
D
72 (2.83)
65 (2.56)
D1
52 (2.05)
52 (2.05)
D2
5 (0.20)
8 (0.31)
D3
18.5(0.73)
DD2 D1
D3
118
(4.6
5)
5 (0.20)
WW1
128
(5.0
4)5
(0.2
0)
- +
6 (0.24) 6 (0.24)
Cooling fan×1
Rating plate
φ5 hole
1.5K, 2.2K, 3.7K
Capacity
1.5K 108 (4.25)
W
·Single-phase 200V power supply
96 (3.78)
W1
155.5 (6.12)
D
65 (2.56)
D1
72 (2.83)
D2
8 (0.31)
D3
(Unit: mm (inches))
5 (
0.20
)
46
Appendix 1 Instructions for Compliance with the
European Standards(The products conforming to the Low Voltage Directive carry the CE mark.)
(1) EMC Directive1) Our view of transistorized inverters for the EMC DirectiveA transistorized inverter is a component designed for installation in a control boxand for use with the other equipment to control the equipment/device. Therefore,we understand that the EMC Directive does not apply directly to transistorizedinverters. For this reason, we do not place the CE mark on the transistorizedinverters. (The CE mark is placed on inverters in accordance with the Low VoltageDirective.) The European power drive manufacturers' organization (CEMEP) alsoholds this point of view.2) ComplianceWe understand that the transistorized inverters are not covered directly by theEMC Directive. However, the EMC Directive applies to machines/equipment intowhich transistorized inverters have been incorporated, and these machines andequipment must carry the CE marks. Hence, we prepared the EuropeanStandard-compliant noise filters and the technical information "EMC InstallationGuidelines" (information number BCN-A21041-202) so that machines andequipment incorporating transistorized inverters may conform to the EMCDirective more easily.3) Outline of installation methodInstall an inverter using the following methods:* Use the inverter with an European Standard-compliant noise filter.* For wiring between the inverter and motor, use shielded cables or run them in a
metal piping and ground the cables on the inverter and motor sides with theshortest possible distance.
* Insert a line noise filter and ferrite core into the power and control lines asrequired.Full information including the European Standard-compliant noise filterspecifications are written in the technical information "EMC InstallationGuidelines" (BCN-A21041-202). Please contact your sales representative.
47
(2) Low Voltage Directive1) Our view of transistorized inverters for the Low Voltage Directive
Transistorized inverters are covered by the Low Voltage Directive.2) Compliance
We have self-confirmed our inverters as products compliant to the Low VoltageDirective and place the CE mark on the inverters.
3) Outline of instructions* Connect the equipment to the earth securely. Do not use an earth leakage circuit
breaker as an electric shock protector without connecting the equipment to theearth.
* Wire the earth terminal independently. (Do not connect two or more cables toone terminal.)
* Use the cable sizes on pages 7, 9 and 11 under the following conditions.• Ambient Temperature: 40°C (104°F) maximum• Wire installation: On wall without ducts or conduits
If conditions are different from above, select appropriate wire according toEN60204 ANNEX C TABLE 5.* Use the no-fuse breaker and magnetic contactor which conform to the EN or IEC
Standard.Design notice: Where residual-current-operated protective device (RCD) is used
for protection in case of direct or indirect contact, only RCD ofType B is allowed on the supply side of this Electronic Equipment(EE). Otherwise another protective measure shall be appliedsuch as separetion of the EE from the environment by double orreinforced insulation or isolation of EE and supply system by atransformer. (Extract from EN51078)
* Use the inverter under the conditions of overvoltage category II andcontamination level 2 or higher specified in IEC664.
* Use the breaker of type B (breaker which can detect both AC and DC). If not,provide double or enhanced insulation between the inverter and otherequipment, or put a transformer between the main power supply and inverter.
* On the input and output of the inverter, use cables of the type and size set forthin EN60204 Appendix C.
* The operating capacity of the relay outputs (terminal symbols A, B, C) should be30VDC, 0.3A.
* The terminals indicated as the control circuit input and output terminals on page5 are separated safely from the main circuit.
* EnvironmentDuring
operationIn storage
Duringtransportation
Ambient Temperature-10°C to +50°C(14°F to 122°F)
-20°C to +65°C(-4°F to +149°F)
-20°C to +65°C(-4°F to +149°F)
Ambient Humidity 90% RH or less 90% RH or less 90% RH or less
Muximum Altitude1,000m
(3280.80feet)1,000m
(3280.80feet)10,000m
(32808.40feet)
Details are given in the technical information "Low Voltage Directive ConformanceGuide" (BCN-A21041-203). Please contact your sales representative.
48
Appendix 2 Instructions for compliance with U.S. and
Canadian Electrical Codes
1. General PrecautionThe bus capacitor discharge time is 10 minutes. Before starting wiring orinspection, switch power off, wait for more than 10 minutes, and check forresidual voltage between terminal P (+) and N (-) with a meter etc., to avoidhazard of electrical shock.
2. EnvironmentBefore installation, check that the environment meets following specifications.
Ambient temperature -10°C to +50°C (14°F to 122°F) (non-freezing)Ambient humidity 90%RH or less (non-condensing)Storage temperature(Note 2)
-20°C to +65°C (-4°F to 149°F)
Ambience Indoors (No Corrosive and flammable gases, oil mist, dust and dirt.)Altitude vibration Below 1000m (3280.80feet), 5.9m/s2 or less
3. InstallationThe below types of inverter have been approved as products for use inenclosure and approval tests were conducted under the following conditions.Design the enclosure so that the ambient temperature, humidity and ambienceof the inverter will satisfy the above specifications.Branch circuit protectionFor installation in United States, branch circuit protection must be provided, inaccordance with the National Electrical Code and any applicable local codes.For installation in Canada, branch circuit protection must be provided inaccordance with the Canada Electrical Code and any applicable provincialcodes.
4. Short circuit ratingsSuitable For Use in A Circuit Capable of Delivering Not More Than 5kA rmsSymmetrical Amperes.
49
5. Motor overload protectionThese inverters provide solid state motor overload protection.Set parameter 9 using the following instructions,(Pr. 9 "electronic thermal O/L relay").
<Setting>• Set the rated current [A] of the motor.
(Normally set the rated current at 50Hz.)• Setting "0" makes the electronic overcurrent protection (motor protective
function) invalid. (The inverter's protective function is valid).• When using a Mitsubishi constant-torque motor, first set "1" in Pr. 71 to choose
the 100% continuous torque characteristic in the low-speed range. Then, setthe rated motor current in Pr. 9.
CAUTION
• When two or more motors are connected to the inverter, they cannot beprotected by the electronic overcurrent protection. Install an external thermalrelay to each motor.
• When the difference between the inverter and motor capacities is large andthe setting is small, the protective characteristics of the electronic overcurrentprotection will be deteriorated.In this cause, use an external thermal relay.
• A special motor cannot be protected by the electronic overcurrent protection.Use an external thermal relay.
REVISIONS*The manual number is given on the bottom left of the back cover.
Print Date *Manual Number Revision
Mar., 2000 IB(NA)-0600026-A First edition