Troubleshooting M-Bus meters
M-Busmeters
PiiGAB M-Bus Setup Wizard Find PiiGAB’s M-Bus gateways on the network.
Set IP-address of PiiGAB’s M-Bus gateways on the network.
Test M-Bus meters.
Set primary address of M-Bus meters.
Set communication speed M-Bus meters.
See the raw data sent to and from the M-Bus meters.
Search M-Bus meters.
PiiGAB M-Bus Explorer Assumes you have an established connection with the M-Bus gateways and the M-Bus
meters.
See what objects are possible to read from an M-Bus meter:
o Objects data types
o Objects physical quantities
o Objects scaling
o Objects values
See what telegram contains the M-Bus meter’s objects.
PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]
MBus2MBus
M-Busmeters
M-Busclient1
M-Busclient2
M-Busclient3
M-Busclient4
M-Busclient2
M-Busclient1
M-Busmeters
Possibilities Transparent M-Bus traffic between the M-Bus meter and the M-Bus client. PiiGAB M-Bus 900
will not affect the requests and responses in any way.
Up to four M-Bus clients can read the M-Bus meters independently.
The M-Bus client can communicate UDP/IP, TCP/IP, RS232 or RS485 with PiiGAB M-Bus 900.
A separate M-Bus master can also be used and will be regarded as an M-Bus client.
Internal switching function with queue that selects what M-Bus client has access to the M-
Bus meters.
Limitations Half duplex on the M-Bus loop. Not possible to read the M-Bus meters in parallel.
Slow readout time of M-Bus meters. Normally there is about a 1 second readout time (2400
baud). It may vary depending on the baud rate from 0,5 seconds to 10 seconds.
The more M-Bus clients the more each client has to take into consideration that the readout
time will increase. Time = Readout time for one M-Bus meter x Number of clients.
PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]
MBus2Modbus
M-Busmeters
Modbusclient1
Modbusclient2
Modbusclient3
Modbusclient4
Modbusclient
M-Busmeters
Possibilities Allowing any Modbus clients to read the M-Bus meters.
Up to four Modbus clients can read the M-Bus meters independently.
Modbus TCP or Modbus RTU over UDP/IP, TCP/IP, RS232 or RS485.
Modbus function 3 or function 4.
Use the PiiGAB M-Bus Explorer to specify which register corresponds to particular objects in
the M-Bus meters.
Use the Modbus client in PiiGAB M-Bus Setup Wizard to test the MBus2Modbus
configuration.
Limitations Half duplex on M-Bus loop. Not possible to read M-Bus meters in parallel.
Slow readout time of M-Bus meters. Normally there is about a 1 second readout time (2400
baud). It may vary depending on the baud rate from 0,5 seconds to 10 seconds.
The more M-Bus clients the more each client has to take into consideration that the readout
time will increase. Time = Readout time for one M-Bus meter x Number of clients.
Beware of multi-telegram M-Bus meters as they might cause long read-out times.
PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]
MBus2MBusASCII
M-Busmeters
MBusASCIIclient1
MBusASCIIclient2
MBusASCIIclient3
MBusASCIIclient4
MBusASCII client
M-Busmeters
Possibilities Allowing any M-Bus ASCII clients to read the M-Bus meters.
Up to four M-Bus ASCII clients can read the M-Bus meters independently.
Allowing the QuickPost in PiiGAB M-Bus 900 to read the M-Bus meters.
M-Bus ASCII over UDP/IP, TCP/IP, RS232 or RS485.
Use the PiiGAB M-Bus Explorer to specify what objects to read from the M-Bus meters.
Use the M-Bus ASCII client in PiiGAB M-Bus Setup Wizard to test the MBus2MBusASCII
configuration.
M-Bus ASCII is PiiGAB’s open data protocol.
Limitations Half duplex on M-Bus loop. Not possible to read M-Bus meters in parallel.
Slow readout time of M-Bus meters. Normally there is about a 1 second readout time (2400
baud). It may vary depending on the baud rate from 0,5 seconds to 10 seconds.
The more M-Bus clients the more each client has to take into consideration that the readout
time will increase. Time = Readout time for one M-Bus meter x Number of clients.
Beware of multi-telegram M-Bus meters as they might cause long read-out times.
PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]
MBus2Clients
M-Busmeters
M-Busclient
Modbusclient
MBusASCIIclient
Possibilities Allowing M-Bus, M-Bus gateways, Modbus or M-Bus ASCII clients to read the M-Bus meters.
Up to four clients can read the M-Bus meters independently.
Communication over UDP/IP, TCP/IP, RS232, RS485 or as M-Bus slave.
Limitations Half duplex on M-Bus loop. Not possible to read M-Bus meters in parallel.
Slow readout time of M-Bus meters. Normally there is about 1 a second readout time (2400
baud). It may vary depending on the baud rate from 0,5seconds to 10 seconds.
The more M-Bus clients the more each client has to take into consideration that the readout
time will increase. Time = Readout time for one M-Bus meter x Number of clients.
Beware of multi-telegram M-Bus meters as they might cause long read-out times.
PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]
Modbus2MBus
M-Busclient
Modbus RTUmeters/slaves
M-Busmeters
Modbus RTUmeters/slaves
Possibilities Allowing Modbus meters/slaves to be converted to M-Bus.
Extend an M-Bus loop with Modbus meters/slaves.
Modbus RTU over RS485, RS232, UDP/IP or TCP/IP.
Modbus function 3 and function 4.
Virtual M-Bus meters will represent the Modbus meters/slaves.
Use primary or secondary addresses.
Limitations Only Modbus RTU meters/slaves.
PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]
QuickPost (MBus2MBusASCII for FTP- or HttpPost-servers)
FTP-serverHttpPost-server
FTP-serverHttpPost-server
M-Busmeters
WWW
Possibilities Reads M-Bus meters with the MBus2MBusASCII principle.
QuickPost uses an internal MBusASCII client.
Specify when to read the M-Bus meters.
All read-out is stored in files.
Specify a FTP-server or an HttpPost-server as the remote server.
Specify when to send the files to the remote server.
Limitations Half duplex on M-Bus loop. Not possible to read M-Bus meters in parallel.
Slow readout time of M-Bus meters. Normally there is about 1 a second readout time (2400
baud). It may vary depending on the baud rate from 0,5seconds to 10 seconds.
The more M-Bus clients the more each client has to take into consideration that the readout
time will increase. Time = Readout time for one M-Bus meter x Number of clients.
Beware of multi-telegram M-Bus meters as they might cause long read-out times.
PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]
Port forward
Client(M-Bus,Modbus,
MBusASCII)
WWW
Meters(M-Bus,
Modbus)
Possibilities No setup needed for port forward in the PiiGAB M-Bus 900. Setup the port forward in the
router.
Read the M-Bus meters or Modbus meters (Modbus2MBus) from the remote clients.
Up to four remote clients.
Remote access for UDP/IP or TCP/IP.
Limitations Half duplex on M-Bus loop. Not possible to read M-Bus meters in parallel.
Slow readout time of M-Bus meters. Normally there is about 1 a second readout time (2400
baud). It may vary depending on the baud rate from 0,5seconds to 10 seconds.
The more M-Bus clients the more each client has to take into consideration that the readout
time will increase. Time = Readout time for one M-Bus meter x Number of clients.
Beware of multi-telegram M-Bus meters as they might cause long read-out times.
PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]
MBus2OPC - General
OPC client 1
OPC client N
M-Busmeters
M-Busmeters
M-Bus client
OPC-server
Possibilities Read any M-Bus meters with primary or secondary addresses.
Communicate with any M-Bus gateways through UDP/IP, TCP/IP or serial.
Handles both single-telegram and multi-telegram M-Bus meters.
Any OPC-clients may connect to the OPC-server to read the M-Bus meters.
PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]
MBus2OPC – Extended
OPC client 1
OPC client N
M-Busmeters
M-Busmeters
M-Bus client
OPC-server
OPC client 1
OPC client N
M-Bus client
OPC-server
M-Busmeters
Possibilities Use the multiple clients feature in the PiiGAB M-Bus 900 to read the M-Bus meters from
several OPC-servers.
PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]
QuickLoop
DatabaseDatabase
OPC-server A
FTPFTP
OPC-server B
M-Busmeters
M-Bus client
OPC-server
OPC-client
Possibilities Use the internal OPC-client in QuickLoop to read any OPC-server.
Specify how often to read the OPC-tags.
Specify how to export the read OPC-tags.
o Export to text-file.
o Export to XML-file.
o Export to Microsoft SQL-server.
o Export to any SQL-server through an ODBC-connection.
Send exported file to a remote FTP-server.
Limitations Beware of how much time it will take for the OPC-servers to read the OPC-tags. Change the
sample period time accordingly.
PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]
Total solution all inclusive
DatabaseDatabase FTPFTP
OPC client 1
cPC client n
Modbus RTUmeters/slaves
M-Busmeters
Modbusclient
M-Busclient
FTP-serverHttpPost-server
FTP-serverHttpPost-server
WWW
Read M-Bus meters
Modbus meters/slaves
Read M-Bus meters from M-Bus-clients
PiiGAB M-Bus Explorer / M-Bus OPC-server
Modbus TCP or Modbus RTU clients
MBusASCII clients, to use the QuickPost application
Convert Modbus meters/slaves to Read the Modbus meters as virtual M-Bus meters with the Modbsu2MBus application.
The virtual M-Bus meters can be used as normal M-Bus meters.
PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]
Contacts
PiiGAB Processinformation Anders Carlssons gata 7
417 55 Göteborg Sweden
Phone + 46 31 55 99 77
www.piigab.com
Distributors Please contact our distributors in respective countries:
Germany Relay GmbH Stettiner Str. 38 33106 Paderborn Germany Phone +49 5251 17670 www.relay.de
Norway Autic Systems AS Stoltenbergs gate 48 3110 Tønsberg Norway Phone +47 33 30 09 50 www.autic.no
Czech Republic Papouch s.r.o. Strasnicka 3164/1a 102 00 PRAGUE 10 Czech Republic Phone +420 267 314 267 www.papouch.com