unit iii - psychrometry

Upload: ba27

Post on 04-Apr-2018

281 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/29/2019 Unit III - Psychrometry

    1/59

    1. M.BALACHANDRAN 10TME002

    2. K.BOOBALAN 10TME004

    3. E.DEVAGURU 10TME005

    4. S. JAKIR HUSSAIN 10TME011

    5. W. JONSON 10TME0126. I. MANIKAM 10TME021

    7. P. RAJAPRASANNA 10TME032

    8. T.RAJA 10TME034

    9. M.RAMESH BABU 10TME037

    10. D.REXDEVARAJ 10TME040

  • 7/29/2019 Unit III - Psychrometry

    2/59

    UNIT III - PSYCHROMETRY

  • 7/29/2019 Unit III - Psychrometry

    3/59

  • 7/29/2019 Unit III - Psychrometry

    4/59

    INTRODUCTION

    In the design and analysis of air conditioning plants,

    the fundamental requirement is to identify the

    various processes being performed on air. Once

    identified, the processes can be analyzed by

    applying the laws of conservation of mass andenergy. All these processes can be plotted easily on

    a psychrometric chart. This is very useful for quick

    visualization and also for identifying the changes

    taking place in important properties such astemperature, humidity ratio, enthalpy etc. The

    important processes that air undergoes in a typical

    air conditioning plant are discussed below.

  • 7/29/2019 Unit III - Psychrometry

    5/59

    SENSIBLE COOLING

    The moisture content of air remains constant but its

    temperature decreases as it flows over a cooling

    coil. For moisture content to remain constant, the

    surface of the cooling coil should be dry and its

    surface temperature should be greater than thedew point temperature of air. If the cooling coil is

    100% effective, then the exit temperature of air will

    be equal to the coil temperature. However, in

    practice, the exit air temperature will be higher thanthe cooling coil temperature. Figure shows the

    sensible cooling process O-A on a psychometric

    chart

  • 7/29/2019 Unit III - Psychrometry

    6/59

    SENSIBLE COOLING CONT.

    The heat transfer rate during this process is given by

    QC = ma(ho-ha)= ma cpm (TO-TA)

    Sensible cooling process O-A on Psychometric chart

    hoha W

    DBT

    A O

  • 7/29/2019 Unit III - Psychrometry

    7/59

    SENSIBLE HEATING

    During this process, the moisture content of air

    remains constant and its temperature increases as

    it flows over a heating coil.

    The heat transfer rate during this process is given

    by

    Qh = ma (hB - hO) = ma cpm (TB-TO)

    where Cpmis the humid specific heat (1.0216 kJ/kg

    dry air) and ma

    is the mass flow rate of dry air

    (kg/s).

  • 7/29/2019 Unit III - Psychrometry

    8/59

    SENSIBLE HEATING PROCESS ON A

    PSYCHROMETRIC CHART

  • 7/29/2019 Unit III - Psychrometry

    9/59

    COOLING AND DEHUMIDIFICATION

    When moist air is cooled below its dew-point by bringing it in

    contact with a cold surface as shown Fig, some of the water

    vapour in the air condenses and leaves the air stream as liquid,

    as a result both the temperature and humidity ratio of air

    decreases as shown. This is the process air undergoes in atypical air conditioning system. Although the actual process

    path will vary depending upon the type of cold surface, the

    surface temperature, and flow conditions, for simplicity the

    process line is assumed to be a straight line. The heat and

    mass transfer rates can be expressed in terms of the initial andfinal conditions by applying the conservation of mass and

    conservation of energy equations

    By applying mass balance for the water:

    ma. wo = ma. wc + mw

  • 7/29/2019 Unit III - Psychrometry

    10/59

    COOLING AND DEHUMIDIFICATION

    CONT.

  • 7/29/2019 Unit III - Psychrometry

    11/59

    HEATING AND HUMIDIFICATION

    During winter it is essential to heat and humidify the

    room air for comfort. As shown in Fig., this is

    normally done by first sensibly heating the air and

    then adding water vapour to the air stream through

    steam nozzles as shown in the figure.

