trouble shooting of new 415v sw.gr. l&t make

49
TROUBLE SHOOTING OF L&T MAKE 415V AIR CKT. BREAKER. UNIT-1 This document is prepared for general idea of Trouble shooting of 415V L&T Make breaker. I am sharing Switch gear experiences along with my knowledge with you. Please give me your valuable suggestions & best support for next version. 2014 MUKESH MISTRY KAPS-1&2, EMU, 1/4/2014

Upload: mukesh-mistry

Post on 20-Feb-2017

197 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Trouble Shooting of New 415V SW.GR. L&T make

TROUBLE SHOOTING

OF L&T MAKE 415V

AIR CKT. BREAKER. UNIT-1

This document is prepared for general idea of Trouble shooting of 415V L&T Make breaker. I am sharing Switch gear experiences along with my knowledge with you. Please give me your valuable suggestions & best support for next version.

2014

MUKESH MISTRY

KAPS-1&2, EMU, 1/4/2014

Page 2: Trouble Shooting of New 415V SW.GR. L&T make

2

415V SW.GR. L&T415V SW.GR. L&T415V SW.GR. L&T415V SW.GR. L&T CIRCUIT CIRCUIT CIRCUIT CIRCUIT BREAKER BREAKER BREAKER BREAKER

� “STAR” Principle must be remembered.

� Isolation must be checked.

� Personal & Electrical safety must be remembered.

� Job must be start with Two Authorized people.

� Latest drawing must be used.

� Don’t hurry for work start.

� Insulated Tools must be used.

� Give feed back to your superior.

All events write properly and History fill up.

Work area clean.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 3: Trouble Shooting of New 415V SW.GR. L&T make

3

INDEXINDEXINDEXINDEX

SR.NO. DESCRIPTION PAGE NO.

1. 415V L&T Make Air Circuit Breaker Details 04

2. Name of ACB Parts 05

3. Name of ACB Cubicle Parts 06

4. Name of ACB & Cubicle Parts 07

5. Operation of Breaker 8 & 9

6. Indicator Provided on Front facia 10 TO 13

7. Electrical Operated Circuit Breaker 14

8. Manual & Electrical Charging 15

9. Closing the Circuit Breaker 16

10. Breaker Position - SERVICE , TEST & ISOLATED 17 & 18

11. Procedure of breaker Racking IN/OUT 19 & 33

12. Electrical Anti - Pumping 20

13. ACB - Accessories 21 & 22

14. Micro switches for Indicating position of the breaker on the cradle 23

15. Racking Interlock 24

16. Operation of Micro Switches (Limit Switch) 25

17. Door Interlock 26 & 27

18. Safety Shutter 28

19. Components to be Greased 29 & 30

20. Adjustment of Arcing Contact 31

21. Procedure to be followed for Removing the Front Facia of a Breaker 32

22. “KEY” Interlock in ISOLATED, SERVICE & TEST Position 34

23. Trouble Shooting of Motor Feeder Breaker 35 TO 39

24. Trouble Shooting of Incomer Breaker 40 TO 44

25. Trouble Shooting of Tie Breaker 45 TO 49

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 4: Trouble Shooting of New 415V SW.GR. L&T make

4

415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T CIRCUIT CIRCUIT CIRCUIT CIRCUIT BREAKERBREAKERBREAKERBREAKER (MOTOR FE(MOTOR FE(MOTOR FE(MOTOR FEEDER)EDER)EDER)EDER)

New 415V L&T Make Air Circuit Breaker Details:

TYPE: CN – CS 1250C

• Rating : 1250 A

• Type Designation : C

• Rated Current (A): 1250A

• Rated Voltage(V): 660V

• No. of Poles: 3

• Breaking Capacity: 50KA, Short Circuit Breaking Capacity: 50KA

• Making Capacity: 105KA

• Opening Time (ms): 40

• Closing Time (ms): 60

TYPE: CN – CS 4000H

• Rating : 4000 A

• Type Designation : H

• Rated Current (A): 4000A

• Rated Voltage(V): 660V

• No. of Poles: 3

• Breaking Capacity: 100KA, Short Circuit Breaking Capacity: 100KA

• Making Capacity: 220KA

• Opening Time (ms): 40

• Closing Time (ms): 60

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 5: Trouble Shooting of New 415V SW.GR. L&T make

5

“C” POWER - RANGE OF L&T MAKE ACB

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 6: Trouble Shooting of New 415V SW.GR. L&T make

6

“C” POWER - RANGE OF L&T MAKE ACB

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 7: Trouble Shooting of New 415V SW.GR. L&T make

7

“C” POWER - RANGE OF L&T MAKE ACB

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 8: Trouble Shooting of New 415V SW.GR. L&T make

8

“C” POWER - RANGE OF L&T MAKE ACB OPERATION OF BREAKER:

Figure – 5.1

MANUALLY OPERATED BREAKERS ACB closes in single stroke operation of the handle. Operating sequence of manual breakers:- Initially breaker is OFF. 1. For carrying out any operation, the breaker-operating handle has to be pulled out fully by holding its top portion. 2. For extra leverage, the handle can be telescoped lengthwise (recommended). RESETTING: 3. Rotate the operating handle by 90 in anti-clockwise direction (till it becomes horizontal). The breaker will trip at the beginning of the resetting operation, if it is in closed condition.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 9: Trouble Shooting of New 415V SW.GR. L&T make

9

“C” POWER - RANGE OF L&T MAKE ACB

Figure – 5.2

CLOSING: 4. Rotate the operating handle by 90 in clockwise direction (till it becomes vertical to close the ACB). 5. After completing the operation ensure that the handle is placed back in the cavity on the front facia.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 10: Trouble Shooting of New 415V SW.GR. L&T make

10

“C” POWER - RANGE OF L&T MAKE ACB An indicator provided on front facia (refer Fig. 5-1) shows the - RED / ON: ‘CLOSED’ - GREEN / OFF: ‘OPEN’ position of the main contacts. Operating Handle (refer Fig. 5-2) can occupy either of the two distinct position spaced 90 apart. - Horizontal Position: ‘OPEN- RESET’ - Vertical Position: ‘CLOSED’ or ’TRIPPED’

Figure-5.3

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 11: Trouble Shooting of New 415V SW.GR. L&T make

11

“C” POWER - RANGE OF L&T MAKE ACB The sequence of operation is RESET? CLOSE? OPEN Caution: Resetting the ACB in ‘ON’ condition will cause the ACB to trip. Precaution: Ensure presence of supply voltage to undervoltage release (if fitted) before closing the ACB. In case of manual reset type ACB actuation of TRIP push button / key of lockable trip push button, resets the tripping mechanism of ACB.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 12: Trouble Shooting of New 415V SW.GR. L&T make

12

“C” POWER - RANGE OF L&T MAKE ACB OPENING THE CIRCUIT BREAKER: The breaker can be opened by the following means: LOCALLY (Manually): 1. Press the TRIP push button. OR 2. Press key of lockable trip push button (when provided).

3. Rotate key of racking interlock for draw out breakers (if provided) when the breaker is in any position between ‘Service’ and ‘Test’.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 13: Trouble Shooting of New 415V SW.GR. L&T make

13

“C” POWER - RANGE OF L&T MAKE ACB

4. Operate handle anti-clockwise. REMOTELY (Electrically):

1. Through shunt release. 2. Through under voltage release.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 14: Trouble Shooting of New 415V SW.GR. L&T make

14

“C” POWER - RANGE OF L&T MAKE ACB ELECTRICALLY OPERATED CIRCUIT BREAKER:

OPERATION FOR C/S1/H/D - RANGE BREAKER

Initially breaker is OFF and spring is discharged. Spring condition is indicated by a mechanical indicator visible through a transparent window on the front facia.

Indicator display spring condition YELLOW CHARGED

BLACK DISCHARGED The spring in the circuit breaker operating mechanism must be charged to store the energy required to close the main contacts. The spring may be charged manually using the charging handle or automatically by the motor.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 15: Trouble Shooting of New 415V SW.GR. L&T make

15

“C” POWER - RANGE OF L&T MAKE ACB Electrical Charging: The spring is automatically charged & automatically recharged after each closing operation. (Provided there is a continuous supply to the motor) Manual Charging: In case of power failure, charge the main spring through multiple strokes of charging handle. The handle has to pull outward by gripping its top portion.

