underground service ud... · appropriate metering assembly specification. 2) other conditions, as...

76
CITY OF SEGUIN ELECTRICAL CONNECTION POLICY UNDERGROUND SERVICE UNDERGROUND SERVICE A. CONSTRUCTION STANDARDS 1) Refer to TABLE OF UNDERGROUND SPECIFICATIONS DRAWINGS for appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from both overhead and underground primary facilities. All loads more than 100kVA single-phase and 300kVA three- phase must be served from pad-mounted transformers. Due to the many clearance and meter location problems, it is imperative that the City of Seguin be contacted before designing this service. 4) It is the responsibility of the customer to furnish and install, at their expense, conduit that meets all specifications of city ordinances, the NEC, and the City of Seguin. The City of Seguin shall provide and install all risers to be placed on the City of Seguin poles, wire, and cable at such cost to the customer as is specifically indicated herein. 5) The customer shall install conduits in accordance with the City of Seguin specification SEEU-910. All conduit depths are minimum and shall be designed such that they are maintained permanently. Special consideration is given to conduits installed in rock. Contact the City of Seguin regarding each of these installations. The City of Seguin will assume ownership of conduit and trench only after the City of Seguin has approved the conduit installation and successfully installed the primary conductors. 6) Single-phase riser and conduit from transformers and/or secondary boxes shall have a conduit size of 2” for meter loops up to 200 amps if the total length of the run is less than 100 feet. A 2” conduit can be used where the total length is less than 150 feet and there is one (1) 90-degree sweep and/or one (1) 45-degree sweep in the horizontal run. Conduit runs exceeding the above limitations shall require a minimum size of 3” conduit. Meter loops over 200 amp shall have a minimum conduit size of 3” or larger. Additional runs of conduit may be required. The customer shall furnish a reducing bushing for the 200 amp meter sockets where 3” conduit is utilized. This is to accommodate a 2” knockout. Sweeps shall have a minimum of 18” radius, or as approved by the City of Seguin. 7) Three-phase risers and conduit from transformers and/or secondary boxes shall have a minimum conduit size of 3” for meter loops. The customer shall furnish a

Upload: others

Post on 18-Aug-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

CITY OF SEGUIN ELECTRICAL CONNECTION POLICY UNDERGROUND SERVICE

UNDERGROUND SERVICE A. CONSTRUCTION STANDARDS

1) Refer to TABLE OF UNDERGROUND SPECIFICATIONS DRAWINGS for appropriate metering assembly specification.

2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from both overhead and underground

primary facilities. All loads more than 100kVA single-phase and 300kVA three-phase must be served from pad-mounted transformers. Due to the many clearance and meter location problems, it is imperative that the City of Seguin be contacted before designing this service.

4) It is the responsibility of the customer to furnish and install, at their expense,

conduit that meets all specifications of city ordinances, the NEC, and the City of Seguin. The City of Seguin shall provide and install all risers to be placed on the City of Seguin poles, wire, and cable at such cost to the customer as is specifically indicated herein.

5) The customer shall install conduits in accordance with the City of Seguin

specification SEEU-910. All conduit depths are minimum and shall be designed such that they are maintained permanently. Special consideration is given to conduits installed in rock. Contact the City of Seguin regarding each of these installations. The City of Seguin will assume ownership of conduit and trench only after the City of Seguin has approved the conduit installation and successfully installed the primary conductors.

6) Single-phase riser and conduit from transformers and/or secondary boxes shall

have a conduit size of 2” for meter loops up to 200 amps if the total length of the run is less than 100 feet. A 2” conduit can be used where the total length is less than 150 feet and there is one (1) 90-degree sweep and/or one (1) 45-degree sweep in the horizontal run. Conduit runs exceeding the above limitations shall require a minimum size of 3” conduit. Meter loops over 200 amp shall have a minimum conduit size of 3” or larger. Additional runs of conduit may be required. The customer shall furnish a reducing bushing for the 200 amp meter sockets where 3” conduit is utilized. This is to accommodate a 2” knockout. Sweeps shall have a minimum of 18” radius, or as approved by the City of Seguin.

7) Three-phase risers and conduit from transformers and/or secondary boxes shall

have a minimum conduit size of 3” for meter loops. The customer shall furnish a

Page 2: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

reducing bushing for the 200 amp meter sockets where 3” conduit is utilized. This is to accommodate a 2” knockout. Additional runs of conduit may be required for larger loads. Sweeps shall have a minimum of 18” radius.

8) CT metered services shall have a minimum of 1” conduit at a maximum distance

of 30’ between the pad mounted transformer and the meter socket. Contact the City of Seguin Electric Department for other approved methods for CT meter installations.

9) Streetlight service conduit shall be a minimum of 1”. 10) All exposed secondary conduit to be GRC (Galvanized Rigid Conduit), IMC

(Intermediate Metal Conduit), Rigid Aluminum, or Schedule 40 PVC only per the following specifications. Schedule 80 PVC may be required in what’s considered a hazardous area. See the National Electric Safety Code (NESC) and National Electric Code (NEC) for a description of hazardous areas.

11) All exposed primary conduit will be GRC (Galvanized Rigid Conduit), IMC,

(Intermediate Metal Conduit), or Rigid Aluminum and all sweeps will be of GRC (Galvanized Rigid Conduit), or Rigid Aluminum with a minimum of 24” radius. No exposed PVC conduit will be accepted on primary installations.

12) At the discretion of the City of Seguin concrete encasement or special backfill

may be required for any conduit at any depth carrying a primary and/or secondary line extension to ensure the longevity and integrity of the circuit and the safety of customers and personnel. Concrete encasement so required shall be furnished and installed by the customer. All concrete encasement must meet the City of Seguin specifications.

13) The customer shall furnish and install, at his expense, a pull string of a minimum

1000# test, whose length is at least 10’ longer than the conduit run where possible without entering or working on any City of Seguin equipment. The pull string will remain the property of the customer at the conclusion of its use by the City of Seguin.

14) Plastic identification tape, red or yellow in color and with black lettering reading,

“CAUTION: BURIED ELECTRIC CABLE BELOW”, shall be placed in the cable trench at a depth of 12” to 18” above electric conduit and below any communication cable or conduit. The customer shall supply this tape. In the event that the tape is inadvertently cut, notify the City of Seguin so that replacement may be made, if necessary.

15) Customer shall obtain and install all meter troughs for permanent underground

service according to the City of Seguin specifications as illustrated herein.

Page 3: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

16) Installation of the above is subject to inspection and approval by the City of Seguin.

17) In no case shall installation requirements be less than those called for in the NEC

or NESC. 18) All primary conduit installations shall be not less than 42 inches to the top of the

conduit and may be reduced due to soil conditions to a lesser depth with written approval by the City of Seguin.

19) The customer will be required to install one (10) ten foot joint of GRC,

(Galvanized Rigid Conduit), IMC (Intermediate Metal Conduit), or Rigid Aluminum at pole risers per specification EU-800 for each pipe installed. To a depth of 18” below grade per 300-5(d) NEC code.

20) All customers must furnish and install, at their expense, all appropriate conduit,

pull strings, tape and pads in accordance with other appropriate sections of this policy.

21) Singe Phase Pads will be furnished by the City of Seguin for a residential

installation only. Commercial customers will be required to pour their transformer pad.

22) Customer shall excavate trench to proper depth and install PVC Schedule 40

Electrical Conduit NEMA TC 2. Conduit elbows (sweeps) for primary shall have a minimum of 24” radius and be of GRC, IMC, or Rigid Aluminum. City maintained conduit elbows for secondary shall have a minimum of 18” radius and be of GRC, IMC or Rigid Aluminum. Conduit shall be sized by the City of Seguin. Where Electrical equipment foundations (for transformers, junction boxes, switchgear) lie on top of trench line, the foundation area shall be back filled with compacted base for the entire depth of the trench. Trenches, which cross or will be under streets, commercial driveways, or parking lots, shall be back filled with Flowable Fill.

