Page 1: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management
Page 2: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

Two Phase Rack Leve l L iqu id Coo l ing So lut ionLentis Pai/Associate Director/Wiwynn

Page 3: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

A g e n d a

• Existing Chassis Level Solution

• Wiwynn Two Phase Immersion Cooling

• Rack Level Liquid Cooling Solution Overview

• Investigation of Single Phase & Two Phase

• Advantage

• Next Investigation

• Schedule

Page 4: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

E x i s t i n g C h a s s i s L e v e l S o l u t i o n

Enhanced Volume Air Cooling

Water Assisted Air Cooling

Loop Heat Pipe

Flexible Solution

Patent

Air

Air

Water + Air

Thermosiphon

Air

Page 5: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

W i w y n n T w o P h a s e I m m e r s i o n C o o l i n g

Two Phase Immersion CoolingBoard Matrix in Tank• 48Vdc

• High Power Efficiency

• High Capacity Usage

• POC Project

• White Paper

Sled

~February 2018

POC Design

April 2018

POC Prototyping

May 2018

POC Test

POC Schedule

Boiling 48Vdc

Page 6: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

Chassis

Level

Immersion

Cooling

• High Power ASICs are in demand with

limited space

• Water leakage is concerned in rack

• Power dissipating ability is enhanced

with data center facility change

C u r r e n t L i m i t a t i o n

Water

Cooling

Page 7: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

Chassis Level

C omplementary So lu t ion

Rack Level

Limited SpaceMore Space

Fan Wall

Page 8: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

Water Cooling

C omplementary So lu t ion

Dielectric Fluid

Water Leakage

Freeze

Corrosion

Minimum Risk

Page 9: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

Immersion Cooling

C omplementary So lu t ion

Two Phase Liquid

Assisted Air Cooling

Facility &

Serviceability

Change

High Heat Transfer

No Change

Page 10: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

C o m p l e m e n t a r y S o l u t i o n

Two Phase Liquid Assisted Rack Level Air Cooling

High heat transfer ability of latent heat of vaporization

Dielectric fluid with minimum leakage concern

More space

No data center facility change

Advantages drive us to investigate

Page 11: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

A g e n d a

• Existing Chassis Level Solution

• Wiwynn Two Phase Immersion Cooling

• Rack Level Liquid Cooling Solution Overview

• Investigation of Single Phase & Two Phase

• Advantage

• Next Investigation

• Schedule

Page 12: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

R a c k L e v e l L i q u i d C o o l i n g O v e r v i e w

Heat

Source

Heat

Source

Coolant In

DIMM

DIMMDIMMDIMM

DIMM

DIMMDIMMDIMM

DIMM

DIMMDIMMDIMM

DIMM

DIMMDIMMDIMM

Coolant Out

Pump

RDHx(with Fan)

System Rack

Fan WallPUMP

Systems

RDHx with Fan(Rear door heat exchanger)

Radiator

Working Fluid

Dielectric Liquid (3M Engineering Fluid)

Page 13: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

Invest igat ion of S ingle Phase and Two Phase

Dielectric Fluid(3M Engineering Fluid)

Single Phase

Two Phase

Cooling Power Optimization

Water vs. Dielectric Fluid

Low Liquid Flow Rate

Uniform Temperature

Flow Management

Page 14: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

L i q u i d C o o l i n g L o o p ( S i n g l e P h a s e )

Pump

Heat, WHot ASIC

COLD

LIQUID

HOT

LIQUID

RDHx(with Fan)

TinQL

QA

Cold Plate

Page 15: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

Optimize QA and QL by cooling power perspective

QL QA

QLQA

Tin

Tin

Keep a target ASIC temperaturePump

Cold Plate

Heat, WHot ASIC

COLD

LIQUID

HOT

LIQUID

RDHx(with Fan)

Cold PlateTinQL

QA

I n v e s t i g a t i o n – C o o l i n g P o w e r O p t i m i z a t i o n

TinQA Power

QL Power

Page 16: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

0

3

6

9

12

15

0

5

10

15

20

25

30

35

40

45

50

36 39 42 45 48 51 54

Tin: Cold Liquid Temperature (oC)

Fa

n P

ow

er

Liq

uid

Pu

mp

Po

wer

Tin with minimum cooling power

Condition: 250W Heat source at 25oC ambient temperature, target heat source case temperature = 55oC

QA0

QL0

QA1

QL1

QA2

QL2

QA3

QL3

QA4

QL4

I n v e s t i g a t i o n – C o o l i n g P o w e r O p t i m i z a t i o n ( E x p e r i m e n t )

