understand how a good heating system design on paper can

47
Positive Condensate Drainage from Heat Transfer Equipment under Modulating Steam Conditions Understand how a good heating system design on paper can become a big problem once installed. November 13, 2017 CNY Expo -

Upload: others

Post on 23-Jan-2022

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Understand how a good heating system design on paper can

Positive Condensate Drainage from Heat Transfer Equipment under Modulating Steam Conditions

Understand how a good heating system design on paper can become a big problem once installed

November 13 2017 CNY Expo -

Looked Good on Paperhellip

Types of Heat Transfer

DirectThe heating medium is directly mixed (convection) with the

substance being heated ie ldquoDirect injectionrdquo

Indirect(Heat Exchange Equipment)

Heat energy from the heating medium is passed to the substance being heated through a physical barrier (conduction)

Steam Heat Transfer 101

1 Steam Supply 2 Heat Transfer 3 Condensate Removal

Heat Exchanger Flow

Heat Exchanger Sizing

Q = U x A x ∆T where U = K (dx Fouling Factors)

dX A

Type amp Thickness of Materials of Construction

Copper

Copper

Stainless Steel

Double Wall

Standard HX sizes163- 258- 352- 446- 540- 634- 729- 823- 917-SQFT

Example 887760 = 324 x 274 x 100

Application requires 274 SQFT but the closest suitable size is 352 SQFT

Therefore the HX starts over-sized by 285

Normal Operation

Heat Exchanger

P2

P1

Product Temperature Input

P1 gt P2 = Heat Exchanger Dry

Vacuum = Negative Differential Pressure

Steam occupies 1675 times the amount of space than water

When steam condenses in a ldquoClosed-Systemrdquo a vacuum is created

3 ft

3 ft

3 ft

Conventional Condensate Removal

System Pressure Modulating vs Constant

Pre

ssu

reP

ress

ure

Time

Time

Modulating Steam Traps

Inverted Bucketbull Continuous Steam ndash Goodbull Intermittent (OnOff) Steam ndash Poorbull Economical Choice Metal-on-Metal

Float amp Thermostaticbull Continuous Steam ndash Excellentbull Intermittent (OnOff) Steam ndash Excellentbull Optimum Choice for Process

Valve Head amp Seat

Float Mechanism

Air Vent

Downstream Lift = System Back Pressure

Heat Exchanger

Stall Condition ndash No Steam Supply

P2

Product Temperature Input

P1ltP2=Heat Exchanger Flooded

P1

Stall Chart

StallPump Mode

Trap Mode

65 = Stallof Load Point

What does a stall chart not take into consideration

Domestic Hot Water

15 PSIG Steam Supply 250F

40F to 140F 100 GPM

0 PSIG Back-Pressure 212F

(aka Gravity-Drain)

After HX is selectedhellipnow the real world

For real-world conditions

Q = U x A x ∆T where U = K (dx)

Domestic WaterFlow Rate Varies with demand typically low to no flow in evening hours

Building HeatFlow rate varies with VFDs responding to demand

Less flow requires less flow of heat (Q)

Domestic WaterIncoming water temperature rises in summer months

Building HeatOutside Air Temperature rises is summer months

Both reduce ∆T requiring less flow of heat

Saturated Steam Table

Actual Stall Conditions40F to 140F 100 GPM using 15 PSIG Steam Supply

Heat Load Summary - Calculating Stall

Flow Rate (GPM)

Heat Load(BTUhr)

Steam Tempin HX

(F)

Steam Pressurein HX(PSIG)

Latent Heat of Steam(BTUs)

Steam amp Condensate Flow

(lbshr)

Trap Differential

(ΔP)

System Condition

100 5004000 2455 1287 9486 5275 1287 Trap Mode

95 4753800 2377 927 9538 4984 927 Trap Mode

85 4253400 2222 325 9638 4413 325 Trap Mode

75 3753000 2066 -149 9737 3854 -149 Stall - Pump Mode

65 3252600 1911 -512 9832 3308 -512 Stall - Pump Mode

50 2502000 1678 -899 9974 2509 -899 Stall - Pump Mode

25 1251000 1289 -1253 10203 1226 -1253 Stall - Pump Mode

15 750600 1133 -1329 10297 729 -1329 Stall - Pump Mode

10 500400 1056 -1357 10337 484 -1357 Stall - Pump Mode

5 250200 978 -1381 10381 241 -1381 Stall - Pump Mode

Reasons for System Stall

bull Overly conservative fouling factors during HEX design ndash adds additional surface area

bull Back pressure at equipment discharge ndash elevation or static pressure

bull Modulating Control ndash Steam pressure

bull Vacuum

bull Process demands- Flow or temp changes

bull Oversized equipment ndash excess surface area

Effects of System Stall

bull Inadequate condensate drainage

bull Water hammer (Thermal Shock)

bull Frozen coils damaged tube bundles

bull Poor temperature control

bull Control valve hunting ndash control stability

bull Reduction in heat transfer capacity

Pumping Condensate

bull Whatrsquos unique about condensatebull High temperature fluid

bull Constant phase change or flashing

bull Intermittent supply inconsistent suction head

2 Types of Condensate Pumps1 Electric Pumps

2 Pressure-Powered Pumps

Electric Pump Operation

What does a lower pressure due to the boiling pointLowers saturation pointGenerates flash steamFlash steam causes cavitation

Vent = Energy Loss

What is Flash Steam

Flash Capacity Calculation

Return amp Vent Sizing

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 2: Understand how a good heating system design on paper can

Looked Good on Paperhellip

Types of Heat Transfer

DirectThe heating medium is directly mixed (convection) with the

substance being heated ie ldquoDirect injectionrdquo

Indirect(Heat Exchange Equipment)

Heat energy from the heating medium is passed to the substance being heated through a physical barrier (conduction)

Steam Heat Transfer 101

1 Steam Supply 2 Heat Transfer 3 Condensate Removal

Heat Exchanger Flow

Heat Exchanger Sizing

Q = U x A x ∆T where U = K (dx Fouling Factors)

dX A

Type amp Thickness of Materials of Construction

Copper

Copper

Stainless Steel

Double Wall

Standard HX sizes163- 258- 352- 446- 540- 634- 729- 823- 917-SQFT

Example 887760 = 324 x 274 x 100

Application requires 274 SQFT but the closest suitable size is 352 SQFT

Therefore the HX starts over-sized by 285

Normal Operation

Heat Exchanger

P2

P1

Product Temperature Input

P1 gt P2 = Heat Exchanger Dry

Vacuum = Negative Differential Pressure

Steam occupies 1675 times the amount of space than water

When steam condenses in a ldquoClosed-Systemrdquo a vacuum is created

3 ft

3 ft

3 ft

Conventional Condensate Removal

System Pressure Modulating vs Constant

Pre

ssu

reP

ress

ure

Time

Time

Modulating Steam Traps

Inverted Bucketbull Continuous Steam ndash Goodbull Intermittent (OnOff) Steam ndash Poorbull Economical Choice Metal-on-Metal

Float amp Thermostaticbull Continuous Steam ndash Excellentbull Intermittent (OnOff) Steam ndash Excellentbull Optimum Choice for Process

Valve Head amp Seat

Float Mechanism

Air Vent

Downstream Lift = System Back Pressure

Heat Exchanger

Stall Condition ndash No Steam Supply

P2

Product Temperature Input

P1ltP2=Heat Exchanger Flooded

P1

Stall Chart

StallPump Mode

Trap Mode

65 = Stallof Load Point

What does a stall chart not take into consideration

Domestic Hot Water

15 PSIG Steam Supply 250F

40F to 140F 100 GPM

0 PSIG Back-Pressure 212F

(aka Gravity-Drain)

After HX is selectedhellipnow the real world

For real-world conditions

Q = U x A x ∆T where U = K (dx)

Domestic WaterFlow Rate Varies with demand typically low to no flow in evening hours

Building HeatFlow rate varies with VFDs responding to demand

Less flow requires less flow of heat (Q)

Domestic WaterIncoming water temperature rises in summer months

Building HeatOutside Air Temperature rises is summer months

Both reduce ∆T requiring less flow of heat

Saturated Steam Table

Actual Stall Conditions40F to 140F 100 GPM using 15 PSIG Steam Supply

Heat Load Summary - Calculating Stall

Flow Rate (GPM)

Heat Load(BTUhr)

Steam Tempin HX

(F)

Steam Pressurein HX(PSIG)

Latent Heat of Steam(BTUs)

Steam amp Condensate Flow

(lbshr)

Trap Differential

(ΔP)