Charge by giving small strokes (25) as shown in Figure in the clockwise direction till indicator display Shows a spring charged condition (yellow colour). Now the breaker is OFF and spring is charged.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 16: Trouble Shooting of New 415V SW.GR. L&T make

16

“C” POWER - RANGE OF L&T MAKE ACB CLOSING THE CIRCUIT BREAKER: (Ensure precautions before closing same as manual ACBs.) Breaker is OFF and spring is charged. LOCALLY (Manually): Press ON push button. REMOTELY (Electrically): The closing electromagnet, when actuated, discharges the spring and closes the breaker.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 17: Trouble Shooting of New 415V SW.GR. L&T make

17

“C” POWER - RANGE OF L&T MAKE ACB RACKING:

Circuit breaker positions The indicator on the front shows the position of the circuit breaker in the cradle. Service position: In service position both power and control circuits are connected.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 18: Trouble Shooting of New 415V SW.GR. L&T make

18

“C” POWER - RANGE OF L&T MAKE ACB Test position: In test position power circuit is open ensuring full safety, while control circuit is connected for checking accessories as well as breaker operation.

Isolated position: In isolated position both power and control circuits are disconnected from supply to ensure complete isolation.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 19: Trouble Shooting of New 415V SW.GR. L&T make

19

“C” POWER - RANGE OF L&T MAKE ACB PROCEDURE of Breaker Racking OUT / IN:

1. Racking operation must be done with the aid of racking handle, provided in racking handle storage location. 2. Insert the racking handle in the racking slot. 3. Rotate the racking handle in clockwise direction to rack in and in anti clockwise direction to rack out. 4. Remove the racking handle from the racking slot. 5. After completion of racking operation ensure that the racking handle is kept in its correct storage location. Note: I. If the panel door is open, keep the door interlock pin pressed during racking. II. If racking interlock is provided press the key inwards and turn it clockwise before racking.

Caution: Open the circuit breaker before racking IN / OUT.

Note: If the breaker is inserted or withdrawn with it’s main contacts in closed position, then a device automatically trips the breaker before separation of the main isolating contacts(during withdrawal) or before they come into contact (during insertion). The same device prevents the closing of the breaker at one particular location between the position ’Test’ and ‘Service’. When racking interlock provided, the key of the lock has to be pressed and turned anti-clockwise (this will trips the breaker if it is in closed condition at any location between the positions ‘Test’ and ‘Service’) before initiation of the racking operation, otherwise it will not be possible to rack the breaker in or out. If the cradle is provided with door interlock, ensure that either the door is closed or interlock is defeated while attempting racking.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 20: Trouble Shooting of New 415V SW.GR. L&T make

20

“C” POWER - RANGE OF L&T MAKE ACB ELECTRICAL ANTI-PUMPING: When a closing command is given, closing coil of the circuit breaker gets supply through a normally closed (NC) contact of the anti-pumping contactor. The closing coil is energized and the breaker closes. The auxiliary contact Q1 of the breaker closes. This energizes the coil K1 of the anti-pumping contactor and the contactor picks up. This opens its normally closed (NC) contact in series with the closing coil breaking the persistent closing command. In order to close the circuit breaker again, the closing coil circuit will have to be reset, which will happen only after the anti-pumping contactor drops off. The contactor will drop off only when the closing command is removed. This ensures that once the breaker has closed and tripped on fault the breaker can close again only after the first closing command is removed and a fresh closing command is given, thus providing anti-pumping. The anti pumping contactor should be selected in accordance with the rating of the closing coil.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 21: Trouble Shooting of New 415V SW.GR. L&T make

21

“C” POWER - RANGE OF L&T MAKE ACB

ACCESSORIES:

AUXILIARY CONTACT: Auxiliary contacts are offered in following combinations: 2 NO + 2 NC 6 NO + 6 NC

Note: Number of aux. contacts available to customers may be less than actual, as some aux. contacts may be used for internal wiring purpose. SECONDARY ISOLATING CONTACTS (SIC):

• Self aligned, spring loaded, fully draw out type • Required for control circuit connections • Maximum four blocks, each of six contacts • The contacts are rated at 16A, 500V AC

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 22: Trouble Shooting of New 415V SW.GR. L&T make

22

“C” POWER - RANGE OF L&T MAKE ACB SPRING CHARGING MOTOR: Electrical charging of the main spring can be achieved by using motor.

1. Offered both in AC and DC rating. 2. Spring charging time: 7 sec (approx.) 3. For 415V application, use a 415V/240V transformer rated for 500 VA

4. For DC control applications, the circuit must be wired for double isolation if AC control to DC control conversion is done. Note: Providing continuous supply to the motor would ensure that the main spring gets charged after ‘Close’ operation and is ready for the next operation.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 23: Trouble Shooting of New 415V SW.GR. L&T make

23

“C” POWER - RANGE OF L&T MAKE ACB MICROSWITCHES FOR INDICATING POSITION OF THE BREAKER ON THE CRADLE:

• Electrical indication available through micro switches • Two micro switches with one changeover contact for

1. Test or Isolated position (C8 & C9) 2. Service (C6 & C7)

• In case of an electrical ACB, a service position micro switch is fitted on the left side as a standard. This can be used to prevent remote closing of ACB in ‘Test’ & ‘Isolated’ positions

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 24: Trouble Shooting of New 415V SW.GR. L&T make

24

“C” POWER - RANGE OF L&T MAKE ACB RACKING INTERLOCK:

• Before initiation of racking operation, the key of the lock is to be pressed and turned anticlockwise. Otherwise the racking operation gets mechanically prevented • In case the breaker is in closed condition, pressing of the key trips the breaker between the Service and Test positions. • The key remains trapped in the lock when not pressed and this makes it suitable for interlocking.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 25: Trouble Shooting of New 415V SW.GR. L&T make

25

“C” POWER - RANGE OF L&T MAKE ACB OPERATION OF MICROSWITCHES:

1. Cam on telescopic rail. 2. Micro switch (C8/9) in test or isolated position. 3. Micro switch (C6/7) in service position. ‘Service’ position: The micro switch operates 3 mm before the ‘service’ position ‘Test’ position: The micro switch operates 3 mm before the ‘test’ position during withdrawal ‘Isolated’ position: The micro switch operates 2 mm before the ‘Isolated’ position

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 26: Trouble Shooting of New 415V SW.GR. L&T make

26

“C” POWER - RANGE OF L&T MAKE ACB DOOR INTERLOCK: Door Open and Breaker in ‘Isolated’ position. When the door is open, the spring-loaded pin interferes with the screw (refer Fig. 4) and hence the racking screw cannot be turned. However, when the door is closed, the pin is pressed and the screw is free to rotate. The breaker can be racked now.

• This arrangement ensures that the breaker cannot be racked to the ‘Test’ and ‘Service’ position unless the door is closed.

