uncoated weathering steel bridge data collection …
TRANSCRIPT
UNCOATED WEATHERING STEEL BRIDGE DATA COLLECTION
AND PERFORMANCE ASSESSMENT: BRIDGE MAINTENANCE PRACTICES,
DEICING AGENT USE, AND FIELD SAMPLING
by
J.T. Rupp
A thesis submitted to the Faculty of the University of Delaware in partial
fulfillment of the requirements for the degree of Master of Civil Engineering
Spring 2020
© 2020 J.T. Rupp
All Rights Reserved
UNCOATED WEATHERING STEEL BRIDGE DATA COLLECTION
AND PERFORMANCE ASSESSMENT: BRIDGE MAINTENANCE PRACTICES,
DEICING AGENT USE, AND FIELD SAMPLING
by
J.T. Rupp
Approved: __________________________________________________________
Jennifer E. Righman McConnell, Ph.D.
Professor in charge of thesis on behalf of the Advisory Committee
Approved: __________________________________________________________
Sue McNeil, Ph.D.
Chair of the Department of Civil and Environmental Engineering
Approved: __________________________________________________________
Levi T. Thompson, Ph.D.
Dean of the College of Engineering
Approved: __________________________________________________________
Douglas J. Doren, Ph.D.
Interim Vice Provost for Graduate and Professional Education and
Dean of the Graduate College
iii
ACKNOWLEDGMENTS
I would like to thank my advisors Dr. Jennifer Righman McConnell and Dr.
Tripp Shenton for providing me the opportunity to work on this research project
along with them, Tian Bai, and Gary Wenczel. They constantly commended me for
my hard work and allowed me to demonstrate my own ideas while providing me
with assistance when needed. The knowledge and experience I have gained from
this research project have allowed me to advance in my professional career as well
as my personal life. I am tremendously grateful for all of their guidance and support
throughout my college career. I would also like to thank Chris Reoli for all of her
help and cheerful attitude that I was pleased to be in the presence of throughout my
graduate program. I would also like to acknowledge the Long-term Bridge
Performance Program (LTBPP) state coordinators and agencies which provided me
with opportunities to collect valuable research data for this project. My gratitude
also goes to the sponsor of this research project, the Federal Highway Association
(FHWA).
Thank you again to all who supported me throughout this journey and
provided me with the opportunity to pursue my life goals.
iv
TABLE OF CONTENTS
LIST OF TABLES .......................................................................................................... x LIST OF FIGURES .................................................................................................... xiii ABSTRACT ................................................................................................................. xix
Chapter
1 INTRODUCTION .............................................................................................. 1
1.1 Project Overview ....................................................................................... 1 1.2 Project Objectives and Scope..................................................................... 2 1.3 Thesis Organization ................................................................................... 3
2 BACKGROUND ................................................................................................ 5
2.1 Uncoated Weathering Steel Background ................................................... 5
2.1.1 Environmental Effects on Corrosion of UWS ............................... 5 2.1.2 Advantages of UWS ...................................................................... 6 2.1.3 Disadvantages of UWS .................................................................. 7
2.2 Methods Previously Used for Assessing UWS .......................................... 8
2.2.1 Visual Inspection ........................................................................... 8 2.2.2 Clear Tape Adhesion Test ............................................................ 11 2.2.3 Ion Chromatography (IC) Analysis ............................................. 11 2.2.4 XRD Analysis .............................................................................. 12
2.3 Past Field Studies ..................................................................................... 12
2.3.1 Coastal Environment Field Studies .............................................. 13
2.3.1.1 Relationship Between Atmospheric Corrosion Rates
and Chloride Concentrations......................................... 13 2.3.1.2 Rust Phases Formed in Coastal Environments ............. 16 2.3.1.3 Goethite/Lepidocrocite Relation to Protective Ability
Index in Coastal Environments ..................................... 17 2.3.1.4 Effects on Corrosion Rates Based on Chemical
Composition of UWS in Coastal Environments ........... 18
v
2.3.1.5 Relationship Between Physical Corrosion
Characteristics and Chloride Concentrations ................ 20
2.3.2 Industrial Environment Field Studies .......................................... 22
2.3.2.1 Relationship Between Atmospheric Corrosion Rates
and Sulfur Oxide Concentrations .................................. 23 2.3.2.2 Rust Phases Formed in Industrial Environments .......... 25 2.3.2.3 Goethite/Lepidocrocite Relation to Protective Ability
Index in Industrial Environments.................................. 26 2.3.2.4 Effects on Corrosion Rates Based on Chemical
Composition of UWS in Industrial Environments ........ 27
2.3.3 Rural Environment Field Studies ................................................. 29
2.3.3.1 Rust Characteristics in Rural Environments ................. 29 2.3.3.2 Rust Phases Formed in Rural Environments ................ 30 2.3.3.3 Goethite/Lepidocrocite Relation to Protective Ability
Index in Rural Environments ........................................ 31
2.3.4 UWS Bridge Washing Field Studies............................................ 32
2.4 Phase 1 and Phase 2 Work ....................................................................... 33
3 FIELD METHODOLOGY ............................................................................... 37
3.1 Bridge Selection ....................................................................................... 37
3.1.1 GIS Database ............................................................................... 39 3.1.2 Reference Bridges ........................................................................ 40 3.1.3 Proximate Bridges ........................................................................ 41 3.1.4 Cluster Bridges............................................................................. 42 3.1.5 Field Bridges ................................................................................ 44
3.2 Field Work ............................................................................................... 46
3.2.1 Equipment .................................................................................... 46 3.2.2 Prior to Field Visit ....................................................................... 48 3.2.3 Once in the Field .......................................................................... 48
3.2.3.1 Visual Documentation .................................................. 49 3.2.3.2 Sample Areas ................................................................ 52
3.2.3.2.1 Locations ..................................................... 52 3.2.3.2.2 Measurements ............................................. 55 3.2.3.2.3 Photographs................................................. 56
vi
3.2.3.3 Dry-Film Thickness ...................................................... 57 3.2.3.4 Tape Samples ................................................................ 57 3.2.3.5 Rust Samples ................................................................. 58 3.2.3.6 Ultrasonic Thickness Measurements ............................ 58 3.2.3.7 Severe Corrosion, Pitting, and Section Loss ................. 59
3.3 Data Collection ........................................................................................ 59
3.3.1 Clear Tape Adhesion Test ............................................................ 59 3.3.2 Ion Chromatography Analysis ..................................................... 60
4 RESULTS ......................................................................................................... 61
4.1 Qualitative Assessments of Bridges ......................................................... 61
4.1.1 Colorado Bridges ......................................................................... 66 4.1.2 Connecticut Bridges ..................................................................... 68
4.1.2.1 CT 3830 ........................................................................ 68 4.1.2.2 CT 4382 ........................................................................ 68 4.1.2.3 CT 5796 ........................................................................ 69
4.1.3 Iowa Bridges ................................................................................ 71
4.1.3.1 IA 004111 ..................................................................... 71 4.1.3.2 IA 041331 ..................................................................... 71 4.1.3.3 IA 042711 ..................................................................... 71
4.1.4 Minnesota Bridges ....................................................................... 73
4.1.4.1 MN 04019 ..................................................................... 73 4.1.4.2 MN 19811 ..................................................................... 75 4.1.4.3 MN 62861 ..................................................................... 76
4.1.5 North Carolina Bridges ................................................................ 77
4.1.5.1 NC 190083 .................................................................... 77 4.1.5.2 NC 1290057 .................................................................. 78 4.1.5.3 NC 1290058 .................................................................. 80
4.1.6 New Hampshire Bridges .............................................................. 81
4.1.6.1 NH 017201120011300 .................................................. 81 4.1.6.2 NH 11101120017900 .................................................... 82 4.1.6.3 NH 017701460003700 .................................................. 84
vii
4.1.7 Ohio Bridges ................................................................................ 86
4.1.7.1 OH 7701977 .................................................................. 86 4.1.7.2 OH 7701993 .................................................................. 86 4.1.7.3 OH 7700105 .................................................................. 86
4.2 Findings Related to Bridge Maintenance Practices ................................. 89
4.2.1 Findings from Review of Maintenance Manuals ......................... 89
4.2.1.1 Response Rates ............................................................. 89 4.2.1.2 Review of Maintenance Manuals Results ..................... 89
4.2.2 Findings from Washing Practices Survey .................................... 94
4.2.2.1 Response Rates ............................................................. 95 4.2.2.2 Washing Practices Survey Results ................................ 97
4.3 Findings Related to Deicing Agent Usage ............................................... 99
4.3.1 Findings from Deicing Agent Usage Survey ............................... 99
4.3.1.1 Response Rates ............................................................. 99 4.3.1.2 Deicing Agent Usage Survey Results ......................... 102
4.4 Field Results........................................................................................... 103
4.4.1 Tape Test Results ....................................................................... 103
4.4.1.1 Cluster Performance Based on Tape Test Results ...... 104 4.4.1.2 Field Bridge Performance Based on Tape Test
Results ......................................................................... 106 4.4.1.3 Standard Sample Area Location Performance Based
on Tape Test Results ................................................... 108
4.4.2 Ion Chromatography Results ..................................................... 111
4.4.2.1 Cluster Ion Chromatography Results .......................... 112 4.4.2.2 Field Bridge Ion Chromatography Results ................. 114 4.4.2.3 Standard Sample Area Location Ion
Chromatography Results ............................................. 118
5 DATA CORRELATIONS DISCUSSION ..................................................... 122
5.1 Introduction ............................................................................................ 122
viii
5.2 Correlations Between Bridge Maintenance Manual Ratings and Tape
Test Results ............................................................................................ 123 5.3 Correlations Between Bridge Washing Practices and Tape Test
Results .................................................................................................... 125 5.4 Correlations Between Bridge Washing Practices and IC Analysis
Results .................................................................................................... 128 5.5 Correlations Between Deicing Agent Usage and Tape Test Results ..... 131 5.6 Correlations Between Deicing Agent Usage and IC Analysis Results .. 133 5.7 Correlations Between IC Analysis Results and Tape Test Results ........ 136
5.7.1 Correlations Between Cluster IC Analysis Results and Tape
Test Results ................................................................................ 137 5.7.2 Correlations Between Field Bridge IC Analysis Results and
Tape Test Results ....................................................................... 140 5.7.3 Correlations Between Sample Location IC Analysis Results
and Tape Test Results ................................................................ 144
5.8 Correlations Between Tape Test Results and Condition Ratings of
Field Bridges .......................................................................................... 148 5.9 Summary of Correlations ....................................................................... 153
6 CONCLUSIONS............................................................................................. 158
6.1 Summary ................................................................................................ 158 6.2 Overview of Results ............................................................................... 158 6.3 Main Takeaways .................................................................................... 164 6.4 Future Work ........................................................................................... 166
REFERENCES ........................................................................................................... 169
Appendix
A CLUSTER BRIDGE CHARACTERISTICS ................................................. 173 B PARAMETRIC COMBINATIONS ............................................................... 177 C FIELD DATA ENTRY SHEETS ................................................................... 180 D MATLAB Script for Digital Image Processing of Tape Samples .................. 204 E MAINTENANCE SURVEYS ........................................................................ 208
E.1 Original Survey ...................................................................................... 208 E.2 Follow-Up Survey for Prior Participants ............................................... 209 E.3 Follow-Up Survey for Agencies with No Prior Response ..................... 211
F SURVEY DATA ............................................................................................ 212 G TAPE SAMPLE RESULTS ........................................................................... 218
ix
G.1 Tape Sample Images .............................................................................. 218 G.2 Tape Test Results Data Tables ............................................................... 225 G.3 Tape Test Results Standard Deviations ................................................. 232 G.4 Tape Test Results Graphs ...................................................................... 234
H ION CHROMATOGRAPHY ANALYSIS RESULTS .................................. 241
H.1 IC Analysis Results Data Tables............................................................ 241 H.2 IC Analysis Results Standard Deviations .............................................. 248
x
LIST OF TABLES
Table 3.1: Phase 3 Cluster Overview ........................................................................ 38
Table 3.2: Characteristics of Phase 3 Reference Bridges ......................................... 41
Table 3.3: Summary Bridge Statistics of Phase 3 Clusters ....................................... 43
Table 3.4: Characteristics of Phase 3 Field Bridges ................................................. 45
Table 3.5: Characteristics of Bridges NH 019700810009300 and NH
017700960015300.................................................................................... 46
Table 3.6: Standard Sample Area Location Descriptions ......................................... 55
Table 4.1: Field Bridge Qualitative Assessment Condition Ratings......................... 65
Table 4.2: Standard Sample Area Location Descriptions of Colorado Bridges ....... 67
Table 4.3: Maintenance Manual Review .................................................................. 91
Table 4.4: Regional Deicing Agent Use Statistics .................................................. 101
Table 5.1: Summary of Overall Bridge Maintenance Manual Ratings and
Average Percent Area of Rust Particles Greater than or Equal to an
1/8 inch for Each Agency/Cluster .......................................................... 124
Table 5.2: Summary of Bridge Washing Practice Ratings and Average Percent
Area of Rust Particles Greater than or Equal to an 1/8 inch for Each
Agency/Cluster ...................................................................................... 126
Table 5.3: Summary of Bridge Washing Practice Ratings and Average Chloride,
Nitrate, and Sulfate Concentrations for Each Agency/Cluster .............. 128
Table 5.4: Summary of Deicing Agent Usage and Average Percent Area of Rust
Particles Greater than or Equal to an 1/8 inch for Each
Agency/Cluster ...................................................................................... 131
Table 5.5: Summary of Deicing Agent Usage and Average Chloride
Concentrations for Each Agency/Cluster............................................... 134
Table 5.6: Summary of Average Chloride, Nitrate, and Sulfate Concentrations
and Average Percent Area of Rust Particles Greater than or Equal to
an 1/8 inch of Each Cluster .................................................................... 138
xi
Table 5.7: Summary of Average Chloride, Nitrate, and Sulfate Concentrations and
Average Percent Area of Rust Particles Greater than or Equal to
an 1/8 inch of Each Field Bridge ........................................................... 141
Table 5.8: Summary of Average Chloride, Nitrate, and Sulfate Concentrations
and Average Percent Area of Rust Particles Greater than or Equal to
an 1/8 inch of Each Standard Sample Area Location ............................ 145
Table 5.9: Summary of Average Percent Area of Rust Particles Greater than or
Equal to an 1/8 inch, SCR, and Weighted Girder CS Ratings for
Each Field Bridge .................................................................................. 149
Table 5.10: Summary of Average Chloride, Nitrate, and Sulfate Concentrations
and Average Percent Area of Rust Particles Greater than or Equal to
an 1/8 inch Sorted from Highest to Lowest of Each Standard Sample
Area Location......................................................................................... 155
Table 6.1: Summary of Chapter 5 Cause and Effect Correlations .......................... 159
Table 6.2: Summary of Chapter 5 IC Analysis and Tape Test Correlations ........... 160
Table 6.3: Summary of Chapter 5 Methods to Assess UWS Performance
Correlations ............................................................................................ 161
Table 6.4: Summary of Cluster and Field Bridge Data Types ................................ 162
Table A.1: CO Cluster Bridges ................................................................................ 173
Table A.2: CT Cluster Bridges ................................................................................ 174
Table A.3: IA Cluster Bridges ................................................................................. 174
Table A.4: MN Cluster Bridges ............................................................................... 175
Table A.5: NC Cluster Bridges ................................................................................ 175
Table A.6: NH Cluster Bridges ................................................................................ 176
Table A.7: OH Cluster Bridges ................................................................................ 176
Table B.1: Deicing Cluster Parametric Combinations ............................................. 177
Table B.2: Deicing + Coastal Cluster Parametric Combinations ............................ 178
Table B.3: Coastal Cluster Parametric Combinations ............................................. 179
xii
Table F.1: Maintenance Manual Responses ............................................................ 212
Table F.2: Washing Practices Responses ................................................................ 214
Table F.3: Deicing Agent Usage Responses ........................................................... 215
Table F.4: Deicing Agent Usage Statistics .............................................................. 217
Table G.1: Tape Test Results Cluster Standard Deviations ..................................... 232
Table G.2: Tape Test Results Field Bridge Standard Deviations ............................ 233
Table G.3: Tape Test Results Standard Sample Area Location Standard
Deviations .............................................................................................. 234
Table H.1: IC Analysis Results Cluster Standard Deviations .................................. 248
Table H.2: IC Analysis Results Field Bridge Standard Deviations ......................... 248
Table H.3: IC Analysis Results Standard Sample Area Location Standard
Deviations .............................................................................................. 249
xiii
LIST OF FIGURES
Figure 3.1: Phase 3 Cluster Locations ........................................................................ 39
Figure 3.2: Photo Example of Wide View of Bridge ................................................. 50
Figure 3.3: Photo Example of View of Bearing Location .......................................... 50
Figure 3.4: Photo Example of Wide View of Interior Girders ................................... 51
Figure 3.5: Photo Example of View of Girder Splice Plate ....................................... 51
Figure 3.6: Photo Example of Lateral Bracing to Girder Connection........................ 52
Figure 3.7: Photo Example of Overall View of General Environment of Bridge ...... 52
Figure 3.8: I-Girder Cross-Section Sample Locations ............................................... 54
Figure 3.9: Example of Complete Sample Area Photograph ..................................... 56
Figure 3.10: Example of Closer Perspective Sample Area Photograph ....................... 57
Figure 4.1: Typical Example of a Compact Rust Patina ............................................ 62
Figure 4.2: Typical Example of Small Rust Flakes.................................................... 63
Figure 4.3: Typical Example of Large Thick Rust Flakes ......................................... 63
Figure 4.4: Typical Web Patina of Colorado Bridges ................................................ 66
Figure 4.5: Typical Bottom of Bottom Flange Patina of Colorado Bridges .............. 68
Figure 4.6: Typical Flange Patina of Connecticut Bridges ........................................ 70
Figure 4.7: Typical Web Patina of Connecticut Bridges............................................ 70
Figure 4.8: Typical Web Patina of Iowa Bridges ....................................................... 72
Figure 4.9: Typical Interior Flange Patina of Iowa Bridges....................................... 73
Figure 4.10: Typical Interior Web Patina of Bridge MN 04019 .................................. 74
Figure 4.11: Typical Interior Flange Patina of Bridge MN 04019 ............................... 74
xiv
Figure 4.12: Exterior Flange and Web Patinas of the Fascia Girder of Bridge MN
19811 ....................................................................................................... 75
Figure 4.13: Typical Interior Flange and Web Patinas of Bridge MN 19811 .............. 76
Figure 4.14: Typical Flange and Web Patinas of Bridge MN 62861 ........................... 77
Figure 4.15: Typical Flange and Web Patinas of Bridge NC 190083 .......................... 78
Figure 4.16: Typical Exterior Flange and Web Patinas of Bridge NC 1290057 .......... 79
Figure 4.17: Typical Interior Flange Patina of Bridge NC 1290057............................ 79
Figure 4.18: Typical Exterior Flange and Web Patinas of Bridge NC 1290058 .......... 80
Figure 4.19: Typical Interior Flange Patina of Bridge NC 1290058............................ 81
Figure 4.20: Typical Flange and Web Patinas of Bridge NH 017201120011300 ....... 82
Figure 4.21: Typical Interior Flange Patina of Bridge NH 11101120017900 ............. 83
Figure 4.22: Typical Exterior Flange and Web Patina of Bridge NH
11101120017900 ..................................................................................... 83
Figure 4.23: Typical Interior Web Patina of Bridge NH 11101120017900 ................. 84
Figure 4.24: Typical Interior Flange Patina of Bridge NH 017701460003700 ........... 85
Figure 4.25: Typical Exterior Flange and Web Patinas of Bridge NH
017701460003700 ................................................................................... 85
Figure 4.26: Typical Exterior Flange Patinas of Ohio Bridges .................................... 87
Figure 4.27: Typical Interior and Exterior Web Patinas of Ohio Bridges ................... 88
Figure 4.28: Typical Interior Flange Patinas of Ohio Bridges ..................................... 88
Figure 4.29: Objective Manual Ratings, by Agency .................................................... 93
Figure 4.30: Subjective Manual Rating, by Agency .................................................... 94
Figure 4.31: Approximate Percentages of Bridges Washed, by Agency ..................... 96
Figure 4.32: Frequency of Bridge Washing, by Agency .............................................. 96
Figure 4.33: Frequency of Girder Washing, by Agency .............................................. 97
xv
Figure 4.34: Deicing Agent Usage, by Agency with Available Data ........................ 103
Figure 4.35: Average Percent Area of Rust Particles Greater than or Equal to an
1/8 inch, by Cluster ................................................................................ 105
Figure 4.36: Average Percent Area of Rust Particles Greater than or Equal to an
1/8 inch, by Field Bridge ....................................................................... 107
Figure 4.37: Average Percent Area of Rust Particles Greater than or Equal to an
1/8 inch, by Standard Sample Area Location ........................................ 109
Figure 4.38: Average Concentration of Chloride, Nitrate, and Sulfate Ions, by
Cluster .................................................................................................... 113
Figure 4.39: Average Concentration of Chloride, by Field Bridge ............................ 115
Figure 4.40: Average Nitrate Concentration, by Field Bridge ................................... 116
Figure 4.41: Average Sulfate Concentration, by Field Bridge ................................... 117
Figure 4.42: Average Concentration of Chloride, Nitrate, and Sulfate Ions, by
Standard Sample Area Location ............................................................ 119
Figure 5.1: Scatter Plot of Overall Bridge Maintenance Manual Ratings Versus
Average Percent Area of Rust Particles Greater than or Equal to an
1/8 inch for Each Agency/Cluster .......................................................... 124
Figure 5.2: Scatter Plot of Bridge Washing Practice Ratings Versus Average
Percent Area of Rust Particles Greater than or Equal to an 1/8 inch
for Each Agency/Cluster ........................................................................ 127
Figure 5.3: Scatter Plot of Bridge Washing Practice Ratings Versus Average
Chloride Concentrations for Each Agency/Cluster ............................... 129
Figure 5.4: Scatter Plot of Average Bridge Washing Practice Ratings Versus
Nitrate Concentrations for Each Agency/Cluster .................................. 129
Figure 5.5: Scatter Plot of Bridge Washing Practice Ratings Versus Average
Sulfate Concentrations for Each Agency/Cluster .................................. 130
Figure 5.6: Scatter Plot of Corrosive Solids’ Usages Versus Average Percent
Area of Rust Particles Greater than or Equal to an 1/8 inch for Each
Agency/Cluster ...................................................................................... 132
xvi
Figure 5.7: Scatter Plot of Corrosive Brines’ Usages Versus Average Percent
Area of Rust Particles Greater than or Equal to an 1/8 inch for Each
Agency/Cluster ...................................................................................... 132
Figure 5.8: Scatter Plot of Corrosive Solids’ Usages Versus Average Chloride
Concentrations for Each Agency/Cluster .............................................. 134
Figure 5.9: Scatter Plot of Corrosive Brines’ Usages Versus Average Chloride
Concentrations for Each Agency/Cluster .............................................. 135
Figure 5.10: Scatter Plot of Average Chloride Concentration Versus Average
Percent Area of Rust Particles Greater than or Equal to an 1/8 inch
of Each Cluster....................................................................................... 138
Figure 5.11: Scatter Plot of Average Nitrate Concentration Versus Average Percent
Area of Rust Particles Greater than or Equal to an 1/8 inch of Each
Cluster .................................................................................................... 139
Figure 5.12: Scatter Plot of Average Sulfate Concentration Versus Average
Percent Area of Rust Particles Greater than or Equal to an 1/8 inch
of Each Cluster....................................................................................... 139
Figure 5.13: Scatter Plot of Average Chloride Concentration Versus Average
Percent Area of Rust Particles Greater than or Equal to an 1/8 inch
of Each Field Bridge .............................................................................. 142
Figure 5.14: Scatter Plot of Average Nitrate Concentration Versus Average
Percent Area of Rust Particles Greater than or Equal to an 1/8 inch
of Each Field Bridge .............................................................................. 142
Figure 5.15: Scatter Plot of Average Sulfate Concentration Versus Average
Percent Area of Rust Particles Greater than or Equal to an 1/8 inch
of Each Field Bridge .............................................................................. 143
Figure 5.16: Scatter Plot of Average Chloride Concentration Versus Average
Percent Area of Rust Particles Greater than or Equal to an 1/8 inch
of Each Standard Sample Area Location ............................................... 146
Figure 5.17: Scatter Plot of Average Nitrate Concentration Versus Average Percent
Area of Rust Particles Greater than or Equal to an 1/8 inch of Each
Standard Sample Area Location ............................................................ 146
Figure 5.18: Scatter Plot of Average Sulfate Concentration Versus Average Percent
Area of Rust Particles Greater than or Equal to an 1/8 inch of Each
Standard Sample Area Location ............................................................ 147
xvii
Figure 5.19: Scatter Plot of SCR Versus Average Percent Area of Rust Particles
Greater than or Equal to an 1/8 inch of Each Field Bridge .................... 150
Figure 5.20: Scatter Plot of SCR Versus WGCS Rating of Each Field Bridge ......... 151
Figure 5.21: Scatter Plot of WGCS Rating Versus Average Percent Area of Rust
Particles Greater than or Equal to an 1/8 inch of Each Field Bridge ..... 152
Figure 5.22: Scatter Plot of Each Standard Sample Area Location Listed for Each
Corresponding Average Chloride Concentration Versus Average
Percent Area of Rust Particles Greater than or Equal to an 1/8 inch ..... 155
Figure 5.23: Scatter Plot of Each Standard Sample Area Location Listed for Each
Corresponding Average Nitrate Concentration Versus Average
Percent Area of Rust Particles Greater than or Equal to an 1/8 inch ..... 156
Figure 5.24: Scatter Plot of Each Standard Sample Area Location Listed for Each
Corresponding Average Sulfate Concentration Versus Average
Percent Area of Rust Particles Greater than or Equal to an 1/8 inch ..... 156
Figure 6.1: Graph of Average Chloride Concentrations and Percent Area of Rust
Particles Greater than or Equal to an 1/8 inch ....................................... 165
Figure G.1: Average Density of Rust Particles, by Cluster ...................................... 234
Figure G.2: Average Percent Area of Rust Particles Greater than or Equal to an
1/8 inch, by Cluster ................................................................................ 235
Figure G.3: Average Percent Area of Rust Particles Greater than or Equal to a
1/4 inch, by Cluster ................................................................................ 235
Figure G.4: Average Percent Area of Rust Particles Greater than or Equal to a
1/2 inch, by Cluster ................................................................................ 236
Figure G.5: Average Density of Rust Particles, by Field Bridge .............................. 236
Figure G.6: Average Percent Area of Rust Particles Greater than or Equal to an
1/8 inch, by Field Bridge ....................................................................... 237
Figure G.7: Average Percent Area of Rust Particles Greater than or Equal to a
1/4 inch, by Field Bridge ....................................................................... 237
Figure G.8: Average Percent Area of Rust Particles Greater than or Equal to a
1/2 inch, by Field Bridge ....................................................................... 238
xviii
Figure G.9: Average Density of Rust Particles, by Standard Sample Area
Location ................................................................................................. 238
Figure G.10: Average Percent Area of Rust Particles Greater than or Equal to an
1/8 inch, by Standard Sample Area Location ........................................ 239
Figure G.11: Average Percent Area of Rust Particles Greater than or Equal to a
1/4 inch, by Standard Sample Area Location ........................................ 239
Figure G.12: Average Percent Area of Rust Particles Greater than or Equal to a
1/2 inch, by Standard Sample Area Location ........................................ 240
xix
ABSTRACT
The long-term performance of uncoated weathering steel (UWS) bridges in the
United States is being assessed to update the current FHWA technical advisory regarding
the use of UWS in highway bridges. The main purpose of the larger research project, to
which the research described in this thesis contributed, is to develop quantitative
recommendations about environmental conditions and maintenance practices that may be
the most suitable for UWS highway bridges. Prior work included the development of a
national UWS GIS database in order to quantify environments. This database was used to
strategically select 21 UWS bridges for field evaluations in 7 states in order to qualitatively
assess the performance of rust patinas and collect rust samples for assessment using
quantifiable metrics. Rust samples were assessed by evaluating data from clear tape
adhesion tests and ion chromatography analyses. Part of this research also included
collecting and analyzing maintenance data collected from state highway agencies
throughout the United States. This data included information from 34 state highway
agencies’ bridge maintenance manuals and bridge washing practices from 33 state highway
agencies. Deicing agent usage data was also obtained from 39 state highway agencies and
existing databases. Correlations between the different data types that were collected were
assessed to investigate any trends in UWS bridge performance based on environmental
conditions and maintenance practices. The most significant finding from this research
involved differences in UWS performance as quantified by chloride concentrations and
rust particle sizes of surface rust based on interior, sheltered girder locations and exterior,
exposed girder locations. Quantifiable data obtained from this research will be useful for
xx
evaluating UWS bridge performance trends with a larger dataset in order to update national
specifications and maintenance practices involving UWS bridges.
1
Chapter 1
INTRODUCTION
1.1 Project Overview
Uncoated weathering steel (UWS) bridges have been in service in the U.S. since
1964. In the 1980’s, some states reported that the performance of their UWS bridges was
undesirable because they were experiencing faster corrosion rates than expected. Because
of this, research projects were conducted to assess what may cause undesirable
performance of UWS. AISI (1982) initiated a long-term project to study the performance
of UWS in different environments by inspecting 52 highway bridges. Furthermore,
Albrecht and Naeemi (1984) and Albrecht et al. (1989) conducted research that assessed
the performance of UWS and recommended guidelines for design, construction,
maintenance, and rehabilitation of UWS bridges. These studies are what led to the Federal
Highway Administration’s (FHWA) Technical Advisory (TA) 5140.22 issued on October
3, 1989. The TA contains general information on environments where UWS should be used
with caution, such as in marine coastal areas; areas with frequent high rainfall, high
humidity or persistent fog; industrial areas where concentrated chemical fumes may drift
directly onto the structure; grade separations in “tunnel-like” conditions; and low-level
water crossings. This TA mostly provides broad qualitative guidelines regarding the use of
UWS and states that “[f]urther work is needed to quantify and understand the performance
of uncoated weathering steel in a variety of circumstances and conditions.”
2
1.2 Project Objectives and Scope
Research through the Long-term Bridge Performance Program (LTBPP) has been
underway to better understand the performance of UWS in order to revise the FHWA 1989
TA with quantified data. The University of Delaware is working as a subconsultant to
Rutgers University under FHWA Contract #693JJ318F000133 to conduct this research on
assessing the long-term performance of UWS bridges in the U.S. The main goal of that
research project is to provide quantitative guidelines to define environments that cause
undesirable rates of corrosion in UWS bridges as well as develop a comprehensive database
and field inspection protocols for future UWS bridge evaluation. Maximizing opportunities
to collect quantifiable data on UWS bridge performance will provide updates to generic
language used in TA 5140.22 regarding unsuitable environments for UWS to be used.
Phase 1 of this research project consisted of the development of field-test protocols
and a national inventory of UWS highway bridges. Phase 2 of this project then focused, in
part, on creating a national GIS database of UWS bridges to associate various geographic
and climate variables to each specific bridge. Thirteen bridges in five states were then
selected based on a data-driven selection process and a survey of bridge owners to better
understand the most critical issues affecting UWS bridges. Phase 2 also included field
inspections of selected bridges as well as reviewing inspection reports of additional
bridges. The results were then analyzed to identify preliminary correlations between UWS
performance and parameters that were identified and collected. Additional clusters were
then identified for further study in Phase 3 of this research project, which is currently being
conducted and is the focus of this thesis. The specific objectives of Phase 3 include:
1. determining seven clusters that encompass environments of concern for use
of UWS in highway bridges (i.e., deicing, coastal, and a combination
deicing and coastal) and selecting bridges within them for field evaluations
and additional data collection.
3
2. performing field evaluations of field bridges selected from each of the seven
clusters.
3. updating LTBPP protocols developed in Phase 1 for field evaluations of
UWS bridges.
4. conducting a survey regarding maintenance practices and deicing agent
usage for each agency in the U.S.
5. analyzing the results to identify preliminary correlations between bridge
maintenance and deicing practices, environmental conditions surrounding
UWS bridges, and UWS bridge performance.
The specific objectives of the research reported here are to contribute towards the above
goals for Phase 3 by:
1. assisting in selecting and evaluating field bridges from each of the seven
clusters.
2. summarizing and synthesizing past research related to this research project
in a literature review.
3. conducting a survey regarding maintenance practices and deicing agent
usage for each agency in the U.S.
4. compiling and interpreting tape test and IC analysis results.
5. analyzing results from the survey, tape test, and IC analyses to identify
preliminary correlations between bridge maintenance and deicing agent
usage practices with UWS performance.
1.3 Thesis Organization
The thesis organization is as follows:
• Chapter 1 includes an overview of the research background,
objectives, scope, and organization.
• Chapter 2 discusses background information about UWS and a
literature review of past research conducted relative to UWS.
• Chapter 3 reviews the methodology behind bridge selection, field
evaluation of bridges, as well as data collection and analysis.
4
• Chapter 4 presents the results of the different data types that were
collected.
• Chapter 5 analyzes correlations between the results presented in
Chapter 4.
• Chapter 6 summarizes work carried out in Phase 3, findings from
Chapters 4 and 5, as well as proposes future work.
5
Chapter 2
BACKGROUND
2.1 Uncoated Weathering Steel Background
Weathering steel, originally trademarked as Cor-Ten, is a high strength, low alloy
steel that was first developed by U.S. Steel in the 1930s. In 1964, UWS was developed for
application in bridges and has currently been used as a high-performance steel (HPS) after
further development in the 1990s. One purpose of developing this new material was to
avoid painting the steel due to its capability of being able to form a stable layer of rust
when exposed to weather. The thin layer of rust that coats the steel is known as the patina,
which protects against future corrosion. The patina is produced by the concentration of
alloying elements, such as copper, chromium, nickel, phosphorous, silicon, and manganese
that make up 3-5 wt.% of the steel material. The main goal of UWS is to reduce the overall
costs of construction and maintenance by reducing the thickness and weight of steel
required due to improved mechanical properties as well as by avoiding the need to paint
the steel.
2.1.1 Environmental Effects on Corrosion of UWS
When exposed to different environments, corrosion resistance characteristics of
UWS are affected in various ways. The corrosion rate of UWS increases when the relative
humidity exceeds about 70%. A high percentage of relative humidity effects the time of
wetting (TOW), which is the length of time a metal remains wet enough to corrode at an
appreciable rate (Albrecht et al., 1989). In order to achieve the most desired protective
capability of the rust layer, wet and dry cycles of nearly equal length should allow the
6
patina to form and provide satisfactory corrosion resistance (Raman et al., 1988), yet it is
noted that corrosion cannot occur in the absence of a wetting cycle.
Three main categories of environments that have often been used to describe UWS
performance are marine, industrial, and rural. Albrecht and Naeemi (1984) describes these
environments and the effects they have on corrosion of UWS. Rural environments are
usually the least aggressive towards causing corrosion issues due to relatively low amounts
of air pollutants, such as sulfur oxides and chlorides. Industrial environments cause
corrosion issues due to the sulfur oxides produced by burning automotive and fossil fuels.
The sulfur oxides tend to only be aggressive towards corrosion when the relative humidity
exceeds 60%. Coastal environments contain airborne salt sprays containing chloride that
can keep the UWS damp for long periods of time. Shorter drying cycles as well as the
presence of salt crystals on the UWS in this environment inhibits the ability for the
protective rust layer to form and results in poor corrosion resistance. Morcillo et al. (2013)
summarizes how differences in chloride content from airborne salt spray, sulfur oxides
from industrial pollution, and TOW can cause variations in corrosion characteristics.
Furthermore, the chemical composition of the steel as well as its orientation and exposure
to the atmosphere also contribute to varying corrosion characteristics. These factors cause
variability in the protective capabilities of the patina that forms on UWS and is why further
research has been required.
2.1.2 Advantages of UWS
One of the main advantages of UWS is the savings it can provide in terms of
construction costs. Morcillo et al. (2013) states that early Cor-Ten steel provided 30%
improvement in mechanical properties as compared to carbon steel (CS). This is due to
higher phosphorous content in early Cor-Ten steel, which raised the yield and tensile
7
strengths (Morcillo et al., 2014). Therefore, the thickness and weight of the steel could be
reduced to provide cost savings on materials.
In terms of maintenance costs, Albrecht et al. (1989) notes that UWS can eliminate
the need for initial and periodic painting of the superstructure due to its enhanced
atmospheric corrosion resistance. Avoiding painting and repainting bridges also eliminates
the need to close lanes and disrupt traffic during painting operations. The corrosion
resistance of UWS is about equal to two times that of copper bearing CS, which is
equivalent to four times CS without copper (Albrecht and Naeemi 1984). Morcillo et al.
(2013) mentions that UWS bridges are more economical than painted CS bridges after
about 15 years in moderately aggressive environments due to UWS not requiring paint to
prevent corrosion.
2.1.3 Disadvantages of UWS
Although UWS can be beneficial in terms of cost savings and atmospheric
corrosion resistance, there are also some disadvantages. When considering TOW and
moisture containing chlorides, structural detailing of UWS bridges becomes a concern.
Expansion joints are known to have issues with leaking. Therefore, UWS within the
vicinity of leaking expansion joints tends to perform poorly and thus it is recommended to
paint the ends of girders (FHWA 1989). Albrecht and Naeemi (1984) mentions how girder
ends on either side of expansion joints have been painted to prevent progressive corrosion
of UWS in these areas. Albrecht et al. (1989) also advises that in order to avoid these
problems created by leaking joints, bridges should have a continuous superstructure, fixed
or integral bearings at piers and abutments, and no bridge deck expansion joints. Because
of these issues involving leaking joints with UWS bridges, design limitations must be
considered and can hinder the usage of UWS in certain scenarios. It should be noted that
8
these structural detailing concerns are not specific to UWS bridges and can affect all types
of bridges.
One of the major disadvantages is the uncertainty regarding performance of UWS
bridges based on exposure conditions as mentioned in Section 2.1.1. The most severe
exposure conditions that have been found to cause issues with rust patina performance
include environments where high concentrations of chloride are present, such as coastal
environments and environments where deicing agents are used. This thesis mainly focuses
on attempting to resolve these uncertainties regarding UWS bridge performance in coastal
and deicing environments.
2.2 Methods Previously Used for Assessing UWS
The proceeding section focuses on four methods most commonly used for
assessing UWS that were described in reviewed literature. These methods include visual
inspection, clear tape adhesion test, ion chromatography (IC) analysis, and x-ray
diffraction (XRD) analysis.
2.2.1 Visual Inspection
In the midst of developing more practical methods for quantitatively evaluating
UWS, visual inspections have been utilized to assess the protectiveness of the rust layer.
Hara et al. (2006) reports on how the appearance of the rust layer has been categorized into
5 indices developed by the Japan Iron and Steel Federation (JISF) and Japan Association
of Steel Bridge Construction (JASBC). The indices are based on the rusts’ flaking
characteristics, size, color, and thickness. The appearance index is correlated with
corrosion rates of UWS that are based on thickness loss vs. exposure time, which allows
for corrosion rates of UWS to be estimated Hara et al. (2006).
9
Crampton et al. (2013) reported on Iowa DOT’s evaluation of their UWS bridge
inventory. Visual inspection methods were used to assess the quality of UWS patinas in
environments with deicing salt usage (in Iowa, specifically). The performance of weathering
steel patinas was assessed according to color of the rust and size of the scale (referred to as rust
flakes in this thesis). Crampton et al. (2013) refers to the National Cooperative Highway Research
Program’s (NCHRP) guidelines to evaluate the condition of the oxide layer on weathering steel
structures based on color and texture (Albrecht and Naeemi, 1984). In terms of color of the oxide
layer:
• yellow orange indicated initial stages of exposure
• light brown indicated early stages of exposure
• chocolate brown to purple brown indicated development of protective
oxide
• black indicated nonprotective oxide
In terms of texture of the oxide layer:
• tightly adherent, capable of withstanding hammering or vigorous wire
brushing indicated a protective oxide
• dusty indicated early stages of exposure which should change after a
few years
• granular was a possible indication of problems depending on length of
exposure and location of structure
• small flakes (6mm (~1/4 in.) in diameter) was an initial indication of
nonprotective oxide
• large flakes (12mm (~1/2 in.) in diameter or greater) indicated
nonprotective oxide
• laminar sheets or nodules indicated nonprotective oxide and severe
corrosion
10
Crampton et al. (2013) notes that good patina performance was typically indicated
by a fine grained, dark brownish-black, tightly adhered, stable rust layer on the surface of
the weathering steel. Poor patina performance was typically indicated by the formation of
loose rust scale caused by the formation of a less protective crystalline oxide rust layer. It
was also found that rust scale appearance is proportional to chloride content where
weathering steel surfaces with higher concentrations of chloride in the oxide layer were
found to have developed larger, thicker rust flakes in the patina.
The colors of corrosion products (ferrous oxyhydroxides) relative to UWS have
been discussed by Cornell and Schwertmann (2006). Goethite and akageneite appear as a
yellow-brown color, lepidocrocite appears as an orange color, maghemite appears as a
brown to brownish red color, and magnetite appears black. These corrosion products are
discussed in more detail in Section 2.2.4 and Section 2.3.
AASHTO also has methods established for visually inspecting UWS bridge girders;
however, the methods are not specific to UWS and encapsulate all steel open girders
regardless of protection system (AASHTO, 2013; 2014; 2017). Condition state (CS)
ratings are used to visually assess performance of the girders. CS1 refers to good condition,
CS2 refers to fair condition, CS3 refers to poor condition and CS4 refers to severe
condition. In terms of corrosion, CS1 includes no visually observed corrosion, CS2
includes visual observation of freckled rust indicating that corrosion of the steel has
initiated, CS3 includes visual observation of section loss or pack rust being present, and
CS4 includes visual observation of corrosion defects that impact strength or serviceability.
Each CS is measured in terms of the sum of all the lengths in feet of visually observed
defects along each girder.
11
2.2.2 Clear Tape Adhesion Test
One method for quantitatively evaluating the performance of UWS is known as the
clear tape adhesion test. McConnell et al. (2014 a) discusses how this method can be used
to analyze the sizes and spatial densities of corrosion products using digital image
processing. Standard procedures for the clear tape adhesion test have been developed in
order to provide simple evaluation methods (McConnel and Shenton, 2018). The procedure
includes adhering a 4 to 5 in. long piece of clear tape to the surface of the UWS girder.
Next, a rubber “J” roller is used to roll over the tape with 10 passes using firm pressure
(e.g., approximately 2 lbs. of normal force through the roller). Then the tape is slowly
peeled off, taking no longer than approximately 5 seconds to remove with a shallow angle
between the tape and the steel surface. The tape sample is then adhered to a clean sheet of
white paper to be used for image processing. In Phase 2 of this research project it was found
that evaluating the percent area of rust particle sizes that adhered to the tape, particularly
the percent area of rust particles that were greater than or equal to an 1/8 inch, correlated
with inspectors’ visual assessments of UWS bridges found in inspection reports
(McConnell et al., 2014 b).
2.2.3 Ion Chromatography (IC) Analysis
In Phase 2 of this research project, IC analyses were performed on rust samples
collected from each UWS bridge that was evaluated. The chloride, nitrate and sulfate ion
concentrations were recorded and compared with other data types in order to assess
correlations related to corrosion; however, no strong correlations were found (McConnell
et al., 2014 b).
12
2.2.4 XRD Analysis
Collection of rust samples from UWS bridges are being used with X-ray Diffraction
(XRD) analysis to assess the corrosion products that form in different environments and at
different stages of corrosion. XRD analysis can be used to determine the proportions of
various ferrous oxyhydroxides found in these rust samples (McConnell et al., 2014 a).
Morcillo et al. (2014) states that the corrosion products form as a result of reactions
between iron and the environment, therefore, the composition of the rust layer varies
depending on surface electrolytes and atmospheric exposure conditions. The three main
ferrous oxyhydroxides that have been found to form on UWS are goethite (alpha-FeOOH),
akageneite (beta-FeOOH), and lepidocrocite (gamma-FeOOH). Lepidocrocite is
considered the initial corrosion product that forms on UWS. Goethite is formed in acidic
solutions and is transformed from lepidocrocite. The formation of goethite has been found
to be dependent on atmospheric sulfate concentrations and temperature (Morcillo et al.
2014). Akaganeite has been found in coastal environments where the surface electrolytes
contain chlorides. Although XRD analysis can be used to determine the proportions of
these ferrous oxyhydroxides, Morcillo et al. (2014) mentions that it has issues
distinguishing between magnetite and maghemite, which are two minor corrosion products
found in UWS. Because of this, Infrared Spectroscopy (IR) and Mossbauer Spectroscopy
(MS) analysis methods also tend to be used to determine the composition of rust samples.
The combination of these three methods allows for a more accurate correlation between
the corrosion products formed on UWS and atmospheric exposure conditions.
2.3 Past Field Studies
As mentioned in Section 1.1, research projects conducted by AISI (1982), Albrecht
and Naeemi (1984), and Albrecht et al. (1989) are what led to the FHWA TA (1989). The
TA concluded that UWS will perform satisfactorily in atmospheric chloride levels
13
averaging up to at least 0.5 mg/100cm2/day. Also, the United Kingdom Standard BD/7/01
recommended that UWS should not be used when the sulfur trioxide level exceeds an
average of 2.1 mg/100cm2/day; however, this value is rarely exceeded in the U.S.
(Highways Agency, 2001). The accuracy of these limits is not well established as well as
the influence of many other variables, which is why there is a need for further research.
The proceeding sections will focus on research performed after the FHWA advisory that
were done to attempt to better quantitatively define these environmental guidelines.
2.3.1 Coastal Environment Field Studies
One of the environments in which field studies have been conducted is coastal
environments. Coastal environments have not been well quantified and are typically
classified simply as being close to the ocean. As a result of being close to the ocean, these
environments have relatively high chloride concentrations from air-borne salt particles. The
chloride content of the environments was assessed in order to correlate this atmospheric
condition with corrosion characteristics of UWS. Field studies that were performed in
coastal environments focused on the effects chloride concentrations and different chemical
compositions of UWS had on atmospheric corrosion rates, the rust phases that formed on
UWS, and the relationship of chloride concentrations and physical corrosion
characteristics.
2.3.1.1 Relationship Between Atmospheric Corrosion Rates and Chloride
Concentrations
Four field studies focused on evaluating atmospheric corrosion rates of UWS in
coastal environments. These studies include Cook et al. (1998), Oh et al. (1999), Diaz et
al. (2018), and Saha (2013) compared UWS specimens exposed in various coastal
environments.
14
Cook et al. (1998) observed atmospheric corrosion rates of ASTM A-588 UWS
specimens (note specific steel specifications are reported herein wherever they are given
in the cited literature) exposed in three different coastal environments in México, one
coastal environment in Kure Beach, North Carolina and one industrial environment in
Bethlehem, Pennsylvania. Specimens that were exposed in atmospheres with higher
chloride concentrations, such as in Veracruz, Mexico (5.20 mg/100cm2/day) and Kure
Beach, North Carolina (3.11 mg/100cm2/day) experienced higher rates of atmospheric
corrosion (207 µm/y and 164 µm/y, respectively) as compared to specimens exposed in
atmospheres with lower chloride concentrations, such as in Campeche, Mexico (0.45
mg/10cm2/day with a corrosion rate of 15 µm/y). The study also concluded that
environments, such as Coatzacoalcos, Mexico (chloride concentration of 0.90
mg/100cm2/day) with relatively higher mean annual temperature (26°C, 79°F), relative
humidity (75%), and TOW (500 hours/”mth”, where “mth” is assumed to be months based
on typical TOW numbers for coastal environments in the United States) can cause
increased corrosion rates of UWS (300 µm/y). The environmental conditions mentioned
from the Cook et al. (1998) study were obtained from monitoring the exposure sites over
the course of three years.
Oh et al. (1999) performed a field study similar to Cook et al.’s (1998) in which
UWS specimens (ASTM A-242 and A-588), a plain carbon steel specimen, and a copper
bearing steel (steel with copper added to increase corrosion resistance) specimen were
exposed to a coastal environment in Kure Beach, NC (chloride concertation of 1.07
mg/100cm2/day). The specimens were also exposed to industrial and rural environments in
Bethlehem, PA and Saylorsburg, PA, respectively. The field study found that when
comparing corrosion rates of UWS specimens with the same chemical compositions in
each of the three environments, specimens exposed in the coastal environment had higher
15
corrosion rates (between 5.57 µm/y and 10.11 µm/y) than the ones exposed in the industrial
(between 1.33 µm/y and 1.43 µm/y) and rural environments (between 1.85 µm/y and 2.62
µm/y).
Diaz et al. (2018) also compared the corrosion rates of ASTM A-588 and ASTM
A-242 UWS specimens between environments with varying chloride concentrations in
Spain. Within the first year of exposure, UWS specimens in the coastal environments of
Cabo Vilano-1 (chloride concentration of 0.204 mg/100cm2/day) and Cabo Vilano-2
(chloride concentration of 0.714 mg/100cm2/day) experienced corrosion rates of about 30
µm/y and 50 µm/y, respectively. Similarly, Wang et al. (2013) assessed the corrosion rates
of five different UWS specimens exposed for five years in the coastal environment of
Qingdao, Japan (chloride deposition of 0.250 mg/100cm2/day) and reported rates of about
0.05 mm/y between each specimen.
