understanding the ncc · 2017-07-05 · understanding the ncc gutter and downpipe provisions for...

4
UNDERSTANDING THE NCC GUTTER AND DOWNPIPE PROVISIONS FOR HOUSING The Performance Requirements of the National Construction Code (NCC) can be met by either using a Performance Solution, 1 a Deemed-to-Satisfy Solution (i.e. complying with the DtS Provisions) or a combination of both. The following is a general representation of the DtS acceptable construction practice provisions in the NCC for the selection and installation of gutters and downpipes, including overflow measures, for housing. Housing is classified as Class 1 and 10 buildings. It is based on a national perspective and does not address any State or Territory variations. 2 This information is useful for building designers, hydraulic consultants, plumbers, builders and other on-site trades. The gutter and downpipe provisions for housing are in Volume Two of the NCC. The requirement to install drainage systems from roofs and sub-soil drains should be confirmed with the appropriate authority. These provisions need only be applied when drainage systems are necessary. The ABCB has developed a ‘Gutter, Downpipe and Overflow’ (GDO) Calculator which can be found in the Resource Library of the ABCB website. EAVE GUTTERS NCC Volume Two (Part 3.5.2) © 2017 Commonwealth of Australia and States and Territories of Australia The ABCB website is www.abcb.gov.au An eave gutter is a gutter that is fixed to a fascia (or an eave) to catch rainwater running off a roof and is part of a roof drainage system. An eave gutter must be supported by suitably fixed brackets at the stop ends and spaced at not more than 1.2 m centres along the entire length of the gutter. Eave gutters must have a minimum fall of 1:500 (unless fixed to a metal fascia). The minimum size required for an eave gutter is dependent on a number of factors. First, you need to consider the location of the building. Different locations have different rainfall intensities that the roof drainage system must cope with. For selection of eave gutters, a rainfall intensity of 5 minute duration and 20 year average recurrence interval expressed as millimetres per hour (mm/h) is used. Rainfall intensities for different locations are shown in Table 3.5.2.1 of Volume Two. 5 MINUTE DURATION RAINFALL INTENSITY EXAMPLES Table 3.5.2.1 in Volume Two shows that Mackay in QLD has a 5 minute duration rainfall intensity of 250 mm/h for a storm with an average recurrence interval (ARI) of 1 in 20 years. For Albury in NSW, it is 139 mm/h. 1 Previously known as an ‘Alternative Solution’. 2 State and Territory variations and additions to the NCC are located in the NCC. The NCC is available at the ABCB website.

Upload: others

Post on 16-Apr-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: UNDERSTANDING THE NCC · 2017-07-05 · UNDERSTANDING THE NCC GUTTER AND DOWNPIPE PROVISIONS FOR HOUSING. The Performance Requirements of the National Construction Code (NCC) can

UNDERSTANDING THE NCC

GUTTER AND DOWNPIPE PROVISIONS FOR HOUSING

The Performance Requirements of the National Construction Code (NCC) can be met by either using a Performance Solution,1 a Deemed-to-Satisfy Solution (i.e. complying with the DtS Provisions) or a combination of both. The following is a general representation of the DtS acceptable construction practice provisions in the NCC for the selection and installation of gutters and downpipes, including overflow measures, for housing. Housing is classified as Class 1 and 10 buildings. It is based on a national perspective and does not address any State or Territory variations.2 This information is useful for building designers, hydraulic consultants, plumbers, builders and other on-site trades.

The gutter and downpipe provisions for housing are in Volume Two of the NCC.

The requirement to install drainage systems from roofs and sub-soil drains should be confirmed with the appropriate authority. These provisions need only be applied when drainage systems are necessary.

The ABCB has developed a ‘Gutter, Downpipe and Overflow’ (GDO) Calculator which can be found in the Resource Library of the ABCB website.

EAVE GUTTERS NCC Volume Two (Part 3.5.2)

© 2017 Commonwealth of Australia and States and Territories of Australia The ABCB website is www.abcb.gov.au

An eave gutter is a gutter that is fixed to a fascia (or an eave) to catch rainwater running off a roof and is part of a roof drainage system. An eave gutter must be supported by suitably fixed brackets at the stop ends and spaced at not more than 1.2 m centres along the entire length of the gutter. Eave gutters must have a minimum fall of 1:500 (unless fixed to a metal fascia).

