ume pd300 eng

210
PD300 MULTIFUNCTION PROTECTION Instruction Manual

Upload: shashiraj-shettigar

Post on 09-Nov-2015

523 views

Category:

Documents


80 download

DESCRIPTION

Ingeteam PD300 Manual

TRANSCRIPT

  • PD300 MULTIFUNCTION PROTECTION

    Instruction Manual

  • UME_PD300_eng Rev.: R (03/11)

    All rights reserved. No part of this publication may be reproduced by whatever means, without the prior written permission of Ingeteam T&D. Ingeteam T&D reserves the right to make any changes without prior notice.

  • INDEX

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual III

    1. GENERAL DESCRIPTION .......................................................................................................................................... 71.1 Manual scope .................................................................................................................................................... 71.2 Functions .......................................................................................................................................................... 71.3 Model coding ..................................................................................................................................................... 91.4 User interface .................................................................................................................................................. 101.5 Hardware Configurations ................................................................................................................................... 101.6 Environmental conditions .................................................................................................................................. 121.7 Tests .............................................................................................................................................................. 12

    1.7.1 Electrical tests ........................................................................................................................................ 121.7.2 Environmental tests ................................................................................................................................. 131.7.3 Mechanical tests ..................................................................................................................................... 13

    1.8 Wiring diagrams ............................................................................................................................................... 141.9 Accuracy ......................................................................................................................................................... 21

    1.9.1 Trafos saturation ..................................................................................................................................... 212. HARDWARE ........................................................................................................................................................... 22

    2.1 Constructive characteristics. Horizontal box (PD300H) ......................................................................................... 222.2 Constructive characteristics. Vertical box (PD300V) ............................................................................................. 222.3 Constructive characteristics. TCP mounted ......................................................................................................... 222.4 Rear terminals ................................................................................................................................................. 232.5 Options for rear communications ports: .............................................................................................................. 242.6 RS485 connection detail between some units ..................................................................................................... 252.7 Ethernet Communication .................................................................................................................................. 25

    2.7.1 Ethernet by GOF ..................................................................................................................................... 252.7.2 Ethernet through RJ45 cable .................................................................................................................... 26

    2.8 Technical characteristics .................................................................................................................................. 262.8.1 Auxiliary power supply voltage .................................................................................................................. 262.8.2 Output contacts ...................................................................................................................................... 272.8.3 Digital inputs (optoisolated) ..................................................................................................................... 272.8.4 IRIG-B input ........................................................................................................................................... 272.8.5 Phase and neutral current circuits (rated current 1/5 A) .............................................................................. 282.8.6 Voltage circuits ....................................................................................................................................... 28

    2.9 Operating frequency ......................................................................................................................................... 292.10 Phase order ................................................................................................................................................... 29

    3. UNIT CONFIGURATION .......................................................................................................................................... 303.1 Programming of digital AND LOGICAL inputs ...................................................................................................... 303.2 Flicker treatment in the digital inputs ................................................................................................................ 313.3 Programming of digital outputs .......................................................................................................................... 323.4 Programming of LEDs ....................................................................................................................................... 333.5 Programming of logic outputs ............................................................................................................................ 333.6 Programming General Settings .......................................................................................................................... 343.7 Differential Protection General setting Programming ............................................................................................ 343.8 Communication Configuration ............................................................................................................................ 35

    3.8.1 Front door Communication (Port 1_1) and rear port no. 2 (Port 1_2) ............................................................ 353.8.2 Communication via rear port n 1 (Port 2) .................................................................................................. 353.8.3 Ethernet Communication ......................................................................................................................... 37

    3.9 Other configuration settings .............................................................................................................................. 383.9.1 Frequency .............................................................................................................................................. 383.9.2 Language ............................................................................................................................................... 383.9.3 Phase order ............................................................................................................................................ 383.9.4 Pushbuttons enabling and lockings by commands ...................................................................................... 383.9.5 Power supply supervision enabling ............................................................................................................ 383.9.6 External power supply supervision ............................................................................................................. 383.9.7 Temperature supervision .......................................................................................................................... 383.9.8 Calibration ............................................................................................................................................. 383.9.9 Display contrast setting ............................................................................................................................ 39

    4. PROTECTION FUNCTIONS. DESCRIPTION AND SETTINGS ....................................................................................... 404.1 Protection function locking ............................................................................................................................... 404.2 Differential protection ....................................................................................................................................... 40

    4.2.1 Percent characteristic .............................................................................................................................. 414.2.2 Harmonic restraint .................................................................................................................................. 41

  • INDEX

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual IV

    4.2.3 Instantaneous differential ........................................................................................................................ 424.2.4 Function 86 ........................................................................................................................................... 43

    4.3 Restricted earth protection ................................................................................................................................ 434.3.1 Winding 1/ Winding 2 .............................................................................................................................. 434.3.2 Autotransformer ...................................................................................................................................... 43

    4.4 Phase overcurrent protection ............................................................................................................................. 444.4.1 General description ................................................................................................................................. 444.4.2 Range of settings for timed characteristics (6 tables) .................................................................................. 444.4.3 Settings ranges of the instantaneous characteristic (low level) (6 tables) ....................................................... 454.4.4 Settings ranges of the instantaneous characteristic (high level) (6 tables) ..................................................... 45

    4.5 Residual overcurrent protection ......................................................................................................................... 454.5.1 General description ................................................................................................................................. 454.5.2 Settings ranges of the timed characteristic (6 tables) .................................................................................. 464.5.3 Settings ranges of the instantaneous characteristic (low level) (6 tables) ....................................................... 464.5.4 Setting ranges of the instantaneous characteristic (high level) (6 tables) ....................................................... 46

    4.6 Current unbalance protection ............................................................................................................................ 464.6.1 General description ................................................................................................................................. 464.6.2 Setting ranges for time unit characteristics (6 tables) ................................................................................. 474.6.3 Setting range for instantaneous characteristics (6 tables) ............................................................................ 47

    4.7 Neutral overcurrent protection ........................................................................................................................... 474.7.1 General description ................................................................................................................................. 474.7.2 Range of settings for timed characteristic (6 tables) ................................................................................... 474.7.3 Settings ranges of the instantaneous characteristic (low level) (6 tables) ....................................................... 484.7.4 Settings ranges of the instantaneous characteristic (high level) (6 tables) ..................................................... 48

    4.8 Overvoltage Protection ...................................................................................................................................... 484.8.1 General description ................................................................................................................................. 484.8.2 Settings ranges of the time characteristic (6 tables) .................................................................................... 494.8.3 Settings ranges of the instantaneous characteristic (6 tables) . .................................................................... 49

    4.9 UNDERVOLTAGE PROTECTION ........................................................................................................................ 494.9.1 General description ................................................................................................................................. 494.9.2 Settings ranges of the time characteristic (6 tables) .................................................................................... 504.9.3 Settings ranges of the instantaneous characteristic (6 tables) ...................................................................... 50

    4.10 Overexcitation protection ................................................................................................................................ 514.10.1 5th harmonic ......................................................................................................................................... 514.10.2 V/f ....................................................................................................................................................... 51

    4.11 Frequency protection ...................................................................................................................................... 514.11.1 Minimum frequency .............................................................................................................................. 524.11.2 Maximum frequency .............................................................................................................................. 52

    4.12 Thermal Image ............................................................................................................................................... 524.12.1 Heating curves ...................................................................................................................................... 544.12.2 Cooling curves ...................................................................................................................................... 55