Saha (2013) evaluated the corrosion rates of UWS specimens exposed in the coastal
environment of Digha, India (0.83 mg NaCl/100cm2/day and trace amounts of sulfur
oxide) and compared them with specimens exposed in Chennai, India (0.42 mg
NaCl/100cm2/day and 16.5 mg sulfur oxide/100cm2/day) and Jamshedpur, India (trace
amounts of NaCl and 22 mg sulfur oxide/100cm2/day). After the first 18 months of
exposure, the UWS specimens exposed in the coastal environment of Digha had the highest
corrosion rates (20.2 µm/y) as compared to Chennai (13.4 µm/y) and Jamshedpur (10.3
µm/y). After 42 months of exposure, the corrosion rate continued to increase for UWS
specimens exposed in the coastal environment of Digha (18.2 µm/y), while corrosion rates
began to stabilize for specimens exposed in the two industrial sites of Chennai and
Jamshedpur (12.3 µm/y and 9.5 µm/y, respectively). Saha (2013) claims that the increasing
corrosion rate after 42 months of exposure is due to the high concentration of chloride in
the atmosphere.
16
2.3.1.2 Rust Phases Formed in Coastal Environments
Furthermore, some field studies also evaluated the rust phases that formed on UWS
specimens in coastal environments. These studies include Oh et al. (1999), Wang et al.
(2013), Diaz et al. (2018), Kamimaru et al. (2005), and Hara et al. (2006). Each of these
studies attempted to draw correlations between corrosion products and corrosion rates of
UWS.
Oh et al.’s (1999) study found that UWS specimens (ASTM A-242 and A-588)
exposed in the coastal environment of Kure Beach, NC had the highest fractions of
superparamagnetic goethite (~80%) relative to the other rust products that formed
(magnetic goethite, lepidocrocite, and maghemite) as compared to the copper bearing
specimen (29%). The copper bearing specimen also exhibited the highest corrosion rate in
the coastal environment (>50 µm/y) as compared to the UWS specimens, which ranged
from about 5 µm/y to 20 µm/y. Oh et al. (1999) states that an increase in the fraction of
superparamagnetic goethite decreases the mean particle size of goethite. This can enhance
the function of the protective rust layer by densely compacting rust particles which can
prevent water and oxygen penetration to the steel. Therefore, Oh et al. (1999) concludes
that the corrosion rate may be related to the fraction of superparamagnetic goethite that
forms in the inner layer of rust because of its protective capabilities. Wang et al. (2013)
also notes how goethite is the most stable, compact, and dense corrosion product formed
by UWS. Alloying additions in UWS result in goethite and lepidocrocite corrosion
products that are denser and more stable than ones that form on CS, much like Oh et al.
(1999) reported.
Oh et al. (1999), Wang et al. (2013), and Diaz et al (2018) each reported that the
main corrosion products that formed on all of the UWS specimens, independent of
exposure conditions were lepidocrocite, goethite and spinel-type iron oxide. However,
17
Diaz et al. (2018) also reported the presence of akaganeite on UWS specimens exposed in
Cabo Vilano-2, which has the highest chloride deposition of 0.714 mg/100cm2/day.
Akaganeite formed in the innermost region of the rust layer due to the accumulation of
chloride ions. Notable pitting was observed in this region using polarized light microscopy
to view cross-sections of the rust layers.
2.3.1.3 Goethite/Lepidocrocite Relation to Protective Ability Index in Coastal
Environments
To further analyze corrosion rates in coastal environments, Kamimaru et al. (2005)
performed field studies involving corrosion of UWS in Japan. UWS specimens (JIS SMA
490AW) were exposed to atmospheres with different amounts of air-borne sea salt
particles. The corrosion products formed on the UWS specimens were analyzed using
XRD. The mass ratio of crystalline goethite to lepidocrocite (goethite/lepidocrocite was
found to be closely related to corrosion rates of UWS when the amount of air-borne salt
was less than 0.2 mg NaCl/100cm2/day. However, when the air-borne salt concentrations
were more than 0.2 mg NaCl/100cm2/day, such as in coastal environments, the mass ratio
of crystalline goethite to the total mass of lepidocrocite, akaganeite, and iron oxide
(expressed as goethite/lepidocrocite*) was found to have a correlation with the rate of
corrosion. Corrosion rates of more than 0.01 mm/year were observed when
goethite/lepidocrocite* was less than 1 and when specimens were exposed in coastal
environments with air-borne salt concentrations greater than 0.2 mg/100cm2/day.
Kamimaru et al. (2005) concluded that these correlations present a possibility for
evaluating the protective ability of the patina formed on UWS in coastal environments with
relatively higher chloride concentrations.
Hara et al. (2006) furthered Kamimaru et al.’s (2005) study of assessing
correlations between corrosion rates of UWS bridges with JIS G3144 type (SMA490W)
18
weathering steel exposed in coastal environments in Japan and the composition of the rust
layers that formed. The bridges located in coastal environments were exposed to air-borne
sea salt concentrations of more than 0.1 NaCl mg/100cm2/day. The goethite/lepidocrocite*
of the rust layer that formed on each bridge was analyzed by collecting rust samples and
using XRD. Hara et al. (2006) found that when goethite/lepidocrocite* is less than 1, the
corrosion rate can be classified by the mass ratio of akaganeite and iron oxide to the total
mass of lepidocrocite, akaganeite, and iron oxide (expressed as (akageneite + iron
oxide)/lepidocrocite*). Whether the corrosion rate is more or less than 0.01 mm/y is
determined by the ratio of (akageneite + iron oxide)/lepidocrocite* being greater than or
less than 0.5, respectively. Hara et al. (2006) then concluded that both
goethite/lepidocrocite* and (akageneite + iron oxide)/lepidocrocite* are useful for
quantitatively evaluating the protectiveness of the patina formed on UWS bridges.
2.3.1.4 Effects on Corrosion Rates Based on Chemical Composition of UWS in
Coastal Environments
Two field studies, Wang et al. (2013) and Cano et al. (2017) evaluated the effects
of chemical compositions of UWS on corrosion when exposed in coastal environments.
Wang et al. (2013) tested UWS specimens (W400QN, W450QN, SPA-H, 09CuPTiRE and
WGJ510C) exposed for 6 years in the coastal environment of Qingdao, Japan (chloride
deposition of 2.50 mg/100cm2/day). Wang et al. (2013) reported that chromium could be
an effective alloying element in UWS to reduce corrosion rates when exposed to higher
atmospheric chloride concentrations. The UWS specimen with the highest chromium
content (0.60 wt.%) showcased the lowest corrosion rates after 5 years of about 0.02 mm/y
as opposed to the UWS specimen with the lowest chromium content (0.013 wt.%) which
showcased corrosion rates after 5 years of about 0.03 mm/y.
19
Cano et al. (2017) performed a field study on UWS specimens (ASTM A-242 and
A-588) with varying chemical compositions exposed in two different locations in Cabo
Vilano, Spain (Cabo Villano-1 and Cabo Vilano-2 had chloride depositions of 0.20
mg/100cm2/day and 0.71 mg/100cm2/day, respectively). Cano et al. (2017) concluded that
the addition of 0.5 wt.% chromium noticeably improved the UWS specimen’s atmospheric
corrosion resistance. Two UWS specimens with 0.50 wt.% of chromium showcased
corrosion rates of about 39 μm/y for 2 years of exposure (chloride depositions of 0.71
mg/100cm2/day) and 16 μm/y for 3 years of exposure in a less severe environment relative
to their specimens exposed for 2 years (chloride depositions of 0.20 mg/100cm2/day). This
was compared to two UWS specimens with 0.08 wt.% chromium that had corrosion rates
of about 44 μm/y for 2 years of exposure in an environment with chloride depositions of
0.71 mg/100cm2/day and 18 μm/y for 3 years of exposure in an environment with chloride
depositions of 0,20 mg/100cm2/day. More importantly, Cano et al. (2017) found that the
best atmospheric corrosion resistance was obtained from UWS specimens with a nominal
value of 3.0 wt.% of nickel. One specimen, with an actual composition of 2.83 wt.% of
nickel, had corrosion rates of about 32 μm/y for 2 years of exposure in an environment
with chloride depositions of 0.71 mg/100cm2/day and 13 μm/y for 3 years of exposure in
an environment with chloride depositions of 0.20 mg/100cm2/day. This was compared to
two UWS specimens with 0.12 wt.% nickel that had corrosion rates of about 44 μm/y for
2 years of exposure in an environment with chloride depositions of 0.71 mg/100cm2/day
and 18 μm/y for 3 years of exposure in an environment with chloride depositions of 0.20
mg/100cm2/day.
20
2.3.1.5 Relationship Between Physical Corrosion Characteristics and Chloride
Concentrations
Some field studies focused on physical characteristics of rust layers that formed on
UWS specimens that were exposed in coastal environments. Two of these studies were
done along the Gulf of Mexico in the United States (McDad el al., 2000 and Raman, 1998).
A third was conducted in Spain (Díaz et al., 2018) and a fourth was conducted in India
(Saha, 2013).
McDad et al. (2000) assessed 40 bridges that used UWS and were located in severe
coastal environments as well as other environments within the state of Texas. Rust samples
were collected and section loss of the steel due to corrosion was assessed using ultrasonic
testing. It was found that all thickness measurements were equal to or greater than the
specified nominal thicknesses. McDad et al. (2000) concluded that this is due to the steel
plates of the girders being rolled with a thickness that is slightly greater than the nominal
thickness. Also, when steel rusts, the rust that forms is thicker than the base metal that it
replaces, thus increasing the thickness. The chloride concentrations that were also
measured from the rust samples were found to be inconsistent. Therefore, no correlations
between chloride concentration and corrosion could be made due to no observed section
loss and inconsistent chloride concentrations.
Raman (1988) also assessed 7 UWS bridges built with ASTM A-588 in coastal
environments, specifically within the state of Louisiana. Rust samples were taken to find a
correlation between rust particle sizes and chloride levels in the rust. A pitting evaluation
was performed and the morphology of the rust was determined using scanning electron
microscopy (SEM) and energy dispersive X-ray analysis (EDXA). Raman (1988) found
that higher chloride concentrations of 2.5 ppm to 6.5 ppm found in the rust resulted in
larger rust particles of a maximum size of 5.0 mm and an average size of 3.0 mm. Lower
21
chloride of 0.5 ppm to 1.5 ppm only resulted in rust particles of a maximum size of 0.75
mm and an average size of 0.5 mm.
These two studies (McDad et al., 2000 and Raman, 1988) give contradictory results
based on similarities between the coastal environments they were performed in. Both field
studies were performed in areas along the Gulf of Mexico, yet McDad et al. (2000) reported
increases in steel thicknesses while Raman (1988) reported instances of section loss and
flaking of large rust particles (maximum size of 5.0 mm and average size of 3.0 mm) in
atmospheres with relatively high chloride concentrations (2.5 ppm to 6.5 ppm). The UWS
bridges McDad et al. (2000) evaluated were older (about 20 years old) as compared to the
ones Raman (1988) inspected (about 12 years old). This is also contradictory of their results
being that UWS bridges that have been in service longer tend to experience more section
loss. It would have been helpful to know the chloride concentrations from the UWS bridges
evaluated by McDad et al. (2000) in order to make comparisons with the chloride
concentrations reported in the Raman (1988) study. One conclusion that can be drawn from
both of these studies is that when UWS is exposed to the sun and rain in these
environments, a protective oxide forms and rust particles are prevented from growing into
coarse flakes. Raman (1988) notes that this is due to the wet-dry cycle the UWS is able to
experience when exposed in these situations, such as on exterior portions of fascia girders.
The interior locations of bridge girders do not experience the same natural wet-dry cycle
as the exterior portions of the fascia girders and were found to perform worse relative to
the exterior locations. Raman (1988) indicates that rust formed at interior (sheltered)
locations tended to be “flaky or sheet-type”. Raman (1988) also mentions that chloride and
salt accumulation was higher at interior girder locations.
Saha (2013) researched UWS specimens exposed from 18 to 42 months within
various environments in India. One of these environments was the coastal environment of
22
Digha, India (0.83 mg NaCl/100cm2/day). After 42 months of exposure, Saha (2013)
reported that the UWS specimens exposed in Digha had an appreciable difference in oxide
film morphology as compared to specimens exposed at the other two industrial
environment test sites. An uneven dark brown, coarse granular oxide film layer had
developed on the UWS specimens. More pitting with a blackish appearance was also
observed on the specimens exposed in the coastal environment. Refer to section 2.2.1 for
information regarding assessments of UWS performance in terms of the color of oxide
layers formed on rust patinas.
Research was conducted by Díaz et al. (2018) on ASTM A-242 and ASTM A-588
UWS specimens in different types of environments within Spain. Visual inspection of the
UWS specimens was performed after 5 years of exposure. A tape test was used to visually
inspect the rust texture of the outermost surface of the UWS specimens. The morphology
of the rust was analyzed using a SEM. This field study found that when both types of UWS
were exposed to atmospheres with higher chloride concentrations (0.204 mg/100cm2/day),
the grain size of the rust increased with the corrosivity of the atmosphere. However, the
color of the rust was found to be similar between the different environments.
2.3.2 Industrial Environment Field Studies
Field studies of UWS were conducted in industrial environments, which are
typically classified as having relatively high sulfur oxide concentrations as opposed to
coastal, and rural environments. Therefore, the sulfur oxide concentrations of the
environments were assessed in each study to draw correlations between this atmospheric
condition and corrosion characteristics of UWS. Some of the studies focused on the
different rust phases that formed on the steel, while others focused on the effects of
23
corrosion rates based on sulfur oxide concentrations and varying chemical compositions of
the steel.
2.3.2.1 Relationship Between Atmospheric Corrosion Rates and Sulfur Oxide
Concentrations
Díaz et al. (2018) performed a field study that assessed the corrosion of UWS
specimens (ASTM A-242 and A-588) exposed at six different test sites, two of them being
industrial environments at Avilés, Spain and Kopisty, Czech Repblic, with higher sulfur
oxide contents (0.0464 and 0.1420 mg/100cm2/day, respectively) than the other four test
sites: one in Pardo, Spain (0.0028 mg/100cm/day), one in Madrid, Spain (0.0080
mg/100cm2/day), and two in Cabo Vilano, Spain (0.0066 mg/100cm2/day). Díaz et al.
(2018) reported the first-year corrosion rates of UWS specimens was about 25 μm/y at the
industrial environment test sites of Avilés, Spain and Kopisty, Czech Republic. This was
higher than the rural (Pardo, Spain) and urban (Madrid, Spain) test sites (about 10 μm/y),
but less than the marine test sites of Cabo Vilano-1 and Cabo Vilano-2 (about 30 μm/y and
50 μm/y, respectively).
Saha (2013) also conducted a field study that assessed UWS specimens exposed in
industrial environments of Chennai, India (0.42 mg NaCl/100cm2/day and 16.5 mg sulfur
oxide/100cm2/day) and Jamshedpur, India (trace amounts of NaCl and 22 mg sulfur
oxide/100cm2/day). Similar to Diaz et al. (2018), Saha (2013) found that after 42 months
of exposure, UWS specimens exposed in Chennai and Jamshedpur had lower corrosion
rates (12.1 μm/y and 9.5 μm/y, respectively) as compared to the specimens exposed in the
coastal environment of Digha, India (18.2 μm/y) with 0.83 mg NaCl/100cm2/day and trace
amounts of sulfur oxide. Furthermore, the corrosion rate was found to have stabilized after
42 months of exposure in the industrial environments (steady corrosion rate of <12 μm/y
achieved at sulfur oxide of 0.02-0.05 mg/100cm2/day), whereas the corrosion rate
24
continued to increase with UWS specimens exposed in the coastal environment. Saha
(2013) concluded that the lower corrosion rates observed with WS specimens exposed in
the industrial environments was due to the higher atmospheric sulfur oxide concentrations
present; however, it is noted that this may be due to coupled differences in sulfur oxide and
chloride concentrations.
Wang et al. (2013) assessed UWS specimens (W400QN, W450QN, SPA-H,
09CuPTiRE and WGJ510C) exposed at three different test sites in Japan. The sulfur oxide
depositions were 4.49 mg/100cm2/day in Qingdao, 6.96 mg/100cm2/day in Jiangjin, and
0.98 mg/100cm2/day in Qionghai. Wang et al. (2013) found, similarly to Diaz et al. (2018)
and Saha (2013), that steel specimens exposed in industrial environments with higher sulfur
oxide concentrations had higher corrosion rates in the initial corrosion stages. UWS
specimens exposed in Jiangjin, which had the highest sulfur oxide concentration also had
the highest corrosion rates in the initial corrosion stages (between 0.07 and 0.05 mm/y),
whereas UWS specimens exposed in Qingdao and Qionghai had initial corrosion rates of
about 0.05-0.06 and 0.03 mm/y, respectively. However, Wang et al. (2013) notes that the
effects of sulfur oxide decreased as the protective rust layer forms and exposure time
prolongs (i.e., the rate of corrosion decreased). This can be seen where the corrosion rates
of UWS specimens after 5 years exposure in both Jiangjin and Qingdao were between 0.02
and 0.03 mm/y, while in Qionghai they were between 0.01 and 0.015 mm/y. Even though
Jiangjin had higher sulfur oxide concentrations than Qingdao as well as higher initial
corrosion rates after the first year of exposure, both corrosion rates after 5 years of exposure
began to reach a steady state of around 0.02 mm/y.
25
2.3.2.2 Rust Phases Formed in Industrial Environments
Díaz et al. (2018) and Wang et al. (2013) both assessed the rust phases formed on
UWS specimens after 5 years exposure in multiple environments, including industrial
environments. In each of the field studies it was found that the rust consisted of two layers
with the inner layer being responsible for protection against atmospheric corrosion. It was
also found that the rust layers were mainly composed of ferric oxyhydroxides, an
amorphous substance, and spinel type iron oxides in some cases. The main ferric
oxyhydroxide structures that formed in the industrial environments were goethite and
lepidocrocite. Each of the field studies focused on how atmospheric conditions affected the
composition of the rust layer and in turn affected the rate of corrosion.
Díaz et al. (2018) found that the proportions of goethite in the industrial
environments was 33-36 wt-%, which was higher than those found in the other
environments with lower sulfur oxide concentrations (25-28 wt-%). It was then concluded
that atmospheric sulfur oxide facilitates the dissolution of lepidocrocite and accelerates the
transformation of lepidocrocite to goethite (Díaz et al., 2018). Wang et al. (2013) concluded
that the pollution of sulfur oxide strongly influences the corrosion behavior in the initial
stages. When the transformation of lepidocrocite to goethite is accelerated due to high
sulfur oxide deposition the corrosion rate in the initial corrosion stages is also accelerated.
However, Wang et al. (2013) notes that as exposure time increases, the increase in the
relative abundance of goethite enhances the corrosion resistance of UWS because of
goethite’s stability, compactness, and density. Wang et al. (2013) found that the relative
abundance of goethite on UWS specimens exposed in Jiangjin was higher than the other
two sites. This coincided with a noticeable decrease in the corrosion rates of UWS
specimens after 5 years of exposure at this test site.
26
2.3.2.3 Goethite/Lepidocrocite Relation to Protective Ability Index in Industrial
Environments
Yamashita et al. (1994) and Kamimura et al. (2005) assessed the performance of
UWS in industrial environments by evaluating the mass ratios of goethite to lepidocrocite
rust phases. Yamashita et al. (1994) stated that the inner layer of rust that formed on UWS
test specimens that were exposed for 26 years had a homogenous composition with small
goethite particles (<10 nm) as the main constituent. The small goethite particles in the inner
rust layer are able to pack densely together and provide corrosion resistance while the outer
layer of rust that formed was mainly composed of lepidocrocite. Furthermore, Kamimura
et al. (2005) also found that UWS exposed in industrial environments was mainly
composed of ultra-fine goethite and that the dissolution of lepidocrocite, precipitation, and
phase transformation to goethite with amorphous oxyhydroxide forms the protective inner
layer of ultra-fine goethite after decades of exposure.
Both Yamashita et al. (1994) and Kamimura et al. (2005) found that the
alpha/gamma mass ratio can be used as an index for evaluating the protectiveness of the
rust layer that forms on the steel. The goethite/lepidocrocite mass ratio was found to
increase with an increase in the duration of exposure in industrial environments and when
the goethite/lepidocrocite mass ratio exceeds a certain value, a lower corrosion rate of less
than 0.01 mm/year was observed (Kamimura et al., 2005). However, there is less
correlation between the alpha/gamma mass ratio and the rate of corrosion when the air-
borne sea salt content is greater than 0.2 mg NaCl/100cm2/day due to the formation of
akaganeite and iron oxide. Instead, Kamimura et al. (2005) found that the
goethite/lepidocrocite* mass ratio, which is the mass ratio of crystalline goethite to the total
mass of lepidocrocite, akaganeite and iron oxide, can be used as a protective ability index
in environments with relatively high air-borne sea salt concentrations. When the
27
goethite/lepidocrocite* mass ratio is greater than a certain threshold, the corrosion rate of
more than 0.01 mm/year is not observed.
2.3.2.4 Effects on Corrosion Rates Based on Chemical Composition of UWS in
Industrial Environments
Oh et al. (1999) and Wang et al. (2013) performed field studies that assessed the
effects of corrosion rates in industrial environments based on the different chemical
compositions of UWS test specimens. These field studies also compared UWS and mild
steel specimens to further evaluate how differences in chemical compositions of steel effect
atmospheric corrosion. Each field study found that the main oxides present in each
corrosion product were magnetic goethite, superparamagnetic goethite, and lepidocrocite,
independent of the different environments and type of steel.
Oh et al. (1999) performed a field study in which carbon steel, copper bearing steel
and UWS coupons with varying chemical compositions were exposed for 16 years in a
moderate industrial environment with a sulfur oxide deposition of 0.25 mg/100cm2/day.
Oh et al. (1999) found that when comparing two UWS coupons with a variation in one of
the chemical contents, such as two coupons with different amounts of nickel, two coupons
with different amounts of silicon, and two coupons with different amounts of phosphorous,
the relative fractions of goethite to all other corrosion products and lepidocrocite to all
other corrosion products that formed on the steel coupons were the same when being
exposed in an industrial environment. Differences were found when assessing the relative
fractions of superparamagnetic goethite (goethite particles less than or equal to 15 nm in
diameter) to goethite with particles greater than 15 nm, lepidocrocite and iron oxides
between coupons with varying chemical compositions. Oh et al. (1999) indicates that
increased fractions of superparamagnetic goethite are correlated with decreased mean
particle size of goethite and result in enhanced corrosion resistance. It was observed that
28
the relative fraction of superparamagnetic component of goethite for a coupon with a higher
amount of silicon was higher than that of a coupon with a lower amount of silicon,
independent of the environmental conditions. This suggests that a higher silicon content
can increase the fraction of goethite, resulting in a decrease of the mean particle size of
goethite and possibly resulting in enhanced corrosion resistance. Furthermore, it was found
that the relative fraction of superparamagnetic goethite in the industrial environment
decreased by 6% in the corrosion products of a coupon with a higher phosphorous content
than another coupon. This suggest that a lower phosphorous content can cause an increase
in the relative fraction of superparamagnetic goethite and result in better corrosion
resistance in an industrial environment.
Wang et al. (2013) conducted a similar study to Oh et al.’s (1999) in which the
effect of the chemical composition of UWS on the corrosion rate was assessed in an
industrial environment. Steel specimens were exposed for 5 years at three different sites in
Japan. Jiangjin, Japan was the test site that was representative of an industrial environment
with a sulfur oxide deposition of 6.96 mg/100cm2/day. Wang et al. (2013) notes that
compared with other alloying elements of UWS, chromium is the most abundant in the
inner rust layer and is the most effective at reducing the rate of corrosion. Wang et al.
(2013) mentions how this finding is similar to Yamashita et al.’s (1994), which reported
that chromium could partly replace iron in the iron oxyhydroxide. When exposed to high
concentrations of sulfur oxide this rust phase transformation is accelerated, which can
account for the higher amounts of chromium found in the rust layer of steel specimens
exposed in Jiangjin as well as reduced corrosion rates as compared to the other test sites.
Furthermore, Wang et al. (2013) found that UWS specimens with a lower amount of
phosphorous and copper had a higher corrosion rate than that of the other UWS specimens
at Jiangjin. This result is the opposite of what Oh et al. (1999) found when assessing UWS
29
specimens with lower amounts of phosphorous that resulted in better corrosion resistance
when exposed in industrial environments.
2.3.3 Rural Environment Field Studies
One of the other environments that field studies of UWS were performed in were
rural environments. Rural environments are typically classified as having relatively lower
chloride and sulfur oxide concentrations as compared to coastal and industrial
environments. The effects of low chloride and sulfur oxide concentrations on corrosion
characteristics of UWS and other types of steel were assessed in each study.
2.3.3.1 Rust Characteristics in Rural Environments
Wang et al. (2013) and Diaz et al. (2018) conducted similar field studies in which
the corrosion of UWS was assessed after 5 years exposure in multiple environments. Wang
et al. (2013) looked at the effects of UWS exposed in Qionghai, Japan, which was classified
as a rural environment with a sulfur oxide deposition of 0.98 mg/100cm2/day and chloride
deposition of 1.99 mg/100cm2/day in comparison to a coastal environment (Qingdao,
Japan) and industrial environment (Jiangjin, Japan). Thickness losses of about 0.8 mm for
the carbon steel specimen and about 0.05 mm for the UWS specimens were found from
exposure after 5 years in the rural environment. These values are both lower than the
corrosion losses reported for both types of steel specimens exposed in the coastal and
industrial environments. Similarly, Diaz et al. (2018) found that steel specimens exposed
in the rural environment of Pardo, Spain with a sulfur oxide deposition of 0.0028
mg/100cm2/day and chloride deposition of 0.027 mg/m2/day had the lowest corrosion rates.
Therefore, it was concluded that UWS exposed in environments with relatively lower
sulfur oxide and chloride depositions would experience lower corrosion losses.
30
Additionally, Wang et al. (2013) found differences in the initial stages of corrosion
rates between specimens exposed in coastal (Qingdao, Japan) and rural (Qionghai, Japan)
environments, however, the long-term corrosion trend was similar. Qionghai, Japan had
both the highest average temperature of 24.3°C and relative humidity of 86% compared to
the other two environments. These two factors contribute to a greater time of wetting
(TOW), which occurs when the temperature and humidity are beyond 0°C and 80%,
respectively (Wang et al., 2013).
2.3.3.2 Rust Phases Formed in Rural Environments
Similar to UWS specimens exposed in an industrial environment, when evaluating
the rust phases that formed on specimens exposed in a rural environment, Oh et al. (1999),
Cook et al. (1999), Diaz et al. (2018), and Kamimura et al. (2005) each found goethite and
lepidocrocite to be the main oxides in each corrosion product.
Oh et al. (1999) studied the corrosion products formed on different UWS (ASTM
A-242 and A-588), carbon steel, and copper bearing steel specimens exposed for 16 years
in industrial, marine, and rural environments. It was found that the fractions of goethite,
maghemite, and lepidocrocite were almost the same in the corrosion products of each steel
specimen, independent of environmental exposure conditions. Cook et al. (1999) also
assessed UWS specimens exposed for 16 years in the rural environment of Saylorsburg,
Pennsylvania and found that the outer rust layer was composed of equal fractions of
lepidocrocite and goethite. Similarly, Diaz et al. (2018) noted that the outer surface of the
rust layer formed on UWS specimens exposed in the rural environment of Pardo, Spain
(sulfur oxide concentration of 0.0028 mg/100cm2/day and chloride deposition of 0.027
mg/100cm2/day) were an “orangey colouring”, which is typical of the lepidocrocite phase.
Cook et al. (1999) states that the inner rust layer of UWS specimens exposed in the rural
31
environment of Saylorsburg, Pennsylvania were entirely made up of goethite (distribution
of particle size 5-30 nm with 60% of particles less than 15 nm) containing small amounts
of maghemite and magnetite (both types of iron oxides). This is comparative with
Kamimura et al. (2005)’s field study where UWS specimens exposed in the rural
environment of Kitahiroshima-city, Japan (amount of air-borne salt particles: 0.01
mg/100cm2/day) were mainly composed of ultra-fine goethite. The ultra-fine particle size
of the goethite rust phase is the main characteristic that contributes to corrosion resistance
of UWS. Thus, it was concluded that ultra-fine goethite forms with exposure conditions in
rural environments with relatively low chloride and sulfur oxide concentrations as well as
a low TOW.
2.3.3.3 Goethite/Lepidocrocite Relation to Protective Ability Index in Rural
Environments
Kamimura et al. (2005) also found that UWS specimens (JIS SMA 490AW)
exposed in the rural environment of Kitahiroshima-city, Japan (amount of air-borne salt
particles: 0.01 mg/100cm2/day) had a relationship between the goethite/lepidocrocite* and
rate of corrosion. Hara et al. (2006)’s field study furthered Kamimura et al. (2005)’s
findings by reporting information about 5 UWS bridges exposed between 1 and 18 years
in the rural environments of Hokkaido, Yamagata, and Fukushima, Japan (<0.05 airborne
sea salt mg/100cm2/day). The goethite/lepidocrocite* was found to be less than 1 and
(akageneite + iron oxide)/lepidocrocite* was less than 0.5. Both field studies reported that
the corrosion rates of the UWS exposed in these rural environments was found to be less
than 0.01 mm/y. Wang et al. (2013) performed a field study in the rural environment of
Qionghai, Japan (sulfur oxide deposition 0.98 mg/100cm2/day & chloride deposition 1.99
mg/100cm2/day) where UWS specimens were exposed for five years. Wang et al. (2013)
found that the rust layer was mainly composed of goethite and lepidocrocite, however the
32
reported corrosion rates were around 0.03 mm/y, which is greater than those reported by
Kamimura et al. (2005) and Hara et al. (2006). Wang et al. (2013) only reported the initial
stages of corrosion (less than 5 years of exposure); however, the corrosion rates of UWS
specimens were beginning to drop below 0.02-0.01 mm/y and stabilize after the initial five
years of exposure.
2.3.4 UWS Bridge Washing Field Studies
Crampton et al. (2013) reported on Iowa DOT’s evaluation of their UWS bridge
inventory. The quality of UWS patinas in environments with deicing salt usage were
assessed to evaluate the potential benefits of routine bridge washing. Clear tape adhesion
and chloride testing as well as patina evaluations were performed at selected areas before
and after the washed areas were permitted to fully dry to assess the immediate effects of
power washing. Overall, Crampton et al. (2013) found that the most effective, efficient,
and practical patina evaluation techniques were the visual inspections and tape adhesion
tests. Bridges that were inspected and washed ranged between being built in 1970-2007.
Crampton et al. (2013) found that bridge washing performed immediately following the
winter deicing season removed many of the chloride contaminants on the surface of the
patinas, but not with chlorides embedded within the rust layer. Crampton et al. (2013) also
notes that the maximum benefits of routine bridge washing are likely to be achieved on
newer UWS bridges where chloride has had less time to build-up and penetrate the
protective oxide layer; however, further study may be needed to confirm these
assumptions. In addition to removing chloride build-up, washing can also help remove
loose rust flakes, dirt, debris, and other contaminants that often retain moisture and prolong
TOW that may result in damaging the patina (Crampton et al., 2013). A proposed
33
inspection rating scale was developed from the study along with maintenance actions based
on each rating.
Ault and Dolph (2018) also notes the benefits of bridge washing (not specific to
UWS) in terms of corrosion prevention. Ault and Dolph (2018) reported a study done by
Alland et al. (2013) at the University of Pittsburgh regarding investigation of the
effectiveness of washing practices on Pennsylvania bridges subject to deicing agents.
Alland et al. (2013) tested the steel surfaces of bridges before and after washing with the
ARP Instruments soluble salt meter (SSM). The reported data showed a salt reduction
between 20% and 95% depending on the location being washed and assessed; however, no
specific information is given on which locations were most or least affected. Ault and
Dolph (2018) reported another study done by Palle et al. (2003) of the Kentucky
Transportation Center (KTC) that evaluated bridge washing. Palle et al. (2003) found
nearly complete removal of chloride, even when there were already low quantities of
chloride present after assessing chloride concentrations before and after washing steel
surfaces of bridges.
2.4 Phase 1 and Phase 2 Work
The main goal of this research project is to provide quantitative guidelines to define
environments that cause undesirable rates of corrosion in UWS, which were previously
described qualitatively in FHWA TA 5140.22. In Phase 1 of this research project, data was
gathered from a survey of UWS bridges across 56 owner agencies (46 states, the District
of Columbia, Puerto Rico, and eight federal agencies) in the U.S. A UWS Geographic
Information System (GIS) database with over 10,000 UWS bridges was put together to
develop a complete macroclimate of all known UWS bridges in the U.S. to make
correlations with corresponding National Bridge Inventory (NBI) data. As a result of a
34
complementary survey of bridge owners, two environments of greatest concern for UWS
bridges were determined: coastal environments and highway overpasses over roadways
treated with deicing agents. (McConnell et al., 2014 c)
Phase 2 of this project then focused on evaluating the field performance of UWS
bridges in these two environments. Thirteen UWS bridges were evaluated in the field as
well as a review of their inspection reports along with 56 other UWS bridges that are
collectively referred to as cluster bridges. In the field, tape adhesion tests for digital image
processing and rust samples for IC analysis were collected. Data collected from these field
samples, inspection reports, and photographic records were used to assess which of the
cluster bridges were experiencing overall corrosion and to determine quantitative
correlations that could be made with their surrounding environmental conditions
(McConnell et al., 2014 b).
Conclusions from this work included correlations between UWS performance and
environmental conditions. Characteristics that contributed to either good or poor
performance of UWS bridges in the coastal environment (Gulf Coast) and deicing
environments were summarized. The consistently poor coastal environment was found to
have a small distance to the coast, high humidity, and high atmospheric chemical
concentrations, while crossing a waterway. The consistently good coastal environments in
comparison to the poor coastal environment were found to have a combination of the
following parameters:
• A greater distance to the coast, equal or lower humidity scores, lower
atmospheric chemical concentrations, while crossing a highway.
• A greater distance to the coast, lower humidity scores, equal or lower
atmospheric chemical concentrations, while crossing a highway.
• A greater distance to the coast, even lower humidity scores than the
environmental combination referenced in the previous bullet point,
35
equal or lower atmospheric chemical concentrations, while having any
crossing type.
Specific quantities for these parameters can be found from McConnell et al. (2014
b). These quantitative conclusions on correlations between coastal environment conditions
and UWS performance were based on a review of data from nearly 50% of the UWS
inventory within 50 miles of the Gulf Coast. Because of this, the careful sampling of
bridges, and the relatively small number of influential parameters affecting UWS
performance in this region, there was a modest level of confidence in the general
applicability of these observed correlations in the absence of a larger data set.
The consistently poor deicing environments were described as highway crossings
with vertical under-clearances less than or equal to 5 meters along with one of the following
additional combinations of influential parameters:
• High ADT.
• Moderate ADT combined with high snowfall.
• Moderately high snowfall combined with moderately high chloride
levels.
The consistently good deicing environments in comparison to the poor deicing
environments consisted of:
• Highway crossings with high vertical under-clearance.
• Highway crossings with low ADT and low chloride concentration
without very high snowfall.
• Highway crossings with low chloride concentration without a more
modest level of high snowfall.
• Highway crossings with low snowfall.
• Waterway crossings that cross no other features.
36
Specific quantities for these parameters can be found from McConnell et al. (2014
b). These quantitative conclusions on correlations between deicing environment conditions
and UWS performance were based only on a small fraction (likely less than 1 percent) of
the total UWS inventory subjected to deicing agents. Therefore, Phase 3 of this research
project is being conducted to further assess these preliminary correlations.
37
Chapter 3
FIELD METHODOLOGY
This chapter describes methodology that was used to select UWS bridges for
analysis and evaluation, bridge evaluation practices carried out prior to field visits and once
in the field, and data collection processes of clear tape adhesion tests as well as IC analyses.
3.1 Bridge Selection
One main aspect of this research project was to maximize opportunities for collecting
quantifiable data on UWS bridge performance. One way of doing this was by compiling
data and identifying UWS bridges for field evaluations. The goal of this section is to
explain how UWS bridges were selected for field evaluation. The proceeding data
collection and analysis plan is based on procedures used in prior work (Phase 2 Report
(McConnell et. al, 2014 b) with refinements as documented in the draft field and laboratory
protocols of Phase 3 (McConnell and Shenton, 2018). The location of seven proposed
“clusters” were chosen based on environments where UWS bridge performance was found
to be unsatisfactory in Phase 1 of this research project (McConnell et. al, 2012). These
environments include regions where atmospheric chloride concentrations are relatively
high, such as in areas near the coast and where large quantities of deicing agents are used
on roadways beneath bridges. These clusters were also defined as being “good” or
“inferior” performing based on overall UWS bridge performance within those regions Ohio
(good deicing), Colorado (good deicing), Minnesota (inferior deicing), Iowa (inferior
deicing), North Carolina (inferior and good coastal), New Hampshire (good coastal and
deicing), and Connecticut (inferior coastal and deicing) were the seven clusters determined
38
to be representative of these environments and part of Phase 3 of this research project. It is
noted that the definition of “good” used in this work is not merely good performance, but
good performance in a severe environment. The rationale for selecting these clusters is
discussed in the Task 3 Report for this research project (McConnell et. al, 2018). Refer to
Table 3.1 for an overview of the Phase 3 clusters and Figure 3.1 for their locations in the
United States.
Table 3.1 Phase 3 Cluster Overview
Deicing Coastal
Deicing
+
Coastal
Inferior 1. MN
5. NC
6. CT 2. IA
Good 3. CO
7. NH 4. OH
39
Figure 3.1 Phase 3 Cluster Locations
3.1.1 GIS Database
A database of UWS highway bridges was compiled after working with 46 LTBPP
state coordinators (representatives from each state in the U.S., Washington D.C., and
Puerto Rico that assist in work related to the LTBPP) and representatives from 8 Federal
agencies to identify UWS bridges within their agencies (McConnell et al., 2014 a). The
National Bridge Inventory (NBI) was then used to collect superstructure condition ratings
(SCR), latitudinal and longitudinal coordinates, average daily traffic (ADT) under
structures, crossing types (highway, railroad, waterway, etc.), year built as well as year
reconstructed, and vertical under-clearances into a database. Climate data (time of wetness,
monthly humidity, and annual snowfall); atmospheric chemical concentrations of chloride,
nitrate, and sulfate; and distance to the coast were also added to the database. All of this
data was compiled to make up the UWS geographic information system (GIS) database,
which consisted of over 10,000 bridges. Overall, this database supplied information
40
regarding the complete macroclimate of UWS bridges in the United States in association
with corresponding NBI data. McConnell et al. (2014 a) describes that this database can be
used in future research to assess specific correlations between environmental parameters
and UWS bridge conditions.
3.1.2 Reference Bridges
After developing the UWS GIS database, bridges were systematically selected for
further analysis. Parametric evaluations based on data from the UWS database were used
to determine good performing reference bridges. Bridges in the most severe environments
were compared with their SCR to determine those in the best condition despite being in a
relatively severe environment. The inferior performing reference bridges were identified
by state-coordinators during Phase 1 (McConnell et. al, 2012). This same concept was
applied to determine “inferior” performing reference bridges, when state-coordinators
could not supply recommendations for specific suitable reference bridge candidates. In
cases where state-coordinators could supply recommendations of inferior performing
reference bridges, inspection reports of these bridges were reviewed and compared based
on SCR as well as condition state ratings of the girders in order to select the most viable
candidate as a reference bridge.
When the reference bridge did not originate from the direct suggestion of the state-
coordinator, candidates were identified based on the representation of specific geography-
related variables, such as bridges that were within a specific distance to the coast or where
snowfall exceeded a particular threshold. The next step was then to consider the
performance of bridges within these constraints to determine a suitable reference bridge.
Furthermore, a suitable reference bridge candidate also required a minimum of 10 bridges
to be within a specified radius and older than a specified age so that these surrounding
41
bridges could be considered as proximate bridges (which are described in Section 3.1.3).
Refer to Table 3.2 for characteristics of each reference bridge that was selected for
evaluation.
Table 3.2 Characteristics of Phase 3 Reference Bridges
3.1.3 Proximate Bridges
Proximate bridges were identified by using the longitudinal and latitudinal
coordinates of the reference bridge as the center of a circle with a specified radius (typically
50 miles) in GIS. GIS was used to identify all UWS bridges within the circle and then the
list of identified bridges was filtered to remove bridges that were built or reconstructed
prior to 1964 and younger than 20 years old. UWS bridges that were reported to be built
or reconstructed prior to 1964 were considered to be an error in the database based on the
fact that UWS was first used in bridges in 1964. Furthermore, UWS bridges that were
younger than 20 years old were generally deemed to be too young for a meaningful
evaluation of their long-term performance. The specified radius of the MN cluster was
increased to 200 miles in order to include the Minneapolis urban area and environments
with relatively higher snowfall. The IA cluster did not contain a minimum of 10 bridges
ClusterStructure
Number
Crossing
Type
Distance
to
Coast
(miles)
ADT
Under
Structure
Vert. Under-
Clearance
(ft.)
Relative
Humidity
Snow
(in.)
Chloride
(mg/L)
Age
(years)SCR
OH 7701993 Highway NA 26000 4.67 0F, 10G, 2H 49.2 0.101 40 8
MN 62861 Highway NA 130000 4.91 4F, 8G, 0H, 0I 52.9 0.057 40 6
IA 041331 Highway NA 88500 5.23 3F, 9G 34.8 0.066 11 7
NH 11101120017900 Highway 2.1 65610 4.92 1F, 4G, 6H, 1I 59.2 0.75 14 8
NC (Inferior) 190083 Rail 4.2 NA NA 1F, 8G, 3H 2.3 0.328 33 5
NC (Good) 1290058 Highway 2.1 23000 5.00 0F, 9G, 3H 2.3 0.717 28 8
NC (Good) 1290057 Highway 2.4 29000 4.93 0F, 9G, 3H 2.3 0.717 28 8
CO E-16-JZ Highway NA 183000 6.00 9E, 3F 62.6 0.045 28 7
CT 3830 Highway 2.2 19400 4.95 5F, 7G, 0H 31.9 0.315 37 6
42
that were within a 50-mile radius of the chosen reference bridge as well as not built or
reconstructed prior to 1964 and older than 20 years old, so younger bridges were included
in the cluster instead of increasing the radius in order to avoid the IA cluster overlapping
with the MN cluster.
3.1.4 Cluster Bridges
Cluster bridges were next selected as a subset of the proximate bridges. Refer to
Table 3.3 for a summary of each cluster’s bridge statistics. Cluster bridges were determined
based on statistical evaluation of key influential parameters from NBI data (SCR, ADT
under structure, crossing type, age, and vertical under-clearance), atmospheric chemical
concentrations (chloride, nitrate, and sulfate), climate data (time of wetness, monthly
humidity, and annual snowfall), and distance to coast. Refer to Appendix A for breakdowns
of the data parameters mentioned above for each cluster bridge within each cluster.
Statistical analysis of this data for the proximate bridge population was then used to
determine the mean, standard deviation, maximum, minimum, and median values of each
parameter. The value of each parameter of each bridge was then categorized as “high”
(greater than the median value of that parameter) or “low” (less than or equal to the median
value of that parameter).
43
Table 3.3 Summary Bridge Statistics of Phase 3 Clusters
The cluster bridges were selected based on parametric combinations of parameters
of interest. For deicing clusters, ADT under structure, vertical under-clearance, relative
humidity, annual snowfall, atmospheric chloride concentration, age, and SCR were key
parameters of consideration. For the combined deicing and coastal clusters, distance to
coast along with the parameters mentioned for deicing clusters were considered. For the
coastal cluster, distance to coast, relative humidity, and chloride concentrations were
considered. The parametric combinations provided each UWS bridge in the list of
proximate bridges with a numbered category. Next, the numbered category associated with
the reference bridge was used to determine other numbered categories of interest by
varying one parameter of interest at a time. For instance, if the reference bridge had a
“high” distance to coast, “high” ADT, and “high” atmospheric chloride concentration, the
Cluster
Distance
to Coast
(miles)
ADT
Under
Structure
Vertical
Uncer-
Clearance
(ft.)
Relative
Humidity
Snow
(in.)
Chloride
(mg/L)
Age
(years)SCR
OH (MAX) NA 99400 329.16 0F, 10G, 2H 95.3 0.101 46 9
OH (MIN) NA 295 53.04 2F, 10G, 0H 23.8 0.070 2 4
MN (MAX) NA 303000 145.92 1F, 5G, 4H, 2I 88.1 0.105 48 9
MN (MIN) NA 35 57.48 5F, 7G, 0H, 0I 25.7 0.030 2 0
IA (MAX) NA 108300 113.40 3F, 9G 34.8 0.066 41 9
IA (MIN) NA 2030 49.44 3F, 9G 21.7 0.066 2 7
NH (MAX) 67.5 246700 219.48 5F, 9G, 6H, 2I 80.8 0.750 59 9
NH (MIN) 0.0 100 37.20 0F, 4G, 0H, 0I 41.6 0.102 2 4
NC (MAX) 32.2 29000 64.32 3F, 9G, 3H 3.0 0.717 33 8
NC (MIN) 2.1 1800 57.60 0F, 8G, 0H 2.3 0.328 28 5
CO (MAX) NA 183000 96.00 9E, 3F 62.6 0.045 33 8
CO (MIN) NA 62500 60.00 9E, 3F 62.6 0.045 28 3
CT (MAX) 30.4 161900 167.88 6F, 8G, 2H 100.1 0.315 78 9
CT (MIN) 0.0 900 50.88 3F, 6G, 0H 23.6 0.127 2 3
44
atmospheric chloride concentration parameter would first be varied to “low” and the
corresponding parametric combination number of “high” distance to coast, “high” ADT,
and “low” atmospheric chloride concentration would be considered to select UWS bridges
matching or close to that numbered category in the list of proximate bridges. Next, ADT
would be varied to “low”, so the parametric combination would be “high” distance to coast,
“low” ADT, and “high” atmospheric chloride concentration, and so on. Refer to Appendix
B, Table B.1 for the list of parametric combinations used for the deicing clusters. Refer to
Appendix B, Table B.2 for the list of parametric combinations used for the deicing and
coastal clusters. Refer to Appendix B, Table B.3 for the list of parametric combinations
used for the coastal cluster.
3.1.5 Field Bridges
Field bridges were next selected after receiving inspection reports on all selected
cluster bridges. These inspection reports were evaluated with close attention to condition
state information of core elements, key words, and photographs relating to UWS issues or
corrosion. Two bridges from the list of cluster bridges were then selected as field bridges,
one generally representing a bridge in the “best” condition and the other representing a
bridge in the “worst” condition within the cluster. Best and worst condition states were
based largely on percentage of girders and other UWS elements in various condition states
considered relative to age and severity of the assigned parametric category. Refer to Table
3.4 for a summary of characteristics for each field bridge.
45
Table 3.4 Characteristics of Phase 3 Field Bridges
It should be noted that the NH cluster originally included four field bridges that
were going to be evaluated; however, two of the bridges (NH 019700810009300 and NH
017700960015300) were found to be painted so they could not be assessed. Refer to Table
3.5 for a summary of bridges NH 019700810009300 and NH 017700960015300
characteristics. Instead, bridge NH 011101120017900 was included as a field bridge and
evaluated after determining it to be a viable replacement of bridge NH 019700810009300
based on a review of the bridge’s characteristics being similar to NH 019700810009300 as
well as it being one of the only bridges that was not painted and within a reasonable travel
distance. A replacement bridge could not be found in time for NH 017700960015300 due
to travel plans.
Cluster CombinationStructure
Number
Crossing
Type
Distance
to Coast
(miles)
ADT
Under
Structure
Vertical
Under-
Clearance
(ft.)
Relative
Humidity
Snow
(in.)
