troubleshooting
DESCRIPTION
Samsung airTRANSCRIPT
Samsung Electronics 4-1
4. Troubleshooting
4-1 Setting Option Setup Method
ex) Option No. :
Step 1 : Enter the Option Setup mode.
1st Take out the batteries of remote control.
2nd Press the temperature button simultaneously and insert
the battery again.
3rd Make sure the remote control display shown as .
Step 2 : Enter the Option Setup mode and select your option according to the following procedure.
Feature Display
The default value is Auto
.
Every time you push the button, the display panel reads Auto Cool Dry Fan Heat , OFF Auto Cool Dry Fan Heat repeatedly.
Push the button to set the display panel to .
Every time you push the button, the display panel reads
...... repeatedly.
Push the button to Cool
.
Push the button to set the display panel to .
Every time you push the button, the display panel reads
...... repeatedly.
Push the button to set the display panel to .
Every time you push the button, the display panel reads
...... repeatedly.
Push the button to Dry
.
Push the button to set the display panel to .
Every time you push the button, the display panel reads
...... repeatedly.
Push the button to set the display panel to .
Every time you push the button, the display panel reads
...... repeatedly.
1
2
3
4
5
6
32
1
4
564 6
Auto
�����������
10
�������
�����������
Auto
Auto
Cool
Dry
Cool
Dry
4-2 Samsung Electronics
Feature Display
Push the button to Fan
.
Push the button to set the display panel to .
Every time you push the button, the display panel reads
...... repeatedly.
Push the button to set the display panel to .
Every time you push the button, the display panel reads
...... repeatedly.
Push the button to Heat
.
Push the button to set the display panel to .
Every time you push the button, the display panel reads
...... repeatedly.
Push the button to Auto
.
Push the button to set the display panel to .
Every time you push the button, the display panel reads
...... repeatedly.
Push the button to set the display panel to .
Every time you push the button, the display panel reads
...... repeatedly.
7
8
9
10
11
Step 3 : Upon completion of the selection, check you made right selections.
Press the Mode Selection key to set the display part and check the display part.
The display part shows like below when each time you press Mode button .
Step 4 : Pressing the ON/OFF button ( )
When pressing the operation ON/OFF key with the direction of remote control for unit, the sound ’’Ding’’ or ’’Diriring’’
is heard and the OPERATION ICON( ) lamp of the display is flickering at the same time, then the input of option is completed. (If the diriring sound isn’t heard, try again pressing the ON/OFF button.)
Step 5 : Unit operation test-run First, Remove the battery from the remote control.
Second, Re-insert the battery into the remote control.
Third, Press ON/OFF key with the direction of remote control for set.
• Error Mode
1st If all lamps of indoor unit are flickering, Plug out, plug in power plug again and press ON/OFF key to retry.
2nd If the unit is not working properly or all lamps are continuously flickering after setting the option code, see if the
correct option code is set up for its model.
78
10
8
91011
Fan
�����������
Fan
Fan
Heat
Auto
Auto
Auto Cool Dry Fan Heat Auto
Samsung Electronics 4-3
Option Items
MODEL OPTIONAL CODE
NS026NHXEA 027770-13022C-200000-300000
NS035NHXEA 027770-15024E-200000-300000
NS052NHXEA 026770-19025C-200000-300000
NS070NHXEA 027770-1C026C-200000-300000
If you are going to use up to SEG 24, please refer to following instruction.SEG 17 : 0 1: Using high ceiling kit for 4way.SEG 18 :
Not in use UseChange temperature display 0(Celsius) 1(Fahrenheit)
Sound Mute 0 2Mixed operation control 0 4
If you want to use multiple functions, add each of the ‘use’ value of the function you want to used and input the final addition as option value.(Use Fahrenheit + Sound mute + Mixed operation control : 1 + 2 + 4 = 7)Ex) 044217-1d00e6-200000-300000When using Sound mute : 044217-1d00e6-200002-300000When using high ceiling kit for 4way and mixed operation error preventing function : 044217-1d00e6-200014-300000
4-4 Samsung Electronics
4-2 Things to check before diagnosis
4-2-1 Display Error mode
If an error occurs during the operation, one or more LED flickers and the operation is stopped except the LED. If you re-operate the air conditioner, it operates normally at first, then detect an error again.