    4.13 Breaker ......................................................................................................................................................... 564.13.1 Breaker failure protection ....................................................................................................................... 564.13.2 Operation Logic .................................................................................................................................... 574.13.3 Breaker supervision ............................................................................................................................... 574.13.4 Coil supervision .................................................................................................................................... 57

    5. DATA ACQUISITION FUNCTION .............................................................................................................................. 595.1 Events reports .................................................................................................................................................. 595.2 Fault records ................................................................................................................................................... 625.3 Measurements ................................................................................................................................................. 62

    5.3.1 Measurements at the secondary ................................................................................................................ 635.3.2 Measurements at the primary ................................................................................................................... 64

    5.4 Measurement historical report ........................................................................................................................... 645.5 Statistical data ................................................................................................................................................ 655.6 Protection status .............................................................................................................................................. 65

    5.6.1 By keyboard / display ............................................................................................................................... 655.6.2 Through PC (Protections Console) ............................................................................................................. 65

    5.7 Oscillograph data recorder ................................................................................................................................ 666. OTHER FUNCTIONS ............................................................................................................................................... 67

    6.1 Time setting and synchronization ....................................................................................................................... 676.1.1 Time setting ........................................................................................................................................... 676.1.2 Synchronization ...................................................................................................................................... 67

  • INDEX

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual V

    6.2 Control messages ............................................................................................................................................. 676.3 Local/Remote command ................................................................................................................................... 686.4 Commands by keyboard .................................................................................................................................... 686.5 Power supply supervision .................................................................................................................................. 696.6 External power supply supervision ...................................................................................................................... 696.7 Temperature supervision ................................................................................................................................... 69

    7. OPERATION MODE ................................................................................................................................................ 707.1 Through keyboard/display .................................................................................................................................. 70

    7.1.1 Introduction ........................................................................................................................................... 707.1.2 Elements of the keyboard /display unit ...................................................................................................... 707.1.3 Operating mode ...................................................................................................................................... 71

    7.2 Using the PC ................................................................................................................................................... 738. RECEPTION, STORAGE, INSTALLATION AND TESTS ................................................................................................ 74

    8.1 Reception and storage ...................................................................................................................................... 748.2 Connecting procedure ....................................................................................................................................... 748.3 Unit addressing ............................................................................................................................................... 758.4 Commissioning ................................................................................................................................................ 75

    APPENDIX I. DIFFERENTIAL CURRENT CALCULATION .......................................................................................... 76I.1. 2-winding models ............................................................................................................................................ 77I.2. 3-winding models ............................................................................................................................................ 78

    APPENDIX II. GENERATOR PROTECTION ............................................................................................................... 82APPENDIX III. KEYBOARD/ DISPLAY ....................................................................................................................... 84APPENDIX IV. CURVES FOR TIMED CHARACTERISTICS ......................................................................................... 111

    IV.1. Curves CEI 255-4./.BS142 ........................................................................................................................... 111IV.2. ANSI Curves ................................................................................................................................................ 124IV.3. User curves ................................................................................................................................................. 133

    APPENDIX V. LIST OF AVAILABLE SIGNALS ......................................................................................................... 135V.1. Digital signals ............................................................................................................................................... 135V.2. Measurements .............................................................................................................................................. 139V.3. Commands ................................................................................................................................................... 140

    APPENDIX VI. LOGIC DIAGRAMS .......................................................................................................................... 142APPENDIX VII. DNP 3.0 RTU PROTOCOL ............................................................................................................... 154

    VII.1. Settings ..................................................................................................................................................... 154VII.2. Operation indications .................................................................................................................................. 156

    VII.2.1 Spontaneous message indicating RESTART ........................................................................................... 156VII.2.2 Synchronization .................................................................................................................................. 156VII.2.3 Treatment and detection of digital changes ............................................................................................ 156VII.2.4 Transfer of spontaneous messages ........................................................................................................ 156VII.2.5 Particular aspects of the operation ........................................................................................................ 156

    VII.3. Device Profile Document .............................................................................................................................. 157VII.4. Implementation table .................................................................................................................................. 158VII.5. Signal lists ................................................................................................................................................. 160

    VII.5.1 Digital signals ..................................................................................................................................... 160VII.5.2 Analogue measurements ...................................................................................................................... 160VII.5.3 Commands ......................................................................................................................................... 160

    APPENDIX VIII. MODBUS RTU PROTOCOL ......................................................................................................... 161VIII.1. Protocol characteristics .............................................................................................................................. 161

    VIII.1.1 Messages format ................................................................................................................................ 161VIII.1.2 MODBUS Functions ........................................................................................................................... 161VIII.1.3 Message examples ............................................................................................................................. 162VIII.1.4 Unit status request ............................................................................................................................. 165VIII.1.5 Change request of digital signals ......................................................................................................... 166VIII.1.6 Data request by user map ................................................................................................................... 167VIII.1.7 Synchronization ................................................................................................................................. 167VIII.1.8 Commands execution ......................................................................................................................... 168VIII.1.9 Error codes ........................................................................................................................................ 168

    VIII.2. Parameters ................................................................................................................................................ 168

  • INDEX

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual VI

    VIII.3. Unit addresses map ................................................................................................................................... 169VIII.4. Data formats .............................................................................................................................................. 170

    APPENDIX IX. IEC 870-5-101 RTU PROTOCOL ...................................................................................................... 173IX.1. Settings ...................................................................................................................................................... 173IX.2. Tables ......................................................................................................................................................... 176IX.3. Interoperability profile IEC 870 5 101 ...................................................................................................... 179

    IX.3.1 System or device (specific parameter of the system) ................................................................................ 179IX.3.2 System configuration (system specific parameter) .................................................................................... 179IX.3.3 Physical layer (system specific parameter) .............................................................................................. 179IX.3.4 Link layer (system specific parameter) .................................................................................................... 180IX.3.5 Application layer .................................................................................................................................. 181IX.3.6 Application basic functions ................................................................................................................... 185

    APPENDIX X. IEC 60870-5-103 PROTOCOL ......................................................................................................... 188X.1. 870-5-103 Communication Protocol Function ................................................................................................. 188X.2. Settings ....................................................................................................................................................... 189X.3. Control signals .............................................................................................................................................. 190X.4. Control analogue measurements ...................................................................................................................... 190X.5. Commands ................................................................................................................................................... 190

    APPENDIX XI. IEC 61850 PROTOCOL ................................................................................................................... 191XI.1. Introduction ................................................................................................................................................. 191XI.2. Previous steps to configure the device ............................................................................................................ 192

    XI.2.1 IED Import to project ............................................................................................................................ 193XI.3. Protection Configuration ............................................................................................................................... 194

    XI.3.1 IED Properties ..................................................................................................................................... 194XI.3.2 Communications .................................................................................................................................. 194XI.3.3 Datasets .............................................................................................................................................. 196XI.3.4 Report Control Blocks (RCB) ................................................................................................................. 198XI.3.5 Goose Control Blocks (GOCB) ................................................................................................................ 198XI.3.6 Goose Subscription ............................................................................................................................... 199XI.3.7 Settings .............................................................................................................................................. 200XI.3.8 Commands .......................................................................................................................................... 200XI.3.9 Private parts ........................................................................................................................................ 201

    XI.4. Protection update ......................................................................................................................................... 202APPENDIX XII. PREVENTIVE MAINTENANCE .......................................................................................................... 203

    XII.1. Failure detection ......................................................................................................................................... 203XII.2. Error handling procedure ............................................................................................................................. 204

    APPENDIX XIII. RECEPTION TESTS ................................................................................................................... 205XIII.1. Material needed ......................................................................................................................................... 205XIII.2. Measurement tests ..................................................................................................................................... 205

    XIII.2.1 Measurements in display .................................................................................................................... 205XIII.2.2 Measurements in Console ................................................................................................................... 205

    XIII.3. Protection functions ................................................................................................................................... 205XIII.3.1 Hardware status ................................................................................................................................. 205XIII.3.2 Instantaneous units (current, voltage, frequency) ................................................................................... 206XIII.3.3 Timed units (current, voltage) .............................................................................................................. 206XIII.3.4 Current unbalance units ...................................................................................................................... 207XIII.3.5 Residual current units ........................................................................................................................ 208

    XIII.4. Coil supervision ......................................................................................................................................... 208XIII.5. Display and clock test ................................................................................................................................ 209XIII.6. Unit time setting ........................................................................................................................................ 209

  • GENERAL DESCRIPTION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 7

    1. GENERAL DESCRIPTION The PD 300 family units are multifunctional protection relays of digital technology and they create the basic element used for the protection, measurement and control for 2 and 3 winding transformers and generator (see appendix). They can be used as autonomous elements for protection, control and measurement of an electrical bay or they can be integrated inside a Protection and Control Integrated System.