When the breaker is in ‘Isolated’ position, make sure that the position of the top end of the lever results in its movement in anti-clockwise direction. Check that on removal of the pressure, the lever comes back to its original position due to spring action.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 27: Trouble Shooting of New 415V SW.GR. L&T make

27

“C” POWER - RANGE OF L&T MAKE ACB Door closed and breaker in ‘Service’ / ‘Test’ position: When the breaker is racked in, the pin on the left side plate of the breaker presses the lever as shown in Fig. 5. The rear portion of the lever rises & comes in front of the latch piece fixed to the cubical door as shown in Fig. 6. The interference between the latch piece and the lever prevents the door from opening. However, when the breaker is withdrawn to the ‘Isolated’ position, the door can be opened since the lever is not pressed by the pin of the breaker side plate and hence there is no interference between the latch piece and the rear portion of the lever. The door interlock can be defeated by rotating the screw on the cubicle door in anti-clockwise direction using a screw driver. RACKING INTERLOCK: Before initiation of racking operation, the key of the lock is to be pressed and turned anticlockwise. Otherwise the racking operation gets mechanically prevented - In case the breaker is in closed condition, pressing of the key trips the breaker between the positions ‘Test’ and ‘Service’

- The key remains trapped in the lock when not pressed and this makes it suitable for interlocking. LOCKABLE TRIP PUSH BUTTON: This system replaces the normal trip push button by a lockable one and used for the purpose of locking & interlocking. The push button is suitable for Manual and Electrical, Draw-out and Fixed Breakers of all ratings, which makes interlocking between any versions and rating possible. The system defeats all positive closing signals (manual / electrical) and prevents nuisance closing of the locked breakers. The key remains trapped on the push button once unlocked which makes it suitable for interlocking and gives easy access (if one desires) to lock the breaker.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 28: Trouble Shooting of New 415V SW.GR. L&T make

28

“C” POWER - RANGE OF L&T MAKE ACB AUTOMATIC SAFETY SHUTTER FOR DRAWOUT BREAKERS: The shutter automatically covers the cradle terminals (which may be live) once the breaker is drawn out of ‘Service Position’. This is to avoid accidental contact of the operating personnel with live parts during maintenance.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 29: Trouble Shooting of New 415V SW.GR. L&T make

29

“C” POWER - RANGE OF L&T MAKE ACB

Page 30: Trouble Shooting of New 415V SW.GR. L&T make

30

“C” POWER - RANGE OF L&T MAKE ACB Components to be greased: All rubbing surfaces in the mechanism, poles etc. are to be greased except the contacts (copper on copper) and sintered bearings. Grease sliding surface of fixed and moving secondary isolating contacts with petroleum jelly. Prior to greasing, these surfaces should be thoroughly cleaned. Excess grease must be wiped out. Note: Please do not use any cleaning agent while cleaning with cloth. Components greased for life The following components are provided with self lubricating sintered rings impregnated with grease for life. - Trip rod - Intermediate shaft of manual control - Free return charging device for electrical operation Components not to be greased - All releases - Main contacts in pole and cradle terminals - Earthing terminal - Secondary isolating contacts Caution: Before any maintenance operation, following procedure must be followed. - Mechanism spring must be discharged. - Draw out breaker must be in isolated/maintenance position. - Circuit breaker which operates rarely must be periodically operated.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 31: Trouble Shooting of New 415V SW.GR. L&T make

31

“C” POWER - RANGE OF L&T MAKE ACB Adjustment of arcing contacts:

Breaker is in ‘Closed’ condition. Move the fixed arcing contacts to obtain the dimension 0.9 ± 0.1 mm between the fixed and moving arcing contacts. Tightening couple of the screw (12): 0.8 kg-m Note: Check the positioning of the arcing contacts again at the end of the inspection schedule. Gap between the arcing contacts (fixed and moving) 0.9 ± 0.1 mm. Maximum difference in this dimension for the arcing contacts of the same pole should not be more than 0.1 mm. Limit of wear = 1.5 mm Tightening couple of the screws (9) and (10): 0.25 kg-m (moving arcing contact)

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 32: Trouble Shooting of New 415V SW.GR. L&T make

32

“C” POWER - RANGE OF L&T MAKE ACB PROCEDURE TO BE FOLLOWED FOR REMOVING THE FRONT FACIA OF A BREAKER:

For removing the front facia, follow the steps mentioned below: 1. Remove the plug of the operating handle using a screw driver. (See Fig. 10-26a) 2. Get screw (1) fully unscrewed. (See Fig. 10-26b) 3. Remove the operating handle. 4. Get the screws at the four corners of the front facia unscrewed. (Fig. 10-26c) 5. Remove the front facia from the breaker.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 33: Trouble Shooting of New 415V SW.GR. L&T make

33

“C” POWER - RANGE OF L&T MAKE ACB PROCEDURE FOR RACK-IN/RACK-OUT:

• Before fitting the breaker on its cradle, ensure that the breaker is in ‘OFF’ position. • Ensure that the closing spring in case of electrically operated breakers is discharged. If it is in charged condition, press the

‘CLOSE’ push button to discharge it and then press the “TRIP” push button to bring the breaker in ‘OFF’ position. • Rack the telescopic rails out to ‘isolated’ position if necessary & further pull them out to ‘Maintenance’ position. • The breaker and cradle are fitted with ‘rating error prevention’ feature. This prevents the mismatch of breaker & cradle, as a

breaker having rating other than that of the cradle cannot be fitted on the telescopic rails of the cradle.

• Place the breaker onto the rails and engage with M8 nuts, spring washers and the on the telescopic rail studs. • Ensure that the breaker is not sitting on the collars of the studs. • Push the breaker in fully and then tighten the nuts on the two accessible studs. • Pull out the breaker so as to tighten the inner two nuts.

RACK-IN OPERATION:

• Push the breaker in, until lug engages with spring loaded catches. This corresponds to ‘Isolated’ position. • Take the racking handle out from its storage location and insert it into the racking screw location. • Before racking ensure that

1. Key of the racking interlock (if provided) is pressed and turned anti-clockwise. 2. Key of position lock (if provided) is turned clockwise. 3. Pin of door interlock is pressed.

• Rotate the racking handle in clockwise direction until position indicator shows ‘SERVICE’ position. Note: Alignment of breaker facia with cradle facia indicates breaker is in ‘SERVICE’ position. RACK- OUT OPERATION:

• Take the racking handle out from its storage location and insert it into the racking screw location. • Before racking out ensure that

1. Key of the racking interlock (if provided) is pressed and turned anti-clockwise. 2. Key of position lock (if provided) is turned clockwise. 3. Pin of door interlock is pressed.

• Rotate the racking handle anti-clockwise until position indicator shows ‘ISOLATED’ position.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 34: Trouble Shooting of New 415V SW.GR. L&T make

34

“C” POWER - RANGE OF L&T MAKE ACB Breaker in ‘ISOLATED’ position • Breaker can be locked & key can be removed. • Breaker cannot be racked in

Breaker in ‘SERVICE’ or ‘TEST’ position • Breaker cannot be locked • Key cannot be removed

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 35: Trouble Shooting of New 415V SW.GR. L&T make

35

415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T MAKE MAKE MAKE MAKE CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER (MOTOR FEEDER)(MOTOR FEEDER)(MOTOR FEEDER)(MOTOR FEEDER)

SR.

NO.

SYSTEM PROBLEM COMMON CAUSES SOLUTIONS

1. Circuit breaker not closes in “TEST”

position.

1. Fuse: F-18 or F-19 Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Local-Remote switch-S2 is not in “Local”

Position.

2. Put Local-Remote switch is in Local position.

3. Control Switch 52CS (S3) contact not

proper make.

3. Control Switch-S3 contact make properly.

4. Test Position (K103) 75T contacts (13-14)

not proper make.

4. Contact 13-14 make properly of Relay K103.

5. Check “NC” contact (21-22) of Relay K101

for Spring charging.

5. Contact 21-22 make properly of Relay K101.

6. Sliding contact not proper make. 6. Sliding contact proper make.

7. Breaker Aux. switch “NC” contact (Q1-

52B) 17& 18 is open.

7. Breaker Aux. switch “NC” contact (Q1-52B) 17&

18 is making.

8. “NC” Contact (21&22) of Relay 94-KA is

open.

8. “NC” Contact (21&22) of Relay 94-KA is making.

9. Breaker Aux. switch “NC” contact (Q1-

52B) is open or Check Ext. Rest.

9. Breaker Aux. switch “NC” contact (Q1-52B) is

make or Ext. Rest. Replaced.

10. Closing coil is Open/bunt. 10. Closing coil Replaced

11. Breaker not in “TEST” position. 11. Breaker put in “TEST” position properly.

12. Any wire remove/Loose from TB. 12. Same is tight in TB.

13. Stuck Breaker Mech. 13. Breaker Mechanism problem solved.

2. Circuit breaker not Trip in “TEST”

position.

( Tripping Coil – 1)

1. Fuse: F-24 or F-25 Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Local-Remote switch-S2 is not in “Local”

Position.