Description
LAMP
OPERATION TIMER DEFROST
Communication error between indoor units X
Error of temperature sensor in the indoor unit (Open/Short) X X
Error of heat exchanger sensor in the indoor unit X
Indoor fan motor mal function X X
EEPROM error
EEPROM option error
On Flickering X Off If you turn off the air conditioner when the LED is flickering, the LED is also turned off.
Samsung Electronics 4-5
4-2-2 Wired remote controller(Option resource)
- If an error occurs is displayed on the wired remote controller. - To see an error code, please press the test button.
Error mode Content Measures
Product operation status in case of error
Error typeOutdoor unit compressor/
outdoor unit fan
Indoor unit communication error Check the communication line for indoor units, check the power supply of the communication phase (DC)
Operation-offCommunication
error
Communication time-out error between indoor/outdoor unit 6-packet over error
Check the communication line for indoor units, check the power supply of the communication phase (DC)
Operation-offCommunication
error
Indoor temperature sensor (open/short error)
Check the temp. sensor of the indoor unit room. Check the indoor PCB connector CN21(white)
Operation-offIndoor sensor
error
Indoor unit Eva In sensor (open/short)
Check the indoor unit drainage pipe sensorCheck the indoor PCB connector CN21 (white)
Operation-offIndoor sensor
error
Dismount of indoor unit Eva In sensor
Check the drainage pipe has been dismounted
Operation-offIndoor sensor
error
Secondary detection of indoor floating switch
Check the indoor unit’s float sensorCheck the indoor PCB connector CN51 (black)
Operation-offSelf-diagnosis
error
Indoor unit not connectedCheck the indoor unit connectionCheck the indoor unit option
Operation-offCommunication
error
Communication error between indoor/outdoor unit INV and Main Micom (1 min.)
Check the Main MICOMCheck the inverter MICOM
-Communication
error
Outdoor temperature sensor errorCheck the connection status of the sensorCheck the sensor locationCheck the resistance values of sensor
Operation-offOutdoor sensor
error
Cond. temperature sensor errorCheck the connection status of the sensorCheck the sensor locationCheck the resistance values of sensor
Operation-offOutdoor sensor
error
[inverter] Emission temperature sensor error
Check the connection status of the sensorCheck the sensor locationCheck the resistance values of sensor
Operation-offOutdoor sensor
error
Excessive temperature emission Not an error (discharge temp. control) -Outdoor unit
protection control error
Power cable connection error Check the status of power connection Operation-offOutdoor sensor
error
4-6 Samsung Electronics
Wired remote controller (cont.)
- If an error occurs is displayed on the wired remote controller. - To see an error code, please press the test button.
Error mode Content Measures
Product operation status in case of error
Error typeOutdoor unit compressor/
outdoor unit fan
Non-connection error of indoor and outdoor Communication wire (connected to the power terminal)
Check the status of power connectionCheck the connection status of the communication line
Operation-offSelf-diagnosis
error
Outdoor fan 1 error
Check the input power connection statusCheck the connection status between the motor and PCB in outdoor unitCheck the fuse of indoor/outdoor units
Operation-offSelf-diagnosis
error
[inverter] Compressor operation error
Check the connection status of the compressorCheck the resistance between different phases in compressor
Operation-offOutdoor unit
protection control error
Discharge current error/ PFC over-current error
Check the input powerCheck refrigerant is filledCheck outdoor fan operates normally
Operation-offOutdoor unit
protection control error
[inverter] IPM over current error
Check refrigerant is filledCheck the connection status of compressor and if it operates normallyCheck for any obstacles around indoor/ outdoor units
Operation-offOutdoor unit
protection control error
[inverter] Compressor rotation error
Check the connection status of the compressorCheck the resistance between different phases in compressor
Operation-offOutdoor unit
protection control error
[inverter] Current sensor error Check PCB operates normally Operation-offOutdoor unit
protection control error
[inverter] DC link voltage sensor error
Check the connection of input powerCheck the status of RY21 and R2000 of Inverter PCB
Operation-offOutdoor unit
protection control error
[inverter] OTP error Check PCB operates normally Operation-offOutdoor unit
protection control error
Outdoor fan 2 error
Check the connection status of input powerCheck the connection status of motor and outdoor PCB Check the fuse of indoor/outdoor unit
Operation-offSelf-diagnosis
error
Gas leakage errorCheck refrigerant is filledCheck the indoor EVA sensor
Operation-offSelf-diagnosis
error
Inconsistent volume Check the indoor unit’s option code Operation-offOutdoor unit
protection control error
Samsung Electronics 4-7
Wired remote controller (cont.)