Page 4: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

TRANSFORMER FUSE: FUSE STOCK #

AutoCAD SHX Text
DEFAULT FUSE SIZE CHART
AutoCAD SHX Text
FUSE
AutoCAD SHX Text
TRANSFORMER PD MT 37.5 KVA 1 PH NO TAPS 120/240
AutoCAD SHX Text
285-034-00055
AutoCAD SHX Text
285-034-00055
AutoCAD SHX Text
285-034-10011
AutoCAD SHX Text
FUSE BAYONET OIL 8A
AutoCAD SHX Text
285-034-00058
AutoCAD SHX Text
285-034-00054
AutoCAD SHX Text
285-034-10014
AutoCAD SHX Text
285-034-10015
AutoCAD SHX Text
285-034-10015
AutoCAD SHX Text
FUSE BAYONET OIL 8A
AutoCAD SHX Text
FUSE BAYONET OIL 15A
AutoCAD SHX Text
FUSE BAYONET OIL 25A
AutoCAD SHX Text
FUSE BAYONET OIL 65A
AutoCAD SHX Text
FUSE BAYONET OIL 100A
AutoCAD SHX Text
FUSE BAYONET OIL 140A
AutoCAD SHX Text
FUSE BAYONET OIL 140A
AutoCAD SHX Text
FUSE BAYONET OIL 8A
AutoCAD SHX Text
FUSE BAYONET OIL 15A
AutoCAD SHX Text
FUSE BAYONET OIL 8A
AutoCAD SHX Text
FUSE BAYONET OIL 8A
AutoCAD SHX Text
FUSE BAYONET OIL 8A
AutoCAD SHX Text
FUSE BAYONET OIL 15A
AutoCAD SHX Text
FUSE BAYONET OIL 8A
AutoCAD SHX Text
285-034-00055
AutoCAD SHX Text
285-034-10011
AutoCAD SHX Text
285-034-00055
AutoCAD SHX Text
285-034-00055
AutoCAD SHX Text
285-034-00055
AutoCAD SHX Text
285-034-10011
AutoCAD SHX Text
285-034-00055
AutoCAD SHX Text
285-034-00055
AutoCAD SHX Text
FUSE BAYONET OIL 8A
AutoCAD SHX Text
285-034-00058
AutoCAD SHX Text
FUSE BAYONET OIL 25A
AutoCAD SHX Text
285-034-00056
AutoCAD SHX Text
FUSE BAYONET OIL 50A
AutoCAD SHX Text
285-034-10011
AutoCAD SHX Text
FUSE BAYONET OIL 15A
AutoCAD SHX Text
285-034-10011
AutoCAD SHX Text
FUSE BAYONET OIL 15A
AutoCAD SHX Text
285-034-00058
AutoCAD SHX Text
FUSE BAYONET OIL 25A
AutoCAD SHX Text
285-034-00058
AutoCAD SHX Text
FUSE BAYONET OIL 25A
AutoCAD SHX Text
285-034-00056
AutoCAD SHX Text
FUSE BAYONET OIL 50A
AutoCAD SHX Text
285-034-00056
AutoCAD SHX Text
FUSE BAYONET OIL 50A
AutoCAD SHX Text
285-034-00056
AutoCAD SHX Text
FUSE BAYONET OIL 50A
AutoCAD SHX Text
TRANSFORMER PD MT 50 KVA 1 PH NO TAPS 120/240
AutoCAD SHX Text
TRANSFORMER PD MT 75 KVA 1 PH NO TAPS 120/240
AutoCAD SHX Text
TRANSFORMER PD MT 75 KVA 3 PH W/ TAPS 120/240
AutoCAD SHX Text
TRANSFORMER PD MT 75 KVA 3 PH W/ TAPS 120/208
AutoCAD SHX Text
TRANSFORMER PD MT 75 KVA 3 PH W/ TAPS 277/480
AutoCAD SHX Text
TRANSFORMER PD MT 100 KVA 1 PH NO TAPS 120/240
AutoCAD SHX Text
TRANSFORMER PD MT 150 KVA 3 PH W/ TAPS 120/240
AutoCAD SHX Text
TRANSFORMER PD MT 150 KVA 3 PH W/ TAPS 120/208
AutoCAD SHX Text
TRANSFORMER PD MT 150 KVA 3 PH W/ TAPS 277/480
AutoCAD SHX Text
TRANSFORMER PD MT 167 KVA 1 PH NO TAPS 120/240
AutoCAD SHX Text
TRANSFORMER PD MT 250 KVA 1 PH NO TAPS 120/240
AutoCAD SHX Text
TRANSFORMER PD MT 300 KVA 3 PH W/ TAPS 120/240
AutoCAD SHX Text
TRANSFORMER PD MT 300 KVA 3 PH W/ TAPS 120/208
AutoCAD SHX Text
TRANSFORMER PD MT 300 KVA 3 PH W/ TAPS 277/480
AutoCAD SHX Text
TRANSFORMER PD MT 500 KVA 3 PH W/ TAPS 120/240
AutoCAD SHX Text
TRANSFORMER PD MT 500 KVA 3 PH W/ TAPS 120/208
AutoCAD SHX Text
TRANSFORMER PD MT 500 KVA 3 PH W/ TAPS 277/480
AutoCAD SHX Text
TRANSFORMER PD MT 750 KVA 3 PH W/ TAPS 120/240
AutoCAD SHX Text
TRANSFORMER PD MT 750 KVA 3 PH W/ TAPS 120/208
AutoCAD SHX Text
TRANSFORMER PD MT 750 KVA 3 PH W/ TAPS 277/480
AutoCAD SHX Text
TRANSFORMER PD MT 1000 KVA 3 PH W/ TAPS 277/480
AutoCAD SHX Text
TRANSFORMER PD MT 1500 KVA 3 PH W/ TAPS 277/480
AutoCAD SHX Text
TRANSFORMER PD MT 2000 KVA 3 PH W/ TAPS 277/480
AutoCAD SHX Text
TRANSFORMER PD MT 2500 KVA 3 PH W/ TAPS 277/480
AutoCAD SHX Text
TRANSFORMER PD MT 25 KVA 1 PH NO TAPS 120/240
AutoCAD SHX Text
285-034-00055
AutoCAD SHX Text
FUSE BAYONET OIL 8A
AutoCAD SHX Text
NTS
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
Page 5: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

TITLE

SCALE DRAWING NO.

DATE ISSUED: 09/28/2010

NTS PCLAB-1

PEDESTAL AND CABLE LABELING

TRANSFORMAER

123

T1

D E

PEDESTAL

123

DT1

PEDESTAL

123

ET1

LOOP #

PEDESTAL #

CABLE LABELS

1

4

0

2

1

4

0

4

1402 HOUSTON 1404 HOUSTON

DO NOT USE LETTERS: A, B, C, I, O, Q, V, Z

AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 6: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

TITLE

SCALE DRAWING NO.

DATE ISSUED: 09/28/2010

NTS PCLAB-2

PRIMARY CABLE LABELING

LETTERS:

A, B, C USED FOR PRIMARY CABLE LABELING ONLY

T2A

T2B

T2C

RS1231 A

RS1231 B

RS1231 C

RS1231 T2

5657

100 KVA

277/480

123

T1

AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 7: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

TITLE

SCALE DRAWING NO.

DATE ISSUED: 09/28/2010

NTS PCLAB-3

RADIAL SWITCH LABEL

RISER-TRANSFORMER : PEDESTAL

RS1231

123

T1

T2 T1

4567

50 KVA

120/240

123

T2

7654

50 KVA

120/240

D

E

T2 T1 D

R

S

1

2

3

1

123

DT1

123

ET1

123

DT2

AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 8: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

TITLE

SCALE DRAWING NO.

DATE ISSUED: 09/28/2010

NTS PCLAB-4

UNDERGROUND - RADIAL

LABELING SCHEME

RS1231

123

T1

T2 T1

4567

50 KVA

120/240

123

T2

7654

50 KVA

120/240

R

S

1

2

3

1

T

50

AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 9: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

TITLE

SCALE DRAWING NO.

DATE ISSUED: 09/28/2010

NTS PCLAB-5

UNDERGROUND LOOP

LABELING SCHEME

LS1231

123

T1

T2 T1

7899

50 KVA

120/240

123

T2

3747

50 KVA

120/240

123

T4

LS1232 T2

3435

50 KVA

120/240

123

T3

7624

50 KVA

120/240

T3

T4T3

LS1231 T50

LS1232 T50

NORMAL OPEN INDICATOR

(SOLID GREEN SQUARE 7" X 7")

WARNING

SIGN

RISER NUMBER

AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 10: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

TITLE

SCALE DRAWING NO.

DATE ISSUED: 09/28/2010

NTS PCLAB-6

PAD MOUNT XFMR - FRONT VIEW

1 PHASE LABELING SCHEME

DEVICE CONNECTED TO

LEFT PRIMARY BUSHING

DEVICE CONNECTED TO

RIGHT PRIMARY BUSHING

RS1231 T2

123

T1

7899

50 KVA

120/240

COMPANY #

SIZE IN KVA

VOLTAGE

LOOP

NUMBER

XFMR #

WARNING

SIGN

AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 11: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

TITLE

SCALE DRAWING NO.

DATE ISSUED: 09/28/2010

NTS PCLAB-7

PAD MOUNT XFMR - FRONT VIEW

3 PHASE LABELING SCHEME

DEVICE CONNECTED TO

'A' BUSHING

DEVICE CONNECTED TO

'B' BUSHING

LS1231 T2

123

T1

1234

100 KVA

277/480

COMPANY #

LOOP

NUMBER

DEVICE #

LOOP OR

RADIAL

WARNING

SIGN

SIZE IN KVA

VOLTAGE

AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 12: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

TITLE

SCALE DRAWING NO.

DATE ISSUED: 09/28/2010

NTS PCLAB-8

PRIMARY RISER LABEL

(LOOP-LS, RADIAL-RS)

R

S

1

2

3

1

T

5

0

FUSE

SIZE

RISER

NUMBER

AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 13: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

TITLE

SCALE DRAWING NO.

DATE ISSUED: 09/28/2010

NTS PCLAB-9

RADIAL SWITCH

LABEL DEFINITION

RADIAL SWITCH

RS1231

DEVICE NUMBER

RADIALS WILL ALWAYS BE

LABELED RS_ _ _ 1

ENDING WITH 1

AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 14: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

TITLE

SCALE DRAWING NO.

