UEW5 series intelligent air circuit breaker UEW5 series intelligent air circuit breakers are applicable to the power distribution circuit under the condition of AC50Hz/60Hz, rated working voltage 400V or 690V, rated current 6306300A, and take the role of distributing power and protecting wires and equipments from being damaged by overload, under-voltage, short circuit and ground fault etc. The breakers with rated current below 1000A can also be used for the infrequent motor starting-up. The circuit breaker, with intelligent protection function, precise selective protection, can improve reliability and safety and avoid unnecessary power failure. UEW5- Rated frame current Number of poles Rated current Intelligent controller Installation method See Tablet 1 See Table 2 3P/4P See Table 2 L/M/H Table 1 Installation under voltage release Shunt release Pick up Auxiliar y switch Opening lock Mechanical interlock Frame draw-out AC380V,220V AC380V,220V AC380V,220V 4NO 4NC one lock one key horizontal interlock draw-out fixed instantaneous delay 1s,3s,5s DC220V,110V DC220V,110V 4NO 4NC 3 locks 2 keys mechanical interlock fixed 2000/ 4- 1250- M- Drawer type Accessories AC400V,230V, DC220V,110V

Upload: trantuyen

Post on 06-Jul-2018

280 views

Category:

Documents


14 download

TRANSCRIPT

UEW5 series intelligent air circuit breaker UEW5 series intelligent air circuit breakers are applicable to the power distribution circuit under

the condition of AC50Hz/60Hz, rated working voltage 400V or 690V, rated current 630~6300A,

and take the role of distributing power and protecting wires and equipments from being damaged by

overload, under-voltage, short circuit and ground fault etc. The breakers with rated current below

1000A can also be used for the infrequent motor starting-up. The circuit breaker, with intelligent

protection function, precise selective protection, can improve reliability and safety and avoid

unnecessary power failure.

UEW5-

Rated frame current Number of poles Rated current Intelligent controller Installation method See Tablet 1

See Table 2 3P/4P See Table 2 L/M/H Table 1

Installation under voltage release Shunt release Pick up Auxiliary switch

Opening lock

Mechanical interlock

Frame

draw-out AC380V,220V AC380V,220V AC380V,220V4NO 4NC

one lock one key

horizontal interlock

draw-out

fixed instantaneous delay

1s,3s,5s DC220V,110V DC220V,110V

4NO 4NC

3 locks 2 keys

mechanical interlock

fixed

2000/ 4- 1250- M- Drawer type Accessories

AC400V,230V, DC220V,110V

Main specification Table 2

Type UEW5-2000 Rated frame current Inm(A) 2000 Rated current In(A) 630 800 1000 1250 1600 2000 Rated working voltage Ue(V) AC400/AC690 Rated insulation voltage Ui(V) AC690 Number of poles 3、4 3、4 3、4 3、4 3、4 3、4 Rated current of N pole IN(A) 50%或 100% In

AC400V 80 80 80 80 80 80 Rated ultimate short-circuit breaking capacity Icu(kA) (effective value) AC690V 50 50 50 50 50 50

AC400V 50 50 50 50 50 50 Rated service short-circuit breaking capacity Ics(kA) (effective value) AC690V 50 50 50 50 50 50

AC400V 176 176 176 176 176 176 Rated short circuit making capacity Icm(kA) (peak value) AC690V 105 105 105 105 105 105

AC400V 50 50 50 50 50 50 Rated short time withstand current (1s)Icw(kA) (effective value) AC690V 40 40 40 40 40 40 Full breaking time (without additional delay) (ms) 25~30 Closing time(ms) 70 at maximum

Basic ○ ○ ○ ○ ○ ○

Multi-functional ○ ○ ○ ○ ○ ○ Intelligent controller Communication ○ ○ ○ ○ ○ ○

Dielectric performance 50Hz AC 2500V 1min AC400V 500 500 500 500 500 500 Electrical life AC690V 500 500 500 500 500 500 Non-maintenance 9500 9500 9500 9500 9500 9500

Operational performance Mechanical life

Maintenance 20000 20000 20000 20000 20000 20000

Connection pattern horizontal vertical

horizontal vertical

horizontal vertical

horizontal vertical

horizontal vertical

horizontal vertical

Draw-out ○ ○ ○ ○ ○ ○ Pattern Fixed ○ ○ ○ ○ ○ ○

Draw-out 3P 395x362x323 Draw-out 4P 395x457x323 Fixed 3P 433x375x420

Externality dimensions

HxWxL(mm) Fixed 4P 433x470x420

Main specification Table 2

UEW5-3200 UEW5-4000 UEW5-6300 3200 4000 6300

2000 2500 2900 3200 3200 3600 4000 4000 5000 6300 AC400/AC690

AC690 3、4 3、4 3、4 3、4 3、4 3、4 3、4 3、4 3、4 3、4

50%或 100% In 100 100 100 100 100/110 100/110 100/110 120 120 120 65 65 65 65 75 75 75 75 75 75 80 80 80 80 80/85 80/85 80/85 100 100 100 65 65 65 65 65 65 65 65 65 65 220 220 220 220 220/242 220/242 220/242 264 264 264 143 143 143 143 165 165 165 165 165 165 80 80 80 80 80/85 80/85 80/85 100 100 100 50 50 50 50 65 65 65 65 65 65

25~30 70 at maximum

○ ○ ○ ○ ○ ○ ○ ○ ○ ○

○ ○ ○ ○ ○ ○ ○ ○ ○ ○

○ ○ ○ ○ ○ ○ ○ ○ ○ ○

AC 2500V 1min 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500

4500 4500 4500 4500 4500 4500 4500 2500 2500 2500 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000

horizontal vertical

horizontal vertical

horizontal vertical

horizontal vertical horizontal horizontal horizontal horizontal horizontal horizontal

○ ○ ○ ○ ○ ○ ○ ○ ○ ○

○ ○ ○ ○

395x422x323 395x544x323 433x435x420 433x550x486 433x928x486 433x550x420 433x788x486 433x1043x486

UEM5 series molded case circuit breaker UEM5 Series Molded Case Circuit Breakers (MCCB for short) are

applicable to the electrical network under the condition of AC50Hz/60Hz,

rated working current 10A - 800A, rated insulation voltage 690V and rated

working voltage 400V or below with overload, short-circuit and

under-voltage protection performances, and can be used to protect the wires

and equipment from damage. Normally, the circuit breakers also take the

role of infrequent turn-on or turn-off and infrequent motor starting-up.

The circuit breakers are of characteristics of compact structure, small size and high breaking

capacity, which can be equipped with the accessories such as under-voltage release, shunt release,

auxiliary contact, alarm contact, motor-driven operation mechanism, turning operation handle and

etc.

This series of circuit breakers have a disconnecting function and the corresponding symbol is shown

as “ ”.