- If an error occurs is displayed on the wired remote controller. - To see an error code, please press the test button.
Error mode Content Measures
Product operation status in case of error
Error typeOutdoor unit compressor/
outdoor unit fan
Communication error between indoor unit and wired remote controller
Check the connection wire linking indoor unit and wired remote controller
Normal operationWired remote
controller control error
Communication error between master and slave wired remote controller
Check the option switch that distinguishes master and slave (Available only for 1 master unit and 1 slave unit)
Normal operationWired remote
controller control error
Cross installation error of COM1/COM2
Check the connection of outdoor unit and wired remote controller is linked to Com2 terminal of the indoor unit
Normal operationWired remote
controller control error
Wired remote controller COM2 setting option error
Check the Dip switch for Com1 and Com2 is set to Com2
Normal operationWired remote
controller control error
4-8 Samsung Electronics
4-3 Fault Diagnosis by Symptom
4-3-1 Indoor temperature sensor (open/short)
Indoor unit display X(Operation) (Timer) X(Defrost)
Criteria In case of disconnection or short-circuit of the indoor temperature sensors
Cause of problem Disconnection or short-circuit of the relevant sensors
Yes
No
No
At that time, does the resistance value deviate from the
temp. table beside?
YesIs indoor temp. sensor connector disconnected?
Resume operation after replacing PCB
Resume operation after connecting to the
connector PCB
Indoor temp. sensor self-defect (replacement)
Disconnect the PCB from the connector of the internal temp. sensor
and then measure the resistance between the two terminals.
ex) Room temperature 26°C~ resistance 09.26KΩ <Temperature sensor
resistance values>
Current Temp. (°C)
Resistance (KΩ)
40 5.800
35 6.900
30 8.300
25 10.00
20 12.10
15 14.70
10 18.00
5 22.00
0 28.30
-5 33.90
-10 42.30
Samsung Electronics 4-9
4-3-2 Indoor Heat Exchange temperature sensor (open/short)
Indoor unit display (Operation) (Timer) X(Defrost)
Criteria In case of disconnection or short-circuit of the heat exchanger of indoor temperature
Cause of problem Disconnection or short-circuit of the relevant sensors
Yes
No
No
At that time, does the resistance value deviate from the temperature
table beside?
YesIs indoor Heat Exchange
temp. sensor connector disconnected?
Resume operation after replacing PCB
Resume operation after connecting to the
connector PCB
Indoor Heat Exchange temp. sensor
self-defect (replacement)
Disconnect the PCB from the connector of the internal temp. sensor
and then measure the resistance between the two terminals.
ex) Room temperature 24°C~ resistance 10.93KΩ <Temperature sensor
resistance values>
Current Temp. (°C)
Resistance (KΩ)
40 5.800
35 6.900
30 8.300
25 10.00
20 12.10
15 14.70
10 18.00
5 22.00
0 28.30
-5 33.90
-10 42.30
4-10 Samsung Electronics
4-3-3 Indoor Fan error
Indoor unit display X(Operation) X(Timer) (Defrost)
Criteria Indoor fan being non-operative/ stop after excessive high speed
Cause of problem Check for motor connector disconnect/ check motor fan fastening
Yes
No
No
Is there any clogging (binding) of foreign substances in the MotorFan?
YesIs Motor connector disconnected from the PCB?
Resume operation after replacing PCB
Resume operation after connecting to the
connector PCB
Resume operation after removing the foreign
substances.
