University of Bologna Department of Electrical Engineering PhD in Electrical Engineering XIV course MODELING OF LIGHTNING-INDUCED VOLTAGES ON DISTRIBUTION NETWORKS FOR THE SOLUTION OF POWER QUALITY PROBLEMS, AND RELEVANT IMPLEMENTATION IN A TRANSIENT PROGRAM PhD Thesis of MARIO PAOLONE Tutor Prof. CARLO ALBERTO NUCCI PhD Coordinator Prof. FRANCESCO NEGRINI 1998-2001

Upload: doanminh

Post on 23-Feb-2018

213 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

University of Bologna

Department of Electrical Engineering

PhD in Electrical Engineering XIV course

MODELING OF LIGHTNING-INDUCED VOLTAGES ON DISTRIBUTION NETWORKS FOR THE SOLUTION

OF POWER QUALITY PROBLEMS, AND RELEVANT IMPLEMENTATION

IN A TRANSIENT PROGRAM

PhD Thesis of MARIO PAOLONE

Tutor Prof. CARLO ALBERTO NUCCI

PhD Coordinator Prof. FRANCESCO NEGRINI

1998-2001

Page 2: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

I

Index

Chapter 1. – Introduction…………………………………………………………. pag. 1

Chapter 2. – Evaluation of lightning-induced voltages on transmission lines…. pag. 4

2.1. – Engineering return-stroke current models………………………………… pag. 6

2.2. – Lightning electromagnetic field appraisal………………………………… pag. 12

2.3. – Transmission line coupling models……………………………………….. pag. 14

Chapter 3. – LEMP-to transmission-line coupling models for distribution

systems and their implementation in a transient program………..

pag. 24

3.1. – Lines with transverse discontinuities……………………………………… pag. 24

3.1.1. – Proposed model………………………………….…………………… pag. 25

3.1.2. – Numerical implementation…………………………………………… pag. 26

3.1.3. – Comparison with experimental results and simulations …………….. pag. 36

3.2. – Distribution systems………………………………………………………. pag. 49

3.2.1. – Proposed approach…………………………………………………… pag. 50

3.2.2. – Interface between the developed line model and transient programs... pag. 51

3.2.3. – Comparison with experimental results and simulations...…………… pag. 56

Chapter 4. – Influence of lightning-induced overvoltages on power quality…... pag. 70

4.1. – Statistical evaluation of the lightning performance of distribution lines….. pag. 72

4.1.1. – Procedure based on the Monte Carlo method and on the developed

LEMP-to-transmission-line coupling models for distribution lines….

pag. 72

4.1.2. – Comparison with the IEEE Std 1410-1997…………………………... pag. 74

4.1.3. – Sensitivity analysis…………………………………………………… pag. 78

4.2. – Case of a typical Italian distribution line………………………………….. pag. 84

4.2.1. – Model extension……………………………………………………… pag. 84

Page 3: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

II

4.2.2. – Results………………………………………………………………... pag. 87

Chapter 5. – Conclusions………………………………………………………….. pag. 90

References………………………………………………………………………….. pag. 94

Appendix A.1. – Numerical treatment of line transverse discontinuities in 1st

order FDTD scheme……………………………………………..

pag. 104

Appendix A.2. – Comparison between 1st and 2nd order FDTD integration

schemes…………………………………………………………..

pag. 107

Page 4: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

III

List of symbols

Ae: incident vector potential; ezA : vertical component of the incident vector potential;

B: total magnetic field;

Be: external incident magnetic field;

Br: radial component of the LEMP magnetic field;

Bs: scattered magnetic field; syB : scattered induction magnetic field;

C': single-conductor line capacitance per-unit-length;

c: vacuum light velocity;

Cdyn: voltage-dependent dynamic capacitance in the corona phenomenon;

[ ]ijC ' : multi-conductor line capacitance matrix per unit length;

d: distance of the stroke location from the line;

dl: lateral attractive distance;

E: total electric field;

Ee: external incident electric field; ezE : vertical component of the incident electric field along the z axis;

nkEh : spatial-temporal discretized value of the horizontal component of the incident electric

field along the line; exE : horizontal component of the incident electric field along the x axis;

rE : radial component of the LEMP electric field;

rE : Fourier-transform of the electric field radial component;

rpE : Fourier-transform of the electric field radial component for an ideal ground;

Es: scattered electric field;

Ez: vertical component of the LEMP electric field;

erfc: complementary error function;

Fp: number of annual insulation flashovers per km of distribution line;

G' : single-conductor line conductance per-unit-length;

G1, G2: Bergeron equivalent generators;

H: lightning channel height;

Page 5: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

IV

h: single-conductor line height;

pH φ : Fourier-transform of the magnetic field radial component for an ideal ground;

i0’(t) current at the EMTP node;

ig: current that flow through the connection between a line conductor and ground;

Ip: lightning return stroke peak value;

I0: channel-base current peak value of the Heidler function;

),( tzi : spatial-temporal lightning current distribution along the return stroke channel;

),( txi : single-conductor line current induced along the line; nki : spatial-temporal discretized value of the induced current along the line;

[igp]: vector of the induced currents diverted to ground in correspondence of the pole;

[ ]),( txii : multi-conductor line induced current vector along the line;

k: spatial discretization index;

kmax: maximum value of the spatial discretization index;

k1, k2: parameters related to the corona model;

L': single-conductor line external inductance per-unit-length;

[ ]ijL' : multi-conductor line external inductance matrix per unit length;

n: exponent of the Heidler function;

n: temporal discretization index;

NC: number of line conductors;

Ng: ground flash density;

nmax: maximum value of the temporal discretization index;

)O( x∆ : remainder term, which approaches zero as the first power of the spatial increment;

)O( 3t∆ : remainder term, which approaches zero as the third power of the temporal

increment;

Pi: probability of lightning current peak to be within interval i;

R: distance of the electric dipole from the observation point;

r: projection of R in the plane xy;

R0: left line termination resistive load;

rg : striking distances to ground;

Rg: pole grounding resistance;

RL: right line termination resistive load;

Page 6: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

V

[Rgp]: diagonal matrix of the phase-to-ground resistances of the poles when a flashover

occurs;

rs: striking distances to wire;

v: return stroke wave front velocity;

),( txvi : single-conductor line incident voltage along the line;

),( txv s : single-conductor line scattered voltage along the line;

),( txv : single-conductor line total voltage along the line;

v0’(t): voltage at the EMTP node; nkv : spatial-temporal discretized value of the scattered voltage along the line;

),(' txv g : voltage drop due to the transient ground impedance;

( )t,xvth : corona threshold voltage;

[ ]),( txvei : multi-conductor line incident voltage along the line;

[ ]),( txv si : multi-conductor line scattered voltage vector for along the line;

[ ]),( txvi : multi-conductor line total voltage vector for along the line;

Z0: vacuum impedance;

Zc : single-conductor line characteristic impedance; 'gZ : ground impedances; 'wZ : wire impedances;

∆t: time integration step;

∆x: spatial integration step;

δ: skin depth factor;

ε0: vacuum permittivity constant;

εrg: relative ground permittivity;

φ : total induced scalar potential;

φ i: incident scalar potential;

Γ0(t) is the EMTP termination type;

Γ : integro-differential operator for the representation of a single-conductor line transverse

discontinuities;

[ΓK]: integro-differential matrix operators for the representation of a multi-conductor line

transverse discontinuities;

Page 7: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

VI

η: correction factor of the Heidler function;

λ: decay constant of the MTLE model;

µ0: vacuum permeability constant;

µg; ground permittivity;

ρ: correlation coefficient between lightning current amplitude and its front duration;

σg: ground conductivity;

τ1: time constant of the wave front of the Heidler function;

τ2: time constant of the wave decay of the Heidler function;

τg: ground time constant;

ω: angular frequency;

ξ’g: inverse Fourier-transform of the ground impedance;

⊗ : convolution product.

Page 8: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 1. – Introduction pag.

1

Chapter 1. – Introduction One of the main causes of a-periodic disturbances on distribution networks, which

seriously affect the power quality, is certainly the lightning activity1, and in particular the so-called lightning ‘indirect’ activity2.

Due to the limited height of distribution lines of medium and low voltage distribution networks as compared to that of the structures in their vicinity, indirect lightning return strokes are more frequent events than direct strokes3, and for this reason we shall focus on such a type of lightning event.

The analysis of the distribution networks response against Lightning Electro Magnetic Pulse (LEMP), requires the availability of accurate models of LEMP-illuminated lines. These should be able to reproduce the real and complex configuration of distribution systems including the presence of shielding wires and their groundings, as well as that of surge arresters and distribution transformers.

In addition to the accurate modeling of the overhead lines, the development of models of the entire distribution networks is clearly necessary. This should allow, in principle, to optimize the number and location of protective devices and then to minimize the number of outages.

The first part of the research activity here reported has been dedicated to the development of a complex LEMP-illuminated line model based on a modification of the Agrawal et al. [1980] coupling model, able of predicting LEMP response of a multi-conductor overhead line with transverse discontinuities represented by groundings of shielding wire, or neutral conductor, and surge arresters on the phase conductors.

The model has been then implemented in a computer code using a numerical integration scheme based on the finite difference time domain (FDTD) technique. In particular a 2nd order FDTD scheme has been selected to improve the numerical stability of the line model.

The developed line model has been validated by means of a series of results obtained during an experimental campaign carried out at the Swiss Federal Institute of Technology in Lausanne during the year 2000 by means of a NEMP simulator.

The natural extension of the developed LEMP-illuminated line model consists in a LEMP-illuminated distribution system. This can be accomplished, in principle, by appropriately rewriting, for each type of termination or model component, the boundary condition of each illuminated line forming the distribution system. An alternative approach has been used to develop such a complex distribution system model. The model is based on

1 [e.g. Boonseng and Kinnares, 2001]. 2 [e.g. Gunther and Mehta, 1995]. 3 [Rusck, 1977; IEEE WG on lightning performance of distribution lines, 1997].

Page 9: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 1. – Introduction pag.

2

the contemporary use of the above mentioned illuminated line model, and the Electro Magnetic Transient Program (EMTP96). Other similar programs have been presented in the literature: they present limitations concerning the calculation of the LEMP and the type of phenomena that can be dealt (e.g. corona), which the present model is aimed at overcoming.

The developed complex system model has also been validated by means of experimental results provided by the lightning group of the University of Saõ Paulo.

We have then made use of the Monte Carlo method and of the developed models, to assemble a statistical procedure aimed at assessing the lightning performance of distribution lines.

So far, several studies on the subject have been carried out without considering the real configuration of the distribution systems, i.e. without considering the presence of shielding wires, of their groundings, of the steady-state voltage superimposed to that induced by lightning and, more important, without any indication on the nature of the real number of faults. The procedure here proposed is aimed at overcoming the above mentioned limitations.

The structure of the thesis is the following: Chapter 2. A résumé on the models proposed and applied in the literature to calculate

lightning-induced overvoltages is given. The chapter is divided in three paragraphs to illustrate: a) the most used lightning current return stroke models, b) the relevant electromagnetic field appraisal and c) the coupling between the LEMP and the overhead multi-conductor line. Section c) also compares the simplified formula of Rusck [1958] with the Agrawal et al. [1980] coupling model.

Chapter 3. This chapter illustrates the models implementation. It gives a description of

the illuminated-line model proposed to take into account line transverse discontinuities. It illustrates the numerical implementation of a FDTD 2nd order integration scheme, applied to the complex line model. The experimental validation of such model is then shown by means of the experimental results obtained with the EMP simulator of the Swiss Federal Institute of Technology. A sensitivity analysis on the effect of periodical groundings of the shielding wire, and on the presence of surge arresters on lightning induced overvoltages is illustrated and discussed.

In the same chapter is also described the illuminated distribution system model based on an interface of the developed line model with the Electro Magnetic Transient Program (EMTP96). A similar interface has been realized also concerning the Power System Blockset in Matlab Environment and a description of it is also given.

Page 10: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 1. – Introduction pag.

3

A comparison between theoretical and experimental results is presented. It is based on the experimental results obtained using a LEMP simulator on a reduced scale distribution system by the lightning research group at the University of Saõ Paulo.

Chapter 4. The statistical procedure based on the developed models and on the Monte

Carlo method is first illustrated and then compared, for simple line configuration, with the similar one proposed in the IEEE Std 1410-1997. A sensitivity analysis is then given and discussed which involves the main parameters such as the ground conductivity, the multi-conductor line configuration, the shielding wire height, its grounding resistance and grounding spacing and the presence of surge arresters. The possibility to take into account the steady-state line voltage and the change of the phase-to-ground coupling factor when a flashover occurs, is finally illustrated and its implications are discussed. The application of the statistical procedure to a typical Italian distribution line is finally presented in order to evaluate the number and type of flashovers that occur per 100 km per year.

Chapter 5 is devoted to the conclusions. This thesis represents one of the results obtained in a framework of an international

collaboration between the University of Bologna, the Swiss Federal Institute of Technology of Lausanne and the University of Rome ‘La Sapienza’.

I would like to thank chiefly prof. Carlo Alberto Nucci for his fundamental guide all

along the three years of PhD and his constant and helpful support. Acknowledgements are also due to prof. Dino Zanobetti for precious advises during the layout of this thesis and to prof. Alberto Borghetti for important discussions on the statistical procedure and on the implementation of the developed models in the transient program.

I would also like to thank prof. Farhad Rachidi for his fundamental help in the experimental activity carried out at the Swiss Federal Institute of Technology in Lausanne and for very useful discussions.

Thanks are also due to prof. Alexandre Piantini for providing the experimental results of the induced surges on the reduced scale distribution system.

Acknowledgements are due to dr. Alberto Gutierrez who has developed the Mat-LIOV code and who has contributed in developing the Mat-LIOV interface with the Power system Blockset in Matlab environment.

Finally I would to thank Luigia for her comprehension and fundamental support all along

the three years of PhD.

Page 11: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 2. – Evaluation of lightning-induced voltages on transmission lines pag.

4

Chapter 2. – Evaluation of lightning-induced voltages on transmission lines

The estimation of lightning induced overvoltages has been the object of various studies

since the early years of the past century. The first studies reported by Wagner K.W. [1908], Bewley [1929], Norinder [1936]

considered the overvoltage as being produced basically via electrostatic induction by a charged cloud. According to Wagner K.W. [1908], when the lightning discharge occurs, the charge bound to the line is released in form of traveling waves of voltage and current. Wagner did not consider the electromagnetic field radiated by the lightning return-stroke current.

In the early 1940's Wagner C.F and McCann [1942], based on Schonland's [1934] investigations of the nature of the lightning discharge, published a paper in which the overvoltage was considered mostly due to the return stroke phase; an assumption that was accepted in practically all the subsequent studies1. Rachidi et al. [1994] have shown that for lightning particularly close to the distribution line (30 m or so), some important overvoltages can be produced also by leader phase preceding the return stroke one. However, in what follows, we shall be interested only in the voltages induced by the electromagnetic field change produced by the return-stroke phase2.

In parallel with the theoretical studies, several measurement campaigns on lightning electromagnetic fields3 and many tests with voltages induced on experimental lines4 have been performed. For our purposes it is worth reminding that practically all the above

1 [Golde, 1954; Lundholm, 1957; Rusck, 1958; Papet-Lépine, 1960; Chowdhuri, 1969,1989; Fisher and

Uman, 1972; Cinieri and Fumi , 1978; Hamelin et al., 1979; Eriksson et al., 1982; Saint-Privat-d'Allier Research Group, 1982; Yokoyama, 1984; Master and Uman, 1984; Liew and Mar, 1986; Diendorfer, 1990; Zeddam and Degauque, 1990; Michishita et al., 1991; Imai et al., 1993; Ishii et al. 1994, Nucci, et al. 1993,2000].

2 All the models dealt with in this thesis can indeed be extended to take into account also the leader field in relatively simple manner. It is reminding that taking into account the leader field not change significantly the results reported here.

3 [Lin and Uman, 1973; Tiller et al., 1976; Weidman and Krider, 1978; Lin et al., 1979; McDonald et al., 1979; Yokoyama, 1980; Cooray and Lundquist, 1982; Krider and Guo, 1983; Cooray and Lundquist, 1985; Rakov and Uman, 1990; Rakov et al., 1998, Shostak et al., 2000; Willett and Krider, 2000; Rachidi et al., 2001].

4 [Norinder, 1936; Berger, 1955; Koga et al., 1981; Eriksson et al., 1982; Yokoyama et al., 1983; Darveniza and Uman, 1984; Master et al., 1984; Cooray and de la Rosa, 1986; Yokoyama et al., 1986; de la Rosa et al., 1988; Rubinstein et al., 1989; Yokoyama et al., 1989; Yacoub et al. 1991; Georgiadis et al., 1992; Michishita and Ishii, 1992; Barker et al., 1993; Fernandez et al., 1999a,1999b; Mata et al., 2000; Uman et al., 2000].

Page 12: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 2. – Evaluation of lightning-induced voltages on transmission lines pag.

5

mentioned studies, both theoretical and experimental, have dealt with single line configuration.

Nowadays the evaluation of lightning induced overvoltages is generally performed in the following way:

! the lightning return-stroke electromagnetic field change is calculated at a number of

points along the line employing a lightning return-stroke current model, namely a model that describes the form of the return stroke current as a function of height and time along the vertical channel. To this purpose, the return stroke channel is generally considered as a straight vertical antenna (see Fig. 2.1);

! the electromagnetic field (LEMP – Lightning Electro Magnetic Pulse) is then evaluated and used to calculate the induced overvoltages making use of a coupling model which describes the interaction between the field and the line conductors.

z'

H

IMMAGINE

dz'i(z',t)

R

R'

r

x

yZ

L

zz'

P (x,y,z)

Z o

Eh

E

r

zE

EE x

P(x,y,z)

φ

IMAGE

v

i(z,t): lightning current; H: lightning channel height; v: lightning wave front velocity.

Fig. 2.1. – Return Stroke channel.

The first point will be discussed in the next paragraph 2.1, while the second one will be

dealt with in the two subsequent paragraphs devoted to the LEMP radiated by a return stroke 2.2, and to the coupling models for the evaluation of the induced overvoltages 2.3 respectively.

Page 13: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 2. – Evaluation of lightning-induced voltages on transmission lines pag.

6

2.1. – Engineering return-stroke current models A comprehensive review of the various models proposed in the literature to predict some

of the observed properties of lightning return strokes is beyond the scope of this thesis; the interested reader is referred to two papers by Rakov and Uman [1998] and by Gomes and Cooray [2000]; here we shall limit the discussion to those models that are generally called ‘engineering return-stroke current models’.

A return stroke current model is a mathematical specification of the spatial-temporal distribution of the lightning current along the discharge channel (or the channel line charge density). Such a mathematical specification include the return stroke wavefront velocity, which is generally one of the model inputs [e.g. Uman and McLain, 1969], the charge distribution along the channel, and a number of adjustable parameters related, to a certain extent, to the discharge phenomenon [e.g. Gomes and Cooray, 2000] and which should be inferred by means of model comparison with experimental results [e.g. Nucci and Rachidi, 1989]. Outputs can be directly used for computation of electromagnetic fields.

In these models the lightning channel is in general assumed to be straight, vertical and perpendicular to the conducting ground plane, as shown in Fig. 2.1, where the geometry of the problem is also defined.