System Condition

100 5004000 2455 1287 9486 5275 1287 Trap Mode

95 4753800 2377 927 9538 4984 927 Trap Mode

85 4253400 2222 325 9638 4413 325 Trap Mode

75 3753000 2066 -149 9737 3854 -149 Stall - Pump Mode

65 3252600 1911 -512 9832 3308 -512 Stall - Pump Mode

50 2502000 1678 -899 9974 2509 -899 Stall - Pump Mode

25 1251000 1289 -1253 10203 1226 -1253 Stall - Pump Mode

15 750600 1133 -1329 10297 729 -1329 Stall - Pump Mode

10 500400 1056 -1357 10337 484 -1357 Stall - Pump Mode

5 250200 978 -1381 10381 241 -1381 Stall - Pump Mode

Reasons for System Stall

bull Overly conservative fouling factors during HEX design ndash adds additional surface area

bull Back pressure at equipment discharge ndash elevation or static pressure

bull Modulating Control ndash Steam pressure

bull Vacuum

bull Process demands- Flow or temp changes

bull Oversized equipment ndash excess surface area

Effects of System Stall

bull Inadequate condensate drainage

bull Water hammer (Thermal Shock)

bull Frozen coils damaged tube bundles

bull Poor temperature control

bull Control valve hunting ndash control stability

bull Reduction in heat transfer capacity

Pumping Condensate

bull Whatrsquos unique about condensatebull High temperature fluid

bull Constant phase change or flashing

bull Intermittent supply inconsistent suction head

2 Types of Condensate Pumps1 Electric Pumps

2 Pressure-Powered Pumps

Electric Pump Operation

What does a lower pressure due to the boiling pointLowers saturation pointGenerates flash steamFlash steam causes cavitation

Vent = Energy Loss

What is Flash Steam

Flash Capacity Calculation

Return amp Vent Sizing

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 3: Understand how a good heating system design on paper can

Types of Heat Transfer

DirectThe heating medium is directly mixed (convection) with the

substance being heated ie ldquoDirect injectionrdquo

Indirect(Heat Exchange Equipment)

Heat energy from the heating medium is passed to the substance being heated through a physical barrier (conduction)

Steam Heat Transfer 101

1 Steam Supply 2 Heat Transfer 3 Condensate Removal

Heat Exchanger Flow

Heat Exchanger Sizing

Q = U x A x ∆T where U = K (dx Fouling Factors)

dX A

Type amp Thickness of Materials of Construction

Copper

Copper

Stainless Steel

Double Wall

Standard HX sizes163- 258- 352- 446- 540- 634- 729- 823- 917-SQFT

Example 887760 = 324 x 274 x 100

Application requires 274 SQFT but the closest suitable size is 352 SQFT

Therefore the HX starts over-sized by 285

Normal Operation

Heat Exchanger

P2

P1

Product Temperature Input

P1 gt P2 = Heat Exchanger Dry

Vacuum = Negative Differential Pressure

Steam occupies 1675 times the amount of space than water

When steam condenses in a ldquoClosed-Systemrdquo a vacuum is created

3 ft

3 ft

3 ft

Conventional Condensate Removal

System Pressure Modulating vs Constant

Pre

ssu

reP

ress

ure

Time

Time

Modulating Steam Traps

Inverted Bucketbull Continuous Steam ndash Goodbull Intermittent (OnOff) Steam ndash Poorbull Economical Choice Metal-on-Metal

Float amp Thermostaticbull Continuous Steam ndash Excellentbull Intermittent (OnOff) Steam ndash Excellentbull Optimum Choice for Process

Valve Head amp Seat

Float Mechanism

Air Vent

Downstream Lift = System Back Pressure

Heat Exchanger

Stall Condition ndash No Steam Supply

P2

Product Temperature Input

P1ltP2=Heat Exchanger Flooded

P1

Stall Chart

StallPump Mode

Trap Mode

65 = Stallof Load Point

What does a stall chart not take into consideration

Domestic Hot Water

15 PSIG Steam Supply 250F

40F to 140F 100 GPM

0 PSIG Back-Pressure 212F

(aka Gravity-Drain)

After HX is selectedhellipnow the real world

For real-world conditions

Q = U x A x ∆T where U = K (dx)

Domestic WaterFlow Rate Varies with demand typically low to no flow in evening hours

Building HeatFlow rate varies with VFDs responding to demand

Less flow requires less flow of heat (Q)

Domestic WaterIncoming water temperature rises in summer months

Building HeatOutside Air Temperature rises is summer months

Both reduce ∆T requiring less flow of heat

Saturated Steam Table

Actual Stall Conditions40F to 140F 100 GPM using 15 PSIG Steam Supply

Heat Load Summary - Calculating Stall

Flow Rate (GPM)

Heat Load(BTUhr)

Steam Tempin HX

(F)

Steam Pressurein HX(PSIG)

Latent Heat of Steam(BTUs)

Steam amp Condensate Flow

(lbshr)

Trap Differential

(ΔP)

System Condition

100 5004000 2455 1287 9486 5275 1287 Trap Mode

95 4753800 2377 927 9538 4984 927 Trap Mode

85 4253400 2222 325 9638 4413 325 Trap Mode

75 3753000 2066 -149 9737 3854 -149 Stall - Pump Mode

65 3252600 1911 -512 9832 3308 -512 Stall - Pump Mode

50 2502000 1678 -899 9974 2509 -899 Stall - Pump Mode

25 1251000 1289 -1253 10203 1226 -1253 Stall - Pump Mode

15 750600 1133 -1329 10297 729 -1329 Stall - Pump Mode

10 500400 1056 -1357 10337 484 -1357 Stall - Pump Mode

5 250200 978 -1381 10381 241 -1381 Stall - Pump Mode

Reasons for System Stall

bull Overly conservative fouling factors during HEX design ndash adds additional surface area

bull Back pressure at equipment discharge ndash elevation or static pressure

bull Modulating Control ndash Steam pressure

bull Vacuum

bull Process demands- Flow or temp changes

bull Oversized equipment ndash excess surface area

Effects of System Stall

bull Inadequate condensate drainage

bull Water hammer (Thermal Shock)

bull Frozen coils damaged tube bundles

bull Poor temperature control

bull Control valve hunting ndash control stability

bull Reduction in heat transfer capacity

Pumping Condensate

bull Whatrsquos unique about condensatebull High temperature fluid

bull Constant phase change or flashing

bull Intermittent supply inconsistent suction head

2 Types of Condensate Pumps1 Electric Pumps

2 Pressure-Powered Pumps

Electric Pump Operation

What does a lower pressure due to the boiling pointLowers saturation pointGenerates flash steamFlash steam causes cavitation

Vent = Energy Loss

What is Flash Steam

Flash Capacity Calculation

Return amp Vent Sizing

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 4: Understand how a good heating system design on paper can

Steam Heat Transfer 101

1 Steam Supply 2 Heat Transfer 3 Condensate Removal

Heat Exchanger Flow

Heat Exchanger Sizing

Q = U x A x ∆T where U = K (dx Fouling Factors)

dX A

Type amp Thickness of Materials of Construction

Copper

Copper

Stainless Steel

Double Wall

Standard HX sizes163- 258- 352- 446- 540- 634- 729- 823- 917-SQFT

Example 887760 = 324 x 274 x 100

Application requires 274 SQFT but the closest suitable size is 352 SQFT

Therefore the HX starts over-sized by 285

Normal Operation

Heat Exchanger

P2

P1

Product Temperature Input

P1 gt P2 = Heat Exchanger Dry

Vacuum = Negative Differential Pressure

Steam occupies 1675 times the amount of space than water

When steam condenses in a ldquoClosed-Systemrdquo a vacuum is created

3 ft

3 ft

3 ft

Conventional Condensate Removal

System Pressure Modulating vs Constant

Pre

ssu

reP

ress

ure

Time

Time

Modulating Steam Traps

Inverted Bucketbull Continuous Steam ndash Goodbull Intermittent (OnOff) Steam ndash Poorbull Economical Choice Metal-on-Metal

Float amp Thermostaticbull Continuous Steam ndash Excellentbull Intermittent (OnOff) Steam ndash Excellentbull Optimum Choice for Process

Valve Head amp Seat

Float Mechanism

Air Vent

Downstream Lift = System Back Pressure

Heat Exchanger

Stall Condition ndash No Steam Supply

P2

Product Temperature Input

P1ltP2=Heat Exchanger Flooded

P1

Stall Chart

StallPump Mode

Trap Mode

65 = Stallof Load Point

What does a stall chart not take into consideration

Domestic Hot Water

15 PSIG Steam Supply 250F

40F to 140F 100 GPM

0 PSIG Back-Pressure 212F

(aka Gravity-Drain)

After HX is selectedhellipnow the real world

For real-world conditions

Q = U x A x ∆T where U = K (dx)

Domestic WaterFlow Rate Varies with demand typically low to no flow in evening hours

Building HeatFlow rate varies with VFDs responding to demand

Less flow requires less flow of heat (Q)

Domestic WaterIncoming water temperature rises in summer months

Building HeatOutside Air Temperature rises is summer months

Both reduce ∆T requiring less flow of heat

Saturated Steam Table

Actual Stall Conditions40F to 140F 100 GPM using 15 PSIG Steam Supply

Heat Load Summary - Calculating Stall

Flow Rate (GPM)

Heat Load(BTUhr)

Steam Tempin HX

(F)

Steam Pressurein HX(PSIG)

Latent Heat of Steam(BTUs)

Steam amp Condensate Flow

(lbshr)

Trap Differential

(ΔP)