Samsung Electronics 4-11
4-3-4 Communication error after completion of tracking
Indoor unit display X(Operation) (Timer) (Defrost)
Criteria If communication between indoor and outdoor units has been blocked for 2 minutes during operation
Cause of problem Communication error between indoor and outdoor unit
No
Yes
Replace PCB of indoor unit after checking out the communica-
tion line
At this time, the voltage between lines is a square wave that is above DC±0.7V as
shown in the picture below
+0.7V
-0.7V
After removing the communication line that links outdoor to indoor units measure
2 lines of the outdoor unit with scope.
After reconnecting the communication line that links outdoor and indoor units,
remove communication connector in the indoor PCB. If communication does not work during operation, replace PCB of
the indoor unit.
Replace PCB after checking the communication line of the outdoor unit
PCB and connector
Good
defect
4-12 Samsung Electronics
Resume operation after replacing PCB
No
Yes
If the circuit part of the EEPROM is okay
(necessary component missing in EEPROM
circuit part/ damage/ soldering defect)
Resume operation after repairing it according to P8-2 circuit diagram’s
EEPROM part, P6~6-10 component list.
If problem occurs during re-operation, replace PCB
4-3-5 EEPROM circuit part defect
Indoor unit display (Operation) (Timer) (Defrost)
Criteria EEPROM circuit part defect
Cause of problem EEPROM component defect/ necessary component missing in EEPROM circuit part/ damage/ soldering
Samsung Electronics 4-13
4-3-6 When outdoor units cannot be turned on
1. Cause of the breakdown
1) Is power voltage 220V?
2) Is AC power properly connected?
3) Are the LEDs of Main PCB and inverter PCB of the outdoor unit on?
4) Is the power supply of the outdoor unit 220V?
2. Inspection order
Yes
NoBridge 10de replacement (DB300)
Yes
Yes
Yes
Yes
Switch off the main power (breaker or power outlet) then turn on again after 30 seconds.
Replace outdoor unit PCB for Outdoor MICOM defect.
Check and replace the wire that connects the outdoor terminal block to outdoor unit’s PCB
(contact point, short-circuit)
NoIs the voltage of N-L of the outdoor unit’s PCB AC187V~AC253V?
Is the voltage of the both side of BD01, “~” and “~” of the outdoor unit’s
Main PCB AC187V~AC253V?
Is the voltage of C101 chemical condenser of the outdoor units’ Main PCB
DC265V~DC357V?
NoR001 Resistance replacement
Is the resistance value of R001 180Ω~220Ω?
NoConnect the connection wire of the reactor
Is reactor 1 and 2 (reactor connection wire) properly connected
to the reactor?
Yes
Power ok?
YesNo
Finish
4-14 Samsung Electronics
4-3-7 DC link and over/lower voltage error
1. Inspection items
1) Is compressor operating properly?
2) Is there a connection between input power and power?
2. Inspection order
Yes
Replace PCB
Turn off the power then reconnectNo
Is EMI PCB andInverter PCB connected
properly?
Samsung Electronics 4-15
4-3-8 IPM and over current error
1. Inspection items
1) Is refrigerant filled?
2) Is the compressor operating without a problem?
3) Is the compressor connected properly?
4) Are there any obstacles around the indoor/outdoor units?
2. Inspection order
Yes
Yes
Yes
Yes
Yes
Reinstall after removing obstaclesNoAre outdoor units installed correctly?
NoReinstall after removing obstaclesAre indoor units installed correctly?
NoCheck the connection status of the compressor
Is the compressor connection line properly connected to the
compressor?
NoResistance replacement
Are the values for R418current sensing resistance within
19mΩ-21mΩ?
NoOpen valvesIs service valve completely opened?
Yes
NoCompressor replacement
Is resistance value of the different compressor phases
(UV, V W, WU) less than 2Ω?
(continued on the back)
Continue
4-16 Samsung Electronics
IPM and over current error (cont.)
Yes
Replace PCB
Turn off the power then reconnect the cable
NoAre the location of the temperature sensor and measurement value
normal?
Yes
Replace compressor No
Yes
Turn off the power then correct the sensor location or replace it
NoIs the connection cable between the compressor and PCB
properly connected?
Is the resistance between the Compressor body and chassis Maga Ω?