UEM5-

Installation pattern code

No code: wiring in front of the

board

H: wiring on back of the board

R: wiring by insertion

Number of poles

3: three poles

4: four poles

Rated Frame Current

Inm=63

Inm=100

Inm=225

Inm=400

Inm=800

Operation Pattern

No code: direct operation

P: motor-driven

Z: turning handle Application code

No code: for power

distribution protection

2: for motor protection

Short circuit breakers capacity

L: typical

M: second high breaking type

Rated current Code for release pattern and

internal accessories

Refer to the release pattern

and internal accessories

codes in detail

The N-pole of the four-pole

Refer to the release pattern

and internal accessories codes

in detail

100 M P / 80 3 300 2 A H

Main specification

Type Rated

current(A)

Pole

number

Rated

insulation

voltage Ui

(V)

Rated

working

voltage

Ue(V)

Rated ultimate/

service short-circuit

breaking capacity

Icu / Ics (kA)

Wiring in front

of board

Installation

dimension(mm)

UEM5-63L 10,16,20,25,

32,40,50,63 3/4 AC500 35/20

X Y

25 111

UEM5-100L 3 35/22

UEM5-100M

10,16,20,25,

32,40,50,63 3/4 50/35

X Y

25 132

UEM5-225L 3 35/25

UEM5-225M

100,125,140,

160 3/4 50/35

X Y

35 126

UEM5-225L 3 35/25

UEM5-225M 180,200,225

3/4 50/35

X Y

35 126

UEM5-400L 3 50/42

UEM5-400M

225,250,315,

350,400 3/4 65/50

X Y

44 194

UEM5-800L 3 50/50

UEM5-800M 400,500,630

3/4 65/50

X Y

70 243

UEM5-800L 3 50/50

UEM5-800M 700,800

3/4

AC690

AC400

65/50

X Y

70 243

UEM5L series molded case circuit breakers with residual current protection UEM5L Series molded case circuit breakers with residual current

protection (circuit breakers for short below) are applicable to the electrical

network under the condition of AC50Hz/60Hz, rated working current

16A~800A, rated insulation voltage 690V and rated working voltage 400V

or below, which can be used to protect human body and equipment from

electric shock and residual current, as well as to prevent from fire danger

due to earth-fault current caused by equipment insulation damage.

Normally, the circuit breakers also take the role of infrequent turn-on or turn-off and infrequent

motor starting-up.

The circuit breakers are of characteristics of compact structure, small size and high breaking

capacity, which can be equipped with the accessories such as under-voltage release, shunt release,

auxiliary contact, alarm contact, motor-driven operation mechanism, turning operation handle, etc.

This series of circuit breakers have a disconnecting function and the corresponding symbol is shown

as “ ”.

residual current circuit breakers

UEM5

Number of poles

3: three poles

4: four poles

Rated Frame Current

Inm=100

Inm=225

Inm=400

Inm=800

Operation Pattern

No code: direct operation

P: motor-driven

Z: turning handle

Installation pattern code

No code: wiring in front

of the board

H: wiring on back of the

board

R: wiring by insertion

Application code

No code: for power

distribution protection

2: for motor protection

Short circuit breaking capacity

L: typical

M: related high breaking type

Rated

current

Code for release pattern and internal

accessories

Refer to the release pattern and

internal accessories codes in detail

The N-pole of the four-pole

Refer to the release pattern

and internal accessories

codes in detail

L - 100 L P / 80 3 300 2 A H

Main specification

Type Rated

current(A)

Pole

number

Rated

insulatio

n voltage

Ui(V)

Rated

working

voltage

Ue(V)

Rated

residual

operating

current I n△

(mA)

Delay

time (s)

Rated ultimate/

service

short-circuit

breaking capacity

Icu / Ics (kA)

UEM5L-100L 3 35/22

UEM5L-100M

16,20,25,

32,40,50,

63,80,100 3/4 50/35

UEM5L-160L 3 35/25

UEM5L-160M

100,125,

140,160 3/4 50/35

UEM5L-225L 3 35/25

UEM5L-225M

180,200,22

5 3/4

30/100/300

adjustable

Non-time

delay/

0.1/0.3

adjustable

50/35

UEM5L-400L 3 50/42

UEM5L-400M

225,250,31

5,

350,400 3/4

100/300/500

adjustable

Non-time

delay

0.2/0.5

adjustable

65/50

UEM5L-630L 3 50/50

UEM5L-630M

400,500,63

0 3/4 65/50

UEM5L-800L 3 50/50

UEM5L-800M

630,700,80

0 3/4

AC690 AC400

300/500/1000

adjustable

Non-time

delay

0.5/1

adjustable 65/50

Remark: 3-pole units with residual current protection will be a special standard

UEM5Z1 series electronic molded case circuit breakers UEM5Z1 series electronic molded case circuit breakers (circuit breakers for short

below) are applicable to the electrical network under the condition of

AC50Hz/60Hz, rated working current 800A, rated insulation voltage 690V and

rated working voltage 400V or below, with overload long-delay definite time,

instantaneous short-circuit and under-voltage protection functions. Normally, the

circuit breakers also take the role of infrequent turn-on or turn-off and infrequent

motor starting-up.

The circuit breakers are of characteristics of compact structure, small size and high breaking

capacity, which can be equipped with the accessories such as under-voltage release, shunt release,

auxiliary contact, alarm contact, motor-driven operation mechanism, turning operation handle, etc.

This series of circuit breakers have a disconnecting function and the corresponding symbol is shown

as“ ”

intelligent over-current tripper (withour residual proction)

UEM5

Number of poles

3: three poles

4: four poles

Rated Frame Current

Inm=100

Inm=225

Inm=400

Inm=800

Operation Pattern

No code: direct operation

P: motor-driven

Z: turning handle

Installation pattern code

No code: wiring in front of

the board

H: wiring on back of the

board

R: wiring by insertion

Application code

No code: for power

distribution protection

2: for motor protection

Short circuit breaking capacity

L: typical

M: Related high breaking capacity type

Rated

current

Code for release pattern and internal

accessories

Refer to the release pattern and

internal accessories codes in detail

The N-pole of the four-pole

Refer to the release pattern

and internal accessories codes

in detail

Z1 - 100 L P / 80 3 300 2 A H

Main specification

Type

Rated

current

(A)

Setting

current

Ir1 (A)

Pole

number

Rated

insulation

voltage Ui

(V)

Rated

working

voltage

Ue(V)

Rated ultimate/

service

short-circuit

breaking capacity

Icu / Ics (kA)

Wiring in front

of board

Installation

dimension

UEM5Z1-100L 3 35/22

UEM5Z1-100M 32,100

10~32A

adjustable

40~100A

adjustable

3/4 50/35

X Y

30 132

UEM5Z1-225L 3 35/25

UEM5Z1-225M 225

100~225A

adjustable 3/4 50/35

X Y

35 126

UEM5Z1-400L 3 50/42

UEM5Z1-400M 400

200~400A

adjustable 3/4 65/50

X Y

44 215

UEM5Z1-800L 3 50/50

UEM5Z1-800M 630

400~630A

adjustable 3/4 65/50

X Y

70 243

UEM5Z1-800L 3 50/50

UEM5Z1-800M 800

600~800A

adjustable 3/4

AC690 AC400

65/50

X Y

70 243

UEM5Z2 series electronic MCCB with residual current protection UEM5Z2 Series electronic molded case circuit breakers with residual current

protection(circuit breakers for short below) are applicable to the electrical

network under the condition of AC50Hz/ AC60Hz, rated working current

800A, rated insulation voltage 690V and rated working voltage 400V or

below with overload long-delay inverse time, short-circuit short-delay inverse

time, short-circuit short-delay definite time, instantaneous short-circuit and

under-voltage protection. Normally, the circuit breakers also take the role in

infrequent turn-on or turn-off and infrequent motor starting-up.