  • 7/29/2019 Unit III - Psychrometry

    12/59

    HEATING AND HUMIDIFICATION CONT.

  • 7/29/2019 Unit III - Psychrometry

    13/59

    COOLING & HUMIDIFICATION

    As the name implies, during this process, the airtemperature drops and its humidity increases. This

    process is shown in Fig. As shown in the figure, this can

    be achieved by spraying cool water in the air stream. The

    temperature of water should be lower than the dry-bulbtemperature of air but higher than its dew-point

    temperature to avoid condensation

    (TDPT < TW < TO)

  • 7/29/2019 Unit III - Psychrometry

    14/59

    COOLING

    & HUMIDIFICATION CONT.

  • 7/29/2019 Unit III - Psychrometry

    15/59

    HEATING AND DE-HUMIDIFICATION

    This process can be achieved by using ahygroscopic material, which absorbs or adsorbsthe water vapour from the moisture. If thisprocess is thermally isolated, then the enthalpy of

    air remains constant, as a result the temperatureof air increases as its moisture content decreasesas shown in Fig. This hygroscopic material canbe a solid or a liquid. In general, the absorption ofwater by the hygroscopic material is an

    exothermic reaction, as a result heat is releasedduring this process, which is transferred to air andthe enthalpy of air increases.

  • 7/29/2019 Unit III - Psychrometry

    16/59

    HEATING AND

    DE-HUMIDIFICATION CONT.

  • 7/29/2019 Unit III - Psychrometry

    17/59

    MIXING OF AIR STREAMS

    Mixing of air streams at different states is commonly

    encountered in many processes, including in air

    conditioning. Depending upon the state of the

    individual streams, the mixing process can take

    place with or without condensation of moisture

  • 7/29/2019 Unit III - Psychrometry

    18/59

    MIXING OF AIR STREAMS

    Without condensation: Figure shows an adiabaticmixing of two moist air streams during which no

    condensation of moisture takes place. As shown in

    the figure, when two air streams at state points 1

    and 2 mix, the resulting mixture condition 3 can beobtained from mass and energy balance

  • 7/29/2019 Unit III - Psychrometry

    19/59

    MIXING OF AIR STREAMS CONT.

  • 7/29/2019 Unit III - Psychrometry

    20/59

    MIXING OF AIR STREAMS CONT.

    Mixing with condensation

    As shown in Fig., when very cold and dry air

    mixes with warm air at high relative

    humidity, the resulting mixture condition maylie in the two-phase region, as a result there

    will be condensation of water vapor and

    some amount of water will leave the system

    as liquid water.

  • 7/29/2019 Unit III - Psychrometry

    21/59

    MIXING OF AIR STREAMS CONT

    Due to this, the humidity ratio of the resulting

    mixture (point 3) will be less than that at point 4.

    Corresponding to this will be an increase in

    temperature of air due to the release of latent

    heat of condensation. This process rarely occurs

    in an air conditioning system, but this is the

    phenomenon which results in the formation of fog

    or frost (if the mixture temperature is below 0oC).

    This happens in winter when the cold air near theearth mixes with the humid and warm air, which

    develops towards the evening or after rains.

  • 7/29/2019 Unit III - Psychrometry

    22/59

    MIXING OF AIR STREAMS CONT

  • 7/29/2019 Unit III - Psychrometry

    23/59

  • 7/29/2019 Unit III - Psychrometry

    24/59

    Identify parts of the chart

    Determine moist air properties

    Use chart to analyze processes involving moist air

  • 7/29/2019 Unit III - Psychrometry

    25/59

    This is a typical psychrometric chart

  • 7/29/2019 Unit III - Psychrometry

    26/59

    This skeleton chart shows the

    arrangement of the various

    lines and/or coordinates:

    1.saturation temperature

    2. dewpoint temperature

    3. enthalpy

    4. relative humidity

    5.humidity ratio (moisturecontent)

    6. wet bulb temperature

    7. volume of mixture

    8. dry bulb temperature.

    The chart is based on a standard barometric

    (atmospheric) pressure of 101.3 kPa or 760 mm Hg.