    Inside this family there are different models, which only differ in some hardware points or in its functionality. The Firmware is common for all the models and the available functions are defined in a programmable logic circuit (PLD) The Firmware can be load in the unit through the serial port, which makes the version updating easier.

    1.1 MANUAL SCOPE This manual does not correspond to a particular PD300 model, but it refers to the whole family. For each model, it will be only applied anything related to its physical characteristics and its functionalities. This manual is divided into two sections; the first one has the information related to configuration, functions and the second one has the appendixes: curves for timed function operation, communication protocols, and structure of the keyboard/display menus.

    On the other hand, each unit is delivered with a summarized Characteristic Sheet in which the functions of that model are related to its connections diagram.

    1.2 FUNCTIONS

    Standard functions Percent differential protection (87) with harmonic restraint (cross-blocking)

    Instantaneous differential protection (87)

    Three-phase overcurrent protection (50/51, with two instantaneous levels)

    Residual overcurrent protection (50N/51N, with two instantaneous levels)

    Unbalance protection in phase currents (46)

    Breaker failure protection (50BF)

    Thermal overload (49)

    5th harmonic overexcitation protection (24 5th harmonic)

    Breaker supervision

    Closing and trip circuit supervision

    Functions 2 winding model and generator Earth-wired overcurrent protection (50G/51G, with two instantaneous levels)

    Restricted earth protection (87G)

    Frequency protection (5 steps): maximum (81M), minimum (81m)

    Overvoltage protection (59)

    Undervoltage protection (27)

    Overexcitation protection V/f (24 V/Hz)

    Functions only in generator Percent and instantaneous differential protection limited by the frequency range (5Hz)

    Percent differential protection without harmonic restraints

    Restricted earth protection (87G)

    Only Yy connections with schedule time zero.

    Measurements

  • GENERAL DESCRIPTION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 8

    Phase currents measurements

    Earthed measurement (2 winding model and generator)

    Phase to earth voltage measurements (2 winding model and generator)

    Current maximeter

    Data acquisition Chronological events recording

    Chronological faults recording

    Maximum and minimum measurement historical recording

    Oscillograph data recorder

    Other characteristics Tables of Settings. Except for configuration, which has only one table, there are 6 tables of different settings for the

    different groups, one of which is the active or working table at a given moment. The active table selection can be done either via command by means of the keyboard/display (in "Settings (change)") or via command by means of a message from the protection Console, or by activating the digital input

  • GENERAL DESCRIPTION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 9

    1.3 MODEL CODING Inside the PD300 protection family the following models are defined:

    3 winding 87 + 50 + 51 + 50N + 51N + 46 + 50BF + 49 + 24 5th harmonic

    2 winding 87 + 87G + 50 + 51 + 50N + 51N + 50G + 51G + 46 + 50BF + 49 + 24 5th harmonic + 81M/m + 59 + 24V/Hz

    Generator 87 + 87G 50 + 51 + 50N + 51N + 50G + 51G + 46 + 50BF + 49 + 24 5th harmonic + 81M/m + 59 + 24V/Hz. Function 87 is filtered by frequency and it does not have harmonic restraint.

    Coding:

  • GENERAL DESCRIPTION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 10

    Transformer location 2 winding model 3 winding model T1 Ia winding 1 Ia winding 1 T2 Ib winding 1 Ib winding 1 T3 Ic winding 1 Ic winding 1 T4 IG1 Ia winding 2 T5 IG2 Ib winding 2 T6 Ia winding 2 Ic winding 2 T7 Ib winding 2 Ia winding 3 T8 Ic winding 2 Ib winding 3 T9 V Ic winding 3

    See the examples about the transformer location in the connection diagrams

    1.4 USER INTERFACE Local. It incorporates a front panel with

    16 key keyboard

    A 2 line, 16 character display

    7 red LED indicators and another one green/red

    Connection via RS232 for direct connection to PC. Procome protocol

    Remote. Depending on the model, it incorporates, on the rear plate, one or two glass Fibre Optic interfaces (ST type connector), plastic Fibre Optic, RS232 or RS485 for connecting to a PC, modem or Substation Control Unit (in Integrated Systems). The protocol can be Procome, DNP3.0, MODBUS, IEC 870-5-101 (except with RS485) or IEC 870-5-103.

    Ethernet communication (RJ45, GFO)

    It is only applied in those models equipped with an Ethernet port

    - PROCOME encapsulated

    - Peer to peer communications.

    - 61850

    IEC 61850 communication options

    - Single RJ45 Ethernet

    - Single FOC Ethernet

    - Double GFO Ethernet redundancy

    For serial communication these IEC 61850 models (R-type box) include:

    - 1 RS232 port Procome protocol

    - 1 GFO (unique option in case of double GFO Ethernet) or RS485 protocol DNP3.0.

    1.5 HARDWARE CONFIGURATIONS The Hardware possibilities that define a specific model are the following:

    Box type Horizontal

    Vertical

    Terminal type Pin type

    For closed terminal

  • GENERAL DESCRIPTION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 11

    Terminals: Torque of terminals mounted on the rear panel.

    Supply terminals

    Minimum: 0.5 Nm (5 in-lb)

    Maximum: 0.8 Nm (7 in-lb)

    I/O terminals:

    Minimum: 0.5 Nm (5 in-lb)

    Maximum: 0.8 Nm (7 in-lb)

    Current and voltage terminals (plug-in connector)

    Minimum: 0.5 Nm (5 in-lb)

    Maximum: 0.8 Nm (7 in-lb)

    Current and voltage terminals (closed terminals)

    Minimum: 0.5 Nm (5 in-lb)

    Maximum: 1.3 Nm (12 in-lb)

    Terminal wiring

    The terminal cables must be made of single-section copper AWG 12 to 18 (4 mm2 to 0.8mm2)

    Supply terminals

    Section AWG 16 to 14 cables (1.5 to 2 mm2)

    I/O terminals:

    Section AWG 16 to 14 cables (1.5 to 2 mm2)

    Current and voltage terminals

    Section AWG 12 cables (4 mm2)

    Power supply nominal voltage 125 / 220 Vcc

    24 / 48 Vcc

    *For more details see 2.8.1.Auxiliary power supply voltaje section. Current transformer measurement range

    Extended (low): 18 up to 160 Vdc

    Extended (high): 86 up to 280 Vdc

    Restricted 24 Vdc: 18 up to 34 Vdc

    Restricted 48 Vdc: 36 up to 60 Vdc

    Restricted 125 Vdc: 85 up to 150 Vdc

    Restricted 220 Vdc: 165 up to 264 Vdc

    Number of digital inputs/outputs Standard:

    8 inputs (5 independent, 3 with a common point)

    7 outputs (4 independent, 3 with a common point)

    Extended: adds to the standard

    9 inputs (6 independent, 3 with a common point)

    7 outputs (4 independent, 3 with a common point)

    Rear communication Glass Optical Fiber (GOF)

  • GENERAL DESCRIPTION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 12

    GOF + GOF

    RS485 + RS232

    GOF + Ethernet (RJ45)

    Plastic Optcical Fiber (POF)

    POF + F POF

    Internal Communication for TCP

    GOF + Ethernet (OF)

    RS232

    FOC + RS232

    RS232 + Ethernet (RJ45)

    RS485

    RS232 + RS232

    RS485 + Ethernet (RJ45)

    In case of having two rear ports, the one mentioned in second place is in parallel with the front RS232 (they occupy the same port), except if one of the ports is Ethernet.