System Condition

100 5004000 2455 1287 9486 5275 1287 Trap Mode

95 4753800 2377 927 9538 4984 927 Trap Mode

85 4253400 2222 325 9638 4413 325 Trap Mode

75 3753000 2066 -149 9737 3854 -149 Stall - Pump Mode

65 3252600 1911 -512 9832 3308 -512 Stall - Pump Mode

50 2502000 1678 -899 9974 2509 -899 Stall - Pump Mode

25 1251000 1289 -1253 10203 1226 -1253 Stall - Pump Mode

15 750600 1133 -1329 10297 729 -1329 Stall - Pump Mode

10 500400 1056 -1357 10337 484 -1357 Stall - Pump Mode

5 250200 978 -1381 10381 241 -1381 Stall - Pump Mode

Reasons for System Stall

bull Overly conservative fouling factors during HEX design ndash adds additional surface area

bull Back pressure at equipment discharge ndash elevation or static pressure

bull Modulating Control ndash Steam pressure

bull Vacuum

bull Process demands- Flow or temp changes

bull Oversized equipment ndash excess surface area

Effects of System Stall

bull Inadequate condensate drainage

bull Water hammer (Thermal Shock)

bull Frozen coils damaged tube bundles

bull Poor temperature control

bull Control valve hunting ndash control stability

bull Reduction in heat transfer capacity

Pumping Condensate

bull Whatrsquos unique about condensatebull High temperature fluid

bull Constant phase change or flashing

bull Intermittent supply inconsistent suction head

2 Types of Condensate Pumps1 Electric Pumps

2 Pressure-Powered Pumps

Electric Pump Operation

What does a lower pressure due to the boiling pointLowers saturation pointGenerates flash steamFlash steam causes cavitation

Vent = Energy Loss

What is Flash Steam

Flash Capacity Calculation

Return amp Vent Sizing

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 5: Understand how a good heating system design on paper can

Heat Exchanger Flow

Heat Exchanger Sizing

Q = U x A x ∆T where U = K (dx Fouling Factors)

dX A

Type amp Thickness of Materials of Construction

Copper

Copper

Stainless Steel

Double Wall

Standard HX sizes163- 258- 352- 446- 540- 634- 729- 823- 917-SQFT

Example 887760 = 324 x 274 x 100

Application requires 274 SQFT but the closest suitable size is 352 SQFT

Therefore the HX starts over-sized by 285

Normal Operation

Heat Exchanger

P2

P1

Product Temperature Input

P1 gt P2 = Heat Exchanger Dry

Vacuum = Negative Differential Pressure

Steam occupies 1675 times the amount of space than water

When steam condenses in a ldquoClosed-Systemrdquo a vacuum is created

3 ft

3 ft

3 ft

Conventional Condensate Removal

System Pressure Modulating vs Constant

Pre

ssu

reP

ress

ure

Time

Time

Modulating Steam Traps

Inverted Bucketbull Continuous Steam ndash Goodbull Intermittent (OnOff) Steam ndash Poorbull Economical Choice Metal-on-Metal

Float amp Thermostaticbull Continuous Steam ndash Excellentbull Intermittent (OnOff) Steam ndash Excellentbull Optimum Choice for Process

Valve Head amp Seat

Float Mechanism

Air Vent

Downstream Lift = System Back Pressure

Heat Exchanger

Stall Condition ndash No Steam Supply

P2

Product Temperature Input

P1ltP2=Heat Exchanger Flooded

P1

Stall Chart

StallPump Mode

Trap Mode

65 = Stallof Load Point

What does a stall chart not take into consideration

Domestic Hot Water

15 PSIG Steam Supply 250F

40F to 140F 100 GPM

0 PSIG Back-Pressure 212F

(aka Gravity-Drain)

After HX is selectedhellipnow the real world

For real-world conditions

Q = U x A x ∆T where U = K (dx)

Domestic WaterFlow Rate Varies with demand typically low to no flow in evening hours

Building HeatFlow rate varies with VFDs responding to demand

Less flow requires less flow of heat (Q)

Domestic WaterIncoming water temperature rises in summer months

Building HeatOutside Air Temperature rises is summer months

Both reduce ∆T requiring less flow of heat

Saturated Steam Table

Actual Stall Conditions40F to 140F 100 GPM using 15 PSIG Steam Supply

Heat Load Summary - Calculating Stall

Flow Rate (GPM)

Heat Load(BTUhr)

Steam Tempin HX

(F)

Steam Pressurein HX(PSIG)

Latent Heat of Steam(BTUs)

Steam amp Condensate Flow

(lbshr)

Trap Differential

(ΔP)

System Condition

100 5004000 2455 1287 9486 5275 1287 Trap Mode

95 4753800 2377 927 9538 4984 927 Trap Mode

85 4253400 2222 325 9638 4413 325 Trap Mode

75 3753000 2066 -149 9737 3854 -149 Stall - Pump Mode

65 3252600 1911 -512 9832 3308 -512 Stall - Pump Mode

50 2502000 1678 -899 9974 2509 -899 Stall - Pump Mode

25 1251000 1289 -1253 10203 1226 -1253 Stall - Pump Mode

15 750600 1133 -1329 10297 729 -1329 Stall - Pump Mode

10 500400 1056 -1357 10337 484 -1357 Stall - Pump Mode

5 250200 978 -1381 10381 241 -1381 Stall - Pump Mode

Reasons for System Stall

bull Overly conservative fouling factors during HEX design ndash adds additional surface area

bull Back pressure at equipment discharge ndash elevation or static pressure

bull Modulating Control ndash Steam pressure

bull Vacuum

bull Process demands- Flow or temp changes

bull Oversized equipment ndash excess surface area

Effects of System Stall

bull Inadequate condensate drainage

bull Water hammer (Thermal Shock)

bull Frozen coils damaged tube bundles

bull Poor temperature control

bull Control valve hunting ndash control stability

bull Reduction in heat transfer capacity

Pumping Condensate

bull Whatrsquos unique about condensatebull High temperature fluid

bull Constant phase change or flashing

bull Intermittent supply inconsistent suction head

2 Types of Condensate Pumps1 Electric Pumps

2 Pressure-Powered Pumps

Electric Pump Operation

What does a lower pressure due to the boiling pointLowers saturation pointGenerates flash steamFlash steam causes cavitation

Vent = Energy Loss

What is Flash Steam

Flash Capacity Calculation

Return amp Vent Sizing

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 6: Understand how a good heating system design on paper can

Heat Exchanger Sizing

Q = U x A x ∆T where U = K (dx Fouling Factors)

dX A

Type amp Thickness of Materials of Construction

Copper

Copper

Stainless Steel

Double Wall

Standard HX sizes163- 258- 352- 446- 540- 634- 729- 823- 917-SQFT

Example 887760 = 324 x 274 x 100

Application requires 274 SQFT but the closest suitable size is 352 SQFT

Therefore the HX starts over-sized by 285

Normal Operation

Heat Exchanger

P2

P1

Product Temperature Input

P1 gt P2 = Heat Exchanger Dry

Vacuum = Negative Differential Pressure

Steam occupies 1675 times the amount of space than water

When steam condenses in a ldquoClosed-Systemrdquo a vacuum is created

3 ft

3 ft

3 ft

Conventional Condensate Removal

System Pressure Modulating vs Constant

Pre

ssu

reP

ress

ure

Time

Time

Modulating Steam Traps

Inverted Bucketbull Continuous Steam ndash Goodbull Intermittent (OnOff) Steam ndash Poorbull Economical Choice Metal-on-Metal

Float amp Thermostaticbull Continuous Steam ndash Excellentbull Intermittent (OnOff) Steam ndash Excellentbull Optimum Choice for Process

Valve Head amp Seat

Float Mechanism

Air Vent

Downstream Lift = System Back Pressure

Heat Exchanger

Stall Condition ndash No Steam Supply

P2

Product Temperature Input

P1ltP2=Heat Exchanger Flooded

P1

Stall Chart

StallPump Mode

Trap Mode

65 = Stallof Load Point

What does a stall chart not take into consideration

Domestic Hot Water

15 PSIG Steam Supply 250F

40F to 140F 100 GPM

0 PSIG Back-Pressure 212F

(aka Gravity-Drain)

After HX is selectedhellipnow the real world

For real-world conditions

Q = U x A x ∆T where U = K (dx)

Domestic WaterFlow Rate Varies with demand typically low to no flow in evening hours

Building HeatFlow rate varies with VFDs responding to demand

Less flow requires less flow of heat (Q)

Domestic WaterIncoming water temperature rises in summer months

Building HeatOutside Air Temperature rises is summer months

Both reduce ∆T requiring less flow of heat

Saturated Steam Table

Actual Stall Conditions40F to 140F 100 GPM using 15 PSIG Steam Supply

Heat Load Summary - Calculating Stall

Flow Rate (GPM)

Heat Load(BTUhr)

Steam Tempin HX

(F)

Steam Pressurein HX(PSIG)

Latent Heat of Steam(BTUs)

Steam amp Condensate Flow

(lbshr)

Trap Differential

(ΔP)