  • 7/29/2019 Unit III - Psychrometry

    27/59

    The main coordinates of theaverage psychrometric chart are:

    saturation curve (100% RH) dry bulb temperature scale line(0% RH.)

    moisture content or humidityratio scale.

    The dry bulb temperature linesrun perpendicular to the basecoordinate. Each line representsone degree of temperaturechange, with the scale rangingfrom

    -10 C to 55 C.

  • 7/29/2019 Unit III - Psychrometry

    28/59

    The wet bulb temperaturelines extend diagonallydownward from thesaturation curve at anapproximate angle of 30 tothe base line.

    Each line represents onedegree of temperaturechange, with a scaleranging from 10 C to33 C.

    The temperature scale is

    located on the saturationcurve.

  • 7/29/2019 Unit III - Psychrometry

    29/59

    The dew pointtemperature scale isthe same scale as thewet bulb scale on thesaturation curve.However, the dew pointlines extendhorizontally to the

    moisture content scaleon the right of thechart.

  • 7/29/2019 Unit III - Psychrometry

    30/59

    The relative humiditylines follow

    approximately thesame curves as thesaturation curve.

    The saturation curveis actually the linerepresenting 100%relative humidity, withthe dry bulbtemperature scaleline representing 0%

    relative humidity ordry air.

  • 7/29/2019 Unit III - Psychrometry

    31/59

    The moisture contentor humidity ratio linesare the same as thedew point temperaturelines. However, thescale for the grams ofmoisture on the right ofthe chart is different

    and reads from 0 to 33grams of moisture perkilogram of air.

  • 7/29/2019 Unit III - Psychrometry

    32/59

    The specific volumelines run at a steep

    angle from top left tobottom right.

    The numerical values,along the bottom of thechart at the ends ofthese lines are given incubic metres perkilogram of dry air andrange from 0.75 to 0.95m/kg.

  • 7/29/2019 Unit III - Psychrometry

    33/59

    Enthalpy is total heatcontent and is designatedby the letter h.

    In psychrometric terms,enthalpy defines the heatquantity in the air and themoisture in the air.

    It is measured in kilojoulesper kilogram of dry air.

    The enthalpy lines on apsychrometric chart arethe same as the wet bulblines.

  • 7/29/2019 Unit III - Psychrometry

    34/59

    The enthalpy scale islocated in convenient

    sections adjacent to thesaturation temperaturecurve and ranges from10 to 110 kJ/kg of dryair.

    The scale can be readby extending the wetbulb lines until theymeet the scale.

  • 7/29/2019 Unit III - Psychrometry

    35/59

    If the value of any two of thepsychrometric properties isknown, the value of any otherproperty can be determined

    from the psychrometric chart. Normal practice is for the dry

    and wet bulb temperatures ofa sample of air to be takenand then these temperatures

    are plotted on the chart. Thetwo lines representing thesetemperatures will alwayscross at some point and thispoint then represents thecondition of the air in thesample.

    Once this point has beendetermined, values for otherproperties can be identified.

  • 7/29/2019 Unit III - Psychrometry

    36/59

    GRAND SENSIBLE HEAT FACTOR (GSHF)

    Grand Sensible Heat Factor is the ratio of the total

    sensible heat to the grand total heat load that the

    conditioning apparatus must handle, including the

    outdoor air heat loads.

    This ratio is expressed as:

  • 7/29/2019 Unit III - Psychrometry

    37/59

    GRAND SENSIBLE HEAT FACTOR

    The air which is passing through the AHU coil increases or

    decreases the temperature and/or the moisture content. The amount

    of rise or fall is determined by the total sensible and latent heat load

    that the conditioning apparatus must handle. The condition of the air

    entering the apparatus (mixture condition of outdoor and returning

    room air) and the condition of the air leaving the apparatus is plottedon the psychrometric chart as shown below

  • 7/29/2019 Unit III - Psychrometry

    38/59

    ROOM SENSIBLE HEAT FACTOR (RSHF)

