Page 1: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

Understanding GFCIs Developed by the NEMA 5PP Personnel

Protection Technical Committee

Page 2: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

What Is to Be Covered? Electrical Shock - Why Have GFCIs?

How GFCI’s Operate

Proper Installation of a GFCI

Wiring Errors

Grounded Neutral Detection

Testing GFCIs

Page 3: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

0.0

5.0

10.0

15.0

20.0

25.0

30.0

35.0

1970

1973

1976

1979

1982

1985

1988

1991

1994

1997

2000

GF

CI's (

millio

ns)

0

100

200

300

400

500

600

700

Ele

ctr

ocu

tio

ns

# of GFCI's # Electrocutions

Electrocutions Associated With

Consumer Products

Page 4: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

Effects of Electric Shock

20A

15A

10A

4A

50mA

30mA

15mA

10mA

4-6 mA

1mA

4 AMPERES AND OVER

Heart Paralysis, Serious Tissue and Organ Burning

50 mA - 4 Amps Fibrillation

IEC RCD Standards Breathing Difficult, Fibrillation in children

Muscles “Freeze” in 50% of the Population

Let-Go Threshold

4-6 UL 943 Class A GFCI Trip Level

Perception Level

Page 5: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

Electric Shock Prevention System Isolation (Physical)

Insulation

Double Insulation

Equipment Grounding

GFCI (solves shortcomings

of above systems)

Page 6: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

L

N

Equipment Grounding

Conductor (EGC)

6A

6A Equipment

Normal Circuit Operation

The same amount of current flow from line to load and returns

from load to line.

Page 7: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

L

N

EGC

Ground-Fault

.06 A

12A

6A

5.94A

Ground-Fault

Ground – Fault (Indirect Contact)

Page 8: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

L

N

Ground-Fault

.1 A

6A

5.9A

Ground – Fault (Direct Contact)

Page 9: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

How GFCIs Operate Knowing how GFCIs work will enable you to understand:

1. Why GFCIs must be installed a certain way

• For Circuit Breaker GFCI:

To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral

terminal, NOT panelboard neutral.

• For Receptacle GFCI:

If line and load conductors are reversed, per 2010 edition UL 943, no power is

available at:

1.Face terminals or

2.Line terminals connected to downstream receptacles.

2. Why do GFCIs trip under various circumstances

• Mis-wiring will cause GFCI to trip if:

1. Ground current is flowing

2. Neutral is grounded on load side of GFCI.

• Portable GFCIs will trip if open neutral is present on the line side of the GFCI.

3. What conditions causes unexpected tripping

• Ground current exceeding 6 mA when a load is applied.

• Load neutral is not connected to correct terminals.

Page 10: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

Load

IIn

IOut

If the current out = current back, the differential current transformer shows no

output.

L

N

The Current “Adding Machine”

Differential Current Transformer

Page 11: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

Current “Adding Machine”

240V

Load

IIN

IOut

L1

L2

N 120/240V

Load

IIN

IOut

L1

L2

Differential Current Transformer

Differential Current Transformer

Page 12: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

Current “Adding Machine”

Under Ground Fault Conditions

Load

IIn = 6A

IOut = 5.9A

Ground-Fault

.1A

L

N

Differential Current Transformer

If I-out does not equal I-in, the differential current transformer creates an output signal.

Page 13: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

What’s in the GFCI? (Receptacle)

Cover

Reset Button

Tamper Resistant Mechanism

(Optional)

Bridge

Face Contacts

Middle Barrier

Base

Terminals

Printed Circuit Board

Terminals

Test Button

Page 14: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

120V Trip

Mechanism

GFCI circuitry with

grounded neutral

detection

Load Terminals Line Terminals

Push-to-test Button

15K Resistor

EGC

Hot

Neutral

What’s in the GFCI? (Receptacle)

Receptacle Face

Hot

Neutral

Face

Load

Face

Load

Page 15: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

What’s in the GFCI? (Circuit Breaker)

Over-Current trip

Panel Neutral

wire Trip

Mechanism

Sensing Coil

Trip Solenoid

“Load Neutral”

Terminal

Printed Circuit

Board

“Line”

Terminal

Push-To-Test

Button

“Load Power”

Terminal Primary

Current-carrying

Contacts

Handle

(ON-OFF)

Page 16: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

What’s in the GFCI? (Circuit Breaker)

Trip Solenoid

Electronic circuitry

with Grounded

Neutral detection

Push-To-Test Button

Test Resistor

“Line”

Terminal

“Load Power”

Terminal

“Load Neutral”

Terminal

Trip

Mechanism

Panel

Neutral

wire

Sensing Coil

Primary

Current-carrying

Contacts

Page 17: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

What’s in the GFCI? (Plug-in)

Electro-

Mechanical

Latching

Device

Current

Imbalance and

Grounded

Neutral

Sensors

Page 18: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

What’s in the GFCI?