Continued
Samsung Electronics 4-17
4-3-9 Compressor starting error, compressor locking error, compressor revolving error
1. Inspection items
1) Is the connection line between power and the compressor properly connected?
2) Is the resistance between different compressor phases normal?
2. Inspection order
Check the connection lineNo
Restart after turning off the power
Yes
Replace the outdoor unit’s PCB
Replace the CompressorNo
Yes
Terminate the serviceNo
Did error occur?
Yes
Replace the CompressorNoIs the resistance
between the Compressor body and chassis Maga Ω?
Yes
Is the Compressor connection line properly connected to the
Compressor?
Is resistance value of the different Compressor phases (UV, V W, W U)
less than 2Ω?
4-18 Samsung Electronics
4-3-10 Outdoor temperature sensor error
1. Inspection items
1) Are the sensors connected properly?
2) Are the sensors located properly?
3) Do the resistance values of the sensors satisfy each temperature?
2. Inspection order
Yes
Yes
Yes
Replace temperature sensorNo
Reconnect the temperature sensor connector
No
Power off
Reconnect the temperature sensor connector
No
No
Yes
Are connectors properly connected to the
relevant colors?
Are temperature sensors connected without separation?
When measuring the resistance of both sides with a single
temperature sensor, does it indicate 10KΩ at room temperature of 25°C?
Yes
Replace PCB after turning off the powerNo
After assembling the temperature sensors on PCB check
the voltage of both sides. Do they indicate DC1V~DC4V?
Is there a short circuit or defective contact in
the sensor wires?
Replace temperature sensor after turning off the power
Yes
Power on
Replace PCB after turning off the power
ex) Room temperature 24°C ~ resistance 10.28kΩ
<Temperature sensor resistance values>
Current temperature
(°C)
Resistance (KΩ)
Current temperature
(°C)
Resistance (KΩ)
70 4 20 12
60 5 10 20
50 6 0 30
40 7 -10 40
30 8
Samsung Electronics 4-19
4-3-11 Emission temperature sensor error
1. Inspection items
1) Are the sensors connected properly?
2) Are the sensors located properly?
3) Do the resistance values of the sensors satisfy each temperature?
2. Inspection order
Yes
Yes
Yes
Replace temperature sensorNo
Reconnect the temperature sensor connector
No
Power off
Reconnect the temperature sensor connector
No
No
Yes
Are connectors properly connected to the
relevant colors?
Are temperature sensors connected without separation?
When measuring the resistance of both sides with a single
temperature sensor, does it indicate 200KΩ at room temperature of 25°C?
Yes
Replace PCB after turning off the powerNo
After assembling the temperature sensors on PCB check
the voltage of both sides. Do they indicate DC1V~DC4V?
Is there a short circuit or defective contact in
the sensor wires?
Replace temperature sensor after turning off the power
Yes
Power on
Replace PCB after turning off the power
ex) Room temperature 23°C ~ resistance 205.4kΩ
<Temperature sensor resistance values>
Current temperature
(°C)
Resistance (KΩ)
Current temperature
(°C)
Resistance (KΩ)
80 40 30 180
70 50 20 220
60 60 10 320
50 90 0 550
40 110
4-20 Samsung Electronics
4-3-12 Cond temperature sensor error
1. Inspection items
1) Are the sensors connected properly?
2) Are the sensors located properly?
3) Do the resistance values of the sensors satisfy each temperature?
2. Inspection order
Yes
Yes
Yes
Replace temperature sensorNo
Reconnect the temperature sensor connector
No
Power off
Reconnect the temperature sensor connector
No
No
Yes
Are connectors properly connected to the
relevant colors?
Are temperature sensors connected without separation?
When measuring the resistance of both sides with a single
temperature sensor, does it indicate 10KΩ at room temperature of 25°C?
Yes
Replace PCB after turning off the powerNo
After assembling the temperature sensors on PCB check
the voltage of both sides. Do they indicate DC1V~DC4V?
Is there a short circuit or defective contact in
the sensor wires?