2. Put Local-Remote switch is in Local position.

3. Control Switch 52CS (S3) contact (2P3 &

2P4) not proper make.

3. Control Switch-S3 contact make properly.

4. Test Position (K103) 75T contacts (43 & 44)

not proper make.

4. Contact 44 & 44 make properly of Relay K103.

5. Test Position (K103) 75T not operated. 5. Test Position (K103) 75T made available.

6. Sliding contact not proper make. 6. Sliding contact proper make.

7. Breaker Aux. switch contact not proper

makes.

7. Breaker Aux. switch contact proper makes.

8. Tripping coil -1 is Open/bunt. 8. Tripping coil -1 Replaced.

9. Any wire remove/Loose from TB. 9. Same is tight in TB.

10. Stuck Breaker Mech. 10. Breaker Mechanism problem solved.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 36: Trouble Shooting of New 415V SW.GR. L&T make

36

415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T MAKE MAKE MAKE MAKE CIRCUIT BREAKERCIRCUIT BREAKERCIRCUIT BREAKERCIRCUIT BREAKER (MOTOR FEEDER)(MOTOR FEEDER)(MOTOR FEEDER)(MOTOR FEEDER) SR.

NO.

SYSTEM PROBLEM COMMON CAUSES SOLUTIONS

3. Circuit breaker not closes in

“SERVICE” position.

1. Fuse: F-18 or F-19 Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Local-Remote switch-S2 is not in “Remote”

Position.

2. Put Local-Remote switch is in Remote position.

3. Service Position (K102) 75S not operated. 3. Test Position (K102) 75S made available.

4. Service Position (K102) 75S contacts (13-

14) not proper make.

4. Contact 13-14 make properly of Relay K102.

5. Check “3C” relay & its contact. 5. Contact make properly.

6. Check “NC” contact (21-22) of Relay

K101 for Spring charging.

6. Contact 21-22 make properly of Relay K101.

7. Sliding contact not proper make. 7. Sliding contact proper make.

8. Breaker Aux. switch “NC” contact (Q1-

52B) 17& 18 is open.

8. Breaker Aux. switch “NC” contact (Q1-52B) 17&

18 is making.

9. “NC” Contact (21&22) of Relay 94-KA is

open.

9. “NC” Contact (21&22) of Relay 94 -KA is making.

10. Breaker Aux. switch “NC” contact (Q1-

52B) is open or Check Ext. Rest.

10. Breaker Aux. switch “NC” contact (Q1-52B) is

make or Ext. Rest. Replaced.

11. Closing coil is Open/bunt. 11. Closing coil Replaced

12. Breaker not in “SERVICE” position. 12. Breaker put in “SERVICE” position properly.

13. Any wire remove/Loose from TB. 13. Same is tight in TB.

14. Stuck Breaker Mech. 14. Breaker Mechanism problem solved.

4. Circuit breaker not Trip in

“SERVICE” position.

( Tripping Coil – 1)

1. Fuse: F-24 or F-25 Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Local-Remote switch-S2 is not in “REMOTE”

Position.

2. Put Local-Remote switch is in Remote position.

3. Service Position (K102) 75S contacts (43 &

44) not proper make.

3. Contact 43 & 44 make properly of Relay K103.

4. Check “3T” relay & its contact. 4. Contact make properly.

5. Sliding contact not proper make. 5. Sliding contact proper make.

6. Breaker Aux. switch (Q1-52A) contact not

proper makes.

6. Breaker Aux. switch contact proper makes.

7. Tripping coil -1 is Open/bunt. 7. Tripping coil -1 Replaced.

8. Any wire remove/Loose from TB. 8. Same is tight in TB.

9. Stuck Breaker Mech. 9. Breaker Mechanism problem solved.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 37: Trouble Shooting of New 415V SW.GR. L&T make

37

415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T MAKE MAKE MAKE MAKE CIRCUIT BREAKERCIRCUIT BREAKERCIRCUIT BREAKERCIRCUIT BREAKER (MOTOR FEEDER)(MOTOR FEEDER)(MOTOR FEEDER)(MOTOR FEEDER)

SR.

NO.

SYSTEM PROBLEM COMMON CAUSES SOLUTIONS

5. Breaker spring charging is not done. 1. Fuse: F-16 or F-17 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Sliding contact not proper make. 2. Sliding contact proper make. 3. Spring charging limit switch contact (C&F,

D&H) not proper make. 3. Spring charging limit switch contact proper

make. 4. Spring charging motor bunt. 4. Spring charging motor replaced.

5. Any wire remove/Loose from TB. 5. Same is tight in TB.

6. Circuit breaker not Trip in

“SERVICE” position. ( Tripping Coil – 2)

1. Fuse: F-20 or F-21 Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Local-Remote switch-S2 is not in “REMOTE”

Position. 2. Put Local-Remote switch is in Remote position.

3. Service Position (K102) 75S contacts (153 &

154) not proper make.

3. Contact 153 & 154 make properly of Relay K103.

4. Check “3T” relay & its contact. 4. Contact make properly.

5. Sliding contact not proper make. 5. Sliding contact proper make. 6. Breaker Aux. switch (Q1-52A) “NO”

contact (23&24) not proper makes. 6. Breaker Aux. switch contact proper makes.

7. Tripping coil -2 is Open/bunt. 7. Tripping coil -2 Replaced.

8. Any wire remove/Loose from TB. 8. Same is tight in TB.

9. Stuck Breaker Mech. 9. Breaker Mechanism problem solved.

7. Contactor 94-KA (Anti Pumping)

is not operated breaker in “TEST”

position.

1. Fuse: F-18 or F-19 Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Local-Remote switch-S2 is not in “Local”

Position.

2. Put Local-Remote switch is in Local position.

3. Control Switch 52CS (S3) contact not

proper make.

3. Control Switch-S3 contact make properly.

4. Test Position (K103) 75T contacts (13-14)

not proper make.

4. Contact 13-14 make properly of Relay K103.

5. Sliding contact not proper make. 5. Sliding contact proper make.

6. Breaker Aux. Switch (Q1-52A) “NO”

contact 19&20 is not proper make.

6. Breaker Aux. Switch (Q1-52A) “NO” contact

19&20 is make.

7. Contactor 94-KA is Open/bunt. 7. Contactor 94-KA is replaced. 8. Any wire remove/Loose from TB. 8. Same is tight in TB.

8. Aux. Contactor K101 is not

operated breaker in “TEST”

position.

1. Fuse: F-16 or F-17 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Sliding contact not proper make. 2. Sliding contact proper make. 3. Spring charging limit switch contact (C&F,

D&H) not proper make. 3. Spring charging limit switch contact proper

make.

4. Contactor K101 is Open/bunt. 4. Contactor K101 is replaced. 5. Any wire remove/Loose from TB. 5. Same is tight in TB.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 38: Trouble Shooting of New 415V SW.GR. L&T make

38

415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T MAKE MAKE MAKE MAKE CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER (MOTOR FEEDER)(MOTOR FEEDER)(MOTOR FEEDER)(MOTOR FEEDER) SR.

NO.

SYSTEM PROBLEM COMMON CAUSES SOLUTIONS

9. Contactor K104 (97) is not

operated when Trip Ckt. Healthy

push button (S4) is press.

( Trip Circuit Supervision )

1. Fuse: F-20 or F-21 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Trip Ckt. Healthy push button (S4)

“NO” contact 23&24 is not proper

make.

2. Trip Ckt. Healthy push button (S4) “NO”

contact 23&24 is making.

3. Ext. Rest. (R) is open. 3. Ext. Rest. (R) is replaced.

4. Contactor K104 (97) is Open/bunt. 4. Contactor K104 (97) is replaced. 5. Sliding contact not proper make. 5. Sliding contact proper make.

6. Trip coil-2 is Open/bunt. 6. Trip coil-2 is replaced.

7. Any wire remove/Loose from TB. 7. Same is tight in TB.

10.

Latching Contactor K103 is not

operated.

( TEST Position )

75 T

1. Fuse: F-18 or F-19 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Test position Limit Switch (C8-Q1)

“NC” contact (1&2) are open.

2. Test position Limit Switch “NC” contact

(1&2) proper make.

