underground tank with indoor use & drip irrigation · underground tank with indoor use &...

9
Underground Tank with Indoor Use & Drip Irrigation Illustrations are for refernce only, other components & designs are acceptable with the approval of Design Engineer and AHJ ©2015 Building in California illustrations by Paddy Morrissey 1 1 2 2 3 3 4 5 6 7 8 9 10 1 Ballast & hold-down required to prevent uplift and shall meet the design standards of the designer and approval by the AHJ Treated & disinfected stormwater Potable water shall be a minimum of 12 in. above untreated stormwater See 3A & 3B for floating inlet alternatives p.3 See detail for airgap alternative p. 6 & 7 Stormwater

Upload: others

Post on 29-Dec-2019

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Underground Tank with Indoor Use & Drip Irrigation · Underground Tank with Indoor Use & Drip Irrigation Illustrations are for refernce only, other components & designs are acceptable

Underground Tank with Indoor Use & Drip IrrigationIllustrations are for refernce only, other components & designs are acceptable with the approval of Design Engineer and AHJ

©2015 Building in Californiaillustrations by Paddy Morrissey

1

1

2

2

3

3

4

5

6

7

89

10

1

Ballast & hold-down required to prevent uplift and shall meet the design standards of the designer and approval by the AHJ

Treated & disinfected stormwater

Potable water shall be a minimum of 12 in. above untreated stormwater

See 3A & 3B for floating inlet alternatives p.3

See detail for airgap alternativep. 6 & 7

Stormwater

Page 2: Underground Tank with Indoor Use & Drip Irrigation · Underground Tank with Indoor Use & Drip Irrigation Illustrations are for refernce only, other components & designs are acceptable

Underground Tank with Indoor Use & Drip IrrigationIllustrations are for refernce only, other components & designs are acceptable with the approval of Design Engineer and AHJ

©2015 Building in Californiaillustrations by Paddy Morrissey

2

Catch basin with media filter

Connections to catch basins and vortex filters shall be through manufacturers’ supplied and ap-proved connections or shall be installed with watertight rings or grommets conforming to ASTM C 923 for concrete structures. Field applied PVC & CPVC bulkhead fittings shall conform to ASTM 1784. Polypropelene bulkhead fittings shall conform to ASTM D 4101.

Vortex filter NOTE: Not all vortex filters or hydrodynamic separators include debris excluders

1

2

Page 3: Underground Tank with Indoor Use & Drip Irrigation · Underground Tank with Indoor Use & Drip Irrigation Illustrations are for refernce only, other components & designs are acceptable

Underground Tank with Indoor Use & Drip IrrigationIllustrations are for refernce only, other components & designs are acceptable with the approval of Design Engineer and AHJ

©2015 Building in Californiaillustrations by Paddy Morrissey

3

3

3A

4

Floating suction inlet with bronze check valve. Check valve acts as a foot valve to maintain prime at pump.NOTE: Floating inlet not only device to accomplish drawing water from tank. Vertical piping may use foot valve and only requirement is water shall be drawn a minimum 4 in. from bottom of tank

Calming inlet and mercury-free float switch.

3B

4 in. min. 4 in. min.

To pump

To pump

Check valveFoot valve

Page 4: Underground Tank with Indoor Use & Drip Irrigation · Underground Tank with Indoor Use & Drip Irrigation Illustrations are for refernce only, other components & designs are acceptable

Underground Tank with Indoor Use & Drip IrrigationIllustrations are for refernce only, other components & designs are acceptable with the approval of Design Engineer and AHJ

©2015 Building in Californiaillustrations by Paddy Morrissey

4

5 6 7

Locking manhole cover to prevent unuthorized entry.

Minimum 24 in. manhole cover with ring extension

Cover shall be a minimum 4 in. above grade

Vent with 1/8 in. or 3175 micron bug screen to prevent mosquitos and insectsBackwater valve on tank over-

flow. Overflow pipe discharges to bio-swale, raingarden, infiltration device or other approved location. All exposed openings shall be screened with 1/8 in. screen mesh.