DATE ISSUED: 09/28/2010

NTS PCLAB-10

LOOP SWITCH

LABEL DEFINITION

LOOP SWITCH

LS1231

DEVICE NUMBER

LOOPS WILL ALWAYS BE

LABELED LS_ _ _ 1 AND LS_ _ _ 2

TO DESIGNATE RISER 1

AND RISER 2

AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 15: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
600A- DEAD BREAK ASSEMBLY WITH 200A BUSHING
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SE6DB
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
SE6DB
Page 16: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
600A- DEAD BREAK ASSEMBLY WITH 200A BUSHING
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SE6DB
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
*FOR TAPE SHIELD APPLICATION USE CONNECTORS AS REQUIRED
AutoCAD SHX Text
cpp
AutoCAD SHX Text
twr
AutoCAD SHX Text
b
AutoCAD SHX Text
el
AutoCAD SHX Text
c
AutoCAD SHX Text
ca
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
Page 17: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
600A- DEAD BREAK ASSEMBLY BUSHING EXTENDER WITH 200A BUSH
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SE6DBE
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
SE6DBE
Page 18: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
600A- DEAD BREAK ASSEMBLY BUSHING EXTENDER WITH 200A BUSH
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SE6DBE
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
cpp
AutoCAD SHX Text
twr
AutoCAD SHX Text
b
AutoCAD SHX Text
be
Page 19: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
600A- DEAD BREAK ASSEMBLY WITH INSULATING PLUG
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SE6DBI
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
SE6DBI
Page 20: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
600A- DEAD BREAK ASSEBMLY WITH INSULATING PLUG
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SE6DBI
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
*FOR TAPE SHIELD APPLICATION USE CONNECTORS AS REQUIRED
AutoCAD SHX Text
p
AutoCAD SHX Text
el
AutoCAD SHX Text
c
AutoCAD SHX Text
ca
Page 21: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
SEANTSL
AutoCAD SHX Text
SEANTSL-ANTIQUE -ANTIQUE STREET LIGHT
AutoCAD SHX Text
NTS
AutoCAD SHX Text
MATERIAL
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
Page 22: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
glg
AutoCAD SHX Text
la
AutoCAD SHX Text
ph
AutoCAD SHX Text
af
AutoCAD SHX Text
pl
AutoCAD SHX Text
*SEE DRAWING SEWDSL FOR CONNECTION
AutoCAD SHX Text
q-cu-g
AutoCAD SHX Text
Break Away Plate
AutoCAD SHX Text
ANTIQUE STREET LIGHT
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SEANTSL
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
Page 23: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
NTS
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
C.T. METER INSTALLATION SINGLE PHASE
AutoCAD SHX Text
SECT1
AutoCAD SHX Text
SECT1
Page 24: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
C.T.'S MOUNTED AT
AutoCAD SHX Text
SECONDARY BUSHINGS
AutoCAD SHX Text
ctd
AutoCAD SHX Text
cw
AutoCAD SHX Text
cg
AutoCAD SHX Text
METER SOCKET MUST NOT BE ATTACHED
AutoCAD SHX Text
DIRECTLY TO PADMOUNTED TRANSFORMER
AutoCAD SHX Text
C.T. METER INSTALLATION SINGLE PHASE
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SECT1
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
Page 25: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
C.T. METER INSTALLATION THREE PHASE
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SECT3
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
SECT3
Page 26: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
C.T. METER INSTALLATION THREE PHASE
AutoCAD SHX Text
NTS
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
C.T.'S MOUNTED AT
AutoCAD SHX Text
SECONDARY BUSHINGS
AutoCAD SHX Text
ctd
AutoCAD SHX Text
cw
AutoCAD SHX Text
cg
AutoCAD SHX Text
SECONDARIES BY CONSUMER
AutoCAD SHX Text
bml
AutoCAD SHX Text
rt located internally
AutoCAD SHX Text
SECT3
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
METER SOCKET ATTACHED DIRECTLY TO PADMOUNTED TRANSFORMER
Page 27: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

If the City of Seguin conductors cross more than 4 linear feet of

roof, clearance must be increased from 18" to 36". If wires cross

more than 6 linear feet of roof, clearance must be greater than

8'.

Point of attachment: 17' above final ground grade

recommended; minimum 12'6". Customer to install point of

attachment 6" below and opposite weatherhead, facing toward

the City of Seguin service lead. Attachment eye part Blackburn

6912 or equivalent.

Metal flashing: If metal roof, plastic may be substituted. Special

roof problems shall be coordinated with the City of Seguin.

Rigid metal conduit: GRC or IMC, secured to wall with two

appropriately spaced 2-hole straps, sized to fit conduit, and

attached with galvanized lag screws.

100 amp loop: 1 1/4" minimum.

200 amp loop: 2" minimum.

Conductors: Minimum 90°C rated insulation and minimum 3'

excess length out of weatherhead.

100 amp loop: Three #2 stranded copper conductors.

200 amp loop: Three #2/0 stranded copper conductors.

Customer to use same copper conductor from weatherhead to

meter socket, and from meter socket to main disconnect.

Neutral shall be marked with white tape in the meter socket and

at the weatherhead.

Meter socket: 5' minimum and 6' maximum from center of

socket to final ground grade, when measured 3' in front of

socket.

Weatherproof main disconnect: Located below or adjacent to

meter socket, with minimum 3' unobstructed clearance in front.

House panel may be located below or adjacent to main

disconnect or inside building (not inside a closet).

Grounding electrode conductor: Minimum #6 copper, connected

to neutral lug in meter socket or neutral bar (NEC 250.24(A)(1)).

Enclose in 1/2" sunlight resistant PVC conduit, continuing 2"

below final ground grade. Secure to wall with two appropriately

spaced 2-hole straps, sized to fit conduit, and attached with

galvanized lag screws.

Ground rod: 5/8" x 8' copper-clad, driven 2" below final ground

grade.

This specification shall be used only in conjunction with the City of Seguin Electrical Connection Policy and may

not reflect all requirements of a specific installation.

METER LOCATION IS DETERMINED BY THE CITY OF SEGUIN. ALL CUSTOMER INSTALLATIONS

REQUIRE INSPECTION BY THE CITY OF SEGUIN.

Final Ground Grade

METERING ASSEMBLY

MAST THROUGH ROOF

SEEH-010NTS

AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 28: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

Pole and point of attachment installed by the City of Seguin.

Weatherhead: Maximum 24" from top of pole.

Rigid metal conduit: GRC or IMC, secured to pole with a

minimum of 3 appropriately spaced 2-hole straps, sized to

fit conduit, and attached with galvanized lag screws.

100 amp loop: 1 1/4" minimum.

200 amp loop: 2" minimum.

Conductors: Minimum 90°C rated insulation and minimum

3' excess length out of weatherhead.

100 amp loop: Three #2 stranded copper conductors.

200 amp loop: Three #2/0 stranded copper conductors.

Customer to use same copper conductors from

weatherhead to meter socket, and from meter socket to

main disconnect. Neutral shall be marked with white tape in

the meter socket and at the weatherhead. Minimum #6

copper bonding shall be provided where necessary (all

non-current carrying parts) to ensure electrical continuity.

Meter socket: 5' minimum and 6' maximum from center of

socket to final ground grade, when measured 3' in front of

socket. Position to face road or driveway, or as

directed/approved by the City of Seguin.

Weatherproof main disconnect: Located below meter

socket, with minimum 3' unobstructed clearance in front.

Grounding electrode conductor: Minimum #6 copper,

connected to neutral lug in meter socket or neutral bar

(NEC 250.24(A)(1)). Enclose in 1/2" sunlight resistant PVC

conduit, continuing 2" below final ground grade. Secure to

pole with two appropriately spaced 2-hole straps, sized to fit

conduit, and attached with galvanized lag screws.

Ground rod: 5/8" x 8' copper-clad, driven 2" below final

ground grade.

This specification shall be used only in conjunction with the City of Seguin Electrical Connection Policy and may not

reflect all requirements of a specific installation.

METER LOCATION IS DETERMINED BY THE CITY OF SEGUIN. ALL CUSTOMER INSTALLATIONS REQUIRE

INSPECTION BY THE CITY OF SEGUIN.

Final Ground Grade

SEEH-020

NTS

METERING ASSEMBLY

ON POLE

AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 29: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

CONDUIT: INSTALL 1-1/4" SCHEDULE 40 PVC.

SECURE CONDUIT WITH TWO APPROPRIATELY

SPACED 2-HOLE STRAPS, SIZED TO FIT CONDUIT

AND ATTACHED WITH GALVANIZED LAG SCREWS.

UNDERGROUND CONDUIT INSTALLED

ACCORDING TO CITY OF SEGUIN SPECIFICATION

SEEU-910. CUSTOMER SHALL CONNECT TO CITY

OF SEGUIN INSTALLED CONDUIT STUB WHERE

POSSIBLE WITHOUT ENTERING OR WORKING ON

ANY CITY OF SEGUIN EQUIPMENT. A 1000# TEST

PULL STRING TO BE INSTALLED IN CONDUIT BY

CUSTOMER. SCHEDULE WITH CITY OF SEGUIN IF

SOURCE FEEDS FROM ENERGIZED EQUIPMENT.

ALL EXPOSED CONDUIT TO BE GRC, IMC, RIGID

ALUMINUM, SCHEDULE 40 PVC OR SCHEDULE 80

PVC IN A HAZARDOUS AREA.

GROUNDING ELECTRODE CONDUCTOR: MINIMUM

#6 COPPER CONNECTED TO NEUTRAL LUG IN

METER SOCKET OR NEUTRAL BAR (NEC 250.24

(A)(1)). ENCLOSE IN 1/2" SUNLIGHT RESISTANT

PVC CONDUIT, CONTINUING 2" BELOW FINAL

GRADE. SECURE TO WALL WITH TWO

APPROPRIATELY SPACED 2-HOLE STRAPS SIZED

TO FIT CONDUIT AND ATTACHED WITH

GALVANIZED LAG SCREWS.

GROUND ROD: 5/8" X 8' COPPER CLAD, DRIVEN 2"

BELOW FINAL GRADE. FOUNDATION STEEL,

WATER PIPE GROUNDING, GAS PIPE BONDING,

AND STRUCTURAL STEEL GROUNDING SHALL BE

INSTALLED PER NEC ARTICLE 250.

METER SOCKET: 5' MINIMUM AND 6' MAXIMUM

FROM CENTER OF SOCKET TO FINAL GROUND

GRADE, WHEN MEASURED 3' IN FRONT OF

SOCKET.

THIS SPECIFICATION SHALL BE USED ONLY IN CONJUNCTION WITH THE CITY OF

SEGUIN ELECTRICAL CONNECTION POLICY AND MAY NOT REFLECT ALL

REQUIREMENTS OF A SPECIFIC INSTALLATION.

METER LOCATION IS DETERMINED BY THE CITY OF SEGUIN. ALL CUSTOMER

INSTALLATIONS REQUIRE INSPECTION BY THE CITY OF SEGUIN,

FINAL GROUND GRADE

AutoCAD SHX Text
CT METER ASSEMBLY MOUNTED ON BUILDING
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SEEU-009
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 9/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 30: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

Meter socket: 5' minimum and 6' maximum from

center of socket to final ground grade, when

measured 3' in front of socket.

Weatherproof main disconnect or shunt trip

device: Located adjacent to meter socket, with

minimum 3' unobstructed clearance in front. For

locations other than this contact the City of

Seguin Inspection Department.

Customer to install conductors from main

disconnect to meter socket per NEC

specifications. Neutral to be marked with white

tape in meter socket. Neutral to be run un-spliced

when possible.

Conduit: To be sized per NEC. Conduit should

be placed on the opposite side of meter socket

from main disconnect. Secure conduit with two

appropriately spaced 2-hole straps, sized to fit

conduit and attached with galvanized lag screws.

All exposed conduit to be GRC, IMC Rigid

Aluminum schedule 40 PVC or schedule 80 PVC

in a hazardous area.

Underground conduit installed according to the

City of Seguin specification SEEU-910.

Customer shall connect to the City of Seguin

installed conduit stub where possible without

entering or working on any City of Seguin

equipment. A 1000# test pull string to be

installed in conduit by customer where possible

without entering or working on any City of Seguin

equipment.