    The room sensible heat factor (RSHF) represents

    the psychometric process of the supply air within

    the conditioned space. Room Sensible Heat Factor

    is the ratio of room sensible and room latent heat

  • 7/29/2019 Unit III - Psychrometry

    39/59

    ROOM SENSIBLE HEAT FACTOR (RSHF) The supply air to a conditioned space must have

    the capacity to offset simultaneously both the room

    sensible and room latent heat loads. The process is

    plotted on the standard psychometric chart as

    below

  • 7/29/2019 Unit III - Psychrometry

    40/59

    BYPASS FACTOR

    In most cooling applications, the air leaving the

    cooling coil is not entirely saturated since some air

    does not come in contact with the cooling coil. The

    fraction of air that misses the coil is called the

    bypass factor, BF. The bypass factor can bedetermined from the temperature of water supplied

    to the cooling coil and from the states of incoming

    and exiting air.

  • 7/29/2019 Unit III - Psychrometry

    41/59

    BYPASS FACTOR

  • 7/29/2019 Unit III - Psychrometry

    42/59

    REQUIREMENTOF COMFORT AIR CONDITIONING

  • 7/29/2019 Unit III - Psychrometry

    43/59

    REQUIREMENTOF COMFORT AIR

    CONDITIONING

  • 7/29/2019 Unit III - Psychrometry

    44/59

    REQUIREMENTOF COMFORT AIR

    CONDITIONING

  • 7/29/2019 Unit III - Psychrometry

    45/59

    REQUIREMENTOF COMFORT AIR

    CONDITIONING

  • 7/29/2019 Unit III - Psychrometry

    46/59

    COMFORT CHART

    The comfort chart, shown in Figure, correlates the perception ofcomfort with the various environmental factors known to influence it.

    The dry-bulb temperature is indicated along the bottom. The right

    side of the chart contains a dew point scale, and the left side a wet

    bulb temperature scale indicating guide marks for imaginary lines

    sloping diagonally down from left to right. The lines curving upwardfrom left to right represent RHs.

    ET* lines are also drawn. These are the sloping dashed lines that

    cross the RH lines and are labelled in increments of 5F. At any point

    along any one of these lines, an individual will experience the same

    thermal sensation and will have the same amount of skin wetnessdue to regulatory sweating. CLO levels at which 94 percent of

    occupants will find acceptable comfort are also indicated.

  • 7/29/2019 Unit III - Psychrometry

    47/59

    COMFORT CHART

  • 7/29/2019 Unit III - Psychrometry

    48/59

    EFFECTIVE TEMPERATURE

    This factor combines the effects of dry bulb temperature

    and air humidity into a single factor. It is defined as the

    temperature of the environment at 50% RH which results

    in the same total loss from the skin as in the actual

    environment. Since this value depends on other factors

    such as activity, clothing, air velocity and Tmrt, a StandardEffective Temperature (SET) is defined for the following

    conditions:

    Clothing = 0.6 clo

    Activity = 1.0 metAir velocity = 0.1 m/s

    Tmrt= DBT (in K)

  • 7/29/2019 Unit III - Psychrometry

    49/59

    TEMPERATURE CONDITION

    Inside design conditions for Winter:

    Top between 20.0 to 23.5oC at a RH of

    60%

    Top between 20.5 to 24.5oC at a DPT of2oC

    Inside design conditions for Summer:

    Top

    between 22.5 to 26.0o

    C at a RH of60%

    Top between 23.5 to 27.0oC at a DPT of

    2oC

  • 7/29/2019 Unit III - Psychrometry

    50/59

    TEMPERATURE CONDITION

  • 7/29/2019 Unit III - Psychrometry

    51/59

    OUTDOOR DESIGN CONDITIONSFOR SUMMER

    Selection of maximum dry and wet bulb temperatures at aparticular location leads to excessively large cooling

    capacities as the maximum temperature generally persists

    for only a few hours in a year. Hence it is recommended that

    the outdoor design conditions for summer be chosen based

    on the values of dry bulb and mean coincident wet bulb

    temperature that is equaled or exceeded 0.4, 1.0 or 2.0 %

    of total hours in an year. These values for major locations in

    the world are available in data books, such as AHRAE

    handbooks. Whether to choose the 0.4 % value or 1.0 %value or 2.0 % value depends on specific requirements. In