See detail example on p.5 forinfiltration device

Page 5: Underground Tank with Indoor Use & Drip Irrigation · Underground Tank with Indoor Use & Drip Irrigation Illustrations are for refernce only, other components & designs are acceptable

Underground Tank with Indoor Use & Drip IrrigationIllustrations are for refernce only, other components & designs are acceptable with the approval of Design Engineer and AHJ

©2015 Building in Californiaillustrations by Paddy Morrissey

5

5A Infiltration Device

Cleanout cover

Manhole may be required for cleaning access

Overflow from storm-water tank

Percolation rates shall bedetermined prior to installationof infiltration devices.

Sample sediment filtration prior to tank inlet

Choose filtration and sediment trap suitable for application

Infiltration Device

Page 6: Underground Tank with Indoor Use & Drip Irrigation · Underground Tank with Indoor Use & Drip Irrigation Illustrations are for refernce only, other components & designs are acceptable

Underground Tank with Indoor Use & Drip IrrigationIllustrations are for refernce only, other components & designs are acceptable with the approval of Design Engineer and AHJ

©2015 Building in Californiaillustrations by Paddy Morrissey

6

Domestic water shut-off

From domestic meter or supply

Reduced pressure backflow device isolation valves

Reduced pressure backflow device

Solonoid valve

Globe valve or circuit setter optional for

throttling & smoothing make-up water

Tank make-up water

8

Air Gap Alternative 1

2X diameter of supplynot less than 1 in.

To tank calming inlet

Solonoid valve

Page 7: Underground Tank with Indoor Use & Drip Irrigation · Underground Tank with Indoor Use & Drip Irrigation Illustrations are for refernce only, other components & designs are acceptable

Underground Tank with Indoor Use & Drip IrrigationIllustrations are for refernce only, other components & designs are acceptable with the approval of Design Engineer and AHJ

©2015 Building in Californiaillustrations by Paddy Morrissey

7

Solonoid valve

2X diameter of supply, not less than 1 in.

Bell reducerlined with1/8 in. screenmesh

Trap primer and P trap shallbe used where the lengthof the calming inlet couldbecome a fouling area &release odors.

Trap primer water shall comefrom pressureized rain water,downstream of particulatefilters & upstream fromdisinfection.

Service valve &Trap primer

Domestic water make-up

Air Gap Alternative 2

To tank calming inlet

Page 8: Underground Tank with Indoor Use & Drip Irrigation · Underground Tank with Indoor Use & Drip Irrigation Illustrations are for refernce only, other components & designs are acceptable

Underground Tank with Indoor Use & Drip IrrigationIllustrations are for refernce only, other components & designs are acceptable with the approval of Design Engineer and AHJ

©2015 Building in Californiaillustrations by Paddy Morrissey

8

9

100 micron filter

On demand pump (does not require a pressure tank)

Depending on pump type & pressure switch, pressure regulator may be required.

Pump inlet from tank

Priming inlet

Outlet for tank pump out

To drip irrigation

(20-30 psi)Swing check valve

Page 9: Underground Tank with Indoor Use & Drip Irrigation · Underground Tank with Indoor Use & Drip Irrigation Illustrations are for refernce only, other components & designs are acceptable

Underground Tank with Indoor Use & Drip IrrigationIllustrations are for refernce only, other components & designs are acceptable with the approval of Design Engineer and AHJ

©2015 Building in Californiaillustrations by Paddy Morrissey

9

Typical small pressure tank & pump set up

Level of treatment required is dependent on beneficial use & local water quality standards for that use. Water shall be tested to determine acceptable level of treatment. Check with the AHJ for treatment & use requirements.

Ultraviolet disinfection

To house, common laundry room & toilet flushing

Primer inlet

From tank

Swing check valve

20 micronfilter

5 micronfilter

Carbon block filter

10