Turn-to-Turn Fault Detection in

Transformers Using Negative

Sequence Currents

Mariya Babiy1, Rama Gokaraju1, Juan Carlos Garcia2

1University of Saskatchewan, Saskatoon, Canada 2Manitoba HVDC Research Centre, Winnipeg, Canada

Page 2: Turn-to-Turn Fault Detection in Transformers Using · PDF fileTurn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents! Mariya Babiy1, Rama Gokaraju1, Juan Carlos

2

Outline

  Traditional Differential Relay

  Proposed Differential Relay Using Negative Sequence

Currents

  Results

  Conclusions

Page 3: Turn-to-Turn Fault Detection in Transformers Using · PDF fileTurn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents! Mariya Babiy1, Rama Gokaraju1, Juan Carlos

Drawback of the differential relay - low sensitivity

Figure 1 – Percentage Differential Relay of the Transformer

3

Traditional Differential Relay

Internal fault

External fault

I1

i1

I2

i2

Page 4: Turn-to-Turn Fault Detection in Transformers Using · PDF fileTurn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents! Mariya Babiy1, Rama Gokaraju1, Juan Carlos

4

  Difficult to detect low-level turn-to-turn faults.

  Change in transformers terminal current is quite small.

  IEEE C37.91-2000 indicates that ~10% of the transformer

winding has to be shorted to cause a detectable change in

terminal current.

  Restraint characteristics usually set to about 20%.

Traditional Percentage Differential

Page 5: Turn-to-Turn Fault Detection in Transformers Using · PDF fileTurn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents! Mariya Babiy1, Rama Gokaraju1, Juan Carlos

5 Fig.2 Traditional Differential Relay – Differential and restraining current for various

percentages of shorted turns.

10% of turns are shorted

3% of turns are shorted

Page 6: Turn-to-Turn Fault Detection in Transformers Using · PDF fileTurn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents! Mariya Babiy1, Rama Gokaraju1, Juan Carlos

Other Differential Relaying Schemes

  Sudden Pressure Relays are slow to operate (50-100ms).

  Sachdev, Sidhu (1989) used electromagnetic equations during internal

faults (accurate for shorted turns > 5%).

  Gajic et. al from ABB in (2005) presented negative sequence current

differential concept .

  Crossley (2004) presented a technique based on increments of flux

linkages (accurate for shorted turns > 10%).

  Wavelet transforms (Kunakorn, 2006) & ANN (Li, 2007). 6

Page 7: Turn-to-Turn Fault Detection in Transformers Using · PDF fileTurn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents! Mariya Babiy1, Rama Gokaraju1, Juan Carlos

Negative Sequence Current Scheme

  Compared to zero sequence currents, negative sequence current differential provides coverage for phase faults as well as for ground faults.

  Two stages of comparison:   Negative sequence magnitudes compared with a pre-set level of 1%.   Directional Comparison: <[0-5 degrees] then it is an internal fault. If it

is 180 degrees then it is an external fault.   For Δ-Y and Y-Δ the appropriate 30 degree phase shifts could be taken

into account.

7

Page 8: Turn-to-Turn Fault Detection in Transformers Using · PDF fileTurn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents! Mariya Babiy1, Rama Gokaraju1, Juan Carlos

8

Primary currents Ia1, Ib1, Ic1

Secondary currents Ia2, Ib2, Ic2

Neg. seq. current INS_P

FFT

Neg. seq. current INS_S

FFT

Relay Logic

INS_P > Imin No

Yes INS_S > I min

No

Yes

If phase shift ≈ [0 – 50 ]

Block

Yes

No

Trip Figure 3. Negative sequence current based logic

Page 9: Turn-to-Turn Fault Detection in Transformers Using · PDF fileTurn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents! Mariya Babiy1, Rama Gokaraju1, Juan Carlos

9 Figure 4. Direction of negative sequence currents during faults

Page 10: Turn-to-Turn Fault Detection in Transformers Using · PDF fileTurn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents! Mariya Babiy1, Rama Gokaraju1, Juan Carlos

10

Simulation Results

  Simulation model developed in PSCAD/EMTDC.