The minimum size required for an eave gutter is dependent on a number of factors. First, you need to consider the location of the building. Different locations have different rainfall intensities that the roof drainage system must cope with. For selection of eave gutters, a rainfall intensity of 5 minute duration and 20 year average recurrence interval expressed as millimetres per hour (mm/h) is used. Rainfall intensities for different locations are shown in Table 3.5.2.1 of Volume Two.

5 MINUTE DURATION RAINFALL INTENSITY EXAMPLESTable 3.5.2.1 in Volume Two shows that Mackay in QLD has a 5 minute duration rainfall intensity of 250 mm/h for a storm with an average recurrence interval (ARI) of 1 in 20 years. For Albury in NSW, it is 139 mm/h.

1 Previously known as an ‘Alternative Solution’.2 State and Territory variations and additions to the NCC are located in the NCC. The NCC is available at the ABCB website.

Page 2: UNDERSTANDING THE NCC · 2017-07-05 · UNDERSTANDING THE NCC GUTTER AND DOWNPIPE PROVISIONS FOR HOUSING. The Performance Requirements of the National Construction Code (NCC) can

Once a rainfall intensity is identified, the catchment area of the roof (that is to flow into the gutter) must be determined. Typically this is done by multiplying the length of the eave gutter by the distance between the ridge and the eave gutter. For example if the gutter is 3 metres long and the distance from the gutter to the ridge is 3 metres, then the catchment area of the roof is 9 square metres (3 m x 3 m = 9 m2).

Once the rainfall intensity and roof catchment area are known, the appropriate type/size of eave gutter is selected using Table 3.5.2.2a in Volume Two.

Volume Two of the NCC has provisions for two types of eave gutter: • Rectangular gutter;• D (quad) gutter.

GUTTER SELECTION EXAMPLETable 3.5.2.2a shows that 30 square metres of roof catchment area (which flows into one downpipe) in a location with a design rainfall intensity of 255 mm/h, requires a minimum of A or C type gutter.

© 2017 Commonwealth of Australia and States and Territories of Australia The ABCB website is www.abcb.gov.au

Top of fascia

25 mm

10 mm

10 mm

Spacer

Top of fascia

10 mmTop of fascia

25 mm

100 mm

Top of fascia

200 mm

25 mm

Top of fascia Top of fascia

25 mm

Top of fascia

20 mm

75 mm 100 mm

D (quad) gutterRectangular gutter

Top of fascia

25 mm

10 mm

10 mm

Spacer

Top of fascia

10 mmTop of fascia

25 mm

100 mm

Top of fascia

200 mm

25 mm

Top of fascia Top of fascia

25 mm

Top of fascia

20 mm

75 mm 100 mm

D (quad) gutterRectangular gutter

These gutters are then broken down into six gutter types (based on their size and shape). They are labelled A through to F and are described below.

Gutter types (as per Table 3.5.2.2b of NCC Volume Two)

Gutter type A is a medium rectangular gutter with a minimum cross sectional area of 6,500 mm².

Gutter type B is a large rectangular gutter with a minimum cross sectional area of 7,900 mm².

Gutter type C is a 115 mm D gutter with a minimum cross sectional area of 5,200 mm².

Gutter type D is a 125 mm D gutter with a minimum cross sectional area of 6,300 mm².

Gutter type E is a 150 mm D gutter with a minimum cross sectional area of 9,000 mm².

Gutter type F must be designed in accordance with the joint Australian and New Zealand Standard AS/NZS 3500.3 or Section 5 of AS/NZS 3500.5.

BOX GUTTERS NCC Volume Two (Part 3.5.2)

A box gutter is typically a gutter that is set into the slope of a roof. As a box gutter is usually located above a room or space in a building, there is an increased risk that rainwater overflow could cause damage to the building, or cause loss of amenity to its occupants.

Because of this increased risk, a box gutter must be able to cope with a 5 minute duration rainfall intensity and a 1 in 100 year average recurrence interval, rather than 1 in 20 as is the case for eave gutters.