Replace temperature sensor after turning off the power
Yes
Power on
Replace PCB after turning off the power
ex) Room temperature 24.5°C ~ resistance 10.17kΩ
<Temperature sensor resistance values>
Current temperature
(°C)
Resistance (KΩ)
Current temperature
(°C)
Resistance (KΩ)
70 4 20 12
60 5 10 20
50 6 0 30
40 7 -10 40
30 8
Samsung Electronics 4-21
4-3-13 Communication error between indoor/outdoor units (1min.)
1. Inspection items
1) Is the communication line between indoor and outdoor units connected properly?
2) Is there a communication connection between power line and communication line?
2. Inspection order
Yes
Replace PCB of the outdoor unit after turning off.
No
Terminate serviceNo
Restart after turning off the power
No
Yes
Is there a communication error?
Is there a communication connection between power line and
communication line?
Is the outdoor terminal block F1–F2, less than DC5V?
Yes
Connection line checkup
When measuring F1–F2, the outdoor terminal block, if the voltage varies
(communicates) below DC5V, the connection status of the connection line is normal.
4-22 Samsung Electronics
4-3-14 Outdoor fan error
1. Inspection items
1) Is input power and power connected properly?
2) Is motor connection line properly connected to the PCB of the outdoor unit?
3) Is the fuse for indoor/outdoor unit connected?
4) Are there any obstacles around Motor or Propeller?
5) Is Motor Driver out of order?
2. Inspection order
Yes
Remove the Fan lock
Yes
NoCheck fan is locked
Replace the FanNo
Does the color of fire wire match?
Yes
Reconnect the connectorNoIs the connection between Fan
and PCB proper?
Yes
No
Check if the outdoor unit’s power supply is defective
Yes
Is the voltage of the No.1 and No. 3 pin of the CN71
between 250V~350V?
Yes
Is the voltage of the No.1 and No. 3 pin of the CN01 between 1V~5V?
No
Is there any change in the voltage of the no.13 pin of
the IC01 (MICOM)?
Defective MICOMReplace the main PCB of the outdoor unit
(continued on the back)
Continue
Replace the main PCB ofthe outdoor unit
Samsung Electronics 4-23
Outdoor fan error (cont.)
Replace the main PCB of the outdoor unit
No Replace the main PCB of the outdoor unit
Yes
No
Is there any change in the voltage of the
no.13 pin of the IC01 (MICOM)?
Replace BLDC fan motor
30 seconds after turning off the power, separate BLDC Fan
connector CN71
Yes
Continued
Is there any change in the voltage
of the no 3 pin and no.6 pin of the IC01 (MICOM)?
4-24 Samsung Electronics
4-3-15 Discharge current error/ PFC over-current error
1. Inspection items
1) Is input power correct?
2) Is refrigerant filled?
3) Is the outdoor fan spinning correctly?
4) Are there any obstacles around indoor/outdoor units?
2. Inspection order
Yes
Yes
Yes
Yes
Reinstall after removing obstacleNoIs the outdoor unit installed correctly?
NoReinstall after removing obstacleIs indoor unit installed correctly?
NoOpen valvesIs the service valve open completely?
NoReplace the compressorIs the compressor operating normally?
Replace PCB
Samsung Electronics 4-25
4-3-16 Gas leakage error
1. Inspection items
1) Is refrigerant filled?
2) Is the indoor EVA sensor connected properly?
2. Inspection order
ace thNo
Yes
Reconnect the sensor connectorNo
Restart after turning off the power
Yes
Replace the outdoor unit’s PCB
Replace the compressorNo
Yes
Terminate the serviceNo
Did error occur?
Yes
Open valvesNo
Is the service valve open completely?
Yes
Is the indoor EVA sensor connected properly?
Is refrigerant filled?
Is resistance value of the different Compressor phases (UV,
V W, W U) less than 2Ω?
4-26 Samsung Electronics
4-3-17 Other
1. Current sensor error
Check PCB operates normally then replace the PCB
2. Compressor V limit error
Check the compressor operates normally then replace the compressor. If an error still occurs after the replacement of the
compressor, replace the PCB
3. OTP error
Check PCB operates normally then replace the PCB
4. DC link Voltage Sensor Error
Check the connection between input power and the power is okay then replace the PCB
5. AC zero Crossing signal out error
Check the connection between input power and the power is okay then replace the PCB
6. Inconsistent volume
Check the option code of the indoor unit.