Grounding electrode conductor: Minimum #6

copper, connected to neutral lug in meter socket

or neutral bar (NEC 250.24 (A)(1)). Enclose in

1/2" sunlight resistant PVC conduit, continuing 2"

below final ground grade. Secure to wall with two

appropriately spaced 2-hole straps sized to fit

conduit and attached with galvanized lag screws.

Ground rod: 5/8" x 8' copper-clad, driven 2"

below final ground grade. Foundation steel, water

pipe grounding, gas pipe bonding and structural

steel grounding shall be installed per NEC Article

250.

This specification shall be used only in conjunction with the City of Seguin Electrical Connection Policy and may

not reflect all requirements of a specific installation.

METER LOCATION IS DETERMINED BY THE CITY OF SEGUIN. ALL CUSTOMER INSTALLATIONS

REQUIRE INSPECTION BY THE CITY OF SEGUIN.

Final Ground Grade

AutoCAD SHX Text
METERING ASSEMBLY UNDERGROUND SERVICE
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SEEU-010
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 9/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 31: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

SEEU-020

NTS

METERING ASSEMBLY

UNDERGROUND SERVICE

ON STAND

This specification shall be used only in conjunction with the City of Seguin Electrical Connection Policy

and may not reflect all requirements of a specific installation.

METER LOCATION IS DETERMINED BY THE CITY OF SEGUIN. ALL CUSTOMER INSTALLATIONS

REQUIRE INSPECTION BY THE CITY OF SEGUIN.

Meter stand: 2" GRC, or IMC, continuing a minimum of 2' below final

ground grade with protective tar tape or polywrap extending 2" above

and encased in concrete, 4 sack mix 300PSI minimum. Top of pipe

to have rain proof cap. As an alternative, a commercially available

meter/disconnect pedestal will be acceptable. Proposed catalog

numbers with complete description shall be submitted for approval.

Galvanized mounting channel, Kendorf or equivalent, 1 1/2" x 1 1/2":

Welded or bolted to stand with galvanized bolts.

Meter socket: 5' minimum and 6' maximum from center of socket to

final ground grade when measured 3' in front of meter. Secure at

four points to two appropriately spaced mounting channels.

Weatherproof main disconnect or shunt trip device: Located

adjacent to meter socket, with minimum 3' unobstructed clearance in

front. Secure at four points to two appropriately spaced mounting

channels. For locations other than this installation contact City

Inspections Department.

Conduit: To be sized per NEC. Conduit should be placed on the

opposite side of meter socket from main disconnect. Secure conduit

to one appropriately spaced mounting channel with Kendorf strap or

equivalent, or galvanized U bolt sized to fit conduit.

All exposed conduit to be GRC, IMC Rigid Aluminium schedule 40

PVC or schedule 80 PVC in a hazardous area.

Customer to install conductors from disconnect to meter socket per

NEC specifications, Neutral to be marked with white tape in meter

socket. Neutral to be un-spliced when possible.

Underground conduit will be installed according to the City of Seguin

specification SEEU-910. Customer shall connect to the City of

Seguin installed conduit stub where possible without entering or

working on any City of Seguin equipment. A 1000# test pull string is

to be installed in conduit by customer where possible without

entering or working on any City of Seguin equipment.

Grounding electrode conductor: Minimum #6 copper. Connect to

neutral lug in meter socket or neutral bar (NEC 250.24 (A)(1)).

Enclose in 1/2" sunlight resistant PVC conduit, continuing 2" below

final ground grade. Secure conduit to mounting channel with Kendorf

strap or equivalent, or galvanized U bolts, sized to fit conduit.

All grounding and bonding to be to NEC Article 250 requirements.

Final Ground Grade

WIRE TYPE

SERVICE MAIN ALUMINUM COPPER

RATING 75°C 90°C 75°C 90°C

60 Amp #4 #6 #6 #6

70 Amp #3 #4 #4 #6

100 Amp #1 #2 #3 #3

125 Amp 1/0 1/0 #1 #2

150 Amp 3/0 2/0 1/0 #1

200 Amp 250 MCM 4/0 3/0 2/0

(NEC Table 310-16)

Note: Other service rating shall be submitted to City of Seguin for approval.

AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 32: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

SEEU-045

NTS

METERING ASSEMBLY

MULTIPLE METERS

UNDERGROUND SERVICE

This specification shall be used only in conjunction with the City of Seguin Electrical Connection Policy

and may not reflect all requirements of a specific installation.

METER LOCATION IS DETERMINED BY THE CITY OF SEGUIN. ALL CUSTOMER INSTALLATIONS

REQUIRE INSPECTION BY THE CITY OF SEGUIN.

Meter mounting equipment shall be commercially available horizontal gang or bussed gutter type.

Proposed catalog numbers and complete description shall be submitted for approval. Any other design

or equipment arrangement shall be submitted for approval. Meter mounting equipment shall be installed

such that the center of the highest meter will be 5' minimum and 6' maximum from final ground grade.

Each disconnect device shall have permanent address marking. These markings by the customer

should

be plain and permanent, giving the street number to the door of the premise served, or the symbol

appearing on the entrance door when this door does not carry a street number. The name of the

customer will not suffice for identification. The meter sockets in multi-tenant buildings shall be clearly

and durably marked.

Conductor to be sized and installed according to NEC and local code requirements.

All exposed conduit to be GRC, IMC, Rigid Aluminum, schedule 40 PVC or schedule 80 PVC in a

hazardous area. See article 300 of the NEC.

Underground conduit: Installed according to the City of Seguin specification SEEU-910. Customer shall

connect to City of Seguin installed conduit stub where possible without entering or working on any City

of Seguin equipment. A 1000# test pull string to be installed in conduit by customer where possible

without entering or working on any City of Seguin equipment.

Where a separate conduit is required for the ground wire, a properly sized ground wire shall be

enclosed in 1/2" or larger sunlight resistant PVC conduit, continuing 2" below final ground grade. Secure

to wall with 2 or more appropriately spaced straps, sized to fit conduit, and attached with galvanized lag

screws. Metal conduit acceptable, but must comply with NEC 250.64(e).

See 250(c) of NEC for grounding electrode system and grounding electrode conductor.

AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 33: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

NTS

SEEU-070

METERING ASSEMBLY

CT STAND

This meter stand is used when metering PT's and CT's are located

within the secondary compartment of the padmount transformer.

Meter assembly stand must be positioned 4' to the side of the

transformer pad. Meter CANNOT be located in front of the

transformer pad due to hot stick access requirements.

Meter stand: 2" GRC or IMC, continuing a minimum of 2' below

final ground grade with protective tar tape or polywrap extending 2"

above and encased in concrete, 4 sack mix minimum. Top of pipe

to have rain proof cap.

Galvanized mounting channel: Kendorf or equivalent, 1 1/2" x 1

1/2", welded or bolted to stand with galvanized bolts.

Meter socket: 5" minimum and 6' maximum from center of socket

to final ground grade when measured 3' in front of meter. Secure

at four points to two appropriately spaced mounting channels.

All exposed conduit to be 1 1/4" sunlight resistant Schedule 40

PVC. For installations subject to possible physical damage,

Schedule 80 PVC shall be substituted per NEC. All PVC will meet

NEMA TC-2-1998 for electrical use. Secure conduit to two

appropriately spaced mounting channels with Kendorf straps or

equivalent, or galvanized U bolts, sized to fit conduit.

Underground conduit: 1 1/4" Schedule 40 PVC, installed

according to NBU specification EU-910. Customer shall connect to

City of Seguin installed conduit stub. 1000# test pull string to be

installed in conduit by customer.

Grounding electrode conductor: Minimum #6 copper, connected to

neutral lug in meter socket or neutral bar (NEC 250.24 (A) (1)),

enclosed in 1/2" sunlight resistant PVC conduit, continuing 2" below

final ground grade and secured to two mounting channels with

Kendorf straps or equivalent, or galvanized U bolts, sized to fit

conduit.

Ground rod: 5/8" x 8' copper-clad, driven 2" below final ground

grade.

Final Ground

Grade

Open

Area

AB C S S S

4'

FRONT VIEW

2"

36" TYP

1

1

4

"

SIDE VIEW

2'

5' (min) - 6' (max)

METER LOCATION IS DETERMINED BY THE CITY OF SEGUIN ELECTRICAL DEPARTMENT. ALL CUSTOMER

INSTALLATIONS REQUIRE INSPECTION BY THE CITY OF SEGUIN ELECTRICAL DEPARTMENT.

This specification shall be used only in conjunction with the City of Seguin Electrical Connection Policy and may not

reflect all requirements of a specific installation.

NOTE:

This installation is not the only

method for metering if the CT's

and PT's are mounted within the

secondary compartment of the

transformer. For other methods

contact the City of Seguin Electric

Department.

AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 34: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

SEEU-110

NTS

METERING ASSEMBLY

UNDERGROUND TEMPORARY

836

BELL

This specification shall be used only in conjunction with the City of Seguin Electrical Connection Policy and may

not reflect all requirements of a specific installation.

METER LOCATION IS DETERMINED BY THE CITY OF SEGUIN. ALL CUSTOMER APPLICATIONS

REQUIRE INSPECTION BY THE CITY OF SEGUIN.

WIRE TYPE

SERVICE MAIN ALUMINUM COPPER

RATING 75°C 90°C 75°C 90°C

60 Amp #4 #6 #6 #6

70 Amp #3 #4 #4 #6

100 Amp #1 #2 #3 #3

125 Amp 1/0 1/0 #1 #2

150 Amp 3/0 2/0 1/0 #1

200 Amp 250 MCM 4/0 3/0 2/0

(NEC Table 310-16)

Note: Other service rating shall be submitted to the City of Seguin

Planning and Coding Department for approval.

Treated 4" x 4" post: Height above final ground grade shall be 7' and

a minimum below ground of 2'. Three wood braces required,

minimum 2" x 4", secured with 2" x 4" stakes driven securely into

ground. Braces shall not be attached to trees or other structures.

Site Address: Marked on 1' x 1' exterior (painted) or marine plywood.

Conductors: Service lateral conductors shall be sized according to

the table below, as a minimum, based upon the main bus rating of

the disconnect device; unless otherwise approved by the City of

Seguin. Conductor insulation shall be rated for direct burial (wet

locations).

