1 Troubleshooting and Lessons Learned Using Protective Relay Event Analysis GE Digital Energy Multilin

Upload: tranhanh

Post on 24-Mar-2018

246 views

Category:

Documents


6 download

TRANSCRIPT

Page 1: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

11

Troubleshooting and Lessons Learned Using Protective Relay Event Analysis

GE Digital Energy Multilin

Page 2: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

22

Seminar Presenter

Terrence [email protected]

423-304-0843

Page 3: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

33

Seminar Agenda

• Overhead distribution ground fault inside industrial facility causes a generator stator fault

• Incorrect current transformer wiring causes bus fault during power transformer energization

• Fault on distribution system causes unusual transformer high side currents• Incorrect current transformer wiring causes motor thermal overload trip• Generator loss of excitation and reverse power trips• Overcurrent trip on paralleling switchgear• Synchronous motor trip on power factor• Substation heat pumps drops bus voltage by 1kV causes capacitor bank

trip

Page 4: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

44

Review Of Symmetrical Components

Page 5: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

55

Symmetrical and Non-Symmetrical Systems:

Symmetrical System:• Counter-clockwise rotation

• All current vectors have equal amplitude

• All voltage phase vectors have equal amplitude

• All current and voltage vectors have 120 degrees phase shifts and a sum of 0v.

3 units

3 units

3 units

120°120°

120 °

Non-Symmetrical System:• Fault or Unbalanced condition

• If one or more of the symmetrical system conditions is not met

3 units

9 units

4 units 120°100°

140°

Page 6: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

66

• A-B-C Counter-clockwisephase rotation

• All phasors with equal magnitude

• All phasors displaced 120 degrees apart

• No Rotation Sequence

• All phasors with equal magnitude

• All phasors are in phase

• A-C-B counter-clockwisephase rotation

• All phasors with equal magnitude

• All phasors displaced 120 degrees apart

Positive Sequence (Always Present)

C

A

B

Zero Sequence Negative Sequence

C

A

B

ABC

120

120

120120

120

120

Symmetrical Components:

Page 7: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

77

Symmetrical Components:

I0 = ⅓ (Ia + Ib + Ic)

I1 = ⅓ (Ia + Ib + 2Ic)

I2 = ⅓ (Ia + 2Ib + Ic)

V0 = ⅓ (Va + Vb + Vc)

V1 = ⅓ (Va + Vb + 2Vc)

V2 = ⅓ (Va + 2Vb + Vc)

Unbalanced Line-to-Neutral Phasors:

ABC

Zero Sequence Component:

PositiveSequence Component:

NegativeSequence Component:

2 = 240

CA

B = 120

Ia = I1 + I2 + I0

Ib = 2I1 + I2 + I0

Ic = I1 + 2I2 + I0

Va = V1 + V2 + V0

Vb = 2V1 + V2 + V0

Vc = V1 + 2V2 + V0

=Phasor @ +120

2 =Phasor @ 240

Page 8: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

88

Calculating Symmetrical Components:

Three-Phase Balanced / Symmetrical System

*Vc

Va

2* Vb

3V2 =0

VcVa

Vb

3V0 =0

2*VcVa * Vb

3V1

Open-Phase Unbalanced / Non-Symmetrical System

Vc

Va

Vb

Ic

IaIb 2*Ic

Ia* Ib

3I1

*Ic

Ia

2* Ib

3I2 Ic

Ia

Ib3I0

Positive Negative Zero

Positive Negative Zero

Vc

Va

Vb

Ic

IaIb

Page 9: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

99

Symmetrical ComponentsExample: Perfectly Balanced & ABC Rotation

Result: 100% I1 (Positive Sequence Component)

Page 10: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

1010

I2

Symmetrical ComponentsExample: B-Phase Rolled & ABC Rotation

Result: 33% I1, 66% I0 and 66% I2

Page 11: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

1111

Symmetrical ComponentsExample: B-Phase & C-Phase Rolled & ABC Rotation

Result: 100% I2 (Negative Sequence Component)

Page 12: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

1212

Summary of Symmetrical Components:

• Under a no-fault condition, the power system is considered to be essentially symmetricaltherefore, only positive sequence currents and voltages exist.