System Condition

100 5004000 2455 1287 9486 5275 1287 Trap Mode

95 4753800 2377 927 9538 4984 927 Trap Mode

85 4253400 2222 325 9638 4413 325 Trap Mode

75 3753000 2066 -149 9737 3854 -149 Stall - Pump Mode

65 3252600 1911 -512 9832 3308 -512 Stall - Pump Mode

50 2502000 1678 -899 9974 2509 -899 Stall - Pump Mode

25 1251000 1289 -1253 10203 1226 -1253 Stall - Pump Mode

15 750600 1133 -1329 10297 729 -1329 Stall - Pump Mode

10 500400 1056 -1357 10337 484 -1357 Stall - Pump Mode

5 250200 978 -1381 10381 241 -1381 Stall - Pump Mode

Reasons for System Stall

bull Overly conservative fouling factors during HEX design ndash adds additional surface area

bull Back pressure at equipment discharge ndash elevation or static pressure

bull Modulating Control ndash Steam pressure

bull Vacuum

bull Process demands- Flow or temp changes

bull Oversized equipment ndash excess surface area

Effects of System Stall

bull Inadequate condensate drainage

bull Water hammer (Thermal Shock)

bull Frozen coils damaged tube bundles

bull Poor temperature control

bull Control valve hunting ndash control stability

bull Reduction in heat transfer capacity

Pumping Condensate

bull Whatrsquos unique about condensatebull High temperature fluid

bull Constant phase change or flashing

bull Intermittent supply inconsistent suction head

2 Types of Condensate Pumps1 Electric Pumps

2 Pressure-Powered Pumps

Electric Pump Operation

What does a lower pressure due to the boiling pointLowers saturation pointGenerates flash steamFlash steam causes cavitation

Vent = Energy Loss

What is Flash Steam

Flash Capacity Calculation

Return amp Vent Sizing

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 7: Understand how a good heating system design on paper can

Normal Operation

Heat Exchanger

P2

P1

Product Temperature Input

P1 gt P2 = Heat Exchanger Dry

Vacuum = Negative Differential Pressure

Steam occupies 1675 times the amount of space than water

When steam condenses in a ldquoClosed-Systemrdquo a vacuum is created

3 ft

3 ft

3 ft

Conventional Condensate Removal

System Pressure Modulating vs Constant

Pre

ssu

reP

ress

ure

Time

Time

Modulating Steam Traps

Inverted Bucketbull Continuous Steam ndash Goodbull Intermittent (OnOff) Steam ndash Poorbull Economical Choice Metal-on-Metal

Float amp Thermostaticbull Continuous Steam ndash Excellentbull Intermittent (OnOff) Steam ndash Excellentbull Optimum Choice for Process

Valve Head amp Seat

Float Mechanism

Air Vent

Downstream Lift = System Back Pressure

Heat Exchanger

Stall Condition ndash No Steam Supply

P2

Product Temperature Input

P1ltP2=Heat Exchanger Flooded

P1

Stall Chart

StallPump Mode

Trap Mode

65 = Stallof Load Point

What does a stall chart not take into consideration

Domestic Hot Water

15 PSIG Steam Supply 250F

40F to 140F 100 GPM

0 PSIG Back-Pressure 212F

(aka Gravity-Drain)

After HX is selectedhellipnow the real world

For real-world conditions

Q = U x A x ∆T where U = K (dx)

Domestic WaterFlow Rate Varies with demand typically low to no flow in evening hours

Building HeatFlow rate varies with VFDs responding to demand

Less flow requires less flow of heat (Q)

Domestic WaterIncoming water temperature rises in summer months

Building HeatOutside Air Temperature rises is summer months

Both reduce ∆T requiring less flow of heat

Saturated Steam Table

Actual Stall Conditions40F to 140F 100 GPM using 15 PSIG Steam Supply

Heat Load Summary - Calculating Stall

Flow Rate (GPM)

Heat Load(BTUhr)

Steam Tempin HX

(F)

Steam Pressurein HX(PSIG)

Latent Heat of Steam(BTUs)

Steam amp Condensate Flow

(lbshr)

Trap Differential

(ΔP)

System Condition

100 5004000 2455 1287 9486 5275 1287 Trap Mode

95 4753800 2377 927 9538 4984 927 Trap Mode

85 4253400 2222 325 9638 4413 325 Trap Mode

75 3753000 2066 -149 9737 3854 -149 Stall - Pump Mode

65 3252600 1911 -512 9832 3308 -512 Stall - Pump Mode

50 2502000 1678 -899 9974 2509 -899 Stall - Pump Mode

25 1251000 1289 -1253 10203 1226 -1253 Stall - Pump Mode

15 750600 1133 -1329 10297 729 -1329 Stall - Pump Mode

10 500400 1056 -1357 10337 484 -1357 Stall - Pump Mode

5 250200 978 -1381 10381 241 -1381 Stall - Pump Mode

Reasons for System Stall

bull Overly conservative fouling factors during HEX design ndash adds additional surface area

bull Back pressure at equipment discharge ndash elevation or static pressure

bull Modulating Control ndash Steam pressure

bull Vacuum

bull Process demands- Flow or temp changes

bull Oversized equipment ndash excess surface area

Effects of System Stall

bull Inadequate condensate drainage

bull Water hammer (Thermal Shock)

bull Frozen coils damaged tube bundles

bull Poor temperature control

bull Control valve hunting ndash control stability

bull Reduction in heat transfer capacity

Pumping Condensate

bull Whatrsquos unique about condensatebull High temperature fluid

bull Constant phase change or flashing

bull Intermittent supply inconsistent suction head

2 Types of Condensate Pumps1 Electric Pumps

2 Pressure-Powered Pumps

Electric Pump Operation

What does a lower pressure due to the boiling pointLowers saturation pointGenerates flash steamFlash steam causes cavitation

Vent = Energy Loss

What is Flash Steam

Flash Capacity Calculation

Return amp Vent Sizing

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 8: Understand how a good heating system design on paper can

Vacuum = Negative Differential Pressure

Steam occupies 1675 times the amount of space than water

When steam condenses in a ldquoClosed-Systemrdquo a vacuum is created

3 ft

3 ft

3 ft

Conventional Condensate Removal

System Pressure Modulating vs Constant

Pre

ssu

reP

ress

ure

Time

Time

Modulating Steam Traps

Inverted Bucketbull Continuous Steam ndash Goodbull Intermittent (OnOff) Steam ndash Poorbull Economical Choice Metal-on-Metal

Float amp Thermostaticbull Continuous Steam ndash Excellentbull Intermittent (OnOff) Steam ndash Excellentbull Optimum Choice for Process

Valve Head amp Seat

Float Mechanism

Air Vent

Downstream Lift = System Back Pressure

Heat Exchanger

Stall Condition ndash No Steam Supply

P2

Product Temperature Input

P1ltP2=Heat Exchanger Flooded

P1

Stall Chart

StallPump Mode

Trap Mode

65 = Stallof Load Point

What does a stall chart not take into consideration

Domestic Hot Water

15 PSIG Steam Supply 250F

40F to 140F 100 GPM

0 PSIG Back-Pressure 212F

(aka Gravity-Drain)

After HX is selectedhellipnow the real world

For real-world conditions

Q = U x A x ∆T where U = K (dx)

Domestic WaterFlow Rate Varies with demand typically low to no flow in evening hours

Building HeatFlow rate varies with VFDs responding to demand

Less flow requires less flow of heat (Q)

Domestic WaterIncoming water temperature rises in summer months

Building HeatOutside Air Temperature rises is summer months

Both reduce ∆T requiring less flow of heat

Saturated Steam Table

Actual Stall Conditions40F to 140F 100 GPM using 15 PSIG Steam Supply

Heat Load Summary - Calculating Stall

Flow Rate (GPM)

Heat Load(BTUhr)

Steam Tempin HX

(F)

Steam Pressurein HX(PSIG)

Latent Heat of Steam(BTUs)

Steam amp Condensate Flow

(lbshr)

Trap Differential

(ΔP)

System Condition

100 5004000 2455 1287 9486 5275 1287 Trap Mode

95 4753800 2377 927 9538 4984 927 Trap Mode

85 4253400 2222 325 9638 4413 325 Trap Mode

75 3753000 2066 -149 9737 3854 -149 Stall - Pump Mode

65 3252600 1911 -512 9832 3308 -512 Stall - Pump Mode

50 2502000 1678 -899 9974 2509 -899 Stall - Pump Mode

25 1251000 1289 -1253 10203 1226 -1253 Stall - Pump Mode

15 750600 1133 -1329 10297 729 -1329 Stall - Pump Mode

10 500400 1056 -1357 10337 484 -1357 Stall - Pump Mode

5 250200 978 -1381 10381 241 -1381 Stall - Pump Mode

Reasons for System Stall

bull Overly conservative fouling factors during HEX design ndash adds additional surface area

bull Back pressure at equipment discharge ndash elevation or static pressure

bull Modulating Control ndash Steam pressure

bull Vacuum

bull Process demands- Flow or temp changes

bull Oversized equipment ndash excess surface area

Effects of System Stall

bull Inadequate condensate drainage

bull Water hammer (Thermal Shock)

bull Frozen coils damaged tube bundles

bull Poor temperature control

bull Control valve hunting ndash control stability

bull Reduction in heat transfer capacity

Pumping Condensate

bull Whatrsquos unique about condensatebull High temperature fluid

bull Constant phase change or flashing

bull Intermittent supply inconsistent suction head

2 Types of Condensate Pumps1 Electric Pumps

2 Pressure-Powered Pumps

Electric Pump Operation

What does a lower pressure due to the boiling pointLowers saturation pointGenerates flash steamFlash steam causes cavitation