Meter socket: 4' 6" minimum and 6' maximum from center of socket

to final ground grade and positioned to face road or driveway, or as

directed/approved by the City of Seguin. Source connections shall

be made on top side of meter socket.

Approved disconnect device(s) in exterior enclosure. Receptacles

shall be in weatherproof enclosure per NEC requirements. Circuits

shall have GFCI protection. Customer to install a minimum of one

120 V, 20 amp receptacle and one 240 V, 20 amp receptacle.

Electrical conduit for service lateral conductors shall be GRC, IMC,

Rigid Aluminum or a minimum of schedule 40 PVC.

100 amp loop: 1 1/4" minimum; 200 amp: 2" minimum. The conduit

shall extend 6" below ground grade at temporary post. Conduit shall

be secured to post with 2 appropriately spaced straps, sized to fit

conduit, and attached with lag screws.

Conductor shall be buried from post to within 6" of service

equipment, at a minimum depth of 24" and have 5' leads at service

equipment.

At least on Ground rod: 5/8" x 8' copper-clad, driven 2" below final

ground grade. See NEC Article 250-56

5/8" X 8"

Ground Rod

Weather proof flexible steel

conduit long enough to enter

into transformer cabinet.

6' 6" to

top of

handles

AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 35: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

NTS

ENCLOSURE

SECONDARY

SEEU-210

18"

(Final Ground Grade)

or compacted fill

Undisturbed earth

4" - 6"

10"

24"

(Final Ground Grade)

This specification shall be used only in conjunction with the City of Seguin Electrical Connection Policy and

may not reflect all requirements of a specific installation.

The electric system layout design, to include secondary enclosure locations, is determined by the

City of Seguin electrical department.

Note: Size of enclosure shall be determined by the City of Seguin electrical department. Make sure

that conduit is not located under lip of box. Primary and Secondary stubouts shall be 5' minimum.

AutoCAD SHX Text
ELECTRIC
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
COVER
AutoCAD SHX Text
BOX - PLAN VIEW
AutoCAD SHX Text
BOX & COVER SECTION
AutoCAD SHX Text
END VIEW
AutoCAD SHX Text
COVER BOLTDOWN OPTION
AutoCAD SHX Text
5' Stubout
AutoCAD SHX Text
5' Stubout
AutoCAD SHX Text
To XFMR
AutoCAD SHX Text
90° pvc conduit elbow, 18"radius size and number of conduits as specified by the City of Seguin electrical department.
Page 36: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

60"

COMPACTED TxDOT GRADE 4, TYPE A,

FLEXIBLE BASE MATERIAL, WASHED SAND,

OR OTHER APPROVED MATERIAL FROM

BOTTOM OF TRENCH TO BOTTOM OF PAD.

6"

36"

18"

6" min.

A

A

C

B B

C

3"

A

A A

AA A B

18"

A

C

B

A

Ground

Rod

6" Typ.

6"

Typ.

4"

Wire mesh, 6 gage

C

A

B

A

C

B

C

C

B B

B B B

C

C CC

6" x 6"

Grade

Final Ground

or compacted fill

Undisturbed earth

B

B

C

Ground Rod

C

A

B

A A A B B B B C CC

Ground Rods

4"

1" (TYP)

A C

A C

SEEU-310

PRIMARY URD PULL BOX

NTS

This specification shall be used only in conjunction with the City of Seguin Electrical Connection Policy and

may not reflect all requirements of a specific installation.

Locations are determined by the City of Seguin. All customer installations require inspection by the City of

Seguin.

A, B, C = Conductor phase; Phase orientation shall be verified prior to installation.

Underground conduit to be installed according to City of Seguin specification SEEU-910.

Conduit to be sized by the City of Seguin and have 1" projection above concrete,

36" radius, 90° sweeps and be of GRC, IMC, or Rigid Aluminium. 1000# test pull string to be installed in each

conduit by the customer where possible without entering or working on any City of Seguin equipment.

Copper-clad ground rods, 5/8" x 8', 2 required, to have 4" projection above bottom of pull box.

All primary stub outs shall be 5' minimum.

Pull Box to be furnished by the City of Seguin and installed by the customer.

AutoCAD SHX Text
SIDE VIEW
AutoCAD SHX Text
TOP VIEW
AutoCAD SHX Text
FRONT
AutoCAD SHX Text
4"
AutoCAD SHX Text
(TYP)
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 37: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

B

B

A

C C

A

* A

B

C

A

B

*

AA

B

C

*

of 3 locations.

Any combination

*

C

B

A

A

B

C

A A B B B C C C

*

B

A A B B B C C C

7"o.c.

COMPACTED TxDOT GRADE 4, TYPE A,

FLEXIBLE BASE MATERIAL, WASHED SAND,

OR OTHER APPROVED MATERIAL FROM

BOTTOM OF TRENCH TO BOTTOM OF FDTN.

60"

4"o.c.

11"

10"

Wire mesh, 6 gage

6" x 6"

6"

3"

TOP VIEW

Ground Rod

11"

30"

15"

4"

15"

Grade

Final Ground

or compacted fill

Undisturbed earth

Ground

Rod

SIDE VIEW

A

A

C

C

Ground Rods

4"

1" (TYP)

PRIMARY, THREE PHASE,

NTS

3 PLACE PULLBOX PAD

SEEU-315

This specification shall be used only in conjunction with the COS Electrical Connection Policy and may not

reflect all requirements of a specific installation. Locations are determined by the City of Seguin electrical

department. All customer installations require inspection by the City of Seguin electrical department.

A, B, C = Conductor phase; Phase orientation shall be verified prior to installation.

Underground conduit to be installed according to City of Seguin specification SEEU-910.

Conduit to be sized by the City of Seguin electrical department and have 1" projection above concrete,

36" radius, 90° sweeps. 1000# test pull string to be installed in each conduit by the customer.

Copper-clad ground rods, 5/8" x 8', 2 required, to have 4" projection above top on concrete.

Concrete to be 4 sack mix minimum.

All primary stub outs shall be 5' minimum.

AutoCAD SHX Text
FRONT
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 38: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

Code Description QtySpec. No. Uom

CONCRETEsc

NON-INVENTORY

WIRE MESH, 6 GAGE, 6" X 6"wm

NON-INVENTORY sq. ft.22

8 FT. GROUND ROD 2285-106-00038gr

ea.

A/R cu. yds.

SEEU-320

PRIMARY (600 AMP),

THREE PHASE, 4 PLACE

NTS

PULLBOX PAD

AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 39: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

A

A

C

B B

C

A

A A

AA

A B

A

C

A

B

A

C

B

C

C

B B

B B B

C

C CC

B

C

B

A A

A B

A C

A C

B B

B

C C

C

76"

COMPACTED TxDOT GRADE 4, TYPE A,

FLEXIBLE BASE MATERIAL, WASHED SAND,

OR OTHER APPROVED MATERIAL FROM

BOTTOM OF TRENCH TO BOTTOM OF FDTN.

12"11.5"

42"

30"

8" min.

SIDE VIEW

4"

12"

TOP VIEW

Ground

Rod

15"

15"

4"

Wire mesh, 6 gage

FRONT

6" x 6"

Grade

Final Ground

or compacted fill

Undisturbed earth

Ground Rods

4"

1" (TYP)

4"

(TYP)

Ground

Rod

8.5"

PRIMARY (600 AMP),

THREE PHASE, 4 PLACE

NTS

PULLBOX PAD

This specification shall be used only in conjunction with the COS Electrical Connection Policy and may not

reflect all requirements of a specific installation. Locations are determined by the City of Seguin electrical

department. All customer installations require inspection by the City of Seguin electrical department.

A, B, C = Conductor phase; Phase orientation shall be verified prior to installation.

Underground conduit to be installed according to City of Seguin specification SEEU-910.

Conduit to be sized by the City of Seguin electrical department and have 1" projection above concrete,

36" radius, 90° sweeps. 1000# test pull string to be installed in each conduit by the customer.

Copper-clad ground rods, 5/8" x 8', 2 required, to have 4" projection above top on concrete.

Concrete to be 4 sack mix minimum.

All primary stub outs shall be 5' minimum.

SEEU-320

AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
Page 40: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

Code Description QtySpec. No. Uom

CONCRETEsc

NON-INVENTORY

WIRE MESH, 6 GAGE, 6" X 6"wm

NON-INVENTORY sq. ft.22

8 FT. GROUND ROD 2285-106-00038gr

ea.

A/R cu. yds.

PRIMARY (600 AMP),

THREE PHASE, 3 PLACE

NTS

PULLBOX PAD

SEEU-325

AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 41: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

S

A

C

B B

C

S

A A

AA A B

A

C

S

S

S

S

S

C

C

B B

B B S

C

C CS

B

C

B

A A

S B

A C

A C

B B

S

C C

S

S

76"

COMPACTED TxDOT GRADE 4, TYPE A,

FLEXIBLE BASE MATERIAL, WASHED SAND,

OR OTHER APPROVED MATERIAL FROM

BOTTOM OF TRENCH TO BOTTOM OF FDTN.

19.5"

42"

30"

8" min.

SIDE VIEW

4"

12"

TOP VIEW

Ground

Rod

15"

15"

4"

Wire mesh, 6 gage

FRONT

6" x 6"

Grade

Final Ground

or compacted fill

Undisturbed earth

Ground Rods

4"

1" (TYP)

4"

(TYP)

Ground

Rod

Spare conduit as needed

12.5"

SEEU-325

PRIMARY (600 AMP),

THREE PHASE, 3 PLACE

NTS

PULLBOX PAD

This specification shall be used only in conjunction with the COS Electrical Connection Policy and may not

reflect all requirements of a specific installation. Locations are determined by the City of Seguin electrical

department. All customer installations require inspection by the City of Seguin electrical department.

A, B, C = Conductor phase; Phase orientation shall be verified prior to installation.

Underground conduit to be installed according to City of Seguin specification SEEU-910.

Conduit to be sized by the City of Seguin electrical department and have 1" projection above concrete,

36" radius, 90° sweeps. 1000# test pull string to be installed in each conduit by the customer.

Copper-clad ground rods, 5/8" x 8', 2 required, to have 4" projection above top on concrete.

Concrete to be 4 sack mix minimum.