The circuit breakers are of compact structure, small size and high breaking capacity, which can be

equipped with the accessories such as under-voltage release, shunt release, auxiliary contact, alarm

contact, motor-driven operation mechanism, turning operation handle, etc.

This series of circuit breakers have a disconnecting function and the corresponding symbol is shown

as“ ”.

intelligent over-current

tripper(residual proction)

UEM5

Number of poles

3: three poles

4: four poles

Rated Frame Current

Inm=100

Inm=225

Inm=400

Inm=800

Operation Pattern

No code: direct operation

P: motor-driven

Z: turning handle

Installation pattern code

No code: wiring in front of the

board

H: wiring on back of the board

R: wiring by insertion Application code

No code: for power

distribution protection

2: for motor protection

Short circuit breakers

capacity

L: typical

M: second high

breaking type

Rated

current

Code for release pattern and internal

accessories

Refer to the release pattern and

internal accessories codes in detail

The N-pole of the four-pole

Refer to the release pattern

and internal accessories codes

in detail

Z2 - 100 L P / 80 3 300 2 A H

Main specification

Type

Intelligent

Releasing

Rated

current(A)

Intelligent

Releaser

Setting

Current(A)

Pole

number

Rated

Insulation

Voltage

Ui(V)

Rated

working

Voltage

Ue(V)

Rated

Residual

Action

Current

IΔn(mA)

Delay

time(s)

Ultimate/

Service

short-circ

uit

breaking

capacity

Icu / Ics

(kA)

UEM5Z2-100L 3 35/22

UEM5Z2-100M 32,100

10~32A

Adjustable

40~100A

Adjustable

3/4 50/35

UEM5Z2-225L 3 35/25

UEM5Z2-225M 225

100~225A

Adjustable 3/4

30/100/300

Adjustable

Non-delay

/0.1/0.3

adjustable

50/35

UEM5Z2-400L 3 50/42

UEM5Z2-400M 400 200~400A

Adjustable 3/4

100/300/50

0

Adjustable

Non-delay

/0.2/0.5

adjustable65/50

UEM5Z2-800L 3 50/50

UEM5Z2-800M 630

400~630A

Adjustable 3/4 65/50

UEM5Z2-800L 3 50/50

UEM5Z2-800M 800

600~800A

Adjustable 3/4

AC690 AC400

300/500/10

00

Adjustable

Non-delay

/0.5/1

adjustable65/50

Remark: 3-pole units with residual current protection will be a special standard

UET5 series automatic transfer switching UET5 Series automatic transfer switching is applicable to the

double-circuit power supply (power distribution to power

distribution, or power distribution to generator), rated frequency

50HZ/60HZ, and rated voltage 400V. The power is shifted

automatically when one power breaks down, which ensures the reliability and safety of the power

supply and makes the power switch to achieve the intelligent unmanned operation and remote

control.

This device adopts a motor-driven operation mechanism with patent technique, providing with

multifunctional intelligent controllers to meet various market demands. This device conforms to

GB/T14048.11 standard.

UET5-□ □ □ /□ □ -□ □

Transfer mechanism: Y- Integrative F-Split

Power supply: A- power distribution –power distribution;

B-power distribution- generator

N-pole types for 4-pole circuit breaker Type A: N-pole without over-current release, it has been switch-on all along, and does not act as other three poles. Type B: N-pole without over-current release, it acts as other three poles. Type C: N-pole fixed with over-current release, it acts as other three poles. Type D: N-pole fixed with over-current release, it has been switch-on all

along, and does not act as other three poles.

Code of release pattern and accessories: 200-Electromagnetic release 300- Thermo/ electromagnetic release

Number of Pole: 2-two poles; 3-three poles; 4-four poles

Rated current of the breakers

Rated short circuit breaking capacity rating

Rated frame current of the breakers

Remark:UET5-63 only with Integrative Structure(Y), Power distribution-Power distribution

Structure.

Main specifications & Performance parameter

Type

Short circuit

breaking

capacity

Rated

Current (A)

Pole

number

Rated

Insulation

Voltage

Ui(V)

Rated

working

Voltage Ue

(V)

Ultimate/ working

short-circuit

breaking capacity

Icu / Ics (kA)

6

UET5-63

6,10,16,

20,25,32,

40,50,63

3/4 AC500 AC400 4.5

L 3 35/22

UET5-100 M

16,20,25,

32,40,50,

63,80,100 3/4 50/35

L 3 35/25

UET5-225 M

100,125,140,

160,180,200,

225 3/4 50/35

L 3 50/42 UET5-400

M

225,250,315,

350,400 3/4 65/50

L 3 50/50 UET5-800

M

400,500,630,

700,800 3/4

AC690 AC400

65/50

Remark: UET5-63 Series automatic transfer switches have been equipped with XMB0 series min.

circuit breaker.

UET6 series automatic transfer switching

UET6 series automatic transfer switching equipment

consists of switch main body and transfer controller.The

product adopts electromagnetic-driven, the transfer

controller adopts main and backup power supply of

working voltage AC 220V, which requires no additional

control power supply. The switch body has electric or mechanical switch-on indicator, which can be

used as an indicator for disconnect function.

This product is of compact size, simple structure, easy operation, quick transferring speed and long

usage life. The product conforms to GB/T14048.11-2002 standard.

UET6- □ □ □ □

2:Two-pole(Only for products below 125A) 3:Three-pole 4:Four-pole

Rated current

NA: Integrative styles ATS below 125 A

(non- generator starts function) C: Split style ATS below 125 A T: Rated current from 160A to 400A two sections

split ATS TN: Rated current from 160A to 400A three sections

split ATS M: Rated current from 630A to1600A two sections

split ATS

Rated frame current

Main Spec. and Performance Parameter

Endurance life(Cycle)

Type Rated

current(A)

Pole

number

Operating

current(A)

Rated

insulation

voltage Ui

(V)

Mechanical

life

Electrical

life

Operation

Frequency

UET6-32NA 16,20,25,32

UET6-125NA 40,50,63,

80,100,125

2,3,4

3.5 5 8000 3000

15s/cyc.