Vent = Energy Loss

What is Flash Steam

Flash Capacity Calculation

Return amp Vent Sizing

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 9: Understand how a good heating system design on paper can

Conventional Condensate Removal

System Pressure Modulating vs Constant

Pre

ssu

reP

ress

ure

Time

Time

Modulating Steam Traps

Inverted Bucketbull Continuous Steam ndash Goodbull Intermittent (OnOff) Steam ndash Poorbull Economical Choice Metal-on-Metal

Float amp Thermostaticbull Continuous Steam ndash Excellentbull Intermittent (OnOff) Steam ndash Excellentbull Optimum Choice for Process

Valve Head amp Seat

Float Mechanism

Air Vent

Downstream Lift = System Back Pressure

Heat Exchanger

Stall Condition ndash No Steam Supply

P2

Product Temperature Input

P1ltP2=Heat Exchanger Flooded

P1

Stall Chart

StallPump Mode

Trap Mode

65 = Stallof Load Point

What does a stall chart not take into consideration

Domestic Hot Water

15 PSIG Steam Supply 250F

40F to 140F 100 GPM

0 PSIG Back-Pressure 212F

(aka Gravity-Drain)

After HX is selectedhellipnow the real world

For real-world conditions

Q = U x A x ∆T where U = K (dx)

Domestic WaterFlow Rate Varies with demand typically low to no flow in evening hours

Building HeatFlow rate varies with VFDs responding to demand

Less flow requires less flow of heat (Q)

Domestic WaterIncoming water temperature rises in summer months

Building HeatOutside Air Temperature rises is summer months

Both reduce ∆T requiring less flow of heat

Saturated Steam Table

Actual Stall Conditions40F to 140F 100 GPM using 15 PSIG Steam Supply

Heat Load Summary - Calculating Stall

Flow Rate (GPM)

Heat Load(BTUhr)

Steam Tempin HX

(F)

Steam Pressurein HX(PSIG)

Latent Heat of Steam(BTUs)

Steam amp Condensate Flow

(lbshr)

Trap Differential

(ΔP)

System Condition

100 5004000 2455 1287 9486 5275 1287 Trap Mode

95 4753800 2377 927 9538 4984 927 Trap Mode

85 4253400 2222 325 9638 4413 325 Trap Mode

75 3753000 2066 -149 9737 3854 -149 Stall - Pump Mode

65 3252600 1911 -512 9832 3308 -512 Stall - Pump Mode

50 2502000 1678 -899 9974 2509 -899 Stall - Pump Mode

25 1251000 1289 -1253 10203 1226 -1253 Stall - Pump Mode

15 750600 1133 -1329 10297 729 -1329 Stall - Pump Mode

10 500400 1056 -1357 10337 484 -1357 Stall - Pump Mode

5 250200 978 -1381 10381 241 -1381 Stall - Pump Mode

Reasons for System Stall

bull Overly conservative fouling factors during HEX design ndash adds additional surface area

bull Back pressure at equipment discharge ndash elevation or static pressure

bull Modulating Control ndash Steam pressure

bull Vacuum

bull Process demands- Flow or temp changes

bull Oversized equipment ndash excess surface area

Effects of System Stall

bull Inadequate condensate drainage

bull Water hammer (Thermal Shock)

bull Frozen coils damaged tube bundles

bull Poor temperature control

bull Control valve hunting ndash control stability

bull Reduction in heat transfer capacity

Pumping Condensate

bull Whatrsquos unique about condensatebull High temperature fluid

bull Constant phase change or flashing

bull Intermittent supply inconsistent suction head

2 Types of Condensate Pumps1 Electric Pumps

2 Pressure-Powered Pumps

Electric Pump Operation

What does a lower pressure due to the boiling pointLowers saturation pointGenerates flash steamFlash steam causes cavitation

Vent = Energy Loss

What is Flash Steam

Flash Capacity Calculation

Return amp Vent Sizing

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 10: Understand how a good heating system design on paper can

System Pressure Modulating vs Constant

Pre

ssu

reP

ress

ure

Time

Time

Modulating Steam Traps

Inverted Bucketbull Continuous Steam ndash Goodbull Intermittent (OnOff) Steam ndash Poorbull Economical Choice Metal-on-Metal

Float amp Thermostaticbull Continuous Steam ndash Excellentbull Intermittent (OnOff) Steam ndash Excellentbull Optimum Choice for Process

Valve Head amp Seat

Float Mechanism

Air Vent

Downstream Lift = System Back Pressure

Heat Exchanger

Stall Condition ndash No Steam Supply

P2

Product Temperature Input

P1ltP2=Heat Exchanger Flooded

P1

Stall Chart

StallPump Mode

Trap Mode

65 = Stallof Load Point

What does a stall chart not take into consideration

Domestic Hot Water

15 PSIG Steam Supply 250F

40F to 140F 100 GPM

0 PSIG Back-Pressure 212F

(aka Gravity-Drain)

After HX is selectedhellipnow the real world

For real-world conditions

Q = U x A x ∆T where U = K (dx)

Domestic WaterFlow Rate Varies with demand typically low to no flow in evening hours

Building HeatFlow rate varies with VFDs responding to demand

Less flow requires less flow of heat (Q)

Domestic WaterIncoming water temperature rises in summer months

Building HeatOutside Air Temperature rises is summer months

Both reduce ∆T requiring less flow of heat

Saturated Steam Table

Actual Stall Conditions40F to 140F 100 GPM using 15 PSIG Steam Supply

Heat Load Summary - Calculating Stall

Flow Rate (GPM)

Heat Load(BTUhr)

Steam Tempin HX

(F)

Steam Pressurein HX(PSIG)

Latent Heat of Steam(BTUs)

Steam amp Condensate Flow

(lbshr)

Trap Differential

(ΔP)

System Condition

100 5004000 2455 1287 9486 5275 1287 Trap Mode

95 4753800 2377 927 9538 4984 927 Trap Mode

85 4253400 2222 325 9638 4413 325 Trap Mode

75 3753000 2066 -149 9737 3854 -149 Stall - Pump Mode

65 3252600 1911 -512 9832 3308 -512 Stall - Pump Mode

50 2502000 1678 -899 9974 2509 -899 Stall - Pump Mode

25 1251000 1289 -1253 10203 1226 -1253 Stall - Pump Mode

15 750600 1133 -1329 10297 729 -1329 Stall - Pump Mode

10 500400 1056 -1357 10337 484 -1357 Stall - Pump Mode

5 250200 978 -1381 10381 241 -1381 Stall - Pump Mode

Reasons for System Stall

bull Overly conservative fouling factors during HEX design ndash adds additional surface area

bull Back pressure at equipment discharge ndash elevation or static pressure

bull Modulating Control ndash Steam pressure

bull Vacuum

bull Process demands- Flow or temp changes

bull Oversized equipment ndash excess surface area

Effects of System Stall

bull Inadequate condensate drainage

bull Water hammer (Thermal Shock)

bull Frozen coils damaged tube bundles

bull Poor temperature control

bull Control valve hunting ndash control stability

bull Reduction in heat transfer capacity

Pumping Condensate

bull Whatrsquos unique about condensatebull High temperature fluid

bull Constant phase change or flashing

bull Intermittent supply inconsistent suction head

2 Types of Condensate Pumps1 Electric Pumps

2 Pressure-Powered Pumps

Electric Pump Operation

What does a lower pressure due to the boiling pointLowers saturation pointGenerates flash steamFlash steam causes cavitation

Vent = Energy Loss

What is Flash Steam

Flash Capacity Calculation

Return amp Vent Sizing

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 11: Understand how a good heating system design on paper can

Modulating Steam Traps

Inverted Bucketbull Continuous Steam ndash Goodbull Intermittent (OnOff) Steam ndash Poorbull Economical Choice Metal-on-Metal

Float amp Thermostaticbull Continuous Steam ndash Excellentbull Intermittent (OnOff) Steam ndash Excellentbull Optimum Choice for Process

Valve Head amp Seat

Float Mechanism

Air Vent

Downstream Lift = System Back Pressure

Heat Exchanger

Stall Condition ndash No Steam Supply

P2

Product Temperature Input

P1ltP2=Heat Exchanger Flooded

P1

Stall Chart

StallPump Mode

Trap Mode

65 = Stallof Load Point

What does a stall chart not take into consideration

Domestic Hot Water

15 PSIG Steam Supply 250F

40F to 140F 100 GPM

0 PSIG Back-Pressure 212F

(aka Gravity-Drain)

After HX is selectedhellipnow the real world

For real-world conditions

Q = U x A x ∆T where U = K (dx)

Domestic WaterFlow Rate Varies with demand typically low to no flow in evening hours

Building HeatFlow rate varies with VFDs responding to demand

Less flow requires less flow of heat (Q)

Domestic WaterIncoming water temperature rises in summer months

Building HeatOutside Air Temperature rises is summer months

Both reduce ∆T requiring less flow of heat

Saturated Steam Table

Actual Stall Conditions40F to 140F 100 GPM using 15 PSIG Steam Supply

Heat Load Summary - Calculating Stall

Flow Rate (GPM)