Now, for the problem we are dealing with, only those models in which the return stroke current i(z',t) can be simply related to the specified channel-base current i(0,t) are of interest from an engineering point of view, since it is only the channel-base current that can be measured directly and for which experimental data are available. We shall call these models, ‘engineering return stroke current models’, or simply ‘engineering models’ in accordance with Rakov [2001].

The most popular engineering model is probably still the Transmission Line (TL) model, proposed about 30 years ago by Uman and McLain [1969]. A number of other models have been subsequently proposed with the primary aim of calculating the return stroke electromagnetic field given a certain lightning current or, vice versa, inferring the lightning current characteristics from remote electromagnetic field measurements5. In addition and although not originally formulated as engineering models, we feel worth mentioning certain more physically plausible models, such as the models by Lin et al. [1980], by Master et al. [1981] and by Cooray [1993,1998a].

In the large majority of the return-stroke models above mentioned6, the channel-base current is viewed as the result of the flowing towards ground of charges contained in the leader channel and in the corona sheath around the channel during the return-stroke phase.

5 [Heidler, 1985b; Rakov and Dulzon, 1987; Nucci et al. ,1988; Diendorfer and Uman, 1990; Thottappillil

et al., 1991; Rakov and Uman, 1998; Gomes and Cooray, 2000]. 6 [Lin et al., 1980; Master et al. 1981; Heidler, 1985b; Nucci et al., 1988; Diendorfer and Uman, 1990;

Thottappillil et al., 1991; Cooray, 1993; Cooray, 1998].

Page 14: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 2. – Evaluation of lightning-induced voltages on transmission lines pag.

7

They are the so-called traveling-current-source-type [Rakov and Uman, 1998], or discharge-type [Gomes and Cooray, 2000] models. These models have been conceived to describe the field change due to the return-stroke phase, the total return-stroke field being the sum of the return-stroke field change plus the final value of the field produced by the preceding leader phase.

The validation of the various return-stroke models is not straightforward since, for natural lightning, no experimental set of simultaneously-measured currents and fields is available. Thus, although a direct comparison between model predictions and experimental results is possible for artificially-initiated lightning7 only a qualitative comparison is possible for natural lightning. In particular, a return stroke model is to be considered adequate if, starting from a typical channel-base current, it reproduces the typical features of the observed fields at different distances. The characterisation of natural lightning electromagnetic fields is therefore of importance, and an exhaustive survey can be found in Uman and Krider [1982]; Uman [1987]; Rakov et al. [1995]; Rakov and Uman [1998].

The validation only with the comparison among each other of some of the most popular return-stroke models can be found in several papers, [e.g. Uman and McLain, 1969; Lin et al., 1980; Nucci et al., 1990], who used essentially data from natural lightning. Thottappillil and Uman [1994] used data from triggered lightning to compare some engineering return-stroke models.

Not all of the above mentioned engineering return-stroke models have been used to calculate lightning-induced voltages. To the best of our knowledge, the most commonly adopted for such a purpose are nowadays:

! the Transmission Line (TL) model [Uman and McLain, 1969]; ! the Traveling Current Source (TCS) model [Heidler, 1985]; ! the Modified Transmission Line Exponential (MTLE) model [Nucci et al., 1988;

Rachidi and Nucci, 1990]; ! the Diendorfer-Uman (DU) model [Diendorfer and Uman, 1990]. From the review papers earlier mentioned (in particular from Nucci et al., [1990];

Thottapphillil et al., [1993b]; Rakov and Uman, [1998]; and Gomes and Cooray, [2000]) we conclude that all the above models allow the reproduction of overall fields that are reasonable approximations of measured fields from natural and triggered lightning; Gomes and Cooray [2000] have shown that also the models by Cooray [1993], can predict with good approximation all typical features of experimentally observed fields.

7 [Saint-Privat-D'Allier Res. Group, 1982; Willett et al., 1988; Leteinturier et al., 1990; Thottappillil and

Uman, 1993b; Rubinstein et al., 1995; Uman et al., 1995].

Page 15: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 2. – Evaluation of lightning-induced voltages on transmission lines pag.

8

If one considers, however, that for lightning-induced voltage calculation it is the early time region of the field that plays the major role in the coupling mechanism [Nucci et al., 1993], it follows that the most adequate models are probably the MTL-type ones (see Tab. 2.1). Additionally, although the TL model does not allow for any net charge removal from the channel and does not reproduce realistic fields for late time calculations [Nucci et al., 1990], the early time field prediction of the TL model is very similar to that of the more physically reasonable MTLL and MTLE models and thus, for the problem of interest, it can be considered a useful and relatively simple engineering tool.

Absolute Error = (Ecalc - Emeas)/Emeas

TL MTL TCS DU

Mean 0.17 0.16 0.43 0.23 St.Dev. 0.12 0.11 0.22 0.20

Min. 0.00 0.00 0.14 0.00 Max. 0.51 0.45 0.84 0.63

Tab. 2.1. – Summary of statistics on the absolute error of the model peak fields on the basis of triggered

lightning simultaneously measured currents, velocities and fields (subsequent return strokes). With reasonable approximation the results of the MTL column apply to both MTLE and MTLL. Adapted from Thottappillil

and Uman [1993b]. For the current at the channel base the following analytical expression [Heidler, 1985a] is

adopted8:

2

1

10

1

),0( τ

τ

τη

t

n

n

et

tIti

+

= (2.1)

where

nn

e

1

1

2

2

1

= ττ

ττ

η (2.2)

8 It is worth noting that so far it has been implicitly assumed that the channel base current is not affected by

reflection of the charges flowing downward the channel during the return stroke phase. Heilder and Hopf [1994] have addressed this issue by extending the TCS model to account for these reflections. This point is certainly of importance and stresses the need for additional experimental data useful for further model validation, but is, however, beyond the scopes of this thesis.

Page 16: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 2. – Evaluation of lightning-induced voltages on transmission lines pag.

9

and ! I0 is the amplitude of the channel-base current; ! τ1 is the front-time constant; ! τ2 is the decay-time constant; ! η is the amplitude correction factor; ! n is an exponent (2÷10). Function (2.1) has been preferred to the commonly used double-exponential function

since it exhibits, as opposed to the double-exponential function, a time-derivative equal to zero at t=0, consistent with measured return-stroke current wave shapes. Additionally, it allows for the adjustment of the current amplitude, the maximum current derivative and the charge transferred nearly independently by varying I0, τ1 and τ2 respectively.

In what follows we shall describe only two return stroke current models, in particular we shall focus on the TL (Transmission line) model [Uman and Mc Lain, 1969] and MTLE (Modified Transmission Line Exponential decay) model.

The Transmission Line (TL) model. In the TL model, it is assumed that the current wave

at the ground travels undistorted and unattenuated up the lightning channel at a constant speed v. Mathematically:

−=

vztitzi ',0),'( z'≤v t

i z t( ' , ) = 0 z'>v t

(2.3)

where ! v is the lightning return stroke wave-front velocity; ! z is the vertical space variable. The transfer of charge takes place only from the bottom of the leader channel to the top;

thus no net charge is removed from the channel, this being an unrealistic situation given the present knowledge of lightning physics [Uman, 1987].

The Modified Transmission Line Exponential decay (MTLE) model. In the MTLE model

[Nucci et al., 1988] the lightning current intensity is supposed to decrease exponentially while propagating up the channel as expressed by:

Page 17: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 2. – Evaluation of lightning-induced voltages on transmission lines pag.

10

λ''),'(

z

evztitzi

−= z'≤v t

0),'( =tzi z'>v t

(2.4)

where ! v is the return-stroke velocity; ! λ is the decay constant which allows the current to reduce its amplitude with height.

This attenuation is not to be considered as due to losses in the channel or to take into

account the already mentioned decay with height of the initial peak luminosity, but has been proposed by Nucci et al. [1988] to take into account the effect of the charges stored in the corona sheath of the leader and subsequently discharged during the return stroke phase. Its value has been determined to be about 2 km by Nucci and Rachidi [1989], by means of tests with experimental results published by Lin et al. [1979,1980].

The MTLE model represents a modification of the TL model which allows net charge to be removed from the leader channel via the divergence of the return stroke current with height, and thus results in a better agreement with experimental results.

Channel-base current measurements have been performed by means of instrumented

towers in some countries9, and statistical elaboration of lightning current data have been presented [e.g. Berger et al. 1975; Anderson and Eriksson, 1980]. Without loosing generality only lightning with lower negative charge to ground will be considered, here since it is generally accepted that, at least in temperate climate, positive flashes occur less frequently and have a lower peak current-derivative.

In Fig. 2.2, typical channel-base current wave shapes for negative first (Fig. 2.2a) and subsequent (Fig. 2.2b) return strokes, as reported by Berger et al. [1975], are shown. The statistics of lightning current parameters which are most significant for the evaluation of induced overvoltages (peak value and front steepness) are shown in Tab. 2.2,2.3 and in Fig. 2.310.

9 e.g. Switzerland [Berger, 1972; Berger et al., 1975; Montandon and Beyeler, 1994], Italy [Garbagnati

and Lo Piparo, 1970,1973,1982; Garbagnati et al. 1980], Russia [Gorin and Shkilev, 1984], South Africa [Eriksson, 1974,1978; Geldenhuys et al., 1988], Germany [Beierl, 1991,1992] and Canada [Chang et al. 1992; Janischewskyj et al. 1992,1993,1994; Bermudez et al. 2001].

10 It is worth observing that since channel-base current is generally measured at the top of the instrumented tower, the statistical distributions of current parameters are presumably affected by current reflections at both bottom and top of the tower [Montandon and Beyeler, 1994; Beierl, 1992; Janischewskyj et al., 1992, Bermudez et al. 2001]. In principle, these reflections might alter both the front steepness and the peak value of the current depending on several factors, e.g. tower height, current wave shape and value of the reflection coefficients. To elaborate meaningful statistics on lightning current parameters, one should ‘decontaminate’

Page 18: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 2. – Evaluation of lightning-induced voltages on transmission lines pag.

11

Fig. 2.2. – Typical channel-base current wave shapes: a) for first negative return strokes, b) for subsequent

negative return strokes. Adapted from Berger et al. [1975].

95% 50% 5% Stroke First Subs First Subs First Subs

Ipeak [kA] 14 4.6 30 12 80 30 Time to crest

[µs] 1.8 0.2 5.5 1.1 18 4.5

( )maxdt

di[kA/ms] 5.5 12 12 40 32 120

Tab. 2.2. – Statistics of peak amplitude, time to crest and maximum front steepness for first ad subsequent

negative return strokes. Adapted from Berger et al. [1975].

the measured currents from the mentioned ‘tower-effects’ [Guerrieri et al. 1994]. The problem of ‘decontaminating’ the lightning current is, however, beyond the scope of this thesis. In what follows we shall assume that the current distributions found in the literature [Berger et al., 1975; Anderson and Eriksson, 1980] are relevant to current measured at ‘ground level’ disregarding the presence of the elevated strike object which would require an appropriate reprocessing of the statistical data [Sabot, 1995].

Page 19: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 2. – Evaluation of lightning-induced voltages on transmission lines pag.

12

1000.00 10000.00 100000.00 1000000.00IP in A

0.010.010.050.10

0.501.

002.005.00

10.00

20.0030.0040.0050.0060.0070.0080.00

90.0095.0098.0099.0099.50

99.9099.95

99.99Pr

obab

il ity

Current amplitude [A]1000.00 10000.00 100000.00 1000000.00

IP in A

0.010.010.050.10

0.501.

002.005.00

10.00

20.0030.0040.0050.0060.0070.0080.00

90.0095.0098.0099.0099.50

99.9099.95

99.99Pr

obab

il ity

1000.00 10000.00 100000.00 1000000.00IP in A

0.010.010.050.10

0.501.

1000.00 10000.00 100000.00 1000000.00IP in A

0.010.010.050.10

0.501.

002.005.00

10.00

20.0030.0040.0050.0060.0070.0080.00

90.0095.0098.0099.0099.50

99.9099.95

99.99Pr

obab

il ity

002.005.00

10.00

20.0030.0040.0050.0060.0070.0080.00

90.0095.0098.0099.0099.50

99.9099.95

99.99Pr

obab

il ity

Current amplitude [A]

1.00E-7 1.00E-6 1.00E-5 1.00E-4Tempo alla cresta tf in s

0.010.01

0.050.10

0.501.002.00

5.0010.00

20.0030.0040.0050.0060.0070.0080.00

90.0095.00

98.0099.0099.50

99.9099.95

99.99

Pro

babi

litPr

obab

il ity

Time to crest [s]1.00E-7 1.00E-6 1.00E-5 1.00E-4

Tempo alla cresta tf in s

0.010.01

0.050.10

0.501.002.00

5.0010.00

20.0030.0040.0050.0060.0070.0080.00

90.0095.00

98.0099.0099.50

99.9099.95

99.99

Pro

babi

litPr

obab

il ity

1.00E-7 1.00E-6 1.00E-5 1.00E-4Tempo alla cresta tf in s

0.010.01

0.050.10

0.501.002.00

5.0010.00

20.0030.0040.0050.0060.0070.0080.00

90.0095.00

98.0099.0099.50

99.9099.95

99.99

Pro

babi

litPr

obab

il ity

Time to crest [s] Fig. 2.3. – Current amplitude and rise time statistical distributions. Adapted from Anderson and Eriksson

[1980].

95% 50% 5% Stroke First Subs First Subs First Subs

Ipeak [kA] 14.1 5.2 31.1 12.3 68.5 29.2 Time to crest

[µs] 1.8 0.1 4.5 0.6 11.3 2.8

( )maxdt

di[kA/ms] 9.1 9.9 24.3 39.9 65.0 161.5

Tab. 2.3. – Statistics of peak amplitude, time to crest and maximum front steepness for first ad subsequent

negative return strokes. Adapted from Anderson and Eriksson [1980]

2.2. – Lightning electromagnetic field appraisal Expressions of the electromagnetic field radiated by a vertical dipole of length dz' at a

height z' along the lightning channel, assumed as an antenna over a perfectly conducting plane, have been derived by Master and Uman [1983] by solving Maxwell's equations in terms of retarded scalar and vector potentials:

[

]

d dE r z tdz r z z

Ri z R c

r z zcR

i z t R c

r z zc R

i z t R ct

ro

t

( , , , )( )

( , / )

( )( , / )

( ) ( , / )

φπε

τ τ

∂∂

=′ − ′

′ − +

+− ′

′ − +

+− ′ ′ −

∫43

3

50

4

2 3

(2.5)

Page 20: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 2. – Evaluation of lightning-induced voltages on transmission lines pag.

13

[

]t

cRtziRc

r

cRtzicR

rzz

cRziR

rzzzdtzrEt

oz

∂∂

ττπε

φ

)/,(

)/,()(2

d)/,()(24

),,,(d

32

2

4

220

5

22

−′−

+−′−′−+

+−′−′−′= ∫

(2.6)

[

]t

cRtzicR

r

cRtziRrzdtzrB o

r

∂∂

πµφ

)/,(

)/,(4

),,,(d

2

3

−′

−′′=

(2.7)

where ! i(z', t) is the current along the channel obtained from one of the return-stroke current

models summarized above; ! c is the speed of light; ! R is the distance of the electric dipole from the observation point; ! r is the projection of R in the plane xy (see Fig. 2.1);

and the geometrical factors are as given in Fig. 2.1. By integrating along the channel expressions (2.5)-(2.7), where the current distribution as

a function of height and time is given by the return-stroke models discussed in previous paragraph, one obtains the electromagnetic exciting field.

For distances not exceeding a few kilometers, the perfect ground conductivity assumption is a reasonable approximation for the vertical component of the electric field and for the horizontal component of the magnetic field as shown by several authors [Djébari et al., 1981; Zeddam and Degauque, 1990; Rubinstein, 1996]. In fact, the contributions of the source dipole and of its image to these field components add constructively and, consequently, small variations in the image field due to the finite ground conductivity will have little effect on the total field.

On the other hand, the horizontal component of the electric field, is appreciably affected by a finite ground conductivity. Indeed, for such a field component, the effects of the two contributions subtract, and small changes in the image field may lead to appreciable changes in the total horizontal field. Although the intensity of the horizontal field component is generally much smaller than that of the vertical one, within the context of certain coupling models it plays an important role in the coupling mechanism [Master and Uman, 1984; Cooray and De la Rosa, 1986; Rubinstein et al., 1989; Diendorfer, 1990; Nucci et al. 1993; Ishi et al., 1994] and, hence, an accurate calculation method has to be chosen for it. Methods

Page 21: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 2. – Evaluation of lightning-induced voltages on transmission lines pag.

14

for the calculation of the horizontal field using the exact Sommerfeld integrals are inefficient from the point of view of computer-time. Simplified expressions exist. One of the approach which appears now most promising is that proposed independently by Cooray and Rubinstein [Rubinstein 1991,1996; Cooray 1992,1994] and discussed by Wait [1997].

The Cooray-Rubinstein expression is given by

δσωωω φ

gprpr

jjzrHjzrEjzrE )1(),0,(),,(),,( +⋅=−= (2.8)

where

! p is the subscript that indicates the fields calculated assuming a perfect ground; ! εrg is the relative ground permittivity; ! σg is the ground conductivity. ! ),,( ωjzrE rp and ),0,( ωφ jrH p are the Fourier-transforms of the horizontal

component of the electric field at height z, and of the azimuthal component of the magnetic field at ground level respectively, both calculated assuming a perfect conducting ground;

! δ is the skin depth factor, ( ggσωµ/2 );

! µg is the ground permittivity. This approach has been shown to produce satisfactory approximation of the horizontal

electric field for some significant cases: in particular, it reproduces the positive, bipolar and negative polarities of the field at close (one hundred meters), intermediate (some kilometers), and far (tens of kilometers) distances respectively, and at all these ranges it predicts results close to those predicted by more accurate expressions [Cooray, 1994; Rubinstein, 1996; Rachidi et al., 1996]. Motivated by the discussion by Wait [1997], Cooray [1998b] has proposed a modified, improved expression of (2.8).

2.3. – Transmission line coupling models To solve the coupling problem, i.e. the determination of voltages and currents induced by

an external field on a conducting system, use could be made of the antenna theory, the general and rigorous approach based on Maxwell's equations [Tesche, 1992]. However, due to the length of distribution lines, the use of such theory for the calculation of lightning-induced overvoltages implies long computing times. In our case, the use of the simplest approach namely the quasi-static approximation [Johnk, 1975], according to which propagation is neglected and coupling between incident fields and the line conductors can be described by means of lumped elements (e.g. an inductance, or a capacitance), is not

Page 22: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 2. – Evaluation of lightning-induced voltages on transmission lines pag.

15

appropriate. In fact, such an approach requires that the dimensions of the line conductors be smaller than about one tenth of the minimum wavelength of the electromagnetic field, an unacceptable assumption for the case of power lines illuminated by LEMP fields (above 1 MHz frequency, that is below 300 m wave length). Another possible approach is the transmission line theory [Taylor et al., 1965]. The basic assumptions of this approximation are that the response of the line is quasi-transverse electromagnetic (quasi-TEM) and that the transverse dimension of the line is smaller than the minimum significant wavelength. The line is represented by a series of elementary sections to which, by virtue of the above assumptions, the quasi-static approximation applies. Each section is illuminated progressively by the incident electromagnetic field so that longitudinal propagation effects are taken into account. The transmission line approximation appears to be the most promising approach for the problem of interest: indeed, in the power literature the most used coupling models are based on it, and in this thesis use will be made of it.