3. Contactor – K103 is Open/bunt. 3. Contactor – K103 Replaced. 4. Any wire remove/Loose from TB. 4. Same is tight in TB.

11. Latching Contactor K102 is not

operated.

( SERVICE Position )

75S

1. Fuse: F-18 or F-19 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Service position Limit Switch (C6-Q1)

“NO” contact (1&3) not proper make.

2. Test position Limit Switch “NO” contact

(1&3) proper make.

3. Contactor – K102 is Open/bunt. 3. Contactor – K102 Replaced. 4. Any wire remove/Loose from TB. 4. Same is tight in TB.

12. Circuit Breaker “OFF” Indication

lamp not Glowing.

H15

1. Fuse: F-18 or F-19 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Breaker Aux. Switch (Q1-52B) “NC”

contact (9&10) are open.

2. Breaker Aux. Switch “NC” contact (9&10)

proper make.

3. Indication Lamp (H15) is fused. 3. Indication Lamp (H15) is replaced. 4. Sliding contact not proper make. 4. Sliding contact proper make. 5. Any wire remove/Loose from TB. 5. Same is tight in TB.

13. Circuit Breaker “ON” Indication

lamp not Glowing.

H14

1. Fuse: F-18 or F-19 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Breaker Aux. Switch (Q1-52A) “NO”

contact (15&16) not proper make.

2. Breaker Aux. Switch “NO” contact (15&16)

proper make.

3. Indication Lamp (H14) is fused. 3. Indication Lamp (H14) is replaced.

4. Sliding contact not proper make. 4. Sliding contact proper make. 5. Any wire remove/Loose from TB. 5. Same is tight in TB.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 39: Trouble Shooting of New 415V SW.GR. L&T make

39

415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T MAKE MAKE MAKE MAKE CIRCUIT BREAKERCIRCUIT BREAKERCIRCUIT BREAKERCIRCUIT BREAKER (MOTOR FEEDER)(MOTOR FEEDER)(MOTOR FEEDER)(MOTOR FEEDER) SR.

NO.

SYSTEM PROBLEM COMMON CAUSES SOLUTIONS

14. Circuit Breaker “SPRING

CHARGED” Indication lamp not

Glowing.

H16

1. Fuse: F-18 or F-19 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Contactor K101 “NC” contact

(31&32) is open.

2. Contactor K101 “NC” contact (31&32) is

proper make.

3. Indication Lamp (H16) is fused. 3. Indication Lamp (H16) is replaced. 4. Any wire remove/Loose from TB. 4. Same is tight in TB.

15.

Circuit breaker “AUTO TRIP”

Indication lamp not glowing

during breaker trip on Protection.

H19

1. Fuse: F-18 or F-19 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Relay – 86X “NO” contact is open. 2. Relay - 86 “NO” contacts is proper make.

3. Indication Lamp (H19) is fused. 3. Indication Lamp (H19) is replaced.

4. Any wire remove/Loose from TB. 4. Same is tight in TB.

16.

“BREAKER IN SERVICE” Indication

lamp not glowing.

H17

1. Fuse: F-18 or F-19 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Contactor K102 “NO” contact

(183&184) is not proper make.

2. Contactor K102 “NO” contact (183&184) is

proper make.

3. Indication Lamp (H17) is fused. 3. Indication Lamp (H17) is replaced. 4. Any wire remove/Loose from TB. 4. Same is tight in TB.

17.

“TRIP CKT. HEALTHY” Indication

lamp not glowing.

H18

1. Fuse: F-18 or F-19 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Contactor K104 “NO” contact (6&7) is

not proper make.

2. Contactor K104 “NO” contact (6&7) is

proper make.

3. Indication Lamp (H18) is fused. 3. Indication Lamp (H18) is replaced. 4. Any wire remove/Loose from TB. 4. Same is tight in TB.

18. “RTM” Meter is not working. 1. Sliding contact not proper make. 1. Sliding contact proper make. 2. Fuse: F-11 or F-12 is Blown. 2. Incase Fuse is blown. Fuse replaced.

3. Control Transformer (T5) 415V/110V is

faulty.

3. Control Transformer (T5) is replaced.

4. MCB-Q2 (Amp -2) is “OFF” condition. 4. MCB-Q2 (Amp -2) is put “ON”.

19. Latching Contactor K105 is not

operated.

(95 for 52 C)

1. Fuse: F-18 or F-19 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Check Breaker Aux. Switch (Q1-52B)

“NC” contact (9&10).

2. Breaker Aux. Switch (Q1-52B) “NC” contact

(9&10) is make.

3. Check Breaker Aux. Switch (Q1-52A)

“NO” contact (15&16).

3. Breaker Aux. Switch (Q1-52A) “NO” contact

(15&16) is make.

4. Latching Contactor K105 is Open/bunt. 4. Latching Contactor K105 is replaced. 5. Any wire remove/Loose from TB. 5. Same is tight in TB.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 40: Trouble Shooting of New 415V SW.GR. L&T make

40

415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T MAKE MAKE MAKE MAKE CIRCUIT BREAKER (INCOMER) CIRCUIT BREAKER (INCOMER) CIRCUIT BREAKER (INCOMER) CIRCUIT BREAKER (INCOMER)

SR.

NO.

SYSTEM PROBLEM COMMON CAUSES SOLUTIONS

20. Circuit breaker not closes in “TEST”

position.

1. Fuse: F-34 or F-35 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Local-Remote switch-S2 is not in “Local”

Position.

2. Put Local-Remote switch is in Local position.

3. Control Switch 52CS (S3) contact

(1P1&1P2) not proper make.

3. Control Switch-S3 contact make properly.

4. Test Position (K103) 75T contacts (13-14)

not proper make.

4. Contact 13-14 make properly of Relay K103.

5. Check “NC” contact (21-22) of Relay K101

for Spring charging.

5. Contact 21-22 make properly of Relay K101.

6. Sliding contact not proper make. 6. Sliding contact proper make.

7. Breaker Aux. switch “NC” contact (Q1-

52B) is open.

7. Breaker Aux. switch “NC” contact (Q1) is

making.

8. Closing coil is Open/bunt. 8. Closing coil Replaced

9. Breaker not in “TEST” position. 9. Breaker put in “TEST” position properly.

10. Any wire remove/Loose from TB. 10. Same is tight in TB.

11. Stuck Breaker Mech. 11. Breaker Mechanism problem solved.

21. Circuit breaker not Trip in “TEST”

position.

( Tripping Coil – 1)

1. Fuse: F-41 or F-42 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Local-Remote switch-S2 is not in “Local”

Position.

2. Put Local-Remote switch is in Local position.

3. Control Switch 52CS (S3) contact (2P3 &

2P4) not proper make.

3. Control Switch-S3 contact make properly.

4. Test Position (K103) 75T contacts (43 & 44)

not proper make.

4. Contact 44 & 44 make properly of Relay K103.

5. Test Position (K103) 75T not operated. 5. Test Position (K103) 75T made available.

6. Sliding contact not proper make. 6. Sliding contact proper make.

7. Breaker Aux. switch (Q1-52A) “NO”

contact not proper makes.

7. Breaker Aux. switch contact proper makes.

8. Tripping coil -1 is Open/bunt. 8. Tripping coil -1 Replaced.

9. Any wire remove/Loose from TB. 9. Same is tight in TB.

10. Stuck Breaker Mech. 10. Breaker Mechanism problem solved.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 41: Trouble Shooting of New 415V SW.GR. L&T make

41

415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T MAKE MAKE MAKE MAKE CIRCUIT BREAKER (CIRCUIT BREAKER (CIRCUIT BREAKER (CIRCUIT BREAKER (INCOMERINCOMERINCOMERINCOMER) ) ) )

SR.

NO.

SYSTEM PROBLEM COMMON CAUSES SOLUTIONS

22. Circuit breaker not closes in

“SERVICE” position.

1. Fuse: F-34 or F-35 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Local-Remote switch-S2 is not in “Remote”

Position.