    Analogue inputs The unit can have up to 9 analogue inputs (through the transformer). The usage of each input is shown in the transformer location table.

    Measurement range of the current transformers Model 2/3 windings Generratorr In = 5 A 0,1A to 160A 0,02A to 32A In = 1 A 0,02A to 32A

    1.6 ENVIRONMENTAL CONDITIONS Operating temperature -10 to 55 C Storage temperature -40 to 85 C Relative humidity up to 95% without condensation

    1.7 TESTS

    1.7.1 Electrical tests Measurement of dielectric rigidity s/ IEC255-5, series C (2 kV, 1 minute) Measurement of insulation resistance s/ IEC 255-5, > 10 Gigaohms at 500 Vdc Pulse (shock wave) s/ IEC -255-4, appendix E., class III HF disturbances s/ IEC -255-22-1, class III Fast transients(burst) s/ IEC 61000-4-4 class IV Electrostatic discharges s/ IEC 61000-4-2 class IV Voltage pulses s/ IEC 61000-4-5 class IV Micro-cuts s/ IEC 60870-2-1 100ms at 110 Vdc Radiated electromagnetic interference s/ EN 61000-6-4 Immunity to radiated fields s/ IEC 61000-4-3, class III Immunity to conducted radiofrequency signals s/ IEC 61000-4-6, class III Immunity to low frequency magnetic field s/ IEC 61000-4-8

  • GENERAL DESCRIPTION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 13

    1.7.2 Environmental tests Cold s/ IEC 68-2-1 (-40C) Dry heat s/ IEC 68-2-2 (+85C) Humid heat s/ IEC 68-2-3 (+70C, 93% relative humidity) Change of temperature s/ IEC 68-2-14 (-20/70C 2 4-hour-cycles) Operating range -10C. up to 55

    1.7.3 Mechanical tests Vibration test s/ IEC 255-21-1 class I Shock and bump test s/ IEC 255-21-1 class I

  • GENERAL DESCRIPTION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 14

    1.8 WIRING DIAGRAMS In all of the following diagrams only one of the possible digital inputs and outputs programming (very easy) is shown. See the possibilities in the section input programming and Output programming

    The order of the phase sequence is programmable via keyboard/display (See Other settings- Define protection").

    Wiring diagram example.

    Pin-type 2-winding models

  • GENERAL DESCRIPTION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 15

    Wiring diagram example.

    Closed-type 2-winding models

  • GENERAL DESCRIPTION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 16

    Wiring diagram example.

    Pin-type 3-winding models

  • GENERAL DESCRIPTION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 17

    Wiring diagram example.

    Closed-type 3-winding models

  • GENERAL DESCRIPTION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 18

    Wiring diagram example.

    Pin type generator winding models

  • GENERAL DESCRIPTION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 19

    Wiring diagram example

    Closed type generator winding models

  • GENERAL DESCRIPTION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 20

    Block diagrams

  • GENERAL DESCRIPTION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 21

    1.9 ACCURACY

    Accuracy (permanent status) Overcurrent units

    Pickup and restoration of phases and neutral 3% of the theoretical value or 20mA (the greater of boths)

    Time measurement

    Accuracy of 5% of the setting or 50ms (the greater of both)

    Differential units

    Pickup and restoration 5% of the theoretical value or 50mA (the greater of both)

    Accuracy in the range 47Hz to 51Hz

    Repetitiveness 3% of the operation time or 40ms (the greater of both)

    Transitory overreach

  • HARDWARE

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 22

    2. HARDWARE

    2.1 CONSTRUCTIVE CHARACTERISTICS. HORIZONTAL BOX (PD300H)

    Units external dimensions

    2.2 CONSTRUCTIVE CHARACTERISTICS. VERTICAL BOX (PD300V)

    Units external dimensions

    2.3 CONSTRUCTIVE CHARACTERISTICS. TCP MOUNTED

    Units external dimensions

  • HARDWARE

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 23

    2.4 REAR TERMINALS In the following pictures are showed several models according to its configuration.

    In models without inputs and output extensin, there are not the upper connectors: terminals 17 to 32 of X1 connector and terminals 14 to 28 of X2 connector.

    2 and 3 winding model (all for pin type terminals)

    2 winding model with closed type terminals for analogue inputs

  • HARDWARE

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 24

    3 winding model with closed type terminals for analogue inputs

    2.5 OPTIONS FOR REAR COMMUNICATIONS PORTS:

    Single port

    OF (Glass or PLastic) RS232 RS485

    Double port

    OF + OF OF+RS232 RS485+RS232 RS232+RS232 Ethernet+OF Ethernet+RS485 Ethernet+RS232

  • HARDWARE

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 25

    2.6 RS485 CONNECTION DETAIL BETWEEN SOME UNITS

    Although there is an internal connection in the unit between 1 and 2 pin and between pin number 3 and 4, if a connection is done on the bus side, as it is shown in the figure, a unit can be removed without causing a loss in the chain continuity.

    2.7 ETHERNET COMMUNICATION

    2.7.1 Ethernet by GOF

    The characteristics of the optical channels are as follows:

    Baud rate: 100Mb

    Connector: ST

    Optical transmitter: LED

    Optical receiver: PIN Photodiode

    Optical output: Without modulating.

    Work wave length: Glass c = 1300nm

    BER 10-9.

    Multimode glass optical fiber: 62.5/125m.

  • HARDWARE

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 26

    The values consider the temperature range from 20C to +85C.

    Losses depending on the Fibre type.

    Max. allowed losses Losses Km Connection losses Glass 62.5/125m 8 db 4 db 0.5 db

    The transmission maximum distance is given by:

    PP= Losses allowed in the link

    PC= Inset losses of additional connections

    ME= Aging margin. 3 db must be considered

    = Cable loss in db/Km

    Reachable maximum distance:

    Under the worst conditions In the best conditions Glass 62.5/125m 1.25 Km 2 Km

    2.7.2 Ethernet through RJ45 cable Interface through isolated transformer of 600 impedance ohms

    Insulation 500 V

    Connector RJ45 (female)

    Baud rate: 10/100 Mb.

    Cable type: Shielded

    Cable length: 100 m max

    2.8 TECHNICAL CHARACTERISTICS

    2.8.1 Auxiliary power supply voltage Power supply technical data:

    Auxiliary power supply 24-48 Vdc Range 18-60 Vdc Ripple 20 % over the rated current 110-125-220 Vdc Range 86-280 Vdc Ripple 20% over the rated current Burden 8W min/ 18W max

    The units have been designed to be installed and run in environments equipped with a safe and stable direct current supply. The switched, high-capacity power supplies can be used with alternating current within the following limits:

    From 18 to 60 Vdc peak values for the 24-48 VDC supply, equivalent to an operating range of 14 Vac to 42 Vac RMS approximately.