Heat Load(BTUhr)

Steam Tempin HX

(F)

Steam Pressurein HX(PSIG)

Latent Heat of Steam(BTUs)

Steam amp Condensate Flow

(lbshr)

Trap Differential

(ΔP)

System Condition

100 5004000 2455 1287 9486 5275 1287 Trap Mode

95 4753800 2377 927 9538 4984 927 Trap Mode

85 4253400 2222 325 9638 4413 325 Trap Mode

75 3753000 2066 -149 9737 3854 -149 Stall - Pump Mode

65 3252600 1911 -512 9832 3308 -512 Stall - Pump Mode

50 2502000 1678 -899 9974 2509 -899 Stall - Pump Mode

25 1251000 1289 -1253 10203 1226 -1253 Stall - Pump Mode

15 750600 1133 -1329 10297 729 -1329 Stall - Pump Mode

10 500400 1056 -1357 10337 484 -1357 Stall - Pump Mode

5 250200 978 -1381 10381 241 -1381 Stall - Pump Mode

Reasons for System Stall

bull Overly conservative fouling factors during HEX design ndash adds additional surface area

bull Back pressure at equipment discharge ndash elevation or static pressure

bull Modulating Control ndash Steam pressure

bull Vacuum

bull Process demands- Flow or temp changes

bull Oversized equipment ndash excess surface area

Effects of System Stall

bull Inadequate condensate drainage

bull Water hammer (Thermal Shock)

bull Frozen coils damaged tube bundles

bull Poor temperature control

bull Control valve hunting ndash control stability

bull Reduction in heat transfer capacity

Pumping Condensate

bull Whatrsquos unique about condensatebull High temperature fluid

bull Constant phase change or flashing

bull Intermittent supply inconsistent suction head

2 Types of Condensate Pumps1 Electric Pumps

2 Pressure-Powered Pumps

Electric Pump Operation

What does a lower pressure due to the boiling pointLowers saturation pointGenerates flash steamFlash steam causes cavitation

Vent = Energy Loss

What is Flash Steam

Flash Capacity Calculation

Return amp Vent Sizing

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 12: Understand how a good heating system design on paper can

Downstream Lift = System Back Pressure

Heat Exchanger

Stall Condition ndash No Steam Supply

P2

Product Temperature Input

P1ltP2=Heat Exchanger Flooded

P1

Stall Chart

StallPump Mode

Trap Mode

65 = Stallof Load Point

What does a stall chart not take into consideration

Domestic Hot Water

15 PSIG Steam Supply 250F

40F to 140F 100 GPM

0 PSIG Back-Pressure 212F

(aka Gravity-Drain)

After HX is selectedhellipnow the real world

For real-world conditions

Q = U x A x ∆T where U = K (dx)

Domestic WaterFlow Rate Varies with demand typically low to no flow in evening hours

Building HeatFlow rate varies with VFDs responding to demand

Less flow requires less flow of heat (Q)

Domestic WaterIncoming water temperature rises in summer months

Building HeatOutside Air Temperature rises is summer months

Both reduce ∆T requiring less flow of heat

Saturated Steam Table

Actual Stall Conditions40F to 140F 100 GPM using 15 PSIG Steam Supply

Heat Load Summary - Calculating Stall

Flow Rate (GPM)

Heat Load(BTUhr)

Steam Tempin HX

(F)

Steam Pressurein HX(PSIG)

Latent Heat of Steam(BTUs)

Steam amp Condensate Flow

(lbshr)

Trap Differential

(ΔP)

System Condition

100 5004000 2455 1287 9486 5275 1287 Trap Mode

95 4753800 2377 927 9538 4984 927 Trap Mode

85 4253400 2222 325 9638 4413 325 Trap Mode

75 3753000 2066 -149 9737 3854 -149 Stall - Pump Mode

65 3252600 1911 -512 9832 3308 -512 Stall - Pump Mode

50 2502000 1678 -899 9974 2509 -899 Stall - Pump Mode

25 1251000 1289 -1253 10203 1226 -1253 Stall - Pump Mode

15 750600 1133 -1329 10297 729 -1329 Stall - Pump Mode

10 500400 1056 -1357 10337 484 -1357 Stall - Pump Mode

5 250200 978 -1381 10381 241 -1381 Stall - Pump Mode

Reasons for System Stall

bull Overly conservative fouling factors during HEX design ndash adds additional surface area

bull Back pressure at equipment discharge ndash elevation or static pressure

bull Modulating Control ndash Steam pressure

bull Vacuum

bull Process demands- Flow or temp changes

bull Oversized equipment ndash excess surface area

Effects of System Stall

bull Inadequate condensate drainage

bull Water hammer (Thermal Shock)

bull Frozen coils damaged tube bundles

bull Poor temperature control

bull Control valve hunting ndash control stability

bull Reduction in heat transfer capacity

Pumping Condensate

bull Whatrsquos unique about condensatebull High temperature fluid

bull Constant phase change or flashing

bull Intermittent supply inconsistent suction head

2 Types of Condensate Pumps1 Electric Pumps

2 Pressure-Powered Pumps

Electric Pump Operation

What does a lower pressure due to the boiling pointLowers saturation pointGenerates flash steamFlash steam causes cavitation

Vent = Energy Loss

What is Flash Steam

Flash Capacity Calculation

Return amp Vent Sizing

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 13: Understand how a good heating system design on paper can

Heat Exchanger

Stall Condition ndash No Steam Supply

P2

Product Temperature Input

P1ltP2=Heat Exchanger Flooded

P1

Stall Chart

StallPump Mode

Trap Mode

65 = Stallof Load Point

What does a stall chart not take into consideration

Domestic Hot Water

15 PSIG Steam Supply 250F

40F to 140F 100 GPM

0 PSIG Back-Pressure 212F

(aka Gravity-Drain)

After HX is selectedhellipnow the real world

For real-world conditions

Q = U x A x ∆T where U = K (dx)

Domestic WaterFlow Rate Varies with demand typically low to no flow in evening hours

Building HeatFlow rate varies with VFDs responding to demand

Less flow requires less flow of heat (Q)

Domestic WaterIncoming water temperature rises in summer months

Building HeatOutside Air Temperature rises is summer months

Both reduce ∆T requiring less flow of heat

Saturated Steam Table

Actual Stall Conditions40F to 140F 100 GPM using 15 PSIG Steam Supply

Heat Load Summary - Calculating Stall

Flow Rate (GPM)

Heat Load(BTUhr)

Steam Tempin HX

(F)

Steam Pressurein HX(PSIG)

Latent Heat of Steam(BTUs)

Steam amp Condensate Flow

(lbshr)

Trap Differential

(ΔP)

System Condition

100 5004000 2455 1287 9486 5275 1287 Trap Mode

95 4753800 2377 927 9538 4984 927 Trap Mode

85 4253400 2222 325 9638 4413 325 Trap Mode

75 3753000 2066 -149 9737 3854 -149 Stall - Pump Mode

65 3252600 1911 -512 9832 3308 -512 Stall - Pump Mode

50 2502000 1678 -899 9974 2509 -899 Stall - Pump Mode

25 1251000 1289 -1253 10203 1226 -1253 Stall - Pump Mode

15 750600 1133 -1329 10297 729 -1329 Stall - Pump Mode

10 500400 1056 -1357 10337 484 -1357 Stall - Pump Mode

5 250200 978 -1381 10381 241 -1381 Stall - Pump Mode

Reasons for System Stall

bull Overly conservative fouling factors during HEX design ndash adds additional surface area

bull Back pressure at equipment discharge ndash elevation or static pressure

bull Modulating Control ndash Steam pressure

bull Vacuum

bull Process demands- Flow or temp changes

bull Oversized equipment ndash excess surface area

Effects of System Stall

bull Inadequate condensate drainage

bull Water hammer (Thermal Shock)

bull Frozen coils damaged tube bundles

bull Poor temperature control

bull Control valve hunting ndash control stability

bull Reduction in heat transfer capacity

Pumping Condensate

bull Whatrsquos unique about condensatebull High temperature fluid

bull Constant phase change or flashing

bull Intermittent supply inconsistent suction head

2 Types of Condensate Pumps1 Electric Pumps

2 Pressure-Powered Pumps

Electric Pump Operation

What does a lower pressure due to the boiling pointLowers saturation pointGenerates flash steamFlash steam causes cavitation

Vent = Energy Loss

What is Flash Steam

Flash Capacity Calculation

Return amp Vent Sizing

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 14: Understand how a good heating system design on paper can

Stall Chart

StallPump Mode

Trap Mode

65 = Stallof Load Point

What does a stall chart not take into consideration

Domestic Hot Water

15 PSIG Steam Supply 250F

40F to 140F 100 GPM

0 PSIG Back-Pressure 212F

(aka Gravity-Drain)

After HX is selectedhellipnow the real world

For real-world conditions

Q = U x A x ∆T where U = K (dx)

Domestic WaterFlow Rate Varies with demand typically low to no flow in evening hours

Building HeatFlow rate varies with VFDs responding to demand

Less flow requires less flow of heat (Q)