2. Put Local-Remote switch is in Remote position.

3. Service Position (K102) 75S not operated. 3. Test Position (K102) 75S made available.

4. Service Position (K102) 75S “NO” contacts

(13-14) not proper make.

4. Contact 13-14 make properly of Relay K102.

5. Check “3C” relay & its contact. 5. Contact make properly.

6. Check “NC” contact (21-22) of Relay

K101 for Spring charging.

6. Contact 21-22 make properly of Relay K101.

7. Sliding contact not proper make. 7. Sliding contact proper make.

8. Breaker Aux. switch “NC” contact (Q1-

52B) is open.

8. Breaker Aux. switch “NC” contact (Q1-52B) is

making.

9. Closing coil is Open/bunt. 9. Closing coil Replaced

10. Breaker not in “SERVICE” position. 10. Breaker put in “SERVICE” position properly.

11. Any wire remove/Loose from TB. 11. Same is tight in TB.

12. Stuck Breaker Mech. 12. Breaker Mechanism problem solved.

23. Circuit breaker not Trip in

“SERVICE” position.

( Tripping Coil – 1)

1. Fuse: F-41 or F-42 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Local-Remote switch-S2 is not in “REMOTE”

Position.

2. Put Local-Remote switch is in Remote position.

3. Service Position (K102) 75S contacts (43 &

44) not proper make.

3. Contact 43 & 44 make properly of Relay K103.

4. Check “3T” relay & its contact. 4. Contact make properly.

5. Sliding contact not proper make. 5. Sliding contact proper make.

6. Breaker Aux. switch (Q1-52A) contact not

proper makes.

6. Breaker Aux. switch contact proper makes.

7. Tripping coil -1 is Open/bunt. 7. Tripping coil -1 Replaced.

8. Any wire remove/Loose from TB. 8. Same is tight in TB.

9. Stuck Breaker Mech. 9. Breaker Mechanism problem solved.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 42: Trouble Shooting of New 415V SW.GR. L&T make

42

415V SW.GR.415V SW.GR.415V SW.GR.415V SW.GR. L&T L&T L&T L&T MAKE MAKE MAKE MAKE CIRCUIT BREAKER (CIRCUIT BREAKER (CIRCUIT BREAKER (CIRCUIT BREAKER (INCOMERINCOMERINCOMERINCOMER) ) ) )

SR.

NO.

SYSTEM PROBLEM COMMON CAUSES SOLUTIONS

24. Breaker spring charging is not done. 1. Fuse: F-32 or F-23 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Sliding contact not proper make. 2. Sliding contact proper make. 3. Spring charging limit switch contact (C&F,

D&H) not proper make. 3. Spring charging limit switch contact proper

make. 4. Spring charging motor bunt. 4. Spring charging motor replaced.

5. Any wire remove/Loose from TB. 5. Same is tight in TB.

25. Circuit breaker not Trip in

“SERVICE” position. ( Tripping Coil – 2)

1. Fuse: F-36 or F-37 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Local-Remote switch-S2 is not in “REMOTE”

Position. 2. Put Local-Remote switch is in Remote position.

3. Service Position (K102) 75S “NO” contacts

(153 & 154) not proper make.

3. Contact 153 & 154 make properly of Relay K103.

4. Check “3T” relay & its contact. 4. Contact make properly.

5. Sliding contact not proper make. 5. Sliding contact proper make. 6. Breaker Aux. switch (Q1-52A) “NO”

contact (23&24) not proper makes. 6. Breaker Aux. switch contact proper makes.

7. Tripping coil -2 is Open/bunt. 7. Tripping coil -2 Replaced.

8. Any wire remove/Loose from TB. 8. Same is tight in TB.

9. Stuck Breaker Mech. 9. Breaker Mechanism problem solved.

26. “R” or “B” Phase Indication lamp

not glowing on panel.

1. Fuse: F-19 or F-20 or F-21is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Sliding contact not proper make. 2. Sliding contact proper make. 3. Check input & output of Voltage

Transformer – T5 & T7.

3. 415V/110V AC

4. Pri. Fuse: F-11 or F-12 or F-13 or F14 is

Blown.

4. Incase Fuse is blown. Fuse replaced.

5. Any wire remove/Loose from TB. 5. Same is tight in TB.

6. “R” or “B” Phase Indication lamp is

fused.

6. “R” or “B” Phase Indication lamp is

replaced.

27. Aux. Contactor K101 is not

operated.

1. Fuse: F-32 or F-23 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Sliding contact not proper make. 2. Sliding contact proper make. 3. Spring charging limit switch contact (C&F,

D&H) not proper make. 3. Spring charging limit switch contact proper

make.

4. Contactor K101 is Open/bunt. 4. Contactor K101 is replaced. 5. Any wire remove/Loose from TB. 5. Same is tight in TB.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 43: Trouble Shooting of New 415V SW.GR. L&T make

43

415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T MAKE MAKE MAKE MAKE CIRCUIT BREAKER (CIRCUIT BREAKER (CIRCUIT BREAKER (CIRCUIT BREAKER (INCOMERINCOMERINCOMERINCOMER) ) ) ) SR.

NO.

SYSTEM PROBLEM COMMON CAUSES SOLUTIONS

28. Contactor K104 (97) is not

operated when Trip Ckt. Healthy

push button (S4) is press.

( Trip Circuit Supervision )

1. Fuse: F-36 or F-37 Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Trip Ckt. Healthy push button (S4)

“NO” contact 23&24 is not proper

make.

2. Trip Ckt. Healthy push button (S4) “NO”

contact 23&24 is making.

3. Ext. Rest. (R) is open. 3. Ext. Rest. (R) is replaced.

4. Contactor K104 (97) is Open/bunt. 4. Contactor K104 (97) is replaced. 5. Sliding contact not proper make. 5. Sliding contact proper make.

6. Trip coil-2 is Open/bunt. 6. Trip coil-2 is replaced.

7. Any wire remove/Loose from TB. 7. Same is tight in TB.

29.

Latching Contactor K103 is not

operated.

( TEST Position )

75 T

1. Fuse: F-34 or F-35 Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Test position Limit Switch (C8-Q1)

“NC” contact (1&2) are open.

2. Test position Limit Switch “NC” contact

(1&2) proper make.

3. Contactor – K103 is Open/bunt. 3. Contactor – K103 Replaced. 4. Any wire remove/Loose from TB. 4. Same is tight in TB.

30. Latching Contactor K102 is not

operated.

( SERVICE Position )

75S

1. Fuse: F-34 or F-35 Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Service position Limit Switch (C6-Q1)

“NO” contact (1&3) not proper make.

2. Test position Limit Switch “NO” contact

(1&3) proper make.

3. Contactor – K102 is Open/bunt. 3. Contactor – K102 Replaced. 4. Any wire remove/Loose from TB. 4. Same is tight in TB.

31. Circuit Breaker “OFF” Indication

lamp not Glowing.

H15

1. Fuse: F-34 or F-35 Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Breaker Aux. Switch (Q1-52B) “NC”

contact (9&10) are open.

2. Breaker Aux. Switch “NC” contact (9&10)

proper make.

3. Indication Lamp (H15) is fused. 3. Indication Lamp (H15) is replaced. 4. Sliding contact not proper make. 4. Sliding contact proper make. 5. Any wire remove/Loose from TB. 5. Same is tight in TB.

32. Circuit Breaker “ON” Indication

lamp not Glowing.

H14

1. Fuse: F-34 or F-35 Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Breaker Aux. Switch (Q1-52A) “NO”

contact (15&16) not proper make.

2. Breaker Aux. Switch “NO” contact (15&16)

proper make.

3. Indication Lamp (H14) is fused. 3. Indication Lamp (H14) is replaced.

4. Sliding contact not proper make. 4. Sliding contact proper make. 5. Any wire remove/Loose from TB. 5. Same is tight in TB.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 44: Trouble Shooting of New 415V SW.GR. L&T make

44

415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T MAKE MAKE MAKE MAKE CIRCUIT BREAKER (CIRCUIT BREAKER (CIRCUIT BREAKER (CIRCUIT BREAKER (INCOMERINCOMERINCOMERINCOMER) ) ) ) SR.

NO.