A box gutter must be installed with a fall not less than 1:100 and be designed in accordance with the joint Australian and New Zealand Standard AS/NZS 3500.3 or Section 5 of AS/NZS 3500.5.

Examples of box gutters are shown below.

The information in this document is intended to be used as guidance material only, and is in no way a substitute for the NCC and related State and Territory legislation. The information in this publication is provided on the basis that all persons accessing the information undertake responsibility for assessing the relevance and accuracy of the information to their particular circumstances.

Page 3: UNDERSTANDING THE NCC · 2017-07-05 · UNDERSTANDING THE NCC GUTTER AND DOWNPIPE PROVISIONS FOR HOUSING. The Performance Requirements of the National Construction Code (NCC) can

© 2017 Commonwealth of Australia and States and Territories of Australia The ABCB website is www.abcb.gov.au

VALLEY GUTTERS NCC Volume Two (Part 3.5.2)

A valley gutter is an exposed open gutter located in the valley of a roof. Valley gutters on a roof with a pitch more than 12.5 degrees must have a width of at least 400 mm with at least 150 mm of the roof covering overhanging past each side of the gutter.

Examples of valley gutters are shown below.

DID YOU KNOW? A valley gutter on a roof with a pitch of less than 12.5 degrees must be designed as a box gutter.

DOWNPIPES NCC Volume Two (Part 3.5.2)

A downpipe is a pipe that carries rainwater from a gutter to a sub-surface drainage system or ground level. They are part of a roof drainage system. One downpipe must serve no more than a 12 m length of gutter and must be located as close as possible to valley gutters.

Volume Two of the NCC has provisions for four types of downpipes. They are: • 75 mm diameter (round)• 90 mm diameter (round) • 100 mm x 50 mm (rectangular)• 100 mm x 75 mm (rectangular)All of these types of downpipes can be used with all eave gutter types, except for 75 mm diameter (round) downpipes which are not suitable for use with Type E 150 mm D gutters.

OVERFLOW DESIGN NCC Volume Two (Part 3.5.2)

Allowing for rainwater overflow is critical in gutter design to minimise the risk of damage to buildings or loss of amenity for occupants. The NCC requires overflow measures capable of coping with a 5 minute duration rainfall intensity and a 100 year recurrence interval. These overflow measures can be continuous or dedicated measures.

Continuous overflow measures run along a length of gutter, for example, slots at regular intervals along the front face of a gutter. Dedicated overflow measures are specific points where rainwater overflow can occur, for example, a rainhead. These measures can be used separately or in combination to achieve the required overflow capacity. Continuous overflow measures are based on the distance from the ridge to gutter (in metres). This is then cross referenced with the 5 minute duration rainfall intensity appropriate to the location (see Table 3.5.2.3a in Volume Two of the NCC) to enable the overflow capacity required to be determined in litres per second per metre of gutter (L/s/m).

DID YOU KNOW?Overflow measures are not required for an eave gutter that is fixed to: • a verandah; or • an eave that is greater than 450 mm

in width, which— - has no lining; or - is a raked eave (with a

lining that falls away from the building).

The information in this document is intended to be used as guidance material only, and is in no way a substitute for the NCC and related State and Territory legislation. The information in this publication is provided on the basis that all persons accessing the information undertake responsibility for assessing the relevance and accuracy of the information to their particular circumstances.

Page 4: UNDERSTANDING THE NCC · 2017-07-05 · UNDERSTANDING THE NCC GUTTER AND DOWNPIPE PROVISIONS FOR HOUSING. The Performance Requirements of the National Construction Code (NCC) can

© 2017 Commonwealth of Australia and States and Territories of Australia The ABCB website is www.abcb.gov.au

Once the required overflow capacity is known, the appropriate overflow measure is selected. For example, a front face slotted gutter provides 0.5 L/s/m of overflow. In other words, 1 metre of slotted gutter will have the capacity to allow 0.5 litres per second of rainwater to overflow. Therefore, 5 metres of slotted gutter will provide 2.5 litres of overflow every second. Some examples of continuous overflow measures are provided below.• Front face slotted gutter (A) provides 0.5 L/s/m of

overflow. It must have a minimum slot opening area of 1200 mm2 per metre of gutter with the lower edge of the slots installed 25 mm below the top of the fascia.