UET6-32C 16,20,25,32

UET6-125C 40,50,63,

80,100,125

2,3,4

3.5 5 8000 3000

15s/cyc.

3

UET6-400T

160,200,250

,

315,400 4

7 35 6000 2000

10s/cyc.

3 UET6-400TN 200,400

4

6 10 5000 1000

10s/cyc.

630 3,4 15 15s/cyc.

800 3,4 18 20s/cyc.

1000 3,4 20 25s/cyc.

1250 3,4 25 25s/cyc.

UET6-1600M

1600 3,4

16

32

2500 500

25s/cyc.

XMB0-63 series mini circuit breaker

Conform to standards GB10963.1 and IEC60898-1;

With protective functions of overload and short circuit;

Can be equipped with various accessories, such as residual release,

auxiliary contact, alarm contact, shunt release, under voltage release, bus

bar and so on;

Adopt any combination, the matched modular and modulus structure series;

Adopt TH35mm standard din rail, easy installation;

Rated working voltage: AC230 / 400V;

Rated working current: 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A;

Releasing characteristic:

B type instantaneous releasing current: 3-5In, for non-inductance or tiny-inductance circuit.

C type instantaneous releasing current: 5~10In, for illumination distribution circuit

D type instantaneous releasing current: 10~20In, for industrial distribution system

The product is applicable to the lead wires which are 25mm² or below.

XMB0 – 63 □ □ / □

Pole number: 1P, 2P, 3P, 4P

Rated operating current:6, 10, 16,

20, 25, 32, 40, 50, 63

Instantaneous tripping characteristic

Type B: 3~5In

Type C: 5~10In

Type D: 10~20In

Rated frame current

XMB0 series high breaking capacity mini circuit breaker (MCB) XMB0 Series miniature circuit breaker is of high breaking capacity and

current-limiting characteristic, with power insulated function. Dual-use terminal

can connect with both bus bar and lead with optional insertion direction. MCB

can be assembled to the combined switches by multi accessories. MCB is used

to protect the circuit from overload and short circuit of AC 50Hz/60Hz, rated

Voltage 230/400V, rated current under 63A, and can be applicable to infrequent

turn-on and turn-off operation and electrical insulation. The products conform to

standards IEC60898 or GB10963.

XMB0 1 63 C

Pole number 1P,2P,3P,4P

Instantaneous characteristic types

B/C/D Rated current6,10,16,20,25, 32,40,50,63A

XMB0 series MCB with single-mould and dual-cutting Conform to the standards IEC60898 and GB10963.1

High breaking capacity 6kA

Rated voltage 230V

Small size, the width for one mould about 18mm

Wide current range, can reach up to 40A

Interruptible shunt, more reliable

High terminal connection capacity 1~16mm2

Protect the electric circuit from overload and short circuit

Applicable for protecting the civilian illumination and socket loop

XMB0 1 40 C N

Pole number1P+N

Rated current10,16,20,25, 32,40A

Instantaneous characteristic

types

C

Interruptible shunt

XMBL0-32 series residual protection circuit breaker

Conform to standards GB16917.1 and IEC61009-1;

With the all characteristics of XMB0-63 mini circuit breaker;

With protector of over load, short circuit and leakage;

Rated operating voltage:AC230 / 400V;

Rated operating current:6A, 10A, 16A, 20A, 25A, 32A,(40A),(50A);

Releasing characteristic: Type C instantaneous tripping current 5~10In,

applied in illumination distribution system;

Rated operating short circuit breaking capacity: 6KA;

The product is applicable to lead wires which are 10mm² or below.

X MBL0 – 32 C □ / □

Pole No.:1P+N,2P,3P,3P+N,4P

Rated operating current:6, 10, 16, 20, 25, 32,(40),(50)

Type C instantaneous tripping

Rated frame current

Notice: The special standard products for bracket

XMBL0 series dual mould residual circuit breaker (RCBO)

Conform to standards IEC61009 and GB16917.1

With residual, overload and short circuit protective function

Very high breaking capacity

Compact structure, small size(2 mould for 36mm width)

The N shunt with interruptible function, more reliable.

Double functioned terminal, better connection capacity

Wide rated current range, can be applied in the main switch for house

The surge protective current to 3000A

The circuit board past the 168 hours aging test

With contact status indicator

Optional line insertion

Ultimate breaking capacity 8kA

Rated voltage 230V.a.c

Rated current 6~40A

Frequency 50/60Hz

Rated residual operated current 30mA

Connected lead section max.25mm2

Standard installation din rail

XMBL0 1 40 C E

Notice: Can provide the over voltage protective products based on customer’s needs (280±5%V).

Pole number

2Poles with 1

protective pole

Rated

current

6,10,16,20,

25,32,40A

Instantaneous

characteristic

types

C/D

Electronic

XMG0 series insulated disconnector Applicable for industrial, commercial and civilian electric line as main disconnector.

Conform to standards IEC60947.3,GB14048.3

Rated voltage 230/400V.a.c

Frequency 50/60Hz

Application type: AC-22B

Double functioned terminal, high connection capability

Connect to lead section max.50mm2

With contact status indicator XMG0 1 40

Pole number 1P,2P,3P,4P

Rated current 40,63,80,100A

UES5 Series Surge Protector UES5 series surge protector, which conforms to standards IEC61643-1,GB18802.1, and is

applicable to various power supply systems of AC 50Hz/60Hz and rated voltage 380V. The product

has a lapsing-divorcement device and a reliable operating status indication, and the function of

remote communicated contact is available to achieve long-distance control; the response time is less

than 25 nanoseconds, and the product adopts 35mm electrical rail with safe use and easy

installation.

Pole 1,2,3,4 , Max. continuous working voltage

1+NPE,

2+NPE,

3+NPE

Norminal current In(kA) Remote signal Protection grade B,C,D

UES5 C/ - □- 20- 420- X

Type Conforming

standard

Rated working Voltage

Un

Rated discharge current

In(8/20us)

Max. discharge current

In(8/20us)

Responding time t(ns)

Protecting grade

accordance with IEC529

UES5D/□-10-140

UES5D/□-10-275

UES5D/□-10-320

UES5D/□-10-385

UES5D/□-10-420

140 275 320 385 420

5kA 10kA

UES5D/□-20-275

UES5D/□-20-320

UES5D/□-20-385

UES5D/□-20-420

275 320 85 420

10kA 20kA

UES5C/□-40-275

UES5C/□-40-320

UES5D/□-40-385

UES5D□-40-420

275 320 385 420

20kA 40kA

UES5C/□-60-275

UES5C/□-60-320

UES5C/□-60-385

UES5C/□-60-420

275 320 385 420

30kA 60kA

UES5B/□-80-275

UES5B/□-80-320

UES5B/□-80-385

UES5B/□-80-420

275 320 385 420

40kA 80kA

UES5B/□-100-320

UES5B/□-100-385

UES5B/□-100-420

320 385 420

50kA 100kA

UES5B/□-140-320

UES5B/□-140-385

UES5B/□-140-420

IEC61643-1 GB18802.1

320 385 420

70kA 140kA

Below 25 IP20

UEB-63 series

Miniature Circuit Breaker

- 1 -

UEB-63 Series Miniature Circuit Breaker

Overview and principle

UEB-63 series miniature circuit breaker (MCB) mainly used in the circuit of AC 50/60Hz, rated

voltage 230V/400V, rated current under 63A, to protect the circuit and electric equipments of building

and the similar places from over current, it’s also applicable for the infrequent opening and closing

operation.