We shall now briefly resume the most popular coupling models based on the transmission line approximation. To do that, let us start considering a single-conductor overhead line parallel to the x-axis and contained in the xz-plane terminated on two resistances R0 and RL (Fig. 2.5). It is important to observe that the incident external electromagnetic field Ee, Be shown in Fig. 2.5 is the sum of the field radiated by the lightning stroke and of the ground-reflected field, both considered in absence of the wire. The total field E, B is given by the sum of the incident field Ee, Be and the scattered field Es, Bs, which represents the reaction of the wire to the incident field. The incident electromagnetic field is related to the incident scalar potential φi and to the incident vector potential Ae by the following expressions:

+∇−=

t

eee

∂∂φ AE (2.9)

ee AB ×∇= (2.10)

L x

y

z

R0 RL

0 x x+dx

h

Ez e

E x e

Bye

Fig. 2.5. – Geometry used for the calculation of overvoltages induced on an overhead power line by an indirect lightning return-stroke

Page 23: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 2. – Evaluation of lightning-induced voltages on transmission lines pag.

16

The Agrawal, Price and Gurbaxani model for a single-conductor line. The most adequate coupling model to describe the coupling between lightning return-stroke fields and overhead lines is nowadays considered the model by Agrawal et al. [1980], which is based on the transmission line approximation [Tesche et al., 1997]. It is indeed the model that allows in a straightforward way to take into account the ground resistivity in the coupling mechanism, and it is the only one that has been thoroughly tested and validated using experimental results, as will be discussed next.

The two transmission line coupling equations of the Agrawal model, expressed in the time domain, are [Agrawal et al., 1980; Tesche et al., 1997; Rachidi et al., 1999]:

),,(),( ),('

),( thxEt

txiLt

txix

txv ex

ig

s

=′+∂

∂⊗+∂

∂ξ∂

∂ (2.11)

0

),( ),('+

),( =′+t

txvCtxvGx

txi ss

∂∂

∂∂ (2.12)

where

! ),,( thxE ex is the horizontal component of the incident electric field along the x axis at

the conductor's height; ! ),( txi is the current induced along the line;

! g'ξ is the inverse Fourier transform of the ground impedance;

! ⊗ denotes the convolution product; ! L', C', G' are the line inductance (external), capacitance and conductance per-unit-

length respectively. In equation (2.11) L’ is the external per-unit-length inductance calculated for a loss less

wire above a perfectly conducting ground, g'ξ is the inverse Fourier transform of the

ground impedance. In particular g'ξ is the inverse Fourier-transform of ωω j

Zj

ZZ gwg '''≅

+

where 'wZ and Z g

' are the wire and the ground impedances respectively. Note, further, that

within the frequency range of interest, the wire impedance can be neglected compared with the ground impedance [Ramo et al., 1984; Rachidi et al., 1996].

The ground impedance can be viewed as a correction factor to the line longitudinal impedance when the ground is not a perfect conductor and can be defined as Rachidi etl al. [1996], Guerrieri [1997], Tesche et al. [1997], Cooray and Schuka [1998]:

Page 24: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 2. – Evaluation of lightning-induced voltages on transmission lines pag.

17

'),(

' LjI

dxzxBjZ

hsy

g ωω

−=∫∞−

(2.13)

In this thesis we shall make reference to the expression derived by Carson [1926], valid

for the so-called ‘low frequency approximation’ ( rgg εωεσ o>> ), and for ground

conductivities not lower than about 0.001 S/m [Rachidi et al. 1999] recently improved in [Rachidi et al., 2000]:

+

=41

41

21

21

terfce

t ,

hmin)t(' gtg

g

o

rgo

og

g ττππτ

µεε

µπ

ξτ

(2.14)

in which ε0 and εrg are the air and ground permittivity respectively, µ0 is the air permeability, τg=h2µ0σg (where σg is the ground conductivity) and erfc is the complementary error function.

In (2.11) and (2.12) the wire impedance, the ground admittance and the line conductance have been assumed negligible (an approximation valid for typical overhead lines a few meters above ground, σg=10-3-10-2S/m, εr=1-10, Rachidi et al. [1996]).

Equations (2.11) and (2.12) are written in terms of scattered voltage ),( txv s 11. The total

voltage ),( txv is given by the sum of the scattered voltage ),( txv s and the so-called

incident voltage

htxEdztzxEv ez

hez

i ⋅−≈−= ∫ ),0,(),,(0

(2.15)

namely,

),(),(),( txvtxvtxv is += (2.16)

The boundary conditions, written for the case of resistive terminations, are

11 The total field is the sum of the incident (or exciting) field and of the scattered field. The first is given by

the field radiated by the lightning channel and by the ground-reflected field in absence of the line conductors; the second is given by the reaction of the overhead conductors to the incident field. To each of these fields one can associate a voltage, namely the incident voltage and the scattered one.

Page 25: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 2. – Evaluation of lightning-induced voltages on transmission lines pag.

18

),0(),0(),0( tvtiRtv io

s −⋅−= (2.17)

),(),(),( tLvtLiRtLv iL

s −⋅= (2.18)

Eqs. (2.11)-(2.16) have the circuit representation of Fig. 2.6.

0

v(x,t)

i(x,t) L'dx

C'dx

x x+dx

+ - i(x+dx,t) +

-

+

-

L

vs(x+dx,t) -vi(0,t)

R0 RL

Exe(x,h,t)dx

ve(x,t)

-vi(L,t) t

(x,t)iξ' ig ∂

∂⊗

Fig. 2.6. – Differential equivalent coupling circuit according to the Agrawal et al. formulation for a lossless single-wire overhead line.

According to the Agrawal model, the forcing functions explicitly appearing in equations

which produce the scattered voltage are: the horizontal component of the incident electric field along the line and the incident vertical electric field at the vertical line terminations. These forcing functions are represented by the voltage sources in Fig. 2.6.

An adequate coupling model for lightning-induced overvoltage calculations is a model that, given as inputs the lightning electromagnetic fields which illuminate a transmission line, predicts satisfactorily the line overvoltages induced by that field. Thus, to adequately test a coupling model, data sets of simultaneously measured fields and voltages are needed.

The Agrawal model has been first applied for the calculation of lightning induced overvoltages by Master and Uman [1984] and then employed by several other authors12. The Agrawal model is the only one that has been thoroughly tested versus experimental results in the sense above specified. Although some of the first tests did not provide satisfactory agreement between theory and measurements [Master and Uman, 1984; Master et al., 1984], in subsequent experiments the agreement was largely improved [Cooray and de la Rosa, 1986; Rubinstein et al. 1989]. Some tests of the Agrawal model have been performed making use of Nuclear Electromagnetic Pulse (NEMP) simulators [Master et al., 1984; Rubinstein et al. 1989] and results have shown a reasonably good agreement between measurements and theory. It is worth mentioning that one of the aim of this thesis is the extension of the Agrawal coupling model to the case of a line with transverse discontinuities

12 [Cooray and De la Rosa, 1986; Rubinstein et al., 1989; Diendorfer, 1990; Iorio et al., 1993; Nucci et al.,

1993,2000; Ishii et al., 1994].

Page 26: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 2. – Evaluation of lightning-induced voltages on transmission lines pag.

19

(see paragraphs 2.4. and 3.1.2.), and that the experimental validation of such a model extension was also successfully accomplished by means of a NEMP simulator.

The Agrawal model has been shown to be completely equivalent to two other models in which the forcing functions are in terms of different components of the electromagnetic field, namely the model by Taylor et al. [1965], and the model by Rachidi [1993]. Indeed, these last three models (Agrawal et al., Taylor et al., and Rachidi) are different though equivalent formulations of the same coupling equations set in terms of different combinations of the various components of the electromagnetic field. This means that it is misleading to speak of the contribution of a given component of the electromagnetic field to the induced overvoltage without specifying the formulation of the coupling model one is using [Nucci and Rachidi, 1995]. Additionally, it has been shown that for the case of a lightning channel perpendicular to a perfectly conductive ground plane the model proposed by Rusck [1958] provides the same results as the Agrawal one. Although for different channel geometry the Rusck model is expected to predict results that might be affected by some inaccuracy, it is still very popular among power engineers, and for this reason we briefly summarize it below.

The Rusck model. To derive the transmission-line coupling equations of this model,

Rusck [1958] started from the expression relating the total electric field on the conductor surface to the scalar and vector potentials. The coupling equations obtained by using the above procedure for a single-conductor line above perfect conducting ground are:

0),(),( =′+t

txiLx

tx∂

∂∂

∂φ (2.19)

[ ] 0),(),(),( =−′+ txtxt

Cx

txi iφφ∂∂

∂∂

(2.20)

where ! L’ and C’ are the line inductance and the line capacitance per unit length

respectively; ! i(x,t) is the total line current; ! φ is the total induced scalar potential. The total induced voltage v(x,t) is given by the following expression

dzt

tzxAtxtxvh e

z∫+=0

),,(),(),(∂

∂φ (2.21)

Page 27: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 2. – Evaluation of lightning-induced voltages on transmission lines pag.

20

where h is the conductor’s height and ezA is the vertical component of the incident vector

potential. The boundary conditions for (2.19) and (2.20) are [Cooray, 1994]:

dzt

tzAtiRth e

z∫−−=0

0),,0(),0(),0(

∂∂φ (2.22)

dzt

tzLAtLiRtLh e

zL ∫−=

0

),,(),(),(∂

∂φ (2.23)

In the Rusck model the forcing functions that explicitly appear in the coupling equations

are the incident scalar potential along the line and the vertical component of the incident vector potential at the line terminations.

Yokoyama et al. [1984,1989] used the Rusck model to compute induced voltages starting from a measured lightning current. The field was calculated from the measured current assuming a simple return-stroke current model and a satisfactory agreement was found between measurements and calculations. Also Eriksson et al. [1982] obtained a satisfactory agreement between theory and calculations. The field they input to the Rusck model was not the one that produced the measured induced voltage but was calculated using a simple return-stroke current model starting from a typical lightning channel-base current: thus their comparison has more a qualitative than a quantitative nature.

It is worth mentioning that Rusck proposed a simplified formula that provides a first estimation of the peak value Vmax of the overvoltages induced on a infinite long line starting from the peak value Ip of the lightning current, the velocity of the return-stroke wavefront and the height of the line:

( )( )

⋅−+

⋅=

20max501

1211

v/c.cv

dhI

ZV p (2.24)

where ! Ip is the lightning peak current; ! d is the distance of the stroke location from the line (in m);

!

0

00 4

1εµ

π=Z = 30 Ω;

! h is the line height (in m); ! v is the return stroke wave front velocity; ! c is the speed of the light.

Page 28: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 2. – Evaluation of lightning-induced voltages on transmission lines pag.

21

Discussion of the simplified Rusck formula. As mentioned earlier, the Rusck simplified analytical formula (2.24) gives the maximum value Vmax of the induced overvoltages on an infinitely long line at the nearest point to the stroke location. Figures 2.7a, b and c show the variation of the maximum amplitude of the voltage induced at the point closest to the stroke location for three different lightning current wave shapes (see Tab. 2.4) and for the different values of ground conductivity, namely infinite, 0.01 and 0.001 S/m calculated adopting the MTLE return stroke model and the Agrawal coupling model. Each case is compared with the prediction of the Rusck formula.

Current types A1 A2 A3

Ip [kA] 12 12 12

(di/dt)max [kA/µs] 12 40 120

Tab. 2.4a. – Subsequent return-stroke current peak values and maximum time derivatives of the adopted currents.

A1 A2 A3 I01 [kA] 10,7 10,7 7,4

τ11 [µs] 0,95 0,25 0,063

τ12 [µs] 4,7 2,5 0,5

I02 [kA] 6,5 6,5 9

τ21 [µs] 4,6 2,1 0,27

τ22 [µs] 900 230 66

n 2 2 2

Tab. 2.4b. – Parameters of the Heidler functions reproducing the adopted currents. The channel base current is approximated by the sum of two Heidler functions.

By observing Fig. 2.7 we can conclude that, in general, when the channel base current

exhibits a steep front (current A3) and when the ground is approximated as a perfectly conducting plane, the Rusck simplified analytical expression provides an estimation for the induced voltages close to the one predicted by the more general Agrawal model in which the forcing functions are calculated by means of the MTLE model. The disagreement between the voltage predicted by the two approaches (Rusck formula and Agrawal-MTLE models) increases with the return-stroke velocity, with the ground resistivity, and with the front duration of the lightning current. As a conclusion, in general, the Rusck simplified formula should not be applied to the case of overhead lines above a lossy ground.

Page 29: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 2. – Evaluation of lightning-induced voltages on transmission lines pag.

22

0

20

40

60

80

100

120

140

160

0 20 40 60 80 100 120 140 160Distance (m)

Indu

ced

Volta

ge U

1 (k

V) infinite0.01 S/m0.001 S/mRusck formula

a)

0

50

100

150

200

0 20 40 60 80 100 120 140 160

Distance (m)

Indu

ced

Volta

ge U

1 (k

V) infinite0.01 S/m0.001 S/mRusck formula

a)

0

50

100

150

200

0 20 40 60 80 100 120 140 160

Distance (m)

Indu

ced

Volta

ge U

1 (k

V) infinite0.01 S/m0.001 S/mRusck formula

b)

0

50

100

150

200

0 20 40 60 80 100 120 140 160Distance (m)

Indu

ced

Volta

ge U

1 (k

V) infinite0.01 S/m0.001 S/mRusck formula

b)

0

50

100

150

200

0 20 40 60 80 100 120 140 160Distance (m)

Indu

ced

Volta

ge U

1 (k

V) infinite0.01 S/m0.001 S/mRusck formula

c)

0

50

100

150

200

0 20 40 60 80 100 120 140 160Distance (m)

Indu

ced

Volta

ge U

1 (k

V) infinite0.01 S/m0.001 S/mRusck formula

c)

Fig. 2.7. – Variation of the induced voltage magnitude at the line center as a function of distance to the stroke location. Left column: return-stroke velocity equal 1.3⋅108 m/s; right column: return-stroke velocity equal 1.9⋅108 m/s. a) lightning current A1, b) lightning current A2, c) lightning current A3. In solid line we have

reported the results obtained from the Rusck simplified analytical expression. Adapted from Borghetti et al. [2000a].

Page 30: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 2. – Evaluation of lightning-induced voltages on transmission lines pag.

23

The Agrawal, Price and Gurbaxani model for a multi-conductor line. The Agrawal model for the case of a multi-conductor line above a lossy ground reads [Tesche et al., 1997, Rachidi et al., 1997]:

[ ] [ ] [ ] [ ] [ ] [ ]),,(),('),('),( thxEtxit

txit

Ltxvx i

exigijiij

si =

∂∂⊗+

∂∂+

∂∂ ξ (2.25)

[ ] [ ] [ ] 0),('),( =∂∂+

∂∂ txv

tCtxi

xsiiji (2.26)

where

! [ ]),,( thxE iex is the horizontal component of the incident electric field along the x axis

at the conductor's height; ! [ ]gij'ξ is the matrix of transient ground resistance;

! [ ]ijL' and [ ]ijC ' are respectively the external inductance and the capacitance matrices

per unit length of the line; ! [ ]),( txii is the current vector;

! ⊗ denotes the convolution product;

! [ ]),( txv si is the scattered voltage vector, related to the [ ]),( txvi , the total voltage

vector, by the following expression:

[ ] [ ] [ ] [ ]

−=+= ∫

ihez

si

ei

sii dztzxEtxvtxvtxvtxv

0

),,(),(),(),(),( (2.27)

The boundary conditions for the scattered voltage at both line ends are:

[ ] [ ][ ] [ ]),0(),0(),0( 0 tvtiRtv eii

si −−= (2.28)

[ ] [ ][ ] [ ]),(),(),( tLvtLiRtLv eiiL

si −= (2.29)

Page 31: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

24

Chapter 3. – LEMP-to transmission-line coupling models for distribution systems and their implementation in a

transient program The evaluation of the LEMP response of distribution networks is crucial for the

assessment of outages on customers and distribution utilities caused by lightning. For this purpose the availability of a model of a LEMP illuminated line having realistic geometrical configuration is of particular interest. This chapter presents the developed complex overhead line model illuminated by a LEMP, its implementation, and the relevant distribution system model developed.

The models here proposed are included in the LIOV (lightning induced overvoltage) code. The LIOV code has been developed in the framework of an international collaboration involving the University of Bologna (Department of Electrical Engineering), the Swiss Federal Institute of Technology (Power Systems Laboratory), and the University of Rome La Sapienza (Department of Electrical Engineering). The LIOV code is based on the field-to-transmission line coupling formulation of Agrawal et al. [1980], suitably adapted for the case of an overhead line illuminated by an indirect lightning electromagnetic field; the return stroke electromagnetic field is calculated by assuming the MTLE engineering model and using the Cooray-Rubinstein formula for the case of lossy grounds [Nucci et al., 1993; Rachidi et al., 1995]. It allows for the calculation of lightning-induced voltages along an overhead line as a function of current wave shape (amplitude, front steepness, duration), return stroke velocity, line geometry (height, length, number and position of conductors), stroke location with respect to the line, ground resistivity and relative permittivity, and value of termination impedances.

The models here proposed are aimed at improving the LIOV code in order to permit for the treatment of more realistic overhead line and distribution systems.

3.1. – Lines with transverse discontinuities Concerning medium voltage overhead lines the main protective measures against

lightning induced overvoltages can be identified as follow: I) use of shielding wires and II) use of surge arresters.

Regarding the first protective measure, several authors have addressed theoretically the issue by assuming the shielding wire at zero potential at any point of it and at any time [Rusck, 1958; Chowdhuri, 1969,1990; Yokoyama et al., 1983,1986], an assumption that appears reasonable only when shielding wire is grounded at short intervals along the line. Further, such an approach does not allow to find the optimal distance between two

Page 32: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

25

consecutives groundings needed to accomplish the required shielding effect. In Yokoyama [1984] an improved approach was used in which the shielding wire was considered as one of the conductors of the multi-conductor line. The coupling model adopted is the same proposed by Rusck [1958] which has been shown to apply for the case of a lightning channel perpendicular to the ground plane.

3.1.1. – Proposed model Line transverse discontinuities are represented by the connections between the line

conductors and the ground. These connections are constituted by the groundings of the shielding wire and by surge arresters connected to the phase conductors. Then the elements that represent these discontinuities could be a simple linear resistance or a non-linear component.

In this thesis, we extend the model already presented in Rachidi et al. [1997,1999] in which the coupling between the LEMP and the multi-conductor transmission line is described by the more general coupling model by Agrawal et al. and in which the shielding wire was treated, similarly to [Yokoyama, 1984], as one of the conductors of the multi-conductor line. In particular, while in [Rachidi et al., 1997,1999] the shielding wire was grounded only at the line terminations, we here propose a model modification with allows for the treatment of multiple groundings along the line. The grounding resistance is also included in our extended model. Comparisons with experimental data obtained by using a reduced scale line model illuminated by an EMP simulator and, also, with those obtained by other authors [Yokoyama, 1984], are presented.

