    TURBINE PROTECTIONS

    LUB OIL PRESSURE LOW

    HIGH AXIAL SHIFT

    LOW VACUUM

    HP EXHAUST TEMP HIGH

    HPC TOP-BOTTOM DIFF TEMP HIGH

    IPC FRONT TOP-BOTTOM DIFF TEMP HIGH

    IPC REAR TOP-BOTTOM DIFF TEMP HIGH

    FIRE PROTECTION

    MFT

    ATRS TRIP

    GENERATOR TRIP LEADING TO TURBINE TRIP

    TURBINE PROTECTIONS

    LIQUID MAIN LEADS TOP HIGH

    COLD GAS COOLERS TEMP A&B HIGH

    COLD GAS COOLERS TEMP C&D HIGH

    SEAL OIL TEMP AFTER COOLER AIR SIDE HIGH

    HOT AIR MAIN EXCITER TEMP HIGH

    PRIMARY WATER TEMP AFTER COOLER HIGH

    STATOR WINDING FLOW LOW

    MAIN BUSHING R FLOW LOW

    MAIN BUSHING S FLOW LOW

    MAIN BUSHING T FLOW LOW

  • 8/18/2019 Turbine-Protections.pdf

    3/8

    3

    ELECTRICAL

    TRIP

    CONDITIONS

    ELECTRICAL

    TRIP

    CONDITIONS

    TRIP

    RELAY 1

    TRIP

    RELAY 1

    TRIP

    SOLENOID 1

    TRIP

    SOLENOID 2

    TURBINE

    TRIP VALVE

    STOP

    VALVE

    HYDRAULIC

    TRIPDEVICES

  • 8/18/2019 Turbine-Protections.pdf

    4/8

    4

    ABSOLUTE EXPANSION

    RELATIVE EXPANSION

    RELATIVE SHAFT VIBRATION

    ABSOLUTE BRG VIBRATION

    ABSOLUTE EXPANSION

    AXIAL SHAFT POSITION

    RELATIVE SHAFT VIBRATION

    ABSOLUTE BRG VIBRATION

    RELATIVE

    EXPANSION

    ECCENTRICITY

    ABSOLUTE BRG

    VIBRATION

    RELATIVE EXPANSION

    RELATIVE SHAFT VIBRATION

    ABSOLUTE BRG VIBRATION

    TURBINE PROTECTIONS

    • Two trip solenoids are provided in the hydraulic

    circuit, which get trip signals from the electrical

    system. Actuation of any one solenoid is sufficient

    to trip the turbine.

    • The electrical system is configured as a 2-channel

    system. Each channel is realized in a Processing

    Unit

    • Both the processor units are completely

    independent of each other and input modules,

    processor module and output modules reside on

    each.

  • 8/18/2019 Turbine-Protections.pdf

    5/8

    5

    TURBINE PROTECTIONS

    Each channel having two processors Unit

    with one processor in hot standby mode .

    Realisation of 2 out of 3 trip logic is carried

    out in the processor.

    Both the channels are tested periodically evenwhile the turbine is running. Cyclic testing is

    done automatically at preset intervals

    CONDENSER PRESSURE

    PROTECTION

    Two types of condenser pressure protection ,

    one with fixed set point (FSP) and one with

    variable set point (VSP), are provided.

    The task of condenser pressure protection isto protect the condenser against a non

    permissible pressure increase and the

    deterioration of vacuum.

    Trip circuit is enabled only, if the turbine

    speed is more than 240 RPM.

  • 8/18/2019 Turbine-Protections.pdf

    6/8

  • 8/18/2019 Turbine-Protections.pdf

    7/8

    7

    ISOLATION OF GENERATOR FROM GRID

    Turbine has tripped and reverse power relay

    has operated. The command signal shall be

    initiated with a delay of 3 Seconds

    Reverse power relay has operated. The

    command signal shall be initiated with a time

    delay of 10 seconds.