Page 17: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

L i q u i d C o o l i n g L o o p ( T w o P h a s e )

BoilingPump

Cold Plate

Heat, WHot ASIC

LIQUIDLIQUID with

VAPOR BUBBLE

RDHx(with Fan)

Cold PlateQL

QA

Tb

≈Tb

Tb: Boiling Temperature

Liquid with

vapor bubble

Page 18: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

Fluid PhaseHeat Source

Power

Liquid Flow

Rate

Air Flow

Rate

Heat Source Case

Temperature

Water Single Phase 400W 0.3 L/min 26CFM

Dielectric Fluid

(3M, FC-72)Two Phase 400W 0.3 L/min 26CFM

Liquid boiling point=56oC

I n v e s t i g a t i o n – D i e l e c t r i c F l u i d v s W a t e r

68.2

63.5

Page 19: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

0.00.30.60.91.21.51.8

80

70

60

50

40

30

20

10

0

16

14

12

10

8

6

4

2

0

Heat

So

urc

e C

ase

Tem

pera

ture

(oC

)

Liq

uid

Pu

mp

Po

wer (W

)

Liquid Flow Rate (L/min)

Single Phase

Liquid with vapor

Heat Source Temperature

Low Liquid Flow Requirement

Two Phase

Boiling

Liquid boiling point=56oC

I n v e s t i g a t i o n – L o w L i q u i d F l o w R a t e

Smaller Pump/ Low-cost Pump

Page 20: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

ASIC 1< ASIC 2

Water (Single Phase)Water

(Single Phase)

More Uniform Temperature

ASIC 1 ASIC 2Dielectric Fluid (Two Phase)

Dielectric Fluid

(Two Phase)

I n v e s t i g a t i o n – U n i f o r m T e m p e r a t u r e

RDHx(with Fan)

ASIC 1 ASIC 2

Hot LiquidCold Liquid

Warm Hot

RDHx(with Fan)

Tb~Tb

~Tb Tb TbASIC 1 ASIC 2

Liquid + VaporLiquid

Warm Warm

Page 21: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

R a c k F l o w M a n a g e m e n t

System 1

System 2

System 3

High Workload

High Workload

Low Workload

Low Workload

QA1

QA1

QA2

QA2

Idle

System 5

System 4

QA3

Pump

RDHx(with Fan)

Rack

Page 22: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

Valve

200W

100W

High Workload

Low Workload

PumpRDHx(with Fan)

200W

100W

High Workload

Low Workload

RDHx(with Fan)

Valve

100% Open

50% OpenSingle Phase

Two Phase Two Phase

Two Phase

Case = 64.2 oC

Case = 54.9 oC

Case = 61.0 oC

Case = 61.0 oC

I n v e s t i g a t i o n – F l o w M a n a g e m e n t

Pump

Rack Flow Management

Page 23: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

A g e n d a

• Existing Chassis Level Solution

• Wiwynn Two Phase Immersion Cooling

• Rack Level Liquid Cooling Solution Overview

• Investigation of Single Phase & Two Phase

• Advantage

• Next Investigation

• Schedule

Page 24: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

A d v a n t a g e

Two Phase Rack Level

Liquid Cooling

Minimum

Leakage Concern

No

Facility Change

High

Heat Transfer

Uniform

Temperature

Page 25: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

I n v e s t i g a t i o n s

Two Phase Cold Plate Boiling Enhancement

Cost ReductionCommercialization

Pressure ControlLow Loop Pressure

Blind Mate TubeEasy Connection

Flow ManagementEfficiency Optimization

Page 26: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

F l e x i b l e H e a t T r a n s f e r

AirRear Door

Heat Exchanger

(RDHx)

Liquid Fan

Wall

Facility

Liquid Loop

LiquidLiquidHeat Exchanger

Page 27: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

High

Low

Immersion Cooling

Rack Level

Two Phase

Dielectric Fluid

Chassis Level Solution

Data Center Facility Change

Serviceability Change

Limited Space

Same Facility

Same Serviceability

Minimum Risk of Leakage

C o n c l u s i o n

WiwynnTwo Phase Rack Level

Liquid Cool ing Solution

Page 28: Two Phase Rack Level - Open Compute Project · 2018-05-29 · Two Phase Two Phase Two Phase Case = 64.2 oC Case = 54.9 oC Case = 61.0 oC Case = 61.0 oC Investigation –Flow Management

S c h e d u l e

Q2 2018

White Paper Publishing

~Q3 2018

Rack Prototyping