    From 18 to 280 Vdc peak values for the 110-125-200 VDC supply, equivalent to an operating range of 70 Vac to 195 Vac RMS approximately.

    These units digital inputs are designed to pick up signals in direct current and within specified ranges

    =MEPCPPl

  • HARDWARE

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 27

    The digital outputs can operate both in DC and in AC power supply systems.

    The units have been tested and certified to IEC standards for installation and operation in direct current systems. They have not been tested to AC equipment standards.

    2.8.2 Output contacts Relays 1-6 and 8-13 Relays 7 and 14 Carry (permanent) at 25 C 5 A 5 A Make(0.5 s) 30 A 30 A Breaking capacity (resistive load) for 220 Vcc

    0.4 A 0.15 A

    for 125 Vcc 1 A 0.4 A for 48 Vcc 3 A 2 A Breaking capacity (L/R=40 ms) for 220 Vcc

    0.2 A 0.1 A

    for 125 Vcc 0.5 A 0.3 A for 48 Vcc 0.5 A 0.5 A

    2.8.3 Digital inputs (optoisolated) Burden: < 3 mA

    Extended range Restricted range Model High Low 24 Vdc 48 Vdc 125 Vdc 220 Vdc Operating range (Vdc) 86 to 280 18 to 160 18 ato34 36 ato60 85 to 150 65 to 264 Inactive below (Vdc) 60 15 15 26 60 110

    2.8.4 IRIG-B input

    Characteristics Demodulated input, TTL level

    Type of cable: 2 shielded wires

    Isolation: 500 V

  • HARDWARE

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 28

    Connections

    The input circuit is a 390 ohm serial resistance with an optoacoplator; for a 5 V signal, the approximate burden is 10 mA

    The number of units that can be connected in parallel to a generator, depends on its capacity to supply output current; a typical value can be 70 mA, so 6 units could be connected (although the wire length and type have influence. The wire must be twisted and screened.

    2.8.5 Phase and neutral current circuits (rated current 1/5 A) Thermal capacity

    Continuous 20 A

    For 1 second 500 A

    For half cycle 1250 A

    Burden for In = 5 A

  • HARDWARE

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 29

    2.9 OPERATING FREQUENCY Rated: 50 or 60 Hz (programmable). Operating range: fn 5 Hz

    2.10 PHASE ORDER ABC or CBA (programmable)

  • UNIT CONFIGURATION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 30

    3. UNIT CONFIGURATION The settings that are defined next configure the unit, so they are basic.

    Some of them are only accessible by keyboard/display; some others are also accessible by Console

    All of them are usually of single table (Table 0). By keyboard/display you access to the programming of the table 0 through the menu Settings (change) by means of the keys .

    The differential protection generals are of 6 tables. By keyboard/display you access through the table programming.

    3.1 PROGRAMMING OF DIGITAL AND LOGICAL INPUTS In this kind of units, two types of inputs vare considered: digital inputs (physical, wired in the fields) or logicals (internals). Each possible input function (for example breaker status)can only be programmed only either as digital or logical, but never both at the same time.

    The digital input programming is as follows:

    It is carried out through the console, in the Configuration of digital inputs screen, in the right upper chart.

    By keyboard/display: PROG. TABLE 0 - PROG.CONFIG CONFIG. INPUTS

    SELECC. N0/NC

    INPUTS ACTIV. T.

    CONFIG INPUTS allows programming a digital input among the following possibilities:

    Breaker status (general and for each breaker)

    Close command (general and for each breaker)

    Open command (general and for each breaker)

    External protection (general and for each breaker)

    Close unblocking

    Set table 1. If a pulse is received, it sets the settings table 1 as the active table

    Set table 2. If a pulse is received, it sets the settings table 2 as the active table

    Set table 3. If a pulse is received, it sets the settings table 3 as the active table

    Set table 4. If a pulse is received, it sets the settings table 4 as the active table

    Set table 5. If a pulse is received, it sets the settings table 5 as the active table

    Set table 6. If a pulse is received, it sets the settings table 6 as the active table

    Set Local/Remote command

    Close circuit supervision with 52 open (2 or 3 breakers depending on the model)

    Close circuit supervision with 52 closed ( 2 or 3 breakers depending on the model)

    Trip circuit supervision with 52 open( 2 or 3 breakers depending on the model)

    Trip circuit supervision with 52 closed ( 2 or 3 breakers depending on the model)

    Local reposition. It turns off the tripping LEDs and it is equal to recognition for Keyboard/display.

    Output reposition. It deactivates the relays programmed as Memorized.

    Relay locking. When activating it set the relay out of service, but when it is deactivate the relay state will be the corresponding to the setting In service.

    Instantaneous inhibition. It locks the trips of the instantaneous overcurrent units, but it allows the pick up

    Instantaneous inhibition winding 1, 2 or 3. It locks the trips of the instantaneous overcurrent units on the indicated winding, but it allows the pick up.

  • UNIT CONFIGURATION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 31

    Neutral inhibition 1 or 2. It locks the trips of the instantaneous overcurrent units on the indicated neutral, but it allows the pick up.

    Free. The input may be used by the protection for lock out or logical, or it may not be used. In any case, its state may be transmitted to control.

    It should not be programmed more than an input with a certain function.

    SELECC. NO/NC. It defines if the input must be interpreted like active when it is viewed closed or when it is viewed open. Regardless it has been selected NO/NC, the digital inputs programmed in outputs, logics,leds, state signalling are seen at 1 when there is voltage in the input, and at 0 when there is no voltage in the input.

    For example, for the status of the circuit breaker, if we use a contact 52a we should program the corresponding input as NO (when it closes it will indicate closed circuit breaker), while if we use a 52b we should program it as NC (when it opens it will indicate closed circuit breaker).

    INPUT ACTIV. T. (time of activation of inputs). It is a software filter for the activation / deactivation of digital inputs. The HW filters is of 1 to 2 ms, and it can be extended by software in the number of programmed milliseconds (range 0 to 20 ms.

    The programming of digital inputs is the following one:

    It is carried out through the console, in the Configuration of digital inputs screen, in the right lower chart.

    A logical input is a virtual input(not physical)the state of which depends on the corresponding digital signal( input 1 corresponds to logical signal 1, input 15, to signal 15. its function is the one programmed( the possibilities of programming are the same as the ones of the digital inputs).

    This procedure allows the assignation of relay internal signals to those inputs as if they were wired field signals. Up to 15 logical inputs are allowed( because there are 15 logical signals).

    NO/NC selection,active input when the logic is active or inactive.

    Delay is not applied to the activation.

    Example: if logical input 3 is programmed as breaker state and NO, the unit will consider that the breaker is closed, when logical sign is inactive.

    A certain function must only be programmed as one input. It is not admissible, for example, to program state of the breaker as a digital input and as a logical input.

    3.2 FLICKER TREATMENT IN THE DIGITAL INPUTS The flicker or bouncing consists of the quick and continuous change of a digital input, usually associated to a failure in the input contact. This function allows carrying out a control to disable the inputs or digital signals that blinks so as not to interfere in the system integrated in the control, because when a digital signal is disabled, it does not generate any state change.

    This function has 3 settings:

    Minimum number of changes to mark NFLICKER fault: Minimum number of changes of a signal that must occur in TFLICKER seconds (parameter) to consider that the contact is faulty and that this signal is disabled (the changes are not treated and its state is not refreshed). Value between 0 and 255. Value 0 inhibites the signal disabling treatment due to blinking.