The above-mentioned model has also be extended in order to deal with the presence of surge arresters along the line. We shall essentially assess the effect of both shielding wires and surge arresters on voltages induced by a nearby cloud-to-ground lightning.

According to the Agrawal transmission line coupling equations (2.25) and (2.26) the scattered voltage, at node g of the conductor i at which a given impedance is connected to ground, can be expressed as follows (see Fig. 3.1):

( )( ) ∫+=ih

ez

ig

si (x,z,t)dzEtiΓ txv

0

),( (3.1)

where Γ is an integro-differential operator which describes the voltage drop across the impedance as function of current ig (Γ=Rg⋅ig for the simple case of a resistance). Since the Agrawal model is expressed in terms of the scattered voltage, it is necessary to include a voltage source in series with the impedance, the so-called incident voltage, which is given

Page 33: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

26

by the integral from the ground level to the line conductor of the incident vertical electric field (see Fig. 3.1).

∫ih

ez (x,z,t)dzE

0

Γ igi(t)

),( txv isconductor i

g

Fig. 3.1. Insertion of discontinuity point in a generic point along a multi-conductor line.

The developed extended model was tested versus experimental data obtained by means

of a reduced line model illuminated by an EMP simulator. Besides, additional validation was performed by testing it with the theoretical results published by Yokoyama [1984]. The entire experimental validation results are presented in the paragraph 3.1.3.

3.1.2. – Numerical implementation Most studies on lightning-induced voltages on overhead power lines use a direct time

domain analysis because of its straightforwardness in dealing with insulation coordination problems, and its ability to handle non-linearities, which arise in presence of protective devices such as surge arresters or corona phenomenon.

One of the most popular approaches to solve the transmission line coupling equations in time domain is the finite difference time domain (FDTD) technique (e.g. [Tafflove, 1995]). Such technique was used indeed by Agrawal et al. in [1980] when presenting their field-to-transmission line coupling equations. In the above publications, partial time and space derivatives were approximated using the 1st order FDTD scheme.

We have proposed, instead, the use of a second order finite difference scheme, it is based on the Lax-Wendroff algorithm [Lax and Wendroff, 1960]. In [Omick Castillo, 1993] this algorithm is applied to the classical transmission line equations excited by lumped excitation sources. We here propose an extension of such an integration scheme to take into account distributed sources due to the action of an external electromagnetic field, according to the Agrawal et al. coupling model.

We shall first deal with the case of a single conductor line above an ideal ground with no discontinuities. Then we shall propose an extension of the Agrawal model to deal with the

Page 34: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

27

case of a lossy ground, and eventually we shall present the algorithm relevant to a line with transverse periodical discontinuities. In Appendix A.1 we report also the treatment of line transverse discontinuities concerning the FDTD 1st order scheme.

Case of a single-conductor line above an ideal ground. For convenience we write below

the Agrawal coupling equations (2.11) and (2.12) which, for the case of interest, assume the following form:

),,(),('),( thxEt

txiLx

txv ex

s

=∂

∂+∂

∂ (3.2)

0),('),( =∂

∂+∂

∂t

txvCx

txi s

(3.3)

The meaning of the symbols that appear in (3.2) and (3.3) is the same than in equations

(2.11) and (2.12). If we differentiate with respect to the x and t variables, the system of equations (3.2) and

(3.3) can be rewritten as

tthxEC

ttxiCL

xtxi e

x

∂∂

−=∂

∂−∂

∂ ),,('),(''),(2

2

2

2

(3.4)

xthxE

ttxvCL

xtxv e

xss

∂∂

=∂

∂−∂

∂ ),,(),(''),(2

2

2

2

(3.5)

Expanding the line current and the scattered voltage using Taylors series applied to the

time variable, and truncating after the second order term yields

)O(2

),(),(),(),( 32

2

2

0 ttt

txvtt

txvtxvtxvss

ss ∆+∆∂

∂+∆∂

∂+= (3.6)

)O(2

),(),(),(),( 32

2

2

0 ttt

txitt

txitxitxi ∆+∆∂

∂+∆∂

∂+= (3.7)

where )O( 3t∆ is the remainder term, which approaches zero as the third power of the

temporal increment. If we substitute the time derivatives in (3.6) and (3.7) with the corresponding expressions

using equations (3.2), (3.3), (3.4), and (3.5), we obtain the following second order differential equation

Page 35: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

28

)O(),(),,(''2

),('

),(),( 32

22

0 tx

txvx

thxECL

tx

txiC

ttxvtxvse

xss ∆+

∂−∂

∂∆−∂

∂∆−= (3.8)

)O(

),,('),(''2

),,(),('

),(),(

3

2

22

0

t

tthxEC

xtxi

CLtthxE

xtxv

Lttxitxi

exe

x

s

∆+

+

∂+∂

∂∆+

−∂

∂∆−= (3.9)

In order to represent equations (3.8) and (3.9) using an FDTD technique, we will proceed

with the discretization of time and space as follows

nk

ss vtnxkvtxv =∆∆= ),(),( (3.10)

nkitnxkitxi =∆∆= ),(),( (3.11)

nk

ex

ex EhtnhxkEthxE =∆∆= ),,(),,( (3.12)

where: ! ∆x: spatial integration step; ! ∆t: time integration step; ! k= 1,2,, kmax; ! n= 1,2, , nmax. In the integration scheme, the scattered voltage and current at time step n are known for

all spatial nodes. Therefore equations (3.8) and (3.9) allow us to compute the scattered voltage and current at the time step n+1.

The spatial derivatives of the scattered voltage, line current, and horizontal electric field can be written respectively as

)O(2

),( 11 xxvv

xtxv n

knk

tnt

s

∆+∆−=

∂∂ −+

∆=

(3.13)

)O(2

),( 11 xxii

xtxi n

knk

tnt

∆+∆−

=∂

∂ −+

∆=

(3.14)

)O(2

),,( 11 xxEhEh

xthxE n

knk

tnt

ex ∆+

∆−=

∂∂ −+

∆=

(3.15)

On the other hand, the time derivative of the horizontal electric field reads

Page 36: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

29

)O(2

),,( 11

ttEhEh

tthxE n

knk

tnt

ex ∆+

∆−

=∂

∂ −+

∆=

(3.16)

The second order spatial derivatives can be written as

)O(2),(211

2

2

xx

vvvx

txv nk

nk

nk

tnt

s

∆+∆

−+=∂

∂ −+

∆=

(3.17)

)O(2),(211

2

2

xx

iiix

txi nk

nk

nk

tnt

∆+∆

−+=

∂∂ −+

∆=

(3.18)

Inserting equations (3.10)-(3.16) into (3.8) and (3.9), we obtain the 1st order FDTD

scheme. If we insert equations (3.10)-(3.18) into (3.8) and (3.9), we obtain the following 2nd order FDTD scheme:

−+−∆−∆−

∆−∆−= −+−+−++

21111

2111 2

2''22' xvvv

xEhEh

CLt

xii

Ctvv

nk

nk

nk

nk

nk

nk

nkn

knk (3.19)

∆−+

∆−+∆+

∆−∆−=

−+−+−++

tEhEhC

xiii

CLtEh

xvv

Ltii

nk

nk

nk

nk

nkn

k

nk

nkn

knk 2

'2''22'

11

211

2111 (3.20)

It is worth noting that, compared to the 1st order point centered scheme adopted in

[Agrawal et al., 1980; Rachidi et al., 1996], the spatial-temporal grid distribution for current and voltage nodes in the 2nd order scheme is quite different. Fig. 3.2 shows a schematic representation of the spatial-temporal grid for both integration schemes.

Page 37: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

30

n+1

n n- 1

k k+1 k - 1 spatial discretization

time discretization

n n i v 00 n k

nk i vmax max n

kn

k i v

R0

∫ h

ez dz tE

0

),0,0 ( ∫ h

e z dzt L E

0 ) , 0 ,(

R L

) t ,h ,x ( E ex

1st order FDTD point centered

n+1

n n- 1

k k+1 k - 1 spatial discretization

time discretization

n n i v 00 , nk

n k i v maxmax ,

n k

n k iv ,

R0

∫ h

e z dz tE

0

) , 0,0 ( ∫ h

e z dzt LE

0 ) , 0 , (

R L

)t,h , x( E e x

2nd order FDTD

Fig. 3.2. FDTD 1st and 2nd order integration schemes applied to the case of a single-conductor lossless overhead line above a perfectly conducting ground illuminated by an external electromagnetic field. Left

column: time and spatial discretization; right column: schematic representation of the spatial discretization along the line.

The boundary conditions for resistive terminations, can be expressed as follows:

∫+−=h

ez

nn dztEiRv0

000 ),0,0( (3.21)

∫+=h

ez

nkL

nk dztLEiRv

0maxmax ),0,( (3.22)

Case of a single-conductor line above a lossy ground. We now extend the FDTD 2nd

order integration scheme previously presented in order to take into account the presence of an uniform lossy ground, characterized by its conductivity σg and its relative permittivity εrg. In this case, the Agrawal et al. coupling equations become [Rachidi et al., 1996]:

),,(),()('),('),(

0

thxEdxitt

txiLx

txv ex

t

g

s=

∂∂−+

∂∂+

∂∂ ∫ τ

τττξ (3.23)

Page 38: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

31

0),('),( =∂

∂+∂

∂t

txvCx

txi s

(3.24)

in which ξg(t) is the transient ground resistance [Rachidi et al., 1999], which can be evaluated using the analytical expression (2.14) [Rachidi et al, 2000].

In equations (3.23) and (3.24), the contributions from the wire impedance and the ground admittance, which have shown to be negligible for typical power lines [Rachidi et al., 1996], are deliberately disregarded. Following a procedure similar to the case of a lossless line, equations (3.23) and (3.24) become

tthxEC

ttxv

Ct

txiCLx

txi exg

∂∂−=

∂∂

−∂

∂−∂

∂ ),,('),('

'),(''),(2

2

2

2

(3.25)

xthxE

xtxv

ttxvCL

xtxv e

xgss

∂∂=

∂∂

+∂

∂−∂

∂ ),,(),('),(''),(2

2

2

2

(3.26)

in which

∫ ∂∂−=

t

gg dittxv0

)()('),(' ττττξ (3.27)

Expanding the current and the scattered voltage using Taylors series, and replacing the

time derivative of the current and of the scattered voltage in equations (3.25) and (3.26), we obtain the following second order differential equation:

)O(),('),(),,(

''2

),('

),(),(

32

22

0

tx

txvx

txvx

thxECL

tx

txiC

ttxvtxv

gse

x

ss

∆+

∂−

∂∂−

∂∂∆−

+∂

∂∆−= (3.28)

)O(),('

'),,('),(''2

),('),,(),('

),(),(

32

22

0

tt

txvC

tthxEC

xtxi

CLt

txvthxEx

txvL

ttxitxi

gex

gex

s

∆+

∂−

∂∂+

∂∂∆+

+

+−∂

∂∆−= (3.29)

Following a procedure similar as that for the ideal ground case, we obtain the 2nd order

FDTD discretized equations:

Page 39: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

32

∆−∆+

+

−+−∆−∆−

∆−∆−=

−+

−+−+−++

xvv

CLt

xvvv

xEhEh

CLt

xii

Ctvv

nkg

nkg

nk

nk

nk

nk

nk

nk

nkn

knk

2''

''2

22''22'

112

21111

2111

(3.30)

∆−∆−

∆−+

∆−+∆+

+

+−∆−∆−=

−−+−+

−++

tvv

Lt

tEhEhC

xiii

CLt

vEhxvv

Ltii

nkg

nkg

nk

nk

nk

nk

nk

nkg

nk

nk

nkn

knk

1211

211

2

111

'''22

'2''2

'2'

(3.31)

Extension to the case of a multi-conductor line. The Agrawal et al. field-to-transmission

line coupling equations for a multi-conductor line above a lossy ground, reported in paragraph 2.3 (equations (2.25) and (2.26)), can be numerically integrated by means of the same FDTD 2nd order scheme used for the single-conductor case, obtaining the following second-order differential equation:

[ ] [ ] [ ] [ ]

[ ][ ][ ] [ ] [ ]

[ ][ ][ ] [ ]

∂∆+

+

∂−∂

∂∆−

+∂

∂∆−=

xtxv

CLt

xtxv

xthxECLt

xtxiCttxvtxv

giijij

sii

ex

ijij

iij

si

si

),('''

2

),(),,(''2

),('),(),(

12

2

21

2

10

(3.32)

[ ] [ ] [ ] [ ] [ ] [ ]

[ ][ ][ ] [ ] [ ] [ ]

[ ][ ][ ] [ ] [ ]

∂∆−

+

∂+∂

∂∆+

+

+−

∂∂∆−=

ttxv

CLCt

tthxEC

xtxiLCt

txvthxEx

txvLttxitxi

giijijij

iex

iji

ijij

giiex

si

ijii

),(''''

2

),,('),(''2

),('),,(),('),(),(

12

2

21

2

10

(3.33)

in which

[ ] [ ] [ ]),('),(' txit

txv igijgi ∂∂⊗= ξ (3.34)

And finally, the 2nd order FDTD representation of (3.32) and (3.33) reads

Page 40: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

33

[ ] [ ] [ ] [ ] [ ]

[ ][ ][ ] [ ] [ ] [ ] [ ] [ ]

[ ][ ][ ] [ ] [ ]

∆−∆+

+

∆−+

−∆−∆−

+

∆−

∆−=

−+−

−+−+−

−+−+

xvv

CLt

xvvv

xEhEh

CLt

xii

Ctvv

nkgi

nkgi

ijij

nki

nki

nki

nki

nki

ijij

nki

nki

ijnki

nki

2''

''2

22

''2

2'

1112

211111

2

1111

(3.35)

[ ] [ ] [ ] [ ] [ ] [ ] [ ]

[ ][ ][ ] [ ] [ ] [ ]

[ ][ ][ ] [ ] [ ] [ ]

[ ][ ][ ] [ ] [ ] [ ]

∆−∆−

+

∆−∆+

+

∆−+∆+

+

+−

∆−

∆−=

−−

−+−

−+−

−+−+

tvv

CLCt

tEhEh

CLCt

xiii

LCt

vEhxvvLtii

nkgi

nkgi

ijijij

nki

nki

ijijij

nki

nki

nki

ijij

nkgi

nki

nki

nki

ijnki

nki

11

2

111

2

2111

2

1111

'''''

2

2'''

2

2''

2

'2

'

(3.36)

Treatment of line transverse discontinuities in FDTD 2nd order scheme for a single-

conductor line. In the proposed FDTD 2nd order scheme, the voltages and currents nodes are coincident, which allows simplifying the equations for the treatment of the periodical groundings. The treatment of a shunt impedance representing one of the conductor groundings for an overhead line illuminated by an external electromagnetic field is schematically illustrated in Fig. 3.3.

∫h

ez dz)t,z,x(E

0

ΓVoltage and Current FDTD 2nd order node

vkn+1, ikn+1 vk-1

n+1, ik-1n+1

dx

k spatial discretization n time discretization dx spatial discretization

ik’ n ik”

n

ign

Known variables: • All internal node scattered

voltages and currents at time step n+1

• Operator Γ (=Rg in case of ground resistance)

• Vertical Electric Field Ez Unknown variables:

• vkn+1

• ikn+1

vk+1n+1, ik+1

n+1

g

Fig. 3.3. Insertion of discontinuity point, in a generic point along a single-conductor line, in the 2nd order

Finite Difference integration scheme.

Page 41: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

34

Applying equation (3.1) the node voltage vkn+1 (see Fig. 3.3) can be expressed as follows:

∫+= ++h

ez

ng

nk (x,z,t)dzE)Γ ( iv

0

11 (3.37)

where ! ig

n+1 is the current flowing in the grounding impedance; ! Γ is an integral-differential operator, which describes the voltage drop across the

shunt impedance as a function of current ig. ( gg iRΓ ⋅= for the simple case of a

resistance). As for the FDTD 1st order scheme (see appendix A.1) current ig

n+1 can be expressed as function of the current ik

n+1, ikn+1 applying Kirchhoffs law on the currents at the

grounding node

1''

1'

1 +++ −= nk

nk

ng iii (3.38)

Currents ik

n+1, ikn+1 can be expressed as a function of the adjacent current nodes

assuming the following linear spatial interpolation:

12

11

1' 2 +

−+−

+ −= nk

nk

nk iii (3.39)

12

11

1'' 2 +

+++

+ −= nk

nk

nk iii (3.40)

By introducing (3.38) (3.39) and (3.40) in (3.37) we obtain the equation for the scattered

voltage at the grounding point:

∫++−−= ++

++

+−

+−

+h

ez

nk

nk

nk

nk

nk (x,z,t)dzE)iiiiΓ (v

0

12

11

12

11

1 22 (3.41)

The node current ik

n, needed in equations (3.19) (3.20) to compute voltages and currents at nodes k-1 and k+1, must be substituted with (3.39) and (3.40) respectively with equations written for the node k-1 and k+1.

Treatment of line transverse discontinuities in FDTD 2nd order scheme for a multi-

conductor line. The treatment of periodical groundings in the FDTD 2nd order integration scheme for a multi-conductor line, is a simple extension in terms of current and voltage

Page 42: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

35

vector of equations (3.37)-(3.41). In particular the equation for the scattered voltage at the grounding of the conductor point reads:

[ ] [ ] [ ] [ ] [ ] [ ]( )

++−−= ∫+

+++

+−

+−+

ihez

nki

nki

nki

nki

nki (x,z,t)dzEiiii ΓK v

0

12

11

12

111 22 (3.42)

Equations (3.39) and (3.40) become:

[ ] [ ] [ ] 12

11

1' 2 +

−+−

+ −= nki

nki

nki iii (3.43)

[ ] [ ] [ ] 12

11

1'' 2 +

+++

+ −= nki

nki

nki iii (3.44)

where

[ ] [ ] ;:

;:

3

2

1

3

2

1

=

=

nkNC

nk

nk

nk

nki

nkNC

nk

nk

nk

nki

v

vvv

v

i

iii

i (3.45)

=

NC

i

hez

hez

hez

hez

hez

(x,z,t)dzE

(x,z,t)dzE

(x,z,t)dzE

(x,z,t)dzE

(x,z,t)dzE

0

0

0

0

0

:

3

2

1

(3.46)

and matrix [ ΓK ]:

[ ]

=

NCNCK

KK

K

K

Γ|000|

0|Γ000|0Γ00|00Γ

Γ 33

22

11

(3.47)

Page 43: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

36

3.1.3. – Comparison with experimental results and simulations The validation of the Agrawal coupling model modified for the treatment of periodical

groundings was performed by means of the experimental results obtained on reduced scale line models illuminated by an EMP simulator. The reported experimental data was obtained from two different sessions performed at the Swiss Federal Institute of Technology in Lausanne on the EMP simulator of their laboratory described in more detail in [Arreghini et al., 1993]. The simulator is a bounded wave vertically-polarized type. A measurement record of the waveform of the electric vertical field inside the working volume, performed in absence of the line during the experimental campaign, is presented in Fig. 3.4.