Chloride
(mg/L)
Age
(years)SCR
MN 2 04019 Highway NA 9700 58.92 2F, 9G, 1H, 0I 53.1 0.030 34 5
MN 6 62861 Highway NA 130000 58.80 4F, 8G, 0H, 0I 52.9 0.057 40 6
MN 8 19811 Highway NA 53000 59.64 4F, 8G, 0H, 0I 44.3 0.057 35 7
NC 3 190083 Rail 4.2 NA NA 1F, 8G, 3H 2.3 0.328 33 5
NC 32,W 1290058 Highway 2.1 23000 60.00 0F, 9G, 3H 2.3 0.717 28 8
NC 38 1290057 Highway 2.4 29000 59.16 0F, 9G, 3H 2.3 0.717 28 8
IA 8 041331 Highway NA 88500 62.76 3F, 9G 34.8 0.066 11 7
IA 16 042711 Highway NA 78360 87.60 3F, 9G 34.8 0.066 10 8
IA 16 004111 Highway NA 73990 66.48 3F, 9G 34.8 0.066 12 8
CO 12 E-16-JZ Highway NA 18300 72.00 9E, 3F 62.6 0.045 28 7
CO 20 E-16-JW Highway NA 62500 60.00 9E, 3F 62.6 0.045 31 8
CO 20 E-16-JX Highway NA 84000 60.00 9E, 3F 62.6 0.045 31 8
OH 1 7701977 Highway NA 23599 57.00 0F, 10G, 2H 49.2 0.101 39 8
OH 1 7701993 Highway NA 26000 56.04 0F, 10G, 2H 49.2 0.101 40 8
OH 24 7805934 Highway NA 7832 55.44 2F, 10G, 0H 40.1 0.100 21 5
CT 4 4382 Highway 2.9 48400 60.60 5F, 7G, 0H 31.9 0.315 32 6
CT 5 5796 Highway 0.6 11600 57.36 5F, 7G, 0H 47.4 0.315 26 7
CT 12 3830 Highway 2.2 19400 59.40 5F, 7G, 0H 31.9 0.315 37 6
NH 3 011101120017900 Highway 2.1 65610 59.04 1F, 4G, 6H, 1I 59.2 0.750 14 8
NH 54 017201120011300 Highway 28.0 3900 53.28 5F, 7G, 0H, 0I 68.2 0.180 36 6
NH 64 017701460003700 Highway 17.6 21000 63.72 5F, 7G, 0H, 0I 55.4 0.180 20 8
46
Table 3.5 Characteristics of Bridges NH 019700810009300 and NH 017700960015300
3.2 Field Work
Field work was conducted in accordance with LTBPP previsit (PRE) and field visit
(FLD) protocols published in FHWA-HRT-16-007 (Hooks and Weidner, 2016) as well as
refinements to these protocols documented in the draft field and laboratory protocols of
Phase 3 (McConnell and Shenton, 2018). Refer to Section 3.2.2 and Section 3.2.3 for the
specific “PRE” and “FLD” protocols that were followed throughout field work conducted
in Phase 3 of this research project.
3.2.1 Equipment
• PRE-PL-LO-004, Personal Health and Safety Plan.
• Ladder, access platform, snooper, bucket truck, man lift, and/or high-
reach equipment (if necessary).
• Pelican case (optional).
• Tool pouch (optional).
• Tool tray (optional).
• Pencil, sketch pad, and clipboard.
• Soap stone/white chalk.
• Permanent marker.
• Temporary marker.
• Field data entry sheets.
Cluster CombinationStructure
Number
Crossing
Type
Distance
to Coast
(miles)
ADT
Under
Structure
Vertical
Under-
Clearance
(ft.)
Relative
Humidity
Snow
(in.)
Chloride
(mg/L)
Age
(years)SCR
NH 3 019700810009300 Highway 3.2 51318 60.00 1F, 4G, 6H, 1I 59.2 0.750 38 7
NH 38 017700960015300 Highway 19.5 71000 59.64 5F, 7G, 0H, 0I 68.2 0.180 26 8
47
• Manila folder (optional).
• Spring clips (optional).
• Tape measure.
• 6-ft. folding ruler.
• Carpenters square.
• Laser measuring device (optional).
• Sample area marking template (4 in. by 6 in., optional).
• Digital camera.
• Magnetic bar with white, black, green, yellow, blue, and red electrical
tape.
• Magnetic lights (optional).
• Clear plastic packing tape with a minimum width of 1.89 in. (48 mm)
and minimum adhesive strength to steel of 55 oz./ in. width according
to ASTM D3330 (e.g., 3M Scotch® Superior Performance Box Sealing
Tape 375).
• Firm rubber “J” roller, 3 in. width minimum.
• Letter size white paper.
• Stainless-steel scoopula.
• Stainless-steel wire brush.
• Stainless-steel chisel, preferably with wide blade.
• Electrical power grinder and stainless-steel wire cup wheel.
• Gram digital scale.
• Clear plastic sealable bags.
• Ultrasonic measuring device and associated coupling agent (optional).
• Lever pit gage.
48
• Dry-film thickness gage.
3.2.2 Prior to Field Visit
Before carrying out field work at each cluster location, work was conducted to plan
out bridge inspections with the goal of minimizing impacts to the traveling public, ensuring
a safe work environment, and collecting high quality data. All pre-field work was
conducted in accordance with LTBPP “PRE-ED-BD-001”, “PRE-ED-BD-005”, “PRE-PL-
LO-001”, “PRE-PL-LO-003”, “PRE-PL-LO-004”, and “PRE-PL-LO-005” protocols
published in FHWA-HRT-16-007 (Hooks and Weidner, 2016) as well as refinements to
these protocols documented in the draft field and laboratory protocols of Phase 3
(McConnell and Shenton, 2018). Pre-field work steps included activities such as:
1. Requesting and reviewing general bridge plan and elevation drawings as
well as steel framing plans and inspection records from state LTBPP
coordinators.
2. Determining where samples would be collected based on draft field and
laboratory protocols of Phase 3 (McConnell and Shenton, 2018), as well as
alignment of the FLD-OP-SP protocols (Hooks and Weidner, 2016), steel
framing plans to assess bridge geometry, accessibility, and traffic control.
3. Coordinating with the bridge owner to identify suitable dates for conducting
the field work, planning for maintenance of traffic (MOT), and any other
logistics. MOT and access equipment were then arranged for the date of the
inspection.
3.2.3 Once in the Field
Evaluations of reference and field bridges were conducted in accordance with
LTBPP “FLD-OP-SP-001”, “FLD-OP-SC-001”, “FLD-OP-SC-002”, “FLD-OP-SC-003”,
“FLD-DC-PH-001”, “FLD-DC-PH-002”, “FLD-DC-PH-003”, “FLD-DC-VIS-002”, and
“FLD-DS-LS-001” protocols published in FHWA-HRT-16-007 (Hooks and Weidner,
2016) as well as refinements to these protocols documented in the draft field and laboratory
49
protocols of Phase 3 (McConnell and Shenton, 2018). A cursory inspection of the structure
to assess any unanticipated issues or problems that affected the ability to collect samples
as planned was performed. If there were unanticipated issues, the plan was modified on
site as needed. Access equipment was setup to gain access to the girders in the specified
locations. The locations on the girders where samples were to be taken were located using
a tape measure or laser measuring device.
3.2.3.1 Visual Documentation
A total of six different types of photos were taken at each site visit as per LTBPP
protocol FLD-DC-PH-002, Photographing for Documentation Purposes (Hooks and
Weidner, 2016) as well as refinements to these protocols documented in the draft field and
laboratory protocols of Phase 3 (McConnell and Shenton, 2018).These include:
4. A wide view of the bridge viewing fascia girders/beams that captures all
girder segments. This photograph was taken from a distance of
approximately 100 ft. back from the bridge, but within the limits of site
traffic control if possible, or on the shoulder of the road if necessary. An
example is shown in Figure 3.2.
5. Girders at all bearing locations. An example is shown in Figure 3.3.
6. A wide view of interior girders for each span. An example is shown in
Figure 3.4.
7. One close-up photo of each splice plate on fascia girders (if applicable). An
example is shown in Figure 3.5.
8. One close-up photo of a lateral bracing to girder connection (if applicable).
An example is shown in Figure 3.6. This photograph focused on bolted
connections, such as between cross-frame members and transverse
stiffeners serving as lateral bracing connection plates, in areas where any
pack rust was developing if applicable.
9. At least one photo depicting the general environmental exposure of the
structure was included if not captured in the wide view of the fascia girder.
An example is shown in Figure 3.7.
50
A hand sketch was provided with these pictures depicting the observer’s location and
viewing angle relative to the bridge.
Figure 3.2 Photo Example of Wide View of Bridge
Figure 3.3 Photo Example of View of Bearing Location
51
Figure 3.4 Photo Example of Wide View of Interior Girders
Figure 3.5 Photo Example of View of Girder Splice Plate
52
Figure 3.6 Photo Example of Lateral Bracing to Girder Connection
Figure 3.7 Photo Example of Overall View of General Environment of Bridge
3.2.3.2 Sample Areas
3.2.3.2.1 Locations
A total of 12 sample area locations was to be used for each bridge that was
inspected. These locations included two different longitudinal cross-sections. If the bridge
was a highway crossing, one longitudinal cross-section location was over the center of the
right travel lane. The second longitudinal cross-section location was typically over a
53
shoulder lane if applicable. If no shoulder lane was present, the second longitudinal cross-
section location was selected by moving about 12 ft. away from the longitudinal cross-
section location over the center of the right travel lane towards the nearest abutment. One
of the bridges that was inspected was a railroad crossing, in which case one longitudinal
cross-section location was about 9 ft. away from the nearest abutment and the second
longitudinal cross-section location was about 18 ft. away from the nearest abutment.
Within each bridge cross-section, one fascia girder and one interior girder was
sampled. The two girders were identified and denoted as per LTBPP protocol FLD-OP-
SC-002, Structure Segmentation and Element Identification System (Hooks and Weidner,
2016). If the bridge was a highway crossing, these girders were on the side of the bridge
facing oncoming traffic in the lanes over which the sampled cross-section was located. On
each of these 2 girders at each (of the 2) longitudinal cross-section locations, samples were
taken in three locations (for a total of 12 sample areas per bridge). One field bridge that
was evaluated from the MN cluster (MN 04019) had only 10 samples taken because two
of the sample locations on the exterior of the fascia girder were obstructed by a sign. The
three locations to be sampled on each girder cross-section were: the top surface of the
bottom flange on both sides of the web and the side of the web facing traffic (if applicable)
approximately one-third of the height of the web above the bottom flange. Specific
locations of sample areas on a typical I-girder cross-section are shown in Figure 3.8.
54
Figure 3.8 I-Girder Cross-Section Sample Locations
When collecting samples from bridges in the field, the 12 sample locations were
numbered based on the order in which they were inspected. Therefore, one field bridge
may have a different sample location numbering system than another. When recording
data, this numbering system was denoted as the Field Test Sample Area ID. In order to
standardize the sample location numbering system between each field bridge a Standard
Sample Area Location ID was also assigned to each sample location. These Standard
Location IDs along with their descriptions can be seen in Table 3.6. This standardized
numbering system allowed data collected at each sample area to be compared between each
field bridge.
55
Table 3.6 Standard Sample Area Location Descriptions
3.2.3.2.2 Measurements
At each sample location, a 4-inch by 6-inch rectangular area along with a
corresponding sample number (for reference) was marked using white chalk and a sample
area marking template cut from cardboard. The longer dimension of the rectangle was
oriented vertically for web locations and longitudinally for flange locations. Sample
locations on the bridge were numbered sequentially starting with 1 and ending with the
maximum number of samples taken from the bridge (typically 12, as previously discussed
in Section 3.2.3.2.1). The sample locations were recorded in field data entry sheets using
the center of the sample location (in x, y, z coordinates) per LTBPP protocol FLD-OP-SC-
002, Structure Segmentation and Element Identification System (Hooks and Weidner,
2016). The vertical distance of the sample area from the roadway or ground, and the
horizontal distance from the nearest joint, pier or abutment was measured (usually with a
Standard
Location
ID
Location Description
1 top of bottom flange of interior girder facing traffic over the shoulder
2 lower web of interior girder facing traffic over the shoulder
3 top of bottom flange of interior girder facing backside of traffic over the shoulder
4 top of bottom flange of exterior girder facing traffic over the shoulder
5 lower web of exterior girder facing traffic over the shoulder
6 top of bottom flange of exterior girder facing backside of traffic over the shoulder
7 top of bottom flange of interior girder facing traffic over the right travel lane
8 lower web of interior girder facing traffic over the right travel lane
9 top of bottom flange of interior girder facing backside of traffic over the right travel lane
10 top of bottom flange of exterior girder facing traffic over the right travel lane
11 lower web of exterior girder facing traffic over the right travel lane
12 top of bottom flange of exterior girder facing backside of traffic over the right travel lane
56
laser rangefinder) and recorded in field data entry sheets. Refer to Appendix C for field
data entry sheets of each field bridge that was evaluated in Phase 3.
3.2.3.2.3 Photographs
Two photographs were taken of each sample area per draft field and laboratory
protocols of Phase 3 (McConnell and Shenton, 2018) while following FLD-DC-PH-002,
Photographing for Documentation Purposes (Hooks and Weidner, 2016). One showed the
complete sampled area and one showed a closer perspective where the entire 4-inch by 6-
inch sample area filled the entire field of view. A magnetic steel bar with white, black,
green, yellow, blue, and red electrical tape was placed on the girder at the bottom of the
sample area as a color reference. These photographs may be used to assess rust
colorization characteristics with spectroscopy methods in the future and may serve as
visual references of each sample area. An example of a complete sample area photograph
is shown in Figure 3.9. An example of a closer perspective sample area photograph is
shown in Figure 3.10.
Figure 3.9 Example of Complete Sample Area Photograph
57
Figure 3.10 Example of Closer Perspective Sample Area Photograph
3.2.3.3 Dry-Film Thickness
A dry-film thickness gage was used to take an average of 9 thickness readings of
the rust layer formed on the girder at each sample location. One thickness reading was
taken at each corner of the sample area (4 readings), one thickness reading in between each
corner of the sample area (4 readings), and one thickness reading at the center of the sample
area. The average and standard deviation of the 9 readings was recorded in field data entry
sheets. Refer to Appendix C for field data entry sheets of each field bridge that was
evaluated in Phase 3.
3.2.3.4 Tape Samples
A clear tape adhesion test was performed by cutting a piece of clear tape
approximately 4 to 5 inches long. The tape was placed on the surface of the steel and rolled
over using a firm rubber “J” roller, making 10 passes with firm pressure (e.g.,
58
approximately 2 lbs. of normal force through the roller) was applied to the tape. The tape
was then removed by slowly peeling one end off from the surface of the steel at a shallow
angle, taking no longer than approximately 5 seconds to completely remove the tape. The
tape was then adhered to a sheet of white paper and the sample number was noted next to
the tape sample.
3.2.3.5 Rust Samples
Samples of rust were collected from each sample location and placed in a clean
clear, sealable plastic bag. Samples were obtained by scraping the steel surface with a
stainless-steel chisel or stainless-steel wire brush and collecting the rust in the plastic bag.
A portable scale was used to attempt to collect at least 2 grams of rust from each sample
location. If the rust sample weight was not sufficient due to good surface conditions, then
additional rust from the surrounding area was collected to total 2 grams wherever possible.
In cases with exceptionally good condition, 2 grams could not be collected after an
excessive amount of time. In all cases, the bag was labeled with the bridge ID and sample
reference number, and whether the sample was from an outer or inner lamina where
applicable.
3.2.3.6 Ultrasonic Thickness Measurements
Ultrasonic thickness measurements were taken in two locations, one representing
typical corrosion and another representing most severe corrosion. Measurements were
taken by removing surface rust and debris with a power grinder and stainless-steel wire
cup wheel, applying coupling gel and taking 5 thickness measurements within the sample
area. It was attempted that one thickness measurement was taken at the middle of the
sample area and one thickness measurement was taken at each corner of the sample area.
The average of the five thickness measurements, or the number for which a reading could
59
be obtained, was recorded in field data entry sheets. Refer to Appendix C for field data
entry sheets of each field bridge that was evaluated in Phase 3.
3.2.3.7 Severe Corrosion, Pitting, and Section Loss
Any severe corrosion, pitting, and section loss was measured and recorded if
applicable. The max length and width of any severely corroded areas was measured with a
tape measure. The depth of any severe pitting was measured with a lever pit gage. The
thickness of any severe section loss after collecting rust samples was measured with a tape
measure. Measurements were recorded in field data entry sheets. Refer to Appendix C for
field data entry sheets of each field bridge that was evaluated in Phase 3.
3.3 Data Collection
3.3.1 Clear Tape Adhesion Test
Tape samples obtained from the field work were analyzed to determine the rust
particle size distribution and percentage of the area of the tape that had rust particles
adhered to it. The tape samples were first scanned to create a digital image of the sample.
The image was then processed using a procedure developed in MATLAB to provide
quantifiable data. Refer to Appendix D for the MATLAB code used for this procedure. The
rust particles were assumed to be circular in order to easily group particles according to
size in diameter, using bins 0 to 1/32 in., 1/32 to 1/16 in., 1/16 to 1/8 in., 1/8 to 1/4 in. 1/4
to 1/2 in., 1/2 to 1 in., 1 in to 2 in., 2 in to 4 in., and greater than 4 in. The percent area of
rust particles represented by each bin as well as the total area of rust particles, or spatial
density of rust that adhered to each tape sample was determined.
60
3.3.2 Ion Chromatography Analysis
IC analyses were done to determine the soluble concentrations of chloride, sulfate,
and nitrate ions in rust samples obtained from the field work. Details regarding this data
collection process are documented in the draft field and laboratory protocols of Phase 3
(McConnell and Shenton, 2018).
61
Chapter 4
RESULTS
4.1 Qualitative Assessments of Bridges
After traveling to each of the seven clusters, a qualitative assessment of the 21 UWS
bridges that were inspected was done based on rust patina characteristics observed in the
field. Refer to Table 3.6 and Figure 3.8 for sample locations that were observed in the field.
This qualitative assessment does not refer to NBI condition ratings of the field bridges but
is rather the author’s subjective interpretation of the relative rust patina conditions of the
field bridges. Each field bridge was given a qualitative condition rating of either good or
poor based on observed characteristics of rust patinas. The locations of observed rust
patinas were organized into four groups: exterior flange of fascia girder (includes standard
sample area locations 4 and 10), exterior web of fascia girder (includes standard sample
area locations 5 and 11), interior flanges (includes standard sample area locations 1, 3, 6,
7, 9, and 12), and interior webs (includes standard sample area locations 2 and 8) as the
locations within these groups exhibited similar rust patina conditions of individual field
bridges.
The observed conditions of rust patinas were grouped into three different categories
of either compact rust patina (rating = 1), small rust flakes (rating = 2), or large thick rust
flakes (rating = 3) as these were typical rust patina conditions of all field bridges that were
assessed. Compact rust patinas were defined as surfaces where the patina was adherent and
it was difficult to remove rust. See Figure 4.1 for a typical example of a compact rust patina.
Small rust flakes and large thick rust flakes were defined as steel surface conditions where
62
the corrosion particles were more easily removed from the surface. Small rust flakes were
defined as granular (spherical like) corrosion products. See Figure 4.2 for a typical example
of small rust flakes. Large thick rust flakes were defined as sheet-like formations of
corrosion products. See Figure 4.3 for a typical example of large thick rust flakes.
Figure 4.1 Typical Example of a Compact Rust Patina
63
Figure 4.2 Typical Example of Small Rust Flakes
Figure 4.3 Typical Example of Large Thick Rust Flakes
The rust patina ratings assigned to each of the four categorized locations were then
summed to obtain an overall qualitative assessment rating of each field bridge. Prior to
64
summing the ratings of the individual categories, the rust patina condition rating of the
interior flange location was multiplied by three because this qualitative assessment location
contained three times the number of standard sample area locations as compared to the
other categories. An overall qualitative assessment rating greater than or equal to 6 (the
minimum possible qualitative assessment rating) and less than or equal to 11 signified good
condition (i.e., the sample locations of these bridges had compact rust patinas throughout
the bridge or a combination of compact rust patinas in some locations and small rust flakes
on one or more flange locations). Conversely, an overall qualitative assessment rating
greater than 11 and less than or equal to 18 (the maximum possible qualitative assessment
rating) signified poor condition (i.e., these bridges had large thick rust flakes observed in
at least one sample location). Refer to Table 4.1 for a summary of qualitative assessment
condition ratings of each field bridge. The colors of the rust patinas are also described in
the following subsections; however, this was mainly done for additional information rather
than an assessment of performance. Future work can be done to assess the relevance of
color to UWS performance, which is discussed in Section 2.2.1.
65
Table 4.1 Field Bridge Qualitative Assessment Condition Ratings
Field Bridge
Rust Patina Condition
of Exterior Flange
of Fascia Girder
Rating
of Exterior Flange
of Fascia Girder
Rust Patina Condition
of Exterior Web
of Fascia Girder
Rating
of Exterior Web
of Fascia Girder
Rust Patina
Condition
of Interior Flanges
Rating
of Interior
Flanges
Rust Patina
Condition
of Interior Webs
Rating
of Interior
Webs
Overall
Qualitative
Assessment
Rating
Condition
CO E-16-JW compact rust patina 1 compact rust patina 1 compact rust patina 1 compact rust patina 1 6 good
CO E-16-JX compact rust patina 1 compact rust patina 1 compact rust patina 1 compact rust patina 1 6 good
CO E-16-JZ compact rust patina 1 compact rust patina 1 compact rust patina 1 compact rust patina 1 6 good
CT 3830 compact rust patina 1 compact rust patina 1 small rust flakes 2 compact rust patina 1 9 good
CT 4382 compact rust patina 1 compact rust patina 1 small rust flakes 2 compact rust patina 1 9 good
CT 5796 small rust flakes 2 compact rust patina 1 small rust flakes 2 compact rust patina 1 10 good
IA 004111 compact rust patina 1 compact rust patina 1 large thick rust flakes 3 compact rust patina 1 12 poor
IA 041331 compact rust patina 1 compact rust patina 1 large thick rust flakes 3 small rust flakes 2 13 poor
IA 042711 compact rust patina 1 compact rust patina 1 large thick rust flakes 3 compact rust patina 1 12 poor
MN 04019 small rust flakes* 2 compact rust patina* 1 large thick rust flakes 3 compact rust patina 1 13 poor
MN 19811 compact rust patina 1 compact rust patina 1 large thick rust flakes 3 small rust flakes 2 13 poor
MN 62861 large thick rust flakes 3 large thick rust flakes 3 large thick rust flakes 3 large thick rust flakes 3 18 poor
NC 190083 compact rust patina 1 compact rust patina 1 compact rust patina 1 compact rust patina 1 6 good
NC 1290057 compact rust patina 1 compact rust patina 1 small rust flakes 2 compact rust patina 1 9 good
NC 1290058 compact rust patina 1 compact rust patina 1 small rust flakes 2 compact rust patina 1 9 good
NH 017201120011300 compact rust patina 1 compact rust patina 1 compact rust patina 1 compact rust patina 1 6 good
NH 11101120017900 compact rust patina 1 compact rust patina 1 large thick rust flakes 3 small rust flakes 2 13 poor
NH 017701460003700 compact rust patina 1 compact rust patina 1 large thick rust flakes 3 compact rust patina 1 12 poor
OH 7700105 compact rust patina 1 small rust flakes 2 large thick rust flakes 3 small rust flakes 2 14 poor
OH 7701977 compact rust patina 1 small rust flakes 2 large thick rust flakes 3 small rust flakes 2 14 poor
OH 7701993 compact rust patina 1 small rust flakes 2 large thick rust flakes 3 small rust flakes 2 14 poor
*The exterior of the fascia girder of bridge MN 04019 was obstructed by a sign, so samples were taken from the interior portion of the fascia girder instead
66
4.1.1 Colorado Bridges
All three Colorado bridges (CO E-16-JW, CO E-16-JX, and CO E-16-JZ) were in
the best condition out of all of the bridges that were inspected. The webs consisted of
smooth, compact rust patinas that were a light orange-maroon color. Refer to Figure 4.4
for a typical example of the webs of the Colorado bridges. It should be noted that all three
of the Colorado bridges were box girders, so samples were taken from the bottom of the
bottom flange rather than the top of the bottom flange. Refer to Table 4.2 for descriptions
of sample locations of the Colorado field bridges.
Figure 4.4 Typical Web Patina of Colorado Bridges
67
Table 4.2 Standard Sample Area Location Descriptions of Colorado Bridges
The bottoms of the bottom flanges appeared to not yet developed a full rust patina
as most of the steel was a smooth texture and grey in color (the research team members
who inspected these bridges questioned whether the bottom flanges were UWS because of
this observation). The rust that had developed so far was compact and an orange-maroon
color at these locations. Refer to Figure 4.5 for a typical example of the bottom of the
bottom flanges of the Colorado bridges. It was very difficult to scrape any material off of
these bridges. Overall, these bridges were in good condition because of their compact rust
patinas at all sampled locations.
Standard
Sample Area
Location ID
Colorado Field Bridge Location Descriptions
1 bottom of bottom flange of interior girder facing traffic over the shoulder
2 lower web of interior girder facing traffic over the shoulder
3 bottom of bottom flange of interior girder facing backside of traffic over the shoulder
4 bottom of bottom flange of exterior girder facing traffic over the shoulder
5 lower web of exterior girder facing traffic over the shoulder
6 bottom of bottom flange of exterior girder facing backside of traffic over the shoulder
7 bottom of bottom flange of interior girder facing traffic over the right travel lane
8 lower web of interior girder facing traffic over the right travel lane
9 bottom of bottom flange of interior girder facing backside of traffic over the right travel lane
10 bottom of bottom flange of exterior girder facing traffic over the right travel lane
11 lower web of exterior girder facing traffic over the right travel lane
12 bottom of bottom flange of exterior girder facing backside of traffic over the right travel lane
68
Figure 4.5 Typical Bottom of Bottom Flange Patina of Colorado Bridges
4.1.2 Connecticut Bridges
4.1.2.1 CT 3830
The exterior flange of the fascia girder of bridge CT 3830 was comprised of a
compact rust patina that was a light maroon color. Both the interior and exterior webs of
the bridge also had compact rust patinas that were a dark maroon color with dark orangey
streaks. The interior flanges’ patinas consisted of small rust flakes that were a light grey-
brown color with many maroon spots. Overall, this bridge was in good condition based on
the compact rust patina formed on the fascia beam and interior webs. The interior flanges
posed minor concerns with the small rust flakes.
4.1.2.2 CT 4382
The exterior flange of the fascia girder of bridge CT 4382 had a compact rust patina
that was a light brown-maroon color. Both of the exterior and interior webs also had
compact rust patinas. The exterior web location was a dark maroon color with dark orangey
69
spots. The interior webs were a dark maroon color with some dark orangey spots and
streaks. The interior flanges had small rust flakes and were a light grey-brown color with
some maroon spots. Overall, this bridge was in good condition based on the compact rust
patinas on the exterior portions of the fascia beam and interior webs. The interior flanges
posed minor concerns based on the small rust flakes observed.
4.1.2.3 CT 5796
Bridge CT 5796 had small rust flakes present on all of the flanges. The rust patina
on the flanges was a light grey-brown color with many maroon spots. Refer to Figure 4.6
for a typical example of the flanges of the Connecticut bridges. The interior and exterior
webs both had compact rust patinas that were a dark maroon color with dark orangey
streaks. Refer to Figure 4.7 for a typical example of the interior and exterior webs of the
Connecticut bridges. Overall, this bridge was in good condition because of the compact
rust patinas formed on the webs. The small rust flakes that were observed on the flanges
posed minor concerns.
70
Figure 4.6 Typical Flange Patina of Connecticut Bridges
Figure 4.7 Typical Web Patina of Connecticut Bridges
71
4.1.3 Iowa Bridges
4.1.3.1 IA 004111
The exterior web of the fascia girder of bridge IA 004111 had a compact rust patina
that was a dark maroon color. The fascia girder’s exterior flange and interior webs both
had compact rust patinas that were a dark maroon color with orangey spots. The interior
flanges had large thick rust flakes that were a grey color with orangey spots. Overall, this
bridge was in poor condition because of the large thick rust flakes found on the interior
flanges.
4.1.3.2 IA 041331
The exterior flange and web of the fascia girder of bridge IA 041331 both had
compact rust patinas that were a dark maroon color with orangey-grey spots. The interior
webs had small rust flakes that were easy to scrape off and were a dark orange color. The
interior flanges had large thick rust flakes that were easy to peel off and were a grey color
with orangey spots. Overall, this bridge was in poor because condition when considering
the large thick rust flakes found on the interior flanges.
4.1.3.3 IA 042711
The exterior flange of the fascia girder of bridge IA 042711 had a compact rust
patina that was a grey color with orangey spots. The interior and exterior webs had compact
rust patinas that were a dark maroon color with some orangey spots. Refer to Figure 4.8
for a typical example of the exterior and interior webs of the Iowa bridges. The interior
flanges had large thick rust flakes that were easily peeled off and were a grey color with
orangey spots. Refer to Figure 4.9 for a typical example of the interior flanges of the Iowa
bridges. The interior flange of the exterior girder was in the worst condition of the locations
that were assessed on the bridge because most of the rust patina was already flaked off.
72
Overall, this bridge was in poor condition because the interior flanges were comprised of
large thick rust flakes.
Figure 4.8 Typical Web Patina of Iowa Bridges
73
Figure 4.9 Typical Interior Flange Patina of Iowa Bridges
4.1.4 Minnesota Bridges
4.1.4.1 MN 04019
The exterior of the fascia girder of bridge MN 04019 was obstructed by a sign, so
samples were taken from the interior portion of the fascia girder. The interior web of the
fascia girder had a compact rust patina that was a dark brown color with some orangey
streaks. The web of the interior girder also had a compact rust patina but showcased a dark
brown color with orangey spots instead of streaks. Refer to Figure 4.10 for a typical
example of the interior webs of bridge MN 04019. The interior flanges of the bridge
exhibited large thick rust flakes that were a grey color with brown spots. Refer to Figure
4.11 for a typical example of the interior flanges of bridge MN 04019. Overall, this bridge
was in poor condition because of the flaking rust patinas found at the flange locations.
74
Figure 4.10 Typical Interior Web Patina of Bridge MN 04019
Figure 4.11 Typical Interior Flange Patina of Bridge MN 04019
75
4.1.4.2 MN 19811
The exterior flange of the fascia girder of bridge MN 19811 had a compact rust
patina that was a brown color with white spots. The exterior web of the fascia girder also
had a compact rust patina that was a dark brown color with some orangey streaks. Refer to
Figure 4.12 for an example of the exterior flange and web of the fascia girder of bridge
MN 19811. The interior flanges’ rust patinas were comprised of large thick rust flakes and
were grey and brown in color. The interior webs had small rust flakes and was brown with
dark maroon spots. Refer to Figure 4.13 for typical example of the interior flanges and
webs of bridge MN 19811. Overall, this bridge was in poor condition because of the flaking
rust patinas of the interior sections of the bridge.
Figure 4.12 Exterior Flange and Web Patinas of the Fascia Girder of Bridge MN 19811
76
Figure 4.13 Typical Interior Flange and Web Patinas of Bridge MN 19811
4.1.4.3 MN 62861
The exterior flange of the fascia girder of bridge MN 62861 had large thick rust
flakes that were a greyish brown color. The interior flanges also had rust patinas with large
thick rust flakes that had a smooth texture and were a grey color. Underneath the smooth
grey flakes the steel was a dark marron color with some orangey spots. The rust patinas of
the both the exterior and interior webs also had large thick rust flakes which were a grey
color with some orangey spots. Refer to Figure 4.14 for a typical example of the flanges
and webs of bridge MN 62861. Overall, this bridge was in poor condition and was
subjectively the worst performing bridge relative to the other two Minnesota bridges
because all portions that were evaluated exhibited large thick rust flakes.
77
Figure 4.14 Typical Flange and Web Patinas of Bridge MN 62861
4.1.5 North Carolina Bridges
4.1.5.1 NC 190083
Bridge NC 190083 was the only field bridge that was evaluated that crossed a
railroad. All portions of bridge NC 190083 consisted of compact rust patinas with no
observed flaking or pitting. The exterior and interior flanges were both a light brown-
maroon color with dark maroon spots. The exterior web was a dark maroon color with dark
orangey-brown streaks while the interior webs were a dark maroon color with dark maroon
spots. Refer to Figure 4.15 for a typical example of the flanges and webs of bridge NC
190083. Overall, this bridge was in good condition because of the compact rust patinas.
78
Figure 4.15 Typical Flange and Web Patinas of Bridge NC 190083
4.1.5.2 NC 1290057
. The exterior of the fascia girder of bridge NC 1290057 exhibited compact rust
patinas that were both a dark maroon color with orange and brown spots. The interior webs
of the bridge also had compact rust patinas that were a dark maroon color with orangey
streaks. Refer to Figure 4.16 for a typical example of the exterior flange and webs of bridge
NC 1290057. The interior flanges of the bridge had small rust flakes and was a greyish
maroon color with orangey spots. Refer to Figure 4.17 for a typical example of the interior
flanges of bridge NC 1290057. Overall this bridge was in good condition because all
inspected locations of the girders showcased compact rust patinas with only minor
concerns of small rust flakes on the interior flanges.
79
Figure 4.16 Typical Exterior Flange and Web Patinas of Bridge NC 1290057
Figure 4.17 Typical Interior Flange Patina of Bridge NC 1290057
80
4.1.5.3 NC 1290058
The exterior flange of the fascia girder of bridge NC 1290058 consisted of a
compact rust patina and were a light brown-maroon color with dark maroon spots. The
exterior and interior webs both exhibited compact rust patinas and were a dark maroon
color with dark orangey-brown streaks. Refer to Figure 4.18 for a typical example of the
exterior flange and webs of bridge NC 1290058. The interior flanges had a mysterious
moist dark grey film covering them. This can be seen in Figure 4.19, which shows a typical
example of the interior flanges of bridge NC 1290058. It appeared the actual rust patina
was underneath the film when scrapping for samples which had some small rust flakes and
was a spotty maroon-orangey color. Overall, this bridge was in good condition because it
mostly consisted of compact rust patinas. There were only minor concerns regarding the
interior flanges which had a mysterious moist dark grey film covering them and exhibited
small rust flakes.
Figure 4.18 Typical Exterior Flange and Web Patinas of Bridge NC 1290058
81
Figure 4.19 Typical Interior Flange Patina of Bridge NC 1290058
4.1.6 New Hampshire Bridges
4.1.6.1 NH 017201120011300
All exterior and interior locations of the bridge that were evaluated showcased
compact rust patinas with no observed flaking or pitting. Refer to Figure 4.20 for a typical
example of the flanges and webs of bridge NH 017201120011300. The flanges were
typically a light maroon color while the webs were typically a dark spotty grey and maroon
color with a lot of orangey spots. Overall, this bridge was in good condition and was
subjectively the best performing bridge of the three bridges inspected in the NH cluster.
82
Figure 4.20 Typical Flange and Web Patinas of Bridge NH 017201120011300
4.1.6.2 NH 11101120017900
Bridge NH 11101120017900 was not originally included as a field bridge for the
NH cluster. Refer to Section 3.1.5 for reasoning of including this bridge as a field bridge
in the NH cluster. The interior flanges of bridge NH 11101120017900 had a smooth texture
on the surface and were a light grey-brown color. When scraping the interior flanges to
collect rust samples, large thick rust flakes would chip off and pitting was created. Refer
to Figure 4.21 for a typical example of the interior flanges of bridge NH 11101120017900.
The patina of the exterior flange and web of the fascia girder had compact rust patinas that
were a rough texture and a dark maroon color with some orangey spots. Refer to Figure
4.22 for a typical example of the exterior flange and webs of bridge NH 11101120017900.
The interior webs exhibited small rust flakes as can be seen in Figure 4.23. Overall, this
bridge was in poor condition because of the large thick rust flakes that easily chipped off
when physically scraping the patina on the interior flanges as well as the small rust flakes
on the interior webs.
83
Figure 4.21 Typical Interior Flange Patina of Bridge NH 11101120017900
Figure 4.22 Typical Exterior Flange and Web Patina of Bridge NH 11101120017900
84
Figure 4.23 Typical Interior Web Patina of Bridge NH 11101120017900
4.1.6.3 NH 017701460003700
Bridge NH 017701460003700 had a lot of birds living on the underside of the
structure. There were multiple nests and bird droppings found along the flanges of the
interior beams. The interior flanges showcased thick large rust flakes. The flanges were
typically a light maroon color. Refer to Figure 4.24 for a typical example of the interior
flanges of bridge NH 017701460003700. The exterior flange of the fascia girder as well as
the interior and exterior webs both consisted of compact rust patinas. The webs were
typically a dark maroon color with some orangey streaks. Refer to Figure 4.25 for a typical
example of the exterior flange and webs of bridge NH 017701460003700. Overall, this
bridge was in poor condition because of the large thick rust flakes and bird nests observed
on the interior flange locations.
85
Figure 4.24 Typical Interior Flange Patina of Bridge NH 017701460003700
Figure 4.25 Typical Exterior Flange and Web Patinas of Bridge NH 017701460003700
86
4.1.7 Ohio Bridges
4.1.7.1 OH 7701977
The exterior flange of the fascia girder of bridge OH 7701977 had a compact rust
patina that was a brown color with grey spots. Both the interior and exterior webs had small
rust flakes that were a dark maroon color with some orangey stripes. The interior flanges
had large thick rust flakes that were a grey and dark brown color. Overall, this bridge was
in poor condition because of the flaking rust patinas observed at interior sections of the
bridge.
4.1.7.2 OH 7701993
The exterior flange of the fascia girder of bridge OH 7701993 had a compact rust
patina that was a brown color with grey spots. Both the interior and exterior webs had small
rust flakes that were a dark maroon color with some orangey stripes. The interior flanges
had large thick rust flakes with a rough texture on the surface. The rust flakes were easy to
peel off and were a brown color. Overall, this bridge was in poor condition because of the
flaking rust patinas observed at interior sections of the bridge.
4.1.7.3 OH 7700105
The exterior flange of bridge OH 7700105 had a compact rust patina that was a
brown color with grey spots. Refer to Figure 4.26 for a typical example of the exterior
flanges of the Ohio bridges Both the interior and exterior webs had small rust flakes that
were a dark maroon color with some orangey spots. Refer to Figure 4.27 for a typical
example of the interior and exterior webs of the Ohio bridges. The interior flanges had
large thick rust flakes with some already flaked off that were a grey color with small orange
spots. Refer to Figure 4.28 for a typical example of the interior flanges of the Ohio bridges
87
Overall, this bridge was in poor condition because of the flaking rust patinas observed at
interior sections of the bridge.
Figure 4.26 Typical Exterior Flange Patinas of Ohio Bridges
88
Figure 4.27 Typical Interior and Exterior Web Patinas of Ohio Bridges
Figure 4.28 Typical Interior Flange Patinas of Ohio Bridges
89
4.2 Findings Related to Bridge Maintenance Practices
4.2.1 Findings from Review of Maintenance Manuals
As part of the maintenance survey that was sent out to 52 agencies, each agency
was asked to provide any bridge maintenance manuals, as described by Question 1 in
Appendix E.1. The purpose of this was to ultimately form possible correlations between
UWS bridge performance and the maintenance practices described in each agencies’
maintenance manual.
4.2.1.1 Response Rates
A summary of the type of responses received (or lack thereof) from the 52 agencies
in terms of maintenance manuals is shown in Appendix F, Table F.1. Overall, bridge
maintenance manuals were available for review from a total of 34 agencies. Twenty-one
(21) agencies that responded to the survey supplied maintenance manuals pertaining to
bridge maintenance practices and manuals were available from an additional thirteen (13)
agencies from prior work (Shenton, 2016). Twelve (12) agencies responded but were
unable to provide a manual. Of these twelve (12), four (4) agencies responded explaining
that they were in the process of working on a manual and eight (8) agencies responded
stating that they did not have a bridge maintenance manual. There were 19 agencies that
did not respond to the survey, and therefore did not provide a manual.
4.2.1.2 Review of Maintenance Manuals Results
The bridge maintenance manuals that were available from the 34 agencies were
each reviewed in terms of information relevant to UWS bridge performance. There were
common categories that were found between most of the manuals. These categories
included joint maintenance, bearing maintenance, bridge washing, girder maintenance,
90
information specific to UWS bridges, and corrosion. Table 4.3 lists the specific categories
of information that were established to organize the contents provided in various manuals.
91
Table 4.3 Maintenance Manual Review
AgencyJoint
Clean
Joint
Repair/
Maint.
Joint
Elim.
Bearing
Clean
Bearing
Repair/
Maint.
Girder
Clean
Bridge
Wash
(gen.)
Beam
End
Wash
(only)
Girder
Repair/
Maint.
UWS
SpecificCorrosion
Objective
Manual
Rating1
Subjective
Manual
Rating2
AL X X — X — — — — X — — 2 2
AZ — — — — — — — — — — — 0 1
AR X X X — — — — X — — — 2 3
CA — X — — — — — — X — — 1 2
CO — X X — X — X — — X X 2 3
CT — X — — X — X — — — X 2 2
DE — X — X X X — — X — — 2 3
FL — X — X X — — — X — X 2 3
GA X X — — X — — — X — — 2 3
HI — X — — X — — — X — — 1 2
IN X — — X — — — X — — — 1 2
IA X X — — X X — — X — — 2 3
MA — — — — — — — — — — — 0 1
MD X X — X X — — — — — — 2 2
MI — X — — — — X — — — — 1 2
MN X X — X X — — — X X — 2 2
MO X X — X X X — — — — — 2 3
MT X X — X — X — — — — — 2 2
NE X X — X X X — — X — X 3 3
NV — X — — X — — — X — X 2 3
NH — — — — — — X — — — — 1 1
NJ — X — — X — — — X X X 2 3
NM — X — — — — — — X — — 1 2
NY — X — X X — — X X X — 2 3
ND X X — X X X — — — — — 2 3
OH — X — — X — — — X — X 2 3
PA X X X X X X — — X — X 3 3
TX X — — — — — — — — — — 1 2
UT — — — — — — — — — — — 0 1
VA — X X — — — — — X — X 2 3
WA X X — — — — — — — — — 1 2
WI X X X X X — — X — — X 3 3
WY X X — X X — — — — — — 2 2
Total 16 27 5 14 19 7 4 4 16 4 10
X = relevant information available
— = no relevant information1 manual rated based on the number of categories it contained with maintenance information relevant to WS performance:
3 = greater than 6 categories
2 = greater than 3, but less than 6 categories
1 = greater than 0, but less than or equal to 3 categories
0 = 0 categories2 manual rated based on qualitative judgement of information provided relevant to WS maintenance:
1 = no repair/maintenance information
2 = mentions repair/maintenance information
3 = extensive repair/maintenance information
(ie. provides information on defects along with suggested repairs/maintenance)
92
Of the 34 manuals that were reviewed, a majority of them (27) included information
about maintaining and / or repairing joints and 16 manuals had information about joint
cleaning. Maintaining and / or repairing bearings was another category that was found in
most (19) of the manuals that were reviewed and 14 had information about bearing
cleaning. Sixteen (16) manuals provided information regarding girder repair and / or
maintenance and ten (10) had information about corrosion issues. The less common
categories of information included bridge washing in terms of girder cleaning (7), joint
elimination (5), information specific to UWS (4), and general bridge washing information
(4), and washing beam ends (4).
To experiment with different ways of quantifying this information, an objective
rating, ranging between 0 and 3, was given to each manual based on the number of the
categories listed in Table 4.2 that it contained. An objective rating of 3 corresponded to
more than 6 categories, a rating of 2 corresponded to 4 or 5 categories, a rating of 1
corresponded to 1 to 3 categories, and a 0 corresponded to 0 categories. A subjective rating,
ranging between 1 and 3, was also given based on the extent of information provided in
the manual. For the subjective rating, a rating of 3 corresponded to extensive information
such as likely defects along with suggested repair and / or maintenance activities; a rating
of 2 corresponded to a mention of repair and / or maintenance activities, and a rating of 1
corresponded to no repair and / or maintenance information.
Figure 4.29 and Figure 4.30 show a summary of the objective and subjective
manual ratings, respectively. Figure 4.29 shows that most of the manuals that were
reviewed contained information on 4 or 5 of the categories listed in Table 4.3 based on
there being 19 agencies with an objective manual rating of 2. The two most common
categories of maintenance information that these manuals included were related to joint
repairs/maintenance (19 manuals) and bearing repairs/maintenance (15 manuals). Figure
93
4.30 shows that the scope of information provided in the manuals is generally rather
detailed. There were three manuals (one from Nebraska, one from Pennsylvania, and one
from Wisconsin) that received both an objective and subjective rating of 3, meaning they
included a majority of the maintenance categories and provided information about bridge
defects along with suggested repairs or maintenance practice protocols. These were the
overall highest rated manuals. Three manuals (one from Arizona, one from Massachusetts,
and one from Utah) received an objective rating of 0 and subjective rating of 1 meaning
they included none of the maintenance categories and had no maintenance or repair
information. These were the overall lowest rated manuals. Future work will include using
these objective and subjective manual ratings to assess correlations with UWS bridge
performance.
Figure 4.29 Objective Manual Ratings, by Agency
Rating = 3, 3
Rating = 2, 19
Rating = 1, 8
Rating = 0, 3
94
Figure 4.30 Subjective Manual Rating, by Agency
4.2.2 Findings from Washing Practices Survey
The survey on washing practices aimed to:
• Determine whether agencies washed bridges or not.
• Quantify the approximate percentage of UWS bridges washed: none, <
10%, 10 – 50%, or > 50%.
• Quantify washing frequency: more than once per year, annually, every
two years, or less frequently than every two years.
• Determine if bridges were: not washed in any particular time of year,
typically washed in the Spring, or typically washed during some other
time of year.
• Determine if the washing practices for UWS bridges included the
girders: always, at least half of the time (i.e., mostly), less than half of
the time (i.e., rarely), or never.
• Determine if different washing practices existed for UWS bridges and
other bridges.
Rating = 3, 16
Rating = 2, 13
Rating = 1, 4
95
The focus of this section is to discuss the responses to the above questions. In
addition to the surveying conducted as part of the present research, it was also discovered
that the American Association of State Highway and Transportation Officials’ (AASHTO)
Highway Subcommittee on Bridges and Structures (SCOBS) conducts an annual “State
Bridge Engineers Survey” (AASHTO, 2018). This survey contains the following questions
regarding bridge washing:
• Does your Agency utilize bridge-washing contracts?
• Has your Agency successfully included any of these preventative
maintenance activities on a bridge-washing contract?
• Has your Agency conducted a comprehensive study of the cost-
effectiveness of bridge cleaning and washing measures?
• Has your Agency evaluated the effect of a periodic program of bridge
cleaning and washing on the service life of bridge elements?
The comparison of the responses to these questions for the most recent surveying year is
also discussed in Section 4.2.2.1 (AASHTO, 2018).
4.2.2.1 Response Rates
Responses in terms of washing practices were received from the 33 state highway
agencies listed in Appendix F, Table F.2. The data in Table F.2 is summarized by Figures
4.31 – 4.33. These figures report the numbers of agencies in different categories, based on
a fixed sample size of 52 possible participants (one from each state highway agency in
addition to the highway agencies in the District of Columbia and Puerto Rico).
96
Figure 4.31 Approximate Percentages of Bridges Washed, by Agency
Figure 4.32 Frequency of Bridge Washing, by Agency
>50%, 7
10-50%, 8
<10%, 4
0%, 11
No Data, 22
Annually, 12
Every 2 Years, 5
Less Frequently, 5
No Data, 30
97
Figure 4.33 Frequency of Girder Washing, by Agency
4.2.2.2 Washing Practices Survey Results
Figure 4.31 shows that 19 agencies reported performing bridge washing to some
extent (sum of the agencies in the >50%, 10-50%, <10% approximate percentage of bridges
washed categories). This represents a majority of the agencies that responded to the survey,
63% of respondents, but only 37% of all agencies. In comparison, 12 agencies out of 40
respondents reported utilizing bridge washing contracts in the AASHTO survey
(AASHTO, 2018). It is possible that the discrepancy in the present survey and the
AASHTO survey is related to the specificity of asking if bridges were washed by contracts
in the AASHTO survey, given that some owners may use their own resources to perform
bridge washing (AASHTO, 2018).
Even though the majority of the respondents in the present survey indicated that
they do perform bridge washing, this should not be interpreted to mean that bridge washing
Always, 2 Typically, 1
Rarely, 8
No, 8
No data, 33
98
is a common practice. This conclusion is based on that fact that Figure 4.31 indicates that
only 7 agencies reported that they wash more than 50% of their bridges.
Figure 4.32 shows that 22 agencies provided information on the frequency of bridge
washing. Figure 4.32 also shows that for bridges that are washed, this is typically conducted
annually (55% of respondents) or bi-annually (23% of respondents). More frequently than
annually was an option provided in the survey, but no agencies reported washing more
frequently than annually. Regarding the time of year during which washing is performed,
16 agencies reported that this was performed in the spring. No other regular time of year
was reported, but 1 agency reported that the time of year varied based on contracts.
Figure 4.33 shows that it is relatively rare for the girders of the bridge to be washed,
with the washing typically limited to other components such as decks, bearings, and / or
drainage systems. Only 3 agencies reported typically or always washing the girders:
Minnesota, Rhode Island, and Washington.
The majority of respondents indicated that they have equivalent washing practices
for UWS and other bridge types. Five agencies reported that they have different practices,
but no details on the differences were provided or could be discerned from the agencies’
maintenance manuals.
Regarding the other aspects of bridge washing that were queried by the AASHTO
survey, no more than one agency indicated the successful use of any other preventative
maintenance activity on a bridge washing contract (AASHTO, 2018). These items
represent fairly generic items. Those that were reported to be successful by a single agency
were: joint sealing, spot painting, joint closures, bridge repairs, drainage repairs, bearing
replacement, corrosion protection, and other. No agencies reported having conducted any
analysis of cost-effectiveness or service life related to bridge washing.