    the absence of any special requirements, the 1.0% or 2%

    value may be considered for summer outdoor design

    conditions

  • 7/29/2019 Unit III - Psychrometry

    52/59

    OUTDOOR DESIGN CONDITIONS FORWINTER

    Similar to summer, it is not economical to design a winter airconditioning for the worst condition on record as this would

    give rise to very high heating capacities. Hence it is

    recommended that the outdoor design conditions for winter

    be chosen based on the values of dry bulb temperaturethat is equalled or exceeded 99.6 or 99.0 % of totalhours in an year. Similar to summer design conditions,these values for major locations in the world areavailable in data books, such as AHRAE handbooks.

    Generally the 99.0% value is adequate, but if thebuilding is made of light-weight materials, poorlyinsulated or has considerable glass or spacetemperature is critical, then the 99.6% value is

    recommended.

  • 7/29/2019 Unit III - Psychrometry

    53/59

    VENTILATION: HUMAN ISSUES

    Comfort ventilation Perceived indoor air quality

    Odors

    Olfs, decipols

    Health ventilation

    Toxicity, illness

    Exposure guidelines:

    Threshold limit values (TLVs)

    Permissible exposure limits (PELs)

    Time weighted average (TWA) Short-term exposure limit (STEL)

    Ceiling limit (CLG)

    Biological Exposure Indices (BEIs)

    ?

  • 7/29/2019 Unit III - Psychrometry

    54/59

    WHYVENTILATEABUILDING?

    Comfort ventilation

    Reduces odors

    Improves thermal comfort

    Health ventilation

    Ilutes air contaminants

    Provides fresh air

    Structural cooling

    Maintains integrity of building envelope and building

    contents

  • 7/29/2019 Unit III - Psychrometry

    55/59

    AIRFLOWPRINCIPLES

    Air flows from areas of high pressure to areas of

    low pressure.

    Air flows from areas of positive pressure to areas of

    negative pressure.

    Blowing is easier than sucking!

  • 7/29/2019 Unit III - Psychrometry

    56/59

    VENTILATION STANDARDS

    European approach is to calculate ventilation requirements based

    on CO2 levels(occupancy) and odors (olfs). The higher ventilation rate from both calculations is the one to be

    applied.

    Assumption is that olfs are predictive of IAQ, which in turn is

    predictive of SBS.

    minimum ventilation rates and other requirements for commercialand institutional buildings

    Minimum ventilation rate - offices 5 cfmpp outdoor air

    Breathing Zone Outdoor Airflow

  • 7/29/2019 Unit III - Psychrometry

    57/59

    VENTILATION STANDARDS

    Ventilation and Acceptable Indoor Air Quality in Low-

    Rise Residential Buildings.

    Nationally recognized indoor air quality standard

    developed solely for residences.

    Defines the roles of and minimum requirements for

    mechanical and natural ventilation systems and the

    building envelope intended to provide acceptable

    indoor air quality in low rise residential buildings.

  • 7/29/2019 Unit III - Psychrometry

    58/59

    VENTILATIONCOMMONASSUMPTIONS

    Increasing the ventilation rate will reduce the

    concentration of indoor air pollutants.

    Increasing the ventilation rate will improve occupant

    perceptions of IAQ.

    Increasing the ventilation rate will decrease

    complaints of odors.

    Increasing the ventilation rate will decrease

    complaints of the sick building syndrome

  • 7/29/2019 Unit III - Psychrometry

    59/59

    COMFORTVENTILATION: ODORCONTROL

    Ventilation is needed to control indoor odors.

    People are a source of indoor odors (body odor).

    Body odor (sweaty armpit smell) is caused by 3-

    methyl-2-hexenoic acid, a metabolic byproduct of

    bacteria that live in the armpit (lipophilic diptheroids)

    and feed on apocrine secretions.

    ~90% of men and 67% of women have these

    bacteria resident in the armpit, and women produce a

    milder odor than men.

    ~5% of people cannot smell body odor.