0

5

10

15

20

25

0 50 100 150 200Time [ns]

Verti

cal

Elec

tric

Fie

ld [

kV/m

]

Fig. 3.4. Vertical electric field in absence of the line measured in the working volume of the SEMIRAMIS

EMP simulator. Adapted from Paolone et al. [2000]. The reduced scale line model reproduces single and multi-conductor lines. The procedure

used for the validation is based on the measurement of the electrical field generated in the simulator (see Fig. 3.4) and the measurement of the induced current in the reduced scale line model at line terminations for each conductor. The measured vertical electric field is used as input in the modified Agrawal coupling model, then the results obtained from the simulations are compared with the measured currents.

In what follows we report the results concerning both a single conductor with a shielding wire grounded at the line extremities (Fig. 3.5), and a three conductor configuration with a shielding wire grounded at line extremities and at the line center (Fig. 3.7).

For the configuration with a single conductor, the shielding wire was placed above and under the phase conductor at different heights (as shown in Fig. 3.5). The comparison between the measurement and the simulation, reported in Figs. 3.6, show the current at line terminations on the phase conductor with and without the presence of the shielding wire.

Page 44: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

37

2m

Shielding Wire

Phase conductor

20 c

m

14-1

6-18

-22-

24-2

6 cm

1.4 mm 0

Ω

680

Ω

680

Ω

0 Ω

Return conductor

Fig. 3.5. Reduced scale line model used in the SEMIRAMIS EMP Simulator composed by a single

conductor with shielding wire grounded at line extremities.

a)

-0.5

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

0.02 0.04 0.06 0.08 0.10 0.12 0.14 0.16 0.18 0.20

Time [µs]

Cur

rent

[A]

without SW measurementwithout SW simulationwith SW 14 cm measurementwith SW 14 cm simulation

b)

-0.5

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

0.02 0.04 0.06 0.08 0.10 0.12 0.14 0.16 0.18 0.20

Time [µs]

Cur

rent

[A]

without SW measurementwithout SW simulationwith SW 16 cm measurementwith SW 16 cm simulation

Page 45: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

38

c)

-0.5

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

0.02 0.04 0.06 0.08 0.10 0.12 0.14 0.16 0.18 0.20

Time [µs]

Cur

rent

[A]

without SW measurementwithout SW simulationwith SW 18 cm measurementwith SW 18 cm simulation

d)

-0.5

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

0.02 0.04 0.06 0.08 0.10 0.12 0.14 0.16 0.18 0.20

Time [µs]

Cur

rent

[A]

without SW measurementwithout SW simulationwith SW 22 cm measurementwith SW 22 cm simulation

e)

-0.5

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

0.02 0.04 0.06 0.08 0.10 0.12 0.14 0.16 0.18 0.20

Time [µs]

Cur

rent

[A]

without SW measurementwithout SW simulationwith SW 24 cm measurementwith SW 24 cm simulation

Page 46: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

39

f)

-0.5

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

0.02 0.04 0.06 0.08 0.10 0.12 0.14 0.16 0.18 0.20

Time [µs]

Cur

rent

[A]

without SW measurementwithout SW simulationwith SW 26 cm measurementwith SW 26 cm simulation

Fig. 3.6. Comparison between the experimental results and simulations relevant to line configuration of Fig.

3.5: induced current on the phase conductor; a) height of shielding 14 cm; b) height of shielding 16 cm; c) height of shielding 18 cm; d) height of shielding 22 cm; e) height of shielding 24 cm; f) height of shielding 26

cm. For the line configuration with three conductors, the shielding wire was placed above the

highest phase conductor (as indicated in Fig. 3.7). The comparison between the measurement and the simulation, reported in Figs. 3.8, show the current at line terminations on all the line conductors (phase conductors and shielding wire) with and without the presence of the shielding wire.

2m

Shielding Wire

Phase conductors

20 c

m

27.4

cm

1.4 mm

0 Ω

680

Ω

0 Ω

680

Ω

680

Ω

680

Ω

0 Ω

68

0 Ω

68

0 Ω

Return conductor

34.8

cm

40

.9 c

m

Fig. 3.7. Reduced scale line model used in the SEMIRAMIS EMP Simulator composed by three conductors

with shielding wire grounded at line extremities.

Page 47: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

40

a)

-0.5

-0.3

-0.1

0.1

0.3

0.5

0.7

0.9

1.1

1.3

1.5

0.02 0.04 0.06 0.08 0.10 0.12 0.14 0.16 0.18 0.20Time [µs]

Cur

rent

[A]

conductor 1 without SW measurementconductor 1 without SW simulationconductor 1 with SW measurementconductor 1 with SW simulation

b)

-0.5

0.0

0.5

1.0

1.5

2.0

2.5

3.0

0.02 0.04 0.06 0.08 0.10 0.12 0.14 0.16 0.18 0.20Time [µs]

Cur

rent

[A]

conductor 2 without SW measurementconductor 2 without SW simulationconductor 2 with SW measurementconductor 2 with SW simulation

c)

-0.5

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

0.02 0.04 0.06 0.08 0.10 0.12 0.14 0.16 0.18 0.20Time [µs]

Cur

rent

[A]

conductor 3 without SW measurementconductor 3 without SW simulationconductor 3 with SW measurementconductor 3 with SW simulation

Page 48: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

41

d)

-0.5

1.5

3.5

5.5

7.5

9.5

11.5

13.5

0.02 0.04 0.06 0.08 0.10 0.12 0.14 0.16 0.18 0.20Time [µs]

Cur

rent

[A]

conductor SW measurementconductor SW simulation

Fig. 3.8. Comparison between the experimental results and simulations relevant to line configuration of Fig. 3.7: induced current on the line conductor; a) conductor 1; b) conductor 2; c) conductor 3; d) shielding wire.

An additional validation of the proposed model was performed by testing it with the

theoretical results of Yokoyama [1984]. The line configuration considered there is presented in Fig. 3.9. Note that there is only one grounding of the shielding wire, at the line center, in front of the stroke location. Our results of computation considering different values for the grounding resistance are presented in Fig. 3.10. The results practically coincide with those presented by Yokoyama, reported in Fig. 3.10b for convenience.

2 km

10 m

0.8 cm

Rg Matched

1000 m

100 m

Grounded Conductor

Matched

0.5 m 0.5 m

Fig. 3.9. Line geometry adopted to evaluate the effect of a shielding wire to a multi-conductor line

[Yokoyama, 1984]. Lightning current: peak value 100 kA; maximum time-derivative 50 kA/µs. Ideal ground.

Page 49: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

42

a)

0

100

200

300

0 2 4 6 8 10 12 14 16 18 20

Time [µs]

Indu

ced

Ove

rvol

tage

[kV]

Rg=0 OhmRg=30 OhmRg=100 OhmRg=200 OhmRg=500 OhmRg=1.E9 Ohm

b) Fig. 3.10. Induced voltage for a variable grounding resistance (Rg). Line configuration of Fig. 3.9: a)

simulation results, b)Yokoyama [1984]-Fig. 4. Adapted from Paolone et al. [2000]. The results of Fig. 3.10 show that the value of the grounding resistance largely affects the

amplitude of the induced voltages. Such results can be ascribed, as we shall see better in what follows, to the fact that the stroke location is situated just in front of the grounding resistance.

Effect of the shielding wires groundings. To better assess the effect of the shielding wire,

of the number of the periodical groundings and of the value of the grounding resistance, we have considered the line geometry shown in Fig. 3.11 in which the stroke location does not face any of the grounding points.

Page 50: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

43

L

Shielding Wire

Phase conductor

Variable

9 m

10 m

1 cm

Rg Rg RgZc ZcRg Rg

750 m

50 m

StrokeLocation

Fig. 3.11. Line geometry adopted to evaluate the effect of the presence of a shielding wire. Lightning

current: peak value 30 kA maximum time derivative 40 kA/µs. Adapted from Paolone et al. [2000]. The adopted lightning current has the following characteristics: peak value 30 kA

maximum time derivative 40 kA/ms. The following results concern the effect on lightning induced voltage peak value of the grounding step namely: 100 m; 200 m; 500 m and 1000 m, and of the grounding resistance namely: 0 Ω; 30 Ω, 100 Ω and 1 kΩ. In Figs 3.12, we present the peak value of the induced overvoltages along the 2 km long line for a perfectly conducting ground; the same results have been computed taking into account the finite ground conductivity (σg=0.001 S/m) and they are shown in Fig. 3.13.

In addition, the following figures which relate to the ideal ground case, the mitigation effect as predicted by the Rusck formula is also shown:

gsw

isw

i

sw

i

i

RZZ

hh

UU

21'

+⋅−== −η (3.48)

where:

! Ui is the lightning induced voltage in conductor i in presence of the shielding wire;

! Ui is the lightning induced voltage in the conductor in absence of the shielding wire;

! hsw is the height of the shielding wire; ! hi is the height of conductor i; ! Zsw-i is the mutual surge impedance between the shielding wire and conductor i; ! Zsw is the surge impedance of the shielding wire; ! Rg is the grounding resistance.

Page 51: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

44

It is worth reminding that the Rusck expression does not cover the case of multiple groundings of the shielding wire (it assumes that the shielding wire is grounded at single point along the line) and that is applicable in the assumption of perfectly conductive ground.

a)

0

50

100

150

200

250

0 500 1000 1500 2000Distance along the line [m]

Peak

Val

ue o

f In

duce

d O

verv

olta

ge [

kV] without SW

3 grs5 grs11 grs21 grsRusck

b)

0

50

100

150

200

250

0 500 1000 1500 2000Distance along the line [m]

Peak

Val

ue o

f In

duce

d O

verv

olta

ge [

kV]

without SW3 grs5 grs11 grs21 grsRusck

Page 52: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

45

c)

0

50

100

150

200

250

0 500 1000 1500 2000Distance along the line [m]

Peak

Val

ue o

f In

duce

d O

verv

olta

ge [

kV]

without SW3 grs5 grs11 grs21 grsRusck

d)

0

50

100

150

200

250

0 500 1000 1500 2000Distance along the line [m]

Peak

Val

ue o

f In

duce

d O

verv

olta

ge [

kV]

without SW3 grs5 grs11 grs21 grsRusck

Fig. 3.12. Induced voltage peak value along the line for a variable number of grounding step and variable

grounding resistance namely: a) 0 Ω, b) 30 Ω, c) 100 Ω, d) 1 kΩ. Line configuration of Fig. 3.11 with L=2 km. Ideal ground. Adapted from Paolone et al. [2000].

Page 53: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

46

a)

0

50

100

150

200

250

300

0 200 400 600 800 1000Distance along the line [m]

Peak

Val

ue o

f In

duce

d O

verv

olta

ge [

kV]

without SW3 grs5 grs11 grs

b)

0

50

100

150

200

250

300

0 200 400 600 800 1000Distance along the line [m]

Peak

Val

ue o

f In

duce

d O

verv

olta

ge [

kV]

without SW3 grs5 grs11 grs

Fig. 3.13. Induced voltage peak value along the line for a variable number of grounding step and variable

grounding resistance namely: a) 10 Ω, b) 300 Ω. Line configuration of Fig. 3.11 with L=1 km. Stroke location at 375 m from the left line termination. Lossy ground σg=0.001 S/m. Adapted from Paolone et al. [2000]. The results reported in Fig. 3.10a show that, if the stroke location is located in front of a

grounding point, the attenuation of the induced overvoltage on the phase conductors is very dependent from the value of the grounding resistance. Additionally, as confirmed by Yokoyama [1984], the prediction of the maximum value of the induced overvoltages obtained by the application of Rusck formula (3.48), is the same as the results obtained by considering the shielding wire an illuminated conductor.

If, instead, the stroke location does not face any grounding point, which is the more frequent case, the results show that for both cases of ideal and lossy ground, the mitigation effect of the shielding wire depends, in general, more on the number of groundings than on the value of the grounding resistance. The presence of a large number of groundings tends,

Page 54: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

47

in fact, to shift the shielding wire potential to the ground one enhancing the mitigation effect as predicted, for instance, by the Rusck approach.

For the case of lossy ground the number of groundings plays a decisive role too. This differs from the case of direct stroke for which the effectiveness of the shielding wire depends strongly on the grounding resistance.

The value of the grounding resistance which appear to influence the attenuation of the induced overvoltage, for both considered ideal and lossy ground conductivity, is 100÷200 Ohms.

The comparison with the Rusck formula is possible only for the case of ideal ground: in most cases, it tends to overestimate the effect of the shielding wire. This is due to the Rusck formula assumption that considers the shielding wire as a conductor at ground potential. Indeed only with a large number of grounding points (e.g. 11-21 groundings), the results predicted by Rusck formula and the proposed model tend to provide the same values.

Effect of the presence of surge arresters. The presence of surge arresters along the line

can be treated in a similar way as for the discontinuities caused by the periodical groundings of shielding wire. In this case, we have modeled the surge arresters representing them with a non-linear V-I characteristic (the integro-differential operator Γ) placed in series with the incident voltage.

To compare the mitigation effect achieved by employing surge arresters with that of the shielding wire periodical grounding technique, we have considered the same single-conductor line of the previous simulation (Fig. 3.14).

L

Phase conductor

Variable

9 m

1 cm

Surge Arrester

Surge Arrester

Surge Arrester

Surge Arrester

Zc Surge Arrester

Zc

750 m

50 m

Stroke Location

Fig. 3.14. Line geometry adopted to evaluate the effect of surge arrester. Lightning current: peak value 30

kA maximum time derivative 40 kA/µs. Adapted from Paolone et al. [2000].

Page 55: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

48

The V-I characteristic of the surge arrester is shown in the following table.

Voltage [V] Current [A] 20820 0.09E-02 25980 0.12E-02 29100 0.06E-01 31140 0.06 33300 0.6 47460 3000 51000 6000 56640 12000

Tab. 3.1. Surge arrester V-I characteristic.

We have considered a variable number of surge arresters placed along the line: 2 (at the

line terminal only) 3 (each 1000 m), 5 (each 500 m) and 11 (each 200 m). The induced overvoltage amplitudes are shown in Figs. 3.15 and 3.16.

-250

-150

-50

50

150

250

0 500 1000 1500 2000Distance along the line [m]

Peak

Val

ue o

f O

verv

olta

ge [

kV]

without SA2 SA3 SA5 SA11 SA

Fig. 3.15. Induced voltage peak value along the line for a variable number of surge arresters along the line.

Line configuration of Fig. 3.14 with L=2 km. Ideal ground. Adapted from Paolone et al. [2000].

Page 56: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

49

-100

0

100

200

300

0 200 400 600 800 1000Distance along the line [m]

Peak

Val

ue o

f O

verv

olta

ge [

kV]

without SA2 SA3 SA6 SA

Fig. 3.16. Induced voltage peak value along the line for a variable number of surge arresters along the line. Line configuration of Fig. 3.14 with L=1 km. Stroke location at 375 m from the left line termination. Lossy

ground σg=0.001 S/m. Adapted from Paolone et al. [2000]. The computed results show that an important reduction of the induced overvoltage can be

achieved only with a large number of surge arresters namely 1 surge arrester each 0.2 km. It can also be seen that for some configurations, the presence of surge arresters could result in important negative peaks which are due to the reflection coefficients, associated with the surge arresters, when the induced voltage exceed the threshold voltage of this non-liner component. Indeed, depending on the line configuration, stroke location and distance between two consecutive surge arresters, the negative voltage wave generated by the non-linear components can produce the maximum amplitude of the induced overvoltage not in the point closest to the stroke location. In addition this overvoltage can be more severe than the maximum voltage amplitude induced in the absence of surge arresters (see Fig. 3.15).

By increasing the number of surge arresters the maximum amplitude of the induced overvoltage tends to stay within the range generated by the positive and negative values of the threshold voltage of the surge arrester V-I non-linear characteristic (see Tab. 3.1).

3.2. – Distribution systems This paragraph reports the developed illuminated distribution system model. It is

obtained by means of an interface between the developed complex overhead line model and two popular programs used for the power system transient analysis, namely: the EMTP96 and the Power System Blockset within Matlab environment.

The developed illuminated distribution system model is aimed at the correct estimation of the induced overvoltages for realistic distribution systems. This estimation is necessary in order to optimize the number and location of protective devices (shielding wire groundings

Page 57: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

50

and surge arresters) and to minimize the number of outages. In particular, the presence of distribution transformers and of the relevant protection devices at the line terminations, as well as the presence of surge arresters along the line, should be considered in the simulation.

The use of the developed illuminated distribution system model permits to perform the analysis of the effect of the aperiodic disturbance caused by LEMP on the various power system components (e.g. the distribution transformers). Indeed the lightning-induced overvoltages on distribution transformers, and their propagation from the medium voltage to the low voltage of the distribution system, is not yet considered in the literature on the argument.

The aim of the proposed model is to gives an engineering tool enabling to analyze the above mentioned aspects.

3.2.1. – Proposed approach For evaluating the lightning performance of distribution networks the availability of a

tool for the calculation of lightning-induced voltages is crucial. Such a tool can be a) a simple analytical formula (as for instance the Rusck [1958] one, adopted in the IEEE WG on lightning performance of distribution lines [1997]), b) a computer code.

An analytical formula presents the advantage of short computational times; on the other hand its application is limited to cases which tend to be unrealistic (as reported in the comparison of Fig. 2.7 between the Rusck simplified formula and the Agrawal model). The distribution system model that we are aimed at developing instead must potentially permit the treatment of realistic cases reported schematically in Fig. 3.17.

In the LIOV code [Nucci et al., 1993; Rachidi et al. 1996,1997, Nucci, 2000] the Agrawal et al. field-to-transmission line coupling model has been implemented for dealing with the case of multi-conductor lines closed on resistive terminations. In principle, the LIOV code could be suitably modified, case by case, in order to take into account the presence of the specific type of termination, line-discontinuities (e.g. surge arresters across the line insulators along the line) and of complex system topologies. This procedure requires that the boundary conditions for the transmission-line coupling equations be properly re-written case by case, as discussed in [Nucci et al., 1994].

However, as proposed by other authors too [Nucci et al., 1994; Orzan et al.,1996; Orzan, 1998; Høidalen, 1997,1999], we found more convenient to link the LIOV code with the EMTP. With these LIOV-EMTP codes it is possible to analyze the response of realistic distribution systems. In [Nucci et al., 1994], the distribution system model is considered, as in the proposed approach (see next paragraph), as consisting of a number of illuminated lines connected to each other through a shunt admittance. The LIOV code has the task of calculating the response of the various lines connecting the two-ports (see Fig. 3.17); the EMTP has the task of solving the boundary condition and presents the advantage of making available a large library of power components.

Page 58: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

51

In this new version of the interface between the LIOV code and the EMTP96 (henceforth called LIOV-EMTP96), each LIOV line is described by the Agrawal coupling model but the partial differential equation are now solved using the previously described line model based on the FDTD 2nd order scheme in order to improve the numerical stability when non-linear phenomena are considered.

In the literature on the argument there are two other proposed models for the evaluation of the LEMP response of distribution networks, proposed by Orzan [Orzan et al.,1996; Orzan, 1998] and Høidalen [1997,1999] respectively.

In [Orzan et al.,1996; Orzan, 1998] for each illuminated line the coupling between the external incident field and the phase conductors is reproduced, in the distribution network model, by means of equivalent current generators whose value is pre-calculated by solving the Agrawal transmission line coupling model. The current generators are then inserted in an EMTP simulation where traditional lines models replace illuminated lines. Such an approach cannot take into account non-linear local phenomena, like a variation in the line-capacitance with space, as necessary for instance when taking into account the presence of corona phenomenon [Nucci et al., 2000].