    Minimum number of changes to remove the QFLICKER default mark: Maximum number of changes of a signal that must occur in TFLICKER seconds (parameter) to consider that the contact is not faulty and that the signal previously disabled is enabled. Value between 0 and 255. Value 0 inhibites the signal automatic enabling treatment when theblinking disappears.

    Default decision interval (TFLICKER): time nterval, in seconds, for the tretament of the disabling or enabling of the digital signals by blinking. Value between 1 and 60. If a digital input changes its state more than NFLICKER times in a time of TFLICKER seconds (parameter) this input is disabled. If the NFLICKER paramater has a value 0, the blinking control is not carried out.

    Once a number of changes higher than the one programmed is detected, the signal is set as invalid, a Procome change is generated indicating the change into invalid and, from this moment on, changes in this signals are not detected.

  • UNIT CONFIGURATION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 32

    For the subsequent enabling of the disabled digital signals, there are three options:

    Manual reset manual of the unit.

    Automatic enabling: if a digital input previously disabled changes its state less than QFLICKER times in a time of TFLICKER seconds, this input is enabled. If the QFLICKER paramater has a value 0, the automatic enabling of the digital outputsl is not carried out.

    Enabling by operators command :Default order or programmed by the user (generic order that can be sent from the console or telecommnad) through which the unit is indicated to enable all the digital inputs that were disabled. The order only provoques the enabling of the disabled digital inputs without having influence in the blinking treatment, that is, if, after the order, input blinking is detected, they get disabled again.

    3.3 PROGRAMMING OF DIGITAL OUTPUTS By console it is carried out in the screen Digital outputs configuration.

    By keyboard/display: PROG. TABLE 0 - PROG.CONFIG PROG. OUTPUTS

    OUTPUT ACTIV. T.

    The functionality of each digital output can be programmed like an OR of the logical signals available in this unit (see point List of available signals, in the appendixes.)

    In the programming through Console (recommended), for each digital output it is clicked with the mouse in the cells corresponding to the signs whose OR wants to be activated by the output. (Matrix programming).

    In the programming screen, at he end of the available signal list, there is a row with the title OTPUT TYPE, in which each output is defined as Trip, T1, T2 , T3, Close, C1, C2 , C3, Memorized or Nothing. The operation depending on the output type:

    If it is of the type trip the output carries out the sealing logic( if the sealing setting is set to yes) and that of opening failure of 2 or 3 breakers (depending on the model).

    If it is of the type T1, T2, T3 the output carries out the sealing logic (if the sealing setting is set to yes) and that of the open failure of the specified breaker.

    If it is of the type Close the output carries out the sealing logic( if the sealing setting is set to yes) and that of opening failure of 2 or 3 breakers (depending on the model).

    If it is of the type C1, C2 o C3 the output carries out the sealing logic (if the sealing setting is set to yes) and that of the open failure of the specified breaker.

    If it is Memorized, once it has been activated, it can only be deactivated by a digital input programmed as output.

    If it is set to nothing it does nothing special

    The output activation time defines the minimum operation time of each physical output, once it has been activated (in seconds). The range is from 0.05 to5 seconds. It appears in the last row of the screen.

    Through keyboard it is more difficult. In PROG OUTPUTS, we can find ASSIGN SIGNALS for each of them with the following possibilities:

    NO SIGNAL (the output remains without assigning, but it can be activated by control commands)

    SAME SIGNALS (it is not wished to change the current programming)

    OTHER SIGNALS (it is wished to change the current programming). When pushing (Intro), it is gone through the logical signals with the arrow ; when we arrive to a signal that we want to use in the OR that defines the output, we press R; when we finish with the signals, we pulse , which takes us to the programming of the output type, with the possibilities already indicated.

  • UNIT CONFIGURATION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 33

    3.4 PROGRAMMING OF LEDS Through Console, it is carried out in the screen LEDs programming By keyboard/display: PROG. TABLE 0 - PROG.CONFIG PROG. LEDs

    OUTPUT ACTIV. T. The proceedings are totally analogous to the programming of digital outputs, except that the activation time is not programmed and that the possible types are Memorized and Non memorized. The non-memorized turns off when the cause for turning on disappears; to turn off the memorized a Fault acknowledgement must be done either by keyboard/display or digital input.

    3.5 PROGRAMMING OF LOGIC OUTPUTS The user can configure up to 15 logic outputs, called logic 1 to logic 15 and they can be assigned to output relays, LEDs, locked inputs, signals to be registered in the oscillograph data recorder , etc

    The logic output programming can be only carried out through the protection Console, (and not through keyboard/display) from he available basic signals which are detailed in the Appendix Available signals (as many of them corresponds to optional functions, all the models do not have all these functions) The programming procedure is described in another document: Protection Console Manual

    Logic signals are generated in accordance with the following layout:

    As it can be seen, defining a logic output involves the following:

    up to 16 of the available signals (or their negations), forming an OR function

    up to 16 of the available signals (or their negations), forming an AND function

    An OR or AND function is programmable from the results of the two foregoing functions.

    A programmable delay for the activation of the output.

    A programmable duration for the activation of the output

    The delay is the time elapsed from the moment there is 1 logic at the output of the logic ports and the moment when the relevant logic output activates. If 1 disappears during that time, the signal does not activate. It can be programmed from 0 to 599.9 sec., in 0.1 sec. steps.

    The pulse time (duration) is the time for which the logic signal remains active. It can be programmed in two ways:

    "By logic": after the delay, the output remains active as long as there is a 1 at the output of the programmed logic.

    "By time": the time is programmed for which the output must remain active, and after that time it de-activates regardless of the status of the programmed logic output. Only another move there from 0 to 1 will re-activate the output, once the delay has elapsed.

    This time can range from 0.1 to 599.9 seconds, with 0.1 sec. steps. A logic output i can be used as available signal for another logic signal programming input j or for itself.

  • UNIT CONFIGURATION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 34

    Simple example of application: Digital output DO7 is to be made to follow digital input DI6 with a 1 second delay.

    Delay time = 1 sec.

    Duration = "by logic"

    SD7 digital output programming: logic 1

    3.6 PROGRAMMING GENERAL SETTINGS Relay on duty: it has to be set on YES for the protection to be completely operational. If it's set on NO the protection responds to communications and the keyboard/display so that it can enter into operation; it also activates the relay and/or LED which has been programmed as "Out of duty relay", deactivating all the rest.

    Breaker number: this is an identification text. It may be programmed alphanumerically through communications, but only numerically through the keyboard.

    Setting Minimum Maximum Step Notes Relay in service YES/NO Breaker number 5 alfanum. Characters

    3.7 DIFFERENTIAL PROTECTION GENERAL SETTING PROGRAMMING It has 6 setting tables:

    Winding Transformation Ratio: it shows, in an independent way, the relations between each winding phase current: transformer ratio. It is used in the differential and restricted earth protection.

    Earthed transformation ratios: Only in 2 winding models and genrator: It shows in an independent way, the relations between each earthed current transformers ratio. It is used in restricted earth.

    Current transformation ratio: Only in 2 winding models: It is used only to give measurements regarding the primary.

    Winding nominal voltage: (kV): it shows, in an independent way, each winding nominal voltage in k. It is used in the differential protection.

    Type of connection: It shows each winding type connection: star, delta or zigzag. In 3 winding models only star or delta connection is allowed

    Time code: It indicates each winding dephase regarding the primary winding

    Application maximum: It shows in MVA the application power. It is used for the differential measurement calculation. If it is set to 0, the valued indicated in the taps is used.