99
4.3 Findings Related to Deicing Agent Usage
4.3.1 Findings from Deicing Agent Usage Survey
Each of the 52 LTBPP state coordinators were asked to supply information
regarding their use of deicing agents. The specific wording of this request can be found as
Question 3 in the survey shown in Appendix E.1. The purpose of this was to assess possible
correlations between UWS bridge performance and amounts of corrosive deicing agents
being applied to roadways. For the purposes of this research, corrosive deicing agents were
defined as those containing chloride, which is known to negatively impact performance of
UWS.
4.3.1.1 Response Rates
In the original survey (Appendix E.1) that was sent out, each agency was asked to
supply as much information as possible regarding salts or chemicals used for deicing and
snow removal. A wide range of types of responses was received in terms of the deicing
chemicals that were used and the level of detail of the data. To refine this information, the
chemicals that were reported by each agency were categorized into corrosive solids,
corrosive brines, and other. Corrosive solids included chloride containing chemicals such
as sodium chloride, magnesium chloride, and calcium chloride. Corrosive brines included
brines containing chloride chemicals such as, sodium chloride brine, magnesium chloride
brine, calcium chloride brine, and prewetting brine. Quantities of other (non-chloride
containing) deicing agents were deemed too variable to be meaningfully synthesized. A
total of 30 responses were received from the original survey. The data that was provided
revealed that the most relevant data that was widely available was agency-wide average of
annual quantities per lane mile. Deicing agent quantities per lane mile provided more
valuable information by normalizing the data between each agency.
100
Thus, a follow-up survey (Appendix E.2 and Appendix E.3) requested deicing
agent usage to be reported in amounts per lane mile if not already provided. A total of 24
responses were received from the follow-up survey, representing 21 clarifying responses
and 3 new responses. At this stage, the existing normalized deicing agent data was
reviewed and found to be highly variable, even between agencies with relatively similar
environments. Thus, the data that had been received from each agency was compared to
the average quantities. Then, this information was shared with the owners and the owners
were asked to confirm if this comparison was reasonable in their opinion or if the data
should be updated (see example text for this inquiry in Question 1 of the follow-up survey
for prior participants shown in Appendix E.2). This process resulted in correcting some
misunderstandings about the type of data that was being sought (e.g., cumulative annual
totals versus application rates per pass of a plow truck) and other reporting errors. All final
data has been reviewed for reasonableness and found to be satisfactory.
Near the conclusion of the data collection period, one of the respondents forwarded
state-level data on deicing agents collected by Clear Roads. Clear Roads “is a national
research consortium focused on rigorous testing of winter maintenance materials,
equipment and methods for use by highway maintenance crews” (Clear Roads, 2019). The
Clear Roads quantities and lane miles were found to be in general agreement with the
deicing agent data that had been previously collected. In 21 cases, the Clear Roads data
contained information from agencies for which no data or incomplete data had been
received as part of the maintenance survey. In these situations, the Clear Roads data was
extracted and added to the data set. In total, deicing agent data is available from 39 agencies
and available in terms of quantities per lane mile from 37 agencies.
There were 4 agencies (Maryland, New Hampshire, Pennsylvania, and Wisconsin)
that supplied a geographic breakdown of their deicing agent usage. The geographic
101
breakdowns included deicing agent usage by different regions (e.g., districts or counties)
within each agency. Specifically, Maryland supplied records for each of their 7 districts,
Pennsylvania and Wisconsin provided data for each of their counties, and New Hampshire
differentiated their data by northern or southern half of the state and the type of roadway
(e.g., interstate, primary and secondary highways). Table 4.4 shows the state average
compared to the local jurisdiction maximum and minimum deicing agent usage for the 4
agencies that supplied regional data.
Table 4.4 Regional Deicing Agent Use Statistics
The data in Table 4.4 is in terms of corrosive solids applied per lane mile, because
only Wisconsin supplied information on corrosive brines at this level of detail. The data
in Table 4.4 shows that the maximum is between 2 and 9 times the minimum deicing agent
use for these four agencies and the maximum is on average twice the average deicing agent
use for these four agencies. The region corresponding with the maximum and minimum
application rates for each agency is also listed. The county level corrosive brine data
provided by Wisconsin showed a variability between 0 (in multiple counties) and 477
gallons/lane mile in Florence County (which is in a rural area), with an average of 76.8
gallons/lane mile. This suggests that maximum deicing agent use is more driven by
topography than population as the maximum deicing agent use generally occurs in rural
Agency
Average
Corrosive
Solids/Lane
Mile
(tons/lane
mile)
Maximum
Corrosive
Solids/Lane
Mile
(tons/lane
mile)
Region with Maximum Corrosive
Solids/Lane Mile
Minimum
Corrosive
Solids/Lane
Mile
(tons/lane
mile)
Region with Minimum
Corrosive Solids/Lane Mile
Maryland 12.1 31.2 District 6 (mountainous and rural) 3.5 District 1 (rural)
New Hampshire 28 41 Interstates in Northern Half of NH 22 Primary and Secondary Highways in Southern Half of NH
Pennsylvania 7.7 14.1 Butler (suburban) 2.7 Juniata (rural)
Wisconsin 15.3 25.3 Vilas (rural) 5.4 Richland (urban)
102
areas. This information may be used to further assess what effects deicing agent usage has
on UWS bridges located in specific regions for these 4 agencies.
4.3.1.2 Deicing Agent Usage Survey Results
Appendix F, Table F.3 shows amounts of corrosive solids and corrosive brines for
the 38 agencies from which this data was available. Total quantities are reported in terms
of tons of corrosive solids (defined as chloride containing chemicals, which included
sodium chloride, magnesium chloride, and calcium chloride) and gallons of corrosive
brines (defined as brines containing chloride, which included sodium chloride brine,
magnesium chloride brine, calcium chloride brine, and prewetting brine). The total number
of lane miles that these deicing agents were applied to by each agency is also reported in
Appendix F, Table F.3. In some cases, there are differing numbers of lane miles for solids
and brines and both numbers are reported, respectively. Deicing agent usage was also
recorded in terms of quantities per lane mile in order to normalize the data and be able to
compare usage rates between each agency.
Appendix F, Table F.4 shows the statistics for the deicing agent data. The median,
mean, standard deviation, maximum, and minimum are reported for corrosive solids,
corrosive solids per lane mile, corrosive brines, and corrosive brines per lane mile. These
statistics can allow comparisons to be made between the deicing agent data for each
agency. For instance, the individual data for each agency can be compared with the mean
or median to see if that agency uses a relatively high or low amount of deicing agents
compared with the rest of the data set. The average amount of corrosive solids per lane
mile was 10.0 tons per lane mile and the average amount of corrosive brines per lane mile
was 156.0 gallons per lane mile.
103
Figure 4.34 graphs the amounts of corrosive solids and corrosive brines in amounts
per lane mile for each agency for which deicing agent usage data was available. This graph
demonstrates the variability in amounts of corrosive chemicals that each agency applied to
their roadways. This data will be used to assess its correlation with UWS bridge
performance.
Figure 4.34 Deicing Agent Usage, by Agency with Available Data
4.4 Field Results
4.4.1 Tape Test Results
The clear tape adhesion test was performed on each field bridge at each of the 12
sample locations except for bridge MN 04019, which only had 10 samples taken (no
samples taken from standard sample area locations 4 and 10) because the top of the bottom
flange of the exterior of the fascia was obstructed by a sign. It was assumed that the test
could provide insight regarding the performance of UWS based on a digital image
0.00
200.00
400.00
600.00
800.00
1,000.00
1,200.00
1,400.00
0
10
20
30
40
50
60
Ala
bam
a
Ala
ska
Ari
zona
Cal
iforn
ia
Colo
rado
Conn
ecticu
t
Del
aw
are
Flo
rida
Geo
rgia
Idah
o
Illi
no
is
India
na
Iow
a
Kan
sas
Ken
tuc
ky
Mai
ne
Mar
yla
nd
Mas
sach
use
tts
Mic
hig
an
Min
nes
ota
Mis
souri
Mon
tana
Neb
rask
a
New
Ham
psh
ire
New
York
Nort
h D
ako
ta
Ohio
Ore
gon
Pen
nsy
lvan
ia
Rho
de
Isla
nd
South
Dak
ota
Texas
Uta
h
Ver
mon
t
Wash
ingto
n
West
Vir
gin
ia
Wis
co
nsi
n
Gal
lon
s per
Lan
e M
ile
Tons
per
Lan
e M
ile
Agency
Corrosive Solids Corrosive Brines
104
processing assessment of particle sizes and spatial densities of rust particles that adhered
to the tape. Appendix G.1 shows cropped digital images of each tape sample. Each bin of
rust particle sizes that were categorized (e.g., 0 to 1/32 inch, 1/32 to 1/16 inch, 1/16 to 1/8
inch, 1/8 to 1/4 inch, 1/4 to 1/2 inch, 1/2 to 1 inch, 1 to 2 inches, and 2 to 4 inches) was
used to assess the percent area of rust particles in each size range that occupied the tape
sample. Refer to Appendix G.2 for data tables of tape test results and Appendix G.3 for
tape test results standard deviations. It was assumed that assessing each percent area of rust
particles within each size range would provide insight into which size range correlated best
with determining performance of UWS. This assumption was made based on the idea that
if large rust particles adhered to the tape when peeled off of the steel that the rust patina
may be performing insufficiently. It was found that assessing the percent area of rust
particles greater than or equal to an 1/8 inch provided the most information relative to UWS
performance. Bar graphs of other rust particle size thresholds that were assessed (i.e.,
average overall percentage of rust particles (density), rust particles greater than or equal to
a 1/4 inch, and rust particles greater than or equal to a 1/2 inch) for the clusters, field
bridges, and standard sample area locations are shown in Appendix G.4. Considering rust
particle sizes less than a 1/8 inch made it difficult to assess differences between results
relative to UWS performance. The 1/8 inch threshold used for the tape test results is also
what was used in Phase 2 of this research project as discussed in Section 2.2.2.
4.4.1.1 Cluster Performance Based on Tape Test Results
The percent area of rust particles greater than or equal to an 1/8 inch from the tape
tests were averaged across each of the three field bridges within a cluster in order to
compare the relative performance of the seven clusters. The average percent area of rust
particles greater than or equal to an 1/8 inch for each cluster along with standard deviations
105
are shown in Figure 4.35. It should be noted that if the standard deviation of a cluster caused
the error bars to include negative values, the range of values was limited to a minimum
value of zero.
Figure 4.35 Average Percent Area of Rust Particles Greater than or Equal to an 1/8 inch,
by Cluster
The CO cluster had an average percent area of rust particles greater than or equal
to an 1/8 inch of 0.23%. This was the lowest value between the seven clusters and therefore
was assumed to be the best performing cluster in terms of the average percent area of rust
particles greater than or equal to an 1/8 inch. The CO cluster also had the smallest range in
values according to the standard deviation shown in Figure 4.35. The MN cluster had an
average percent area of rust particles greater than or equal to an 1/8 inch of 11.07%. This
was the greatest value between each of the seven clusters and, therefore was the worst
performing cluster in terms of the tape test results. The remaining five clusters’ average
0.23
8.15
3.41
11.0710.10
7.038.17
0.00
5.00
10.00
15.00
20.00
25.00
CO(good
deicing)
CT(inferior
deicing & coastal)
IA(inferior
deicing)
MN(inferior
deicing)
NC(good & inferior
coastal)
NH(good
deicing & coastal)
OH(good
deicing)
Per
cen
t A
rea
(%)
Cluster
106
percent area of rust particles greater than or equal to an 1/8 inch values from least to greatest
were IA – 3.41%, NH – 7.03%, CT – 8.15%, OH – 8.17%, and NC – 10.10%. The MN,
NC, NH, and OH clusters had the largest ranges in values according to the standard
deviations shown in Figure 4.35. It appears that clusters that had relatively higher average
percent areas of rust particles greater than or equal to an 1/8 inch also had a larger range in
their data sets, and vice versa when looking at the standard deviations shown in Figure
4.35. Bar graphs of the average percent area of rust particles greater than or equal to a 1/4
inch, average percent area of rust particles greater than or equal to a 1/2 inch, and the
average overall percentage of rust particles (density) from the tape tests are shown in
Appendix G.4, Figures G.4.1 – G.4.4.
4.4.1.2 Field Bridge Performance Based on Tape Test Results
The percent area of rust particles greater than or equal to a 1/8 inch from the tape
tests were averaged for each field bridge in order to compare the relative performance of
individual bridges. The average percent area of rust particles greater than or equal to a 1/8
inch along with standard deviations for each field bridge are shown in Figure 4.36. It should
be noted that if the standard deviation of a field bridge caused the error bars to include
negative values, the range of values was limited to a minimum value of zero.
107
Figure 4.36 Average Percent Area of Rust Particles Greater than or Equal to an 1/8 inch,
by Field Bridge
Each field bridge shown in Figure 4.36 is categorized by color based on the cluster
they belong to in order to make it simpler to compare bridges and clusters. It can be seen
that one field bridge in the NH cluster, two field bridges in the MN cluster, and one field
bridge in the NC cluster had the highest average percent areas of rust particles greater than
or equal to an 1/8 inch (NH 017701460003700 – 13.56%, MN 19811 – 13.93%, MN 62861
– 15.28%, NC 1290058 – 17.40%). These field bridges were the worst performing relative
to the other field bridges in terms of their tape test results. Field bridge NC 1290058 was
found to have a mysterious dark film present on the tops of the bottom flanges at interior
girder locations as mentioned in Section 4.1.5.3. This mysterious dark film was found to
cover most of the tape sample and may be why this field bridge had significantly higher
percent area value. Field bridges from CO had the lowest average percent areas of rust
particles greater than or equal to an 1/8 inch (CO E-16-JW – 0.13%, CO E-16-JX – 0.01%
CO E-16-JZ – 0.56%). These field bridges were the best performing relative to the other
field bridges in terms of their tape test results. The CT, NH, and OH clusters had field
0.13 0.01 0.56
6.82
12.23
5.403.07
5.521.63 2.58
13.9315.28
1.75
11.15
17.40
1.975.58
13.56
5.59
11.56
7.36
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
40.00
45.00
CO
E-1
6-JW
CO
E-1
6-JX
CO
E-1
6-JZ
CT 3
830
CT 4
382
CT 5
796
IA 0
0411
1
IA 0
4133
1
IA 0
4271
1
MN 0
4019
MN 1
9811
MN 6
2861
NC 1
9008
3
NC 1
2900
57
NC 1
2900
58
NH 0
1720
1120
0113
00
NH 1
1101
1200
1790
0
NH 0
1770
1460
0037
00
OH 7
7001
05
OH 7
7019
77
OH 7
7019
93
Per
cen
t A
rea
(%)
Field Bridge
108
bridges with similar results in terms of the average percent area of rust particles greater
than or equal to an 1/8 inch. It appears that field bridges that had relatively higher average
percent areas of rust particles greater than or equal to an 1/8 inch also had a larger range in
their data sets and vice versa when looking at the standard deviations shown in Figure 4.36.
Bar graphs of the average percent area of rust particles greater than or equal to a 1/4 inch,
average percent area of rust particles greater than or equal to a 1/2 inch, and the average
overall percentage of rust particles (density) for each field bridge are shown in Appendix
G.4, Figures G.4.5 – G.4.8.
4.4.1.3 Standard Sample Area Location Performance Based on Tape Test Results
The relative performance of individual sample area locations was assessed by
averaging the percent area of rust particles greater than or equal to an 1/8 inch from the
tape tests for each standard sample area location across all field bridges except for the CO
bridges because of the different standard sample area locations used for these bridges (refer
to Table 4.2). See Table 3.6 for descriptions of each of the 12 different standard sample
area locations. The average percent area of rust particles greater than or equal to an 1/8
inch along with standard deviations for each standard sample area location are shown in
Figure 4.37. It should be noted that if the standard deviation of a standard sample area
location caused the error bars to include negative values, the range of values was limited
to a minimum value of zero.
109
Figure 4.37 Average Percent Area of Rust Particles Greater than or Equal to an 1/8 inch,
by Standard Sample Area Location
It was found that sample locations 4, 5, 10, and 11 performed the best relative to
the rest of the locations. When looking at Figure 4.37 these four locations had the lowest
average percent area of rust particles greater than or equal to an 1/8 inch (sample location
4 had 2.56%, sample location 5 had 2.51%, sample location 10 had 2.40%, and sample
location 11 had 2.51%). One aspect that these four sample areas had in common was that
they were all located on the fascia of the exterior girders of each field bridge. Refer to Table
3.6 for the standard sample area location descriptions. The performance of these four
locations may relate to their exposure to environmental conditions such as rain and sunlight
being that they are on the fascia of the exterior girder. It has been reported that TOW plays
an important role in UWS patina formation. Therefore, the fascia of the exterior girder
being easily exposed to rain and sunlight may be a reason for these four locations
performing relatively well.
11.23
8.40
12.83
2.56 2.51
9.22
12.83
7.06
15.22
2.40 2.51
8.14
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
1 2 3 4 5 6 7 8 9 10 11 12
Per
cen
t A
rea
(%)
Standard Sample Area Location ID
110
Furthermore, it was found that sample locations 2, 6, 8, and 12 performed fairly
relative to the rest of the locations when looking at Figure 4.37 (sample location 2 had
8.40%, sample location 6 had 9.22%, sample location 8 had 7.06%, and sample location
12 had 8.14%). Sample locations 6 and 12 were located on the top of the bottom flanges of
the interior of the fascia girders. Sample locations 2 and 8 were located on the webs of the
interior girders. Refer to Table 3.6 for the standard sample area location descriptions. The
performance of these four locations may relate to exposure conditions being that they are
located on the interior portions of the bridge. The interior portions of the bridge are more
susceptible to retaining moisture because they are not exposed to sunlight that can allow
the steel to dry. This means that they may experience a longer TOW. Therefore, these four
interior locations may perform worse relative to the exterior locations on the fascia girder.
Finally, sample locations 1, 3, 7, and 9 performed the worst relative to the rest of
the locations. When looking at Figure 4.37 these three locations had the highest average
percent area of rust particles (sample location 1 had 11.23%, sample location 3 had 12.83%,
sample location 7 had 12.83%, and sample location 9 had 15.22%). One aspect that these
four sample areas had in common was that they were all located on the top of the bottom
flanges of the interior girders of each field bridge. Refer to Table 3.6 for the standard
sample location descriptions. The performance of these four locations may be correlated
with their exposure conditions. Similar to locations 2, 6, 8, and 12, locations 1, 3, 7, and 9
were also located on the interior portions of the bridge. However, locations 1, 3, 7, and 9
were each located on the top of the bottom flanges. The top surfaces of the bottom flanges
are susceptible to retaining moisture and the interior girder locations are more sheltered,
which may be why locations 1, 3, 7, and 9 performed the worst relative to the rest of the
sample area locations.
111
It appears that field bridges that had relatively higher average percent areas of rust
particles greater than or equal to an 1/8 inch also had a larger range in their data sets and
vice versa when looking at the standard deviations shown in Figure 4.37. Bar graphs of the
average percent area of rust particles greater than or equal to a 1/4 inch, average percent
area of rust particles greater than or equal to a 1/2 inch, and the average overall percentage
of rust particles (spatial density) for each standard sample area location are shown in
Appendix G.4, Figures G.4.9 – G.4.12.
4.4.2 Ion Chromatography Results
Ion chromatography tests were performed on rust samples collected from each field
bridge (except for bridges CO E-16-JW, NC 1290058, NH 017701460003700, and NH
11101120017900 as samples from these bridges were not yet processed at the time of this
writing due to the COVID-19 pandemic causing the University of Delaware’s labs to be
shut down during the semester in which this thesis was completed) at each of the sampled
locations. It was the objective to assess the influence of chloride, nitrate, and sulfate
concentrations on the characteristics of the rust samples based on prior knowledge
regarding the effects that these ions have on patina performance. Chloride ions typically
originate from deicing agents and salt spray from the ocean, nitrate ions typically come
from rainwater that originated from organic matter found in soil, and sulfate ions typically
come from air pollutants. From past research discussed in Chapter 2, chloride has been
found to be the most problematic ion affecting rust patina performance of UWS, sulfate
typically negatively impacts UWS performance within the initial stages of patina
formation, and nitrate was found to have minor effects on UWS performance. Refer to
Appendix H.1 for data tables IC analysis results and Appendix H.2 for IC analysis results
standard deviations.
112
Ion concentrations presented in Sections 4.4.2.1, 4.4.2.2, and 4.4.2.3 are relatively
larger than ion concentrations presented in Chapter 2. This difference may be due to what
the results are relative to. The ion concentrations in units of parts per million presented in
Sections 4.4.2.1, 4.4.2.2, and 4.4.2.3 are relative to the number of ions present in 1 kg of
rust. The ion concentrations in units of parts per million presented in Chapter 2 are
unknown what they are relative to because the field studies did not specify this information.
However, it is assumed they are relative to the amount of ions in a liquid solution.
4.4.2.1 Cluster Ion Chromatography Results
The ion chromatography results were used to assess the concentrations of ions
found in rust samples of each of the seven clusters by averaging results across each of the
three field bridges within a cluster. Figure 4.38 shows the results of the averaged chloride,
nitrate, and sulfate concentrations along with standard deviations for each cluster. Chloride
concentrations were typically the highest of the three different ions that were assessed in
each of the clusters except for the NC cluster, which had sulfate as the highest average ion
concentration between the three ions (chloride – 582 ppm, nitrate – 359 ppm, and sulfate –
2,670 ppm). It should be noted that if the standard deviation of a cluster caused the error
bars to include negative values, the range of values was limited to a minimum value of
zero.
113
Figure 4.38 Average Concentration of Chloride, Nitrate, and Sulfate Ions, by Cluster
One aspect of this research project was to assess the effects that the distance of
UWS bridges from the coast had on performance of the rust patina due to salt spray from
the ocean causing atmospheres in these environments to contain relatively higher
concentrations of chloride. The NC cluster was categorized as a coastal cluster with all
three field bridges being within less than 5 miles from the coast. However, the NC cluster
had the lowest average chloride concentration of 583 ppm relative to the other clusters.
This suggests that the effects of this coastal climate are less severe than the effects of
deicing agents in all other Phase 3 locations considered. The CO cluster, which is not
located near a coast and was considered a deicing cluster had the highest ion concentrations
12009
1816
4825
6229
583
1923
3537
1264
377 273 315 361 311 341
3545
9521517 1569
2745
396
2630
0
5000
10000
15000
20000
CO CT IA MN NC NH OH
Co
nce
ntr
atio
n (
pp
m)
Cluster
Average Chloride Average Nitrate Average Sulfate
114
of all three ions that were assessed (chloride – 12,009 ppm, nitrate – 1,264 ppm, and sulfate
– 3,545 ppm) relative to the other clusters. The CT (chloride – 1,816 ppm, nitrate – 377
ppm, and sulfate – 952 ppm) and NH (chloride – 1,923 ppm, nitrate – 311 ppm, and sulfate
– 396 ppm) clusters were categorized as combination deicing and coastal clusters; however,
they both had relatively low concentrations of chloride ions found in rust samples. The IA
(chloride – 4,825 ppm, nitrate – 273 ppm, and sulfate – 1,517 ppm), and MN (chloride –
6,229 ppm, nitrate – 315 ppm, and sulfate – 1,569 ppm), and OH (chloride – 3,537 ppm,
nitrate – 341 ppm, and sulfate – 2,630 ppm) clusters were categorized as deicing clusters.
Aside from the CO cluster, these three clusters had relatively high concentrations of ions
found in rust samples, especially chloride concentrations from the MN cluster.
4.4.2.2 Field Bridge Ion Chromatography Results
The ion chromatography results were averaged across all field bridges to compare
concentrations of chloride, nitrate, and sulfate ions between individual bridges. The
average concentrations of chloride, nitrate, and sulfate ions along with standard deviations
for each field bridge are shown in Figure 4.39, Figure 4.40, and Figure 4.41, respectively.
It should be noted that if the standard deviation of a field bridge caused the error bars to
include negative values, the range of values was limited to a minimum value of zero.
115
Figure 4.39 Average Concentration of Chloride, by Field Bridge
13437
10438
16682658
1052
4300
54094813 4650 4425
9216
563 601
1923
40323343 3236
0
5000
10000
15000
20000
CO
E-1
6-JX
CO
E-1
6-JZ
CT 3
830
CT 4
382
CT 5
796
IA 0
0411
1
IA 0
4133
1
IA 0
4271
1
MN 0
4019
MN 1
9811
MN 6
2861
NC 1
9008
3
NC 1
2900
57
NH 0
1720
1120
0113
00
OH 7
7001
05
OH 7
7019
77
OH 7
7019
93
Co
nce
ntr
atio
n (
pp
m)
Field Bridge
116
Figure 4.40 Average Nitrate Concentration, by Field Bridge
1582
913
393 406329
154
346 330220
456
246312
405311
365305
355
0
500
1000
1500
2000
2500
CO
E-1
6-JX
CO
E-1
6-JZ
CT 3
830
CT 4
382
CT 5
796
IA 0
0411
1
IA 0
4133
1
IA 0
4271
1
MN 0
4019
MN 1
9811
MN 6
2861
NC 1
9008
3
NC 1
2900
57
NH 0
1720
1120
0113
00
OH 7
7001
05
OH 7
7019
77
OH 7
7019
93
Co
nce
ntr
atio
n (
ppm
)
Field Bridge
117
Figure 4.41 Average Sulfate Concentration, by Field Bridge
Each field bridge shown in Figure 4.39, Figure 4.40, and Figure 4.41 is categorized
by color based on the cluster they belong to in order to make it simpler to compare bridges
and clusters. The average chloride concentrations were considerably much higher than the
average nitrate and sulfate concentrations for each field bridge. The CO E-16-JX bridge
had the highest average chloride (13,437 ppm), nitrate (1,582 ppm), and sulfate (5,094
ppm) concentrations as compared to the other field bridges. Bridge MN 62861 had a
relatively high average chloride concentration (9,216 ppm) as compared to the other field
bridges. The NC 190083 and NC 1290057 bridges had the lowest average chloride
concentrations (563 ppm and 601 ppm, respectively) as compared to the other field bridges.
Bridge NC 1290057 had a relatively high average sulfate concentration (4,396 ppm) as
compared to the other field bridges. Bridge NH 017201120011300 had a relatively low
5094
1841
1253
809 776 781
1843 19941634
2192
898 944
4396
396
1893
2781
3216
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
CO
E-1
6-JX
CO
E-1
6-JZ
CT 3
830
CT 4
382
CT 5
796
IA 0
0411
1
IA 0
4133
1
IA 0
4271
1
MN 0
4019
MN 1
9811
MN 6
2861
NC 1
9008
3
NC 1
2900
57
NH 0
1720
1120
0113
00
OH 7
7001
05
OH 7
7019
77
OH 7
7019
93
Co
nce
ntr
atio
n (
pp
m)
Field Bridge
118
average sulfate concentration (396 ppm) as compared to the other field bridges. The rest of
the field bridges had relatively intermediate average chloride, nitrate, and sulfate
concentrations that were comparable between each other.
4.4.2.3 Standard Sample Area Location Ion Chromatography Results
To compare concentrations of chloride, nitrate, and sulfate ions of individual
sample area locations, the ion chromatography results were averaged across all field
bridges except for the CO bridges because of the different standard sample area locations
used (refer to Table 4.2). See Table 3.6 for a description of each of the 12 different standard
sample area locations. Figure 4.42. shows the average chloride, nitrate, and sulfate ion
concentrations along with standard deviations for each of the 12 standard sample area
locations. It should be noted that if the standard deviation of a standard sample area location
caused the error bars to include negative values, the range of values was limited to a
minimum value of zero.
119
Figure 4.42 Average Concentration of Chloride, Nitrate, and Sulfate Ions, by Standard
Sample Area Location
The concentrations of nitrate found in rust samples across all standard sample area
locations were very similar as can be seen in Figure 4.42. Therefore, nitrate concentrations
were excluded from the proceeding discussion of comparing standard sample area locations
IC results. It was found that sample locations 5 and 11 had the lowest average
concentrations of chloride and sulfate ions relative to the rest of the locations (sample
location 5 had chloride – 1,473 ppm and sulfate – 646 ppm and sample location 11 had
chloride – 1,410 ppm and sulfate 452 ppm). These two sample areas were both located on
the exterior web of the fascia girders for each field bridge. Refer to Table 3.6 for the
standard sample area location descriptions. The low concentration of ions found at these
two sample locations may relate to their exposure to rainwater and vertical orientation.
Rainwater being able to run down the exterior webs may have aided in washing the ions
4755
2287
4364
2363
1473
4768
5356
2906
4879
2390
1410
4847
381 276 399 354 270 347 380 243 413 266 221401
2148
1231
2749
1283
646
2931
2103
1686
2406
964
452
2265
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
10000
1 2 3 4 5 6 7 8 9 10 11 12
Co
nce
ntr
atio
n (
pp
m)
Standard Sample Area Location ID
Average Chloride Average Nitrate Average Sulfate
120
off of the steel and may relate to these two sample areas having the lowest concentrations
of ions relative to the other sample locations.
Sample locations 1, 3, 6, 7, 9, and 12 from Figure 4.42 had the highest average
chloride and sulfate concentrations relative to the rest of the locations (sample location 1
had chloride – 4,755 ppm and sulfate – 2,148 ppm, sample location 3 had chloride – 4,364
ppm and sulfate – 2,749 ppm, sample location 6 had chloride – 4,768 ppm and sulfate –
2,931 ppm, sample location 7 had chloride – 5,356 ppm and sulfate – 2,103 ppm, sample
location 9 had chloride – 4,879 ppm and sulfate – 2,406 ppm, and sample location 12 had
chloride – 4,847 ppm and sulfate – 2,265 ppm). These six sample areas were all located on
the tops of the bottom flanges at interior portions of each field bridge. Refer to Table 3.6
for the standard sample area location descriptions. The interior location and horizontal
orientation of these sample areas may relate to higher concentration of ions being found in
the rust. The interior portions of bridges have no direct exposure to rainwater or sunlight
to rinse ions and dry off the steel. The horizontal orientation of the flanges makes these
locations susceptible to retaining moisture or debris. Furthermore, the interior portions of
bridges that cross over roadways may be subject to salt spray caused by vehicles driving
under the bridge. Uplift may cause deicing agents and other pollutants to blow up onto the
tops of the bottom flanges of interior portions of bridges and therefore cause higher
concentrations of ions to reside in these locations.
Sample locations 2, 4, 8, and 10 had intermediate average concentrations of
chloride and sulfate ions relative to the other sample locations as can be seen in Figure 4.42
(sample location 2 had chloride – 2,287 ppm and sulfate – 1,231 ppm, sample location 4
had chloride – 2,363 ppm and sulfate – 1,283 ppm, sample location 8 had chloride – 2,906
ppm and sulfate 1,686 ppm, and sample location 10 had chloride – 2,390 ppm and sulfate
– 964 ppm). Sample locations 4 and 10 were located on the tops of the bottom flanges of
121
the exterior portion of the fascia girder similar to locations 5 and 11; however, locations 5
and 11 were on the exterior web of the fascia girder. Refer to Table 3.6 for the sample
location descriptions. Locations 4 and 10 having slightly higher ion concentrations than 5
and 11 may be due to the horizontal orientation of the flanges being susceptible to retaining
moisture or debris. Sample areas 2 and 8 were located on the web of the interior girder and
may be susceptible to “tunnel-like” conditions as well as poor exposure to rainwater and
sunlight resulting in higher concentrations of ions found in the rust, but not as high
concentrations as the interior flange locations (e.g., sample locations 1, 3, 6, 7, 9, and 12)
122
Chapter 5
DATA CORRELATIONS DISCUSSION
5.1 Introduction
Correlations between various data types collected throughout this research project
(e.g., bridge maintenance manual ratings, reported bridge washing practices, reported
deicing agent usage, tape test results, IC analysis results, and UWS bridge condition
ratings) were assessed to understand any data trends. Data trends between bridge
maintenance manual ratings and tape test results, bridge washing practices and tape test
results, bridge washing practices and IC analysis results, deicing agent usage and tape test
results, as well as deicing agent usage and IC analysis results were compared to assess any
cause (maintenance practices and deicing agent use practices) and effect (tape test results
and IC analysis results) relationships. The IC analysis results and tape test results were also
compared to assess if there was a cause (IC analysis results) and effect (tape test results)
relationship. Data trends between UWS bridge condition ratings and tape test results were
compared to assess whether or not there was any agreement between these two methods
used for evaluating bridge performance. Evaluating these trends may provide insight
regarding maintenance practices, environments that are or are not suitable for UWS
bridges, and measures of UWS bridge performance.
The bridge maintenance manuals, bridge washing practices, and deicing agent
usage data received from the Colorado, Connecticut, Iowa, Minnesota, New Hampshire,
and Ohio agencies were compared with the tape test results as well as the IC analysis results
for each corresponding cluster. It should be noted that the data received from each agency
123
was applied to the corresponding cluster within that agency (hence the use of the term
“agency/cluster” in the proceeding sections). There was no bridge maintenance manual,
bridge washing practices, or deicing agent usage data provided by North Carolina,
therefore, correlations of these three data types could not be compared with the tape test
results and IC analysis results from the North Carolina cluster.
5.2 Correlations Between Bridge Maintenance Manual Ratings and Tape Test
Results
The ratings of bridge maintenance manuals that were reviewed were compared with
tape test results because it was assumed that both of these data types may have a
relationship in terms of cause (bridge maintenance manuals) and effect (tape test results)
regarding UWS bridge maintenance practices and performance. The objective and
subjective bridge maintenance manual ratings were summed together to create an overall
bridge maintenance manual rating for each agency in order to make it simpler to compare
with the tape test results. Table 5.1 provides a summary of the overall bridge maintenance
manual ratings for each agency that was considered along with the average percent area of
rust particles greater than or equal to an 1/8 inch from each corresponding cluster. Figure
5.1 shows a scatter plot of the overall bridge maintenance manual ratings versus the average
percent area of rust particles greater than or equal to an 1/8 inch for each agency/cluster.
124
Table 5.1 Summary of Overall Bridge Maintenance Manual Ratings and Average Percent
Area of Rust Particles Greater than or Equal to an 1/8 inch for Each Agency/Cluster
Figure 5.1 Scatter Plot of Overall Bridge Maintenance Manual Ratings Versus Average
Percent Area of Rust Particles Greater than or Equal to an 1/8 inch for Each
Agency/Cluster
It was assumed that as the overall bridge maintenance manual rating decreased, the
average percent area of rust particles greater than or equal to an 1/8 inch would increase
Agency/Cluster
Objective
Manual
Rating
Subjective
Manual
Rating
Overall
Manual
Rating
Average
Percent Area
of Rust Particles
≥ 1/8" (%)
Colorado 2 3 5 0.23
Connecticut 2 2 4 8.15
Iowa 2 3 5 3.41
Minnesota 2 2 4 11.07
New Hampshire 1 1 2 7.03
Ohio 2 3 5 8.17
R² = 0.1436
0.00
2.00
4.00
6.00
8.00
10.00
12.00
0 2 4 6
Av
erag
e P
erce
nt A
rea
of
Ru
st
Par
ticl
es ≥
1/8
" (%
)
Overall Manual Rating
125
because of the assumption that a higher percent area of rust particles greater than or equal
to an 1/8 inch coincided with poorer performance of the rust patina, which may be a result
of poor maintenance practices (e.g., lower overall bridge maintenance manual rating).
Although Figure 5.1 shows a decreasing linear trendline for the data, there is little to no
correlation between the average percent area of rust particles greater than or equal to an
1/8 inch and the overall bridge maintenance manual ratings based on the low R2 value of
0.1436. Therefore, while these results suggest that there may be no correlation between
these two data types, there may be a weak correlation that is obscured by the influence of
other variables, or more data points may be required to assess this correlation.
5.3 Correlations Between Bridge Washing Practices and Tape Test Results
Reported bridge washing practices from the maintenance survey and results from
the tape tests were compared to assess if these two data types may have a cause (bridge
washing practices) and effect (tape test results) relationship regarding UWS bridge
maintenance practices and performance. In order to compare bridge washing practices with
the tape test results, a rating system was developed to summarize and quantify bridge
washing practices of each agency. The responses to the bridge washing survey regarding
approximate percentage of UWS bridges washed, frequency of washing, and girder
washing practices were determined to be the most useful for rating and comparing the
overall bridge washing practices of each agency because they supply information about
how likely and how often the girders of UWS bridges are washed. Refer to section 4.2.2
for findings related to these bridge washing practices. In terms of approximate percentage
of UWS bridges washed, agencies that answered with >50% were given a rating of 3, 10 –
50% were given a rating of 2, <10% were given a rating of 1, and 0% were given a rating
of 0. In terms of frequency of washing, agencies that answered with more than once per
126
year were given a rating of 4, annually were given a rating of 3, every 2 years were given
a rating of 2, less frequently were given a rating of 1, and no indication of frequency of
washing were given a rating of 0. In terms of girder washing practices, agencies that
answered with always wash girders were given a rating of 3, at least half of the time were
given a rating of 2, less than half of the time were given a rating of 1, and never washing
the girders or no indication of washing the girders were given a rating of 0. Next, the rating
from each bridge washing practices category was summed in order to give each agency an
overall bridge washing practice rating. While it is not expected that there is necessarily a
linear relationship between this rating system and the effectiveness of bridge washing, this
provides a simple numerical scale for assessing possible influences of washing.
Table 5.2 shows bridge washing practice ratings given to each agency that was
considered along with the average percent area of rust particles greater than or equal to an
1/8 inch from each corresponding cluster’s tape test results. Figure 5.2 shows a scatter plot
of bridge washing practice ratings versus the average percent area of rust particles greater
than or equal to an 1/8 inch for each agency/cluster.
Table 5.2 Summary of Bridge Washing Practice Ratings and Average Percent Area of
Rust Particles Greater than or Equal to an 1/8 inch for Each Agency/Cluster
Agency/Cluster
Percentage
Washed
(%)
Frequency Wash GirdersWashing
Rating
Average
Percent Area
of Rust Particles
≥ 1/8" (%)
Colorado 0 — — 0 0.23
Connecticut 0 — — 0 8.15
Iowa <10 Less frequently Rarely (less than half of the time) 3 3.41
Minnesota >50 Annually Typically (at least half of the time) 8 11.07
New Hampshire 10-50 Every 2 years Rarely (less than half of the time) 5 7.03
Ohio 10-50 Annually No (never) 5 8.17
127
Figure 5.2 Scatter Plot of Bridge Washing Practice Ratings Versus Average Percent Area
of Rust Particles Greater than or Equal to an 1/8 inch for Each Agency/Cluster
It was assumed that as the bridge washing practice rating decreased, the average
percent area of rust particles greater than or equal to an 1/8 inch would increase because of
the assumption that a higher percent area of rust particles greater than or equal to an 1/8
inch coincided with poorer performance of the rust patina, which may be a result of poor
bridge washing practices (e.g., lower bridge washing practice rating). Figure 5.2 shows the
opposite of this assumption by the increasing linear trendline for the data. Furthermore,
there is a slight correlation between the area of rust particles and the bridge washing
practices’ ratings based on the low R2 value of 0.4634, however, as mentioned, it is
opposite to the trend one might expect. Overall, there may be no correlation between these
two data types, there may be a weak correlation that is obscured by the influence of other
variables, or more data points may be required to assess this correlation.
R² = 0.4634
0.00
2.00
4.00
6.00
8.00
10.00
12.00
0 2 4 6 8 10
Av
erag
e P
erce
nt A
rea o
f R
ust
P
art
icle
s ≥
1/8
" (%
)
Washing Rating
128
5.4 Correlations Between Bridge Washing Practices and IC Analysis Results
Reported bridge washing practices from the maintenance survey and results from the
IC analyses were compared to assess if these two data types may have a cause (bridge
washing practices) and effect (IC analysis results) relationship regarding UWS bridge
maintenance practices and ion concentrations on the rust patinas. Table 5.3 shows bridge
washing practice ratings (refer to Section 5.3 for an explanation of the bridge washing
practice rating system) given to each agency that was considered along with the average
concentrations of chloride, nitrate, and sulfate ions from each corresponding cluster’s IC
analyses. Figure 5.3, Figure 5.4, and Figure 5.5 show scatter plots of bridge washing
practice ratings versus the average chloride concentrations, nitrate concentrations, and
sulfate concentrations, respectively for each agency/cluster.
Table 5.3 Summary of Bridge Washing Practice Ratings and Average Chloride, Nitrate,
and Sulfate Concentrations for Each Agency/Cluster
Agency/Cluster
Percentage
Washed
(%)
Frequency Wash GirdersWashing
Rating
Average
Chloride
(ppm)
Average
Nitrate
(ppm)
Average
Sulfate
(ppm)
Colorado 0 — — 0 12009 1264 3545
Connecticut 0 — — 0 1816 377 952
Iowa <10 Less frequently Rarely (less than half of the time) 3 4825 273 1517
Minnesota >50 Annually Typically (at least half of the time) 8 6229 315 1569
New Hampshire 10-50 Every 2 years Rarely (less than half of the time) 5 1923 311 396
Ohio 10-50 Annually No (never) 5 3537 341 2630
129
Figure 5.3 Scatter Plot of Bridge Washing Practice Ratings Versus Average Chloride
Concentrations for Each Agency/Cluster
Figure 5.4 Scatter Plot of Average Bridge Washing Practice Ratings Versus Nitrate
Concentrations for Each Agency/Cluster
R² = 0.0593
0
2000
4000
6000
8000
10000
12000
14000
0 2 4 6 8 10
Av
erag
e C
hlo
ride
(ppm
)
Washing Rating
R² = 0.3302
0
200
400
600
800
1000
1200
1400
0 2 4 6 8 10
Aver
age
Nit
rate
(p
pm
)
Washing Rating
130
Figure 5.5 Scatter Plot of Bridge Washing Practice Ratings Versus Average Sulfate
Concentrations for Each Agency/Cluster
It was assumed that as the bridge washing practice rating increased, the average ion
concentration would decrease because of the assumption that better bridge washing
practices would result in lower amounts of ions present in the rust patina after being washed
away. Figure 5.3, Figure 5.4, and Figure 5.5 each agree with this assumption exhibited by
the decreasing linear trendlines. However, there is little to no correlation between the
average concentration of chloride, nitrate, and sulfate ions and the bridge washing practice
ratings based on the low R2 values of 0.0593, 0.3302, 0.0739; respectively. The MN agency
was assigned a significantly higher washing rating as compared to the other agencies. The
bridge washing practices rating system may be too heavily biased towards higher ratings.
Overall, there may be no correlation between these two data types, there may be a weak
correlation that is obscured by the influence of other variables, or more data points may be
required to assess this correlation.
R² = 0.0739
0
500
1000
1500
2000
2500
3000
3500
4000
0 2 4 6 8 10
Av
erag
e S
ulf
ate
(ppm
)
Washing Rating
131
5.5 Correlations Between Deicing Agent Usage and Tape Test Results
Reported deicing agent usage values from the deicing agent survey and results from
the tape tests were compared to assess if these two data types may have a cause (deicing
agent usage) and effect (tape test results) relationship regarding environmental conditions
of UWS bridges and performance. Table 5.4 shows a summary of the deicing agent usage
values in terms of corrosive solids per lane mile and corrosive brines per lane mile for each
agency that was considered along with the average percent area of rust particles greater
than or equal to an 1/8 inch from each corresponding cluster. Figure 5.6 and Figure 5.7
show scatter plots of the corrosive solids usages and corrosive brines usages, respectively
versus the average percent area of rust particles greater than or equal to an 1/8 inch for each
agency/cluster.
Table 5.4 Summary of Deicing Agent Usage and Average Percent Area of Rust Particles
Greater than or Equal to an 1/8 inch for Each Agency/Cluster
Agency/Cluster
Corrosive
Solids
(tons/lane
mile)
Corrosive
Brines
(gal./lane
mile)
Average
Percent Area
of Rust Particles
≥ 1/8" (%)
Colorado 7.53 498.73 0.23
Connecticut 20.37 141.13 8.15
Iowa 5.71 1,167.35 3.41
Minnesota 8.10 151.19 11.07
New Hampshire 24.69 41.21 7.03
Ohio 17.44 247.59 8.17
132
Figure 5.6 Scatter Plot of Corrosive Solids’ Usages Versus Average Percent Area of Rust
Particles Greater than or Equal to an 1/8 inch for Each Agency/Cluster
Figure 5.7 Scatter Plot of Corrosive Brines’ Usages Versus Average Percent Area of Rust
Particles Greater than or Equal to an 1/8 inch for Each Agency/Cluster
It was assumed that as both of the corrosive solids and corrosive brines usages
increased, the average percent area of rust particles greater than or equal to an 1/8 inch
R² = 0.1592
0.00
2.00
4.00
6.00
8.00
10.00
12.00
0.00 5.00 10.00 15.00 20.00 25.00 30.00
Av
erag
e P
erce
nt A
rea
of
Rust
P
arti
cles
≥ 1
/8"
(%)
Corrosive Solids (tons/lane mile)
R² = 0.3829
0.00
2.00
4.00
6.00
8.00
10.00
12.00
0.00 200.00 400.00 600.00 800.00 1,000.00 1,200.00 1,400.00
Av
era
ge P
erc
en
t A
rea o
f R
ust
P
art
icle
s ≥
1/8
" (%
)
Corrosive Brines (gal./lane mile)
133
would also increase because of the assumption that a higher percent area of rust particles
greater than or equal to an 1/8 inch coincided with poorer performance of the rust patina,
which may be a result of greater deicing agent usages. Figure 5.6 shows an increasing linear
trendline for the data, which matches these assumptions; however, the correlation was low
(R2 value of 0.1592). Figure 5.7 shows a decreasing linear trendline for the data, which is
the opposite of the previously mentioned assumptions. Furthermore, there is little
correlation between the average percent area of rust particles greater than or equal to an
1/8 inch and the corrosive brines’ usages based on the low R2 value of 0.3829. It should be
noted that the IA agency had significantly higher corrosive brines usage rates. Overall,
there may be no correlations between deicing agent usages and tape test results based on
inconsistencies between assumptions and results when considering the corrosive brines
usage rates and tape test results, an insignificant R2 value when considering corrosive solids
usage rates and tape test results, a weak correlation that is obscured by the influence of
other variables, or more data may be required to assess these correlations.
5.6 Correlations Between Deicing Agent Usage and IC Analysis Results
Reported deicing agent usage values from the deicing agent survey and average
chloride concentration results from the IC analyses (only the chloride concentrations were
considered because this is the only ion from the IC analyses that is also contained in deicing
agents) were compared to assess if these two data types may have a cause (deicing agent
usage) and effect (chloride concentrations) relationship regarding environmental
conditions of UWS bridges and chloride concentrations of the rust patinas. Table 5.5 shows
a summary of the deicing agent usage values in terms of corrosive solids per lane mile and
corrosive brines per lane mile for each agency that was considered along with the average
chloride concentrations from each corresponding cluster. Figure 5.8 and Figure 5.9 shows
134
a scatter plot of the corrosive solids’ usages and corrosive brines’ usages, respectively
versus the average chloride concentrations for each agency/cluster.
Table 5.5 Summary of Deicing Agent Usage and Average Chloride Concentrations for
Each Agency/Cluster
Figure 5.8 Scatter Plot of Corrosive Solids’ Usages Versus Average Chloride
Concentrations for Each Agency/Cluster
Agency/Cluster
Corrosive
Solids
(tons/lane
mile)
Corrosive
Brines
(gal./lane
mile)
Average
Chloride
(ppm)
Colorado 7.53 498.73 12009
Connecticut 20.37 141.13 1816
Iowa 5.71 1,167.35 4825
Minnesota 8.10 151.19 6229
New Hampshire 24.69 41.21 1923
Ohio 17.44 247.59 3537
R² = 0.5292
0
2000
4000
6000
8000
10000
12000
14000
0.00 5.00 10.00 15.00 20.00 25.00 30.00
Av
erag
e C
hlo
ride
(ppm
)
Corrosive Solids (tons/lane mile)
135
Figure 5.9 Scatter Plot of Corrosive Brines’ Usages Versus Average Chloride
Concentrations for Each Agency/Cluster
It was assumed that as both of the corrosive solids and corrosive brines usages
increased, the average chloride concentration would also increase because of the
assumption that a higher concentration of chloride ions coincided with greater deicing
agent usages. Figure 5.8 shows a decreasing linear trendline for the data, which is opposite
of these assumptions. There is a slight correlation between the average chloride
concentrations and the corrosive solids’ usages based on the R2 value of 0.5292. Figure 5.9
shows an increasing linear trendline for the data, which matches the previously mentioned
assumptions; however, there is little to no correlation between the average chloride
concentrations and the corrosive brines’ usages based on the low R2 value of 0.0918. It
should be noted that the IA agency had significantly higher corrosive brines usage rates
than the other agencies. Furthermore, the CO cluster had significantly higher average
chloride concentrations than the other clusters. Overall, there may be no correlations
between deicing agent usages and chloride concentrations based on inconsistencies
R² = 0.0918
0
2000
4000
6000
8000
10000
12000
14000
0.00 200.00 400.00 600.00 800.00 1,000.00 1,200.00 1,400.00
Av
erag
e C
hlo
ride
(ppm
)
Corrosive Brines (gal./lane mile)
136
between assumptions and results in terms of corrosive solids usage rates and average
chloride concentrations, an insignificant R2 value in terms of corrosive brines usage rates
and average chloride concentrations, a weak correlation that is obscured by the influence
of other variables, or more data may be required to assess these correlations.