In the model proposed by Høidalen [1997,1999], the analysis of the response of the illuminated distribution system uses the same concepts adopted in the model developed by Orzan namely each illuminated line response is reproduced by means of equivalent voltage generators. The main difference with Nucci et al. [1994] and [Orzan et al.,1996; Orzan, 1998] is in the evaluation of the coupling between the external incident field and each illuminated line: Høidalen solves it using an analytical approach valid only for the ideal ground case.

Finally, compared to [Nucci et al., 1994], the advantages of this new LIOV-EMTP96 program are that: (i) the illuminated line model is able to take into account more complex line configuration, (ii) it does not require any modification of the EMTP source code, (iii) it allows for the treatment of corona effect which was implemented.

3.2.2. – Interface between the developed line model and transient programs Interface between LIOV and EMTP96. As previously mentioned, in order to perform in a

straightforward way the analysis of the LEMP response of real distribution systems characterized by a certain topological complexity, the developed program based on the 2nd order FDTD scheme has been interfaced with the Electromagnetic Transient Program (EMTP96). Note that in principle, the developed program could have been suitably enlarged and extended case by case to take into account the specific system configuration, as discussed in [Nucci et al., 1994]. As a matter of fact, paragraph 3.1 relevant to the transverse discontinuities, report an example of such a concept.

Page 59: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

52

The concept at the basis of the new interface, a beta-version of which has been presented in [Borghetti et al., 2000a; Paolone et al., 2001b] , is schematically described in Fig. 3.17.

Γ

0

LIOV lines

n-port

Fig. 3.17. Electrical distribution system illuminated by LEMP. The distribution system network is considered as consisting of a number of illuminated

lines connected to each other through a shunt admittance. This admittance represent the presence of surge arresters, of groundings of shielding wires, of distribution transformers or of other power components. Each section of the distribution system between two consecutive shunt admittances is modeled as a single line henceforth called LIOV-line, while the program which result from the link between the LIOV and the EMTP96 will be called LIOV-EMTP96.

The difference from [Nucci et al., 1994] is that the new interface does not require any modification to the source code of the EMTP: the modified LIOV code is indeed contained in a dynamic link library (DLL), called within the TACS environment. The data exchange between the LIOV code and EMTP96 is realize in the following way: the induced currents at the terminal nodes, computed by the modified LIOV code are input to the EMTP via current controlled generators, and the voltages calculated by the EMTP are input to the modified LIOV code via voltage sources.

The scheme of the data exchange in the developed interface is shown in Fig. 3.18.

Page 60: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

53

EMTP

(1) Line terminals node currents and voltages attime step N TACS LIOV

LINE

(2) Line terminals node currents and voltages attime step N

(3) Line terminals voltageat time step N+1

(4) Line terminals voltage at time step N+1

N=N+1

(6) Line terminals voltage attime step N+1 inserted in the EMTP by current controlled generators (5) EMTP time step

increment for node voltagesand branch currents

TACS – LIOV LINE (2) (3)

(6) (6)

EMTP (4) (5) V (1)

V

V (1)

I (1) I (1)

V Line Termination

Line Termination

Fig. 3.18. Interface between LIOV code and EMTP96. Adapted from Paolone et al. [2001a]. The link between the LIOV-line and the EMTP96 is realized by means of a loss less

Bergeron line (see Fig. 3.19). The insertion of this line in necessary to write, in an appropriate way, the link equation between the terminal nodes of the FDTD spatial discretization of the illuminated line, and the line generic EMTP96 termination. In what follows we shall refer to the left termination of a single-conductor line; the right line termination is treated in the same way.

Node ‘0’

+

-

v0(t), i0(t)

G2 +

-+

-

Γ0(t)

v1(t), i1(t)

Zc

v0’(t)

i0’(t) ve(t)

Node ‘1’

LIOV line Bergeron Line EMTP termination

+

--ve(t)

G1

Zc

v2(t), i2(t) Node ‘2’

∆x

Fig. 3.19. Insertion of the Bergeron loss less line for the data exchange between the LIOV code and the EMTP96 environment at the left line termination.

Page 61: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

54

where: ! G1 and G2 are the Bergeron equivalent generators; ! ve(t) is the incident voltage defined in equation (2.13); ! Zc is the line characteristic impedance; ! v0(t), v1(t), i0(t), i1(t) are the voltages and currents at nodes of the FDTD spatial

discretization; ! v0(t), i0(t) are the voltage and current at the EMTP node; ! Γ0(t) is the EMTP termination type. The generators due to the incident voltages ve(t), can be introduced in the Bergeron G1

and G2 generators respectively. From the Bergeron equations in a fixed time step n we can write the following equations:

hEiZvG nz

nc

n0'0'01 +−= (3.49)

hEiZvG nz

nc

n 10

10

102

+++ +−= (3.50)

where: ! Zc is the characteristic impedance of the line; ! h is the conductor height; ! Ez0 is the vertical component of the electric field at the left line termination. We can write, for node 0 of the FDTD spatial discretization of the LIOV line, the

following equations. In particular if we consider the node 0 as connected with the Bergeron line we can write:

1

01

011

0+++ −+= n

cnz

n iZhEGv (3.51)

Now if we consider node 0 as connected to the LIOV line we can obtain the scattered

voltage v0n+1 from the discretization of the second equation of the Agrawal coupling model

for a single-conductor line (2.12):

001

01

01

1 =∆−+

∆− +++

tvvC

xii nnnn

(3.52)

( ) nnnn viixCtv 0

10

11

10 +−

∆∆= +++ (3.53)

Page 62: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

55

From (3.52) and (3.53) we can write the following equation, from which we can obtain variable i0

n+1:

−−

∆∆+

−∆∆= ++++

11

01

11

01

01 GhEi

xCtv

ZxCti n

znn

c

n (3.54)

In summary the algorithm for the data exchange between the LIOV line and the EMTP

consists of the following steps: ! calculation of the input voltage for the generators G1 located at line left and right

terminations with the (3.49) (see Fig. 3.19); ! calculation, at time step n+1, of the scattered voltages and currents at all FDTD

spatial nodes; ! calculation of the currents i0

n+1 and ikmaxn+1 1 from (3.54);

! calculation of the scattered voltages v0n+1 and vkmax

n+1 from (3.53); ! calculation of the values of the output variable for generators G2, located at line left

and right terminations, from (3.50). Interface between LIOV and Power System Blockset within Matlab

environment. The procedure above described for the interface between the LIOV code with EMTP96, has been also implemented in a Matlab core code (Mat-LIOV). In the Mat-LIOV code, as in the LIOV one, the model adopted to describe the lightning return stroke is the MTLE model, the calculation of the incident electromagnetic field is performed in the presence of a finite conducting ground by using the Cooray-Rubinstein approach [Rubinstein 1991,1996; Cooray 1992,1994], and the coupling between the external incident field and a single multi-conductor line is modeled by means of the Agrawal et al. [1980] coupling model.

The basic concept of the developed interface is the same developed for the EMTP96 one: leave the task of solving the transmission line coupling equations relevant to each line to the Mat-LIOV code, and that of solving the boundary conditions to the Power System Blockset. The link between the Mat-LIOV and the Power System Blockset is realized also in this case by using a Bergeron line, which accomplish the data exchange between the two mentioned tasks (see Fig. 3.19. 3.20).

The Mat-LIOV task is contained in an s-function developed to exchange line terminals voltages and currents with the Power System Blockset environment as shown in Fig. 3.20. In particular, the s-function calculates the necessary line parameters (inductance,

1 kmax is the last FDTD spatial node at line right termination.

Page 63: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

56

capacitance and surge impedance matrix) and solves, for each line, the discretized transmission line coupling equations by means of the 2nd order FDTD scheme.

The computational procedure is the following: at a given time step the Power System Blockset sends the nodal voltages at each line termination to the s-function block which solves the discretized transmission line coupling equations. Then, one time step later, the s-function block sends the voltage at the line terminations back to the Power System Blockset; this information exchange is accomplished step by step by means of a Bergeron line as described in the previous paragraph for the interface with the EMTP96 (see Fig. 3.19).

S-Fuction (Mat-LIOV)

V

V

V

I I

V Line Termination

Line Termination

Fig. 3.20. Interface scheme between Mat-LIOV code and Power System Blockset in Matlab environment.

Adapted from Gutierrez et al. [2001].

3.2.3. – Comparison with experimental results and simulations An experimental validation of the the developed LIOV-EMTP96 program and relevant

algorithm, is realized by means of the experimental results obtained by Piantini and Janischewskyj [1992]. The measurements have been performed on reduced scale models set up at the University of Sao Paulo in Brazil, which reproduce a typical overhead distribution system (main feeder plus branches) including surge arresters, neutral grounding, T-junctions (between line branches) and shunt capacitors aimed at modeling distribution transformers. The surge arresters are simulated by means of a combination of diodes and resistances, and their V-I non-linear characteristic is shown in Fig. 3.22. For cases 1.1 and 1.2 the lines of such system have 4 conductors and the line geometry is represented in Fig. 3.21a in the real scale. For cases 2.1, 2.2 and 2.3 the lines of the system have a simplified configuration with 2 conductors (see Fig 3.21b).

The system that simulates the lightning current generate a current wave shape that can be approximated with a triangular profile with a time to peak value equal to 2 µs and a half time equal to 85 µs. For all cases the lightning return stroke velocity is, in the real scale, equal to 0.33⋅108 m/s, the lightning channel height is 600 m and the lightning return stroke model can be represented with the TL model. For each case different value for the lightning peak current are considered.

Page 64: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

57

a)

8 m

10 m

2 cm0.75 m

b)

8 m

10 m

2 cm

Fig. 3.21. Line geometries used for the reduced scale models in [Piantini and Janischewskyj, 1992]. a) line geometry adopted for the cases 1.1 and 1.2, b) line geometry adopted for the cases 2.1, 2.2 and 2.3.

Fig. 3.22. Surge arresters V-I non-linear characteristic. Adapted from Piantini and Janischewskyj [1992]. Case 1.1. The network configuration is shown in Fig. 3.23, scaled to real dimension. In

Figs. 3.24 are reported the connection types of the line terminations. The stroke location is represented in Fig. 3.23 at point r.s.m., two different value of lightning current are considered for this case, their characteristics are given in Tab. 3.2.

Lightning current (kA) Time (µs)

Case 1.1.a Case 1.1.b 0. 0. 0. 2. 34. 70.

85. 17. 35.

Tab. 3.2. Lightning current for the case 1.1.

Page 65: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

58

90 m 210 m

150 m 148 m

210 m 148 m

346 m

42 m 132 m

284 m

210 m

152 m

210 m

150 m

170 m

150 m150 m

r.s.m.70 m

20 m

M1

Fig. 3.23. Network configuration for the case 1.1.

1 2 3

N

R = 50 Ohm

L = 22 uH

SA SA SACt Ct Ct

Ct = 0.5 nF

1 2 3

N

R = 50 Ohm

L = 22 uH

M1

1 2 3

N

Cp Ct Ct

Cp = 0.65 nF

Ct = 0.5 nF

L = 22 uH

SA

L = 1 uH

Rpr

C = 13.5 uF

Ipr [A] Vpr [V]

0. 0.

36. 27000.

54. 27900.

360. 29700.1620. 32220.

Fig. 3.24. Termination types for the network configuration of Fig. 3.23. Fig. 3.25 reports a comparison between the voltage measured at node M1 (see Fig. 3.23),

and the simulation performed with the LIOV-EMTP96 for lightning current peak values equal respectively to 34 kA and 70 kA. The measurement and simulation regard the phase conductor close to the stroke location.

Page 66: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

59

a)

-400

-300

-200

-100

0

100

200

300

400

0 1 2 3 4 5 6 7 8

Time [µs]

Indu

ced

Ove

rvol

tage

[kV

]

'LIOV-EMTP96'Measurement

b)

-800

-600

-400

-200

0

200

400

600

800

0 1 2 3 4 5 6 7 8

Time [µs]

Indu

ced

Ove

rvol

tage

[kV

]

'LIOV-EMTP96'Measurement

Fig. 3.25. Comparison between measurement and simulation for the case 1.1- a) Lightning current peak

value equal to 34 kA. b) Lightning current peak value equal to 70 kA. Case 1.2. The network configuration is reported in Fig. 3.26. In Figs. 3.27 are shown the

connection types of the line terminations. The stroke location is represented in Fig. 3.26 at point r.s.m., three different value of lightning current are considered for this case, their characteristics are given in Tab. 3.3.

Lightning current (kA) Time (µs)

Case 1.2.a Case 1.2.b Case 1.2.c Case 1.2.d 0. 0. 0. 0. 0. 2. 34. 50. 60. 70.

85. 17. 25. 30. 35.

Tab. 3.3. Lightning current for the case 3.2.

Page 67: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

60

90 m 210 m

150 m 148 m

210 m 148 m

346 m

42 m 132 m

284 m

210 m

152 m

210 m

150 m

170 m150 m

150 m

r.s.m.70 m

20 m

M1

Fig. 3.26. Network configuration for the case 1.2.

1 2 3

N

R = 50 Ohm

L = 22 uH

SA SA SACt Ct Ct

Ct = 0.5 nF

SA

L = 1 uH

Rpr

C = 13.5 uF

Ipr [A] Vpr [V]

0. 0.

36. 27000.

54. 27900.

360. 29700.1620. 32220.

M1

1 2 3

N

Cp Ct Ct

Cp = 0.65 nF

Ct = 0.5 nF

L = 22 uH

1 2 3

N

R = 50 Ohm

L = 22 uH

SA SA SA

Fig. 3.27. Termination types for the network configuration of Fig. 3.26.

Page 68: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

61

Fig. 3.28 reports a comparison between the voltage measured in the node M1 (see Fig. 3.26), and the simulation performed with the LIOV-EMTP96 for various lightning current peaks namely 34 kA (Fig. 3.28a), 50 kA (Fig. 3.28b), 60 kA (Fig. 3.28c) and 70 kA (Fig. 3.28d).

a)

-120

-100

-80

-60

-40

-20

0

20

40

0 1 2 3 4 5 6 7 8

Time [µs]

Indu

ced

Ove

rvol

tage

[kV

]

'LIOV-EMTP96'Measurement

b)

-200

-150

-100

-50

0

50

100

0 1 2 3 4 5 6 7 8

Time [µs]

Indu

ced

Ove

rvol

tage

[kV

]

'LIOV-EMTP96'Measurement

Page 69: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

62

c)

-200

-150

-100

-50

0

50

100

0 1 2 3 4 5 6 7 8

Time [µs]

Indu

ced

Ove

rvol

tage

[kV

]

'LIOV-EMTP96'Measurement

d)

-250

-200

-150

-100

-50

0

50

100

0 1 2 3 4 5 6 7 8

Time [µs]

Indu

ced

Ove

rvol

tage

[kV

]

'LIOV-EMTP96'Measurement

Fig. 3.28. Comparison between measurement and simulation for the case 1.2- a) Lightning current peak value equal to 34 kA. b) Lightning current peak value equal to 50 kA. c) Lightning current peak value equal to 60 kA.

d) Lightning current peak value equal to 70 kA. Case 2.1. The network configuration is reported in Fig. 3.29. In Figs. 3.30 are shown the

connection types of the line terminations. The stroke location is represented in Fig. 3.29 at point r.s.m., the lightning current characteristics considered for this case are given in Tab. 3.4.

Lightning current (kA) Time (µs)

Case 2.1 Case 2.2 Case 2.3 0. 0. 0. 0. 2. 70. 34. 50.

85. 35. 17. 25.

Tab. 3.4. Lightning current for the cases 2.1, 2.2, 2.3.

Page 70: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

63

90 m 210 m

150 m 148 m

210 m 148 m

346 m

42 m 132 m

284 m

210 m

152 m

210 m

150 m

170 m

150 m150 m

r.s.m.

M2

70 m

75 m

Fig. 3.29. Network configuration for the case 2.1.

1

N

Ct

Ct = 0.5 nF

R = 50 Ohm

L = 22 uH

M2

1

N

Cp

Cp = 0.65 nF

L = 22 uH

SA

L = 1 uH

Rpr

C = 13.5 uF

Ipr [A] Vpr [V]

0. 0.

36. 27000.

54. 27900.

360. 29700.1620. 32220.

1

N

R = 50 Ohm

L = 22 uH

1

N

R = 50 Ohm

L = 22 uH

SACt

Ct = 0.5 nF

Fig. 3.30. Termination types for the network configuration of Fig. 3.29.

Fig. 3.31 reports a comparison between the voltage measured in the node M2 (see Fig.

3.29), and the simulation performed with the LIOV-EMTP96 for lightning current peak equal to 70 kA.

Page 71: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

64

-100

-50

0

50

100

150

200

0 1 2 3 4 5 6 7 8

Time [µs]

Indu

ced

Ove

rvol

tage

[kV

]

'LIOV-EMTP96'Measurement

Fig. 3.31. Comparison between measurement and simulation for the case 2.1. Lightning current peak value

equal to 70 kA. Case 2.2. The network configuration is reported in Fig. 3.32. In Figs. 3.33 are shown the

connection types of the line terminations. The stroke location is represented in Fig. 3.32 at point r.s.m., the lightning current characteristics considered for this case are the same for the case 2.1 and are given in the previous Tab. 3.4.

90 m 210 m

150 m 148 m

210 m 148 m

346 m

42 m 132 m

284 m

210 m

152 m

210 m

150 m

170 m

150 m150 m

r.s.m.

M2

70 m

75 m

Fig. 3.32. Network configuration for the case 2.2.

Page 72: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

65

1

N

Ct

Ct = 0.5 nF

R = 50 Ohm

L = 22 uH

SA

L = 1 uH

Rpr

C = 13.5 uF

Ipr [A] Vpr [V]

0. 0.

36. 27000.

54. 27900.

360. 29700.1620. 32220.

1

N

R = 50 Ohm

L = 22 uH

M2

N

CpCp = 0.65 nF

L = 22 uH

SA

Fig. 3.33. Termination types for the network configuration of Fig. 3.32. Fig. 3.34 reports a comparison between the voltage measured in the node M2 (see Fig.

3.32), and the simulation performed with the LIOV-EMTP96 for lightning current peak namely 70 kA.

0

5

10

15

20

25

30

35

0 1 2 3 4 5 6 7 8

Time [µs]

Indu

ced

Ove

rvol

tage

[kV

]

'LIOV-EMTP96'Measurement

Fig. 3.34. Comparison between measurement and simulation for the case 2.2. Lightning current peak value

equal to 34 kA. Case 2.3. The network configuration is reported in Fig. 3.35. In Figs. 3.36 are shown the

connection types of the line terminations. The stroke location is represented in Fig. 3.35 at point r.s.m., the lightning current characteristics considered for this case are the same for the case 2.1-2.2 and are given in the previous Tab. 3.4.

Page 73: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

66

90 m 210 m

150 m 148 m

210 m 148 m

346 m

42 m 132 m

284 m

210 m

152 m

210 m

150 m

170 m

150 m150 m

r.s.m.

M2

70 m

75 m

Fig. 3.35. Network configuration for the case 2.3.