Type nomenclature

Number of poles: 1P, 2P, 3P, 4P

Rated current: 1A, 2A, 3A, 4A, 6A, 10A, 16A,

20A, 25A, 32A, 40A, 50A, 63A

Instantaneous tripping characteristic:

Type B: 3~5In

Type C: 5~10In

Type D: 10~20In

Breaking capacity: “H” for 10k A

Without code: 6kA

Frame current (A)

Miniature circuit breaker

Corporation code: Homer

Application condition

Ambient temperature: -5C~ +40C°;

Relative humidity 95% (under 20 )

Altitude 2000m;

Pollution degree: class 2;

The places no obvious vibration and shock.

UEB-63 series

Miniature Circuit Breaker

- 2 -

Conforming standard

Products features

Overload and short circuit protection;

Use the arc resistant material, high breaking capacity, long electrical life;

Use the safe wiring structure against the electrical shock;

The shelf and the parts use the imported high flame and stamping resistance plastic

Module structure for free combination;

Suitable for disconnecting, symbol is

Main specification

Rated voltage: AC230 / 400V;

Rated current: 1A, 2A, 3A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A;

Instantaneous tripping characteristic

Type B: 3~5In,

Type C: 5~10In,

Type D: 10~20In;

Breaking capacity: 6kA, 10kA;

Number of poles: 1P, 2P, 3P, 4P

UEB-63 series

Miniature Circuit Breaker

- 3 -

Wiring capacity

35mm² and below

Dimension

Products selection table

UEB-63 seris

Pole

no.Type B Type C Type D

Rated

current

Breaking

capacity

UEB-63 series

Miniature Circuit Breaker

- 4 -

Pole

no.Type B Type C Type D

Rated

current

Breaking

capacity

UEB-63 series

Miniature Circuit Breaker

- 5 -

UEB-63H Series

Pole

no.Type B Type C Type D

Rated

current

Breaking

capacity

UEB-63 series

Miniature Circuit Breaker

- 6 -

UEB-63H series

Pole

no.Type B Type C Type D

Rated

current

Breaking

capacity

UEBL-63/40 H series

Residual current circuit breaker

UEBL-63/40(H) series residual current circuit breaker

Overview and principle

mainly used in the circuit

of AC 50/60Hz, rated voltage under 400V, rated current under 63A, to protect the circuit and electric

equipments of building and the similar places from over current, as well as providing the protection once

the over current equipment fault and the fire risk due to the ground current fault it’s also applicable for

the infrequent opening and closing operation.

Type nomenclature

- 7 -

Number of poles: 1P+N,2P,3P,3P+N,4P

Rated current(A): 6A,10A,16A,20A,25A,

32A,40A,50A,63A

Instantaneous tripping characteristic:

Type C: 5~10In

Type D: 10~20In

Rated breaking capacity: H: 10kA,

Without H: 6kA

Frame current: 63, 40

Residual current circuit breaker

Corporation code: Homer

UEBL-63/40 H series

Residual current circuit breaker

Conforming standard

Application condition

Ambient temperature: -5C~ +40C°

Relative humidity 95% (under 20 )

Altitude 2000m;

Pollution degree: class 2;

The places no obvious vibration and shock.

Products features

It’s of the all features of UEB-63 series MCB;

- 8 -

Overload, short circuit and residual current protection;

Protect the human from the indirect contact;

Provide the supplementary protection from the direct contact;

Provide the protection on insulation failure of electric equipment

(Such as electric fire);

Manual control: handle allows two kinds of reset mode

! Circuit breakers and residual current operated devices reset

at the same time

! Circuit breakers and residual current operated devices reset

individually, residual current operated device resets before the circuit breaker resets.

Prevent transient overvoltage (Lightening, state grid operation) caused

by the malfunction.

UEBL-63/40 H series

Residual current circuit breaker

Main specification

UEBL-63 series

! Rated voltage: AC230/400V;

! Rated current: 6A, 10A, 16A, 20A, 25A, 32A,, 40A, 50A, 63A;

! Instantaneous tripping characteristic:

Type C: 5~10In, applied in the distribution circuit illumination;

Type D: 10~20In, applied in the industrial distribution system;

! Breaking capacity: 6kA, 10kA;

! Rated residual operated current: 30mA

! Number of poles: 1P+N,2P,3P,3P+N,4P

UEBL-40(H) series

! Rated voltage: AC230;

! Rated current: Type C: 6A, 10A, 16A, 20A, 25A, 32A,, 40A;

Type D: 6A, 10A, 16A, 20A;

! Instantaneous tripping characteristic:

Type C: 5~10In, applied in the distribution circuit illumination;

Type D: 10~20In, applied in the industrial distribution system;

! Breaking capacity 8kA

! Rated residual operated current: 30mA

! Number of poles: 1P+N

Wiring capacity

! 35mm² and below(UEBL-40 series for 25mm2and below)

- 9 -

UEBL-63/40 H series

Residual current circuit breaker

Dimension

- 10 -

UEBL-63/40 H series

Residual current circuit breaker

Products selection table

UEBL-40 H series

Pole no. Type C Type D Rated

current

Breaking

capacity

- 11 -

UEBL-63/40 H series

Residual current circuit breaker

- 12 -

UEBL-63 series

Pole no. Type C Type D Rated

current

Breaking

capacity

UEBL-63/40 H series

Residual current circuit breaker

- 13 -

UEBL-63 series

Pole no. Type C Type D Rated

current

Breaking

capacity

UEBL-63/40 H series

Residual current circuit breaker

- 14 -

UEBL-63H series

Pole no. Type C Type D Rated

current

Breaking

capacity

UEBL-63/40 H series

Residual current circuit breaker

- 15 -

UEBL-63H series

Pole no. Type C Type D Rated

current

Breaking

capacity

UEG0-100 series disconnector

Disconnector

UEG0-100 series

Application

To make and break the circuit under the load condition, it’s of disconnecting

function, which can disconnect the circuit during inspection and maintenance.

Type nomenclature

Number of poles: 2P 3P 4P

Rated current: 40A 63A 80A 100A

Frame current

Corporation code: Homer

Products features

Applicable in the industrial, commercial and residential circuit as the main switch.

