understanding online partial discharge testing

19
Understanding Online Partial Discharge Testing Sanket Bolar Megger USA

Upload: others

Post on 28-Oct-2021

19 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Understanding Online Partial Discharge Testing

SEPTEMBER 4 - 6, 2019

Understanding Online Partial Discharge Testing

Sanket BolarMegger USA

Page 2: Understanding Online Partial Discharge Testing

SEPTEMBER 4 - 6, 2019

Need for condition based maintenance

• Time based maintenance – Tests done at prescheduled times to assess the condition of the asset

• Example, discharge test on a battery

• Condition based maintenance – Certain parameters associated with the condition of the asset monitored continuously

• Example, online DGA on a transformer

Page 3: Understanding Online Partial Discharge Testing

SEPTEMBER 4 - 6, 2019

What is partial discharge?

• Localized electrical discharge that only partially bridges the insulation

Page 4: Understanding Online Partial Discharge Testing

SEPTEMBER 4 - 6, 2019

Conventional method of PD measurement

• Mainly employed in factory testing• Measured quantity is called apparent charge • Apparent charge (pC) is the pulse charge

measured at the test terminal because of the charge transfer inside the test object due to partial discharge

• Measuring impedance calibrated by injecting a controlled pulse train

• Asset energized by a test voltage source and subjected to overvoltage conditions for a specified duration

• The apparent charge measured during the course of the test needs to be less than the limit specified in the standards

Page 5: Understanding Online Partial Discharge Testing

SEPTEMBER 4 - 6, 2019

Unconventional methods of PD measurement

• Using conventional method not practical onsite because of the presence of noise

• Unconventional methods used for detecting partial discharge onsite

• PD detection based on physical properties • No correlation with apparent charge• The following technologies used –

• RF detection• Acoustic methods• Optical methods• Chemical methods

PD

RFI

Sound

Gases

Light

Page 6: Understanding Online Partial Discharge Testing

SEPTEMBER 4 - 6, 2019

Sensor technologies

UHF measurement• PD pulse emits electromagnetic waves• UHF range: 300MHz to 3GHz• Most of the background noise is present in

lower frequencies• Some of the sensors used: Field grading

sensors, window sensors, disc sensors, etc.

Page 7: Understanding Online Partial Discharge Testing

SEPTEMBER 4 - 6, 2019

Sensor technologies

Acoustic methods• PD emits sound waves in the ultrasonic range• Measurement range: 10kHz to 300kHz• Sensors: Piezo-electric transducers,

accelerometers, condenser microphones, etc.• PD localization using multiple sensors possible• Difficulties in PD localization: Velocity of

propagation differs with media, reflections and refractions can occur

Page 8: Understanding Online Partial Discharge Testing

SEPTEMBER 4 - 6, 2019

Sensor technologies

HF measurements• HFCT uses inductive coupling• PD results in short duration current pulses

which are measured by HFCT connected on the ground of the equipment

• Difficulty: HFCT can also detect current pulses from other sources on the grounding grid

• Transient Earth Voltage (TEV) sensors use capacitive coupling

• Transient voltages develop on the metal enclosure because of internal PD

• TEV sensor can be placed on enclosure to detect PD

• Used mostly on switchgear• Difficulty: External sources can also induce TEV

Page 9: Understanding Online Partial Discharge Testing

SEPTEMBER 4 - 6, 2019

PD data for corona discharge

Page 10: Understanding Online Partial Discharge Testing

SEPTEMBER 4 - 6, 2019

PD data for corona discharge

Page 11: Understanding Online Partial Discharge Testing

SEPTEMBER 4 - 6, 2019

PD data for void discharge

At 5 kV At 9 kV

Page 12: Understanding Online Partial Discharge Testing

SEPTEMBER 4 - 6, 2019

PD data for void discharge

Page 13: Understanding Online Partial Discharge Testing

SEPTEMBER 4 - 6, 2019

PD data for surface discharge

At 3.5 kV At 6 kV

Page 14: Understanding Online Partial Discharge Testing

SEPTEMBER 4 - 6, 2019

PD data for surface discharge

At 160 MHz

Page 15: Understanding Online Partial Discharge Testing

SEPTEMBER 4 - 6, 2019

PD data for surface discharge

At 1.5 kV

Page 16: Understanding Online Partial Discharge Testing

SEPTEMBER 4 - 6, 2019

PD data for surface discharge

At 9 kV

Page 17: Understanding Online Partial Discharge Testing

SEPTEMBER 4 - 6, 2019

Case study I - Bushing on an oil circuit breaker

Page 18: Understanding Online Partial Discharge Testing

SEPTEMBER 4 - 6, 2019

Case study II – Surface discharge on cables

Page 19: Understanding Online Partial Discharge Testing

SEPTEMBER 4 - 6, 2019

Questions?

• Hope you slept comfortably