• At the time of a fault, positive, negative and possibly zero sequence currents and voltages exist.

o All positive, negative and zero sequence currents can be calculated using real world phase voltages and currents along with Fortescue’s formulas.

o In = Ia + Ib + Ic = 3 I0

Page 13: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

1313

Data Sample 1 = No Fault Data Sample 2 = Fault

Relay

Power System FaultsFault Analysis

Page 14: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

1414

300 A

300 A

300 A

120°

120°

120°

For Normal Conditions:

Data Sample 1 = No Fault

Data Sample 1 Phasor Diagram:

Waveform Capture:

Power System FaultsFault Analysis

Page 15: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

1515

Negative Sequence Component, I2:For Fault Condition:

I2 = 200 A

2Ib = 300 A

Ic = 300 A

I2= 1/3(600 A)Ia = 900 A

I2 = 1/3(Ia+2Ib+Ic)

= 1/3(600 A)

I2 = 200 Amps

600 A

Power System FaultsFault Analysis - Example

Page 16: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

1616

Zero Sequence Component, I0:For Fault Condition:

300 A

900 A

300 A

Ib Ic

I0= 1/3(Ia+Ib+Ic)

Power System FaultsFault Analysis - Example

Page 17: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

1717

Zero Sequence Component, I0:For Fault Condition:

Ib= 300 A

Ic= 300 A

Ia = 900 A

I0= 1/3(Ia+Ib+Ic)

= 1/3(600 A)

I0= 200 Amps

I0 = 200 AI0= 1/3(600 A)

600 A

Power System FaultsFault Analysis - Example

Page 18: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

1818

Verifying Fault Current on Phase A:For Fault Condition:

Ia = I1 + I2 + I0= 500 A + 200 A + 200 A

Ia = 900 Amps= actual fault current measured on Phase A

Fault, Ia

At the time of a fault, positive (I1), negative (I2) and possibly zero (I0) sequence currents exist.

Power System FaultsFault Analysis - Example

Page 19: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

1919

Sequence Networks

• Where is sequence voltage highest?

• What generates negative and zero sequence currents?

Page 20: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

2020

How do we connect so that I1=I2=I0?

• The sequence networks have to be in series for a phase to ground fault on a solidly grounded system.

Page 21: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

2121

Common Fault Types:

Page 22: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

2222

Transformer Interconnections:

Page 23: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

2323

Analysis of Interesting Events Using Waveforms

Page 24: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

24

Snake Causes a Distribution Fault

Page 25: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

25

Snake Causes a Distribution Fault

Relays at all three locations tripped. All three had different times. Are these events related???

Page 26: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

26

Relays at all three locations tripped. All three had different times. Are these events related???

CB01

CB402

Why B phase on one and C on the other?

Page 27: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

27

What about the Generator???

C phase terminal fault current, but…

Small C phase neutral fault current

CG Stator fault close to the terminal

Page 28: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

28

What happened here??

• C phase to ground fault because of the snake• Zone interlocking scheme failed because of a

settings error• Generator failed due to the extra stress

caused by the fault.• Biggest Challenge was synchronizing the

time differences in the relays.

Page 29: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

29

Challenges to Time Synch

Page 30: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

30

Modern Time Synchronization

Add 1588 capabilities for future expansion while supporting in-

service IRIG-B devices

Page 31: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

31

1588 Protocol over a wide area with legacy devices

Page 32: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

32

Generator Relay Failure to Trip on Loss of Excitation

Page 33: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

3333

The Story

• We lost the exciter• The relay failed to trip on loss of excitaton

Page 34: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

34

This ring down in current looks like loss of excitation (40)

But 40 function does not operate!

Page 35: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

35

Why is current in opposite direction from voltage?

Let’s look at the phasors

Page 36: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

36

Limited by OEL

Limited by SCL

Limited by MEL

Overexcited

Underexcited

Real Power

Rea

ctiv

e Po

wer

Increasing pressure (cooling)

Machine limits

Page 37: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

37

Loss of field

5.157120

18900VT

16005

8000CT

54.15

5.1571600

21118(sec)

22

MVAkV

VTRCTR

MVAbasekVbase

Zbase

36.354.15216.0(sec)(sec) ZbaseXX dd

57.3054.15967.1(sec)(sec) ZbaseXX dd

Page 38: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

38

Something with your current is not right !

Ok, then why don’t I trip on Differential?

Page 39: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

39

Once I account for transformer, currents sum to zero

Page 40: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

40

So what's wrong with 40 function?

Page 41: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

4141

Fault on Distribution System Causes

Unusual Transformer High Side Currents

Page 42: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

4242

The Story

• Distribution transformer feeding medium voltage overhead distribution.

• In oscillography, we see two phases of fault current on the high side of the transformer for a single phase to ground fault on the low side

Page 43: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

4343

Page 44: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

4444

Page 45: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

4545

Page 46: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

4646

F1 Symmetrical components

M1 Symmetrical components

Pre-fault all positive seq.