    Winding tap: It is used for the differential measurement calculation, as long as the application maximum power is set to 0.

  • UNIT CONFIGURATION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 35

    2/3 windings: In the 3 winding models it shows if the differential uses 2 or 3 windings

    Nominal voltage in winding 1(kV) 1 1000 0.1 Nominal voltage in winding 2(kV) 1 1000 0.1 Nominal voltage in winding 3(kV) 1 1000 0.1 T i ratio in winding 1 1 10000 0.1 T i ratio in winding 2 1 10000 0.1 T i ratio in winding 3 1 10000 0.1 Type of connection in winding 1 Y/D Type of connection in winding 2 Y/D Type of connection in winding 3 Y/D Time code 1-2 0 11 1 Time code 1-3 0 11 1 Enable function 86 YES/NO IG 1 trafo ratio 1 10000 0.1 IG 2 trafo ratio 1 10000 0.1 Voltage trafo ratio 1 10000 0.1 Nominal voltage in winding 1(kV) 1 1000 0.1 Application maximum current (MVA) 0.2 5000 0.1

    Winding tap 1 0.5 0.1

    100 20

    0.01 0.01

    In = 5A In = 1A

    Winding tap 2 0.5 0.1

    100 20

    0.01 0.01

    In = 5A In = 1A

    Winding tap 3 0.5 0.1

    100 20

    0.01 0.01

    In = 5A In = 1A

    2/3 winding differential 2wind/3wind

    Note: In case of obtaining the winding tap by calculation (see appendix), the obtained result must be between the indicated limits for the tap, according the In calibre (0.5 to 100A for In=5A and 0.1 to 20 for In=1A); in case the result is higher than the maximum it will be fixed in the maximum, but if it is lower than the minimum, it will be fixed in the minimum.

    3.8 COMMUNICATION CONFIGURATION

    3.8.1 Front door Communication (Port 1_1) and rear port no. 2 (Port 1_2) PD300 unit has its own address identifying number, which makes possible identify the messages sent to the unit from the PC through its front port ( or rear port) with protocol PROCOME. This address is programmable from the keyboard/display entering CHANGE SETTINS, "PROG. TABLE 0", "COMUNICAT.", FRONT PORT, UCL ADDRESS".

    The units leave the factory with the address 4. This number is the one used in de Engineering program when defining the installation.

    If for any reason this number is changed in Engineering, the address programming has to be changed and vice versa.

    If a PD300 unit is replaced by another one, the installed unit must have the same address as the removed one.

    The baud rate, parity and the number of STOP bits can also be programmed in the "COMUNICAT ". The units leave the factory at 19200 baud, even parity and 1 bit of Stop.

    The established communication setting can be viewed on display, by entering SETTINGS (see), SEE TABLE 0, COMMUNICAT, PORT COM1..

    3.8.2 Communication via rear port n 1 (Port 2) The protocol type to be used by this port is defined in SETTINGS (change), PROG. TABLE 0, COMMUNIC., SELEC. COMMUN.COM2. The options are: Procome, DNP, MODBUS, IEC870-5-101 (not valid for RS485) or IEC870-5-103.

    In DNP, MODBUS, IEC870-5-101 protocols, a digital signal Control RTS is available, which is activated during the data transmission from the protection.

  • UNIT CONFIGURATION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 36

    Procome If the option chosen is Procome, in SETTINGS (change), PROG. TABLE 0, COMMUNIC. PORT COM2, a settings group is programmed (it is not necessary that they have the same values) which is analogous to the one defining the front port, but, besides, there is another setting CONTROL SIGNALS, with the options None and RTS; this setting also affects the port COM1.

    DNP If the option chosen is DNP, the address is programmable from the keyboard/display, entering SETTINGS (change), PROG. TABLE 0, COMMUNIC PORT COM2, CONFIG.DNP, LCU ADDRESS. This address does not need to be the same as the one of the front port, but it is convenient to avoid confusions. The units leave the factory with the address and the rest of DNP parameters without being programmed. They have to be programmed by the user.

    If a replacement of the PD300 unit by other is made, the installed unit must have the same address as the one removed.

    The unit also has an identification number of the Master unit it is connected to, and which only accepts messages coming from there. It is also programmable in the unit within the CONFIG. DNP. The units leave the factory with the address 0. They are also programmable the baud rate, the parity and the number of STOP bits. The units leave the factory at 9600 baud, without parity, 1 Stop bit.

    The established communication settings can be seen on the display, entering SETTINGS (see), SEE TABLE 0, COMMUNICATIONS, PORT COM2, CONFIG. DNP

    The settings can be displayed/programmed both via keyboard/display and via PC with the Protection Console.

    For more detail on communication DNP, see the corresponding Appendix.

    MODBUS If the chosen option is MODBUS, the address is programmable from the keyboard/display, entering SETTINGS (change), PROG. TABLE 0, COMMUNICATIONS PORT COM2, CONFIG.MODBUS, LCU ADDRESS. This address does not need to be the same as the one of the front port, but it is convenient to avoid confusions. The units leave the factory with the address and the rest of the MODBUS parameters without been programmed. They have to be programmed by the user.

    If the PD300 unit is replaced by other, the installed unit must have the same address as the one removed.

    They are also programmable the baud rate, the parity and the auxiliary timers for activation and deactivation of the RT signal (internal).

    The established communication settings can be seen on display, entering SETTINGS (see), SEE TABLE 0, COMMUNICATIONS, PORT COM2, CONFIG. MODBUS

    The settings can be displayed/programmed both via keyboard/display and via PC with the Protection Console.

    For more detail on communication MODBUS, see the corresponding Appendix.

    IEC 870-5-101 If the chosen option is 101, the address is programmable from the keyboard/display, entering SETTINGS (change), PROG. TABLE 0, COMMUNICATIONS PORT COM2, "GENERALS", "LINK ADDRESS" and APPLIC ADDRESS. This address does not need to be the same as the one of the front port, but it is convenient to avoid confusions. The units leave the factory with the address and the rest of the 101 parameters without been programmed. They have to be programmed by the user.

    If the PD300 unit is replaced by other, the installed unit must have the same address as the one removed. They are also programmable the baud rate, the parity and the auxiliary timers for activation and deactivation of the RT signal (internal).

    The established communication settings can be seen on display, entering SETTINGS (see), SEE TABLE 0, COMMUNICATIONS, PORT COM2, "GENERALS"

    The settings can be displayed/programmed both via keyboard/display and via PC with the Protection Console.

    This protocol is not valid for RS485 ports. For more details on 101 communications, see the corresponding setting.

    IEC 870-5-103

  • UNIT CONFIGURATION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 37

    If the chosen option is 103, the address is programmable from the keyboard/display, entering SETTINGS (change), PROG. TABLE 0, CONFIG. COMMUNICAT., PORT COM2, LCU ADDRESS. This address does not need to be the same as the one of the front port, but it is convenient to avoid confusions. The units leave the factory with the address and the rest of the 103 parameters without been programmed. They have to be programmed by the user.

    If the PL300 unit is replaced by another one, the installed unit must have the same address as the one removed.

    They are also programmable the baud rate, the parity and the auxiliary timers for activation and deactivation of the RT signal (internal).

    The established communication settings can be seen on display, entering SETTINGS (see), SEE TABLE 0, CONFIG. COMMUNICAT., PORT COM2.

    Apart from the keyboard/display, the settings can also be displayed/programmed from the PC.

    For more detail on 103 communication, see the corresponding Appendix.