5.7 Correlations Between IC Analysis Results and Tape Test Results
The IC analysis and tape test results were compared to assess data correlations
relevant to UWS bridge performance. It was assumed that higher concentrations of ions
would coincide with poorer performance of rust patinas based on prior knowledge
regarding the effects that chloride, nitrate, and sulfate ions have on patina performance.
Chloride ions typically originate from deicing agents and salt spray from the ocean, nitrate
ions typically come from rainwater that originated from organic matter found in soil, and
sulfate ions typically come from air pollutants. From past research discussed in Chapter 2,
chloride has been found to be the most problematic ion affecting rust patina performance
of UWS, sulfate typically negatively impacts UWS performance within the initial stages
of patina formation, and nitrate was found to have minor effects on UWS performance.
Similarly, tape test results with higher average percent area of rust particles greater
than or equal to an 1/8 inch were also assumed to coincide with poorer performance of the
rust patina. Therefore, each cluster’s IC analysis results were compared with each cluster’s
tape test results to evaluate trends of UWS bridge performance between clusters.
Furthermore, each field bridge’s IC analysis results were compared with each field bridge’s
tape test results to evaluate any trends in UWS performance between individual bridges.
The IC analysis results and tape test results were also compared for each standard sample
area location to evaluate any trends in UWS performance between different locations of
rust patinas on girders. It should be noted that only available data between both the IC
137
analyses and tape tests were compared. Refer to Section 4.4.2 for IC analysis data that was
not available to be included in the data set and, therefore was not compared with the tape
test data.
5.7.1 Correlations Between Cluster IC Analysis Results and Tape Test Results
The average concentrations of chloride, nitrate, and sulfate ions from each cluster’s
IC analysis results were compared with the average percent area of rust particles greater
than or equal to an 1/8 inch from each cluster’s tape test results to assess if there was a
cause (ion concentrations) and effect (tape test results) relationship regarding UWS bridge
performance between clusters. Table 5.6 shows a summary of the average chloride, nitrate,
and sulfate concentrations along with the average percent area of rust particles greater than
or equal to an 1/8 inch of each cluster. Figure 5.10, Figure 5.11, and Figure 5.12 show
scatter plots of the average chloride concentrations, nitrate concentrations, and sulfate
concentrations, respectively versus the average percent area of rust particles greater than
or equal to an 1/8 inch for each cluster.
138
Table 5.6 Summary of Average Chloride, Nitrate, and Sulfate Concentrations and
Average Percent Area of Rust Particles Greater than or Equal to an 1/8 inch of Each
Cluster
Figure 5.10 Scatter Plot of Average Chloride Concentration Versus Average Percent Area
of Rust Particles Greater than or Equal to an 1/8 inch of Each Cluster
Cluster
Average
Chloride
(ppm)
Average
Nitrate
(ppm)
Average
Sulphate
(ppm)
Average
Percent Area
of Rust Particles
≥ 1/8" (%)
CO 12009 1264 3545 0.30
CT 1816 377 952 7.81
IA 4825 273 1517 3.54
MN 6229 315 1569 11.16
NC 583 361 2745 6.64
NH 1923 311 396 1.97
OH 3537 341 2630 8.17
R² = 0.1448
0.00
2.00
4.00
6.00
8.00
10.00
12.00
0 2000 4000 6000 8000 10000 12000 14000
Av
erag
e P
erce
nt A
rea
of
Ru
st
Par
ticl
es ≥
1/8
" (%
)
Average Chloride (ppm)
139
Figure 5.11 Scatter Plot of Average Nitrate Concentration Versus Average Percent Area
of Rust Particles Greater than or Equal to an 1/8 inch of Each Cluster
Figure 5.12 Scatter Plot of Average Sulfate Concentration Versus Average Percent Area
of Rust Particles Greater than or Equal to an 1/8 inch of Each Cluster
R² = 0.3333
0.00
2.00
4.00
6.00
8.00
10.00
12.00
0 200 400 600 800 1000 1200 1400
Av
erag
e P
erce
nt A
rea
of
Ru
st
Par
ticl
es ≥
1/8
" (%
)
Average Nitrate (ppm)
R² = 0.0203
0.00
2.00
4.00
6.00
8.00
10.00
12.00
0 1000 2000 3000 4000
Av
erag
e P
erce
nt A
rea
of
Rust
P
arti
cles
≥ 1
/8"
(%)
Average Sulfate (ppm)
140
It was assumed that higher concentrations of ions would coincide with higher
average percent area of rust particles greater than or equal to an 1/8 inch and may indicate
poorer performance of rust patinas. However, Figure 5.10, Figure 5.11, and Figure 5.12
each show decreasing linear trendlines, which is opposite of this assumption. There is also
little to no correlation between the average percent area of rust and average concentrations
of ions based on the low R2 values of 0.1448, 0.3333, and 0.0203; respectively. It should
be noted that the CO cluster had significantly higher average ion concentrations than the
other clusters. Overall, there may be no correlations between tape test results and IC
analysis results in terms of cluster bridges, there may be a weak correlation that is obscured
by the influence of other variables, or more data may be required to assess these
correlations.
5.7.2 Correlations Between Field Bridge IC Analysis Results and Tape Test
Results
The average concentrations of chloride, nitrate, and sulfate ions from each field
bridge’s IC analysis results were compared with the average percent area of rust particles
greater than or equal to an 1/8 inch from each field bridge’s tape test results to assess if
there was a cause (ion concentrations) and effect (tape test results) relationship regarding
UWS bridge performance between field bridges. Table 5.7 shows a summary of the average
chloride, nitrate, and sulfate concentrations along with the average percent area of rust
particles greater than or equal to an 1/8 inch of each field bridge. Figure 5.13, Figure 5.14,
and Figure 5.15 show scatter plots of the average chloride concentrations, nitrate
concentrations, and sulfate concentrations, respectively versus the average percent area of
rust particles greater than or equal to an 1/8 inch for each field bridge.
141
Table 5.7 Summary of Average Chloride, Nitrate, and Sulfate Concentrations and
Average Percent Area of Rust Particles Greater than or Equal to an 1/8 inch of Each Field
Bridge
Field BridgeAverage Chloride
(ppm)
Average
Nitrate
(ppm)
Average
Sulfate
(ppm)
Average
Percent Area
of Rust Particles
≥ 1/8" (%)
CO E-16-JX 13437 1582 5094 0.01
CO E-16-JZ 10438 913 1841 0.63
CT 3830 1668 393 1253 6.29
CT 4382 2658 406 809 12.15
CT 5796 1052 329 776 4.71
IA 004111 4300 154 781 3.07
IA 041331 5409 346 1843 5.98
IA 042711 4813 330 1994 1.61
MN 04019 4650 220 1634 1.95
MN 19811 4425 456 2192 13.93
MN 62861 9216 246 898 15.28
NC 190083 601 405 4396 1.72
NC 1290057 563 312 944 11.15
NH 017201120011300 1923 311 396 1.97
OH 7700105 93 8 44 5.59
OH 7701977 97 9 77 11.56
OH 7701993 115 10 101 7.36
142
Figure 5.13 Scatter Plot of Average Chloride Concentration Versus Average Percent Area
of Rust Particles Greater than or Equal to an 1/8 inch of Each Field Bridge
Figure 5.14 Scatter Plot of Average Nitrate Concentration Versus Average Percent Area
of Rust Particles Greater than or Equal to an 1/8 inch of Each Field Bridge
R² = 0.0521
0.00
2.00
4.00
6.00
8.00
10.00
12.00
14.00
16.00
18.00
0 5000 10000 15000
Av
erag
e P
erce
nt A
rea
of
Rust
P
arti
cles
≥ 1
/8"
(%)
Average Chloride (ppm)
R² = 0.1507
0.00
2.00
4.00
6.00
8.00
10.00
12.00
14.00
16.00
18.00
0 500 1000 1500 2000
Av
erag
e P
erce
nt A
rea
of
Rust
P
arti
cles
≥ 1
/8"
(%)
Average Nitrate (ppm)
143
Figure 5.15 Scatter Plot of Average Sulfate Concentration Versus Average Percent Area
of Rust Particles Greater than or Equal to an 1/8 inch of Each Field Bridge
Figure 5.13, Figure 5.14, and Figure 5.15 each have decreasing linear trendlines
which portray opposite results of what was assumed in terms of correlations between the
average ion concentrations and average percent area of rust particles greater than or equal
to an 1/8 inch. It was assumed that higher concentrations of ions would coincide with higher
percent areas of rust particles and may indicate poorer performance of rust patinas. Figure
5.13, Figure 5.14, and Figure 5.15 also show little to no correlation in the data based on the
low R2 values of 0.0483, 0.0642, and 0.0001; respectively. It should be noted that bridges
CO E-16-JX and CO E-16-JZ had significantly higher average ion concentrations than the
other field bridges. Overall, there may be no correlations between tape test results and IC
analysis results in terms of individual field bridges, there may be a weak correlation that is
obscured by the influence of other variables, or more data may be required to assess these
correlations.
R² = 0.1807
0.00
2.00
4.00
6.00
8.00
10.00
12.00
14.00
16.00
18.00
0 1000 2000 3000 4000 5000 6000
Aver
age
Per
cen
t A
rea
of
Ru
st
Par
ticl
es ≥
1/8
" (%
)
Average Sulfate (ppm)
144
5.7.3 Correlations Between Sample Location IC Analysis Results and Tape Test
Results
The average concentrations of chloride, nitrate, and sulfate ions and the average
percent area of rust particles greater than or equal to an 1/8 inch were compared for each
standard sample area to assess if there was a cause (ion concentrations) and effect (tape test
results) relationship regarding UWS bridge performance between different locations of rust
patinas on girders. Table 5.8 shows a summary of the average chloride, nitrate, and sulfate
concentrations along with the average percent area of rust particles greater than or equal to
an 1/8 inch of each standard sample area location. Figure 5.16, Figure 5.17, and Figure
5.18 show scatter plots of the average chloride concentrations, nitrate concentrations, and
sulfate concentrations, respectively versus the average percent area of rust particles greater
than or equal to an 1/8 inch for each standard sample area location.
145
Table 5.8 Summary of Average Chloride, Nitrate, and Sulfate Concentrations and
Average Percent Area of Rust Particles Greater than or Equal to an 1/8 inch of Each
Standard Sample Area Location
Standard
Sample
Area
Location
Average
Chloride
(ppm)
Average
Nitrate
(ppm)
Average
Sulfate
(ppm)
Average
Percent Area
of Rust Particles
≥ 1/8" (%)
1 4755 381 2148 10.88
2 2287 276 1231 8.45
3 4364 399 2749 12.50
4 2363 354 1283 2.85
5 1473 270 646 2.47
6 4768 347 2931 6.93
7 5356 380 2103 11.08
8 2906 243 1686 5.67
9 4879 413 2406 11.54
10 2390 266 964 2.22
11 1410 221 452 2.14
12 4847 401 2265 7.98
146
Figure 5.16 Scatter Plot of Average Chloride Concentration Versus Average Percent Area
of Rust Particles Greater than or Equal to an 1/8 inch of Each Standard Sample Area
Location
Figure 5.17 Scatter Plot of Average Nitrate Concentration Versus Average Percent Area
of Rust Particles Greater than or Equal to an 1/8 inch of Each Standard Sample Area
Location
R² = 0.6871
0.00
2.00
4.00
6.00
8.00
10.00
12.00
14.00
0 1000 2000 3000 4000 5000 6000
Av
erag
e P
erce
nt A
rea
of
Ru
st
Par
ticl
es ≥
1/8
" (%
)
Average Chloride (ppm)
R² = 0.5731
0.00
2.00
4.00
6.00
8.00
10.00
12.00
14.00
0 100 200 300 400 500
Av
erag
e P
erce
nt A
rea
of
Rust
P
arti
cles
≥ 1
/8"
(%)
Average Nitrate (ppm)
147
Figure 5.18 Scatter Plot of Average Sulfate Concentration Versus Average Percent Area
of Rust Particles Greater than or Equal to an 1/8 inch of Each Standard Sample Area
Location
The R2 values of 0.6871, 0.5731, and 0.6285 of Figure 5.16, Figure 5.17, and Figure
5.18; respectively each showcase relatively strong correlations between average ion
concentrations and average percent area of rust particles greater than or equal to an 1/8 inch
in terms of standard sample area location as compared to the other data correlations that
were assessed in this chapter. The increasing trendlines shown in each scatter plot also
agree with the assumption that higher concentrations of ions coincide with higher percent
areas of rust particles greater than or equal to an 1/8 inch and may indicate poorer
performance of rust patinas. More data related to average percent areas of rust particles and
average ion concentrations of ions should be assessed to draw conclusions regarding UWS
performance in terms of standard sample area location.
R² = 0.6285
0.00
2.00
4.00
6.00
8.00
10.00
12.00
14.00
0 1000 2000 3000 4000
Aver
age
Per
cen
t A
rea
of
Ru
st
Par
ticl
es ≥
1/8
" (%
)
Average Sulfate (ppm)
148
5.8 Correlations Between Tape Test Results and Condition Ratings of Field
Bridges
Correlations between the average percent area of rust particles greater than or equal
to an 1/8 inch and reported condition ratings (SCR from the NBI database and CS of girders
from inspection reports) of each field bridge were assessed. It was assumed that assessing
data trends between UWS bridge condition ratings and tape test results would validate
whether or not there was agreement between these methods used for evaluating UWS
bridge performance. The CS rating of the girders for each field bridge was normalized by
using a weighted girder condition state (WGCS) rating based on the formula WGCS =
CS1/100*1 + CS2/100*2 + CS3/100*3 + CS4/100*4. A WGCS rating of 1.00
corresponded with the best rating while a WGCS rating of 4.00 corresponded with the
worst rating. Table 5.9 shows a summary of the SCR, WGCS ratings, and average percent
area of rust particles greater than or equal to an 1/8 inch for each field bridge that was
evaluated. Figure 5.19 shows a scatter plot of the SCR versus the average percent area of
rust particles greater than or equal to an 1/8 inch for each field bridge.
149
Table 5.9 Summary of Average Percent Area of Rust Particles Greater than or Equal to
an 1/8 inch, SCR, and Weighted Girder CS Ratings for Each Field Bridge
Field Bridge SCRWGCS
Rating
Average
Percent Area
of Rust Particles
≥ 1/8" (%)
CO E-16-JW 8 1.32 0.13
CO E-16-JX 8 1.04 0.01
CO E-16-JZ 7 1.00 0.56
CT 3830 6 1.12 6.82
CT 4382 6 2.01 12.23
CT 5796 7 1.00 5.40
IA 004111 8 1.00 3.07
IA 041331 7 1.00 5.52
IA 042711 8 1.00 1.63
MN 04019 5 1.08 2.58
MN 19811 7 1.28 13.93
MN 62861 6 1.50 15.28
NC 190083 5 1.00 1.75
NC 1290057 8 1.00 11.15
NC 1290058 8 1.00 17.40
NH 017201120011300 6 1.05 1.97
NH 11101120017900 8 2.00 5.58
NH 017701460003700 8 1.00 13.56
OH 7700105 6 1.00 5.59
OH 7701977 8 1.00 11.56
OH 7701993 8 1.00 7.36
150
Figure 5.19 Scatter Plot of SCR Versus Average Percent Area of Rust Particles Greater
than or Equal to an 1/8 inch of Each Field Bridge
It was assumed that as the SCR decreased, the average percent area of rust particles
greater than or equal to an 1/8 inch would increase because of the assumption that a higher
average percent area of rust particles greater than or equal to an 1/8 inch coincided with
poorer UWS performance. Figure 5.19 shows the opposite of this assumption with an
increasing linear trendline; however, there is little to no correlation between the tape test
results and SCR when looking at the very low R2 value of 0.0145. The reason for little to
no correlation between the tape test results and reported SCR may be due to the fact that
the SCR is a rating of the entire bridge’s superstructure, whereas the tape test evaluates
performance of the girders’ rust patina at specific locations. So, a lower SCR rating due to
joint or bearing issues may not be representative of UWS performance. These
inconsistencies may be why there do not appear to be correlations between the tape test
results and SCR. Another reason for little to no correlation between the tape test results
and reported SCR may be due to the subjective nature of inspecting and rating bridges.
R² = 0.0145
0.00
2.00
4.00
6.00
8.00
10.00
12.00
14.00
16.00
18.00
20.00
0 2 4 6 8 10
Av
erag
e P
erce
nt A
rea
of
Rust
P
arti
cles
≥ 1
/8"
(%)
SCR
151
Different bridge inspectors may have different perspectives regarding the conditions of
bridges. The processes and criteria for inspecting bridges may also vary between states.
To attempt to eliminate ambiguity of the reported SCR of each field bridge while
assessing correlations between reported UWS bridge performance and the tape test results,
the WGCS ratings from inspection reports were used. When looking at Figure 5.20, which
shows a scatter plot of SCR versus the WGCS rating of each field bridge it can be seen that
there is little to no correlation between the SCR and WGCS ratings based on the
significantly low R2 value of 0.0092. Therefore, using the WGCS rating to assess
correlations between UWS bridge condition ratings and tape test results may provide better
agreements between these two methods used for evaluating UWS bridge performance.
Figure 5.21 shows a scatter plot of the WGCS rating versus the average percent area of rust
particles greater than or equal to an 1/8 inch of each field bridge.
Figure 5.20 Scatter Plot of SCR Versus WGCS Rating of Each Field Bridge
R² = 0.0092
1.00
1.50
2.00
2.50
3.00
3.50
4.00
0 2 4 6 8
WG
CS
Rat
ing
SCR
152
Figure 5.21 Scatter Plot of WGCS Rating Versus Average Percent Area of Rust Particles
Greater than or Equal to an 1/8 inch of Each Field Bridge
It was assumed that as the WGCS rating decreased, the average percent area of rust
particles greater than or equal to an 1/8 inch would also decrease because of the assumption
that a lower average percent area of rust particles greater than or equal to an 1/8 inch
coincided with better UWS performance. Figure 5.21 shows an agreement with this
assumption based on the decreasing linear trendline; however, there is little to no
correlation between the tape test results and WGCS rating when looking at the low R2 value
of 0.049. The reason for little to no correlation between the tape test results and WGCS
ratings may also be due to the subjective nature of inspecting and rating bridges as
mentioned previously. Furthermore, the girder CS rating is a rating of the entire length of
all the girders for a bridge, whereas the tape test results were obtained from 12 small areas
on just two girders. So, a higher WGCS rating due to corrosion issues at some locations on
the girders may not be representative of UWS performance indicated by tape test results
from samples taken at other locations along the girders. These inconsistencies may be why
R² = 0.049
0.00
2.00
4.00
6.00
8.00
10.00
12.00
14.00
16.00
18.00
20.00
1.002.003.004.00
Av
erag
e P
erce
nt A
rea
of
Rust
P
arti
cles
≥ 1
/8"
(%)
WGCS Rating
153
correlations between the tape test results and WGCS ratings did not showcase a strong
agreement. Lastly, most of the bridges had a WGCS of 1.00 (a somewhat default rating)
and these bridges exhibited a wide range of average percent area of rust particles greater
than or equal to an 1/8 inch; if these bridges are removed from the dataset, the R2 value in
Figure # increases to 0.2158.
5.9 Summary of Correlations
When looking at all preliminary correlations that were evaluated in Chapter 5, the
weakest correlations were the bridge maintenance manual ratings versus tape test results
(R2 value of 0.1436), bridge washing practices versus IC analysis results (R2 values of
0.0593, 0.3302, and 0.0739 for chloride, nitrate, and sulfate, respectively), deicing agent
usage rates versus tape test results (R2 values of 0.1592 and 0.3829 for corrosive solids and
corrosive brines, respectively), corrosive brines’ usage rates versus average chloride
concentrations (R2 value of 0.0918), tape test results versus IC analysis results in terms of
cluster (R2 values of 0.1448, 0.3333, and 0.0203 for chloride, nitrate, and sulfate,
respectively), as well as individual field bridges (R2 values of 0.0521, 0.1507, and 0.1807
for chloride, nitrate, and sulfate respectively), and tape test results versus bridge condition
ratings (R2 values of 0.0145 and 0.049 for SCR and WGCS rating, respectively). For each
of these preliminary correlations there may be no correlations; however, there may be a
weak correlation that is obscured by the influence of other variables or more data may be
required to assess each of them.
The strongest preliminary correlation that was evaluated was between the tape test
results and IC analysis results in terms of standard sample area location (R2 values of
0.6871, 0.5731, and 0.6285 for chloride, nitrate, and sulfate, respectively). This correlation
matched assumptions regarding higher concentrations of ions coinciding with higher
154
percent areas of rust particles greater than or equal to an 1/8 inch and may indicate poorer
performance of rust patinas. One reason as to why this correlation was stronger than
correlations between tape test results and IC analysis results in terms of clusters or
individual field bridges may be due to the CO bridges. These bridges had significantly
higher average ion concentrations. Furthermore, the CO bridges’ data were not included in
the average tape test and IC analysis results for the standard sample area locations because
of the different standard sample area locations used for these bridges (refer to Table 4.2).
Data from Phase 2 tape test results and IC analysis results should be included with Phase
3 data and assessed to further evaluate UWS performance in terms of standard sample area
location due to this being the strongest preliminary correlation that was assessed.
Table 5.10 shows a summary of the average chloride, nitrate, and sulfate
concentrations along with the average percent area of rust particles greater than or equal to
an 1/8 inch sorted from highest to lowest of each standard sample area location. Figure
5.22, Figure 5.23, and Figure 5.24 show scatter plots of the average chloride
concentrations, nitrate concentrations, and sulfate concentrations, respectively versus the
average percent area of rust particles greater than or equal to an 1/8 inch for each standard
sample area location, which are listed next to each data point. Looking at the data in this
way will make it easier to evaluate the performance of standard sample area locations based
on the tape test results and their corresponding relations to the IC analysis results.
155
Table 5.10 Summary of Average Chloride, Nitrate, and Sulfate Concentrations and
Average Percent Area of Rust Particles Greater than or Equal to an 1/8 inch Sorted from
Highest to Lowest of Each Standard Sample Area Location
Figure 5.22 Scatter Plot of Each Standard Sample Area Location Listed for Each
Corresponding Average Chloride Concentration Versus Average Percent Area of Rust
Particles Greater than or Equal to an 1/8 inch
Standard
Sample
Area
Location
Average
Chloride
(ppm)
Average
Nitrate
(ppm)
Average
Sulfate
(ppm)
Average
Percent Area
of Rust Particles
≥ 1/8" (%)
3 4364 399 2749 12.50
9 4879 413 2406 11.54
7 5356 380 2103 11.08
1 4755 381 2148 10.88
2 2287 276 1231 8.45
12 4847 401 2265 7.98
6 4768 347 2931 6.93
8 2906 243 1686 5.67
4 2363 354 1283 2.85
5 1473 270 646 2.47
10 2390 266 964 2.22
11 1410 221 452 2.14
1
2
3
45
6
7
8
9
1011
12
0.00
2.00
4.00
6.00
8.00
10.00
12.00
14.00
0 1000 2000 3000 4000 5000 6000
Av
erag
e P
erce
nt A
rea
of
Ru
st
Par
ticl
es ≥
1/8
" (%
)
Average Chloride (ppm)
156
Figure 5.23 Scatter Plot of Each Standard Sample Area Location Listed for Each
Corresponding Average Nitrate Concentration Versus Average Percent Area of Rust
Particles Greater than or Equal to an 1/8 inch
Figure 5.24 Scatter Plot of Each Standard Sample Area Location Listed for Each
Corresponding Average Sulfate Concentration Versus Average Percent Area of Rust
Particles Greater than or Equal to an 1/8 inch
12
3
45
6
7
8
9
1011
12
0.00
2.00
4.00
6.00
8.00
10.00
12.00
14.00
0 100 200 300 400 500
Aver
age
Per
cen
t A
rea
of
Ru
st
Par
ticl
es ≥
1/8
" (%
)
Average Nitrate (ppm)
12
3
45
6
7
8
9
1011
12
0.00
2.00
4.00
6.00
8.00
10.00
12.00
14.00
0 1000 2000 3000 4000
Av
erag
e P
erce
nt A
rea
of
Rust
P
arti
cles
≥ 1
/8"
(%)
Average Chloride (ppm)
157
Other notably strong correlations include bridge washing practices versus tape test
results (R2 value of 0.4634), and corrosive solids’ usage rates versus average concentrations
of chloride (R2 value of 0.5292). Although each of these correlations were relatively strong
in comparison to the other preliminary correlations, both of these scatter plots showed data
trends that were opposite of what was assumed. Overall, there may be no correlations
between these data types, there may be a weak correlation that is obscured by the influence
of other variables, or more data may be required to assess each of them.
158
Chapter 6
CONCLUSIONS
6.1 Summary
Field evaluations of 21 UWS bridges were performed in Phase 3 of this work, which
was the focus of this thesis, in order to obtain additional data relevant to data collected
from field evaluations of 13 UWS bridges conducted in Phase 2 of this research project.
The field evaluations carried out in Phase 3 also provided opportunities to update and refine
LTBPP UWS bridge field evaluation protocols developed in Phase 1 of this research
project. The main data types that were collected from field evaluations and that were
discussed in this thesis include tape test data and IC analysis data of rust samples.
Qualitative condition assessments of each UWS field bridge from Phase 3 were also
performed. Furthermore, work carried out in Phase 3 included conducting a survey
regarding maintenance practices (including a review of bridge maintenance manuals and
bridge washing practices) of UWS bridges and deicing agent usage for each agency in the
U.S.
6.2 Overview of Results
The results from the field evaluations (tape tests and IC analyses), survey (UWS
bridge maintenance practices and deicing agent usages), and UWS bridge condition ratings
(qualitative condition rating, SCR, and weighted girder CS rating) were compared to
identify any preliminary correlations between possible cause and effect relationships as
well as to assess whether or not there was agreement between methods used for evaluating
UWS bridge performance. It was assumed that more extensive bridge maintenance
159
practices and lower deicing agent usage rates (causes) would result in better UWS bridge
condition ratings, a lower average percent area of rust particles greater than or equal to an
1/8 inch from tape test results, and lower average ion concentrations from IC analysis
results. It was intended that evaluating these assumed correlations would further quantify
and understand the performance of UWS bridges in a variety of circumstances and
conditions. Table 6.1, Table 6.2, and Table 6.3 provide summaries of the data correlations
that were presented in Chapter 5 in terms of whether the correlation was positive or
negative, the strength of the correlation indicated by the R2 value, and the corresponding
scatter plot (Figure) of the correlation.
Table 6.1 Summary of Chapter 5 Cause and Effect Correlations
Chloride Nitrate Sulfate
Negative
R2 = 0.1436
Figure 5.1
Positive
R2 = 0.4634
Figure 5.2
Negative
R2 = 0.0593
Figure 5.3
Negative
R2 = 0.3302
Figure 5.4
Negative
R2 = 0.0739
Figure 5.5
Corrosive
Solids
Positive
R2 = 0.1592
Figure 5.6
Negative
R2 = 0.5292
Figure 5.8
Corrosive
Brines
Negative
R2 = 0.3829
Figure 5.7
Positive
R2 = 0.0918
Figure 5.9
Deicing Agent
Usage
IC Analysis ResultsTape Test
Results
Manual Rating
Washing Rating
160
Table 6.2 Summary of Chapter 5 IC Analysis and Tape Test Correlations
ClusterField
Bridge
Standard
Sample Area
Location
Cluster
Negative
R2 = 0.1448
Figure 5.10
Field Bridge
Negative
R2 = 0.0521
Figure 5.13
Standard
Sample Area
Location
Positive
R2 = 0.6871
Figure 5.16
Cluster
Negative
R2 = 0.3333
Figure 5.11
Field Bridge
Negative
R2 = 0.1507
Figure 5.14
Standard
Sample Area
Location
Positive
R2 = 0.5731
Figure 5.17
Cluster
Negative
R2 = 0.0203
Figure 5.12
Field Bridge
Negative
R2 = 0.1807
Figure 5.15
Standard
Sample Area
Location
Positive
R2 = 0.6285
Figure 5.18
Tape Test Results
IC
Analysis
Results
Chloride
Nitrate
Sulfate
161
Table 6.3 Summary of Chapter 5 Methods to Assess UWS Performance Correlations
Table 6.4 provides a summary of each cluster that was evaluated in Phase 3 along
with the cluster’s classification, maintenance and deicing agent usage practices (where
higher numbers in the “maintenance manual rating” and “washing practices rating”
columns indicate better practices; see Section 5.2 and Section 5.3, respectively), as well as
each field bridge that was evaluated in Phase 3 along with measures of performance
(qualitative condition, SCR, WGCS rating, and average percent area of rust particles
greater than or equal to an 1/8 inch from tape test results) and environmental conditions
(average chloride, nitrate and sulfate concentrations from IC analysis results). There was
no reported IC analysis data for bridges CO E-16-JZ, NC 1290058, NH 11101120017900,
and NH 017701460003700 as samples from these bridges were not yet processed at the
time of this writing due to the COVID-19 pandemic causing the University of Delaware’s
labs to be shut down during the semester in which this thesis was completed. There was
also no data obtained from the survey for the NC cluster in terms of bridge maintenance
manuals, bridge washing practices, and deicing agent usages.
SCR WGCS
Tape
Test
Results
Positive
R2 = 0.0145
Figure 5.19
Negative
R2 = 0.049
Figure 5.21
162
Table 6.4 Summary of Cluster and Field Bridge Data Types
ClusterCluster
Classification
Maintenance
Manual
Rating
Washing
Practices
Rating
Corrosive
Solids
(tons/lane
mile)
Corrosive
Brines
(gal./lane
mile)
Field Bridge1 Qualitative
ConditionSCR
WGCS
Rating
Average
Percent Area
of Rust Particles
≥ 1/8" (%)
Average
Chloride
(ppm)
Average
Nitrate
(ppm)
Average
Sulfate
(ppm)
CO E-16-JW good 8 1.32 0.13 13437 1582 5094
CO E-16-JX good 8 1.04 0.01 10438 913 1841
CO E-16-JZ good 7 1.00 0.56 — — —
CT 3830 good 6 1.12 6.82 1668 393 1253
CT 4382 good 6 2.01 12.23 2658 406 809
CT 5796 good 7 1.00 5.40 1052 329 776
IA 004111 poor 8 1.00 3.07 4300 154 781
IA 041331 poor 7 1.00 5.52 5409 346 1843
IA 042711 poor 8 1.00 1.63 4813 330 1994
MN 04019 poor 5 1.08 2.58 4650 220 1634
MN 19811 poor 7 1.28 13.93 4425 456 2192
MN 62861 poor 6 1.50 15.28 9216 246 898
good coastal — — — — NC 190083 good 5 1.00 1.75 601 405 4396
— — — — NC 1290057 good 8 1.00 11.15 563 312 944
— — — — NC 1290058 good 8 1.00 17.40 — — —
NH 017201120011300 good 6 1.05 1.97 1923 311 396
NH 11101120017900 poor 8 2.00 5.58 — — —
NH 017701460003700 poor 8 1.00 13.56 — — —
OH 7700105 poor 6 1.00 5.59 93 8 44
OH 7701977 poor 8 1.00 11.56 97 9 77
OH 7701993 poor 8 1.00 7.36 115 10 101
1 - Green highlighted bridges denote Reference bridges
247.59
inferior coastal
498.73
141.13
1167.35
151.19
41.21
5
0
0
2
7
4
4
5
4
17.44
7.53
20.37
5.71
8.10
24.69
CO
CT
IA
MN
NC
good
deicing
inferior
deicing & coastal
inferior
deicing
inferior
deicing
good
deicing & coastal
5
4
2NH
OHgood
deicing
163
From an overview of the data presented in Table 6.4, it was difficult to form
conclusions based on inconsistencies in terms of assumed cause and effect relationships
and assumed agreements between methods used for evaluating UWS bridge performance.
Simply looking at the performance of reference bridges (highlighted in green in Table 6.4,
whose stated performance in inspection reports coincided with the cluster classifications)
in comparison to the qualitative conditions of the reference bridges, it can be seen that there
is not much agreement between these assessments of UWS bridge performance. All three
of the field bridges in the NC cluster were considered reference bridges and there was no
reference bridge included in the NH cluster because the original reference bridge (NH
017700960015300) was not evaluated due to it being painted as discussed in Section 3.1.5.
The CO, MN, and IA clusters were the only clusters that had agreement between these
parameters. The CT cluster was considered to have an inferior performing UWS reference
bridge in a severe deicing and coastal environment; however, the qualitative condition of
the reference bridge (along with the other two field bridges) was determined to be good.
The NC cluster was split between being classified as a good and inferior performing cluster
in a severe coastal environment; however, all UWS bridges were determined to have good
qualitative conditions. The NH cluster was classified as having a good performing UWS
reference bridge in a severe deicing and coastal environment; yet two out of the three field
bridges that were assessed (one of these two bridges included the replacement bridge, NH
011101120017900) were determined to have poor qualitative conditions. Finally, the OH
cluster was classified as having a good performing UWS reference bridge in a severe
deicing environment, but the reference bridge (along with the other two field bridges) was
determined to be in a poor qualitative condition.
It should be noted that comparisons between cluster classifications and field bridge
data may have inconsistencies due to the fact that cluster classifications consider the entire
164
UWS bridge inventory within the agency associated with that cluster, while field bridge
data considers individual bridges. Furthermore, correlations between other pairs of data
types in Table 6.4 may be obscured by the influence of additional variables, or more data
points may be required to assess these correlations. The data presented in Table 6.4 only
summarizes data collected from Phase 3 of this research project. Compiling all data
collected thus far (Phase 2 and Phase 3) may provide better understandings of preliminary
correlations discussed in this thesis. Doing so may allow clusters to be more easily
compared in terms of environmental conditions, maintenance practices, and UWS
performance in order to draw conclusions regarding environments and maintenance
practices that are and are not suitable for UWS bridges.
6.3 Main Takeaways
One of the main takeaways from this thesis involved the correlation found between
the tape test results and IC analysis results in terms of standard sample area location.
Section 5.7.3 shows the correlations between the average percent area of rust particles
greater than or equal to an 1/8 inch and the average chloride, average nitrate, and average
sulfate concentrations for each standard sample area location. The higher values from the
tape test results tended to correspond with the higher values of each ion that was assessed,
and vice versa.
The discussion of the tape test results and IC analysis results in terms of standard
sample area location in Section 4.4.1.3 and Section 4.4.2.3, respectively were very similar
in regard to the locations that performed poor (in terms of tape test results) and had higher
ion concentrations (in terms of IC analysis results) as well as the locations that performed
good (in terms of tape test results) and had lower ion concentrations (in terms of IC analysis
results). Standard sample area locations 1, 3, 7, and 9 each had higher average percent areas
165
of rust particles greater than or equal to an 1/8 inch and average ion concentrations than
the other locations. On the other hand, standard sample area locations 5 and 11 both had
lower average percent areas of rust particles greater than or equal to an 1/8 inch and average
ion concentrations than the other locations. Standard sample area locations 1, 3, 7, and 9
were each located on the tops of the bottom flanges of interior bridge girders while standard
sample area locations 5 and 11 were both located on the web of the exterior portion of the
fascia girder. Refer to Table 3.6 for descriptions of each standard sample area location.
Figure 6.1 shows a bar graph of the average chloride concentrations and percent area of
rust particles greater than or equal to an 1/8 inch.
Figure 6.1 Graph of Average Chloride Concentrations and Percent Area of Rust Particles
Greater than or Equal to an 1/8 inch
Similarly, the Raman et al. (1988) study discussed in Section 2.3.1.5 mentions that
interior locations of girders were found to perform the worse in terms of the observed flaky
4755
2287
4364
2363
1473
4768
5356
2906
4879
2390
1410
484710.88
8.45
12.50
2.852.47
6.93
11.08
5.67
11.54
2.22 2.14
7.98
0
2
4
6
8
10
12
14
0
1000
2000
3000
4000
5000
6000
1 2 3 4 5 6 7 8 9 10 11 12
Per
cent A
rea
(%)
Co
nce
ntr
atio
n (
ppm
)
Standard Sample Area Location ID
Average Chloride(ppm)
Average Percent Areaof Rust Particles ≥ 1/8" (%)
166
or “sheet-type” rust that formed at these locations. This same observation was made in the
qualitative assessment of field bridges from Phase 3 shown in Table 4.1 and discussed in
Section 4.1 where large and small rust flakes were most commonly found at interior
locations. Raman et al. (1988) also mentions that chloride and salt accumulation was higher
at interior locations. Interior portions of the bridge girders are more susceptible to retaining
moisture being that they are not exposed to sunlight that can allow the steel to dry. This
means that they may experience a longer TOW and be susceptible to trapping higher
concentrations of chloride because they are subject to chloride laden moisture from road
spray but not the rinsing action of rainwater. The agreement between the correlation of tape
test results and IC analysis results in terms of standard sample area location presented in
this thesis and the Raman et al. (1988) study are significant in providing justification for
locations of UWS girders on bridges that typically perform worse. This may provide
evidence for the effectiveness of the clear tape adhesion test being used to evaluate the
performance of UWS.
6.4 Future Work
Referring back to Section 6.3, Raman et al. (1988) also found a correlation between
the sizes of observed rust flakes formed on steel surfaces at interior, sheltered locations and
chloride contents in the rust patinas (refer to Section 2.3.1.5). Similarly, Crampton et al.
(2013) notes the size of rust flakes and their correlation to patina performance when using
the NCHRP guidelines (Albrecht and Naeemi, 1984) (refer to Section 2.2.1). Crampton et
al. (2013) found that UWS surfaces with higher concentrations of chloride in the oxide
layer were found to have developed larger, thicker rust flakes in the patina. Similar to these
two studies, future work could include a digital image processing method to assess the size
of rust flakes from sample area photographs collected in Phase 3 field evaluations (e.g.
167
refer back to example sample area photos in Section 3.2.3.2.3). The sizes of rust flakes may
then be compared with tape test results and IC analysis results to evaluate correlations
between the size of rust flakes, chloride contents, and patina performance similar to Raman
et al. (1988) and Crampton et al. (2013). This may provide more insight regarding
evaluating UWS performance in terms of chloride concentrations, the clear tape adhesion
test, and visual inspection of rust patinas.
Future work for this research project also includes assessing the effectiveness of
new inspection methods that were used in Phase 3 to evaluate UWS bridge performance.
One of these new inspection methods includes rust color analyses from photos of rust
patinas collected at each sample area that was evaluated. This will hopefully provide
insight regarding UWS bridge performance similar to the Hara et al. (2006) and Crampton
et al. (2013) studies, which included using the 5 indices developed by the Japan Iron and
Steel Federation (JISF) and Japan Association of Steel Bridge Construction (JASBC) and
NCHRP guidelines (Albrecht and Naeemi, 1984), respectively to evaluate conditions of
UWS.
XRD analyses of rust samples collected from each field bridge will be used to
identify and quantify ratios of different corrosion products of rust patinas. Evaluating
preliminary correlations between this information and other data types, such as bridge
maintenance practices, environmental conditions, and UWS bridge performance measures
may provide insight regarding methods for assessing UWS performance. If correlations
exist, XRD analysis may pose as an effective method for predicting long-term performance
of UWS bridges. Refer to Section 2.2.4 and Section 2.3 regarding some background
information about XRD analysis and corrosion products, respectively.
Another new inspection method involved using dry-film thickness measurements
to measure the thickness of rust patinas at each sample area that was evaluated. The
168
effectiveness of these measurements determining characteristics of the rust patina may be
evaluated as well as used to hopefully predict corrosion rates based on dry-film
measurements being taken again at the same sample area locations at periodic intervals.
Refer to Appendix C for dry-film thickness measurements of field bridges evaluated in
Phase 3.
Finally, ultrasonic thickness measurements will similarly be used to determine
characteristics of the rust patina and hopefully predict corrosion rates by taking
measurements again at the same sample area locations at periodic intervals. Refer to
Appendix C for ultrasonic thickness measurements of field bridges evaluated in Phase 3.
Assessing these UWS bridge inspection methods will further develop field inspection
protocols for future UWS bridge evaluations.
Other future work includes compiling all data collected thus far in the GIS database
that was created in Phase 2. Preliminary correlations from Phase 3 discussed in this thesis
as well as preliminary correlations found in Phase 2 of this research project will then be
further evaluated by a multivariate statistical analysis. This will allow for comparisons to
be made between clusters with similar environmental conditions and maintenance
practices, but differing UWS bridge conditions. Doing so may allow for better
understanding of correlations associated with UWS bridge performance and provide
quantitative guidelines to define environments that cause undesirable rates of corrosion in
UWS bridges. This will in turn provide updates to generic language used in TA 5140.22
regarding unsuitable environments for UWS bridges to be used.
169
REFERENCES
Albrecht, P., and Naeemi, A. H. (1984). “Performance of Weathering Steel in
Bridges (Ser. National Cooperative Highway Research Program Report, 272)”.
Transportation Research Board, National Research Council, Washington, D.C.
Albrecht, P., Coburn, K., Wattar, F. M., Tinklenberg, G. L., and Gallagher W. P.
(1989). “Guidelines for the Use of Weathering Steel in Bridges (Ser. National
Cooperative Highway Research Program Report, 314)”. Transportation Research
Board, National Research Council, Washington, D.C.
Alland, K., Vandenbossche, J. M., Vidic, R., & Ma, X. (2013). “Evaluation of Bridge
Cleaning Methods on Steel Structures, Final Report.” FHWA-PA-2013-007-PIT
WO 2, Pennsylvania Department of Transportation, Harrisburg, Pennsylvania.
American Association of State Highway and Transportation Officials (AASHTO). (2013;
2014; 2017). “Manual for Bridge Element Inspection (1st Edition), with 2015 and
2018 Interim Revisions.” American Association of State Highway and
Transportation Officials, Washington, D.C.
American Association of State Highway and Transportation Officials (AASHTO).
(2018). “AASHTO Subcommittee on Bridge and Structures Annual State Bridge
Engineers Survey.” Retrieved from https://bridges.transportation.org/bridge-
surveys/ last accessed, May 13, 2020.
American Iron and Steel Institute (AISI) (1982). “Performance of Weathering Steel in
Highway Bridges.” AISI PS 288 0782-5M-SS, First Phase Report, American Iron
and Steel Institute, Washington, D.C.
Ault, J. P., & Dolph, J. D. (2018). “Corrosion Prevention for Extending the Service Life
of Steel Bridges (Ser. NCHRP Synthesis, 517).” National Cooperative Highway
Research Program, American Association of State Highway and Transportation
Officials, United States Federal Highway Administration, Transportation
Research Board, Washington, D.C.
Cano, H., Diaz I., de la Fuente, D., Chico, B., & Morcillo, M. (2018). “Effect of Cu, Cr
and Ni Alloying Elements on Mechanical Properties and Atmospheric Corrosion
Resistance of Weathering Steels in Marine Atmospheres of Different
Aggressivities.” Materials and Corrosion, 69(1), 8–19.
170
Clear Roads (2019). “Annual Survey of State Winter Maintenance Data.” Retrieved from
https://clearroads.org/winter-maintenance-survey/ last accessed, May 13, 2020.
Cook, D. C., Van Orden, A. C., Carpio, J. J., & Oh, S. J. (1998). “Atmospheric Corrosion
in the Gulf of Mexico.” Hyperfine Interactions, 113(1-4), 319–329.
Cook, D. C., Oh, S. J., Balasubramanian, R., & Yamashita, M. (1999). “The Role of
Goethite in the Formation of the Protective Corrosion Layer on Steels.” Hyperfine
Interactions, 122(1-2), 59–70.
Cornell, R. and Schwertmann, U. (2006). “The Iron Oxides: Structure, Properties,
Reactions, Occurrences, and Uses.” John Wiley and Sons, Weinheim, Germany.
Crampton, D. D., Holloway, K. P., & Fraczek, J. (2013). “Assessment of Weathering
Steel Bridge Performance in Iowa and Development of Inspection and
Maintenance Techniques.” Wiss, Janney, Elstner Associates, Inc., Iowa
Department of Transportation, & United States Federal Highway Administration.
Diaz, I., Cano, H., Crespo, D., Chico, B., de la Fuente, D., & Morcillo, M. (2018).
“Atmospheric Corrosion of ASTM A-242 and ASTM A-588 Weathering Steels in
Different Types of Atmosphere.” Corrosion Engineering, Science and
Technology, 53(6), 449–459.
Federal Highway Administration (FHWA) (1989). “Uncoated Weathering Steel in
Structures,” Technical Advisory 5140.22 Federal Highway Administration,
Washington, DC.
Hara, S., Kamimura, T., Miyuki, H., & Yamashita, M. (2007). “Taxonomy for Protective
Ability of Rust Layer Using its Composition Formed on Weathering Steel
Bridge.” Corrosion Science, 49(3), 1131–1142.
Hooks, J. M. & Weidner, J. (2016). “Long-Term Bridge Performance (LTBP) Program
Protocols (Version 1).” U.S. Department of Transportation, Federal Highway
Administration, Research, Development and Technology, Turner-Fairbank
Highway Research Center.
Kamimura, T., Hara, S., Miyuki, H., Yamashita, M., & Uchida, H. (2006). “Composition
and Protective Ability of Rust Layer Formed on Weathering Steel Exposed to
Various Environments.” Corrosion Science, 48(9), 2799–2812.
McConnell, J., Mertz, D., Shenton, H., Lee, S., and Roda, A. (2012). “Long‐Term
Bridge Performance (LTBP) Program: Evaluation of Unpainted Weathering Steel
Highway Bridge Performance Phase I Report”, Center for Innovative Bridge
Engineering, University of Delaware, Newark, DE.
171
McConnell, J. R., Shenton III, H. W., Mertz, D. R., and Kaur, D. (2014 a) “Performance
of Uncoated Weathering Steel Highway Bridges throughout the United States.”
Proceedings of the 2014 Transportation Research Board Annual Meeting,
Washington, D.C., January 2014.
McConnell, J., Shenton, H., and Mertz, D. (2014 b). “Long‐Term Bridge Performance
(LTBP) Program: Evaluation of Unpainted Weathering Steel Highway Bridge
Performance Phase II Report”, Center for Innovative Bridge Engineering,
University of Delaware, Newark, DE.
McConnell, J. R., Shenton III, H. W., Mertz, D. R., & Kaur, D. (2014 c). “National
Review on use and Performance of Uncoated Weathering Steel Highway
Bridges.” Journal of Bridge Engineering, 19(5), 04014009.
McConnell, J. R., Shenton III, H. W., & Mertz, D. R. (2016). “Performance of Uncoated
Weathering Steel Bridge Inventories: Methodology and Gulf Coast Region
Evaluation.” Journal of Bridge Engineering, 21(12), 04016087.
McConnell, J. Shenton III, H. W., Bai, T., and Rupp, J. (2018). “Phase 3: Weathering
Steel Performance Data Collection Task 3 Report”, submitted to Federal Highway
Administration.
McConnell, J. R. and Shenton III, H. W. (2018). “Recommended Revisions to FLD-DC-
VIS-002.” Task 2 Interim Report for Uncoated Weathering Steel Data Collection
submitted to Federal Highway Administration.
McDad, B. (2000). “Performance of Weathering Steel in TxDOT Bridges: A Research
Project Conducted for the Texas Department of Transportation (Ser. Report, no.
1818-1).” Texas Dept. of Transportation, Construction Division, Materials
Section, Austin, Texas.
Morcillo, M., Chico, B., Díaz, I., Cano, H., & de la Fuente, D. (2013). “Atmospheric
Corrosion Data of Weathering Steels. A Review.” Corrosion Science, 77, 6–24.
Morcillo, M., Diaz, I., Chico, B., Cano, H., & de la Fuente, D. (2014). “Weathering
Steels: From Empirical Development to Scientific Design. A Review.” Corrosion
Science, 83, 6–31.
Oh, S. J., Cook, D. C., & Townsend, H. E. (1999). “Atmospheric Corrosion of Different
Steels in Marine, Rural and Industrial Environments.” Corrosion Science, 41(9),
1687–1702.
Palle, S., Younce, R., & Hopwood II, T. (2003). “Investigation of Soluble Salts on
Kentucky Bridges.” Kentucky Transportation Center, University of Kentucky,
Lexington.
172
Raman, A., Dean, S. W., & Lee, T.S. (1987). “Atmospheric Corrosion Problems with
Weathering Steels in Louisiana Bridges.” American Society of Testing and
Materials, Philadelphia, Pennsylvania, pp. 16-29.