1

N

Ct

Ct = 0.5 nF

R = 50 Ohm

L = 22 uH

M2

1

N

Cp

Cp = 0.65 nF

L = 22 uH

SA

L = 1 uH

Rpr

C = 13.5 uF

Ipr [A] Vpr [V]

0. 0.

36. 27000.

54. 27900.

360. 29700.1620. 32220.

1

N

R = 50 Ohm

L = 22 uH

1

N

R = 50 Ohm

L = 22 uH

SACt

Ct = 0.5 nF

Fig. 3.36. Termination types for the network configuration of Fig. 3.35. Fig. 3.37 reports a comparison between the voltage measured in the node M2 (see Fig.

3.35), and the simulation performed with the LIOV-EMTP96 for lightning current peak equal to 70 kA.

Page 74: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

67

0

10

20

30

40

50

60

70

0 1 2 3 4 5 6 7 8

Time [µs]

Indu

ced

Ove

rvol

tage

[kV

]

'LIOV-EMTP96'Measurement

Fig. 3.37. Comparison between measurement and simulation for the case 2.3. Lightning current peak value

equal to 50 kA. The results above reported show a good agreement between the simulations and the

measurements. For case 1.1 the agreement between the simulations and the measurements is better than for case 1.2. This difference is probably due to the presence, for case 1.2, of a larger number of surge arresters than for case 1.1. This is supported by the results shown in Fig. 3.34 for case 2.2 where the observation point is placed on a surge arrester. Indeed, at this point the LEMP-response of the distribution system is due, mainly, to the surge arrester non-linear characteristic, which means that the difference between the simulation and the results are mainly affected by the surge arrester representation.

Which refer to the simplest line geometry and the reduced number of surge arresters, cases 2.1 and 2.3 show the better agreement between simulations and measurements.

Additional reasons for disagreement between measurements and simulations, for all cases, can be addressed also to: a) measuring errors: the overall uncertainty of the measuring system used in the tests was less than ±5%; b) high frequencies oscillations associated with the switching device of the generating system; c) variation of the current propagation velocity, its distortion and attenuation as it progresses upwards along the stroke channel.

However, if we consider the complexity of the considered distribution systems and the relative low disagreement between measurements and model simulations, the experimental validation of the proposed model can be considered satisfactory.

Case of corona. The developed LIOV-EMTP96 interface allows also for the computation

of lightning-induced overvoltages in presence of corona. The same model described in [Guerrieri, 1997; Correia de Barros et al., 1999; Nucci et al., 2000] has been indeed implemented in the illuminated line model described in paragraph 3.1. According to this model, from a macroscopic point of view, corona can be described by a charge-voltage

Page 75: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

68

diagram [Wagner et al., 1954; Gary et al., 1978]. After an initial linear increase of the charge with the voltage, a threshold voltage ( )t,xvth is reached and a sudden change of the

derivative of charge with respect to the voltage takes place. This derivative defines a voltage-dependent dynamic capacitance (Cdyn). We here consider a simplified corona model given by [Correia de Barros and Borges da Silva, 1984; Correia de Barros, 1985] for a single-conductor line:

( ) ( ) ( )( )( ) ( ) ( )( ) ( )( )

( ) ( ) ( )

>>

−+=

<=

0

21

tt,xvandt,xvt,xvfor

t,xv/t,xvt,xvkk'Ct,xCt,xvt,xvfor'Ct,xC

th

ththdyn

thdyn

∂∂

( ) ( )

<= 0

tt,xvfor'Ct,xCdyn ∂

(3.55)

where ! k1 (≥1) is related to the sudden change of the capacitance when the voltage exceeds

the corona threshold vth (typical values are in the range 1.5-3); ! k2 (≥0) is related to the gradual increase of the capacitance when the voltage is rising

above the threshold. A value of k2=0 corresponds to the simplest approach to model corona, that is

considering that the dynamic capacitance switches between only two values. The dynamic capacitance Cdyn is then inserted in the Agrawal equations in lieu of C. Fig. 3.39 reports some results obtained using the LIOV-EMTP96 program for the line

geometry shown in Fig. 3.38 relevant to a lightning stroke with current amplitude of 35 kA, maximum time-derivative of 42 kA/µs, ground conductivity of 0.01 S/m.

1 km

7.5

m

1 cm

Zc

500 m

Stroke Location Zc

50 m

Fig. 3.38. Line geometry adopted to evaluate the effect of corona. Lightning current: peak value 35 kA;

maximum time-derivative 42 kA/µs. ground conductivity 0.01 S/m.

Page 76: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 3. LEMP-to transmission-lines coupling models for distribution systems and their implementation in a transient program pag.

69

-50

0

50

100

150

200

250

300

0 1 2 3 4 5

Time [µs]

Indu

ced

Ove

rvol

tage

[kV

]

0 m250 m500 m

Fig. 3.39. Induced voltages along the line in presence of corona. Line configuration of Fig. 3.38.

Page 77: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 4. – Influence of lightning-induced overvoltages on power quality pag.

70

Chapter 4. – Influence of lightning-induced overvoltages on power quality

The overvoltages induced by lightning on distribution and transmission networks, can

cause phase-to-ground and phase-to-phase flashovers that need, for their removal, the use of recloser breakers. In the case of distribution networks the use of these breakers determines a temporal decrease of consumers voltage feeding, known as ‘voltage sags’. The duration of these voltage sags depends on the cycle type of the recloser breakers, which, in turn, depends on the fault removal time.

As known, voltage sags cause serious malfunction of a large number of apparatus as, in particular, of the electrical d.c. and a.c. motors. As a matter of fact, some types of speed controls for electrical motors interrupt their normal operation for a 15% decrease of the voltage supply that have a duration of one half cycle [Bollen, 1997].

There are different causes for voltage sags; for example, the start of electric motors with large rated power, or inrush currents due to transformer insertion. There is, however, clear evidence that in electrical systems located in regions with high value of isoceraunic level, thunderstorm days with lightning activity are associated to more than 80% of the voltage sags determining apparatus malfunction [Boonseng and Kinnares, 2001] (see Fig. 4.1 and 4.2). Nevertheless, lightning activity is not the only one responsible of the voltage sag related to the thunderstorm days because, associated with the same days, there are other natural causes [Dugan et al., 1996] such as is the wind effect, that may cause short circuits (e.g. branch of trees-ground; conductor-conductor).

Therefore it results of fundamental importance the estimation of the lightning performance of distribution lines in order to infer whether lightning is natural cause of outages or voltage sags during thunderstorm days or not.

2

4

6

8

10

12

14

16

0 2 4 6 8Lightning flash density (fl / km^2 / year)

Sags

/ m

onth

/ no

de

Fig. 4.1. – Influence of lightning flash density on voltage sags. Adapted from Gunther et al. [1995].

Page 78: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 4. – Influence of lightning-induced overvoltages on power quality pag.

71

0

2

4

6

8

10

12

14

16

18

Gen Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

%

Fig. 4.2. – Percentage of voltage sags, during one year, in 130 US and Canadian monitoring sites. Summer months are characterized with the greater number of thunderstorm days. Adapted from Dugan et al. [1996]

The basic question for a power engineer is how many lightning faults per year a certain

distribution line may experience, as a function of its insulation and of its design. The issue has been the object of several studies1.

In [Rusk, 1977; Pettersson, 1991] the frequency of overvoltages exceeding a given insulation level is evaluated by means of analytical methods for the case of an infinite long line over a perfect conducting plane. The amplitude of the lightning current at the channel base is considered as a random variable taking into account its probability distribution, while the front time of the lightning current and the return stroke velocity are considered fixed.

In [Chowdhuri, 1989b; Jankov and Grzybowski, 1997] a statistical method is employed. Both the probability distribution of amplitude and that of front time of the lightning current are considered. In [Chowdhuri, 1989b] the coefficient correlation between the two above-mentioned parameters is taken into account. The striking distance of the indirect stroke from the line (lightning strokes occurring within a certain distance from the line will directly strike the line) is evaluated as a function of the return stroke peak current (while in [Rusk, 1977] it is considered as independent of the current). The return stroke velocity is fixed and the ground is considered as a perfectly conductive plane.

All the above studies deal with single conductor lines, of infinite length, above a perfectly conducting ground.

In [Hermosillo and Cooray, 1995] the Monte Carlo method has been employed to solve the problem. The induced voltages are calculated at the termination of a 2 km overhead line

1 [Rusk, 1977; Chowdhuri, 1989b; Pettersson, 1991; Hermosillo and Cooray, 1995; Jankov and

Grzybowski, 1997].

Page 79: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 4. – Influence of lightning-induced overvoltages on power quality pag.

72

above a ground of finite conductivity. The Monte Carlo simulation involves 104 events taking place over a surface covering the line and 1000 m away from it. The same striking distance equation from the line as in [Chowdhuri, 1989b; Jankov and Grzybowski, 1997] is adopted. The correlation between peak value and front time of lightning current distributions is disregarded.

In this thesis, to estimate the frequency of lightning induced overvoltages exceeding a given insulation level on an overhead distribution line, we propose a procedure based on the Monte Carlo method, whose basis are found in [Borghetti and Nucci, 1998]. The proposed procedure allows to evaluate the lightning performance of distribution lines taking into account not only more realistic configurations than those usually considered in the literature, namely lines provided with shielding wires or neutral conductors with periodical groundings and surge arresters above a lossy ground, but also the line steady-state voltage and the type of flashover induced by lightning, namely phase-to-ground or phase-to-phase. Besides, according to the types of distribution transformer connections, the developed procedure allows also to take into account the change of the coupling factor between the phase conductors and the ground when a flashover occurs, and the relevant fault occurrence.

The proposed procedure will be first compared with the one proposed for the same purpose by IEEE [IEEE WG on the lightning performance of distribution lines, 1997], and eventually applied for a sensitivity analysis and for the lightning performance assessment of a typical Italian distribution line.

4.1. – Statistical evaluation of the lightning performance of distribution lines

4.1.1. – Procedure based on the Monte Carlo method and on the developed LEMP-to-transmission-line coupling models for distribution lines

In the developed procedure lightning-induced voltages are calculated using the proposed models for the LEMP illuminated distribution lines. For our purposes, and in order to reduce the computation time, the wave shape of the return stroke current at the channel base is approximated with a ramp until the peak value Ip is reached at time tf , then the current value is kept constant. The Monte Carlo method is applied to generate a significant number of events (larger than 10÷20⋅103), each characterized by four random variables: the peak value of the lightning current Ip , its front time tf , and the two coordinates of the stroke location.

We assume a correlation coefficient (ρ) between current amplitude and front duration equal to 0.47 [Chowdhuri, 1989b] and the statistical parameters of log-normal distribution of the peak and the front time published in [Anderson and Eriksson, 1980]. The stroke locations are supposed uniformly distributed within a certain surface around the line. The

Page 80: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 4. – Influence of lightning-induced overvoltages on power quality pag.

73

‘striking area’ relevant to the surface that we consider in our study, has to be chosen wide enough to include all the lightning events that can induce a voltage along the line with maximum amplitude greater than the considered insulation level. The maximum dimension of this area (xmax, ymax of Fig. 4.3), is preliminarily determined by evaluating the induced overvoltages due to the maximum lightning current of the statistical distribution at various distances and position from the line.

Fig. 4.3. – Indirect stroke area to overhead line (top view).

The ‘striking area’ does not include the points whose distance from the line is less than

the values dl (lateral attractive distance, see Fig. 4.3). In this study, the expression adopted by the IEEE Working Group on Lightning

performance of transmission lines [IEEE WG on the lightning performance of distribution lines, 1997] is used for the evaluation of the lateral attractive distance dl. Such expression, is based on the ‘Electro-Geometric’ model of the last step of the lightning flash, which gives the following relation between the critical distances (the striking distances to the wire (rs) and to ground (rg)) and the lightning current I [IEEE WG on estimation lightning performance of transmission lines, 1985]):

65.010 Irs ⋅= , sg rr ⋅= 9.0 (4.1)

where rs and rg are expressed in m and the lightning current I in kA. As shown in Fig. 4.4, the value dl is then determined from

( )2g

2sl hrrd −−= (4.2)

Page 81: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 4. – Influence of lightning-induced overvoltages on power quality pag.

74

where h is the line height (in m). If the distance of the stroke location from the line is beyond the lateral distance, the event

is considered an indirect flash and the maximum amplitude of the induced overvoltages is computed.

In order to infer the classical flashover vs BIL curves, for each event we calculate the maximum of the voltage amplitudes induced along the line. Note that we do not limit the calculation to the point closest to the stroke location as done in all procedures which assume an infinitely long line and the ground as a perfect conductor, since for that case the maximum amplitude occurs indeed at that point [Hermosillo and Cooray, 1995]. This because, when the ground is not a perfect conductor, stroke locations close to one of the line terminations can induce the larger overvoltages at the opposite one [de la Rosa et al., 1988]

rs

rg

indirect stroke direct stroke

h dl

Fig. 4.4. – Striking distances to a conductor (rs) and to ground (rg) and lateral attractive distance (dl) of a line.

Adapted from Chowdhuri [1989b]. Then we compute the annual number of events that, for 100 km of line and for a given

ground flash density, induce an overvoltage with amplitude exceeding the various insulation levels of the line. For all calculations the ground flash density is Ng=1 flash/km2/year and, otherwise specified, the line length is 2 km and its height 10 m.

4.1.2. – Comparison with the IEEE Std 1410-1997 A brief description of the IEEE Std 1410 IEEE WG on the lightning performance of

distribution lines, 1997] will be given. Concerning the model used for the calculation of the lightning induced overvoltages, the IEEE Std 1410 adopts the simplified formula presented by Rusck [1958] (hereafter called the Rusck formula). As earlier mentioned that formula has been inferred by the same Rusck from the more general model he proposed in [Rusck, 1958]; it applies to the simple case of a step current and of an infinitely-long single-conductor line above a perfectly conducting ground. It is worth remanding that the Rusck

Page 82: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 4. – Influence of lightning-induced overvoltages on power quality pag.

75

formula (equation (2.24) of the paragraph 2.3) gives the maximum value Vmax (in kV) of the induced overvoltages at the point of the line nearest to the stroke location.

Concerning the statistical procedure used to infer the lightning performance of a distribution line, the IEEE Std 1410 follows the procedure presented in [Chowdhuri, 1989b], which we summarize here for convenience. The amplitude of the stroke current is varied from 1 to 200 kA in intervals of 1 kA. The number of annual insulation flashovers per km of distribution line Fp is obtained as the summation of the contributions from all intervals considered as expressed by

( ) igi

iip PNyyF ⋅⋅−⋅= ∑

=

200

1minmax2 (4.3)

where Ng is the ground flash density and Pi is the probability of current peak to be within interval i; it is determined as the difference between the probability for current to be equal or larger than the lower limit and the probability for current to reach or exceed the higher limit of the interval. For the probabilistic distribution of the lightning current peak, the following expression is adopted [Anderson, 1982]:

( ) kA 20031/1

1)( *6.2*

* ≤+

=≥ pp

pp II

IIP (4.4)

For each current value, ymin and ymax of equation (4.3) are the minimum distance for

which lightning will not divert to the line, and the maximum distance at which the stroke may produce an insulation flashover, respectively. The value of ymin is obtained by expression (4.2). The value of ymax is obtained by solving equation (2.24) for d, by taking Ip as the lower limit of the interval and by taking Vmax = 1.5·CFO. The results for an ungrounded overhead 10 m high line are shown in Fig. 4.5. The value of v in (2.29) is chosen equal to 1.2⋅108 m/s. The results relevant to an ungrounded and grounded neutral or shielding wire are obtained in [IEEE WG on the lightning performance of distribution lines, 1997] from the preceding ones by applying a scale factor of 0.75 to the induced voltages.

Page 83: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 4. – Influence of lightning-induced overvoltages on power quality pag.

76

Fig. 4.5. – Number of annual induced flashovers vs distribution-line insulation level. Taken from IEEE WG on

the lightning performance of distribution lines [1997]. We have first verified that the proposed statistical procedure gives the same results of the

IEEE Std 1410 when the induced voltages are evaluated by using the Rusk formula instead of using LIOV, and when the same probability distribution (4.4) of the lightning current, the same values of return-stroke velocity (v=1.2⋅108 m/s), line height (10 m) and lateral distance expression (4.2) are assumed. Then, we have found that the adoption of the peak distribution of [Anderson and Eriksson, 1980] instead of (4.4) does not have a significant influence on the results.

We have then compared the IEEE Std 1410 guide results of Fig. 4.5 with those obtained by using our procedure (LIOV plus Monte Carlo), assuming the statistical distributions of peak current and rise time of Fig. 2.3 (paragraph 2.1), a 2 km long line (beyond such a line length the line illumination by the LEMP field for a perfectly conducting ground does not affect the results [Borghetti and Nucci, 1999]). The comparison is shown in Fig. 4.6.

Page 84: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 4. – Influence of lightning-induced overvoltages on power quality pag.

77

0.001

0.010

0.100

1.000

10.000

100.000

0 50 100 150 200 250 300CFO [kV]

No.

of i

nduc

ed o

verv

olta

ges

with

mag

nitu

de

exce

edin

g th

e BI

L/(1

00 k

m y

ear)

IEEE Guide

Proposed method

Fig. 4.6. – Comparison between the lightning performance evaluated by using the IEEE Std 1410 procedure

and the proposed one. tf is lognormally distributed with a median value of 3.83 µs. Adapted from Borghetti et al. [2001a].

The difference between our results and those of the IEEE Std 1410 can be explained by

observing that the simplified Rusck formula applies to the case of a step wave shape for the lightning current [Rusck, 1958]. We therefore repeated our computation by keeping constant the value of tf throughout Monte Carlo simulation. Fig. 4.7 shows the results of four different computations relevant to four different values of tf: 0.5, 1, 3 and 5 µs respectively. From Fig. 4.7 we can observe that when tf decrease , the two procedures predict basically the same results.

0.001

0.010

0.100

1.000

10.000

100.000

0 50 100 150 200 250 300CFO [kV]

No.

of i

nduc

ed o

verv

olta

ges

with

mag

nitu

de

exce

edin

g th

e BI

L/(1

00 k

m y

ear)

IEEEProposed method with tf=0.5usProposed method with tf=1usProposed method with tf=3usProposed method with tf=5us

Fig. 4.7. – Comparison between the lightning performances evaluated by using the IEEE Std 1410 procedure

and the proposed one, with different fixed value of tf.

Page 85: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 4. – Influence of lightning-induced overvoltages on power quality pag.

78

4.1.3. – Sensitivity analysis This paragraph describe the results of a sensitivity analysis carried out using the

proposed procedure. In particular we shall deal first with the case of a single conductor line where we analyze the effect of the ground conductivity and the presence of surge arresters along the line. Then for the multi-conductor case we analyze the effect of the grounding resistance of the shielding wire, of the grounding intervals and of the different shielding wire height.

Single conductor line. Since the maximum values of the induced voltage amplitudes

could be higher than for the case of a line above an ideal ground [Guerrieri et al., 1996,1997] for these calculations a larger indirect stroke area is considered. In particular the results refer to a 1 km long overhead line and to a 20 km2 indirect stroke area, with xmax equal to 5 km, ymax equal to 2 km. The relative permittivity of the ground is assumed equal to 10. Since, for line lengths shorter than about 2 km and for ground conductivity not lower than 0.001 S/m, the effect of the lossy ground on surge attenuation along the line is not significant [Rachidi et al., 1996], the presence of a lossy ground in our calculations is taken into account only in the propagation of the incident electromagnetic field.