Conform to IEC60947.3,GB14048.3 standard

Rated voltage: AC230/400V

Frequency: 50/60Hz

Use type: AC-22B

Double function terminal, strong wiring capacity

Connection lead section area: max.50mm2

It’s of contact status indicator

16

UEG0-100 series disconnector

Disconnector

Products selection table

Max wiring

capacity (mm²)Pole no. Type

Rated

current

(A)Rated voltage

V

Width

mm

17

- 1 -

XMC0 Series Definite Purpose Contactors

Description HOMER XMC0 series high performance definite purpose contactors (1-Pole,

1-Pole+1Shunt, 1-Pole+1NC, 1-Pole+1NO, 2-Pole, 3-Pole,3-Pole+1NC and

3-Pole+1NO ,from 12A to 90A ) are ideal for(HVAC)air conditioning, refrigeration, heating, data

processing, welding, elevators, hoists & cranes, washing machine, lighting, pools & spas and food

service equipment. XMC0 series definite purpose contactors meet ARI 780 and UL508 standard

Features

1. Unique structure of amortization system eliminates contact bounce.

2. No tools required for snap-on accessories require that make modification quick and easy.

3. Various terminal options for specific application needs.

4. Easy to change coil.

5. Universal mounting plate allows easy replacement for other brands.

6. Heavy duty Silver Metal Oxide composition contacts ensure long electrical endurance.

7. Coils are Class F (155℃) temperature insulated with wide range of voltage and 50/60Hz ratings.

8. Double E Magnet Assembly provides optimal performance with reduced power consumption.

9. Effective dustproof structure.

10. UL, TÜV, CCC, CE approved.

Type model nomenclature - Ordering Information

XM C 0 - □ □ · □ □ □ □ □ □ □ 1 2 3 4 5 6 7 8 9 10 11 12

Number digit 1: Manufacturer’s code

XM – Xiamen Hongmei Electronic Co., Ltd.

Number digit 2: Product Type

C – Contactor

- 2 -

Number digit 3: Design Sequence Number – 0

Number digit 4: Full Load Amperes (FLA) – 12, 18, 20, 25, 32, 40, 50, 63, 75 or 90

Number digit 5: Number of Poles – 1,2, 2R, 3, 3A, 3B,3R, 5, 6, 7, 8 or 9

Number

digit 5 1 2* 2R 3 3A 3B

Number

of poles

1-pole+

1shunt 2-pole

2-pole

(1a1b) 3-pole

2-pole

(3pl frame)

3-pole

(small frame)

Number

digit 5 3R 5 6 7 8 9

Number

of poles

3-pole

(2a1b) 1-pole+1NC 1-pole+1NO 1-pole

3-pole+1NC

( small frame)

3-pole+1NO

(small frame)

Number digit 6: Coil Voltage – D, E, F, I, L, N, U

Number digit 6 D E F I J* L N U

50Hz 12V 24V 110-120V 208-220V 220V -- 380-415V 550-600V Coil

voltage 60Hz 12V 24V 110-120V 208-240V -- 277V 440-480V 550-600V

Number digit 7: Mounting plate – A, B

A – plastic base

B – metal plate

Number digit 8: Cover –A, B

A – long cover

B – short cover

Number digit 9: Terminal –A, B, C, D, E, F

A – screw w/quick connect

B – sems clamp w/quick connect

C – slotted & hex head washer w/ quick connect

D – box lug w/ quick connect

E –box lug w/quick connect (Line)

slotted&hex head washer w/quick connect (Load)

F –slotted&hex head washer w/quick connect (Line)

box lug w/quick connect (Load)

- 3 -

Number digit 10: Auxiliary contact blocks (for 3-pole) (Left & Right) side– 0, 1, 3, 4, 5, 6, 1P, 3P, 4P, 5P, 6P

Auxiliary contact block at left Auxiliary contact block at right

0- None (Standard type)

1- 1NC+1NO, pressure plate screws w/ quick connect

3- 1NC, pressure plate screws w/ quick connect

4- 1NO, pressure plate screws w/ quick connect

5- 2NC, pressure plate screws w/ quick connect

6- 2NO,pressure plate screws w/ quick connect

1P- 1NC+1NO, pressure plate screws

3P- 1NC, pressure plate screws

4P- 1NO, pressure plate screws

5P-2NC, pressure plate screws

6P-2NO, pressure plate screws

For example:

34P- 1NC pressure plate screws w/ quick connect at left and 1NO pressure plate screws at right

56- 2NC pressure plate screws w/ quick connect at left and 2NO pressure plate screws w/ quick connect at right

Number digit 11: Coil terminals– Blank, F

Blank – dual terminals without screws in 1-and 2- pole models and single terminals with screws in 3-pole models.

F-dual terminals with screws in 3- pole models.

Number digit 12: Power quick terminals– Blank, G, D, Q

Blank – quad terminals in 1-and 2- pole models.

dual terminals in 3-pole models.

G-without any terminals

D-dual terminals in 1-and 2- pole models

Q-dual terminals at the side near coil terminal and quad terminals at the other side in 3-pole models.

*If this will be the final digit(s) in selection, omit from model nomenclature.

- 4 -

Characteristics

Rated insulation voltage V 690

Conforming to standard IEC60947-4-1, GB14048.4, EN60947, ARI780

Approvals CCC UL CSA TÜV SEMKO EK CE

Protective treatment Total climate tropical use “TH”

Operating position Vertical ±5°

Operating altitude m 2000

operation ℃ -25℃~+70℃ Ambient temperature

storage ℃ -40℃~+70℃

Relative humidity 95% at 55℃

Pollution degree 3

contactor open g 6 Shock resistance 1/2 sine wave=11 ms contactor

closed g 15

contactor open g 2 Vibration resistance 5 to 300 Hz contactor

closed g 4

Performance

XMC0-

Poles 1 2 3 3A 3B 5 6 7 8 9

Rated insulation voltage V 690

Rated operating voltage V 480/277(60Hz) or 400/240(50Hz)600/345(60Hz)

Full load ampere(FLA) A 12 18 25 32 40 50 63 75 90

Resistive load ampere(RLA) A 20 25 35 40 50 63 75 95 120

Making capacity(230V cosφ0.45) A 12×FLA

Breaking capacity(230V cosφ0.45) A 10×FLA

Switching frequency op/h 360

Electrical endurance cycle 200,000

Mechanical endurance cycle 3,000,000

- 5 -

Pole Characteristics Locked Rotor amps Horsepower ratings Full

Load Amps

Resistive Amps Per

Pole 230

/277V 480V 600V 230V

1 Phase

480V 3

Phase

600V 3

Phase

Poles Catalog Number

3P XMC0 – 123 3P+1NC XMC0 – 128 12 20 72 60 48 1.5 3 5 3P+1NO XMC0 – 129 3P XMC0 – 183 3P+1NC XMC0 – 188 18 25 108 90 72 2 5 7.5 3P+1NO XMC0 – 189 1P+Shunt XMC0 – 251 2P XMC0 – 252 2P(1a1b) XMC0 – 252R 3P(at 40A frame) XMC0 – 253 2P(at 3P) XMC0 – 253A 3P(at 25A frame) XMC0 – 253B 3P(2a1b) XMC0 – 253R 1P+1NC XMC0 – 255 1P+1NO XMC0 – 256 1P XMC0 – 257 3P+1NC XMC0 – 258