Saha, J. K. (2013). “Corrosion of Constructional Steels in Marine and Industrial
Environment.” Frontier Work in Atmospheric Corrosion. Springer.
Shenton III, H. W., Mertz, D. R., and Weykamp, P. J. (2016). “Guidelines for
Maintaining Small Movement Bridge Expansion Joints, NCHRP 12-100 Final
Report (Part 1).” Transportation Research Board, National Academy of Sciences,
Washington, D.C.
Wang, Z., Liu, J., Wu, L., Han, R., & Sun, Y. (2013). “Study of the Corrosion Behavior
of Weathering Steels in Atmospheric Environments.” Corrosion Science, 67, 1–
10.
Yamashita, M., Miyuki, H., Matsuda, Y., Nagano, H., & Misawa, T. (1994). “The Long
Term Growth of the Protective Rust Layer Formed on Weathering Steel by
Atmospheric Corrosion During a Quarter of a Century.” Corrosion Science, 36(2),
283–299.
173
Appendix A
CLUSTER BRIDGE CHARACTERISTICS
Table A.1 CO Cluster Bridges
Number CombinationStructure
Number
Corssing
Type
ADT
Under
Structure
ADT
Cat.
(H/L)
Verticle
Under-
Clearance
(ft.)
Vert.
Cat.
(H/L)
Relative
Humidity
Humidity
Cat.
(H/L)
Snow
(in.)
Snow
Cat.
(H/L)
Chloride
(mg/L)
Chloride
Cat.
(H/L)
Age
(years)SCR
1 12 E-16-JZ Highway 183000 H 19.69 H 9E, 3F L 62.6 L 0.045 L 28 7
2 20 E-16-JW Highway 62500 L 16.40 L 9E, 3F L 62.6 L 0.045 L 31 8
3 20 E-16-JX Highway 84000 L 16.40 L 9E, 3F L 62.6 L 0.045 L 31 8
4 20 E-16-JY Highway 84000 L 16.40 L 9E, 3F L 62.6 L 0.045 L 31 8
5 24 E-16-JT Highway — L* 16.40 L 9E, 3F L 62.6 L 0.045 L 33 3
6 24 E-16-JU Highway — L* 16.40 L 9E, 3F L 62.6 L 0.045 L 33 3
7 28 E-16-JV Highway 62500 L 26.25 H 9E, 3F L 62.6 L 0.045 L 31 7
8 W E-16-KB Water — — — — 9E, 3F L 62.6 L 0.045 L 33 8
9 W E-16-KC Water — — — — 9E, 3F L 62.6 L 0.045 L 32 7
10 W E-16-KD Water — — — — 9E, 3F L 62.6 L 0.045 L 33 7
95200 18.28 9.0E, 3.0F 62.6 0.045 31.6 7
50245 3.72 0.0E, 0.0F 0.0 0.000 1.6 2
183000 26.25 9E, 3F 62.6 0.045 33.0 8
62500 16.40 9E, 3F 62.6 0.045 28.0 3
84000 16.40 9E, 3F 62.6 0.045 31.5 7
— = data not provided
* = assumed category value because not provided
Mean
Standard Deviation
Max
Min
Median
174
Table A.2 CT Cluster Bridges
Table A.3 IA Cluster Bridges
Number CombinationStructure
NumberCorssing Type
Distance
to Coast
(miles)
Dist.
Cat.
(H/L)
ADT
Under
Structure
ADT
Cat.
(H/L)
Verticle
Under-
Clearance
(ft.)
Vert.
Cat.
(H/L)
Relative
Humidity
Humidity
Cat.
(H/L)
Snow
(in.)
Snow
Cat.
(H/L)
Chloride
(mg/L)
Chloride
Cat.
(H/L)
Age
(years)SCR
1 3 2928 Highway 3.8 L 37400 H 16.17 L 4F, 8G, 0H H 26.3 L 0.315 H 38 6
2 13 5843 Highway 1.4 L 153700 H 17.09 H 5F, 7G, 0H L 47.4 H 0.315 H 26 6
3 13 5555 Highway 1.8 L 161900 H 16.57 H 5F, 7G, 0H L 47.4 H 0.315 H 28 6
4 15 4382 Highway 2.9 L 48400 H 16.57 H 5F, 7G, 0H L 31.9 L 0.315 H 32 6
5 21 5796 Highway 0.6 L 11600 L 15.68 L 5F, 7G, 0H L 47.4 H 0.315 H 26 7
6 23,W 3831 Highway-Water 2.2 L 4200 L 15.91 L 5F, 7G, 0H L 31.9 L 0.315 H 37 7
7 28,R 14 Highway-Rail 0.0 L — L* 26.67 H 4F, 7G, 1H H 36.1 L 0.251 L 13 7
8 29 4295 Highway 1.0 L 11200 L 29.99 H 5F, 7G, 0H L 47.4 H 0.315 H 34 7
9 29 5844D Highway 1.1 L — L* 16.24 H 5F, 7G, 0H L 47.4 H 0.315 H 26 6
10 29 5558 Highway 3.7 L — L* 16.50 H 5F, 7G, 0H L 41.2 H 0.315 H 26 7
11 29 5844B Highway 1.2 L — L* 18.67 H 5F, 7G, 0H L 47.4 H 0.315 H 25 6
12 31 3830 Highway 2.2 L 19400 L 16.24 L 5F, 7G, 0H L 31.9 L 0.315 H 37 6
13 31,W 3832 Highway-Water 1.2 L 4200 L 16.67 H 5F, 7G, 0H L 31.9 L 0.315 H 37 7
14 31,W 4383 Highway-Water 4.5 L 9000 L 16.40 H 5F, 7G, 0H L 31.9 L 0.315 H 32 6
15 53 5230 Highway 7.9 H 13400 L 15.91 L 5F, 7G, 0H L 41.2 H 0.315 H 31 7
16 53 3588 Highway 6.4 H — L* 13.91 L 5F, 7G, 0H L 41.2 H 0.315 H 44 7
17 54 5307 Highway 18.8 H 5300 L 14.93 L 5F, 7G, 0H L 38.7 H 0.127 L 29 8
18 55,R 3912 Highway-Rail 7.3 H — L* 14.67 L 5F, 7G, 0H L 35.7 L 0.315 H 42 5
19 61 4276 Highway 11.7 H 16500 L 16.40 H 5F, 7G, 0H L 41.2 H 0.315 H 35 7
20 62 5308 Highway 18.9 H 1020 L 16.67 H 5F, 7G, 0H L 38.7 H 0.127 L 29 7
21 62 3607 Highway 22.3 H 5550 L 16.24 H 5F, 7G, 0H L 100.1 H 0.18 L 43 7
7.5 47453 17.34 4.7F, 7.2G, 0.0H 38.3 0.273 23.5 7
7.4 44392 3.81 0.5F, 0.4G, 0.2H 12.3 0.071 11.9 1
30.4 161900 29.99 6F, 8G, 2H 100.1 0.315 78.0 9
0.0 900 13.91 3F, 6G, 0H 23.6 0.127 2.0 3
5.4 33800 16.40 5F, 7G, 0H 36.1 0.315 24.0 7
— = data not provided
Standard Deviation
Max
Min
Median
Mean
* = assumed category value because not provided
Number CombinationStructure
Number
Corssing
Type
ADT
Under
Structure
ADT
Cat.
(H/L)
Verticle
Under-
Clearance
(ft.)
Vert.
Cat.
(H/L)
Relative
Humidity
Humidity
Cat.
(H/L)
Snow
(in.)
Snow
Cat.
(H/L)
Chloride
(mg/L)
Chloride
Cat.
(H/L)
Age
(years)SCR
1 8 041331 Highway 88500 H 17.16 L 3F, 9G L 34.8 L 0.066 L 11 7
2 8 042061 Highway 36200 H 16.50 L 3F, 9G L 23.8 L 0.066 L 7 9
3 8 609280 Highway 65700 H 16.34 L 3F, 9G L 23.8 L 0.066 L 10 7
4 8 042571 Highway 93110 H 17.16 L 3F, 9G L 34.8 L 0.066 L 6 7
5 8 042611 Highway 77610 H 16.83 L 3F, 9G L 34.8 L 1.066 L 10 9
6 16 608565 Highway 94500 H 19.00 H 3F, 9G L 34.8 L 0.066 L 10 9
7 16 042491 Highway 85700 H 18.67 H 3F, 9G L 34.8 L 0.066 L 10 7
8 16 042711 Highway 78360 H 24.02 H 3F, 9G L 34.8 L 0.066 L 10 8
9 16 004111 Highway 73990 H 18.18 H 3F, 9G L 34.8 L 0.066 L 12 8
10 24 606775 Highway 5900 L 17.16 L 3F, 9G L 34.8 L 0.066 L 16 7
11 24 601935 Highway 18400 L 16.77 L 3F, 9G L 34.8 L 0.066 L 13 8
12 32 015225 Highway 12400 L 17.91 H 3F, 9G L 28.2 L 0.066 L 41 7
13 32 601770 Highway 18400 L 20.18 H 3F, 9G L 34.8 L 0.066 L 16 8
14 32 607285 Highway 7200 L 18.77 H 3F, 9G L 34.8 L 0.066 L 13 9
41394 18.19 3.0F, 9.0G 30.7 0.066 9.9 8
32612 2.01 0.0F, 0.0G 5.4 0.000 5.1 1
108300 24.02 3F, 9G 34.8 0.066 41.0 9
2030 16.34 3F, 9G 21.7 0.066 2.0 7
27500 17.54 3F, 9G 34.8 0.066 9.5 8
Mean
Standard Deviation
Max
Min
Median
175
Table A.4 MN Cluster Bridges
Table A.5 NC Cluster Bridges
Number CombinationStructure
NumberCorssing Type
ADT
Under
Structure
ADT
Cat.
(H/L)
Verticle
Under-
Clearance
(ft.)
Vert.
Cat.
(H/L)
Relative
Humidity
Humidity
Cat.
(H/L)
Snow
(in.)
Snow
Cat.
(H/L)
Chloride
(mg/L)
Chloride
Cat.
(H/L)
Age
(years)SCR
1 2 04019 Highway 9700 H 16.11 L 2F, 9G, 1H, 0I H 53.1 H 0.030 L 34 5
2 2 71007 Highway 12000 H 16.11 L 2F, 6G, 4H, 0I H 46.4 H 0.057 L 34 7
3 2 73868 Highway 12300 H 16.70 L 1F, 5G, 4H, 2I H 47.0 H 0.039 L 37 6
4 3 600200 Highway 17500 H 16.57 L 2F, 9G, 1H, 0I H 34.2 L 0.070 H 43 7
5 6 27049 Highway 10300 H 16.70 L 4F, 8G, 0H, 0I L 56.0 H 0.057 L 24 7
6 6 62838 Highway 51800 H 16.40 L 4F, 8G, 0H, 0I L 52.9 H 0.057 L 40 7
7 6 62861 Highway 130000 H 16.11 L 4F, 8G, 0H, 0I L 52.9 H 0.057 L 40 6
8 8 19811 Highway 53000 H 16.31 L 4F, 8G, 0H, 0I L 44.3 L 0.057 L 35 7
9 8 19866 Highway 53000 H 16.99 L 4F, 8G, 0H, 0I L 44.3 L 0.057 L 34 7
10 12,R,W 69102 Highway-Water-Rail 66900 H 18.11 H 0F, 10G, 2H, 0I H 42.3 L 0.037 L 30 6
11 14 27796 Highway 135600 H 19.39 H 4F, 8G, 0H, 0I L 56.0 H 0.057 L 35 7
12 14 27047 Highway 111000 H 39.90 H 4F, 8G, 0H, 0I L 56.0 H 0.057 L 25 7
13 14 27727B Highway 109300 H 18.50 H 4F, 8G, 0H, 0I L 56.0 H 0.057 L 35 5
14 15 07018 Highway 13700 H 18.11 H 2F, 10G, 0H, 0I L 42.6 L 0.105 H 36 7
15 18 04021 Highway 3450 L 16.31 L 2F, 9G, 1H, 0I H 47.9 H 0.030 L 38 6
16 22,R 62532 Highway-Rail 2050 L 16.21 L 4F, 8G, 0H, 0I L 52.9 H 0.057 L 33 7
17 22 62870 Highway 3400 L 16.60 L 4F, 8G, 0H, 0I L 52.9 H 0.057 L 40 7
18 23 07017 Highway 7600 L 16.60 L 2F, 10G, 0H, 0I L 42.6 L 0.105 H 36 7
19 30,R 62526 Highway-Rail 300 L 25.30 H 3F, 9G, 0H, 0I L 52.9 H 0.057 L 40 5
20 30,R 62531 Highway-Rail 1025 L 20.31 H 4F, 8G, 0H, 0I L 52.9 H 0.057 L 36 8
29425 18.67 2.2F, 8.9G, 0.9H, 0.0I 45.3 0.065 31.3 7
51512 5.45 0.9F, 1.3G, 1.3H, 0.2I 7.8 0.025 8.9 1
303000 39.90 1F, 5G, 4H, 2I 88.1 0.105 48.0 9
35 16.11 5F, 7G, 0H, 0I 25.7 0.030 2.0 0
7800 16.65 2F, 10G, 0H, 0I 45.5 0.057 34.0 7
Mean
Standard Deviation
Max
Min
Median
Number CombinationStructure
Number
Corssing
Type
Distance
to Coast
(miles)
Dist.
Cat.
(H/L)
ADT
Under
Structure
ADT
Cat.
(H/L)
Verticle
Under-
Clearance
(ft.)
Vert.
Cat.
(H/L)
Relative
Humidity
Humidity
Cat.
(H/L)
Snow
(in.)
Snow
Cat.
(H/L)
Chloride
(mg/L)
Chloride
Cat.
(H/L)
Age
(years)SCR
1 3 1900831 Rail 4.2 L — — — — 1F, 8G, 3H L 2.3 L 0.328 L 33 5
2 3 190084 Rail 4.2 L — — — — 1F, 8G, 3H L 2.3 L 0.328 L 33 7
3 3 470381 Highway 32.2 H 1800 L 16.60 H 3F, 9G, 0H L 3.0 H 0.328 L 30 7
4 3 470382 Highway 32.2 H 2000 L 16.31 L 3F, 9G, 0H L 3.0 H 0.328 L 30 7
5 19 1290044 Highway 5.3 H 2500 L 17.42 H 0F, 9G, 3H H 2.4 H 0.717 L 29 7
6 19 1290045 Highway 5.3 H 2500 L 17.16 H 0F, 9G, 3H H 2.4 H 0.717 L 29 8
7 32 12900582 Highway 2.1 L 23000 H 16.40 L 0F, 9G, 3H H 2.3 L 0.717 L 28 8
8 32 1290059 Highway 2.1 L 25000 H 15.75 L 0F, 9G, 3H H 2.3 L 0.717 L 28 7
9 38 12900572 Highway 2.4 L 29000 H 16.17 L 0F, 9G, 3H H 2.3 L 0.717 L 28 8
10 38 1290042 Highway 4.7 H 29000 H 17.59 H 0F, 9G, 3H H 2.4 H 0.717 L 30 7
9.4 14350 16.67 0.8F, 8.8G, 2.4H 2.5 0.561 29.8 7
12.0 13139 0.65 1.2F, 0.4G, 1.3H 0.3 0.201 1.9 1
32.2 29000 17.59 3F, 9G, 3H 3.0 0.717 33.0 8
2.1 1800 15.75 0F, 8G, 0H 2.3 0.328 28.0 5
4.4 12750 16.50 0F, 9G, 3H 2.4 0.717 29.5 7
— = data not provided
Mean
Standard Deviation
Max
Min
Median1 = Inferior Reference Bridge
2 = Good Reference Bridge
176
Table A.6 NH Cluster Bridges
Table A.7 OH Cluster Bridges
Number Combination Structure Number Corssing Type
Distance
to Coast
(miles)
Dist.
Cat.
(H/L)
ADT
Under
Structure
ADT
Cat.
(H/L)
Verticle
Under-
Clearance
(ft.)
Vert.
Cat.
(H/L)
Relative
Humidity
Humidity
Cat.
(H/L)
Snow
(in.)
Snow
Cat.
(H/L)
Chloride
(mg/L)
Chloride
Cat.
(H/L)
Age
(years)SCR
1 3 019700810009300 Highway 3.2 L 51318 H 16.40 L 1F, 4G, 6H, 1I H 59.2 L 0.750 H 38 7
2 3 019700990014400 Highway 3.6 L 51318 H 16.04 L 1F, 4G, 6H, 1I H 59.2 L 0.750 H 38 7
3 3 010201410010900 Highway 0.9 L 51318 H 16.17 L 1F, 4G, 6H, 1I H 59.2 L 0.750 H 41 7
4 3 11101120017900 Highway 2.1 L 65610 H 16.14 L 1F, 4G, 6H, 1I H 59.2 L 0.75 H 14 8
5 3 011001740004000 Highway 1.2 L 79000 H 16.27 L 0F, 6G, 5H, 1I H 57.3 L 0.750 H 38 7
6 19 022200590009600 Highway 12.3 L — L* 14.50 L 3F, 8G, 1H, 0I H 59.2 L 0.259 H 35 7
7 19 022200510009400 Highway 12.6 L — L* 14.21 L 3F, 8G, 1H, 0I H 59.2 L 0.259 H 35 8
8 32,W 022800870006300 Highway-Water 5.7 L — L* 17.95 H 5F, 6G, 1H, 0I L 57.3 L 0.180 L 22 9
9 32 021900760009600 Highway 14.4 L 18571 L 16.73 H 4F, 7G, 1H, 0I L 59.2 L 0.154 L 31 7
10 38 012800920005900 Highway 24.9 H 68103 H 16.50 L 4F, 7G, 1H, 0I L 65.1 H 0.180 L 37 7
11 38 017700960015300 Highway 19.5 H 71000 H 16.31 L 5F, 7G, 0H, 0I L 68.2 H 0.180 L 26 8
12 40 017701340007300 Highway 17.6 H 75000 H 16.50 L 5F, 7G, 0H, 0I L 55.4 L 0.180 L 16 8
13 46 005201560013800 Highway 30.5 H 41000 H 23.29 H 4F, 8G, 0H, 0I L 65.1 H 0.154 L 35 7
14 46 012800680009900 Highway 26.8 H 64000 H 17.13 H 4F, 7G, 1H, 0I L 65.1 H 0.154 L 37 7
15 46,R,W 016101230007300 Highway-Water-Rail 23.9 H 77400 H 20.57 H 4F, 7G, 1H, 0I L 65.1 H 0.180 L 25 7
16 54 017201120011300 Highway 28.0 H 3900 L 14.57 L 5F, 7G, 0H, 0I L 68.2 H 0.180 L 36 6
17 54 005201540012100 Highway 31.3 H 14000 L 16.50 L 4F, 8G, 0H, 0I L 65.1 H 0.154 L 33 7
18 54 005201750005100 Highway 33.1 H 100 L 14.83 L 4F, 8G, 0H, 0I L 65.1 H 0.154 L 20 7
19 56,W 017701000011200 Highway-Water 19.3 H — L* 10.17 L 5F, 7G, 0H, 0I L 55.4 L 0.180 L 17 8
20 56,W 017701010011200 Highway-Water 19.3 H — L* 10.17 L 5F, 7G, 0H, 0I L 55.4 L 0.180 L 17 8
21 58 016101280012700 Highway 21.8 H — L* 17.72 H 3F, 8G, 1H, 0I H 65.1 H 0.180 L 36 8
22 58 003700950007000 Highway 19.2 H — L* 16.96 H 3F, 8G, 1H, 0I H 65.1 H 0.154 L 28 8
23 64 017701460003700 Highway 17.6 H 21000 L 17.42 H 5F, 7G, 0H, 0I L 55.4 L 0.180 L 20 8
24 64 017701510005700 Highway 17.1 H 26000 L 18.73 H 5F, 7G, 0H, 0I L 55.4 L 0.180 L 20 8
25 W 006502010002400 Water 0.1 L — — — — 1F, 4G, 6H, 1I H 59.2 L 0.750 H 29 7
26 W 006501310012300 Water 0.2 L — — — — 1F, 5G, 6H, 0I H 59.2 L 0.750 H 37 8
27 W 006501280012200 Water 0.3 L — — — — 1F, 5G, 6H, 0I H 59.2 L 0.750 H 38 7
28 W 006501230012600 Water 0.6 L — — — — 1F, 6G, 5H, 0I H 59.2 L 0.750 H 35 7
18.8 36748 16.33 3.8F, 6.9G, 1.2H, 0.1I 59.6 0.258 20.0 8
17.0 33592 2.77 1.2F, 1.1G, 1.6H, 0.3I 8.5 0.176 12.5 1
67.5 246700 23.29 5F, 9G, 6H, 2I 80.8 0.750 59.0 9
0.0 100 10.17 0F, 4G, 0H, 0I 41.6 0.102 2.0 4
15.3 27950 16.50 4F, 7G, 1H, 0I 59.2 0.180 18.0 8
— = data not provided
Mean
Standard Deviation
Max
Min
Median
* = assumed category value because not provided
Number CombinationStructure
NumberCorssing Type
ADT
Under
Structure
ADT
Cat.
(H/L)
Verticle
Under-
Clearance
(ft.)
Vert.
Cat.
(H/L)
Relative
Humidity
Humidity
Cat.
(H/L)
Snow
(in.)
Snow
Cat.
(H/L)
Chloride
(mg/L)
Chloride
Cat.
(H/L)
Age
(years)
SC
R
1 1 7700105 Highway 47308 H 15.09 L 0F, 11G, 1H H 43.4 H 0.101 H 9 6
2 1 7701977 Highway 23599 H 15.58 L 0F, 10G, 2H H 49.2 H 0.101 H 39 8
3 1 7701993 Highway 26000 H 15.32 L 0F, 10G, 2H H 49.2 H 0.101 H 40 8
4 1 7808054 Highway 15168 H 15.42 L 1F, 11G, 0H H 57.2 H 0.101 H 43 5
5 2 7701853 Highway 10281 H 15.49 L 0F, 10G, 2H H 49.2 H 0.070 L 45 8
6 2,W 7701799 Highway-Water 92927 H 16.01 L 0F, 11G, 1H H 49.2 H 0.100 L 32 5
7 2 7702043 Highway 10032 H 15.26 L 0F, 10G, 2H H 49.2 H 0.100 L 39 8
8 3 7808186 Highway 10108 H 15.16 L 1F, 11G, 0H H 40.1 L 0.101 H 45 6
9 4 7801246 Highway 8970 H 15.42 L 1F, 11G, 0H H 40.1 L 0.100 L 43 5
10 6 7606524 Highway 32165 H 16.08 L 2F, 10G, 0H L 49.2 H 0.100 L 31 7
11 6 7803788 Highway 8469 H 15.32 L 2F, 10G, 0H L 57.2 H 0.100 L 46 5
12 18 7701802 Highway 5161 L 15.26 L 0F, 11G, 1H H 49.2 H 0.100 L 32 7
13 18,W 7701810 Highway-Water 5394 L 15.26 L 0F, 10G, 2H H 49.2 H 0.100 L 32 7
14 24 7805934 Highway 7832 L 15.16 L 2F, 10G, 0H L 40.1 L 0.100 L 21 5
15 25 7700148 Highway 2931 L 17.85 H 1F, 11G, 0H H 43.4 H 0.101 H 31 6
16 25,W,R 7708645 Highway-Water-Rail 5508 L 23.00 H 0F, 10G, 2H H 49.2 H 0.101 H 37 7
17289 16.04 0.6F, 10.4G, 0.9H 43.1 0.100 43.1 8
22909 1.97 0.8F, 0.5G, 0.9H 12.7 0.002 12.7 1
99400 23.00 0F, 10G, 2H 95.3 0.101 95.3 9
295 15.09 2F, 10G, 0H 23.8 0.070 23.8 4
7832 15.37 0F, 11G, 1H 40.1 0.100 40.1 8
Standard Deviation
Max
Min
Median
Mean
177
Appendix B
PARAMETRIC COMBINATIONS
Table B.1 Deicing Cluster Parametric Combinations
CombinationCrossing
Type
ADT
Under
Structure
Vertical
Under-
Clearance
Relative
HumiditySnow Chloride
1 Highway High Low High High High
2 Highway High Low High High Low
3 Highway High Low High Low High
4 Highway High Low High Low Low
5 Highway High Low Low High High
6 Highway High Low Low High Low
7 Highway High Low Low Low High
8 Highway High Low Low Low Low
9 Highway High High High High High
10 Highway High High High High Low
11 Highway High High High Low High
12 Highway High High High Low Low
13 Highway High High Low High High
14 Highway High High Low High Low
15 Highway High High Low Low High
16 Highway High High Low Low Low
17 Highway Low Low High High High
18 Highway Low Low High High Low
19 Highway Low Low High Low High
20 Highway Low Low High Low Low
21 Highway Low Low Low High High
22 Highway Low Low Low High Low
23 Highway Low Low Low Low High
24 Highway Low Low Low Low Low
25 Highway Low High High High High
26 Highway Low High High High Low
27 Highway Low High High Low High
28 Highway Low High High Low Low
29 Highway Low High Low High High
30 Highway Low High Low High Low
31 Highway Low High Low Low High
32 Highway Low High Low Low Low
R Railway NA NA NA NA NA
W Waterway NA NA NA NA NA
178
Table B.2 Deicing + Coastal Cluster Parametric Combinations
CombinationCrossing
Type
Distance
to
Coast
ADT
Under
Structure
Vertical
Under-
Clearance
Relative
HumiditySnow Chloride
1 Highway Low High Low High High High
2 Highway Low High Low High High Low
3 Highway Low High Low High Low High
4 Highway Low High Low High Low Low
5 Highway Low High Low Low High High
6 Highway Low High Low Low High Low
7 Highway Low High Low Low Low High
8 Highway Low High Low Low Low Low
9 Highway Low High High High High High
10 Highway Low High High High High Low
11 Highway Low High High High Low High
12 Highway Low High High High Low Low
13 Highway Low High High Low High High
14 Highway Low High High Low High Low
15 Highway Low High High Low Low High
16 Highway Low High High Low Low Low
17 Highway Low Low Low High High High
18 Highway Low Low Low High High Low
19 Highway Low Low Low High Low High
20 Highway Low Low Low High Low Low
21 Highway Low Low Low Low High High
22 Highway Low Low Low Low High Low
23 Highway Low Low Low Low Low High
24 Highway Low Low Low Low Low Low
25 Highway Low Low High High High High
26 Highway Low Low High High High Low
27 Highway Low Low High High Low High
28 Highway Low Low High High Low Low
29 Highway Low Low High Low High High
30 Highway Low Low High Low High Low
31 Highway Low Low High Low Low High
32 Highway Low Low High Low Low Low
33 Highway High High Low High High High
34 Highway High High Low High High Low
35 Highway High High Low High Low High
36 Highway High High Low High Low Low
37 Highway High High Low Low High High
38 Highway High High Low Low High Low
39 Highway High High Low Low Low High
40 Highway High High Low Low Low Low
41 Highway High High High High High High
42 Highway High High High High High Low
43 Highway High High High High Low High
44 Highway High High High High Low Low
45 Highway High High High Low High High
46 Highway High High High Low High Low
47 Highway High High High Low Low High
48 Highway High High High Low Low Low
49 Highway High Low Low High High High
50 Highway High Low Low High High Low
51 Highway High Low Low High Low High
52 Highway High Low Low High Low Low
53 Highway High Low Low Low High High
54 Highway High Low Low Low High Low
55 Highway High Low Low Low Low High
56 Highway High Low Low Low Low Low
57 Highway High Low High High High High
58 Highway High Low High High High Low
59 Highway High Low High High Low High
60 Highway High Low High High Low Low
61 Highway High Low High Low High High
62 Highway High Low High Low High Low
63 Highway High Low High Low Low High
64 Highway High Low High Low Low Low
R Railway NA NA NA NA NA NA
W Waterway NA NA NA NA NA NA
179
Table B.3 Coastal Cluster Parametric Combinations
CombinationDistance
to CoastHumidity Chloride
1 Low High High
2 Low High Low
3 Low Low High
4 Low Low Low
5 High High High
6 High High Low
7 High Low High
8 High Low Low
180
Appendix C
FIELD DATA ENTRY SHEETS
181
Bridge: CO E-16-JWDate: 10/17/19
Span #1
st FB
(A)
2nd
B
(B)WL BFB
Facing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Average of 9
Readings
(microns)
Standard
Deviation
Example 1 X X X X 10 10 Left abutment 10 0.1 0.1 100 30
1 1 X X X X 22.645 54.5 Abutment 2 99.5 1.5 18 42.1 13.4
2 1 X X X X 21.135 54.5 Abutment 2 99.5 4 0 16.6 2.5
3 1 X X X X 20.729 51.697 Abutment 2 102.303 75 0 31.6 29.7
4 1 X X X X 21.927 41.468 Abutment 2 112.532 1.5 18 33.6 6.1
5 1 X X X X 20.208 41.052 Abutment 2 112.948 4 0 20.9 4.9
6 1 X X X X 19.791 38.093 Abutment 2 115.907 75 0 25.2 7.1
7 1 X X X X 20.75 37.791 Abutment 2 116.209 1.5 18 32.2 21.8
8 1 X X X X 19.083 37.791 Abutment 2 116.209 4 0 34.7 44.2
9 1 X X X X 18.916 36.25 Abutment 2 117.75 75 0 39.8 14.9
10 1 X X X X 21.583 48.75 Abutment 2 105.25 1.5 18 24.3 6.6
11 1 X X X X 20.083 47.666 Abutment 2 106.334 4 0 28.8 6
12 1 X X X X 19.666 49.666 Abutment 2 104.334 75 0 49.3 44
W BFT BFB TFBFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Typical
Ultrasonic
Thickness
1A X X X 21.927 41.468 Abutment 2 112.532 1.5 18
Most
Corrosive
Ultrasonic
Thickness
1B X X X 21.583 48.75 Abutment 2 105.25 1.5 18
Dry Film Thickness
Tape Samples, Rust Samples, Ultrasonic
Component
Structural Component
Test
Area
ID
Orientation Above (Rail)
Evaluating
Structural ComponentOrientation Above (Rail)
0.318
Note: Very odd/different bridges. Flanges have virtually no patina, only some mill scale and some pitting. Could flanges be regular steel? Webs have very fine, light patina. Splice plates clearly are WS. No chance of getting
samples from flanges. Very difficult to get on web also.
LocationCoordinates
Horizontal distance
Horizontal distance
Thickness (in.)
Location
Vertical distance
from roadway/
ground (ft)
Coordinates
Element
Identifier
Component
Vertical distance
from roadway/
ground (ft)
Beam
0.307
1st FB - fascia beam facing traffic first; 2nd beam - 2nd beam in the traffic direction
WL - Web near bottom flange; W - Web; BFT - Bottom flange top side; BFB - Bottom flange bottom side; TFB - Top flange bottom side
Element Identifier Examples: 1A - Fascia beam, Span 1; 2B - Second beam (interior beam adjacent to exterior beam) Span 2
182
Bridge: CO E-16-JXDate: 10/16/19
Span #1
st FB
(A)
2nd
B
(B)WL BFB
Facing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Average of 9
Readings
(microns)
Standard
Deviation
Example 1 X X X X 10 10 Left abutment 10 0.1 0.1 100 30
1 1 X X X X 20.937 41.604 Abutment 2 147.066 1.5 24 87.8 21
2 1 X X X X 18.937 41.604 Abutment 2 147.066 4 0 73.4 47.6
3 1 X X X X 18.802 38.166 Abutment 2 150.504 68 0 40.7 11.6
4 1 X X X X 21.822 60.083 Abutment 2 128.587 1.5 24 79.1 21.4
5 1 X X X X 19.822 60.083 Abutment 2 128.587 4 0 79.6 38.2
6 1 X X X X 19.687 55.75 Abutment 2 132.92 68 0 75.9 36.1
7 1 X X X X 19.083 38.416 Abutment 2 150.254 1.5 24 55.4 14.9
8 1 X X X X 21.083 35.916 Abutment 2 152.754 4 0 160.2 86.9
9 1 X X X X 18.916 37.625 Abutment 2 151.045 68 0 51 11.2
10 1 X X X X 21.833 55.791 Abutment 2 132.879 1.5 24 119.6 39.2
11 1 X X X X 19.791 55.25 Abutment 2 133.42 4 0 158.4 48.9
12 1 X X X X 19.666 52.416 Abutment 2 136.254 68 0 68.3 18.9
W BFT BFB TFBFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Typical
Ultrasonic
Thickness
1A X X X 18.802 38.166 Abutment 2 150.504 68 0
Most
Corrosive
Ultrasonic
Thickness
1B X X X 21.833 55.791 Abutment 2 132.879 1.5 24
1st FB - fascia beam facing traffic first; 2nd beam - 2nd beam in the traffic direction
WL - Web near bottom flange; W - Web; BFT - Bottom flange top side; BFB - Bottom flange bottom side; TFB - Top flange bottom side
Element Identifier Examples: 1A - Fascia beam, Span 1; 2B - Second beam (interior beam adjacent to exterior beam) Span 2
Dry Film Thickness
Tape Samples, Rust Samples, Ultrasonic
Component
Structural Component
Test
Area
ID
Orientation Above (Rail)
Evaluating
Structural ComponentOrientation Above (Rail)
0.385
Element
Identifier
Component
Vertical distance
from roadway/
ground (ft)
Beam
1.733
LocationCoordinates
Horizontal distance
Horizontal distance
Thickness (in.)
Location
Vertical distance
from roadway/
ground (ft)
Coordinates
183
Bridge: CO E-16-JZDate: 10/15/19
Span #1
st FB
(A)
2nd
B
(B)WL BFB
Facing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Average of 9
Readings
(microns)
Standard
Deviation
Example 1 X X X X 10 10 Left abutment 10 0.1 0.1 100 30
1 2 X X X X 23.635 86.593 Pier 2 245.593 1.25 25 93.8 13.5
2 2 X X X X 21.625 86.593 Pier 2 245.593 4 0 68.9 34.6
3 2 X X X X 21.239 89.833 Pier 2 248.833 66 0 199.8 87.6
4 2 X X X X 23.666 102.968 Pier 2 261.968 1.25 25 74.8 21
5 2 X X X X 21.583 102.968 Pier 2 261.968 4 0 45.6 37.4
6 2 X X X X 21.166 76.666 Pier 3 270.584 66 0 181.3 85.3
7 2 X X X X 20.468 73.734 Pier 3 273.516 1.25 25 66.2 29.2
8 2 X X X X 20.39 72.848 Pier 3 274.402 4 0 106.8 70.1
9 2 X X X X 20.104 67.385 Pier 3 279.865 66 0 259.3 103.3
10 2 X X X X 20.421 87.453 Pier 3 259.797 1.25 25 91 35.1
11 2 X X X X 20.291 91.166 Pier 3 256.084 4 0 199.6 69
12 2 X X X X 20 86.697 Pier 3 260.553 66 0 259.3 55.4
W BFT BFB TFBFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Typical
Ultrasonic
Thickness
2A X X X 23.666 102.968 Pier 2 261.968 1.25 25
Most
Corrosive
Ultrasonic
Thickness
2B X X X 20.421 87.453 Pier 3 259.797 1.25 25
1st FB - fascia beam facing traffic first; 2nd beam - 2nd beam in the traffic direction
WL - Web near bottom flange; W - Web; BFT - Bottom flange top side; BFB - Bottom flange bottom side; TFB - Top flange bottom side
Element Identifier Examples: 1A - Fascia beam, Span 1; 2B - Second beam (interior beam adjacent to exterior beam) Span 2
Dry Film Thickness
Tape Samples, Rust Samples, Ultrasonic
Component
Structural Component
Test
Area
ID
Orientation Above (Rail)
Evaluating
Structural ComponentOrientation Above (Rail)
0.373
Element
Identifier
Component
Vertical distance
from roadway/
ground (ft)
Beam
0.361
LocationCoordinates
Horizontal distance
Horizontal distance
Thickness (in.)
Location
Vertical distance
from roadway/
ground (ft)
Coordinates
184
Bridge: CT 3830Date: 5/7/19
Span # 1st FB 2nd B WL BFTFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
With plastic
shim (261
microns thick)
(microns)
Standard
Deviation
Without plastic
shim (microns)
Standard
Deviation
Example 1 X X X X 10 10 Left abutment 10 0.1 0.1 100 30 100 30
1 1 X X X X 20.7 48.83 Abut. No. 1 48.83 16.5 1.5 640 247
2 1 X X X X 20.49 48.83 Abut.No. 1 48.83 11.5 21.5 578 169
3 1 X X X X 20.85 63.33 Abut.No. 1 63.33 16.5 1.5 708 80 221 68
4 1 X X X X 22.64 63.33 Abut.No. 1 63.33 11.5 21.5 602 38 144 25
5 1 X X X X 20.85 63.33 Abut.No. 1 63.33 5.5 1.5 767 132 256 43
6 1 X X X X 20.7 49.25 Abut.No. 1 49.25 5.5 1.5 950 282 385 138
7 1 X X X X 20.09 51.15 Abut.No. 1 51.15 17 1.5 1150.4 170 567.6 71
8 1 X X X X 21.86 51.15 Abut.No. 1 51.15 11.5 21.5 927.6 230 424.8 148
9 1 X X X X 20.25 62.01 Abut.No. 1 62.01 17 1.5 807.2 82 463.2 111
10 1 X X X X 21.86 62.01 Abut.No. 1 62.01 11.5 21.5 815.2 173 223.2 124
11 1 X X X X 20.16 62.01 Abut.No. 1 62.01 5 1.5 1046 122 547.6 173
12 1 X X X X 20.13 51.15 Abut. No. 1 51.15 5 1.5 1072.8 171 489.6 173
W BFT BFB TFBFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Typical
Ultrasonic
Thickness
1E X X X 20.7 48.83 Abut. No. 1 48.83 16.5 1.5
Most
Corrosive
Ultrasonic
Thickness
1D X X X 20.13 51.15 Abut. No. 1 51.15 5 1.5
LocationCoordinates
Horizontal distance
Horizontal distance
Thickness (in.)
Location
Vertical distance
from roadway/
ground (ft)
CoordinatesComponent
Vertical distance
from roadway/
ground (ft)
Beam
1.235
1.456
1st FB - fascia beam facing traffic first; 2nd beam - 2nd beam in the traffic direction
WL - Web near bottom flange; W - Web; BFT - Bottom flange top side; BFB - Bottom flange bottom side; TFB - Top flange bottom side
Element Identifier Examples: 1A - Fascia beam, Span 1; 2B - Second beam (interior beam adjacent to exterior beam) Span 2
Dry Film Thickness
Tape Samples, Rust Samples, Ultrasonic
Component
Structural Component
Test
Area
ID
Orientation Above
Evaluating
Structural ComponentOrientation Above
Element
Identifier
185
Bridge: CT 4382Date: 5/8/19
Span #1
st FB
(A)
2nd
B
(B)WL BFT
Facing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designation
X (ft)
[from Pier 1]Y (in.) Z (in.)
With plastic
shim (261
microns thick)
(microns)
Standard
Deviation
Without plastic
shim (microns)
Standard
Deviation
Example 1 X X X X 10 10 Left abutment 10 0.1 0.1 100 30 100 30
1 2 X X X X 17.75 56.67 Abut. 2 69.17 5.5 2.25 1191.2 198 879.8 375
2 2 X X X X 19.08 56.67 Abut. 2 69.17 11.5 18.25 831.6 114 235.2 42
3 2 X X X X 17.75 56.67 Abut. 2 69.17 18.75 2.25 761.2 117 348.4 143
4 2 X X X X 17.58 80.83 Abut. 2 45.01 6 2.25 1240 246 690 357
5 2 X X X X 18.92 80.83 Abut. 2 45.01 11.5 18.25 1150.4 206 556.8 205
6 2 X X X X 17.58 80.83 Abut. 2 45.01 18.75 2.25 818.8 89 307.2 87
7 2 X X X X 16.74 43.97 Pier 1 43.97 18.125 2 312 79 741 40
8 2 X X X X 18.07 43.97 Pier 1 43.97 12 18 707 113 252 104
9 2 X X X X 16.74 43.97 Pier 1 43.97 18.125 2 834 40 280 39
10 2 X X X X 16.69 59.84 Pier 1 59.84 5.875 2 656 36 264 65
11 2 X X X X 18.02 59.84 Pier 1 59.84 12 18 674 47 240 47
12 2 X X X X 16.69 59.84 Pier 1 59.84 18.125 2 772 148 412 177
W BFT BFB TFBFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Typical
Ultrasonic
Thickness
2A X X X 16.74 43.97 Pier 1 43.97 18.125 2
Most
Corrosive
Ultrasonic
Thickness
2B X X X 17.58 80.83 Abut. 2 45.01 6 2.25
1st FB - fascia beam facing traffic first; 2nd beam - 2nd beam in the traffic direction
WL - Web near bottom flange; W - Web; BFT - Bottom flange top side; BFB - Bottom flange bottom side; TFB - Top flange bottom side
Element Identifier Examples: 1A - Fascia beam, Span 1; 2B - Second beam (interior beam adjacent to exterior beam) Span 2
Dry Film Thickness
Tape Samples, Rust Samples, Ultrasonic
Component
Structural Component
Test
Area
ID
Orientation Above
Evaluating
Structural ComponentOrientation Above
Element
Identifier
Component
Vertical distance
from roadway/
ground (ft)
Beam
2.213
1.961
LocationCoordinates
Horizontal distance
Horizontal distance
Thickness (in.)
Location
Vertical distance
from roadway/
ground (ft)
Coordinates
186
Bridge: CT 5796Date: 5/9/19
Span #1
st FB
(K)
2nd
B
(L)WL BFT
Facing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designation
X (ft)
[from Pier 1]Y (in.) Z (in.)
With plastic
shim (261
microns thick)
(microns)
Standard
Deviation
Without plastic
shim (microns)
Standard
Deviation
Example 1 X X X X 10 10 Left abutment 10 0.1 0.1 100 30 100 30
1 1 X X X X 15.21 27.85 Left abut. 27.85 5.81 1.88 1131 271 796 243
2 1 X X X X 16.83 27.85 Left abut. 27.85 11.75 21.25 665 28.7 183.2 67.7
3 1 X X X X 15.21 27.85 Left abut. 27.85 18.25 1.88 826 86.7 342.4 115.2
4 1 X X X X 15.73 45.98 Left abut. 45.98 5.81 1.88 935.2 217.7 654.8 491.5
5 1 X X X X 17.33 45.98 Left abut. 45.98 11.75 21.25 554.4 29.3 380 56.9
6 1 X X X X 15.73 45.98 Left abut. 45.98 18.25 1.88 853.2 30.7 594.8 262.1
7 1 X X X X 16.21 25.16 Left abut. 25.16 18.00 2.13 840.4 106 356.4 128
8 1 X X X X 18.05 25.16 Left abut. 25.16 11.75 21.25 478.8 41.3 124 34
9 1 X X X X 16.21 25.16 Left abut. 25.16 5.75 2.13 827.2 54 294.8 129
10 1 X X X X 16.85 46.96 Left abut. 46.96 18.50 2.13 1178.4 156.9 786.8 337
11 1 X X X X 18.72 46.96 Left abut. 46.96 11.75 21.25 702.8 59.1 571.2 68.1
12 1 X X X X 16.86 46.96 Left abut. 46.96 5.75 2.13 1235.2 244.8 703.2 327
W BFT BFB TFBFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Typical
Ultrasonic
Thickness
1K X X X 15.73 45.98 Left abut. 45.98 11.75 21.25
Most
Corrosive
Ultrasonic
Thickness
1L X X X 16.85 46.96 Left abut. 46.96 18.50 2.13
LocationCoordinates
Horizontal distance
Horizontal distance
Thickness (in.)
Location
Vertical distance
from roadway/
ground (ft)
CoordinatesComponent
Vertical distance
from roadway/
ground (ft)
Beam
2.114
1.947
1st FB - fascia beam facing traffic first; 2nd beam - 2nd beam in the traffic direction
WL - Web near bottom flange; W - Web; BFT - Bottom flange top side; BFB - Bottom flange bottom side; TFB - Top flange bottom side
Element Identifier Examples: 1A - Fascia beam, Span 1; 2B - Second beam (interior beam adjacent to exterior beam) Span 2
Dry Film Thickness
Tape Samples, Rust Samples, Ultrasonic
Component
Structural Component
Test
Area
ID
Orientation Above
Evaluating
Structural ComponentOrientation Above
Element
Identifier
187
Bridge: IA 004111Date: 5/14/19
Span #1
st FB
A
2nd
B
BWL BFT
Facing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designation
(facing traffic)
X (ft) Y (in.) Z (in.)
Average of 9
Readings
(mills)
Standard
Deviation
Example 1 X X X X 10 10 Left abutment 10 0.1 0.1 100 30
1 2 X X X X 21 68closest face of
pier139 3 1.25 39.41 18.19
2 2 X X X X 21 68closest face of
pier139 6 18 12.31 3.17
3 2 X X X X 21 68closest face of
pier139 10 1.25 49.93 18.64
4 2 X X X X 21 67closest face of
pier138 3 1.25 13.19 5.07
5 2 X X X X 21 67closest face of
pier138 6 18 13.26 4.7
6 2 X X X X 21 67closest face of
pier138 10 1.25 45.84 18.73
7 2 X X X X 21 80closest face of
pier151 3 1.25 51.04 19.06
8 2 X X X X 21 80closest face of
pier151 6 18 16.24 5.75
9 2 X X X X 21 80closest face of
pier151 10 1.25 49.9 23.83
10 2 X X X X 21 77closest face of
pier148 3 1.25 8.71 1.71
11 2 X X X X 21 77closest face of
pier148 6 18 10.89 3.72
12 2 X X X X 21 77closest face of
pier148 10 1.25 51.9 16.14
W BFT BFB TFBFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Typical
Ultrasonic
Thickness
2A
(sample
6)
X X X 21 67closest face of
pier138 10 1.25 1.223,1.228,1.223
Most
Corrosive
Ultrasonic
Thickness
2A
(sample
4)
X X X 21 67closest face of
pier138 3 1.25 1.223, 1.225, 1.227,1.223,1.224
1st FB - fascia beam facing traffic first; 2nd beam - 2nd beam in the traffic direction
WL - Web near bottom flange; W - Web; BFT - Bottom flange top side; BFB - Bottom flange bottom side; TFB - Top flange bottom side
Element Identifier Examples: 1A - Fascia beam, Span 1; 2B - Second beam (interior beam adjacent to exterior beam) Span 2
Component
Structural Component
Test
Area
ID
Orientation Above
Evaluating
Structural ComponentOrientation Above
Location
Vertical distance
from roadway/
ground (ft)
1.225
1.224
Dry Film Thickness
Tape Samples, Rust Samples, Ultrasonic
Thickness (in.)
Coordinates
Element
Identifier
Component
Vertical distance
from roadway/
ground (ft)
Beam
LocationCoordinates
Horizontal distance
Horizontal distance
188
Bridge: IA 041331Date: 5/14/19
Span #1
st FB
A
2nd
B
BWL BFT
Facing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designation
(facing traffic)
X (ft) Y (in.) Z (in.)
Average of 9
Readings
(mills)
Standard
Deviation
Example 1 X X X X 10 10 Left abutment 10 0.1 0.1 100 30
1 2 X X X X 17 85 East abutment 208 4 1.5 72.56 7.46
2 2 X X X X 19 85 East abutment 208 8 23.5 19.96 5.6
3 2 X X X X 17 85 East abutment 208 12 1.5 66.4 18.75
4 2 X X X X 17 86 East abutment 207 4 1.5 7.21 2.1
5 2 X X X X 19 86 East abutment 207 8 23.5 11.27 1.71
6 2 X X X X 17 86 East abutment 207 12 1.5 70.24 6.97
7 2 X X X X 17 95 East abutment 198 4 1.5 7.46 1.6
8 2 X X X X 19 95 East abutment 198 8 23.5 9.82 1.33
9 2 X X X X 17 95 East abutment 198 12 1.5 53.5 21.71
10 2 X X X X 17 95 East abutment 198 4 1.5 65.49 9.02
11 2 X X X X 19 95 East abutment 198 8 23.5 29.49 7.6
12 2 X X X X 17 95 East abutment 198 12 1.5 71.36 9.52
W BFT BFB TFBFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Typical
Ultrasonic
Thickness
2A
(sample
4)
X X X X 17 86 East abutment 207 4 1.5
Most
Corrosive
Ultrasonic
Thickness
2A
(sample
6)
X X X X 17 86 East abutment 207 12 1.5
1st FB - fascia beam facing traffic first; 2nd beam - 2nd beam in the traffic direction
WL - Web near bottom flange; W - Web; BFT - Bottom flange top side; BFB - Bottom flange bottom side; TFB - Top flange bottom side
Element Identifier Examples: 1A - Fascia beam, Span 1; 2B - Second beam (interior beam adjacent to exterior beam) Span 2
Component
Structural Component
Test
Area
ID
Orientation Above
Evaluating
Structural ComponentOrientation Above
Location
Vertical distance
from roadway/
ground (ft)
1.458
1.444
Dry Film Thickness
Tape Samples, Rust Samples, Ultrasonic
Thickness (in.)