    3.8.3 Ethernet Communication It is only applied in models with Ethernet port.

    In order to configure the Ethernet port the fist parameter to be configured corresponds to the TCP/IP communication selection. It is programmed from the keyboard/display, by entering "SETTINGS (change)", "PROG. TABLE 0", "COMMUNICATIONS", SELECT COM TCPIP. The options of this parameter are: Procome and No. The operation according to this parameter is as follows:

    Procome: Through Ethernet port communication with Procome protocol is possible. In this case the selection of Procome protocol in the other rear port (com 2) is not allowed. In short, through Ethernet port the communication is with Procome protocol, whilst in the second rear port (if available) communication is carried out through the selected protocol, except Procome.

    NO. communication is not carried out through Ethernet port. In this case, the second rear port (if available) communicates through the selected protocol, Procome is allowed.

    The remaining configuration parameters of Ethernet port are configured with the Sipcon console, in the menu Configuration TCP/IP). These parameters are those below:

    Generals Protection IP address. It shows the protection IP address (server unit). They are 32 bits, in decimal notation separated

    by dots.

    Subnet mask. It defines which part of the IP address identified by the network. They are 32 bits, in decimal notation separated by dots. All those IP addresses that do not fulfil the net mask, that is, those which do not have the part of the net mask at 1 are not considered to belong to the net and they are not treated. For example, the mask 255.255.255.000 allows 256 server addresses that would share the first three values of the address.

    Gateway. Link gate. It shows the IP address the messages will be sent to for those servers tat do not belong to the local net. It will be the IP address of the unit in charge of carrying out the router functions of the net.

    No. of connections. It is fixed at 1.

    Procome Master IP address. It shows the protection IP address (client unit).

    Port. It shows the port to which the master unit is connected.

    UCL Address. It is the protection address, to which the protocol responds.

  • UNIT CONFIGURATION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 38

    3.9 OTHER CONFIGURATION SETTINGS Only accessible by keyboard/display, on SETTINGS (change), PROG. TABLE 0, DEFINE PROTECT.. They are the following:

    3.9.1 Frequency It can be 50 Hz or 60 Hz. It is the fundamental basic protection setting. If it is not the correct one, the measurements and, therefore, the protection operation will be wrong.

    3.9.2 Language It can be English or Spanish. It relates to the texts shown on display.

    3.9.3 Phase order It can be A, B, C or C, B, A. It affects only to the protection functions of broken conductor and unbalance (currents and voltages). To verify that the order corresponds to the wiring, check in Measurements that the ratio of the inverse/direct component is close to 0%, when introducing 3 balanced currents of about 1 A.

    3.9.4 Pushbuttons enabling and lockings by commands Under the name PUSHBUTTONS there are two settings:

    ENAB. PUSHBUT (Pushbuttons enabling ): If this setting is at FUNCTIONALS, they keys can be used to give commands; if they are at NO, they cannot.

    ENAB. LOCK. COMMAND (Enabling of locking/unlocking by commands): If this setting is at YES, the protection function locking/unlocking control commands that have been programmed are enabled; if they are at NO, they are disabled.

    3.9.5 Power supply supervision enabling The power supply supervision can be or cannot be enabled. See section Power supply supervision for its operation.

    3.9.6 External power supply supervision Only available in those model with the option Battery voltage measurement. The three settings for this function, enable, minimum threshold (V) and maximum threshold(V), are in this menu. See section External power supply supervision for its operation.

    3.9.7 Temperature supervision The three settings for this function, enable, minimum threshold () and maximum threshold(), are in this menu. See section temperature supervision for its operation.

    3.9.8 Calibration This menu position is exclusively to be used by the Ingeteam Transmission & Distribution SA technicians, according to a certain procedure. It should not be used by the user.

  • UNIT CONFIGURATION

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 39

    3.9.9 Display contrast setting The procedure that should be followed is the following:

    By the pressing key (of a 16 key keyboard) for 3 to 5 seconds, you enter in the contrast setting menu, appearing the text: -DOWN +UP.

    With the keys and the contrast is adjusted. With more brightness is given and with it gets dark.

    To validate, press ESC or after a minute it goes back to the usual position, with the carried-out changes.

  • PROTECTION FUNCTIONS. DESCRIPTION AND SETTINGS

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 40

    4. PROTECTION FUNCTIONS. DESCRIPTION AND SETTINGS

    4.1 PROTECTION FUNCTION LOCKING Each of the protection functions can be locked by a digital input or by a logic function (combination of inputs and/or control signals). See Programming logic signals in the Configuration section

    The locking programming is carried out through console and keyboard/display as any other setting inside the corresponding function.

    4.2 DIFFERENTIAL PROTECTION The differential protection will be in percent terms with harmonic restraint and instantaneous. The protection function is the same for 2 and 3 winding, and the difference lays in the calculation of the differential current (see the corresponding appendix).

    The settings corresponding to the differential currents (shown as xIn) are indicated in tap steps.

    The differential protection generic curve is the following one:

    Depending on the step and gradient current settings, different characteristics can be obtained, for example:

  • PROTECTION FUNCTIONS. DESCRIPTION AND SETTINGS

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 41

    4.2.1 Percent characteristic It matches the graphic section with the possibility of restraint. It can be double gradient or single gradient

    The protection operation takes place when once the programmed time has elapsed, since the differential current is inside the trip area with restraint possibility (see graph) and besides, the 2nd and 5th harmonic constituents do not cause restraint.

    The settings (6 tables) are:

    Setting Minimum Maximum Step Notes Enable YES/NO Sensitivity (xTap) 0.15 2 0.01 See note I step 1 (xTap) 0 2 0.01 I step 2 (xTap) 0 20 0.01 1 (%) 5 100 1 2 (%) 5 200 1 Additional time (s) 0 60 0.01

    Note: The sensitivity value must fulfil the following:

    InySensitivitTap imum 05.0min

    being In the rated current (5A or 1A). If not, the sensitivity value is automatically modified to fulfil it.

    The sensitivity and step currents are shown in tap steps.

    The settings are in the Console, in the Differential Protection screen.

    4.2.2 Harmonic restraint

    4.2.2.1 Inrush restraint The protection differentiates the inrush currents by means of the differential currents 2nd harmonic component or 2nd + 4th of the differential current according the setting selection.

    When the component of the 2nd or the 2nd + 4th harmonic of the differential current in one or more phases exceed the set percent of the fundamental, the trip will be inhibited in that phase or in all of them, depending on the selection.

    In order to the harmonic restrain act, the differential current of the fundamental must exceed the set minimum value set, so if it below that threshold, the harmonic restrain does not act.

    Setting Magnitude Operation No Idif_2 It does not inhibit in any phase 2nd PHASE Idif_2 It inhibits only in the phases exceeding the harmonic setting.

    2nd GLOBAL Idif_2 It inhibits in the three phases when any of them exceeds the harmonic setting.

    2nd + 4th PHASE 22 )4_()2_( IdifIdif + It inhibits only in the phases exceeding the harmonic setting.

    2nd + 4th GLOBAL 22 )4_()2_( IdifIdif + It inhibits in the three phases when any of them exceeds the harmonic setting..

    Being:

    Idif_2: Idifferential 2nd harmonic

    Idif_4: Idifferential 2nd harmonic

  • PROTECTION FUNCTIONS. DESCRIPTION AND SETTINGS

    Ingeteam Transmission & Distribution S.A.

    PD300 User Manual 42

    The settings (6 tables) are the following:

    Setting Min Max Step Notes

    Enable 2nd harmonic restrain NO / 2nd PHASE / 2nd GLOBAL / 2nd +4th PHASE /

    2nd +4th GLOBAL 2nd harmonic restrain threshold