25 35 150 125 100 3 7.5 10

3P+1NO XMC0 – 259 1P+Shunt XMC0 – 321 2P XMC0 – 322 2P(1a1b) XMC0 – 322R 3P XMC0 – 323 2P(at 3P) XMC0 – 323A 3P(2a1b) XMC0 – 323R 1P+1NC XMC0 – 325 1P+1NO XMC0 – 326

32 40 180 150 120 3 10 15

1P XMC0 – 327 1P+Shunt XMC0 – 401 2P XMC0 – 402 2P(1a1b) XMC0 – 402R 3P XMC0 – 403 2P(at 3P) XMC0 – 403A 3P(2a1b) XMC0 – 403R 1P+1NC XMC0 – 405 1P+1NO XMC0 – 406

40 50 240 200 160 5 15 20

1P XMC0 – 407 3P XMC0 – 503

50 63 300 250 200 5 20 25 2P(at 3P) XMC0 – 503A 3P XMC0 – 633

63 75 360 300 240 7.5 25 30 2P(at 3P) XMC0 – 633A 3P XMC0 – 753

75 95 450 375 300 15 40 50 2P(at 3P) XMC0 – 753A 3P XMC0 – 903

90 120 540 450 360 15 50 60 2P(at 3P) XMC0 – 903A

- 6 -

Auxiliary contacts block characteristics

Conventional thermal current (A) 10

Rated insulation voltage (V) 690

A600(AC-15) 230/380V

3/1.9 Rated operational current

(A) N600(DC-13) 11O/230V

2.2/1.1

Coil characteristics

Voltage Part number Inrushed

VA Sealed

VA Sealed Watts Pick-up Drop-out

XMC0-□1/5/6/7 40 7.5 2.5-3.5

XMC0-□2 45 8 2.5-4

XMC0-□3/3A/3R 90 16 3.5-5

XMC0-□3/3B/8/9 90 16 3.5-5

XMC0-503/633 145 20 5-7

XMC0-753/903 235 32 10-12

≤0.8Us ≥0.2Us

Dimensions

1-pole/1-pole+shunt/1p+1NC/1pole+1NO (plastic base, 25-40A)

- 7 -

2-pole compact (plastic base, 25-40A)

3-pole (plastic base, 25-40A)

- 8 -

1-pole/1-pole+shunt/1p+1NC/1pole+1NO (metal base, 25-40A)

2-pole compact (metal base, 25-40A)

- 9 -

3-pole (metal base, 25-40A)

3-pole (metal base, 50-63A)

- 10 -

3-pole (metal base, 75-90A)

3-pole (small frame, plastic base, 12-25A)

- 1 -

XMCK Series Definite Purpose Contactors

Description HOMER XMCK series AC Contactors are applied for controlling of air conditioning, electric motor load under condition of frequency 50Hz/60Hz, rated insulation voltage ≤690V, rated current ≤40A. (IEC standard AC-8a,AC-8b), and can be used for the other home appliance and similar electric motor load. XMCK series AC contactors conform to ARI 780 and UL 508 standard.

Features 1. Low cost design project of contactor. 2. Solid configuration design, electric pure steel magnet.

3. Easy to change coil.

4. Compact size and configuration, universal mounting plate allows easy replacement of other brands.

5. Heavy duty Sliver Metal Oxide composition contacts ensure long electrical endurance.

6. Coils are Class F (155℃) temperature insulated with wide range of voltage and 50/60Hz ratings.

7. UL,KETI,TÜV and CCC approved.

Type model nomenclature - Ordering Information XM C K - □ □ □ □ 1 2 3 4 5 6 7

Number digit 1: Manufacturer’s code

XM – Xiamen Hongmei Electronic Co., Ltd.

Number digit 2: Product Type

C – Contactor

Number digit 3: Design number - K

Number digit 4: Resistive Load Ampere(RLA)– 25, 30, 40 or 50.

Number digit 5: Number of Poles – D, DN or 2.

Number digit 5 D DN 2

Number of poles 1-pole 1-pole+1shunt 2-pole

Number digit 6: Coil Voltage –024, 120, 240, 277

Number digit 6 024 120 240 277

60Hz 24V 110-120V 208-240V 277V Coil voltage

50Hz 24V 110-120V 208-240V ---

- 2 -

Number digit 7:Terminal –A, B, C, D, E, F

A – screw w/quick connect

B – sems clamp w/quick connect

C – slotted & hex head washer w/ quick connect

D – box lug w/ quick connect

E –box lug w/quick connect (Line)

slotted&hex head washer w/quick connect (Load)

F –slotted&hex head washer w/quick connect (Line)

box lug w/quick connect (Load)

Characteristics Rated insulation voltage V 690

Conforming to standard IEC60947-4-1, GB14048.4, ARI780, UL508

Approvals UL/CUR SEMKO KETI CCC

Operating position Vertical ±5°

Operating altitude m 2000

operation ℃ -25℃~ +70℃ Ambient temperature

storage ℃ -40℃~ +70℃

Relative humidity 90-95%RH

Pollution degree 3

Performance

XMCK-

Poles D DN 2

Rated insulation voltage V 690

Rated operating voltage V 480/277,60Hz

Or 400/230,50Hz; 600/345,60Hz

Full load ampere(FLA) A 20 25 30 40

Resistive load ampere(RLA) A 25 30 40 50

Making capacity(230V cosφ0.45) A 12×FLA

Breaking capacity(230V cosφ0.45) A 10×FLA

Switching frequency op/h 360

Electrical endurance(ARI 780) cycle 100,000

Mechanical endurance(ARI 780) cycle 500,000

- 3 -

Pole Characteristics

Locked Rotor amps Power Full Load Amps

Resistive Amps Per

Pole 230

/277V 480V 600V 230V 1 Phase

480V 3 Phase

600V 3 Phase

Poles Catalog Number

1P XMCK – 25D

1P+Shunt XMCK – 25DN 20 25 120 100 80 2 5 7.5

2P XMCK – 252

1P XMCK – 30D

1P+Shunt XMCK – 30DN 25 30 150 125 100 3 7.5 10

2P XMCK – 302

1P XMCK – 40D 150 75 50 1P+Shunt XMCK – 40DN 30 40

180 150 120 3 10 15

2P XMCK – 402

1P XMCK – 50D

1P+Shunt XMCK – 50DN 40 50 240 200 160 5 15 20

2P XMCK – 502

Coil characteristics

Voltage Part number Inrushed

VA Sealed

VA Sealed Watts Pick-up Drop-out

XMCK-□D

XMCK-□DN 32 6 2-4

XMCK-□2 40 7 2.5-4.5

≤0.8US ≥0.2US

- 4 -

Dimensions

1-pole/1-pole+1shunt

2-pole

- 1 -

XMC2 Series AC Contactors

Description HOMER XMC2 series contactors are developed by Hongmei Electronic

according to customer’s requirements for high performance,

high reliability. It is of wider range coil voltage, better contact operating

ability, higher thermal-resistance class and better performance in anti-shock and vibration than same level product. It

is applied for controlling of air conditioning electric motor load under condition of 50HZ/60HZ, rated insulation voltage

≤690V, rated current ≤32A. (IEC criterion AC-8a, AC-8b). It also can be used in power supply system for long

distance making and breaking circuit, controlling electric motor load (IEC category: AC-3, AC-4). It can work with

thermal relays to be a magnet starter assembly to protect circuit from over- load current.