Coordinates
Element
Identifier
Component
Vertical distance
from roadway/
ground (ft)
Beam
LocationCoordinates
Horizontal distance
Horizontal distance
189
Bridge: IA 042711Date: 5/14/2019
Span #1
st FB
G
2nd
B
FWL BFT
Facing
TrafficBackside Right Lane Shoulder Distance (ft)
Nearest
joint designation
(facing traffic)
X (ft) Y (in.) Z (in.)
Average of 9
Readings
(mills)
Standard
Deviation
Example 1 X X X X 10 10 Left abutment 10 0.1 0.1 100 30
1 2 X X X X 25 56Bearing of Pier
1171 12 1 50.49 17.05
2 2 X X X X 25 56Bearing of Pier
1171 8 17 9.37 2.16
3 2 X X X X 25 56Bearing of Pier
1171 4 1 60.6 11.45
4 2 X X X X 25 56Bearing of Pier
1171 12 1 8.03 1.36
5 2 X X X X 25 56Bearing of Pier
1171 8 17 8.8 2.88
6 2 X X X X 25 56Bearing of Pier
1171 4 1 15.83 10.14
7 2 X X X X 26 47Bearing of Pier
1162 12 1 9.06 2.89
8 2 X X X X 26 47Bearing of Pier
1162 8 17 6.81 3.13
9 2 X X X X 26 47Bearing of Pier
1162 4 1 51.28 13.68
10 2 X X X X 25 48Bearing of Pier
1163 12 1 52.49 17.29
11 2 X X X X 25 48Bearing of Pier
1163 8 17 40.47 5.8
12 2 X X X X 25 48Bearing of Pier
1163 4 1 53.83 12.48
W BFT BFB TFBFacing
TrafficBackside Right Lane Shoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Typical
Ultrasonic
Thickness
2G
(sample
5)
X X X 25 56Bearing of Pier
18 17
Most
Corrosive
Ultrasonic
Thickness
2G
(sample
6)
X X X 25 56Bearing of Pier
14 1
note: the unit for dry film here is not micro, it should be mills
1st FB - fascia beam facing traffic first; 2nd beam - 2nd beam in the traffic direction
WL - Web near bottom flange; W - Web; BFT - Bottom flange top side; BFB - Bottom flange bottom side; TFB - Top flange bottom side
Element Identifier Examples: 1A - Fascia beam, Span 1; 2B - Second beam (interior beam adjacent to exterior beam) Span 2
Component
Structural Component
Test
Area
ID
Orientation Above
Evaluating
Structural ComponentOrientation Above
Location
Vertical distance
from roadway/
ground (ft)
0.96
0.962
Dry Film Thickness
Tape Samples, Rust Samples, Ultrasonic
Thickness (in.)
Coordinates
Element
Identifier
Component
Vertical distance
from roadway/
ground (ft)
Beam
LocationCoordinates
Horizontal distance
Horizontal distance
190
Bridge: MN 04019Date: 6/3/2019
Span # 1st
FB 2nd
B WL BFTFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Average of 9
Readings
(mills)
Standard
Deviation
1 2 X X X X 17 37from face pier
1111 4 1.25 38.49 11.25
2 2 X X X X 19 37from face pier
1111 8 22 9.68 2.34
2A 2 X X X X 20 37from face pier
1111 8 28 5.34 2.22
3 2 X X X X 18 35from face pier
1109 12 1 45.73 7.83
4 2 X X X X 19 35from face pier
1109 8 22 18.59 7.96
5 2 X X X X 18 35from face pier
1109 4 1 18.92 5.17
6A 2 X X X X 17 50from face pier
1124 4 1 29.99 25.16
6 2 X X X X 17 53from face pier
1127 4 1 46.18 25.57
7 2 X X X X 22 53from face pier
1127 8 44 10.4 1.38
8 2 X X X X 18 51from face pier
1125 12 1 32.97 10.13
9 2 X X X X 18 51from face pier
1125 8 22 11.32 3.32
10 2 X X X X 18 51from face pier
1125 4 22 30.5 8.91
W BFT BFB TFBFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Typical
Ultrasonic
Thickness2A X X X 17 50
from face pier
1124 4 1
Most
Corrosive
Ultrasonic
Thickness
2B X X X 18 35from face pier
1109 12 1
Vertical distance
from roadway/
ground (ft)
1.110
1.123
Dry Film Thickness
Tape Samples, Rust Samples, Ultrasonic
Thickness (in.)
Coordinates
Element
Identifier
Component
Vertical distance
from roadway/
ground (ft)
Beam
LocationCoordinates
Horizontal distance
Horizontal distance
1st FB - fascia beam facing traffic first; 2nd beam - 2nd beam in the traffic direction
WL - Web near bottom flange; W - Web; BFT - Bottom flange top side; BFB - Bottom flange bottom side; TFB - Top flange bottom side
Element Identifier Examples: 1A - Fascia beam, Span 1; 2B - Second beam (interior beam adjacent to exterior beam) Span 2
Component
Structural Component
Test
Area
ID
Orientation Above
Evaluating
Structural ComponentOrientation Above
Location
191
Bridge: MN 19811Date: 6/5/2019
Span # 1st
FB 2nd
B WL BFTFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Average of 9
Readings
(microns)
Standard
Deviation
1 2 X X X X 16 26 Pier 1, bearing 84.5 12 1 16.21 7.54
2 2 X X X X 19 26 Pier 1, bearing 84.5 8 27 9.61 2.84
3 2 X X X X 16 26 Pier 1, bearing 84.5 4 1 51.54 18.18
4 2 X X X X 17 26 Pier 1, bearing 84.5 12 1 56.1 13.55
5 2 X X X X 19 26 Pier 1, bearing 84.5 8 23 24.87 6.56
6 2 X X X X 17 26 Pier 1, bearing 84.5 4 1 33.98 19.17
7 2 X X X X 16 12 Pier 1, bearing 70.5 12 1 36.67 25.81
8 2 X X X X 18 12 Pier 1, bearing 70.5 8 23 16.76 5.44
9 2 X X X X 16 12 Pier 1, bearing 70.5 4 1 58.57 21.57
10 2 X X X X 16 10 Pier 1, bearing 68.5 12 2 13.51 8.44*
11 2 X X X X 18 10 Pier 1, bearing 68.5 8 24 9.07 1.59*
12 2 X X X X 16 10 Pier 1, bearing 68.5 4 2 42.06 17.53
W BFT BFB TFBFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Typical
Ultrasonic
Thickness2B X X X 17 26 Pier 1, bearing 84.5 12 1
Most
Corrosive
Ultrasonic
Thickness
2B X X X 16 12 Pier 1, bearing 70.5 12 1
Tape Samples, Rust Samples, Ultrasonic
Thickness (in.)
Coordinates
Element
Identifier
Component
Vertical distance
from roadway/
ground (ft)
Beam
LocationCoordinates
Horizontal distance
Horizontal distance
Structural Component
Test
Area
ID
Orientation Above
Vertical distance
from roadway/
ground (ft)
1st FB - fascia beam facing traffic first; 2nd beam - 2nd beam in the traffic direction
WL - Web near bottom flange; W - Web; BFT - Bottom flange top side; BFB - Bottom flange bottom side; TFB - Top flange bottom side
Element Identifier Examples: 1A - Fascia beam, Span 1; 2B - Second beam (interior beam adjacent to exterior beam) Span 2
Component
Evaluating
Structural ComponentOrientation Above
Location
0.979
0.992
Dry Film Thickness
192
Bridge: MN 62861Date: 6/4/19
Span # 1st
FB 2nd
B WL BFTFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint
designation
X (ft) Y (in.) Z (in.)
Average of 9
Readings
(microns)
Standard
Deviation
1 1 X X X X 18 36 S. Abut. 36 15 2 NA NA
2 1 X X X X 20 36 S. Abut. 36 10 21 43.13 18.07
3 1 X X X X 18 36 S. Abut. 36 5 2 72.53 14.10
4 1 X X X X 18 36 S. Abut. 36 15 2 77.4 0
5 1 X X X X 20 36 S. Abut. 36 10 19 50.44 23.11
6 1 X X X X 18 36 S. Abut. 36 5 2 73.71 5.91
7 1 X X X X 19 24 S. Abut. 24 15 2 78.8 0
8 1 X X X X 20 24 S. Abut. 24 10 18 54.01 19.66
9 1 X X X X 19 24 S. Abut. 24 5 2 65.73 12.87
10 1 X X X X 19 24 S. Abut. 24 15 2 72.28 4.19
11 1 X X X X 20 24 S. Abut. 24 10 22** 66.24 12.6
12 1 X X X X 19 24 S. Abut. 24 5 2 71.07 14.19
W BFT BFB TFBFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint
designation
X (ft) Y (in.) Z (in.)
Typical
Ultrasonic
Thickness1B X X X 18 36 S. Abut. 36 15 2
Most
Corrosive
Ultrasonic
Thickness
1B X X X 19 24 S. Abut. 24 15 2
1st FB - fascia beam facing traffic first; 2nd beam - 2nd beam in the traffic direction
WL - Web near bottom flange; W - Web; BFT - Bottom flange top side; BFB - Bottom flange bottom side; TFB - Top flange bottom side
Element Identifier Examples: 1A - Fascia beam, Span 1; 2B - Second beam (interior beam adjacent to exterior beam) Span 2
Component
Structural Component
Test
Area
ID
Orientation Above
Evaluating
Structural ComponentOrientation Above
Location
Vertical
distance from
roadway/
ground (ft)
1.320
1.318
Dry Film Thickness
Tape Samples, Rust Samples, Ultrasonic
Thickness (in.)
Coordinates
Element
Identifier
ComponentVertical
distance from
roadway/
ground (ft)
Beam
LocationCoordinates
Horizontal distance
Horizontal distance
193
Bridge: NC 190083Date: 9/16/19
Span #1
st FB
(A)
2nd
B
(B)WL BFT
Facing
TrafficBackside
1/2
Point of
Span
1/4
Point of
Span
Distance (ft)Nearest
joint designationX (ft) Y (in.) Z (in.)
Average of 9
Readings
(microns)
Standard
Deviation
Example 1 X X X X 10 10 Left abutment 10 0.1 0.1 100 30
1 1 X X X X 6.17 9.25 Left abutment 9.25 4.88 9 135 35.7
2 1 X X X X 5.5 9.25 Left abutment 9.25 2.25 0.63 176.4 48.7
3 1 X X X X 5.5 9.25 Left abutment 9.25 7.75 0.63 202.4 67.8
4 1 X X X X 6.42 9.42 Left abutment 9.42 4.88 9.25 123.1 15.4
5 1 X X X X 5.67 9.42 Left abutment 9.42 2.25 0.63 324.2 119.2
6 1 X X X X 5.67 9.42 Left abutment 9.42 7.75 0.63 232.7 72.7
7 1 X X X X 13.25 18.17 Left abutment 18.17 4.88 9 117.3 34
8 1 X X X X 12.5 18.17 Left abutment 18.17 2.25 0.63 195.6 54.4
9 1 X X X X 12.5 18.17 Left abutment 18.17 7.75 0.63 224.7 63.2
10 1 X X X X 13.25 19.17 Left abutment 19.17 4.88 9.63 185.1 24.4
11 1 X X X X 12.5 19.17 Left abutment 19.17 2.25 0.63 312.9 115.6
12 1 X X X X 12.5 19.17 Left abutment 19.17 7.75 0.63 228.2 112.9
W BFT BFB TFBFacing
TrafficBackside
1/2
Point of
Span
1/4
Point of
Span
Distance (ft)Nearest
joint designationX (ft) Y (in.) Z (in.)
Typical
Ultrasonic
Thickness
1A X X X 12.5 18.17 Left abutment 18.17 2.25 0.63
Most
Corrosive
Ultrasonic
Thickness
1B X X X 12.5 19.17 Left abutment 19.17 2.25 0.63
1st FB - fascia beam facing traffic first; 2nd beam - 2nd beam in the traffic direction
WL - Web near bottom flange; W - Web; BFT - Bottom flange top side; BFB - Bottom flange bottom side; TFB - Top flange bottom side
Element Identifier Examples: 1A - Fascia beam, Span 1; 2B - Second beam (interior beam adjacent to exterior beam) Span 2
Dry Film Thickness
Tape Samples, Rust Samples, Ultrasonic
Component
Structural Component
Test
Area
ID
Orientation Above (Rail)
Evaluating
Structural ComponentOrientation Above (Rail)
0.638
Element
Identifier
Component
Vertical distance
from roadway/
ground (ft)
Beam
0.639
LocationCoordinates
Horizontal distance
Horizontal distance
Thickness (in.)
Location
Vertical distance
from roadway/
ground (ft)
Coordinates
194
Bridge: NC 1290057Date: 9/18/19
Span #1
st FB
(D)
2nd
B
(C)WL BFT
Facing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Average of 9
Readings
(microns)
Standard
Deviation
Example 1 X X X X 10 10 Left abutment 10 0.1 0.1 100 30
1 2 X X X X 19.46 13.9First Pier from
Origin73.23 10.75 0.75 180.4 43.4
2 2 X X X X 20.76 13.9First Pier from
Origin73.23 7.38 15.38 121.1 27.8
3 2 X X X X 19.46 13.9First Pier from
Origin73.23 3.5 0.75 358.7 149.7
4 2 X X X X 18.96 27.52First Pier from
Origin86.85 10.75 1.38 138.7 40.6
5 2 X X X X 20.38 27.52First Pier from
Origin86.85 7.38 16 125.3 30.3
6 2 X X X X 18.96 27.52First Pier from
Origin86.85 3.5 1.38 273.1 75.7
7 2 X X X X 19.33 11.67First Pier from
Origin71 10.63 0.75 462 78.3
8 2 X X X X 20.58 11.67First Pier from
Origin71 7.38 15.75 166 76.2
9 2 X X X X 19.33 11.67First Pier from
Origin71 3.5 0.75 519.1 359.1
10 2 X X X X 19.92 26.08First Pier from
Origin85.42 10.88 1.38 617.6 181.7
11 2 X X X X 21.17 26.08First Pier from
Origin85.42 7.38 16.38 250.9 61
12 2 X X X X 19.92 26.08First Pier from
Origin85.42 3.25 1.38 399.1 93.4
W BFT BFB TFBFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Typical
Ultrasonic
Thickness
2D X X X 19.46 13.9First Pier from
Origin73.23 10.75 0.75
Most
Corrosive
Ultrasonic
Thickness
2C X X X 19.92 26.08First Pier from
Origin85.42 10.88 1.38
1st FB - fascia beam facing traffic first; 2nd beam - 2nd beam in the traffic direction
WL - Web near bottom flange; W - Web; BFT - Bottom flange top side; BFB - Bottom flange bottom side; TFB - Top flange bottom side
Element Identifier Examples: 1A - Fascia beam, Span 1; 2B - Second beam (interior beam adjacent to exterior beam) Span 2
Dry Film Thickness
Tape Samples, Rust Samples, Ultrasonic
Component
Structural Component
Test
Area
ID
Orientation Above
Evaluating
Structural ComponentOrientation Above
1.353
Element
Identifier
Component
Vertical distance
from roadway/
ground (ft)
Beam
0.719
LocationCoordinates
Horizontal distance
Horizontal distance
Thickness (in.)
Location
Vertical distance
from roadway/
ground (ft)
Coordinates
195
Bridge: NC 1290058Date: 9/17/19
Span #1
st FB
(A)
2nd
B
(B)WL BFT
Facing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Average of 9
Readings
(microns)
Standard
Deviation
Example 1 X X X X 10 10 Left abutment 10 0.1 0.1 100 30
1 2 X X X X 16.67 6.83First pier from
right131.92 4 0.88 174.9 33.8
2 2 X X X X 18.58 6.83First pier from
right131.92 7.75 17.88 163.8 44.9
3 2 X X X X 16.67 6.83First pier from
right131.92 12.13 0.88 374 111.5
4 2 X X X X 16.67 7.67First pier from
right131.08 4 0.88 368.9 79.4
5 2 X X X X 18.58 7.67First pier from
right131.08 7.75 17.88 173.8 49.7
6 2 X X X X 16.67 7.67First pier from
right131.08 12.13 0.88 371.3 85.1
7 2 X X X X 17.11 22.25First pier from
right116.5 3.88 0.88 152.7 49.1
8 2 X X X X 18.53 22.25First pier from
right116.5 7.75 17.88 123.6 33.4
9 2 X X X X 17.11 22.25First pier from
right116.5 12.13 0.88 810 260.1
10 2 X X X X 17.24 21.17First pier from
right117.58 3.88 0.88 490 83.5
11 2 X X X X 18.57 21.17First pier from
right117.58 7.75 17.88 177.8 23.7
12 2 X X X X 17.24 21.17First pier from
right117.58 12.13 0.88 746.7 192.6
W BFT BFB TFBFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Typical
Ultrasonic
Thickness2A X X X 17.11 22.25
First pier from
right116.5 3.88 0.88
Most
Corrosive
Ultrasonic
Thickness
2B X X X 17.24 21.17First pier from
right117.58 12.13 0.88
LocationCoordinates
Horizontal distance
Horizontal distance
Thickness (in.)
Location
Vertical distance
from roadway/
ground (ft)
Coordinates
Element
Identifier
Component
Vertical distance
from roadway/
ground (ft)
Beam
0.86
1st FB - fascia beam facing traffic first; 2nd beam - 2nd beam in the traffic direction
WL - Web near bottom flange; W - Web; BFT - Bottom flange top side; BFB - Bottom flange bottom side; TFB - Top flange bottom side
Element Identifier Examples: 1A - Fascia beam, Span 1; 2B - Second beam (interior beam adjacent to exterior beam) Span 2
Dry Film Thickness
Tape Samples, Rust Samples, Ultrasonic
Component
Structural Component
Test
Area
ID
Orientation Above
Evaluating
Structural ComponentOrientation Above
0.86
196
Bridge: NH 017201120011300Date: 7/9/19
Span #1
st FB
A
2nd
B
BWL BFT
Facing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designation
(facing traffic)
X (ft) Y (in.) Z (in.)
Average of 9
Readings
(microns)
Standard
Deviation
Example 1 X X X X 10 10 Left abutment 10 0.1 0.1 100 30
1 1 X X X X 15.47 26.19Right
abutment41.96 2.5 0.875 362.7 94.5
2 1 X X X X 16.51 26.19Right
abutment41.96 5.75 11.625 257.8 85.7
3 1 X X X X 15.47 26.19Right
abutment41.96 8.75 0.875 303.1 51.1
4 1 X X X X 15.91 15.41Right
abutment52.78 3 0.875 303.8 125.4
5 1 X X X X 16.96 15.41Right
abutment52.78 5.75 11.125 90.7 22.8
6 1 X X X X 15.91 15.41Right
abutment52.78 8.75 0.875 302.7 86
7 1 X X X X 14.85 25.46Right
abutment42.04 2.5 0.75 263.1 80.2
8 1 X X X X 15.81 25.46Right
abutment42.04 5.75 12.25 101.1 22.7
9 1 X X X X 14.85 25.46Right
abutment42.04 9.5 0.75 394.4 122.2
10 1 X X X X 15.4 14.85Right
abutment52.69 2.5 0.75 220.4 114.5
11 1 X X X X 16.42 14.85Right
abutment52.69 5.75 12.25 92.2 26.9
12 1 X X X X 15.4 14.85Right
abutment52.69 9.5 0.75 303.1 95.6
W BFT BFB TFBFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Typical
Ultrasonic
Thickness1A X X X 15.4 14.85
Right
abutment52.69 2.5 0.75
Most
Corrosive
Ultrasonic
Thickness
1B X X X 15.47 26.19Right
abutment41.96 8.75 0.875
1st FB - fascia beam facing traffic first; 2nd beam - 2nd beam in the traffic direction
WL - Web near bottom flange; W - Web; BFT - Bottom flange top side; BFB - Bottom flange bottom side; TFB - Top flange bottom side
Element Identifier Examples: 1A - Fascia beam, Span 1; 2B - Second beam (interior beam adjacent to exterior beam) Span 2
Component
Structural Component
Test
Area
ID
Orientation Above
Evaluating
Structural ComponentOrientation Above
Location
Vertical distance
from roadway/
ground (ft)
0.772
0.785
Dry Film Thickness
Tape Samples, Rust Samples, Ultrasonic
Thickness (in.)
Coordinates
Element
Identifier
Component
Vertical distance
from roadway/
ground (ft)
Beam
LocationCoordinates
Horizontal distance
Horizontal distance
197
Bridge: NH 1110112007900Date: 7/11/19
Span #1
st FB
A
2nd
B
BWL BFT
Facing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designation
(facing traffic)
X (ft) Y (in.) Z (in.)
Average of 9
Readings
(microns)
Standard
Deviation
Example 1 X X X X 10 10 Left abutment 10 0.1 0.1 100 30
1 2 X X X X 18.42 60.23Right
abutment102.21 5 1 179.8 53.2
2 2 X X X X 20.5 60.23Right
abutment102.21 9.75 26 224.4 59.6
3 2 X X X X 18.42 60.23Right
abutment102.21 15.5 1 1861.8 141.6
4 2 X X X X 18.02 70.71Right
abutment91.07 15.5 1 1737.1 203.5
5 2 X X X X 18.02 70.71Right
abutment91.07 5 1 194 49.5
6 2 X X X X 20.1 70.71Right
abutment91.07 9.75 26 208 42
7 2 X X X X 18.08 59.35Right
abutment101.9 5 1.125 1980 180
8 2 X X X X 20.25 59.35Right
abutment101.9 9.875 27.125 492.4 236.6
9 2 X X X X 18.08 59.35Right
abutment101.9 15.25 1.125 >2000 -
10 2 X X X X 17.96 69.5Right
abutment91.9 5 1.125 >2000 -
11 2 X X X X 20.13 69.5Right
abutment91.9 9.875 1.125 339.1 142.3
12 2 X X X X 20.96 69.5Right
abutment91.9 15.25 1.125 >2000 -
W BFT BFB TFBFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Typical
Ultrasonic
Thickness
2A X X X 18.02 70.71Right
abutment91.07 5 1
Most
Corrosive
Ultrasonic
Thickness
2B X X X 17.96 69.5Right
abutment91.9 5 1.125
0.975
0.939
Dry Film Thickness
Tape Samples, Rust Samples, Ultrasonic
Thickness (in.)
Coordinates
Element
Identifier
Component
Vertical distance
from roadway/
ground (ft)
Beam
LocationCoordinates
Horizontal distance
Horizontal distance
1st FB - fascia beam facing traffic first; 2nd beam - 2nd beam in the traffic direction
WL - Web near bottom flange; W - Web; BFT - Bottom flange top side; BFB - Bottom flange bottom side; TFB - Top flange bottom side
Element Identifier Examples: 1A - Fascia beam, Span 1; 2B - Second beam (interior beam adjacent to exterior beam) Span 2
Component
Structural Component
Test
Area
ID
Orientation Above
Evaluating
Structural ComponentOrientation Above
Location
Vertical distance
from roadway/
ground (ft)
198
Bridge: NH 1110112007900
Date: 7/11/19
W BFT BFB TFBFacing
TrafficBackside
Right
LaneShoulder
Distance
(ft)
Nearest
joint
designation
X (ft) Y (in.) Z (in.)
Depth (in.)
Severity
(Approximate
Surface Area
in.2)
2B X X X 18.08 59.35Right
abutment101.9 15.25 1.125 0.1
2B X X X 18.08 59.35Right
abutment101.9 15.25 1.125 0.11
Thickness (in.)
Severity
(Approximate
Surface Area
in.2)
Corrosion, Pitting, & Section Loss
AboveMax Length of
Corroded Area
(in.)
Max Width of
Corroded Area
(in.)
Corrosion
(If Applicable)
Horizontal distance
Section
Loss
(If Applicable)
Evaluating
Pitting
(If Applicable)
Element Identifier Examples: 1A - Fascia beam, Span 1; 2B - Second beam (interior beam adjacent to exterior beam) Span 2
W - Web; BFT - Bottom flange top side; BFB - Bottom flange bottom side; TFB - Top flange bottom side
Element
Identifier
Component Vertical
distance
from
roadway/
ground (ft)
Structural ComponentOrientation
LocationCoordinates
199
Bridge: NH 017701460003700Date: 7/8/19
Span #1
st FB
G
2nd
B
FWL BFT
Facing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designation
(facing traffic)
X (ft) Y (in.) Z (in.)
Average of 9
Readings
(microns)
Standard
Deviation
Example 1 X X X X 10 10 Left abutment 10 0.1 0.1 100 30
1 1 X X X X 20.44 32.72Right
abutment32.72 12.5 1.38 198 41.4
2 1 X X X X 22.44 32.72Right
abutment32.72 9.25 25.38 260.7 73.4
3 1 X X X X 20.45 32.13Right
abutment32.13 4 1.38 946.7 343.5
4 1 X X X X 20.56 32.76Right
abutment32.76 12.5 1.5 1786.4 599.3
5 1 X X X X 22.56 32.76Right
abutment32.76 9.25 25.5 261.6 83.2
6 1 X X X X 20.43 32.04Right
abutment32.04 4.5 1.5 1505.1 615.2
7 1 X X X X 19.71 17.82Right
abutment17.82 13.5 1.5 906.9 674.9
8 1 X X X X 21.83 17.82Right
abutment17.82 9 25.5 206.4 58.4
9 1 X X X X 19.7 17.78Right
abutment17.78 4.38 1.5 575.3 344.1
10 1 X X X X 19.71 17.71Right
abutment17.71 13.5 1.38 153.3 19.8
11 1 X X X X 21.83 17.71Right
abutment17.71 9 25.38 198 44
12 1 X X X X 19.65 17.69Right
abutment17.69 4.5 1.5 447.6 217.7
W BFT BFB TFBFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Typical
Ultrasonic
Thickness
1G X X X 19.71 17.71Right
abutment17.71 13.5 1.38
Most
Corrosive
Ultrasonic
Thickness
1F X X X 20.56 32.76Right
abutment32.76 12.5 1.5
1.339
1.371
Dry Film Thickness
Tape Samples, Rust Samples, Ultrasonic
Thickness (in.)
Coordinates
Element
Identifier
Component
Vertical distance
from roadway/
ground (ft)
Beam
LocationCoordinates
Horizontal distance
Horizontal distance
1st FB - fascia beam facing traffic first; 2nd beam - 2nd beam in the traffic direction
WL - Web near bottom flange; W - Web; BFT - Bottom flange top side; BFB - Bottom flange bottom side; TFB - Top flange bottom side
Element Identifier Examples: 1A - Fascia beam, Span 1; 2B - Second beam (interior beam adjacent to exterior beam) Span 2
Component
Structural Component
Test
Area
ID
Orientation Above
Evaluating
Structural ComponentOrientation Above
Location
Vertical distance
from roadway/
ground (ft)
200
Bridge: NH 017701460003700
Date: 7/8/19
W BFT BFB TFBFacing
TrafficBackside
Right
LaneShoulder
Distance
(ft)
Nearest
joint
designation
X (ft) Y (in.) Z (in.)
Depth (in.)
Severity
(Approximate
Surface Area
in.2)
Thickness (in.)
Severity
(Approximate
Surface Area
in.2)
1F X X X 20.56 32.76Right
abutment32.76 12.5 1.5 0.0625
1F X X X 20.43 32.04Right
abutment32.04 4.5 1.5 0.03125
Corrosion, Pitting, & Section Loss
AboveMax Length of
Corroded Area
(in.)
Max Width of
Corroded Area
(in.)
Corrosion
(If Applicable)
Horizontal distance
Section
Loss
(If Applicable)
Evaluating
Pitting
(If Applicable)
Element Identifier Examples: 1A - Fascia beam, Span 1; 2B - Second beam (interior beam adjacent to exterior beam) Span 2
W - Web; BFT - Bottom flange top side; BFB - Bottom flange bottom side; TFB - Top flange bottom side
Element
Identifier
Component Vertical
distance
from
roadway/
ground (ft)
Structural ComponentOrientation
LocationCoordinates
201
Bridge: OH 7700105
Date: 6/19/2019
Span # 1st FB 2nd B WL BFTFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Average of 9
Readings
(microns)
Standard
Deviation
1 2 X X X X 16 24E. Abut.
Bearing24 3 1 237.6 115.2
2 2 X X X X 16 24E. Abut.
Bearing24 6 12 589.8 433.2
3 2 X X X X 16 24E. Abut.
Bearing24 9 1 1599.8 322.8
4 2 X X X X 15 29E. Abut.
Bearing29 3 1 272.9 62.5
5 2 X X X X 15 29E. Abut.
Bearing29 6 12 563.8 214.1
6 2 X X X X 15 29E. Abut.
Bearing29 9 1 1277.1 315.8
7 2 X X X X 16 24E. Abut.
Bearing24 3 1 1463.8 175.6
8 2 X X X X 16 24E. Abut.
Bearing24 6 12 735.3 288.6
9 2 X X X X 16 24E. Abut.
Bearing24 9 1 1381.1 302.9
10 2 X X X X 16 31E. Abut.
Bearing31 3 1 1403.3 286.9
11 2 X X X X 16 31E. Abut.
Bearing31 6 12 639.8 303
12 2 X X X X 16 31E. Abut.
Bearing31 9 1 1605.8 443.2
W BFT BFB TFBFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Typical
Ultrasonic
Thickness
2A X X X 16 24E. Abut.
Bearing24 3 1
Most
Corrosive
Ultrasonic
Thickness
2B X X X 16 24E. Abut.
Bearing24 9 1
1st FB - fascia beam facing traffic first; 2nd beam - 2nd beam in the traffic direction
WL - Web near bottom flange; W - Web; BFT - Bottom flange top side; BFB - Bottom flange bottom side; TFB - Top flange bottom side
Element Identifier Examples: 1A - Fascia beam, Span 1; 2B - Second beam (interior beam adjacent to exterior beam) Span 2
Component
Structural Component
Test
Area
ID
Orientation Above
Evaluating
Structural ComponentOrientation Above
Location
Vertical distance
from roadway/
ground (ft)
0.871
0.902
Dry Film Thickness
Tape Samples, Rust Samples, Ultrasonic
Thickness (in.)
Coordinates
Element
Identifier
Component
Vertical distance
from roadway/
ground (ft)
Beam
LocationCoordinates
Horizontal distance
Horizontal distance
202
Bridge: OH 7701977Date: 6/18/19
Span # 1st
FB 2nd
B WL BFTFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Average of 9
Readings
(microns)
Standard
Deviation
1 2 X X X X 17 31East Abut.
Bearing31 4 1 452.7 501.8
2 2 X X X X 17 31East Abut.
Bearing31 9 18 421.1 549.9
3 2 X X X X 17 31East Abut.
Bearing31 14 1 940.9 466.5
4 2 X X X X 17 41East Abut.
Bearing41 4 1 330 83.1
5 2 X X X X 17 41East Abut.
Bearing41 9 18 208.2 67.2
6 2 X X X X 17 41East Abut.
Bearing41 14 1 976.4 220.2
7 2 X X X X 18 32East Abut.
Bearing32 4 1 1032.4 320.7
8 2 X X X X 18 32East Abut.
Bearing32 9 18 656.9 622.4
9 2 X X X X 18 32East Abut.
Bearing32 14 1 798.2 372.5
10 2 X X X X 17 42East Abut.
Bearing42 4 1 1373.6 414.2
11 2 X X X X 17 42East Abut.
Bearing42 9 18 348.7 94.2
12 2 X X X X 17 42East Abut.
Bearing42 14 1 1478.9 245.6
W BFT BFB TFBFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Typical
Ultrasonic
Thickness2A X X X 17 41
East Abut.
Bearing41 4 1
Most
Corrosive
Ultrasonic
Thickness
2B X X X 18 32East Abut.
Bearing32 14 1
0.962
1.005
Dry Film Thickness
Tape Samples, Rust Samples, Ultrasonic
Thickness (in.)
Coordinates
Element
Identifier
Component
Vertical distance
from roadway/
ground (ft)
Beam
LocationCoordinates
Horizontal distance
Horizontal distance
1st FB - fascia beam facing traffic first; 2nd beam - 2nd beam in the traffic direction
WL - Web near bottom flange; W - Web; BFT - Bottom flange top side; BFB - Bottom flange bottom side; TFB - Top flange bottom side
Element Identifier Examples: 1A - Fascia beam, Span 1; 2B - Second beam (interior beam adjacent to exterior beam) Span 2
Component
Structural Component
Test
Area
ID
Orientation Above
Evaluating
Structural ComponentOrientation Above
Location
Vertical distance
from roadway/
ground (ft)
203
Bridge: OH 7701993Date: 6/19/19
Span #1
st FB
(D)
2nd
B
(C)WL BFT
Facing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Average of 9
Readings
(microns)
Standard
Deviation
1 2 X X X X 19 15S. Pier 1
Bearing15 9 1 245.6 45
2 2 X X X X 19 15S. Pier 1
Bearing15 6 12 117.1 28
3 2 X X X X 19 15S. Pier 1
Bearing15 3 1 803.8 335.1
4 2 X X X X 18 35S. Pier 1
Bearing35 10 1 333.8 71.8
5 2 X X X X 18 35S. Pier 1
Bearing35 6 12 237.8 73.9
6 2 X X X X 18 35S. Pier 1
Bearing35 3 1 556.4 248.9
7 2 X X X X 19 15S. Pier 1
Bearing15 9 1 706.4 226.3
8 2 X X X X 19 15S. Pier 1
Bearing15 6 12 238.7 67.3
9 2 X X X X 19 15S. Pier 1
Bearing15 3 1 518.4 208.1
10 2 X X X X 18 35S. Pier 1
Bearing35 10 1 480.4 143.3
11 2 X X X X 18 35S. Pier 1
Bearing35 6 12 282.7 66.7
12 2 X X X X 18 35S. Pier 1
Bearing35 3 1 628 239.1
W BFT BFB TFBFacing
TrafficBackside
Right
LaneShoulder Distance (ft)
Nearest
joint designationX (ft) Y (in.) Z (in.)
Typical
Ultrasonic
Thickness2D X X X 18 35
S. Pier 1
Bearing35 10 1
Most
Corrosive
Ultrasonic
Thickness
2C X X X 19 15S. Pier 1
Bearing15 9 1
1st FB - fascia beam facing traffic first; 2nd beam - 2nd beam in the traffic direction
WL - Web near bottom flange; W - Web; BFT - Bottom flange top side; BFB - Bottom flange bottom side; TFB - Top flange bottom side
Element Identifier Examples: 1A - Fascia beam, Span 1; 2B - Second beam (interior beam adjacent to exterior beam) Span 2
Component
Structural Component
Test
Area
ID
Orientation Above
Evaluating
Structural ComponentOrientation Above
Location
Vertical distance
from roadway/
ground (ft)
0.99
0.995
Dry Film Thickness
Tape Samples, Rust Samples, Ultrasonic
Thickness (in.)
Coordinates
Element
Identifier
Component
Vertical distance
from roadway/
ground (ft)
Beam
LocationCoordinates
Horizontal distance
Horizontal distance
204
Appendix D
MATLAB Script for Digital Image Processing of Tape Samples
%MATLAB script for image processing of tape samples
%% Program to determine the particle size distribution of Rust in a Tape Sample
% *** Notes ****
% Reads all pictures in a given folder and outputs the equivalent diameter of
% each individual particle in inches.
% Computes rust percentage using *optimized* graythresh.
% Computes the equivalent diameter of each particle by converting its area.
% Will ignore all particles below provided minimum threshold.
% Prints an rgb example image with green bounding boxes around the
% particles the program has captured (uncomment commands if this is to
% be done)
% Output is saved to excel file called Results.xlsx.
% Excel sheet will contain 1 row per sample. The first column will contain
% the name of the tape file, the second row contains the total rust
% percentage, and the following columns include the rust percentage for
% those % particular sizes. For instance, the column labeled 0.03125
% (1/32) represents the percentage of particles with diameters in the
% range of 0-1/32". The next would represent 1/32"-1/16", 1/16"-1/8"
% and so on.
clearvars
clc; %clears command window
tic;
% ******* CHOOSE THE LOCATION OF DATA DUMP *******
myFolder = 'C:\Users\ruppjt\Desktop\Images';
% ***** SELECT MINIMUM THRESHOLD FOR DIAMETER (in.)(anything lower will be
% removed)
Min_Thresh = 0;
%Throw error message if aforementioned path incorrect
if ~isdir(myFolder)
errorMessage = sprintf('Error: The following folder does not exist:\n%s', myFolder);
uiwait(warndlg(errorMessage));
return;
end
%Reads all text files sequentially
filePattern = fullfile(myFolder, '*.jpg');
%Counts total number of text files in the folder
imgFiles = dir(filePattern);
%Throw error message if data folder is incorrect
if isempty(imgFiles)
errorMessage = sprintf('No text files in folder\n');
uiwait(warndlg(errorMessage));
return; %Stops further execution of Program
end
for k = 1:length(imgFiles)
205
baseFileName = imgFiles(k).name;
fullFileName = fullfile(myFolder, baseFileName);
%Displays name of file being read
fprintf(1, 'Now reading %s\n', fullFileName);
im1=imread(fullFileName); % Reading image
%% Evaluating Rust Density
%Computing threshold for converting original image (tape sample) to binary
% image
gl=graythresh(im1);
% Converting to binary image with *optimised* graythresh value as level
% (Threshold)
bwg=im2bw(im1,(gl+.25)/2);
% Get dimensions of the binary image. It should be same for both images
[A1,B1]=size(bwg);
% Finding the percentage of black (Rust in our case)
l2=find(bwg==0);
bldensity2=length(l2)/(A1*B1);
%% Capturing Individual Particle Areas
bwg=1-bwg; %inverting the binary image to make the background 0 and the rust
particles 1
[bwg_labeled,num]=bwlabel(bwg); %labeling each individual rust particle
example=label2rgb(bwg_labeled); %creating example image in rgb to show distinction
between particles
%finding the area of each particle (in pixels) using regionprops
area_vect=regionprops(bwg_labeled, 'Area');
final_areas=[area_vect(:).Area];
final_areas=sort(final_areas); %sorting for purposes of output
area_sum=sum(final_areas(:)); %used later in calculating percentages
%converting from pixels to inches
conversion_factor=0.438/40000;
final_areas=sqrt(4*(conversion_factor*final_areas)/pi);
%creating a minimum threshold
idx=1;
while idx<=length(final_areas)
if final_areas(idx)<Min_Thresh
final_areas(idx)=[];
else
idx=idx+1;
end
end
% Uncomment these commands for bounding boxes
% %printing green bounding boxes around each particle
% boxes=regionprops(bwg_labeled, 'BoundingBox').';
% final_boxes=[boxes(:).BoundingBox];
% final_boxes=reshape(final_boxes, [4,num]);
% %removing the boxes below the minimum threshold
% ix=1;
% finl_areas=[area_vect(:).Area];
% finl_areas=conversion_factor*finl_areas;
% while ix<=length(finl_areas)
% if finl_areas(ix)<Min_Thresh
% finl_areas(ix)=[];
% final_boxes(:,ix)=[];
% else
206
% ix=ix+1;
% end
% end
% hold on
% imshow(example);
% for indx= 1:length(final_boxes)
% rectangle('Position',final_boxes(:,indx),'EdgeColor','g');
% end
% hold off
%% Creating Histogram Table
%Takes any 1 row vector as an input.
%Produces two vectors, X and Y.
%X is a 1 row vector whose values represent a range of diameters,
% starting from the previous value and ending at the current one. i.e.
% 0.25 means 0.125-0.25.
%Y is a 1 row vector that contains the percentage of the total image
% occupied by all particles in that range of diameters.
X=0;
Y=0;
Am = final_areas;
Y(1)=0;
X_idx=1;
X(1)=1/32;
for q=1:length(Am)
if Am(q)<X(X_idx)
Y(X_idx)=Y(X_idx)+(pi*(Am(q)^2)/(4*conversion_factor));
else
while Am(q)>=X(X_idx)
X_idx=X_idx+1;
X(X_idx)=2*X(X_idx-1);
Y(X_idx)=0;
end
Y(X_idx)=(pi*(Am(q)^2)/(4*conversion_factor));
end
end
Y=100*Y/(A1*B1);
%% Writing output to excel file - Area/Frequency of each individual Particle
[ext,name] = fileparts(baseFileName);
name=str2num(name);
filename=strcat('Results','.xlsx'); %Creating excel file
A = {'Test Area ID', 'Density', '% of Area'}; %Creates Header Row
sheet=1;
xlRangea = 'A1';
xlswrite(filename,A,sheet,xlRangea);
B = X;
xlRangeb = 'C2';
xlswrite(filename,B,sheet,xlRangeb);
C = Y;
cellc=strcat('C', num2str(name+2));
xlRangec = cellc;
xlswrite(filename,C,sheet,xlRangec);
E = sum(Y);
cellc=strcat('B', num2str(name+2));
xlRangec = cellc;
xlswrite(filename,E,sheet,xlRangec);
D = {name};
celld=strcat('A', num2str(name+2));
xlRanged = celld;
xlswrite(filename,D,sheet,xlRanged);
207
end %Ends For Loop
%% Statistical Analysis
xlswrite(filename,{'=average(B3:B58)'},sheet,'B60');
xlswrite(filename,{'=STDEV.P(B3:B58)'},sheet,'B61');
xlswrite(filename,{'=B60/B61'},sheet,'B62');
xlswrite(filename,{'=max(B3:B58)'},sheet,'B63');
xlswrite(filename,{'=min(B3:B58)'},sheet,'B64');
xlswrite(filename,{'=median(B3:B58)'},sheet,'B65');
xlswrite(filename,{'Average'},sheet,'A60');
xlswrite(filename,{'Standard Deviation'},sheet,'A61');
xlswrite(filename,{'Coefficient of variation'},sheet,'A62');
xlswrite(filename,{'Maximum'},sheet,'A63');
xlswrite(filename,{'Minimum'},sheet,'A64');
xlswrite(filename,{'Median'},sheet,'A65');
%% Clearing temporary variables
%bar(X,Y);
%clearvars %Clears all variables
toc;
208
Appendix E
MAINTENANCE SURVEYS
E.1 Original Survey
Dear LTBP State Coordinator:
The University of Delaware’s Center for Innovative Bridge Engineering, in conjunction
with the Rutgers’ Center for Advanced Infrastructure and Transportation, is currently
conducting a research project evaluating the performance of uncoated weathering steel
(UWS) highway bridges in the United States as part of the FHWA Long Term Bridge
Performance Program (LTBPP). This research will ultimately be used to provide
guidance to bridge owners on appropriate uses of UWS. One task of this project is to
gather information on maintenance practices and the use of deicing agents. Your
assistance in providing information related to this task would be greatly appreciated.
We would like to request the following from you:
1. Electronic versions of any manuals, specifications, or procedures for
maintenance of your bridges. This would include information that is applicable
to all of your bridges, as well as any maintenance information that is specific to
UWS.
2. Information/data on bridge washing. Specifically, (1) does your state wash their
bridges, and (2) if so, please provide information on the frequency and
procedure for washing.
3. Information/data on the use of deicing salts and chemicals. Specifically, (1)
does your state use any salts or chemicals for deicing and snow removal, and
(2) if so, please provide information on the type and annual quantities of
materials dispersed. Please provide as much detail as existing data allows, e.g.,
tons-per-lane mile of roadway or average tons per county, versus total amounts,
if possible. Our goal here is to calculate a best estimate of the amount of
deicing agents that are dispersed on to the decks of your UWS bridges. Any
quantitative information that you can provide that would lead to this result is
appreciated.
209
Responses are requested via email to Tripp Shenton ([email protected]) by 1/11/18.
Any questions or comments regarding this request for information or the research project
can be directed to Jennifer McConnell at [email protected] / 302-668-6772. We
sincerely appreciate your participation in this effort.
Sincerely,
Jennifer McConnell
On behalf of Robert Zobel and the LTBPP team
E.2 Follow-Up Survey for Prior Participants
In the follow-up survey, the survey was customized based on the participants previous
responses. The template below indicates the possible questions that were asked, where
question numbers followed with a capital letter indicate that one of these options was
possibly asked.
Dear [State Coordinator],
Thank you for your assistance in completing our survey related to deicing agent use and
washing of weathering steel bridges within your agency.
In analyzing the data received from all agencies on bridge washing, we have developed
categorical responses to organize agencies in different categories. Based on the responses
you previously submitted, we have entered the following information for your agency.
Please review this information and either confirm we have correctly categorized your
agency or let us know of any corrections that should be made.
In terms of deicing agent usage:
1A. We have concluded based on the data you provided that you have an annual use
of [Value] tons of chloride-based solid deicing agents and [Value] gallons of
brine. We know that you also reported other deicing materials that are used by
your agency, however we are only concerned with deicing materials that pose
corrosive issues to weathering steel.
1B. You reported that your agency uses deicing agents, but did not provide quantities.
Can you please provide annual quantities of the following materials:
a. Tons of chloride compounds
b. Gallons of brine containing chloride (in addition to the chloride quantities
reported in Part a, i.e., the same quantity of chloride should only be
reported once)
c. Other (please specify quantity and type(s))
1C. We have compared the deicing agent usage per lane mile in the 12 state agencies
where it was possible for us to do so. The average amount of chloride-containing
solids was 17 tons / lane mile and the average amount of chloride-containing
brine was 65 gal / lane mile. Your agency's average deicing agent use of [Value]
tons of chloride-containing solids/lane mile and [Value] gallons of chloride-
210
containing brine / lane mile represents [Value (%)] and [Value (%)] of these
average values, respectively. The state agencies in this comparator group are CO,
CT, DE, IL, IA, NE, NH, NY, ND, OR, RI, and WI. Could you please either
confirm these values are reasonable from your perspective or provide an updated
estimate? We know that you also reported other deicing materials that are used by
your agency, however we are only concerened with deicing materials that pose
corrosive issues to weathering steel.
2. We have assumed that the quantity of brine is in addition to the quantity of solid
deicing agents. In other words, the chloride compounds used to make the brine are
not otherwise represented in the data. Is this correct?
3. Please provide your best estimate of the number of lane miles to which these
deicing agents are applied.
In terms of washing maintenance practices:
1. You reported that your agency washes bridges. Do you have different washing
practices for uncoated weathering steel bridges and other bridges? (Yes or No)
If you answered “yes” to the previous question, please answer the following questions
based on uncoated weathering steel bridges. If you answered “no” to the previous
question, please answer the following questions based on all bridges:
2. Approximately what percentage of your bridges do you wash? Please choose one
(<10%, 10%-50%, or >50%)
3. How frequently do you wash your bridges? Please choose one (more than once
per year, annually, every two years, less frequently, never)
4. Is there a specific time period in which your uncoated weathering steel bridges are
washed? Please choose one (Spring, none, other [please specify])
5. Do you wash the girders of your bridges? Please choose one (Yes (always),
Mostly (at least half of the time), Rarely (less than half of the time), or No
(never))
Your response to this survey is urgently requested by 9/16/19. Any questions or
comments regarding this request for information or the research project can be directed to
Jennifer McConnell at [email protected] / 302-668-6772. We sincerely appreciate your
participation in this effort.
Appreciatively,
Jennifer McConnell
On behalf of Robert Zobel and the LTBPP team
Jennifer McConnell
Associate Professor
Department of Civil and Environmental Engineering
University of Delaware
211
302-668-6772
E.3 Follow-Up Survey for Agencies with No Prior Response
Deicing Agent Use
1. Does your agency use any salts or chemicals for deicing or snow removal? (Yes
or No)
2. How many tons of chloride containing compounds does your agency use
annually?
3. How many gallons of brine containing chloride does your agency use annually?
(Note: Please report values in addition to any quantities reported in the previous
question. In other words, the same quantity of chloride should only be reported
once.)
4. How many lane miles are treated with these quantities of deicing agents?
5. Do you have more detailed information available regarding your agency's use of
deicing agents? If so, please upload this data with a file name clearly identifying
the name of the agency you represent.
6. Is there any other information related to your agency's use of deicing agents that
you believe would be helpful in our effort to estimate the quantity of chlorides
applied to specific bridges in your agency?
Bridge Washing Practices
1. Approximately what percentage of your UWS bridges does your agency wash?
(None, < 10%, 10-50%, > 50%)
Please answer the following questions considering your agencies practices with
uncoated weathering steel (UWS, i.e., weathering steel that has not been painted or
treated with any other coating system)
2. How frequently do you wash your UWS bridges? (More than once per year,
Annually, Every two years, Less Frequently)
3. Is there a specific time period in which your UWS bridges are washed? (No, Yes
[Spring], Yes [Other])
4. Do your washing practices for UWS bridges include the girders? (Yes [Always],
Mostly [at least half of the time], Rarely [less than half of the time], No [never])
5. Do you have different washing practices for UWS bridges and other bridges? (No
or Other [Please specify…])
Maintenance Manuals
1. Does your agency have a maintenance manual? (Yes or No)
If your agency has a maintenance manual please upload the manual here.