SYSTEM PROBLEM COMMON CAUSES SOLUTIONS

33. Circuit Breaker “SPRING

CHARGED” Indication lamp not

Glowing.

H16

1. Fuse: F-34 or F-35 Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Contactor K101 “NC” contact (31&32)

is open.

2. Contactor K101 “NC” contact (31&32) is

proper make.

3. Indication Lamp (H16) is fused. 3. Indication Lamp (H16) is replaced.

4. Any wire remove/Loose from TB. 4. Same is tight in TB.

34.

Circuit breaker “AUTO TRIP”

Indication lamp not glowing

during breaker trip on Protection.

H19

1. Fuse: F-34 or F-35 Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Relay – 86X “NO” contact is open. 2. Relay - 86 “NO” contacts is proper make.

3. Indication Lamp (H19) is fused. 3. Indication Lamp (H19) is replaced.

4. Any wire remove/Loose from TB. 4. Same is tight in TB.

35.

“BREAKER IN SERVICE” Indication

lamp not glowing.

H17

1. Fuse: F-34 or F-35 Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Contactor K102 “NO” contact

(183&184) is not proper make.

2. Contactor K102 “NO” contact (183&184) is

proper make.

3. Indication Lamp (H17) is fused. 3. Indication Lamp (H17) is replaced. 4. Any wire remove/Loose from TB. 4. Same is tight in TB.

36.

“TRIP CKT. HEALTHY” Indication

lamp not glowing.

H18

1. Fuse: F-34 or F-35 Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Contactor K104 “NO” contact (6&7) is

not proper make.

2. Contactor K104 “NO” contact (6&7) is

proper make.

3. Indication Lamp (H18) is fused. 3. Indication Lamp (H18) is replaced.

4. Any wire remove/Loose from TB. 4. Same is tight in TB. 37. Voltages not show in Panel Volt

meter. 1. Panel Volt meter is faulty. 1. Panel Volt meter is replaced. 2. Fuse: F-19 or F-20 or F-21is Blown. 2. Incase Fuse is blown. Fuse replaced.

3. Sliding contact not proper make. 3. Sliding contact proper make. 4. Check input & output of Voltage

Transformer – T5 & T7.

4. 415V/110V AC

5. Pri. Fuse: F-11 or F-12 or F-13 or F14 is Blown. 5. Incase Fuse is blown. Fuse replaced.

6. Any wire remove/Loose from TB. 6. Same is tight in TB.

38. Latching Contactor K105 is not

operated.

(95 for 52 C)

1. Fuse: F-34 or F-35 Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Check Breaker Aux. Switch (Q1-52B)

“NC” contact (9&10).

2. Breaker Aux. Switch (Q1-52B) “NC” contact

(9&10) is make.

3. Check Breaker Aux. Switch (Q1-52A)

“NO” contact (15&16).

3. Breaker Aux. Switch (Q1-52A) “NO”

contact (15&16) is make.

4. Latching Contactor K105 is Open/bunt. 4. Latching Contactor K105 is replaced. 5. Any wire remove/Loose from TB. 5. Same is tight in TB.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 45: Trouble Shooting of New 415V SW.GR. L&T make

45

415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T MAKE MAKE MAKE MAKE CIRCUIT BREAKER (TIE) CIRCUIT BREAKER (TIE) CIRCUIT BREAKER (TIE) CIRCUIT BREAKER (TIE)

SR.

NO.

SYSTEM PROBLEM COMMON CAUSES SOLUTIONS

39. Circuit breaker not closes in “TEST”

position.

1. Fuse: F-15 or F-16 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Local-Remote switch – 43LR (S2) is not in

“Local” Position.

2. Put Local-Remote switch is in Local position.

3. Control Switch 52CS (S3) contact

(1P1&1P2) not proper make.

3. Control Switch-S3 contact make properly.

4. Test Position (K103) 75T contacts (13-14)

not proper make.

4. Contact 13-14 make properly of Relay K103.

5. Check “NC” contact (21-22) of Relay K101

for Spring charging.

5. Contact 21-22 make properly of Relay K101.

6. Sliding contact not proper make. 6. Sliding contact proper make.

7. Breaker Aux. switch “NC” contact (Q1-

52B) is open.

7. Breaker Aux. switch “NC” contact (Q1) is

making.

8. Closing coil is Open/bunt. 8. Closing coil Replaced

9. Breaker not in “TEST” position. 9. Breaker put in “TEST” position properly.

10. Any wire remove/Loose from TB. 10. Same is tight in TB.

11. Stuck Breaker Mech. 11. Breaker Mechanism problem solved.

40. Circuit breaker not Trip in “TEST”

position.

( Tripping Coil – 1)

1. Fuse: F-21 or F-22 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Local-Remote switch - 43LR (S2) is not in

“Local” Position.

2. Put Local-Remote switch is in Local position.

3. Control Switch 52CS (S3) contact (2P3 &

2P4) not proper make.

3. Control Switch-S3 contact make properly.

4. Test Position (K103) 75T contacts (43 & 44)

not proper make.

4. Contact 44 & 44 make properly of Relay K103.

5. Test Position (K103) 75T not operated. 5. Test Position (K103) 75T made available.

6. Sliding contact not proper make. 6. Sliding contact proper make.

7. Breaker Aux. switch (Q1-52A) “NO”

contact not proper makes.

7. Breaker Aux. switch contact proper makes.

8. Tripping coil -1 is Open/bunt. 8. Tripping coil -1 Replaced.

9. Any wire remove/Loose from TB. 9. Same is tight in TB.

10. Stuck Breaker Mech. 10. Breaker Mechanism problem solved.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 46: Trouble Shooting of New 415V SW.GR. L&T make

46

415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T MAKE MAKE MAKE MAKE CIRCUIT BREAKER (TIE) CIRCUIT BREAKER (TIE) CIRCUIT BREAKER (TIE) CIRCUIT BREAKER (TIE)

SR.

NO.

SYSTEM PROBLEM COMMON CAUSES SOLUTIONS

41. Circuit breaker not closes in

“SERVICE” position.

1. Fuse: F-15 or F-16 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Local-Remote switch – 43LR (S2) is not in

“Remote” Position.

2. Put Local-Remote switch is in Remote position.

5. Service Position (K102) 75S not operated. 5. Test Position (K102) 75S made available.

4. Service Position (K102) 75S “NO” contacts

(13-14) not proper make.

4. Contact 13-14 make properly of Relay K102.

5. Check “3C” relay & its contact. 5. Contact make properly.

6. Check “NC” contact (21-22) of Relay

K101 for Spring charging.

6. Contact 21-22 make properly of Relay K101.

7. Sliding contact not proper make. 7. Sliding contact proper make.

8. Breaker Aux. switch “NC” contact (Q1-

52B) is open.

8. Breaker Aux. switch “NC” contact (Q1-52B) is

making.

9. Closing coil is Open/bunt. 9. Closing coil Replaced

10. Breaker not in “SERVICE” position. 10. Breaker put in “SERVICE” position properly.

11. Any wire remove/Loose from TB. 11. Same is tight in TB.

12. Stuck Breaker Mech. 12. Breaker Mechanism problem solved.

42. Circuit breaker not Trip in

“SERVICE” position.

( Tripping Coil – 1)

1. Fuse: F-21 or F-22 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Local-Remote switch – 43LR (S2) is not in

“REMOTE” Position.

2. Put Local-Remote switch is in Remote position.

3. Service Position (K102) 75S contacts (43 &

44) not proper make.

3. Contact 43 & 44 make properly of Relay K103.

4. Check “3T” relay & its contact. 4. Contact make properly.

5. Sliding contact not proper make. 5. Sliding contact proper make.

6. Breaker Aux. switch (Q1-52A) contact not

proper makes.

6. Breaker Aux. switch contact proper makes.

7. Tripping coil -1 is Open/bunt. 7. Tripping coil -1 Replaced.

8. Any wire remove/Loose from TB. 8. Same is tight in TB.

9. Stuck Breaker Mech. 9. Breaker Mechanism problem solved.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 47: Trouble Shooting of New 415V SW.GR. L&T make

47

415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T MAKE MAKE MAKE MAKE CIRCUIT BREAKER (TIE) CIRCUIT BREAKER (TIE) CIRCUIT BREAKER (TIE) CIRCUIT BREAKER (TIE)

SR.