• Controlled back gap (B) provides 1.5 L/s/m of overflow. It must have a 10 mm (or greater) spacer permanently installed between the back of the gutter and the fascia. The spacer must be installed at every bracket (and be no more than 50 mm wide). The back of the gutter must be installed a minimum of 10 mm below the top of the fascia.

• Controlled front bead height (C) provides 1.5 L/s/m of overflow. It must have the front of the gutter installed a minimum of 10 mm below the top of the fascia.

Dedicated overflow measures are based on the roof catchment area (in square metres). This is then cross referenced with the 5 minute duration rainfall intensity for a specific location (see Table 3.5.2.3b in Volume Two of the NCC) to enable the overflow capacity required to be determined in litres per second.

For example, one end stop weir will allow 0.5 litres of rainwater to overflow every second. Some examples of dedicated overflow measures are provided below.• An end stop weir (D) provides 0.5 L/s of overflow. It must

have a minimum clear width of 100 mm and be installed a minimum of 25 mm below the top of the fascia.

• An inverted nozzle (E) provides 1.2 L/s of overflow. It must be installed within 500 mm of the gutter high point with a minimum nozzle size of 100 mm x 50 mm (positioned lengthways in the gutter). The top of the nozzle must be a minimum of 25 mm below the top of the fascia.

• A front face weir (F) provides 1.0 L/s of overflow. It must have a minimum clear width of 200 mm with a minimum height of 20 mm. The weir edge must be installed 25 mm below the top of the fascia.

• A rainhead (G) provides 3.5 L/s of overflow. It must have a 75mm diameter hole in its outer face with the centre line of the hole positioned 100 mm below the top of the fascia.

Top of fascia

25 mm

10 mm

10 mm

Spacer

Top of fascia

10 mmTop of fascia

25 mm

100 mm

Top of fascia

200 mm

25 mm

Top of fascia Top of fascia

25 mm

Top of fascia

20 mm

75 mm 100 mm

D (quad) gutterRectangular gutterA

Top of fascia

25 mm

10 mm

10 mm

Spacer

Top of fascia

10 mmTop of fascia

25 mm

100 mm

Top of fascia

200 mm

25 mm

Top of fascia Top of fascia

25 mm

Top of fascia

20 mm

75 mm 100 mm

D (quad) gutterRectangular gutter

B

Top of fascia

25 mm

10 mm

10 mm

Spacer

Top of fascia

10 mmTop of fascia

25 mm

100 mm

Top of fascia

200 mm

25 mm

Top of fascia Top of fascia

25 mm

Top of fascia

20 mm

75 mm 100 mm

D (quad) gutterRectangular gutter

C

Top of fascia

25 mm

10 mm

10 mm

Spacer

Top of fascia

10 mmTop of fascia

25 mm

100 mm

Top of fascia

200 mm

25 mm

Top of fascia Top of fascia

25 mm

Top of fascia

20 mm

75 mm 100 mm

D (quad) gutterRectangular gutter

D

Top of fascia

25 mm

10 mm

10 mm

Spacer

Top of fascia

10 mmTop of fascia

25 mm

100 mm

Top of fascia

200 mm

25 mm

Top of fascia Top of fascia

25 mm

Top of fascia

20 mm

75 mm 100 mm

D (quad) gutterRectangular gutter

E

Top of fascia

25 mm

10 mm

10 mm

Spacer

Top of fascia

10 mmTop of fascia

25 mm

100 mm

Top of fascia

200 mm

25 mm

Top of fascia Top of fascia

25 mm

Top of fascia

20 mm

75 mm 100 mm

D (quad) gutterRectangular gutter

F

Top of fascia

25 mm

10 mm

10 mm

Spacer

Top of fascia

10 mmTop of fascia

25 mm

100 mm

Top of fascia

200 mm

25 mm

Top of fascia Top of fascia

25 mm

Top of fascia

20 mm

75 mm 100 mm

D (quad) gutterRectangular gutter

G

The information in this document is intended to be used as guidance material only, and is in no way a substitute for the NCC and related State and Territory legislation. The information in this publication is provided on the basis that all persons accessing the information undertake responsibility for assessing the relevance and accuracy of the information to their particular circumstances.