All primary stub outs shall be 5' minimum.

AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
Page 42: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

COMPACTED TxDOT GRADE 4, TYPE A, FLEXIBLE

BASE MATERIAL, WASHED SAND, OR OTHER

APPROVED MATERIAL FROM BOTTOM OF

TRENCH TO BOTTOM OF FDTN.

Ground Rod

3/8' REBAR, 12" CENTERS

Ground Rod

Grade

Final Ground

or compacted fill

Undisturbed earth

SEEU-330

PRIMARY, SINGLE PHASE,

PULLBOX FOUNDATION

NTS

This specification shall be used only in conjunction with the COS Electrical Connection Policy and may not

reflect all requirements of a specific installation.

Locations are determined by the City of Seguin electrical department. All customer installations require

inspection by the City of Seguin electrical department.

Underground conduit to be installed according to City of Seguin specification SEEU-910.

Conduit to be sized by the City of Seguin electrical department and have 1" projection above concrete,

36" radius, 90° sweeps. 1000# test pull string to be installed in each conduit by the customer.

Copper-clad ground rods, 5/8" x 8', 1 required, to have 4" projection above top on concrete.

Concrete to be 4 sack mix minimum.

All primary stub outs shall be 5' minimum.

AutoCAD SHX Text
4"o.c.
AutoCAD SHX Text
46"
AutoCAD SHX Text
34"
AutoCAD SHX Text
SIDE VIEW
AutoCAD SHX Text
4"
AutoCAD SHX Text
FRONT
AutoCAD SHX Text
TOP VIEW
AutoCAD SHX Text
17"
AutoCAD SHX Text
4"
AutoCAD SHX Text
17"
AutoCAD SHX Text
4"
AutoCAD SHX Text
5"
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 43: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

5' min

6'

TOP VIEW DETAIL

SIDE VIEW

24"

8 1/2"

Bolts from bolt kits; 1" - 8 UNC

8 1/2"

Bolts from bolt kit, 1" - 8 UNC,

to have 3 1/2" projection

above top of concrete.

sweeps, extended 2' from concrete

1 1/4" Schedule 40 PVC with 90

Concrete to be 3000 PSI with a

system.

and/or connected to conduit

4" tooled radius on edge.

1

2

" Schedule 40 PVC

conduit for ground wire

Final Grade

5

8

" x 8' Ground Rod

6" Wide Caution Tape

(6)

5

8

" x 5' rebar with

3

8

" rebar

ties at 12" O.C. or

3

8

" spiral

rebar with 12" pitch.

3

8

" Rebar coiled steel tied at 12"

spacing

1" Projection above top of concrete

STANDARD METAL LIGHT

NTS

FOUNDATION

SEEU-410

#6 copper installed by the City of Seguin

Bolt kit provided by the City of Seguin.

1

2

" Sch 40 PVC conduit

This specification shall be used only in conjunction with the City of Seguin Electrical

Connection Policy and may not reflect all requirements of a specific installation Locations are

determined by the City of Seguin electrical department. All customer installations require

inspection by the City of Seguin electrical department.

AutoCAD SHX Text
12"
AutoCAD SHX Text
24" min
AutoCAD SHX Text
4"
AutoCAD SHX Text
6"
AutoCAD SHX Text
3" (TYP)
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 44: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

SEEU-420

NTS

This specification shall be used only in conjunction with the City of Seguin Electrical Connection Policy and

may not reflect all requirements of a specific installation.

Locations are determined by the City of Seguin. All customer installations require inspection by the City of

Seguin.

The City of Seguin shall install pole, hang private light, pull Type UF cable, and make all connections. The

City of Seguin will furnish and install 1" riser. The 1" lateral shall be furnished by customer to meet the City of

Seguin specifications. Customer shall provide pull string in conduit. Comply with NEC 300-5.

1" service lateral. Concrete encasement

required if lateral is under driveway.

SECURITY LIGHT

UNDERGROUND SERVICE

Parking lot or vehicle traffic.

To pad mount transformer,

secondary pull box, trough

or overhead source.

Caution tape 12" above service lateral.

AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
12"
AutoCAD SHX Text
12"
AutoCAD SHX Text
CAUTION
AutoCAD SHX Text
CAUTION
AutoCAD SHX Text
CAUTION
Page 45: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

TITLE

SCALE DRAWING NO.

DATE ISSUED: 09/28/2010

NTS SEEU-500

PADMOUNT TRANSFORMER

CLEARANCES

This specification shall be used only in conjunction with the City of Seguin Electrical Connection Policy and may not

reflect all requirements of a specific installation. The fencing or bushes are not required. The measurements are

only intended to show distance requirements should fencing and bushes be used to hide transformer.

Transformer location must be accessible at all

times. Clearance around the City of Seguin

equipment to any barrier shall be 3' minimum.

Any installation that would enclose any

metering/disconnect assemble within the barrier

shall be assessable by some means like a gate

and approved by the City of Seguin.

Barrier can be vegetation, chain link, wood,

concrete block, or appropriate material.

Fencing/gate material shall be designed to allow for

adequate air circulation around equipment and is

subject to the City of Seguin approval.

The front of the City of Seguin transformer shall

have a minimum 10' of clearance due to hot stick

access requirements.

Top

View

Side View

8' max

Front

3'

3'

3'

Transformer Pad

8'

AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 46: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

EQUIPMENT PROTECTION BOLLARD

SEEU-505

NTS09/28/2010

AutoCAD SHX Text
ISSUED
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NUMBER
AutoCAD SHX Text
Rounded Smooth Top
AutoCAD SHX Text
Location of Bollards will be determined and inspected by the City of Seguin Electrical Engineering Department.
AutoCAD SHX Text
4" or 6" diameter 14" Gauge Steel Pipe
AutoCAD SHX Text
6" or 7" Concrete Encasement
AutoCAD SHX Text
Ground level
AutoCAD SHX Text
Interior of pipe will be filled with 4 sac concrete mix
AutoCAD SHX Text
Paint Optional
Page 47: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

Center primary

conduits in this

area.

Center

secondary

conduits in this

area.

3/8" Re-bar 12" o.c.

Final Grade

Ground Rod

NTS SEEU-510

This specification shall be used only in conjunction with the City of Seguin Electrical Connection Policy and may not

reflect all requirements of a specific installation.

Locations are determined by the City of Seguin. All customer installations require inspection by the City of Seguin.

Underground conduit to be installed according to City of Seguin specification SEEU-910. Conduit to be sized by the

City of Seguin and have 5" projection above concrete, 36" radius, 90° sweeps. 1000# test pull string to be installed by

customer where possible without entering or working on any City of Seguin equipment.

Copper-clad ground rods, 5/8" x 8', 1 required, to have 4" projection above top on concrete.

Transformer Pad shall be a minimum of 8" thick from top to bottom.

All primary and secondary stub cuts shall be 5' minimum.

Open Area

Conduit

TRANSFORMER PAD

THREE PHASE FOR 2000 KVA AND

SMALLER

Ground Rod

AutoCAD SHX Text
44"
AutoCAD SHX Text
24"
AutoCAD SHX Text
96"
AutoCAD SHX Text
96"
AutoCAD SHX Text
8"
AutoCAD SHX Text
16"
AutoCAD SHX Text
6"
AutoCAD SHX Text
74"
AutoCAD SHX Text
20"
AutoCAD SHX Text
4"
AutoCAD SHX Text
5"
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
26"
AutoCAD SHX Text
26"
AutoCAD SHX Text
4"
Page 48: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

Center primary

conduits in this

area.

Center

secondary

conduits in this

area.

3/8" Re-bar 12" o.c.

Final Grade

Ground Rod

Ground Rod

NTS SEEU-511

This specification shall be used only in conjunction with the City of Seguin Electrical Connection Policy and may not

reflect all requirements of a specific installation.

Locations are determined by the City of Seguin. All customer installations require inspection by the City of Seguin.

Underground conduit to be installed according to City of Seguin specification SEEU-910. Conduit to be sized by the

City of Seguin and have 5" projection above concrete, 36" radius, 90° sweeps. 1000# test pull string to be installed by

customer where possible without entering or working on any City of Seguin equipment.

Copper-clad ground rods, 5/8" x 8', 1 required, to have 4" projection above top on concrete.

Transformer Pad shall be a minimum of 12" thick from top to bottom.

All primary and secondary stub cuts shall be 5' minimum.

Open Area

Conduit

TRANSFORMER PAD

THREE PHASE LARGER

THAN 2000 KVA

AutoCAD SHX Text
72"
AutoCAD SHX Text
38"
AutoCAD SHX Text
126"
AutoCAD SHX Text
108"
AutoCAD SHX Text
12"
AutoCAD SHX Text
22"
AutoCAD SHX Text
10"
AutoCAD SHX Text
76"
AutoCAD SHX Text
34"
AutoCAD SHX Text
4"
AutoCAD SHX Text
5"
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
27"
AutoCAD SHX Text
27"
AutoCAD SHX Text
4"
Page 49: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

SEEU-520

SINGLE PHASE TRANSFORMER PAD

N.T.S

This specification shall be used only in conjunction with the City of Seguin Electrical Connection Policy and may not

reflect all requirements of a specific installation.

Locations are determined by the City of Seguin. All customer installations require inspection by the City of Seguin.

Underground conduit to be installed according to City of Seguin specification SEEU-910. Conduit to be sized by the

City of Seguin and have 5" projection above concrete, 36" radius, 90° sweeps. 1000# test pull string is to be installed

by customer where possible without entering or working on any City of Seguin equipment.

Copper-clad ground rods, 5/8" x 8', 1 required, to have 4" projection above top on concrete.

Transformer Pad shall be a minimum of 8" thick from top to bottom.

All primary and secondary stub cuts shall be 5' minimum.

3/8" Re-bar 12" on center

Final Grade

Ground RodConduit

Secondary

Conduits

Primary

Conduits

GRD RODGRD ROD

AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
14"
AutoCAD SHX Text
62"
AutoCAD SHX Text
67"
AutoCAD SHX Text
8"
AutoCAD SHX Text
13"
AutoCAD SHX Text
13"
AutoCAD SHX Text
14"
AutoCAD SHX Text
4"
AutoCAD SHX Text
5"
AutoCAD SHX Text
17"
AutoCAD SHX Text
4"
AutoCAD SHX Text
17"
AutoCAD SHX Text
28" Open Box
Page 50: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

This specification shall be used only in conjunction with the City of Seguin Electrical Connection Policy and may not reflect all requirements of a specific

installation.