212
Appendix F
SURVEY DATA
Table F.1 Maintenance Manual Responses
Agency
Response
with
Manual
Response
with
Working
on
Manual
Response
with No
Manual
No
Response
Manual
from Other
Work1
Alabama — — X — X
Alaska — — — X —
Arizona X — — — —
Arkansas — X — — X
California X — — — —
Colorado X — — — —
Connecticut X — — — —
Delaware — — X — X
Florida X — — — —
Georgia — — — X X
Hawaii — — — X X
Idaho — — — X —
Illinois — X — — —
Indiana X — — — —
Iowa X — — — —
Kansas — — — X —
Kentucky — — — X —
Louisiana — — — X —
Maine X — — — —
Maryland — — X — X
Massachusetts — — — X —
Michigan — X — — X
Minnesota X — — — —
Mississippi — — — X —
Missouri X — — — —
Montana — — — X X
213
Table F.1 Continued
Agency
Response
with
Manual
Response
with
Working
on
Manual
Response
with No
Manual
No
Response
Manual
from Other
Work1
Nebraska — — X — X
Nevada — — — X X
New Hampshire X — — — —
New Jersey — — — X X
New Mexico X — — — —
New York X — — — —
North Carolina — — — X —
North Dakota X — — — —
Ohio X — — — —
Oklahoma — — — X —
Oregon — X — — —
Pennsylvania X — — — —
Peurto Rico — — — X —
Rhode Island — — X — —
South Carolina — — — X —
South Dakota — — X — X
Tennessee — — — X —
Texas X — — — —
Utah — — — X X
Vermont — — X — —
Virginia X — — — —
Washington X — — — —
Washington, DC — — X — —
West Virginia — — — X —
Wisconsin X — — — —
Wyoming X— — — —
Total 21 4 8 19 13
X = relevant information
— = no relevant information
1 manual obtained from other work, not via the survey (Shenton, 2016)
214
Table F.2 Washing Practices Responses
AgencyWash
(Y/N)1
Percent
(%)Frequency Time Period
Wash
Girders2
Difference
Between
UWS and
Other Bridges
(Y/N)1
Alabama N 0 — — — —
Arizona N 0 — — — —
Arkansas Y <10 Less frequently Spring No N
California N 0 — — — —
Colorado N 0 — — — —
Connecticut N 0 — — — —
Delaware N 0 — — — —
Florida N 0 — — — —
Illinois Y <10 Annually Other (by contract) Rarely N
Indiana Y >50 Annually Spring No N
Iowa Y <10 Less frequently Spring Rarely Y
Maine Y >50 Annually Spring No N
Maryland N 0 — — — —
Michigan Y <10 Annually Spring Rarely N
Minnesota Y >50 Annually Spring Typically N
Missouri Y 10-50 Annually Spring Rarely N
Montana N 0 — — — —
Nebraska Y <10 Annually — Rarely Y
New Hampshire Y 10-50 Every 2 years Spring Rarely N
New Mexico N 0 — — — —
New York Y 10-50 Every 2 years Spring No Y
North Dakota Y 10-50 Annually Spring Rarely N
Ohio Y 10-50 Annually Spring No N
Oregon Y — Every 2 years — — —
Pennsylvania Y 10-50 Less frequently — No Y
Rhode Island Y 10-50 Every 2 years Spring Yes N
South Dakota Y >50 Annually Spring No N
Texas Y — Less frequently — — —
Virginia Y <10 Annually Spring No N
Washington Y <10 Annually Spring Yes Y
Washington, DC Y — Less frequently — — —
Wisconsin Y 10-50 Every 2 years Spring Rarely N
Wyoming N 0 — — — —
2 Yes = always; Typically = at least half of the time; Rarely = less than half of the time; and No = never
1 Y = yes and N = no
— = data not provided
215
Table F.3 Deicing Agent Usage Responses
Agency
Corrosive
Solids1
(tons)
Corrosive
Solids1/Lane
Mile
(tons/lane
mile)
Corrosive
Brines2
(gal.)
Corrosive
Brines2/Lane
Mile
(gal./lane
mile)
Number of
Lane Miles
Deicing Agenst
Applied to
Alabama3 26,260 0.9 357,000 12.2 29,273
Alaska3 6,203 0.5 1,169,000 99.4 11,766
Arizona 19,008 1.4 198,956 14.2 14,000
Arkansas — — — — —
California3 35,000 0.7 1,350,000 26.6 50,679
Colorado 173,243 7.5 11,470,846 498.7 23,000
Connecticut3 221,450 20.4 1,534,050 141.1 10,870
Delaware3 108,000 8.0 2,539,000 188.5 13,472
Florida 0 0.0 0 0.0 —
Georgia3 20,863 0.5 800,000 20.0 39,919
Hawaii — — — — —
Idaho3 116,828 9.5 9,335,189 757.7 12,320
Illinois6 550,230 12.1 1,963,470 43.0 45,617/25,801
Indiana 225,000 7.5 0 0.0 30,000
Iowa 140,000 5.7 28,600,000 1,167.3 24,500
Kansas3 96,000 3.8 3,918,000 154.9 25,300
Kentucky3 241,000 3.8 1,494,800 23.5 63,500
Louisiana — — — — —
Maine 140,000 17.9 550,000 70.5 7,800
Maryland4 210,193 12.2 — — 17,203
Massachusetts3 455,885 29.5 1,772,200 114.8 15,436
Michigan3 619,043 19.3 2,361,691 73.7 32,045
Minnesota 246,500 8.1 4,600,000 151.2 30,426
Mississippi — — — — —
Missouri3 145,000 1.9 3,896,000 50.2 77,570
Montana3 1,858 0.1 10,169,485 406.8 25,000
Nebraska3 104,729 4.5 1,040,104 44.9 23,168
Nevada — — — — —
New Hampshire3 231,257 24.7 386,011 41.2 9,366
New Jersey — — — — —
New Mexico 741 — 0 — —
New York 840,340 22.9 1,104,830 30.1 36,704
North Carolina — — — — —
North Dakota5 26,255 2.6 — 114.0 17,255
216
Table F.3 Continued
Agency
Corrosive
Solids1
(tons)
Corrosive
Solids1/Lane
Mile
(tons/lane
mile)
Corrosive
Brines2
(gal.)
Corrosive
Brines2/Lane
Mile
(gal./lane
mile)
Number of
Lane Miles
Deicing Agenst
Applied to
Ohio 759,826 17.4 10,787,372 247.6 43,570
Oklahoma — — — — —
Oregon 1,108 0.1 264,609 25.4 10,405
Pennsylvania 928,081 10.9 11,682,400 137.6 84,903
Puerto Rico — — — — —
Rhode Island3 154,000 48.4 14,800 4.6 3,185
South Carolina — — — — —
South Dakota 60,016 6.8 1,940,850 219.4 8,847
Tennessee — — — — —
Texas3 22,230 0.1 5,815,454 30.9 188,128
Utah3 260,105 10.6 273,422 11.2 24,500
Vermont3 173,365 26.6 2,853,974 438.3 6,511
Virginia — — — — —
Washington 82,000 2.3 2,364,000 67.5 35,000
Washington, DC — — — — —
West Virginia3 281,342 3.8 1,093,151 14.6 75,000
Wisconsin3 567,696 16.4 6,053,329 174.6 34,678
Wyoming7 222,668 11,793,705 770,000/40,000
7 Wyoming's reported lane miles is believed to be the cumulative number of lane miles that
were treated throughout the year rather than the number of lane miles that Wyoming
maintains given the extremely high value of lane miles for corrosive solids. Because of this,
Wyoming's data was not reported in quantities per lane mile.
— = data not provided
1 corrosive solids include chloride containing chemicals such as, sodium chloride,
magnesium chloride, and calcium chloride
2 corrosive brines include brines containing chloride chemicals such as, sodium chloride brine,
magnesium chloride brine, calcium chloride brine, and prewetting brine
3 data obtained from Clear Roads State Winter Maintenance Data and Statistics
4 Maryland reported amounts of corrosive solids (sodium chloride) used to make corrosive
brine.
5 North Dakota reported 2.6 tons of corrosive solids/lane mile, however this value does not
match the calculated amount of 1.5 tons of corrosive solids/lane mile determined by dividing the
reported 26,255 tons of corrosive solids by the reported 17,255 lane miles. The reported value
of 2.6 tons of corrosive solids/lane mile was used in the data set.
6 Illinois' reported data had differences in the amount of lane miles that corrosive solids and
corrosive brines were applied to (ie. 45,617 lane miles for corrosive solids and 25,801 lane
miles for corrosive brines).
217
Table F.4 Deicing Agent Usage Statistics
Statistic
Corrosive
Solids1
(tons)
Corrosive
Solids1/Lane
Mile
(tons/lane
mile)
Corrosive
Brines2
(gal.)
Corrosive
Brines2/Lane
Mile
(gal./lane
mile)
Mean 218290 10.0 3933722 156.0
Standard Deviation 241643 10.6 5604680 238.6
Max 928081 48.4 28600000 1167.3
Min 0 0.0 0 0.0
Median 145000 7.5 1772200 69.01 corrosive solids include chloride containing chemicals such as, sodium
chloride, magnesium chloride, and calcium chloride2 corrosive brines include brines containing chloride chemicals such as,
sodium chloride brine, magnesium chloride brine, calcium chloride brine, and
prewetting brine
218
Appendix G
TAPE SAMPLE RESULTS
G.1 Tape Sample Images
219
220
221
222
223
224
225
G.2 Tape Test Results Data Tables
E-16-JW E-16-JX E-16-JZ Average
1 1.27 6.69 7.40 5.12
2 3.76 7.59 6.06 5.80
3 0.38 6.31 6.51 4.40
4 0.08 8.21 2.65 3.64
5 2.76 5.08 3.92 3.92
6 1.05 6.65 6.35 4.68
7 0.54 7.93 9.23 5.90
8 3.47 5.92 6.42 5.27
9 0.54 6.17 6.72 4.47
10 0.09 4.42 8.91 4.47
11 3.08 5.36 5.84 4.76
12 1.07 5.22 5.19 3.83
Average 1.51 6.30 6.27 4.69
E-16-JW E-16-JX E-16-JZ Average
1 0.65 0.00 0.60 0.41
2 0.00 0.00 0.00 0.00
3 0.20 0.00 0.44 0.21
4 0.00 0.00 0.19 0.06
5 0.00 0.00 0.00 0.00
6 0.31 0.00 1.09 0.47
7 0.10 0.00 1.64 0.58
8 0.00 0.00 0.00 0.00
9 0.10 0.09 0.97 0.39
10 0.00 0.00 1.49 0.50
11 0.00 0.00 0.00 0.00
12 0.18 0.00 0.28 0.15
Average 0.13 0.01 0.56 0.23
E-16-JW E-16-JX E-16-JZ Average
1 0.32 0.00 0.29 0.20
2 0.00 0.00 0.00 0.00
3 0.00 0.00 0.00 0.00
4 0.00 0.00 0.00 0.00
5 0.00 0.00 0.00 0.00
6 0.00 0.00 0.00 0.00
7 0.00 0.00 0.00 0.00
8 0.00 0.00 0.00 0.00
9 0.00 0.00 0.00 0.00
10 0.00 0.00 0.17 0.06
11 0.00 0.00 0.00 0.00
12 0.00 0.00 0.00 0.00
Average 0.03 0.00 0.04 0.02
E-16-JW E-16-JX E-16-JZ Average
1 0.00 0.00 0.00 0.00
2 0.00 0.00 0.00 0.00
3 0.00 0.00 0.00 0.00
4 0.00 0.00 0.00 0.00
5 0.00 0.00 0.00 0.00
6 0.00 0.00 0.00 0.00
7 0.00 0.00 0.00 0.00
8 0.00 0.00 0.00 0.00
9 0.00 0.00 0.00 0.00
10 0.00 0.00 0.00 0.00
11 0.00 0.00 0.00 0.00
12 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
CO
Standard Sample
Area Location ID
Density (%)
Standard Sample
Area Location ID
Percent Area ≥ 1/4" (%)
Standard Sample
Area Location ID
Percent Area ≥ 1/2" (%)
Standard Sample
Area Location ID
Percent Area ≥ 1/8" (%)
226
3830 4382 5796 Average
1 14.28 24.09 7.40 15.26
2 12.64 13.89 6.06 10.86
3 12.58 22.49 6.51 13.86
4 6.57 11.41 2.65 6.88
5 6.82 10.92 3.92 7.22
6 15.01 17.62 6.35 13.00
7 17.39 16.97 9.23 14.53
8 10.95 16.55 6.42 11.31
9 15.13 17.97 6.72 13.27
10 8.04 12.36 8.91 9.77
11 8.59 12.88 5.84 9.10
12 10.16 20.46 5.19 11.94
Average 11.51 16.47 6.27 11.42
3830 4382 5796 Average
1 11.30 18.88 8.31 12.83
2 5.70 9.67 0.04 5.13
3 8.78 15.47 4.81 9.69
4 3.20 7.70 8.98 6.63
5 1.21 6.67 3.32 3.73
6 12.58 13.89 8.07 11.51
7 12.62 15.11 9.52 12.42
8 4.29 13.11 0.05 5.81
9 10.84 13.30 4.89 9.68
10 3.53 8.70 9.54 7.26
11 2.93 9.05 0.07 4.02
12 4.85 15.27 7.16 9.09
Average 6.82 12.23 5.40 8.15
3830 4382 5796 Average
1 8.64 15.89 6.08 10.21
2 1.36 3.15 0.00 1.51
3 4.95 8.94 2.83 5.57
4 0.87 4.83 7.88 4.52
5 0.00 2.26 0.16 0.81
6 9.66 9.93 4.13 7.91
7 8.92 13.54 7.91 10.12
8 0.63 8.91 0.00 3.18
9 6.17 8.22 2.75 5.71
10 0.38 5.44 7.02 4.28
11 0.00 3.77 0.00 1.26
12 2.53 11.51 4.33 6.12
Average 3.68 8.03 3.59 5.10
3830 4382 5796 Average
1 5.40 8.58 2.57 5.52
2 0.00 0.00 0.00 0.00
3 0.78 2.80 0.00 1.19
4 0.00 0.00 5.41 1.80
5 0.00 0.00 0.00 0.00
6 3.87 3.32 0.00 2.40
7 3.02 10.37 3.91 5.77
8 0.00 0.69 0.00 0.23
9 0.00 2.02 1.13 1.05
10 0.00 0.00 2.95 0.98
11 0.00 0.45 0.00 0.15
12 0.00 5.67 0.59 2.09
Average 1.09 2.82 1.38 1.76
CT
Standard Sample
Area Location ID
Density (%)
Standard Sample
Area Location ID
Percent Area ≥ 1/4" (%)
Standard Sample
Area Location ID
Percent Area ≥ 1/2" (%)
Standard Sample
Area Location ID
Percent Area ≥ 1/8" (%)
227
004111 041331 042711 Average
1 2.93 10.77 3.60 5.77
2 10.50 9.59 10.55 10.21
3 9.32 16.12 7.34 10.93
4 4.75 2.33 2.78 3.29
5 8.30 5.94 5.32 6.52
6 7.71 3.65 4.85 5.40
7 2.29 5.92 4.38 4.20
8 10.72 20.04 10.51 13.75
9 5.39 13.25 7.53 8.73
10 3.38 2.30 2.14 2.61
11 7.65 4.34 2.87 4.95
12 10.43 6.47 4.84 7.25
Average 6.95 8.39 5.56 6.97
004111 041331 042711 Average
1 1.25 8.20 0.92 3.46
2 4.79 7.04 1.81 4.55
3 6.13 12.92 3.68 7.58
4 0.69 0.18 0.00 0.29
5 0.99 0.39 0.14 0.50
6 5.83 1.20 2.69 3.24
7 0.78 3.90 1.82 2.17
8 4.82 17.09 1.92 7.95
9 3.78 9.77 4.02 5.86
10 0.17 0.18 0.11 0.15
11 0.76 0.31 0.03 0.37
12 6.88 5.02 2.35 4.75
Average 3.07 5.52 1.63 3.41
004111 041331 042711 Average
1 0.51 6.00 0.14 2.22
2 1.42 4.83 0.00 2.08
3 4.78 10.56 1.90 5.75
4 0.00 0.00 0.00 0.00
5 0.00 0.00 0.00 0.00
6 4.09 0.44 2.21 2.25
7 0.12 3.00 0.95 1.36
8 1.00 15.43 0.00 5.48
9 2.29 6.28 2.12 3.56
10 0.00 0.00 0.00 0.00
11 0.00 0.00 0.00 0.00
12 4.51 4.45 1.18 3.38
Average 1.56 4.25 0.71 2.17
004111 041331 042711 Average
1 0.00 2.49 0.00 0.83
2 0.00 0.00 0.00 0.00
3 2.01 4.87 0.00 2.30
4 0.00 0.00 0.00 0.00
5 0.00 0.00 0.00 0.00
6 3.20 0.00 1.37 1.52
7 0.00 1.13 0.00 0.38
8 0.00 11.54 0.00 3.85
9 0.00 2.09 0.00 0.70
10 0.00 0.00 0.00 0.00
11 0.00 0.00 0.00 0.00
12 1.04 3.87 0.00 1.64
Average 0.52 2.17 0.11 0.93
IA
Standard Sample
Area Location ID
Density (%)
Standard Sample
Area Location ID
Percent Area ≥ 1/4" (%)
Standard Sample
Area Location ID
Percent Area ≥ 1/2" (%)
Standard Sample
Area Location ID
Percent Area ≥ 1/8" (%)
228
04019 19811 62861 Average
1 6.21 39.49 12.28 19.33
2 12.01 16.21 40.76 23.00
3 2.71 49.03 18.56 23.43
4 — 3.45 9.33 6.39
5 5.27 7.29 8.97 7.18
6 0.88 10.78 10.34 7.33
7 7.29 29.99 16.43 17.91
8 5.31 7.02 31.64 14.66
9 2.81 19.15 34.98 18.98
10 — 3.29 5.34 4.31
11 3.31 8.07 7.74 6.37
12 20.43 7.91 20.86 16.40
Average 6.62 16.81 18.10 14.27
04019 19811 62861 Average
1 3.58 37.62 10.29 17.16
2 8.24 12.04 36.48 18.92
3 1.62 46.95 14.69 21.08
4 — 1.29 8.56 4.93
5 0.48 1.01 8.27 3.25
6 0.53 8.98 8.74 6.08
7 3.41 27.35 14.79 15.18
8 0.32 6.28 26.20 10.93
9 1.31 15.51 29.57 15.46
10 — 1.45 3.99 2.72
11 0.43 2.00 6.48 2.97
12 5.87 6.70 15.36 9.31
Average 2.58 13.93 15.28 11.07
04019 19811 62861 Average
1 1.26 36.34 8.43 15.34
2 3.41 5.04 34.45 14.30
3 0.87 45.30 12.36 19.51
4 — 0.00 7.59 3.80
5 0.00 0.00 7.47 2.49
6 0.28 8.28 7.13 5.23
7 0.26 25.42 13.15 12.94
8 0.00 4.63 22.65 9.09
9 0.34 13.19 25.03 12.85
10 — 0.72 2.87 1.80
11 0.00 0.00 4.93 1.64
12 14.28 6.27 12.52 11.02
Average 2.07 12.10 13.21 9.54
04019 19811 62861 Average
1 0.00 34.78 6.63 13.80
2 0.00 0.00 31.25 10.42
3 0.00 43.89 8.12 17.34
4 — 0.00 6.75 3.37
5 0.00 0.00 5.36 1.79
6 0.00 7.85 3.62 3.82
7 0.00 23.62 10.99 11.54
8 0.00 0.73 15.35 5.36
9 0.00 7.84 20.08 9.31
10 — 0.00 1.19 0.59
11 0.00 0.00 3.32 1.11
12 12.50 5.70 7.07 8.43
Average 1.25 10.37 9.98 7.55
Standard Sample
Area Location ID
Density (%)
MN
Standard Sample
Area Location ID
Percent Area ≥ 1/4" (%)
Standard Sample
Area Location ID
Percent Area ≥ 1/2" (%)
Standard Sample
Area Location ID
Percent Area ≥ 1/8" (%)
229
190083 1290057 1290058 Average
1 11.18 25.75 40.62 25.85
2 10.15 10.34 10.42 10.30
3 14.20 40.35 43.85 32.80
4 5.40 5.27 9.04 6.57
5 5.96 3.77 6.88 5.54
6 8.77 21.87 44.14 24.93
7 9.83 29.00 29.67 22.83
8 10.04 10.38 10.37 10.26
9 9.27 29.11 48.00 28.79
10 6.23 3.94 8.60 6.26
11 7.28 4.55 5.01 5.62
12 10.44 31.93 32.18 24.85
Average 9.06 18.02 24.07 17.05
190083 1290057 1290058 Average
1 2.34 16.94 36.08 18.45
2 1.21 0.91 0.87 1.00
3 5.75 34.24 39.80 26.60
4 0.44 0.00 0.74 0.39
5 0.30 0.00 0.25 0.18
6 1.97 13.61 38.93 18.17
7 2.11 20.38 22.24 14.91
8 1.36 0.92 1.09 1.13
9 2.05 19.82 43.20 21.69
10 0.31 0.06 0.22 0.19
11 0.88 0.00 0.00 0.29
12 2.25 26.95 25.39 18.20
Average 1.75 11.15 17.40 10.10
190083 1290057 1290058 Average
1 0.12 11.93 33.44 15.17
2 0.00 0.00 0.00 0.00
3 1.68 30.59 37.20 23.16
4 0.00 0.00 0.00 0.00
5 0.00 0.00 0.00 0.00
6 0.00 8.30 35.70 14.67
7 0.14 15.79 19.73 11.89
8 0.00 0.00 0.00 0.00
9 0.00 12.34 41.59 17.98
10 0.00 0.00 0.00 0.00
11 0.00 0.00 0.00 0.00
12 0.00 24.04 22.45 15.50
Average 0.16 8.58 15.84 8.20
190083 1290057 1290058 Average
1 0.00 7.65 29.97 12.54
2 0.00 0.00 0.00 0.00
3 0.00 27.07 33.15 20.07
4 0.00 0.00 0.00 0.00
5 0.00 0.00 0.00 0.00
6 0.00 2.91 30.73 11.21
7 0.00 11.77 15.06 8.94
8 0.00 0.00 0.00 0.00
9 0.00 6.37 40.88 15.75
10 0.00 0.00 0.00 0.00
11 0.00 0.00 0.00 0.00
12 0.00 18.51 18.63 12.38
Average 0.00 6.19 14.03 6.74
Standard Sample
Area Location ID
Density (%)
NC
Standard Sample
Area Location ID
Standard Sample
Area Location ID
Percent Area ≥ 1/4" (%)
Percent Area ≥ 1/2" (%)
Standard Sample
Area Location ID
Percent Area ≥ 1/8" (%)
230
017201120011300 11101120017900 017701460003700 Average
1 8.88 1.83 5.30 5.34
2 3.36 25.42 16.67 15.15
3 5.64 2.62 4.52 4.26
4 5.58 5.03 4.11 4.90
5 3.33 8.58 9.69 7.20
6 5.41 2.73 24.65 10.93
7 9.80 2.39 51.65 21.28
8 4.74 28.52 16.10 16.45
9 8.02 2.38 60.36 23.59
10 5.60 5.35 3.02 4.66
11 3.65 12.31 10.31 8.76
12 5.02 2.77 4.98 4.26
Average 5.75 8.33 17.61 10.56
017201120011300 11101120017900 017701460003700 Average
1 4.04 0.00 2.82 2.29
2 0.00 23.99 6.52 10.17
3 1.77 0.39 3.28 1.81
4 2.89 1.01 1.93 1.95
5 0.00 5.48 4.39 3.29
6 2.57 0.16 21.77 8.17
7 4.46 0.21 49.74 18.14
8 0.00 27.19 6.31 11.17
9 3.10 0.20 57.43 20.24
10 2.68 1.04 1.19 1.64
11 0.04 7.18 5.84 4.36
12 2.09 0.08 1.44 1.20
Average 1.97 5.58 13.56 7.03
017201120011300 11101120017900 017701460003700 Average
1 1.51 0.00 1.28 0.93
2 0.00 21.95 0.40 7.45
3 0.48 0.31 2.54 1.11
4 1.27 0.00 0.56 0.61
5 0.00 3.32 1.22 1.51
6 1.56 0.00 20.54 7.37
7 0.91 0.00 48.66 16.52
8 0.00 26.07 0.54 8.87
9 0.86 0.00 55.29 18.72
10 0.56 0.00 0.14 0.24
11 0.00 1.66 1.73 1.13
12 0.35 0.00 0.57 0.30
Average 0.63 4.44 11.12 5.40
017201120011300 11101120017900 017701460003700 Average
1 0.75 0.00 0.00 0.25
2 0.00 16.00 0.00 5.33
3 0.00 0.00 1.16 0.39
4 0.00 0.00 0.00 0.00
5 0.00 0.70 0.00 0.23
6 0.65 0.00 17.44 6.03
7 0.00 0.00 46.26 15.42
8 0.00 22.11 0.00 7.37
9 0.00 0.00 54.12 18.04
10 0.00 0.00 0.00 0.00
11 0.00 0.00 0.00 0.00
12 0.00 0.00 0.00 0.00
Average 0.12 3.23 9.92 4.42
NH
Standard Sample
Area Location ID
Density (%)
Standard Sample
Area Location ID
Percent Area ≥ 1/4" (%)
Standard Sample
Area Location ID
Percent Area ≥ 1/2" (%)
Standard Sample
Area Location ID
Percent Area ≥ 1/8" (%)
231
Standard Sample
7700105 7701977 7701993 Average
1 3.21 36.29 14.72 18.07
2 16.11 24.15 9.89 16.72
3 5.92 19.79 19.73 15.15
4 4.73 8.03 7.21 6.66
5 13.98 10.53 4.74 9.75
6 14.17 4.29 14.05 10.84
7 2.53 30.46 17.91 16.97
8 5.26 15.82 14.39 11.82
9 9.62 36.66 17.07 21.12
10 3.99 9.49 7.25 6.91
11 10.42 11.89 8.10 10.14
12 5.39 9.50 16.24 10.38
Average 7.95 18.07 12.61 12.88
7700105 7701977 7701993 Average
1 0.60 27.30 11.67 13.19
2 14.53 16.21 1.19 10.64
3 2.80 10.75 17.18 10.24
4 1.73 1.66 2.52 1.97
5 12.00 0.19 0.03 4.08
6 11.54 0.38 12.44 8.12
7 0.18 28.33 14.05 14.19
8 4.31 10.06 1.67 5.35
9 7.41 33.35 14.41 18.39
10 1.65 2.38 3.68 2.57
11 8.50 0.50 0.10 3.03
12 1.87 7.63 9.41 6.30
Average 5.59 11.56 7.36 8.17
7700105 7701977 7701993 Average
1 0.00 23.76 9.94 11.23
2 13.21 7.61 0.00 6.94
3 2.08 7.74 14.26 8.03
4 0.93 0.00 0.44 0.46
5 9.74 0.00 0.00 3.25
6 10.03 0.00 10.12 6.72
7 0.00 26.40 12.23 12.88
8 3.41 2.84 0.11 2.12
9 6.38 30.58 11.92 16.30
10 0.62 0.00 1.72 0.78
11 6.73 0.00 0.00 2.24
12 0.48 5.62 6.61 4.23
Average 4.47 8.71 5.61 6.26
7700105 7701977 7701993 Average
1 0.00 20.34 6.65 8.99
2 7.92 0.00 0.00 2.64
3 1.42 3.02 4.57 3.00
4 0.00 0.00 0.00 0.00
5 6.44 0.00 0.00 2.15
6 8.86 0.00 2.54 3.80
7 0.00 21.90 8.55 10.15
8 1.11 0.00 0.00 0.37
9 4.92 23.81 5.47 11.40
10 0.00 0.00 0.00 0.00
11 2.53 0.00 0.00 0.84
12 0.00 1.57 2.90 1.49
Average 2.77 5.89 2.56 3.74
Density (%)
OH
Standard Sample
Area Location ID
Percent Area ≥ 1/4" (%)
Standard Sample
Area Location ID
Percent Area ≥ 1/2" (%)
Standard Sample
Area Location ID
Percent Area ≥ 1/8" (%)
232
G.3 Tape Test Results Standard Deviations
Table G.1 Tape Test Results Cluster Standard Deviations
ClusterDensity
(%)
Percent Area
≥ 1/8" (%)
Percent Area
≥ 1/4" (%)
Percent Area
≥ 1/2" (%)
CO 2.70 0.43 0.07 0.00
CT 4.63 4.83 4.21 2.62
IA 4.13 3.90 3.34 2.20
MN 12.46 12.11 11.74 11.10
NC 13.68 14.12 13.21 11.80
NH 13.05 13.20 13.09 12.44
OH 8.52 8.55 7.85 6.25
233
Table G.2 Tape Test Results Field Bridge Standard Deviations
Field BridgeDensity
(%)
Percent Area
≥ 1/8" (%)
Percent Area
≥ 1/4" (%)
Percent Area
≥ 1/2" (%)
CO E-16-JW 1.37 0.19 0.09 0.00
CO E-16-JX 1.19 0.02 0.00 0.00
CO E-16-JZ 1.84 0.60 0.09 0.00
CT 3830 3.56 4.14 3.78 1.90
CT 4382 4.34 3.79 4.28 3.58
CT 5796 2.65 3.77 3.13 1.87
IA 004111 3.09 2.53 1.89 1.05
IA 041331 5.68 5.63 4.87 3.40
IA 042711 2.85 1.41 0.92 0.40
MN 04019 5.75 2.70 4.41 3.95
MN 19811 14.99 15.37 15.35 15.26
MN 62861 11.74 10.18 9.44 8.53
NC 190083 2.52 1.48 0.48 0.00
NC 1290057 13.05 12.39 10.63 8.85
NC 1290058 17.15 18.53 17.55 16.02
NH 017201120011300 2.11 1.62 0.59 0.27
NH 11101120017900 9.26 9.65 9.24 7.51
NH 017701460003700 19.15 19.54 19.95 19.53
OH 7700105 4.73 5.01 4.61 3.37
OH 7701977 11.32 12.07 11.46 9.80
OH 7701993 4.95 6.42 5.76 3.08
234
Table G.3 Tape Test Results Standard Sample Area Location Standard Deviations
G.4 Tape Test Results Graphs
Figure G.1 Average Density of Rust Particles, by Cluster
Standard Sample
Area Location ID
Density
(%)
Percent Area
≥ 1/8" (%)
Percent Area
≥ 1/4" (%)
Percent Area
≥ 1/2" (%)
1 12.75 11.85 11.39 10.59
2 8.63 9.61 9.25 8.14
3 14.21 13.80 13.42 13.09
4 2.72 2.96 2.64 2.03
5 2.93 3.50 2.83 1.91
6 10.30 9.58 8.90 7.82
7 13.28 13.10 12.95 12.15
8 7.61 8.56 8.19 6.47
9 16.39 15.97 15.72 15.63
10 3.14 2.86 2.08 0.76
11 3.15 3.28 2.03 0.95
12 8.99 7.82 7.41 6.18
4.69
12.41
6.97
14.27
17.05
10.56
12.88
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
CO(good
deicing)
CT(inferior
deicing & coastal)
IA(inferiordeicing)
MN(inferiordeicing)
NC(good & inferior
coastal)
NH(good
deicing & coastal)
OH(good
deicing)
Per
cent A
rea
(%)
Cluster
235
Figure G.2 Average Percent Area of Rust Particles Greater than or Equal to an 1/8 inch,
by Cluster
Figure G.3 Average Percent Area of Rust Particles Greater than or Equal to a 1/4 inch, by
Cluster
0.23
8.15
3.41
11.0710.10
7.038.17
0.00
5.00
10.00
15.00
20.00
25.00
CO(good
deicing)
CT(inferior
deicing & coastal)
IA(inferior
deicing)
MN(inferior
deicing)
NC(good & inferior
coastal)
NH(good
deicing & coastal)
OH(good
deicing)
Per
cen
t A
rea
(%)
Cluster
0.02
5.10
2.17
9.54
8.20
5.406.26
0.00
5.00
10.00
15.00
20.00
25.00
CO(good
deicing)
CT(inferior
deicing & coastal)
IA(inferiordeicing)
MN(inferiordeicing)
NC(good & inferior
coastal)
NH(good
deicing & coastal)
OH(good
deicing)
Per
cent A
rea
(%)
Cluster
236
Figure G.4 Average Percent Area of Rust Particles Greater than or Equal to a 1/2 inch, by
Cluster
Figure G.5 Average Density of Rust Particles, by Field Bridge
0.00
1.760.93
7.556.74
4.423.74
0.00
5.00
10.00
15.00
20.00
25.00
CO(good
deicing)
CT(inferior
deicing & coastal)
IA(inferiordeicing)
MN(inferiordeicing)
NC(good & inferior
coastal)
NH(good
deicing & coastal)
OH(good
deicing)
Per
cen
t A
rea
(%)
Cluster
1.51
6.30 6.27
11.51
16.47
9.246.95
8.395.56 6.62
16.8118.10
9.06
18.02
24.07
5.758.33
17.61
7.95
18.07
12.61
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
40.00
45.00
CO
E-1
6-JW
CO
E-1
6-JX
CO
E-1
6-JZ
CT 3
830
CT 4
382
CT 5
796
IA 0
0411
1
IA 0
4133
1
IA 0
4271
1
MN 0
4019
MN 1
9811
MN 6
2861
NC 1
9008
3
NC 1
2900
57
NC 1
2900
58
NH 0
1720
1120
0113
00
NH 1
1101
1200
1790
0
NH 0
1770
1460
0037
00
OH 7
7001
05
OH 7
7019
77
OH 7
7019
93
Per
cent A
rea
(%)
Field Bridge
237
Figure G.6 Average Percent Area of Rust Particles Greater than or Equal to an 1/8 inch,
by Field Bridge
Figure G.7 Average Percent Area of Rust Particles Greater than or Equal to a 1/4 inch, by
Field Bridge
0.13 0.01 0.56
6.82
12.23
5.403.07
5.521.63 2.58
13.9315.28
1.75
11.15
17.40
1.975.58
13.56
5.59
11.56
7.36
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
40.00
45.00
CO
E-1
6-JW
CO
E-1
6-JX
CO
E-1
6-JZ
CT 3
830
CT 4
382
CT 5
796
IA 0
0411
1
IA 0
4133
1
IA 0
4271
1
MN 0
4019
MN 1
9811
MN 6
2861
NC 1
9008
3
NC 1
2900
57
NC 1
2900
58
NH 0
1720
1120
0113
00
NH 1
1101
1200
1790
0
NH 0
1770
1460
0037
00
OH 7
7001
05
OH 7
7019
77
OH 7
7019
93
Per
cen
t A
rea
(%)
Field Bridge
0.03 0.00 0.04
3.68
8.03
3.59
1.56
4.25
0.712.07
12.1013.21
0.16
8.58
15.84
0.63
4.44
11.12
4.47
8.71
5.61
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
CO
E-1
6-JW
CO
E-1
6-JX
CO
E-1
6-JZ
CT 3
830
CT 4
382
CT 5
796
IA 0
0411
1
IA 0
4133
1
IA 0
4271
1
MN 0
4019
MN 1
9811
MN 6
2861
NC 1
9008
3
NC 1
2900
57
NC 1
2900
58
NH 0
1720
1120
0113
00
NH 1
1101
1200
1790
0
NH 0
1770
1460
0037
00
OH 7
7001
05
OH 7
7019
77
OH 7
7019
93
Per
cen
t A
rea
(%)
Field Bridge
238
Figure G.8 Average Percent Area of Rust Particles Greater than or Equal to a 1/2 inch, by
Field Bridge
Figure G.9 Average Density of Rust Particles, by Standard Sample Area Location
0.00 0.00 0.001.09
2.821.38 0.52
2.170.11
1.25
10.37 9.98
0.00
6.19
14.03
0.12
3.23
9.92
2.77
5.89
2.56
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
CO
E-1
6-JW
CO
E-1
6-JX
CO
E-1
6-JZ
CT 3
830
CT 4
382
CT 5
796
IA 0
0411
1
IA 0
4133
1
IA 0
4271
1
MN 0
4019
MN 1
9811
MN 6
2861
NC 1
9008
3
NC 1
2900
57
NC 1
2900
58
NH 0
1720
1120
0113
00
NH 1
1101
1200
1790
0
NH 0
1770
1460
0037
00
OH 7
7001
05
OH 7
7019
77
OH 7
7019
93
Per
cent A
rea
(%)
Field Bridge
15.13 14.31
16.78
6.247.69
12.35
16.42
13.00
19.11
6.007.53
12.80
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
40.00
1 2 3 4 5 6 7 8 9 10 11 12
Per
cent A
rea
(%)
Standard Sample Area Location ID
239
Figure G.10 Average Percent Area of Rust Particles Greater than or Equal to an 1/8 inch,
by Standard Sample Area Location
Figure G.11 Average Percent Area of Rust Particles Greater than or Equal to a 1/4 inch,
by Standard Sample Area Location
11.23
8.40
12.83
2.56 2.51
9.22
12.83
7.06
15.22
2.40 2.51
8.14
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
1 2 3 4 5 6 7 8 9 10 11 12
Per
cen
t A
rea
(%)
Standard Sample Area Location ID
9.18
5.38
10.52
1.43 1.34
7.36
10.95
4.79
12.52
1.15 1.05
6.76
0.00
5.00
10.00
15.00
20.00
25.00
30.00
1 2 3 4 5 6 7 8 9 10 11 12
Per
cent A
rea
(%)
Standard Sample Area Location ID
240
Figure G.12 Average Percent Area of Rust Particles Greater than or Equal to a 1/2 inch,
by Standard Sample Area Location
6.99
3.07
7.38
0.71 0.69
4.80
8.70
2.86
9.37
0.24 0.35
4.34
0.00
5.00
10.00
15.00
20.00
25.00
30.00
1 2 3 4 5 6 7 8 9 10 11 12
Per
cent A
rea
(%)
Standard Sample Area Location ID
241
Appendix H
ION CHROMATOGRAPHY ANALYSIS RESULTS
H.1 IC Analysis Results Data Tables
E-16-JW E-16-JX E-16-JZ Average
1 — 12680 3460 8070
2 — 11721 6323 9022
3 — 9243 — 9243
4 — 15663 853 8258
5 — 2261 194 1227
6 — — 14621 14621
7 — 16103 11644 13873
8 — 15404 11319 13361
9 — 17074 40054 28564
10 — 21771 2075 11923
11 — 2447 — 2447
12 — 23442 13838 18640
Average — 13437 10438 12009
E-16-JW E-16-JX E-16-JZ Average
1 — 1451 525 988
2 — 1326 688 1007
3 — 1710 — 1710
4 — 2313 303 1308
5 — 295 105 200
6 — — 1332 1332
7 — 1948 1296 1622
8 — 1793 1429 1611
9 — 1929 1599 1764
10 — 1901 679 1290
11 — 282 — 282
12 — 2458 1177 1817
Average — 1582 913 1264
E-16-JW E-16-JX E-16-JZ Average
1 — 7918 1147 4532
2 — 5930 1679 3804
3 — 3847 — 3847
4 — 3951 0 1976
5 — 1279 169 724
6 — — 1553 1553
7 — 10339 1620 5980
8 — 4316 2941 3629
9 — 3258 7064 5161
10 — 5394 512 2953
11 — 1505 — 1505
12 — 8295 1724 5009
Average — 5094 1841 3545
CO
Standard Sample
Area Location ID
Standard Sample
Area Location ID
Standard Sample
Area Location ID
Chloride (ppm)
Nitrate (ppm)
Sulfate (ppm)
242
3830 4382 5796 Average
1 1916 3146 1560 2207
2 973 1593 247 938
3 2370 1707 1119 1732
4 2022 5229 2232 3161
5 327 1003 315 548
6 2045 1282 — 1663
7 — 4077 1589 2833
8 1059 — 246 653
9 1986 2767 1566 2106
10 1699 4882 — 3291
11 229 1352 234 605
12 3722 2204 1411 2446
Average 1668 2658 1052 1816
3830 4382 5796 Average
1 420 465 429 438
2 436 369 87 297
3 412 418 420 417
4 438 421 404 421
5 398 368 453 406
6 397 402 — 399
7 — 395 390 393
8 411 — 102 257
9 427 373 419 406
10 424 432 — 428
11 57 369 157 194
12 507 453 427 462
Average 393 406 329 377
3830 4382 5796 Average
1 2837 1507 1359 1901
2 918 399 116 478
3 2640 704 933 1426
4 517 853 1009 793
5 427 391 488 435
6 2555 1116 — 1835
7 — 1356 1547 1452
8 959 — 114 536
9 1955 630 937 1174
10 459 446 — 452
11 62 404 193 220
12 459 1097 1066 874
Average 1253 809 776 952
CT
Standard Sample
Area Location ID
Standard Sample
Area Location ID
Standard Sample
Area Location ID
Chloride (ppm)
Nitrate (ppm)
Sulfate (ppm)
243
004111 041331 042711 Average
1 6328 5646 8406 6793
2 3589 5545 — 4567
3 4400 7710 6367 6159
4 3378 1538 455 1790
5 2493 2931 1555 2326
6 5889 9697 7072 7553
7 5319 — 9307 7313
8 3697 5311 3864 4291
9 5658 9130 7947 7578
10 3223 1431 424 1693
11 2297 3192 742 2077
12 5336 7368 6807 6504
Average 4300 5409 4813 4825
004111 041331 042711 Average
1 246 477 552 425
2 98 162 — 130
3 227 474 515 406
4 87 547 155 263
5 69 181 226 159
6 239 456 225 306
7 218 — 518 368
8 65 136 124 108
9 251 532 486 423
10 48 222 105 125
11 68 164 230 154
12 227 450 498 392
Average 154 346 330 273
004111 041331 042711 Average
1 987 1395 2635 1672
2 707 3403 — 2055
3 789 1785 2332 1635
4 1251 1936 1132 1440
5 45 640 1521 735
6 1032 2095 2776 1968
7 801 — 2546 1673
8 901 3009 2617 2176
9 964 2080 2568 1870
10 978 1688 919 1195
11 44 572 611 409
12 877 1666 2280 1608
Average 781 1843 1994 1517
IA
Standard Sample
Area Location ID
Standard Sample
Area Location ID
Standard Sample
Area Location ID
Chloride (ppm)
Nitrate (ppm)
Sulfate (ppm)
244
04019 19811 62861 Average
1 798 6247 18795 8613
2 — 2924 6903 4913
3 4148 6517 8599 6421
4 — 1162 7047 4104
5 1960 563 6151 2891
6 6041 6563 6806 6470
7 6666 8709 13808 9728
8 7689 4357 6369 6138
9 4531 10566 12115 9070
10 — 703 8501 4602
11 2326 629 4833 2596
12 7693 4161 10670 7508
Average 4650 4425 9216 6229
04019 19811 62861 Average
1 60 424 303 263
2 — 163 269 216
3 95 462 260 272
4 — 1078 218 648
5 154 241 247 214
6 117 492 260 290
7 335 518 288 380
8 307 187 80 191
9 150 514 291 318
10 — 717 225 471
11 226 261 251 246
12 534 416 255 402
Average 220 456 246 315
04019 19811 62861 Average
1 350 1879 1132 1120
2 — 3549 1066 2307
3 1650 2636 895 1727
4 — 1875 603 1239
5 2479 267 1032 1259
6 2289 2872 640 1934
7 1288 2063 946 1432
8 1151 3635 890 1892
9 1906 3890 1187 2328
10 — 1463 557 1010
11 1285 278 884 816
12 2309 1896 939 1715
Average 1634 2192 898 1569
Sulfate (ppm)
MN
Standard Sample
Area Location ID
Chloride (ppm)
Nitrate (ppm)Standard Sample
Area Location ID
Standard Sample
Area Location ID
245
190083 1290057 1290058 Average
1 763 737 — 750
2 284 436 — 360
3 527 985 — 756
4 521 182 — 352
5 292 208 — 250
6 928 1092 — 1010
7 — 834 — 834
8 375 788 — 582
9 466 910 — 688
10 594 143 — 369
11 298 284 — 291
12 1146 607 — 876
Average 563 601 — 583
190083 1290057 1290058 Average
1 69 547 — 308
2 323 395 — 359
3 409 539 — 474
4 113 100 — 106
5 394 78 — 236
6 431 490 — 461
7 — 600 — 600
8 316 555 — 435
9 435 527 — 481
10 84 78 — 81
11 400 414 — 407
12 460 539 — 499
Average 312 405 — 361
190083 1290057 1290058 Average
1 1028 6260 — 3644
2 365 907 — 636
3 1570 7574 — 4572
4 549 1252 — 901
5 438 186 — 312
6 1620 7249 — 4434
7 — 7108 — 7108
8 411 6718 — 3565
9 1350 7617 — 4483
10 423 744 — 584
11 452 545 — 498
12 2182 6586 — 4384
Average 944 4396 — 2745
Standard Sample
Area Location ID
Chloride (ppm)
Nitrate (ppm)
Sulfate (ppm)
Standard Sample
Area Location ID
Standard Sample
Area Location ID
NC
246
017201120011300 11101120017900 017701460003700 Average
1 2332 — — 2332
2 158 — — 158
3 2731 — — 2731
4 3409 — — 3409
5 115 — — 115
6 2171 — — 2171
7 2498 — — 2498
8 136 — — 136
9 2865 — — 2865
10 3706 — — 3706
11 113 — — 113
12 2840 — — 2840
Average 1923 — — 1923
017201120011300 11101120017900 017701460003700 Average
1 410 — — 410
2 63 — — 63
3 425 — — 425
4 456 — — 456
5 64 — — 64
6 410 — — 410
7 435 — — 435
8 75 — — 75
9 435 — — 435
10 436 — — 436
11 123 — — 123
12 400 — — 400
Average 311 — — 311
017201120011300 11101120017900 017701460003700 Average
1 494 — — 494
2 76 — — 76
3 694 — — 694
4 578 — — 578
5 49 — — 49
6 533 — — 533
7 479 — — 479
8 85 — — 85
9 601 — — 601
10 446 — — 446
11 101 — — 101
12 612 — — 612
Average 396 — — 396
Chloride (ppm)
Nitrate (ppm)
Sulfate (ppm)
Standard Sample
Area Location ID
Standard Sample
Area Location ID
NH
Standard Sample
Area Location ID
247
Standard Sample
7700105 7701977 7701993 Average
1 4085 5375 5192 4884
2 3650 2343 1091 2361
3 5765 5399 7117 6094
4 1822 2430 1649 1967
5 2576 918 689 1394
6 7179 3464 6529 5724
7 3478 4528 3459 3822
8 3322 2026 1446 2264
9 4106 5263 3310 4226
10 1758 1728 2273 1920
11 2778 836 999 1538
12 7863 5805 5079 6249
Average 4032 3343 3236 3537
Standard Sample
7700105 7701977 7701993 Average
1 515 372 428 438
2 363 444 412 406
3 352 435 546 444
4 465 224 243 311
5 442 146 584 391
6 0 483 456 313
7 472 0 394 289
8 468 420 153 347
9 471 452 433 452
10 456 137 89 227
11 369 98 121 196
12 0 446 401 282
Average 365 305 355 341
Standard Sample
7700105 7701977 7701993 Average
1 2600 3885 3877 3454
2 1543 2284 669 1499
3 3481 4638 8916 5678
4 1462 2265 2678 2135
5 542 364 819 575
6 2898 5612 7750 5420
7 1962 2743 2394 2366
8 709 1740 671 1040
9 2500 3775 4129 3468
10 1131 1592 1687 1470
11 606 334 413 451
12 3276 4135 4594 4002
Average 1893 2781 3216 2630
OH
Sulfate (ppm)
Chloride (ppm)
Nitrate (ppm)
248
H.2 IC Analysis Results Standard Deviations
Table H.1 IC Analysis Results Cluster Standard Deviations
Table H.2 IC Analysis Results Field Bridge Standard Deviations
Cluster Chloride Nitrate Sulfate
CO 9363 704 2944
CT 1283 111 726
IA 2651 170 874
MN 4039 202 969
NC 305 181 2939
NH 1388 171 244
OH 2004 168 1996
Field Bridge Chloride Nitrate Sulfate
CO E-16-JX 6823 717 2842
CO E-16-JZ 11742 518 2030
CT 3830 993 115 1036
CT 4382 1497 35 406
CT 5796 734 149 519
IA 004111 1374 86 371
IA 041331 2886 169 851
IA 042711 3475 181 792
MN 04019 2555 150 689
MN 19811 3364 254 1193
MN 62861 4009 58 204
NC 190083 280 150 640
NC 1290057 338 201 3269
NH 017201120011300 1388 171 244
OH 7700105 1961 178 1048
OH 7701977 1855 171 1661
OH 7701993 2255 164 2797
249
Table H.3 IC Analysis Results Standard Sample Area Location Standard Deviations
Standard Sample
Area Location IDChloride Nitrate Sulfate
1 4562 152 1584
2 2154 142 1160
3 2657 123 2509
4 1904 260 684
5 1603 161 635
6 2843 154 2320
7 3721 160 1731
8 2425 166 1807
9 3578 107 1853
10 2295 207 501
11 1386 122 328
12 2912 142 1724