(Plug-in) Push-to-test Button

15k

Resistor

Load Hot

Load Neutral

Current Imbalance

and Grounded

Neutral Sensor

Electro

Mechanical

Latching

Device

EGC

Circuitry with

Open and

Grounded

Neutral

detection

Page 19: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

Standard 120V Connection (GFCI Circuit Breaker)

120/240Vac Source

L1 N L2 HOT

N

GND

NEUTRAL

EQUIPMENT GROUND

1-POLE CIRCUIT

BREAKER WITH

GFCI

DUPLEX

RECEPTACLE

240

120

120 120

Page 20: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

120/240Vac

Source

N

N L1 L2

Line

Terminals Load

Terminals

Standard 120 Volt Connection (GFCI Receptacle)

Page 21: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

240 Volt Load – No Neutral

120/240Vac Source

L1 N L2 HOT B

N

GND

HOT A

EQUIPMENT GROUND

2-POLE CIRCUIT

BREAKER WITH

GFCI

250V DUPLEX

RECEPTACLE

240

120

120 240

Note: Load neutral circuit

not used in this circuit

Page 22: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

120/240 Volt Load

120/240Vac Source

L1 N L2 HOT B

N

GND

HOT A

EQUIPMENT GROUND

2-POLE CIRCUIT

BREAKER WITH

GFCI

240

120

120

NEUTRAL

120/240 VAC

LOAD

Page 23: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

Single Phase 120V Circuit

1A

1A

L

N

120V

Page 24: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

Multi-Wire Circuits

1A

1A

Switch Open

0A

One leg of multi-wire circuit in use

120V

120V

Page 25: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

Multi-Wire Circuits

1A

0A

Both legs of multi-wire circuit in use

120V

120V

1A

If what goes out…. Comes back.. The GFCI sees

zero total current on the circuit.

Page 26: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

GFCI Circuit Breaker on Multi-Wire Circuits

120/240Vac Source

L1 N L2 HOT B

N

GND

HOT A

EQUIPMENT GROUND

2-POLE CIRCUIT

BREAKER WITH

GFCI

240

120

120 NEUTRAL

DUPLEX

RECEPTACLE

DUPLEX

RECEPTACLE

120

120

NEUTRAL

Page 27: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

Downstream

Receptacles

N

Downstream

Receptacles

L1 L2

GFCI Receptacles

Use two GFCI

receptacles

Separate Neutrals

Junction Box

T R

GFCI Receptacle on Multi-Wire Circuits

R T

Page 28: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

This “Old House” Problem

N

GFCI installed on one circuit

Second circuit installed and neutral

“stolen” from a close-by circuit

6A

?

6A

L1

L2

Page 29: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

Line and Load Reversal on Receptacles

To Panelboard

To Downstream

Receptacle

Incorrect Wiring

To Panelboard

To Downstream

Receptacle

Correct Wiring

In the case of incorrect wiring

there will be no power at the face

or downstream.

Page 30: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

GFCI Circuit Breaker Miswiring

120/240Vac Source

L1 N L2 HOT

N

GND

NEUTRAL

EQUIPMENT GROUND

1-POLE CIRCUIT

BREAKER WITH

GFCI

DUPLEX

RECEPTACLE 240

120

120

Current does not

return through the

sensor in the circuit

breaker

Page 31: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

L

N

EGC

6A

?

?

Neutral grounded downstream

Grounded Neutral Detection

Equipment

GFCI Device

Leakage Current

Page 32: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

UL GFCI Tests

Every GFCI must pass the following end-of-line manufacturing tests:

1. no trip below 4mA (no load)

2. must trip at 6mA (no load)

3. no trip below 4mA (with load) at rated voltage

4. must trip at 6mA (with load) at rated voltage

5. must trip with 2 ohm grounded neutral

6. must trip within 25 ms with a 500 ohm fault

7. must trip with test button at +10/-15% rated voltage

8. must not trip with noise test of GFCI Standard

9. calibration test at +10/-15% rated voltage

Page 33: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

GFCI Testers Why are testers used?

• verify operation of the GFCI

• check protection of downstream receptacles

Will not test:

• GFCI calibration

• ALL types of improper installation

• Danger on 2-wire circuits

Will test for some types of improper installation:

• line/load reversal

• which outlets are protected by GFCI

• reverse polarity

• presence of the equipment ground

Page 34: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

• Test and reset buttons verify proper functioning of the GFCI

• Test button will initiate end-of-life indication or power denial if product

is no longer operational

Push-to-test Button

Test and Reset Buttons (Receptacle)

Reset Button

Page 35: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

GFCI Testers

Plug-in testers divert current

to the equipment grounding

conductor

What if there is not equipment ground....? Such as in a

406.3(D)(2)(b) and 406.3(D)(2)(c) application?

The GFCI will not trip with the external tester. The test

button must be used.

Page 36: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

Benefits of UL943 (GFCI) vs. IEC (RCD) Increased Safety Benefits

UL943 Max 6 mA - threshold for “let-go” current.

IEC Min 20 mA - threshold current for ventricular fibrillation.

Receptacle End of Life indication

Grounded Neutral protection

Portable units - Load protection if both supply neutral and ground conductors are open together.

Page 37: Understanding GFCIs...• For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. • For Receptacle

The Association of Electrical and Medical Imaging Equipment Manufacturers

Summary GFCIs have contributed significantly to the reduction in the

number of deaths due to electric shock

GFCIs look at the current going out and compare it to the

current coming back

Remember that GFCIs detect ground to neutral

connections downstream

Test the GFCI by using the test button and a load

GFCIs will not protect between line and neutral

Only Class A GFCIs (6mA) protect from electrocution from

“let-go” situations