Locations are determined by the City of Seguin. All customer installations require inspection by the City of Seguin.

Underground conduit installed according to the City of Seguin specification SEEU-910. Conduit to be sized by the City of Seguin and have 5" projection

above concrete, 36" radius, 90° sweeps. A 1000# test pull string to be installed by customer where possible without entering or working on any City of

Seguin equipment.

Copper-clad ground rods, 5'8" x 8', 2 required, to have 4" projection above top of concrete.

Switch Cabinet Pad shall be a minimum of 8" thick from top to bottom.

All primary and secondary stub cuts shall be 5" minimum.

FINAL GRADE

CONDUIT GROUND ROD

AutoCAD SHX Text
AIS-9 SWITCH CABINET CONCRETE PAD
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SEEU-530
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 9/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 51: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

This specification shall be used only in conjunction with the City of Seguin Electrical Connection Policy and may not

reflect all requirements of a specific installation.

Locations are determined by the City of Seguin. All customer installations require inspection by the City of Seguin..

Pole and bracket installed by the city of Seguin.

Conduit size will be specified by the City of Seguin

for each project.

Riser must be plumb with pole and attached to a

stand off bracket.

Underground conduit installed according to the City

of Seguin specification SEEU-910. Conduit to be

sized by the City of Seguin. Conduit sweep to be a

minimum of 24" radius and be GRC, IMC or Rigid

Aluminum. A 1000# test pull string is to be installed

by customer where possible without entering or

working on any City of Seguin equipment.

PRIMARY

NEUTRAL

FINAL GRADE

Offset from pole to center of conduit shall be as

follows:

3" Conduit = 9"

2" Conduit = 8 1/2"

Extend one 10' joint of GRC, IMC or Rigid

Aluminum so that it is a minimum of 5' above final

grade with either a coupling at the top or threaded

to receive a coupling. Rigid will be installed 18"

below grade for protection per 300-5(d) NEC.

1ST RISER

BRACKET

SEEU-800

NTS

STUB OUT ON POLE RISER

AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 52: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

Multi-phase service

Single-phase service

Primary

Secondary

Caution: Buried Electric Cable

18" min.

12" to 18"

Final Ground Grade

Communication

Cable (opt)

54" min.

24" min.

STREET

A

B

C

C

B

A

Mound earth 3" to 4" above final ground grade.

Communication cable/conduit shall be installed

above all electrical conduit(s) and caution tape.

A 6" wide plastic caution tape, red or yellow in color

with black lettering reading, "Caution: Buried

Electric Cable Below", will be placed in the trench

12" to 18" above electrical conduit but below any

communication cables. For more than 2 conduits

horizontally in trench, 2 tapes shall be installed.

Customer shall excavate trench to proper depth and

install PVC Schedule 40 Electrical Conduit NEMA

TC 2. Conduit elbows (sweeps) for primary shall

have 36" radius. Conduit elbows for secondary shall

have 18" radius. Conduit shall be sized by NBU.

Where electrical equipment foundations (for

transformers, junctions boxes, switchgear) lie on top

of trench line, the foundation area shall be back

filled with compacted base for the entire depth of the

trench.

Trenches which cross or will be under streets,

commercial driveways, or parking lots shall be back

filled with compacted base material or washed sand.

Customer to furnish and install 1000# test pull string.

No pipe, gas, or water line shall be closer than 36"

vertically or horizontally from any underground

electrical conductor.

At no time shall any electric line, primary or

secondary, be connected for service if found to

cross under any building foundation.

7" (TYP)

7" (TYP)

This specification shall be used only in conjunction with the City of Seguin Electrical Connection

Policy and may not reflect all requirements of a specific job.

Locations are determined by the City of Seguin electrical engineering department. All customer

installations require inspection by the City of Seguin electrical engineering department.

All Primary and Secondary stubouts shall be 5' minimum.

For multi-phase service, conductor phase

orientation shall be as shown unless approved

otherwise by the City of Seguin electrical

engineering department.

SEEU-910

UNDERGROUND CONDUIT

INSTALLATION

NTS

AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 53: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

SINGLE PHASE

6 POLE C.T. METERING

NTS SEM1-1

TITLE

SCALE DRAWING NO.

DATE ISSUED: 09/28/2010

NOTES:

1. WHITE REPRESENTED AS GREY

2. LID MUST CLOSE WITH SWITCHES OPEN

X3

X1

X1X2

X2 X1

AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 54: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

THREE PHASE

10 POLE C.T. METERING

NTS SEM3-1

TITLE

SCALE DRAWING NO.

DATE ISSUED: 09/28/2010

NOTES:

1. WHITE REPRESENTED AS GREY

2. LID MUST CLOSE WITH SWITCHES OPEN

X3

X1X2

X2

X1X2

X1

X1X2

AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 55: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
Primary Enclosure Grounding Assembly
AutoCAD SHX Text
NTS
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
SEPEGRND
AutoCAD SHX Text
** CONDUCTOR LARGER THAN 1/0 MUST USE LARGE CONDUCTOR APPLICATION
AutoCAD SHX Text
OPTIONS ARE A0, B0, C1, A2, B2
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
SEPEGRND
Page 56: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
Primary Enclosure Grounding Assembly
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SEPEGRND
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
cj
AutoCAD SHX Text
rc
AutoCAD SHX Text
rc
AutoCAD SHX Text
200 AMP 1 ENCLOSURE APPLICATION
AutoCAD SHX Text
PEGRNDA_
AutoCAD SHX Text
TANK
AutoCAD SHX Text
cj
AutoCAD SHX Text
rc
AutoCAD SHX Text
cu
AutoCAD SHX Text
bw
AutoCAD SHX Text
bo
AutoCAD SHX Text
cu
AutoCAD SHX Text
cj
AutoCAD SHX Text
600 AMP 3 3 & 4 PLACE ENCLOSURE APPLICATION
AutoCAD SHX Text
rc
AutoCAD SHX Text
PEGRNDC_
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
TANK
AutoCAD SHX Text
cj
AutoCAD SHX Text
rc
AutoCAD SHX Text
cu
AutoCAD SHX Text
cu
AutoCAD SHX Text
cj
AutoCAD SHX Text
200 AMP 3 3 & 4 PLACE ENCLOSURE APPLICATION
AutoCAD SHX Text
rc
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
PEGRNDB_
AutoCAD SHX Text
sb
AutoCAD SHX Text
sb
AutoCAD SHX Text
sb
AutoCAD SHX Text
sb
AutoCAD SHX Text
ADD NEUTRAL BUSS ON 4/0 AND LARGER CONDUCTORS.
Page 57: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

3-PHASE PADMOUNT

DEADFRONT SWITCH GEAR

ASSEMBLY PAD

600A 25 Kv 125Kv BIL

*CONDUIT POSITIONS MUST BE APPROVED

BY THE CITY OF SEGUIN ELECTRICAL

ENGINEERING DEPARTMENT PRIOR TO

CONSTRUCTION

6"

13" 12" 12" 22" 12" 12" 13"

22

1

2

"

96"

23"

17

3

4

" 19" 17

1

2

"

S

200 AMP SIDE

96"

12" MIN

4"

1"

4"

FINAL

GROUND GRADE

UNDISTURBED EARTH

OR COMPACTED FILL

8' X 5/8" COPPER

ROUND ROD

3/8" REBAR (MIN)

12" OC

8' X 5/8" COPPER

ROUND ROD

TOP VIEW

S = SPARE CONDUIT

HWY 46

SIDE VIEW

A B C

C B AA B C

C B AA B C

*ANCHOR BOLTS TO

SECURE SWITCH WILL

BE INSTALLED BY THE

CITY OF SEGUIN

WASHED GRAVEL

OR OTHER APPROVED MATERIAL FROM

BOTTOM OF TRENCH TO BOTTOM OF FDTN

8' X 5/8" COPPER

GROUND ROD

13"

3" 3" 3"

4" 4" 4"4" 4" 4"

4"4"

10

1

2

" 10

1

2

" 10

1

2

" 10

1

2

"

3"3"3"

ABC

S

600 AMP SIDE

17"

17"

48"

2"

200 AMP SIDE

600 AMP SIDE

14"

13"

14"

13"

14"

13"

14"

8' X 5/8" COPPER

GROUND ROD

8' X 5/8" COPPER

GROUND ROD

8' X 5/8" COPPER

GROUND ROD

2"

2" PVC FOR

GROUNDING CONDUCTOR

6"

47"

47"

6"

7"

This specification shall be used only in conjunction with the City of Seguin Electrical Connection Policy and

may not reflect all requirements of a specific installation.

Locations are determined by the City of Seguin electrical engineering department. All customer

installations require inspection by the CIty of Seguin electrical engineering department.

Underground conduit to be installed according to City of Seguin specification SEEU-910.

Conduit to be sized by the City of Seguin and have 1" projection above concrete, 36" radius, 90° sweeps.

1000# test pull string to be installed by customer.

Concrete to be 4 sack mix minimum.

NTS

SESG1

TITLE

SCALE DRAWING NO.

DATE ISSUED: 09/28/2010

SWITCH GEAR DESIGN #1

AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 58: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

14"

13"

6"

13" 12" 12" 20

1

4

" 10

1

2

" 10

1

2

" 17

3

4

"

22

1

2

"

96"

23"

17

3

4

" 18

1

2

" 17

3

4

"

S

200 AMP SIDE

96"

12" MIN

4"

1"

4"

FINAL

GROUND GRADE

UNDISTURBED EARTH

OR COMPACTED FILL

8' X 5/8" COPPER

ROUND ROD

3/8" REBAR (MIN)

12" OC

8' X 5/8" COPPER

ROUND ROD

TOP VIEW

S = SPARE CONDUIT

SIDE VIEW

A B C

C B AA B C

*ANCHOR BOLTS TO

SECURE SWITCH WILL

BE INSTALLED BY THE

CITY OF SEGUIN

3-PHASE PADMOUNT

DEADFRONT SWITCH GEAR

ASSEMBLY PAD

600A 25 Kv 125Kv BIL

WASHED GRAVEL

OR OTHER APPROVED MATERIAL FROM

BOTTOM OF TRENCH TO BOTTOM OF FDTN

8' X 5/8" COPPER

GROUND ROD

14"

13"

3"

10

1

2

" 10

1

2

" 10

1

2

" 10

1

2

"

4"

8' X 5/8" COPPER

GROUND ROD

8' X 5/8" COPPER

GROUND ROD

8' X 5/8" COPPER

GROUND ROD

23"

C B A

3"3"

4"

4" 4"

4" 4" 4"

4"

4"4"4"

4"

S

S

600 AMP SIDE

C B ACBA

600 AMP SIDE600 AMP SIDE

17"

2"

17"

2"

14"

13"

14"

13"

STREET

2" PVC FOR

GROUNDING CONDUCTOR

6"

47"

46"

6"

7"

NTS

SESG2

TITLE

SCALE DRAWING NO.

