UltraSmart Recloser

Ultra-flexible robust design

Page 2: Ultra-flexible robust design - Trinetics Recloser... · UltraSmart Recloser • 15kV & 27kV 3ph ganged operation • 630A & 800A; 12.5kA • Compatible with multiple controls •

UltraSmart Recloser• 15kV&27kV3phgangedoperation•630A&800A;12.5kA•Compatiblewithmultiplecontrols•Vacuuminsoliddielectric•3or6voltagesensors

NOTE:Fordetailedspecificationsregardingratingsandoperatingcharacteristics,pleaseseetheinstallationinstructionsfortheUltraSmartRecloserandtheappropriatecontrol.

URCIIFalcon

UltraSmart RecloserReclosersprotectdistributionfeedersandequipmentfromdamagingfaultsandovercurrentsthatcanoccurduringabnormalsystemconditions.Whenafaultoccurs,theUltraSmartRecloser,togetherwiththecompatiblecontrol,detectsandinterruptsthefaultaccordingtoyourpreselectedsettingsandtheactualfaultconditions.

Featureslikeembeddedvoltageandcurrentsensors,alongwithcontroldependentfeatureslikedirectionalfaultprotection,loadmonitoring,profiles,eventlogsandoscillography,arejustafewofthestandardtoolsthatareavailableforsystemanalysisandcontrol.Withratingsfrom15kVthrough27kVand630Athrough800A,selecttheUltraSmartRecloserandcontroltomeetyourprotectionrequirements.

© 2012 Trinetics, a division of Maysteel, LLC. All Rights Reserved. SS_02_012_E_0512

Trinetics,adivisionofMaysteel,LLC,POBox1240,MenomoneeFalls,WI53052-1240Trinetics.com

Dimensions

Q u a l i t y C E Rt i F i E DISO 9001:2008

RecloSeR

Rated maximum voltage (kV, RMS) 15.5kV 27kV

Power frequency insulation level withstand test1 minute dry10 seconds wet

50kV45kV

60kV50kV

Creepage between upper & horizontal conductor (in/mm) 47/1195 47/1195

Creepage between horizontal conductor & ground (in/mm) 36/914 36/914

Weight (lbs/kg) 248.6/113 270.6/123

Rated lightning impulse withstand voltage (kV BIL) 110 125

Rated power frequency (Hz) 50/60

Rated continuous current (A rms) 630/800

Rated short-time withstand current 1 second (kA rms) 12.5/(16)kA1

Rated peak withstand current (kA) 32.5/(41.6)kA1

Rated symmetrical interrupting current (kA rms) 12.5/(16)kA1

Rated asymmetrical making current (kA peak) 32.5kA

Rated operating sequence O-0.25s-CO-2.0s-CO-2.0s-CO

Rated line charging interrupting current (A rms) 5A

Rated cable charging interrupting current (A rms) 25A

Mechanical operating sequences (CO) 10,000

Operating temperature range (˚C) –40˚C to 55˚C

Relative humidity (%) 0–100%

Maximum altitude above sea level (masl) 3000

Manufacture standards ANSI IEEE C37.60, IEC 62271-111

Current transformer ratio 600/1, 800/1–600/5, 800/52

Voltage transformer ratio 6.5V sensor or 120V PT2

Trip and close speed Time to close 60msTime to open 40ms

Duty cycle: 20% of interrupting rating with 12.0kA 50% of interrupting rating with 12.0kA 100% of interrupting rating with 12.0kA

44 operations56 operations16 operations

Auxiliary supply options 125–230Vac-Vdc

The UltraSmart Recloser is compatible with the following controls:• SEL-351R Falcon control• ICMI URC II control

1Thevaluesbetween()arevalidupto24kV2Selectpreferredoptionattimeoforder.

40.5”

25.5”

15”

15.1” 15” 15”

17.6”

2.5”

39”