Pre-Fault Values

Page 47: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

4747

Fault Values

F1 Pos, Neg, and no Zero

M1 Pos, Neg, and Zero

Why are the sequence values of M1 and F1 different??????

Page 48: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

4848

The Fault Network as Seen From F1

Page 49: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

4949

The Fault Network as Seen From M1

Page 50: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

5050

What Effect Does this Fault Have on Voltage?

Page 51: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

5151

What Effect Does this Fault Have on Voltage?

Page 52: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

5252

Incorrect current transformer wiring causes

bus fault during power transformer energization

Page 53: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

5353

The Story

• I have energized the transformer• As soon as I pickup load, I get a

transformer differential.

Page 54: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

54

Oscillography

Percent Differential Operates

Page 55: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

55

Oscillography

Page 56: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

56

What I expect to see for ABC rotation:

Typically H Winding leads X winding by 30 degrees

Page 57: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

57

What I expect to see for ABC rotation:

Typically H Winding leads X winding by 30 degrees

We compensate the measured currents with settings

Page 58: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

58

What I expect to see for ABC rotation:

Page 59: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

59

But this isn’t ABC rotation:

Page 60: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

60

But this isn’t ABC rotation:

Typically H Winding lags X winding by 30 degrees on ACB rotation

Page 61: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

61

Trip occurred because of setting

Typically H Winding lags X winding by 30 degrees on ACB rotation

Page 62: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

62

What happens if I swap phases on my H winding:

Swapping phases on the High side changes my transformer from 30 lag to 30 lead

c

a

C

A

Page 63: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

63

Reversed Phase Causes Motor Thermal Overload Trip

Page 64: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

6464

The Story

• New switchgear feeding motor• When we start the motor, it trips after

about 10 minutes.

Page 65: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

6565

Waveforms

Clearly, there is a phase reversed

Why would this take 10 minutes to trip

Page 66: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

6666

• Thermal Capacity Used (TCU) is a criterion selected in thermal model to evaluate thermal condition of the motor.

• TCU is defined as percentage of motor thermal limit utilized during motor operation.

• A running motor will have some level of thermal capacity used due to Motor Losses.

• Thermal Trip when Thermal Capacity Used equals 100%

Thermal Model – Thermal Capacity Used

Page 67: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

6767

Thermal Model - Current Unbalance BiasNegative sequence currents (or unbalanced phase currents) will cause additional rotor heating that will be accounted for in Thermal Model.

Positive Sequence

Negative Sequence

• Main causes of current unbalance• Blown fuses• Loose connections• Stator turn-to-turn faults• System voltage distortion and unbalance• Faults

Page 68: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

6868

Thermal Model - Current Unbalance Bias

• Equivalent heating motor current is employed to bias thermal model in response to current unbalance.

))II(K(1II 212

2MEQ

• Im - real motor current; K - unbalance bias factor; I1 & I2 - positive and negative sequence components of motor current.

• K factor reflects the degree of extra heating caused by the negative sequence component of the motor current.

• IEEE guidelines for typical and conservative estimates of K.

2LRCI175K TYPICAL

2LRCI230K CONSERVATIVE

Page 69: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

6969

Is the reversed phase the only error here?

Page 70: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

7070

VAB voltage relative to VAG

For an ABC rotation, VAG lags VAB by 30 degrees

Page 71: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

7171

Is the reversed phase the only error here?

For an ABC rotation, VAG lags VAB by 30 degrees

Page 72: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

7272

How to fix

For an ABC rotation, VAG lags VAB by 30 degrees

What is really A phase is wired to B phase and is rolled 180 degrees

Page 73: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

7373

How to fix

Move wire from B to A and roll 180 degrees

Move wire from C to B and roll 180 degrees

Move wire from A to C and don’t roll.

Page 74: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

7474

Lessons Learned

• This relay had a rolled phase, but also a lot of other issues

• During start up, verify metered values• Negative sequence voltage and current should be

small relative to positive sequence quantities• Power factor should be as expected 80-90% lagging

for induction machines and loads.• Phase relationships should be as expected (across

transformers)

Page 75: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

75

Low Impedance Bus Differential Trip When the Second Breaker is Closed

on the Bus

Page 76: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

7676

The Story

• We are installing a bus differential• When we pick up load, we trip

Page 77: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

77

Page 78: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

78

87B Bus Differential Configuration

Page 79: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

79

How do we fix this monstrosity?

Let’s look at the phasors

Page 80: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

80

We must maintain ABC rotation

Corrective action required

Page 81: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

81

Paralleling Switchgear Trip

Page 82: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

8282

The Story

• This relay trips every time I close the breaker

• It is tripping on Overcurrent.• You need to send me a new relay because

this one is obviously bad.