XMC2 series contactors not only can meet the high requirements for Air conditioning compressor and freezing

container but also can be used for all kinds of power system. It’s flexible to attach auxiliary contact to meet all

customers’ requirements and providing various contact arrangements: 3P, 3P+1NC, 3P+1NO, 2NO+2NC, 4P .

XMC2 series conform to IEC60947, GB/T14048 and ARI 780/790 standards.

Features 1. The structure of amortization system is unique, which eliminated contact bounce.

2. Heavy duty Silver Metal Oxide composition contacts ensure long electrical endurance.

3. Various contact arrangements meet different customer requirements.

4. Interface available for Auxiliary contact and protection module, easy to assemble.

5. The maximum ambient temperature can approach +80 ℃

6. Excellent performance on anti- shock and vibration (acceleration 0~20G&40Hz no failure.)

7. Coils are Class H (180 ) temperature insulated with wide range of voltage and 50/60Hz ratings.℃

8. Two types of coil terminal: double coil terminal and triple coil terminal and easy to change.

9. Easy to change coil.

10. Universal mounting plate, easily replace other brands’ contactors.

11. Double E Magnet Assembly provides optimal performance with reduced power consumption.

12. Effective dustproof structure.

- 2 -

Type model nomenclature - Ordering Information

XM C 2 - □ □ □· □ □ 1 2 3 4 5 6 7 8

Number digit 1 : Manufacturer’s code

XM – Xiamen Hongmei Electronics Co. Ltd.

Number digit 2 : Product Type

C – Contactor

Number digit 3 : Design Sequence Number – 2.

Number digit 4 : Full Load Amperes (FLA) –12, 18, 30, 32, 40, 50

Number digit 5 : Number of Poles – 3 , 2R, 4, 8 or 9.

Number digit 5 3 2R 4 8 9

Number of poles 3-pole 4-pole (2a2b) 4-pole 3-pole+1NC 3-pole+1NO

Number 6 : coil terminal type:— P , S

P:Double coil terminal(Standard type, can be omitted)

S:Triple coil terminal

Number digit 7 : Coil Voltage –D,E,F,G,I,L,N,U

Number digit 7 D E F I L N

60Hz 12V 24V 110-120V 208-240V 277V 440-480V Coil voltage

50Hz 12V 24V 110V 208-220V 230V 380-415V Remark:Lis common type, it can be removed in regular production.

数字 8:3pole auxiliary contact block -00, 1L, L1, 2L, L2, 1R, R1, 2R, R2, 10, 01, RL,11

00*- None(Standard type, can be omitted)

1L- 1NC at left L1- 1NO at left, 2L- 2NC at left, L2- 2NO at left 1R- 1NC at right, R1- 1NO at right, 2R- 2NC at right, R2- 2NO at right 10- 1NC+1NO at left 01- 1NC+1NO at right RL- 1NO at left, 1NC at right 11- 1NO+1NC at both sides

- 3 -

Characteristics Rated insulation voltage V 690

Conforming to standard IEC60947-4-1, GB/T14048.4, EN60947-4, ARI780/790

Approvals CCC

Protective treatment TH

Operating position Vertical ±5°

Operating altitude m 2000

operation ℃ -25 ~ +70 ℃ ℃ Ambient temperature

storage ℃ -40 ~ +70℃ ℃

Relative humidity 95% at 55 ℃

Pollution degree 3

contactor open g 30 Shock resistance 1/2 sine wave=11 ms contactor closed g 30

contactor open g 10 Vibration resistance 5 to 60 Hz

contactor closed g 15

Performance

XMC2- Poles 3 4 2R 8 9

Rated insulation voltage V 690

Rated operating voltage V 480/277(60Hz) or 400/230(50Hz)

Full load ampere(FLA) A 12 18 30 32 40 50

Resistive load ampere(RLA) A 20 25 32 40 50 63

Making capacity(400V cos 0.45φ ) A 12×FLA

Breaking capacity(400V cos 0.45φ ) A 10×FLA

Switching frequency op/h 360

Electrical endurance(ARI 780) cycle 200,000

Mechanical endurance cycle 10,000,000

- 4 -

Pole Characteristics

Locked Rotor amps Power Full Load Amps

Resistive Amps

Per Pole 230/277V 480V 600V 230V

1 Phase480V

3 Phase600V

3 PhasePoles Part Number

3P XMC2 – 123 3P+1NC XMC2 – 128 3P+1NO XMC2– 129

12 20 72 60 48 1.5 3 5

4P(2a2b) XMC2 – 122R 3P XMC2– 183 3P+1NC XMC2 – 188 3P+1NO XMC2 – 189

18 25 108 90 72 2 5 7.5

4P(2a2b) XMC2– 182R 3P XMC2 – 303 3P+1NC XMC2 – 308 3P+1NO XMC2 – 309

30 32 150 125 100 3 7.5 10

4P(2a2b) XMC2 – 302R 3P XMC2 – 323 3P+1NC XMC2 – 328 3P+1NO XMC2 – 329

32 40 180 150 120 3 10 15

4P(2a2b) XMC2– 322R 3P XMC2 – 403 3P+1NC XMC2 – 408 3P+1NO XMC2 – 409

40 50 240 200 160 5 15 20

4P(2a2b) XMC2 – 402R 3P XMC2– 503 3P+1NC XMC2 – 508 3P+1NO XMC2 – 509

50 63 300 250 200 5 20 25

4P(2a2b) XMC2 – 502R

Auxiliary contacts block characteristics

Conventional thermal current (A) 10

Rated insulation voltage (V) 690

A600(AC-15) 230/380V 3/1.9 Rated operational current (A)

N600(DC-13) 110/230V 2.2/1.1

Coil characteristics

Voltage Part number Inrushed

VA Sealed

VA Sealed Watts Pick-up Drop-out

XMC2-12~32 25 5 0.45-0.9

XMC2-40~50 40 6 2.5-4.5 ≤0.8US ≥0.3US

- 5 -

Dimensions

XMC2-12~32A(3P/3P+1NC/3P+1NO/2NO+2NC/4P)

XMC2-12~32A with auxiliary contact (3P/3P+1NC/3P+1NO/2NO+2NC/4P)

XMC2 Auxiliary Contact