Domestic WaterIncoming water temperature rises in summer months

Building HeatOutside Air Temperature rises is summer months

Both reduce ∆T requiring less flow of heat

Saturated Steam Table

Actual Stall Conditions40F to 140F 100 GPM using 15 PSIG Steam Supply

Heat Load Summary - Calculating Stall

Flow Rate (GPM)

Heat Load(BTUhr)

Steam Tempin HX

(F)

Steam Pressurein HX(PSIG)

Latent Heat of Steam(BTUs)

Steam amp Condensate Flow

(lbshr)

Trap Differential

(ΔP)

System Condition

100 5004000 2455 1287 9486 5275 1287 Trap Mode

95 4753800 2377 927 9538 4984 927 Trap Mode

85 4253400 2222 325 9638 4413 325 Trap Mode

75 3753000 2066 -149 9737 3854 -149 Stall - Pump Mode

65 3252600 1911 -512 9832 3308 -512 Stall - Pump Mode

50 2502000 1678 -899 9974 2509 -899 Stall - Pump Mode

25 1251000 1289 -1253 10203 1226 -1253 Stall - Pump Mode

15 750600 1133 -1329 10297 729 -1329 Stall - Pump Mode

10 500400 1056 -1357 10337 484 -1357 Stall - Pump Mode

5 250200 978 -1381 10381 241 -1381 Stall - Pump Mode

Reasons for System Stall

bull Overly conservative fouling factors during HEX design ndash adds additional surface area

bull Back pressure at equipment discharge ndash elevation or static pressure

bull Modulating Control ndash Steam pressure

bull Vacuum

bull Process demands- Flow or temp changes

bull Oversized equipment ndash excess surface area

Effects of System Stall

bull Inadequate condensate drainage

bull Water hammer (Thermal Shock)

bull Frozen coils damaged tube bundles

bull Poor temperature control

bull Control valve hunting ndash control stability

bull Reduction in heat transfer capacity

Pumping Condensate

bull Whatrsquos unique about condensatebull High temperature fluid

bull Constant phase change or flashing

bull Intermittent supply inconsistent suction head

2 Types of Condensate Pumps1 Electric Pumps

2 Pressure-Powered Pumps

Electric Pump Operation

What does a lower pressure due to the boiling pointLowers saturation pointGenerates flash steamFlash steam causes cavitation

Vent = Energy Loss

What is Flash Steam

Flash Capacity Calculation

Return amp Vent Sizing

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 15: Understand how a good heating system design on paper can

After HX is selectedhellipnow the real world

For real-world conditions

Q = U x A x ∆T where U = K (dx)

Domestic WaterFlow Rate Varies with demand typically low to no flow in evening hours

Building HeatFlow rate varies with VFDs responding to demand

Less flow requires less flow of heat (Q)

Domestic WaterIncoming water temperature rises in summer months

Building HeatOutside Air Temperature rises is summer months

Both reduce ∆T requiring less flow of heat

Saturated Steam Table

Actual Stall Conditions40F to 140F 100 GPM using 15 PSIG Steam Supply

Heat Load Summary - Calculating Stall

Flow Rate (GPM)

Heat Load(BTUhr)

Steam Tempin HX

(F)

Steam Pressurein HX(PSIG)

Latent Heat of Steam(BTUs)

Steam amp Condensate Flow

(lbshr)

Trap Differential

(ΔP)

System Condition

100 5004000 2455 1287 9486 5275 1287 Trap Mode

95 4753800 2377 927 9538 4984 927 Trap Mode

85 4253400 2222 325 9638 4413 325 Trap Mode

75 3753000 2066 -149 9737 3854 -149 Stall - Pump Mode

65 3252600 1911 -512 9832 3308 -512 Stall - Pump Mode

50 2502000 1678 -899 9974 2509 -899 Stall - Pump Mode

25 1251000 1289 -1253 10203 1226 -1253 Stall - Pump Mode

15 750600 1133 -1329 10297 729 -1329 Stall - Pump Mode

10 500400 1056 -1357 10337 484 -1357 Stall - Pump Mode

5 250200 978 -1381 10381 241 -1381 Stall - Pump Mode

Reasons for System Stall

bull Overly conservative fouling factors during HEX design ndash adds additional surface area

bull Back pressure at equipment discharge ndash elevation or static pressure

bull Modulating Control ndash Steam pressure

bull Vacuum

bull Process demands- Flow or temp changes

bull Oversized equipment ndash excess surface area

Effects of System Stall

bull Inadequate condensate drainage

bull Water hammer (Thermal Shock)

bull Frozen coils damaged tube bundles

bull Poor temperature control

bull Control valve hunting ndash control stability

bull Reduction in heat transfer capacity

Pumping Condensate

bull Whatrsquos unique about condensatebull High temperature fluid

bull Constant phase change or flashing

bull Intermittent supply inconsistent suction head

2 Types of Condensate Pumps1 Electric Pumps

2 Pressure-Powered Pumps

Electric Pump Operation

What does a lower pressure due to the boiling pointLowers saturation pointGenerates flash steamFlash steam causes cavitation

Vent = Energy Loss

What is Flash Steam

Flash Capacity Calculation

Return amp Vent Sizing

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 16: Understand how a good heating system design on paper can

Saturated Steam Table

Actual Stall Conditions40F to 140F 100 GPM using 15 PSIG Steam Supply

Heat Load Summary - Calculating Stall

Flow Rate (GPM)

Heat Load(BTUhr)

Steam Tempin HX

(F)

Steam Pressurein HX(PSIG)

Latent Heat of Steam(BTUs)

Steam amp Condensate Flow

(lbshr)

Trap Differential

(ΔP)

System Condition

100 5004000 2455 1287 9486 5275 1287 Trap Mode

95 4753800 2377 927 9538 4984 927 Trap Mode

85 4253400 2222 325 9638 4413 325 Trap Mode

75 3753000 2066 -149 9737 3854 -149 Stall - Pump Mode

65 3252600 1911 -512 9832 3308 -512 Stall - Pump Mode

50 2502000 1678 -899 9974 2509 -899 Stall - Pump Mode

25 1251000 1289 -1253 10203 1226 -1253 Stall - Pump Mode

15 750600 1133 -1329 10297 729 -1329 Stall - Pump Mode

10 500400 1056 -1357 10337 484 -1357 Stall - Pump Mode

5 250200 978 -1381 10381 241 -1381 Stall - Pump Mode

Reasons for System Stall

bull Overly conservative fouling factors during HEX design ndash adds additional surface area

bull Back pressure at equipment discharge ndash elevation or static pressure

bull Modulating Control ndash Steam pressure

bull Vacuum

bull Process demands- Flow or temp changes

bull Oversized equipment ndash excess surface area

Effects of System Stall

bull Inadequate condensate drainage

bull Water hammer (Thermal Shock)

bull Frozen coils damaged tube bundles

bull Poor temperature control

bull Control valve hunting ndash control stability

bull Reduction in heat transfer capacity

Pumping Condensate

bull Whatrsquos unique about condensatebull High temperature fluid

bull Constant phase change or flashing

bull Intermittent supply inconsistent suction head

2 Types of Condensate Pumps1 Electric Pumps

2 Pressure-Powered Pumps

Electric Pump Operation

What does a lower pressure due to the boiling pointLowers saturation pointGenerates flash steamFlash steam causes cavitation

Vent = Energy Loss

What is Flash Steam

Flash Capacity Calculation

Return amp Vent Sizing

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 17: Understand how a good heating system design on paper can

Actual Stall Conditions40F to 140F 100 GPM using 15 PSIG Steam Supply

Heat Load Summary - Calculating Stall

Flow Rate (GPM)

Heat Load(BTUhr)

Steam Tempin HX

(F)

Steam Pressurein HX(PSIG)

Latent Heat of Steam(BTUs)

Steam amp Condensate Flow

(lbshr)

Trap Differential

(ΔP)

System Condition

100 5004000 2455 1287 9486 5275 1287 Trap Mode

95 4753800 2377 927 9538 4984 927 Trap Mode

85 4253400 2222 325 9638 4413 325 Trap Mode

75 3753000 2066 -149 9737 3854 -149 Stall - Pump Mode

65 3252600 1911 -512 9832 3308 -512 Stall - Pump Mode

50 2502000 1678 -899 9974 2509 -899 Stall - Pump Mode

25 1251000 1289 -1253 10203 1226 -1253 Stall - Pump Mode

15 750600 1133 -1329 10297 729 -1329 Stall - Pump Mode

10 500400 1056 -1357 10337 484 -1357 Stall - Pump Mode

5 250200 978 -1381 10381 241 -1381 Stall - Pump Mode

Reasons for System Stall

bull Overly conservative fouling factors during HEX design ndash adds additional surface area

bull Back pressure at equipment discharge ndash elevation or static pressure

bull Modulating Control ndash Steam pressure

bull Vacuum

bull Process demands- Flow or temp changes

bull Oversized equipment ndash excess surface area

Effects of System Stall

bull Inadequate condensate drainage

bull Water hammer (Thermal Shock)

bull Frozen coils damaged tube bundles

bull Poor temperature control

bull Control valve hunting ndash control stability

bull Reduction in heat transfer capacity

Pumping Condensate

bull Whatrsquos unique about condensatebull High temperature fluid

bull Constant phase change or flashing

bull Intermittent supply inconsistent suction head

2 Types of Condensate Pumps1 Electric Pumps

2 Pressure-Powered Pumps

Electric Pump Operation

What does a lower pressure due to the boiling pointLowers saturation pointGenerates flash steamFlash steam causes cavitation