Page 83: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

8383

Events

Page 84: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

8484

Waveforms

Page 85: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

8585

How Microprocessor Relays Fail• Power Supplies – Failures there most likely mean the

relay is dead with no lights.• Processor failures – Failures there cause an alarm

which takes the relay out of service and illuminates an alarm LED.

• DSP failures – Failures there are rare, would typically raise an alarm and would show distorted metering values.

• Safe to say, this relay has NO problems, it is doing what it is suppose to do.

Page 86: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

8686

Where is this relay and when is it tripping?

So what are you actually paralleling?

Page 87: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

8787

So what are you actually paralleling?

230KV Transmission System

13KV Distribution System

Page 88: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

8888

Equivalent Circuit

Since Parallel:ZdistIdist=ZtranItran

Zdist/Ztran=Itran/Idist

If Zdist>>Ztran

Then Itran>>Idist

Page 89: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

8989

Possible Solutions• Can’t really raise the TOC pickup setting on the tie

breaker 750 and can’t really make the time delay longer• Could add controls to trip a selected breaker after all

three are closed.• Never parallel these two sources. Add mechanical

interlocks to prevent parallel of all three sources.

Page 90: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

90

Synchronous Motor Trip on Power Factor

Page 91: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

9191

The Story

• Synchronous motor is tripping on power factor pull-out

• Four of these compressors at the facility and is only happening to this compressor

• Started happening after we had the motor rebuilt.

Page 92: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

9292

Synchronous Motor Theory

Page 93: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

9393

Machine Excitation

Typical Generator Operation

Under-Excited Generator Operation

Synchronous Motor Operation

Induction Motor Operation

Page 94: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

94

Synchronous Machines

• In an induction motor, the more load you have, the larger your slip.

• In a synchronous motor, slip=0. The more load you have (without increasing excitation) the greater your (negative) power factor.

• To prevent slipping a pole (pull-out protection) you use power factor protection to trip when your load changes beyond what your exciter can keep up with.

Page 95: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

9595

Reciprocal Compressors

Page 96: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

9696

Reciprocal Compressors

Page 97: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

9797

The Problem Compressor – Loaded Cycle

Page 98: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

9898

The Problem Compressor – Un-Loaded Cycle

Within 60 Degrees of slipping a pole!

Page 99: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

99

Problem

• This cannot be fixed with relay settings.• Must talk to motor manufacture about why this

compressor behaves this way.• A mechanical problem was causing the issue.

Page 100: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

100

Substation heat pumps drops bus voltage by 1kV causes

capacitor bank trip

Page 101: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

101101

The Story

• This relay is tripping on B phase voltage differential.

• Two relays in the station and they are both tripping on B phase voltage differential.

• The redundant relays are not tripping.

Page 102: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

102102

Six Capacitor Banks – 2 Relays

16.7KV 600KVAR9 Elements/Can

0.8KV 167KVAR

83.13KV/115V

300/5

87

Protective Relay

00

0

144KV Line to Line

Page 103: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

103103

Pre-Fault Values of the Trip

95,924-274(350.7130)=171=0.002pu

Page 104: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

104104

Fault Values of the Trip

94047-274(350.6185)=2022=0.022

Trip is set to 0.02 with a 50ms Delay

Page 105: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

105105

Event Records

Page 106: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

106106

Event Records

Page 107: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

107107

One of these things isn’t like the others!

Page 108: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

108108

Page 109: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

109109

Page 110: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

110110

Page 111: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

111111

Page 112: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

112112

What can I do to prevent nuisance trips when the heat pump kicks on?

• Capacitor Bank Protection is set very sensitive. In this case at 2%.

• Can interlock the heat pump contactor with an 89B contact (humor intended)

• Can add a standard VT to provide voltages for protection.

Page 113: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

113113

How would this effect other relaying

• Phase and Ground Distance Protection:• Could cause an element to over-reach if

a fault occurred at the same instance of a heat pump start.

• Probably wouldn’t affect steady state conditions unless extremely heavily loaded line.

Page 114: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

114114

How would this effect other relaying

• Bus Under-voltage:• Probably would be unaffected because

of the duration.

Page 115: Troubleshooting and lessons learned using protective relay ... Relay... · Troubleshooting and Lessons Learned Using Protective Relay Event Analysis ... For an ABC rotation, VAG

115115

Lessons Learned

• Capacitor Bank Protection requires very sensitive settings.

• VT error can influence those setting.• We still spend most of our time talking

about instrument transformers.