TURBINE PROTECTIONS
LUB OIL PRESSURE LOW
HIGH AXIAL SHIFT
LOW VACUUM
HP EXHAUST TEMP HIGH
HPC TOP-BOTTOM DIFF TEMP HIGH
IPC FRONT TOP-BOTTOM DIFF TEMP HIGH
IPC REAR TOP-BOTTOM DIFF TEMP HIGH
FIRE PROTECTION
MFT
ATRS TRIP
GENERATOR TRIP LEADING TO TURBINE TRIP
TURBINE PROTECTIONS
LIQUID MAIN LEADS TOP HIGH
COLD GAS COOLERS TEMP A&B HIGH
COLD GAS COOLERS TEMP C&D HIGH
SEAL OIL TEMP AFTER COOLER AIR SIDE HIGH
HOT AIR MAIN EXCITER TEMP HIGH
PRIMARY WATER TEMP AFTER COOLER HIGH
STATOR WINDING FLOW LOW
MAIN BUSHING R FLOW LOW
MAIN BUSHING S FLOW LOW
MAIN BUSHING T FLOW LOW
-
8/18/2019 Turbine-Protections.pdf
3/8
3
ELECTRICAL
TRIP
CONDITIONS
ELECTRICAL
TRIP
CONDITIONS
TRIP
RELAY 1
TRIP
RELAY 1
TRIP
SOLENOID 1
TRIP
SOLENOID 2
TURBINE
TRIP VALVE
STOP
VALVE
HYDRAULIC
TRIPDEVICES
-
8/18/2019 Turbine-Protections.pdf
4/8
4
ABSOLUTE EXPANSION
RELATIVE EXPANSION
RELATIVE SHAFT VIBRATION
ABSOLUTE BRG VIBRATION
ABSOLUTE EXPANSION
AXIAL SHAFT POSITION
RELATIVE SHAFT VIBRATION
ABSOLUTE BRG VIBRATION
RELATIVE
EXPANSION
ECCENTRICITY
ABSOLUTE BRG
VIBRATION
RELATIVE EXPANSION
RELATIVE SHAFT VIBRATION
ABSOLUTE BRG VIBRATION
TURBINE PROTECTIONS
• Two trip solenoids are provided in the hydraulic
circuit, which get trip signals from the electrical
system. Actuation of any one solenoid is sufficient
to trip the turbine.
• The electrical system is configured as a 2-channel
system. Each channel is realized in a Processing
Unit
• Both the processor units are completely
independent of each other and input modules,
processor module and output modules reside on
each.
-
8/18/2019 Turbine-Protections.pdf
5/8
5
TURBINE PROTECTIONS
Each channel having two processors Unit
with one processor in hot standby mode .
Realisation of 2 out of 3 trip logic is carried
out in the processor.
Both the channels are tested periodically evenwhile the turbine is running. Cyclic testing is
done automatically at preset intervals
CONDENSER PRESSURE
PROTECTION
Two types of condenser pressure protection ,
one with fixed set point (FSP) and one with
variable set point (VSP), are provided.
The task of condenser pressure protection isto protect the condenser against a non
permissible pressure increase and the
deterioration of vacuum.
Trip circuit is enabled only, if the turbine
speed is more than 240 RPM.
-
8/18/2019 Turbine-Protections.pdf
6/8
-
8/18/2019 Turbine-Protections.pdf
7/8
7
ISOLATION OF GENERATOR FROM GRID
Turbine has tripped and reverse power relay
has operated. The command signal shall be
initiated with a delay of 3 Seconds
Reverse power relay has operated. The
command signal shall be initiated with a time
delay of 10 seconds.
GOVERNING RACK
-
8/18/2019 Turbine-Protections.pdf
8/8
8
GOVERNING RACK