  Three-phase transformer bank constructed using three

single phase transformer banks (each 33.3 MVA, 23/132

kV). Mutual coupling taken into account.

  Number of turns on primary: 150. Number of turns on

secondary: 866.

  Accurate values of leakage reactance were obtained for

different shorted turns.

Page 11: Turn-to-Turn Fault Detection in Transformers Using · PDF fileTurn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents! Mariya Babiy1, Rama Gokaraju1, Juan Carlos

11

Figure 5. Negative sequence current magnitudes for various percentages of shorted turns on primary winding (Y-Y).

10% of turns are shorted

1% of turns are shorted

Page 12: Turn-to-Turn Fault Detection in Transformers Using · PDF fileTurn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents! Mariya Babiy1, Rama Gokaraju1, Juan Carlos

12 12

Figure 7. Phase angle comparison between two negative sequence currents for various percentages of shorted turns on primary winding (Y-Y).

10% of turns are shorted

1% of turns are shorted

Page 13: Turn-to-Turn Fault Detection in Transformers Using · PDF fileTurn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents! Mariya Babiy1, Rama Gokaraju1, Juan Carlos

13 13

Figure 8. Response of the proposed scheme during an external B-to-ground fault on the secondary side (Y-Y).

Negative sequence current magnitudes

Phase angle between two phasors of negative sequence currents

Page 14: Turn-to-Turn Fault Detection in Transformers Using · PDF fileTurn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents! Mariya Babiy1, Rama Gokaraju1, Juan Carlos

14

Time, s

Mag

nitu

de,

A

INS_S INS_P Pre-set level

Figure 9. Negative sequence current magnitudes for 3% shorted turns on secondary (Δ-Y)

Page 15: Turn-to-Turn Fault Detection in Transformers Using · PDF fileTurn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents! Mariya Babiy1, Rama Gokaraju1, Juan Carlos

15

Deg

rees

Time, s

INS_P_ph

INS_S_ph

300

Figure 10. Phase angle comparison between two negative sequence currents for 3% shorted turns on secondary (Δ-Y) with 30º phase shift

Deg

rees

INS_S_ph

INS_P_ph

Time, s

Page 16: Turn-to-Turn Fault Detection in Transformers Using · PDF fileTurn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents! Mariya Babiy1, Rama Gokaraju1, Juan Carlos

16

Phase   Load Amps  

A   4.1759  

B   4.5976  

C   4.3906  

Table 5.7 – Phase currents due to a small unbalance

Mag

nitu

de,

A

Time, s

INS_P and INS_S during the small unbalance

Pre-set level

Figure 12. Negative sequence current magnitudes due to a small unbalance in the power system

Page 17: Turn-to-Turn Fault Detection in Transformers Using · PDF fileTurn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents! Mariya Babiy1, Rama Gokaraju1, Juan Carlos

17

Deg

rees

Time, s

INS_S_ph

INS_P_ph

Figure 13. Phase angle between two phasors of negative sequence currents during a small unbalance in the power system

Trip

Sig

nal

Time, s

Figure 14. Output signal from the proposed technique for a small unbalance in the power system

Page 18: Turn-to-Turn Fault Detection in Transformers Using · PDF fileTurn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents! Mariya Babiy1, Rama Gokaraju1, Juan Carlos

18

Mag

nitu

de,

A

Time, s

INS_P

INS_S

Figure 15. Negative sequence currents magnitudes during inrush current

Deg

rees

Time, s

INS_S_ph

INS_S_ph

Figure 16. Phase angle between two phasors of negative sequence currents during inrush current

Page 19: Turn-to-Turn Fault Detection in Transformers Using · PDF fileTurn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents! Mariya Babiy1, Rama Gokaraju1, Juan Carlos

•  Simple to implement (uses standard sequence current logic).

•  successfully detects turn-to-turn fault even when small number of turns are shorted ( 1-2%).

•  accurately discriminates between internal and external faults.

•  detection time approximately 12 ms. •  Tested for various operating conditions, inrush

currents, unbalanced operation. •  does not require any extra customization compared to

the traditional differential relay. 19

Conclusions