DATE ISSUED: 09/28/2010

SWITCH GEAR DESIGN #2

AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 59: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
STREET LIGHT ALUMINUM STANDARD
AutoCAD SHX Text
NTS
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
SESLAS
AutoCAD SHX Text
SESLAS
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
Page 60: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SESLAS
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
b
AutoCAD SHX Text
q
AutoCAD SHX Text
as
AutoCAD SHX Text
bonding attachment
AutoCAD SHX Text
k-g
AutoCAD SHX Text
cu
AutoCAD SHX Text
SPECIFY PAD UNIT SEPARATELY.
AutoCAD SHX Text
NOTE:
AutoCAD SHX Text
STREET LIGHT ALUMINUM STANDARD
AutoCAD SHX Text
*SEE SPEC SEWDSL FOR FOR CONNECTION.
Page 61: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
STREET LIGHT WOOD POLE APPLICATION
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SESLPW
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
SESLPW
Page 62: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
6"
AutoCAD SHX Text
c-aw
AutoCAD SHX Text
b
AutoCAD SHX Text
c-aw-d
AutoCAD SHX Text
o
AutoCAD SHX Text
g
AutoCAD SHX Text
STREET LIGHT WOOD POLE APPLICATION
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SESLPW
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
*SEE SPEC SEWDSL FOR FOR CONNECTION.
AutoCAD SHX Text
q
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
Page 63: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
STREET LIGHT RISER FOR WOOD OR STEEL CONSTRUCTION
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SESLR
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
SESLR
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
Page 64: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
6"
AutoCAD SHX Text
e-s
AutoCAD SHX Text
pc (1st 10')
AutoCAD SHX Text
gc
AutoCAD SHX Text
STREET LIGHT RISER FOR WOOD OR STEEL CONSTRUCTION
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SESLR
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
Page 65: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

SEUM26-6__

AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DATE
AutoCAD SHX Text
STREET LIGHT (ALUMINUM STANDARD)
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SEUM26-6__
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
Page 66: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

b

q

as

gl

cg

k

cu

p

l

SPECIFY PAD UNIT SEPARATELY.

NOTE:

cg

m-n

AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DATE
AutoCAD SHX Text
STREET LIGHT (ALUMINUM STANDARD)
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SEUM26-6__
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
Page 67: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
SEURSB
AutoCAD SHX Text
SEURSB-UNDERGROUND -UNDERGROUND RISER SWITCH- BRACKET MOUNTED
AutoCAD SHX Text
NTS
AutoCAD SHX Text
MATERIAL
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
Page 68: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
48"
AutoCAD SHX Text
48"
AutoCAD SHX Text
*JUMPER LENGTHS AS REQUIRED
AutoCAD SHX Text
s
AutoCAD SHX Text
brk
AutoCAD SHX Text
c-dd-aw
AutoCAD SHX Text
rn-tb
AutoCAD SHX Text
t
AutoCAD SHX Text
t
AutoCAD SHX Text
t
AutoCAD SHX Text
FLEXIBLE CONDUIT HOLDER
AutoCAD SHX Text
RIV NUT & GRD LUG
AutoCAD SHX Text
10' FIBERGLASS CROSSARM
AutoCAD SHX Text
LIGHTNING ARRESTOR
AutoCAD SHX Text
CONDUCTOR ATTACHMENT
AutoCAD SHX Text
42"
AutoCAD SHX Text
36"
AutoCAD SHX Text
RIV NUT & GRD LUG
AutoCAD SHX Text
NEUTRAL
AutoCAD SHX Text
CONCENTRIC NEUTRAL
AutoCAD SHX Text
UNDERGROUND RISER SWITCH- BRACKET MOUNTED
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SEURSB
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
Page 69: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
NTS
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
UNDERGROUND RISER SWITCH- NO SWITCH
AutoCAD SHX Text
SEURS-NS
AutoCAD SHX Text
SEURS-NS
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
Page 70: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
UNDERGROUND RISER SWITCH- NO SWITCH
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SEURS-NS
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
84"
AutoCAD SHX Text
60"
AutoCAD SHX Text
N
AutoCAD SHX Text
*JUMPER LENGTHS AS REQUIRED
AutoCAD SHX Text
ip-bd-pla-d-aw
AutoCAD SHX Text
*
AutoCAD SHX Text
t
AutoCAD SHX Text
z
Page 71: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
SEURSX
AutoCAD SHX Text
SEURSX-UNDERGROUND -UNDERGROUND RISER WITH (3) 100 AMP CUTOUTS
AutoCAD SHX Text
NTS
AutoCAD SHX Text
MATERIAL
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
Page 72: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
36"
AutoCAD SHX Text
s
AutoCAD SHX Text
d-e-f
AutoCAD SHX Text
c
AutoCAD SHX Text
8' FIBERGLASS HEAVY DUTY CROSSARM
AutoCAD SHX Text
FLEXIBLE CONDUIT HOLDER
AutoCAD SHX Text
CONDUCTOR ATTACHMENT
AutoCAD SHX Text
42"
AutoCAD SHX Text
36"
AutoCAD SHX Text
RIV NUT & GRD LUG
AutoCAD SHX Text
NEUTRAL
AutoCAD SHX Text
CONCENTRIC NEUTRAL
AutoCAD SHX Text
RIV NUT & GRD LUG
AutoCAD SHX Text
*JUMPER LENGTHS AS REQUIRED
AutoCAD SHX Text
UNDERGROUND RISER WITH (3) 100 AMP CUTOUTS
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SEURSX
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
Page 73: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
NTS
AutoCAD SHX Text
WSERS1
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 9/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
SERS1
AutoCAD SHX Text
*Add spare riser conduit if pole is 45' or greater. *See reference sheet for primary & neutral connections.
AutoCAD SHX Text
SINGLE PHASE PRIMARY RISER FOR WOOD/STEEL CONSTRUCTION
Page 74: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
Neutral
AutoCAD SHX Text
36"
AutoCAD SHX Text
60"
AutoCAD SHX Text
12"
AutoCAD SHX Text
12"
AutoCAD SHX Text
ugk
AutoCAD SHX Text
cap
AutoCAD SHX Text
usc
AutoCAD SHX Text
tb-rn
AutoCAD SHX Text
uso
AutoCAD SHX Text
pc
AutoCAD SHX Text
cj
AutoCAD SHX Text
*
AutoCAD SHX Text
c-d-aw
AutoCAD SHX Text
SINGLE PHASE PRIMARY RISER FOR WOOD/STEEL CONSTRUCTION
AutoCAD SHX Text
NTS
AutoCAD SHX Text
WSERS1
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
DATE ISSUED: 9/28/2010
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
*
AutoCAD SHX Text
cu
AutoCAD SHX Text
*Connectors as required
AutoCAD SHX Text
P
AutoCAD SHX Text
STIRRUP
AutoCAD SHX Text
HOTLINE CLAMP
AutoCAD SHX Text
12" STANDOFF BRACKET
AutoCAD SHX Text
N
AutoCAD SHX Text
1Ø FIBERGLASS CROSSARM
AutoCAD SHX Text
1Ø FIBERGLASS CROSSARM
Page 75: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from

*******

AutoCAD SHX Text
Add spare riser conduit when pole height is over 45'
AutoCAD SHX Text
CUT OUT SIZE AS REQUIRED
AutoCAD SHX Text
SERS3
AutoCAD SHX Text
SEE REFERENCE SHEETC CC1 & CC2 FOR PRIMARY & NEUTRAL CONNECTORS
AutoCAD SHX Text
WSERS3-3 PHASE -3 PHASE PRIMARY RISER FOR WOOD/STEEL CONSTRUCTION
AutoCAD SHX Text
NTS
AutoCAD SHX Text
MATERIAL
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DATE ISSUED: 09/28/2010
Page 76: UNDERGROUND SERVICE UD... · appropriate metering assembly specification. 2) Other conditions, as contained in this policy, may apply. 3) Underground service can be provided from
AutoCAD SHX Text
Neutral
AutoCAD SHX Text
12"
AutoCAD SHX Text
ugk
AutoCAD SHX Text
cap
AutoCAD SHX Text
usc
AutoCAD SHX Text
pc
AutoCAD SHX Text
uso
AutoCAD SHX Text
cu
AutoCAD SHX Text
tb-rn
AutoCAD SHX Text
c-d-aw
AutoCAD SHX Text
cj
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
gl
AutoCAD SHX Text
ALL JUMPERS LENGTH AND SIZE AS REQUIRED
AutoCAD SHX Text
*
AutoCAD SHX Text
rn-gl
AutoCAD SHX Text
*SEE APPENDIX FOR GROUNDING DIAGRAM
AutoCAD SHX Text
STIRRUP
AutoCAD SHX Text
HOTLINE CLAMP
AutoCAD SHX Text
Fiberglass arm
AutoCAD SHX Text
Neutral
AutoCAD SHX Text
CONCENTRIC NEUTRAL
AutoCAD SHX Text
CONCENTRIC NEUTRAL
AutoCAD SHX Text
CONCENTRIC NEUTRAL
AutoCAD SHX Text
3 PHASE PRIMARY RISER FOR WOOD/STEEL CONSTRUCTION
AutoCAD SHX Text
NTS
AutoCAD SHX Text
WSERS3
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DATE ISSUED: 09/28/2010