Vent = Energy Loss

What is Flash Steam

Flash Capacity Calculation

Return amp Vent Sizing

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 18: Understand how a good heating system design on paper can

Reasons for System Stall

bull Overly conservative fouling factors during HEX design ndash adds additional surface area

bull Back pressure at equipment discharge ndash elevation or static pressure

bull Modulating Control ndash Steam pressure

bull Vacuum

bull Process demands- Flow or temp changes

bull Oversized equipment ndash excess surface area

Effects of System Stall

bull Inadequate condensate drainage

bull Water hammer (Thermal Shock)

bull Frozen coils damaged tube bundles

bull Poor temperature control

bull Control valve hunting ndash control stability

bull Reduction in heat transfer capacity

Pumping Condensate

bull Whatrsquos unique about condensatebull High temperature fluid

bull Constant phase change or flashing

bull Intermittent supply inconsistent suction head

2 Types of Condensate Pumps1 Electric Pumps

2 Pressure-Powered Pumps

Electric Pump Operation

What does a lower pressure due to the boiling pointLowers saturation pointGenerates flash steamFlash steam causes cavitation

Vent = Energy Loss

What is Flash Steam

Flash Capacity Calculation

Return amp Vent Sizing

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 19: Understand how a good heating system design on paper can

Effects of System Stall

bull Inadequate condensate drainage

bull Water hammer (Thermal Shock)

bull Frozen coils damaged tube bundles

bull Poor temperature control

bull Control valve hunting ndash control stability

bull Reduction in heat transfer capacity

Pumping Condensate

bull Whatrsquos unique about condensatebull High temperature fluid

bull Constant phase change or flashing

bull Intermittent supply inconsistent suction head

2 Types of Condensate Pumps1 Electric Pumps

2 Pressure-Powered Pumps

Electric Pump Operation

What does a lower pressure due to the boiling pointLowers saturation pointGenerates flash steamFlash steam causes cavitation

Vent = Energy Loss

What is Flash Steam

Flash Capacity Calculation

Return amp Vent Sizing

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 20: Understand how a good heating system design on paper can

Pumping Condensate

bull Whatrsquos unique about condensatebull High temperature fluid

bull Constant phase change or flashing

bull Intermittent supply inconsistent suction head

2 Types of Condensate Pumps1 Electric Pumps

2 Pressure-Powered Pumps

Electric Pump Operation

What does a lower pressure due to the boiling pointLowers saturation pointGenerates flash steamFlash steam causes cavitation

Vent = Energy Loss

What is Flash Steam

Flash Capacity Calculation

Return amp Vent Sizing

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 21: Understand how a good heating system design on paper can

Electric Pump Operation

What does a lower pressure due to the boiling pointLowers saturation pointGenerates flash steamFlash steam causes cavitation

Vent = Energy Loss

What is Flash Steam

Flash Capacity Calculation

Return amp Vent Sizing

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 22: Understand how a good heating system design on paper can

What is Flash Steam

Flash Capacity Calculation

Return amp Vent Sizing

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 23: Understand how a good heating system design on paper can

Flash Capacity Calculation

Return amp Vent Sizing

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 24: Understand how a good heating system design on paper can

Return amp Vent Sizing

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 25: Understand how a good heating system design on paper can

Standard Vent Size on Electric Pump Receivers

Too Small

Not designed for flash steam

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 26: Understand how a good heating system design on paper can

Sub-Cooling - Avoid Cavitation

bull Flash additional energy upstream away from mechanical pumps

bull Sub-Cool condensate to 190 F before entering pump receiver

bull High amp Medium Pressure Condensate provide options for Heat Recovery

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 27: Understand how a good heating system design on paper can

What do we GainLose from Sub-Cooling

Lose28 BTUslb of Condensate 15 PSIG87 BTUslb of Condensate 60 PSIG135 BTUslb of Condensate 125 PSIG

Gain25 of Potential Dissolved Oxygen

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 28: Understand how a good heating system design on paper can

How do we Remove the Flash Vent

Use a Pressure PumpUp to 400 F

No Energy Loss

Does not require Sub-Cooling of Condensate

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 29: Understand how a good heating system design on paper can

Pressure Pump amp Steam Trap Combo

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 30: Understand how a good heating system design on paper can

Pump-Trap Combo w Single Float Mechanism

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 31: Understand how a good heating system design on paper can

Stall Alleviation

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 32: Understand how a good heating system design on paper can

Closed-Loop System

Heat Exchanger stays dry 100 of the time

1 HX reaches temperature or demand stops

2 Control Valve Shutsbull 0 PSIG Steam Supplybull Lose Positive Differential

Pressure3 Steam within System

Condensesbull Draws a vacuumbull More efficient heat

exchange4 Pumps

bull Create Positive Differential Pressure

bull Maintains Vacuum Conditions

Off ndash 0 PSIG Steam Supply

Vacuum1000+ BTUslb of Steam

GravityDrain

Power SupplyMotive

SteamAirNo Electrical

Power

125 PSIG280 ft + of Lift

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 33: Understand how a good heating system design on paper can

Typical InstallationOpen-Loop Gravity-Drain Design

125 HPS

10 LPC

Roof

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 34: Understand how a good heating system design on paper can

125 HPS

10 LPC

Roof

15 HPS

Closed-Loop Feed-Forward Design

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 35: Understand how a good heating system design on paper can

Closed-Loop Pump-Trap Design

125 HPS

10 LPC

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 36: Understand how a good heating system design on paper can

Condensate Pump Application Considerations

1 Will there be lift after the steam trap

2 Will there be variable process conditions

3 Will the leaving process conditions temperature be equal or less than 212degF

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 37: Understand how a good heating system design on paper can

System Stall Solutions

Installation of a vacuum breaker

Objective

To relieve a vacuum within equipment allowing for condensate drainage

Shortcoming

This practice will only help if the condensate is gravity drain to atmosphere

Allows undesirable air into the system

Vacuum breakers often fail due to a poorly chosen location

Loss of valuable flash steam

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 38: Understand how a good heating system design on paper can

Installation of a safety drainObjectiveThe use of a second steam trap located above the primary trap which discharges condensate to drain when the system goes into a stall condition ShortcomingA significant amount of condensateflash steam and valuable BTUrsquos are lost down the drain when the system is in stall Stall load may be as high as 90 or more of the design load therefore 90 of thecondensate coming from the equipment goes down the drain

System Stall Solutions

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 39: Understand how a good heating system design on paper can

Installation of a positive pressure system

Objective

The use of air or other gas to maintain set pressure to ensure a positive pressure differential across the trap allowing for condensate drainage

Shortcomings

Injects a significant amount of undesirable air into the equipment This large amount of air may cause multiple problems

Air acts as an insulator thereby decreasing the heat transfer capacity of the equipment

A heavy dependence on air vents to evacuate the air from the equipment

Air vents may be open a significant amount of time allowing for loss of valuable BTUrsquos

System Stall Solutions

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 40: Understand how a good heating system design on paper can

Closed Loop Condensate System

The application of a ldquoclosedrdquo system pump trap on your modulating steam equipment can provide the following benefits

Continuous condensate drainage even in a vacuum

Eliminates the need for vacuum breakers

Saves valuable flash steam from escaping into the atmosphere

No need to run expensive vent lines

No rotating seals cavitation or NPSH requirements

Negligible operating cost

Longer equipment life

Reduced corrosion

Better temperature control

Shortcomings Relative costs versus conventional systems

System Stall Solutions

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 41: Understand how a good heating system design on paper can

Spot the issue

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 42: Understand how a good heating system design on paper can

How did this end up this way

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 43: Understand how a good heating system design on paper can

If we donrsquot fix it add onhellip

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 44: Understand how a good heating system design on paper can

Done right with forethought

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 45: Understand how a good heating system design on paper can

Recap

bull By design heat exchange equipment have excess surface area

bull Condensate must flow from a higher pressure to a lower pressure ndash account for this in design

bull Air and non ndashcondensable gases need to be managed along with flash steam in the condensate system

bull Whenever you have modulating steam pressure for temperature control the potential for system stall exists

bull Electric condensate pump receivers are not used as flash tanks

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 46: Understand how a good heating system design on paper can

How well did I do

1 Identify two types of heat transfer2 In the equation Q = U x A x ∆T - Define U Define A3 Define the general definition of ldquosystem stallrdquo4 When lowering the pressure of condensate in system we create5 Heat exchangers typically have surplus surface area ndash TF6 A flash tank in front of an electric condensate pump is a good idea ndash

TF7 Reducing the effects potential for system stall will improve ndash List

three items8 List three consideration where you may want to incorporate a

condensate pumping system

Selection Expertise Solutions

Page 47: Understand how a good heating system design on paper can

Selection Expertise Solutions