NO.

SYSTEM PROBLEM COMMON CAUSES SOLUTIONS

43. Breaker spring charging is not done. 1. Fuse: F-13 or F-14 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Sliding contact not proper make. 2. Sliding contact proper make. 3. Spring charging limit switch contact (C&F,

D&H) not proper make. 3. Spring charging limit switch contact proper

make. 4. Spring charging motor bunt. 4. Spring charging motor replaced.

5. Any wire remove/Loose from TB. 5. Same is tight in TB.

44. Circuit breaker not Trip in

“SERVICE” position. ( Tripping Coil – 2)

1. Fuse: F-17 or F-18 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Local-Remote switch – 43LR (S2) is not in

“REMOTE” Position. 2. Put Local-Remote switch is in Remote position.

3. Service Position (K102) 75S “NO” contacts

(153 & 154) not proper make.

3. Contact 153 & 154 make properly of Relay K103.

4. Check “3T” relay & its contact. 4. Contact make properly.

5. Sliding contact not proper make. 5. Sliding contact proper make. 6. Breaker Aux. switch (Q1-52A) “NO”

contact (23&24) not proper makes. 6. Breaker Aux. switch contact proper makes.

7. Tripping coil -2 is Open/bunt. 7. Tripping coil -2 Replaced.

8. Any wire remove/Loose from TB. 8. Same is tight in TB.

9. Stuck Breaker Mech. 9. Breaker Mechanism problem solved.

45. Latching Contactor K105 is not

operated.

(95 for 52 C)

1. Fuse: F-15 or F-16 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Check Breaker Aux. Switch (Q1-52B)

“NC” contact (9&10).

2. Breaker Aux. Switch (Q1-52B) “NC” contact

(9&10) is make.

3. Check Breaker Aux. Switch (Q1-52A)

“NO” contact (15&16).

3. Breaker Aux. Switch (Q1-52A) “NO” contact

(15&16) is make.

4. Latching Contactor K105 is Open/bunt. 4. Latching Contactor K105 is replaced. 5. Any wire remove/Loose from TB. 5. Same is tight in TB.

46. Spring Charge Aux. Contactor

K101 is not operated.

1. Fuse: F-13 or F-14 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Sliding contact not proper make. 2. Sliding contact proper make. 3. Spring charging limit switch contact (C&F,

D&H) not proper make. 3. Spring charging limit switch contact proper

make.

4. Aux. Contactor 101 is Open/bunt. 4. Contactor 101 is replaced. 5. Any wire remove/Loose from TB. 5. Same is tight in TB.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 48: Trouble Shooting of New 415V SW.GR. L&T make

48

415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T MAKE MAKE MAKE MAKE CIRCUIT BREAKER (TIE) CIRCUIT BREAKER (TIE) CIRCUIT BREAKER (TIE) CIRCUIT BREAKER (TIE) SR.

NO.

SYSTEM PROBLEM COMMON CAUSES SOLUTIONS

47. Contactor K104 (97) is not

operated when Trip Ckt. Healthy

push button (S4) is press.

( Trip Circuit Supervision )

1. Fuse: F-17 or F-18 Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Trip Ckt. Healthy push button (S4)

“NO” contact 23&24 is not proper

make.

2. Trip Ckt. Healthy push button (S4) “NO”

contact 23&24 is making.

3. Ext. Rest. (R) is open. 3. Ext. Rest. (R) is replaced.

4. Contactor K104 (97) is Open/bunt. 4. Contactor K104 (97) is replaced. 5. Sliding contact not proper make. 5. Sliding contact proper make.

6. Trip coil-2 is Open/bunt. 6. Trip coil-2 is replaced.

7. Any wire remove/Loose from TB. 7. Same is tight in TB.

48.

Latching Contactor K103 is not

operated.

( TEST Position )

75 T

1. Fuse: F-15 or F-16 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Test position Limit Switch (C8-Q1)

“NC” contact (1&2) are open.

2. Test position Limit Switch “NC” contact

(1&2) proper make.

3. Contactor – K103 is Open/bunt. 3. Contactor – K103 Replaced. 4. Any wire remove/Loose from TB. 4. Same is tight in TB.

49. Latching Contactor K102 is not

operated.

( SERVICE Position )

75S

1. Fuse: F-15 or F-16 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Service position Limit Switch (C6-Q1)

“NO” contact (1&3) not proper make.

2. Test position Limit Switch “NO” contact

(1&3) proper make.

3. Contactor – K102 is Open/bunt. 3. Contactor – K102 Replaced. 4. Any wire remove/Loose from TB. 4. Same is tight in TB.

50. Circuit Breaker “OFF” Indication

lamp not Glowing.

H15

1. Fuse: F-15 or F-16 Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Breaker Aux. Switch (Q1-52B) “NC”

contact (9&10) are open.

2. Breaker Aux. Switch “NC” contact (9&10)

proper make.

3. Indication Lamp (H15) is fused. 3. Indication Lamp (H15) is replaced. 4. Sliding contact not proper make. 4. Sliding contact proper make. 5. Any wire remove/Loose from TB. 5. Same is tight in TB.

51. Circuit Breaker “ON” Indication

lamp not Glowing.

H14

1. Fuse: F-15 or F-16 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Breaker Aux. Switch (Q1-52A) “NO”

contact (15&16) not proper make.

2. Breaker Aux. Switch “NO” contact (15&16)

proper make.

3. Indication Lamp (H14) is fused. 3. Indication Lamp (H14) is replaced.

4. Sliding contact not proper make. 4. Sliding contact proper make. 5. Any wire remove/Loose from TB. 5. Same is tight in TB.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00

Page 49: Trouble Shooting of New 415V SW.GR. L&T make

49

415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T 415V SW.GR. L&T MAKE MAKE MAKE MAKE CIRCUIT BREAKER (TIE) CIRCUIT BREAKER (TIE) CIRCUIT BREAKER (TIE) CIRCUIT BREAKER (TIE) SR.

NO.

SYSTEM PROBLEM COMMON CAUSES SOLUTIONS

52. Circuit Breaker “SPRING

CHARGED” Indication lamp not

Glowing.

H16

1. Fuse: F-15 or F-16 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Contactor K101 “NC” contact (31&32)

is open.

2. Contactor K101 “NC” contact (31&32) is

proper make.

3. Indication Lamp (H16) is fused. 3. Indication Lamp (H16) is replaced. 4. Any wire remove/Loose from TB. 4. Same is tight in TB.

53.

Circuit breaker “AUTO TRIP”

Indication lamp not glowing

during breaker trip on Protection.

H19

1. Fuse: F-15 or F-16 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Relay – 86X “NO” contact is open. 2. Relay - 86 “NO” contacts is proper make.

3. Indication Lamp (H19) is fused. 3. Indication Lamp (H19) is replaced.

4. Any wire remove/Loose from TB. 4. Same is tight in TB.

54.

“BREAKER IN SERVICE” Indication

lamp not glowing.

H17

1. Fuse: F-15 or F-16 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Contactor K102 “NO” contact (183

&184) is not proper make.

2. Contactor K102 “NO” contact (183 &184) is

proper make.

3. Indication Lamp (H17) is fused. 3. Indication Lamp (H17) is replaced. 4. Any wire remove/Loose from TB. 4. Same is tight in TB.

55.

“TRIP CKT. HEALTHY” Indication

lamp not glowing.

H18

1. Fuse: F-15 or F-16 is Blown. 1. Incase Fuse is blown. Fuse replaced.

2. Contactor K104 “NO” contact (6&7) is

not proper make.

2. Contactor K104 “NO” contact (6&7) is

proper make.

3. Indication Lamp (H18) is fused. 3. Indication Lamp (H18) is replaced. 4. Any wire remove/Loose from TB. 4. Same is tight in TB.

PREPARED BY: MUKESH MISTRY, FM/B, EMU M -9408709971 DATE: 01.04.2014 REVISION: 00