OLCT 80 d or id(with intrinsic safety
sensor block)
II2GD For combustible and toxic gases and
oxygen Fitted with pre-calibrated sensor blocks Up to 9 cable-glands
(powers/inputs/outputs) Measurement and alarms visualisation
OLCT80 :dimensions and weights
IR bloc version :367 x (h) 189 x (p) 120 mm
Weights: # 2.95Kgs LEL, Tox and
O2 versions
# 4.78Kgs IR bloc version.
OLCT 80 (indications)Alarms 1 and 2
flashing/fixed
alphanumeric readout, (units, type of gas, internal parametres , etc..)
Measurement
Remote control IR detector
ON/OFFTrouble alarm
• Fitted with a memory: 3 files (FIFO 2O max.) :
• last events ( hour and date).
• Last measurements ( hour and date).
• Histograms of calibrations and drifts.
LOCAL INDICATIONS…
OLCT 80
OLCT 80: analog/digital output signals
4/20 mA with smart signal processing: Analog signal 0…4-20…25 mA or 1/0 RS485 (1200bauds,38kb Modbus ASCII
for MX62) The RS485 link gives access to: The measurement, status and default Internal relays
The relays are 2A /250VAC ( with potentiel free SPDT contacts)
Relays are actuated either :
- directly by the sensor electronics of the sensor ( programmable) or supplementary inputs
- from the MX62 central unit,
- or the control unit system to which connected the sensor is connected .
OLCT 80:relay option
The relays can be :
- in FAIL SAFE or Negative safety
- Triggered on increasing or decreasing alarms
- manually * or automatically acknowledged
* by remote control, by pressing an external pushbutton connected to the dedicated binary input * by acknowledging on the MX62 or the control system to which the sensor is connected .
OLCT 80:relay option
OLCT20OLCT IR
0-3V4-20mA
0-3V4-20mA
Block of cell
Analog inputN° 1
Analog inputN° 2
AL1
AL2
CENTRAL UNIT MX62
Faultgestion
MX62 protocole
FAULT RELAY
RELAY 2
RELAY 1
Positive safety or not
internal or external ( MX62) actions
programmablealarm levels
Programmableactionsmanual or automatic acknowledgement
Parametres
CONTACTS OF FAULT RELAY
CONTACTS OF RELAY 2
CONTACTS OF RELAY 1
OLCT 80
Precalibrated sensor block
« OLCT20 »
« is» range accepted
Remore sensor version (local
display)
OR
MANY POSSIBILITIES
Cell block type « OLCT… »
RS485 (M20) input
Power supply (M25) input
RS485 (M20) output
Power supply (M25) output
relays(M20), contacts
TOR output (M20)
Option
OLCT 80 For classified
explosion risk zones
It can be used such as a local stand alone fixed unit.
INCLUDED
OLCT 80 :extremelylow energy requirements
Power supply : from 11 to 28Vcc Tox, O2.
: from 16 to 28 Vcc (LEL + OLCT IR)
consumptions* : # < 10 mA Tox et O2 versions
: # < 30 mA LEL version
: # < 190 mA IR version. (estimation)
This major advantage means that more sensors can be connected, with smaller wire cross-sections and over greater distances.
* about: without relays, without 4…20mA and 10% of back-light
ex: the loop allows a gestion of
16 adresses ( lenght of 1.2 to 4.8 Kms *
Section 1
Section 2
< 1.2 Kms
* Example with more than 3 TOX. sensors. Power supply wiring :2x0,75mm² + network wiring: 1paire of 0.32 mm².
OLCT 80
local power supply.
µC A
µC B
INTERFACE RS485
INTERFACE RS485
INTERFACE RS485
INTERFACE RS485
MX62
adapter module for digital adressable sensors in a loop
Bus loop
RS485
RS485
ALIM
4 adapter modules per MX62 16 adresses per loop
16 adresses/module
Non-intrusive dialogue via intrinsically safe IR remote control
Without opening, an IR remote control allows a remote dialogue with the sensor, during operations of maintenance or configuration. Marking : IR20 CE 0080
II 2 G
EEx ia IIC T4
INERIS 04ATEX0011X
IR remote control « IR20 » Receptor
accessible informations via the remote control Measurements from the sensor block, the
two 4-20 mA auxiliary inputs. Last MIN et MAX measurements since the
last calibration
calibrations « ZERO » and « SPAN » of 3 inputs (sensor, 4-20 mA, binary …)
Alarm relays programming
alarm levels programming …..OLCT 80