Fig. 4.8 shows the results obtained with two different ground conductivities, namely σg=0.01 S/m and σg=0.001 S/m. These results are also compared with those obtained with an ideal ground. It can be observed that lower values of ground conductivity result in higher flashover rates, a result which is explained by the fact that, as already mentioned, the ground resistivity enhances the induced voltages depending on the stroke location and on the observation point [Guerrieri et al., 1996,1997].

0.010

0.100

1.000

10.000

100.000

1000.000

0 50 100 150 200 250 300CFO [kV]

No.

of i

nduc

ed o

verv

olta

ges

with

mag

nitu

de

exce

edin

g th

e BI

L/(1

00 k

m y

ear)

ideal ground

lossy ground 0.01 S/m

lossy ground 0.001 S/m

Fig. 4.8. – Effect of the ground conductivity, tf is lognormally distributed with a median value of 3.83 µs.

Page 86: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 4. – Influence of lightning-induced overvoltages on power quality pag.

79

To illustrate the influence of the presence of surge arresters along the line, we have considered the line configuration presented in Fig. 4.9 (we consider, for this case, only common-mode voltages). The surge arresters are represented by the non-linear V-I characteristic given in Tab. 3.1.

Phase conducorh=9m d=1cm

Surge Arrester

Surge Arrester Zc Surge

Arrester Zc

2 km Fig. 4.9. – Line configuration with surge arresters.

As discussed in paragraph 3.1.3 the presence of surge arrester along the line, can be

produce the maximum amplitude of the induced overvoltage not in the point closest to the stroke location. In order to reduce this effect, we have connected, at both line terminations in parallel with the surge arresters, two resistive loads equal to the line characteristic impedance.

The computed results are shown in Fig. 4.10. were we can observe that the presence of surge arresters affects considerably the lightning performance of distribution lines.

0.010

0.100

1.000

10.000

100.000

0 50 100 150 200 250 300CFO [kV]

No.

of i

nduc

ed o

verv

olta

ges

with

mag

nitu

de

exce

edin

g th

e BI

L/(1

00 k

m y

ear)

phase conductor only

phase conductor with 3 SA

Fig. 4.10. – Influence of the presence of surge arresters.

Page 87: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 4. – Influence of lightning-induced overvoltages on power quality pag.

80

Multi conductor line. In this section we first evaluate the lightning performance of a typical three-phase Italian distribution line (see Fig. 4.11). For this purpose we consider a 1.8 km long line matched at both terminations, within an indirect stroke area of 7.6 km2.

10,8 m

a

b

c

1,3 m

10 m

Fig. 4.11. – Geometrical configuration of an Italian MV line.

The calculations have been carried out assuming two different values of ground

conductivity σg (infinite and 0.001 S/m). They are plot in Fig. 4.12, which shows the number of events resulting in overvoltages with amplitude exceeding the value indicated in abscissa. We observe the larger number of overvoltages at phase b than at phases a and c, due to the higher position of the phase b conductor. Note, again, the increase of the number of induced voltages due to the poor ground conductivity.

0.01

0.10

1.00

10.00

100.00

1000.00

0 50 100 150 200 250 300

CFO [kV]

No.

of i

nduc

ed o

verv

olta

ges

with

mag

nitu

de

exce

edin

g th

e BI

L/(1

00 k

m y

ear)

phase a or c with ideal groundphase b with ideal groundphase a or c with lossy groundphase b with lossy ground

Fig. 4.12. – Statistical evaluation of lightning induced voltage in the Italian MV line of Fig. 4.11. Cases for

ideal ground and lossy ground (σg=0.001 S/m). Adapted from Borghetti et al. [2001a].

Page 88: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 4. – Influence of lightning-induced overvoltages on power quality pag.

81

We now consider a 2 km long, two-conductor line (phase conductor and shielding wire) over a perfectly conducting plane, a case similar to the one discussed in [IEEE WG on the lightning performance of distribution lines, 1997]. As shown in Fig. 4.13, the shielding wire is grounded at the line terminations and at intervals along the line. The spacing between two adjacent grounding is 2000 m (2 grs), 1000 m (3 grs), or 400 m (6 grs). The simulations are carried out with the aim of evaluating the influence of the presence of the shielding wire, of its height, of the spacing between two adjacent groundings as well as the value of the grounding resistance.

Shielding Wire

Phase conductor

variable: 2km 1km 0.4km

9m 10

m

1 cm

Rt Rt Rt Rt RtZc Zc

Fig. 4.13. – Line configuration with shielding wire. Fig. 4.14 shows the results relevant to the phase conductor obtained with three different

shielding wire heights, namely 9.7 m, 10 m, 10.4 m. The results are affected by the presence of the shielding wire, but the influence of the shielding wire height for the considered cases is limited.

0.01

0.10

1.00

10.00

100.00

0 50 100 150 200 250 300

CFO [kV]

No.

of i

nduc

ed o

verv

olta

ges

with

mag

nitu

de

exce

edin

g th

e BI

L/(1

00 k

m y

ear)

phase conductor only

6 grs, Hsw=9.7 Rg=10ohm

6 grs, Hsw=10m Rg=10ohm

6 grs, Hsw=10.4 Rg=10ohm

Fig. 4.14. – Influence of shielding wire height. The spacing between to adjacent grounding is 400 m (i.e. 6

groundings overall) and the grounding resistance is equal 10 Ω.

Page 89: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 4. – Influence of lightning-induced overvoltages on power quality pag.

82

a)

0.01

0.10

1.00

10.00

100.00

0 50 100 150 200 250 300

CFO [kV]

No.

of i

nduc

ed o

verv

olta

ges

with

mag

nitu

de

exce

edin

g th

e BI

L/(1

00 k

m y

ear)

phase conductor only

2 grs, Rg=0ohm

2 grs, Rg=10ohm

2 grs, Rg=100ohm

b)

0.01

0.10

1.00

10.00

100.00

0 50 100 150 200 250 300

CFO [kV]

No.

of i

nduc

ed o

verv

olta

ges

with

mag

nitu

de

exce

edin

g th

e BI

L/(1

00 k

m y

ear)

phase conductor only

3 grs, Rg=0ohm

3 grs, Rg=10ohm

3 grs, Rg=100ohm

Page 90: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 4. – Influence of lightning-induced overvoltages on power quality pag.

83

c)

0.01

0.10

1.00

10.00

100.00

0 50 100 150 200 250 300

CFO [kV]

No.

of i

nduc

ed o

verv

olta

ges

with

mag

nitu

de

exce

edin

g th

e BI

L/(1

00 k

m y

ear)

phase conductor only

6 grs, Rg=0ohm

6 grs, Rg=10ohm

6 grs, Rg=100ohm

Fig. 4.15. – Influence of grounding resistance. a) The shielding wire is grounded only at its terminations

(overall 2 grs). b) The spacing between two adjacent grounding is 1 km (overall 3 grs). c) The spacing between two adjacent grounding is 400 m (overall 6 grs).

Fig. 4.15 shows the influence of the grounding resistance (the shielding wire in this case

is at 10 m above ground). Three values of grounding resistance are considered, namely 0, 10 and 100 Ohm. The results do not differ considerably, at least when the number of grounding is low (2 and 3 grs). On the other hand, the spacing between two adjacent grounding appears to have a larger influence, as also illustrated in Fig. 4.16 for a value of grounding resistance of 10 Ohm and a shielding wire height of 10 m.

0.01

0.10

1.00

10.00

100.00

0 50 100 150 200 250 300

CFO [kV]

No.

of i

nduc

ed o

verv

olta

ges

with

mag

nitu

de

exce

edin

g th

e BI

L/(1

00 k

m y

ear)

phase conductor only

2 grs, Rg=10ohm

3 grs, Rg=10ohm

6 grs, Rg=10ohm

Fig. 4.16. – Influence of spacing between adjacent grounding.

Page 91: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 4. – Influence of lightning-induced overvoltages on power quality pag.

84

It has been shown that the shielding wire appears to have a large influence on the performance of the distribution line; additionally, as analyzed for single stroke location in paragraph 3.1.3, the spacing between two adjacent grounding of the shielding wire seems to have the major impact in decreasing the number of induced voltages exceeding a given value, in accordance with the results presented in paragraph 3.1.3.

The results obtained by using the three values of grounding resistance do not differ considerably, at least when the number of grounding is low (2 and 3 grs). On the other hand, the spacing between two adjacent grounding appears to have a larger influence, as also illustrated in Fig. 4.16 for a value of grounding resistance of 10 Ohm and a shielding wire height of 10 m, again, in accordance with the results of paragraph 3.1.3.

4.2. – Case of a typical Italian distribution line To improve the power quality assessment of a distribution line which experience induced

overvoltages, some additional features of the proposed models have been developed and are described in this section. In particular, they are aimed at investigating the effects of two parameters that are not considered in the previous model namely: the steady-state voltage and the change of coupling factor among the line conductors and the ground at the location where flashovers occur.

In the following paragraph the proposed model extensions are described, then an application of procedure is made.

4.2.1. – Model extension The steady-state voltage at industrial-frequency, taken into account both in the generation

procedure of the events and in the overvoltages calculations, is assumed constant, due to the high frequency content and the short duration of the induced voltages.

In the generation procedure of the events, uniformly distributed random values of the phase voltage are generated for one of the three phases; the voltages of the two remaining phases are assumed to form, together with the first one, a positive system for each event.

In the overvoltages calculation, the steady-state values of each phase voltage is taken into account by simply adding it to the incident voltage of equation (2.27). The reason for this is that the current circulating in the line before any lightning event does not effect the amplitude of the induced voltages, and therefore the coupling equations (2.25) and (2.26) remain unvaried.

Another additional feature of the proposed procedure, compared to [Borghetti and Nucci, 1998], is that it takes into account also the change in the coupling factor among the line conductors and the ground at the location where a flashover occurs. We consider each phase-conductor connected to ground through a resistance Rgp at each pole: in normal

Page 92: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 4. – Influence of lightning-induced overvoltages on power quality pag.

85

conditions, the value of Rgp is equal to infinite; when a phase-to-ground flashover occurs at a certain pole, the relevant value of Rgp is set at a value corresponding to the grounding resistance of the specific pole and the fault impedance. With such a model, we are able to investigate up to which extent a flashover at of one phase of the line can affect the overvoltages on the other two conductors . The scattered voltage at the points xp of the phase conductors where the induced voltage exceeds the CFO are calculated by means of

[ ] [ ] [ ]

+⋅= ∫

ihezgpgpp

si (x,z,t)dzEtiRtxv

0

)(),( (4.6)

where ! [igp] is the matrix of the induced currents diverted to ground in correspondence of the

pole (see Fig. 3.1); ! [Rgp] is the diagonal matrix of the phase-to-ground resistances of the poles. We consider that an overvoltage causes a flashover when it exceeds the value of

1.5·CFO. The 1.5 factor is an approximation that accounts for the turn up in the insulation volt-time curve, which is the same criterion proposed by the IEEE Std 1410 [IEEE WG on the lightning performance of distribution lines, 1997].

Fig. 4.17 shows the voltages induced by a lightning event with Ip=40 kA, tf=3 µs, on a typical Italian distribution line (see Fig. 4.11). We consider a 1.8 km long line matched at both terminations and stroke location equidistant to the line termination, 50 m from the line.

The line span between two consecutive poles is 150 m. The electromagnetic field radiated by lightning is calculated assuming the ground conductivity equal to 0.01 S/m. Also, we assume a phase to ground voltage equal to 16 kV on phase b (where the flahover occur) and a resistance Rgp of the poles during a phase to ground flashover equal to 10 Ω.

Figs. 4.17 a÷c shows the behavior of the induced voltage amplitude on phase conductors a, b and c respectively at the various poles. The flashover of phase b at pole 6 at about 2 µs causes a voltage reduction at the same pole, which propagates in both directions along the line. This flashover causes an instant voltage reduction both on phases a and phase c where the flashover does not occur, producing in turn a shielding effect similar to that of a shielding wire.

Page 93: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 4. – Influence of lightning-induced overvoltages on power quality pag.

86

a) Poles

150 kV

112.5 kV

75 kV

37.5 kV

1 2 3 4 5 6 7 8 9 10 11Time [µs]

0

1

2

3

4

5

Poles

150 kV

112.5 kV

75 kV

37.5 kV

1 2 3 4 5 6 7 8 9 10 11

Tim

e [µ

s]

0

1

2

3

4

5

0 kV

b) Poles

200 kV

150 kV

100 kV

50 kV

1 2 3 4 5 6 7 8 9 10 11Time [µs]

0

1

2

3

4

5

Poles

200 kV

150 kV

100 kV

50 kV

1 2 3 4 5 6 7 8 9 10 11

Tim

e [µ

s]

0

1

2

3

4

5

0 kV

c) Poles

160 kV

120 kV

80 kV

40 kV

1 2 3 4 5 6 7 8 9 10 11 Time [µs]

0

1

2

3

4

5

Poles

160 kV

120 kV

80 kV

40 kV

1 2 3 4 5 6 7 8 9 10 11

Tim

e [µ

s]

0

1

2

3

4

5

0 kV

Fig. 4.17. – Voltage amplitude induced on phase b by a lightning event with Ip = 40 kA, tf = 3 µs, stroke location equidistant to the line termination, 50 m from the line of Fig. 4.9. The LEMP is calculated assuming a ground conductivity σg=0.01 S/m. The grounding resistance of the poles Rgp=10 Ω. a) phase a; b) phase b; c)

phase c. Adapted from Borghetti et al. [2001b].

Page 94: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 4. – Influence of lightning-induced overvoltages on power quality pag.

87

4.2.2. – Results In this paragraph we evaluate the lightning performance of the typical Italian distribution

line previously described (see Fig. 4.9). We consider the same line length and indirect stroke area assumed in the paragraph 4.2.1.: 1.8 km long line matched at both terminations, within an indirect stroke area of 7.6 km2, the number of considered events is 2⋅105. The poles are made out of concrete or steel and are assumed to have a grounding resistance Rgp in the range 10-100 Ω. The line span between two consecutive poles is 150 m. The amplitude of the r.m.s. value of the steady-state phase-to-phase voltage is 20 kV and the CFO of the line is 125 kV.

We consider also the pole grounding resistance at those poles of the line where the CFO is exceeded by the induced overvoltages and consequently a flashover occurs. The LEMP is now calculated assuming two different values for the ground conductivity, namely 0.1 S/m and 0.01 S/m.

In Figs. 4.18-4.21 we show the results of the statistical analysis (80000 events overall) carried out on the Italian MV line configuration of Fig. 4.10, for two different values of ground conductivity, and of pole grounding resistance. In particular, they report the expected number of flashovers, distinguishing among one phase to ground, and two or three phases to ground, caused by a single event.

To better assess the importance of taking into account the steady-state voltage in the calculations, in Figs 4.18-4.21 we report also the results for the case in which the steady-state voltage is disregarded.

To better assess the range of influence of the grounding resistance, Fig. 4.22 report the number of flashovers for a fixed value of ground conductivity and three different values of grounding resistances namely 100, 200 and 500 Ω.

0

0.5

1

1.5

phase a phase b phase c bi and/or threephases

Num

ber

of f

lash

over

s / 1

00 k

m /

year

with steady-state voltage

without steady-state voltage

Fig. 4.18. – Number of flashovers along the line, Rgp=10 Ω and σg=0.1 S/m. Adapted from Borghetti et al.

[2001b].

Page 95: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 4. – Influence of lightning-induced overvoltages on power quality pag.

88

0

0.5

1

1.5

2

2.5

3

3.5

phase a phase b phase c bi and/or threephases

Num

ber

of f

lash

over

s / 1

00 k

m /

year

with steady-state voltage

without steady-state voltage

Fig. 4.19. – Number of flashovers along the line, Rgp=10 Ω and σg=0.01 S/m. Adapted from Borghetti et al.

[2001b].

0

0.5

1

1.5

phase a phase b phase c bi and/or threephases

Num

ber

of f

lash

over

s / 1

00 k

m /

year

with steady-state voltage

without steady-state voltage

Fig. 4.20. – Number of flashovers along the line, Rgp=100 Ω and σg=0.1 S/m. Adapted from Borghetti et al.

[2001b].

0

0.5

1

1.5

2

2.5

3

phase a phase b phase c bi and/or threephases

Num

ber

of f

lash

over

s / 1

00 k

m /

year

with steady-state voltage

without steady-state voltage

Fig. 4.21. – Number of flashovers along the line, Rgp=100 Ω and σg=0.01 S/m. Adapted from Borghetti et al.

[2001b]..

Page 96: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 4. – Influence of lightning-induced overvoltages on power quality pag.

89

0

0.5

1

1.5

2

phase a phase b phase c bi and/or threephases

Num

ber

of f

lash

over

s / 1

00 k

m /

year

100 Ohm200 Ohm500 Ohm

Fig. 4.22. – Number of flashovers along the line, Rgp=100-200-500 Ω and σg=0.01 S/m.

As regard the presence of the steady-state voltage, a parameter that is not usually

considered in the literature, we can observe that the taking into account of it results in a larger number of flashovers: 1.5 instead of 1.3 in Figs. 4.18 and 4.20, 3.7 instead of 3.2 in Figs. 4.19 and 4.21. For all cases the average increase of the number of flashovers/100 km/yr obtained taking into account the steady-state voltage is about 15%.

Concerning the line geometry influence, we can observe the larger number of ground flashovers at phase b than at the two others phases, independently of the steady-state voltage. This is a consequence of the higher position of phase b (see also Fig. 4.11).

Concerning the increase of the pole grounding resistance we observe that produces, in general, an increase of the number of simultaneous faults to ground (two or three phases). The shielding effect produced by the phase where a flashover occurs tends in fact to decrease with the increase of the grounding resistance [Paolone et al., 2000]. The value of the poles grounding resistance starting from which this effect becomes important is of about 100÷200 Ω.

Page 97: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 5. – Conclusions pag.

90

Chapter 5. – Conclusions Aims of this thesis are 1. – the development of models and their implementation in a

computer programs for an accurate estimation of the lightning-induced overvoltages on distribution power networks, and their test against experimental results; 2. – the improved assessment of the lightning performance of distribution systems in view of the solution of power quality problems.

In what follows are summarized the contributions of this thesis thought to be original. Development of a complex overhead line model illuminated by external electromagnetic

field. We have developed an overhead line model, based on a modification of the Agrawal coupling model, originally introduced for the calculation of lightning-induced voltages on uniform lines, to take into account the presence of overhead line transverse discontinuities, such as those caused by periodically grounded shielding wires and surge arresters.

For solving the proposed model equations, we have proposed a 2nd order FDTD integration scheme. The developed integration scheme applies to multi-conductor lines above a frequency-dependent lossy ground. It has been compared with a similar one, also developed within the framework of this thesis, based on the 1st order FDTD integration scheme, and it has been shown to be numerically more stable when considering frequency-dependent parameters and/or non-linearities like surge arresters.

Compared to similar models developed in the literature, which consider the shielding wire at ground potential at any point along it and at any time, the proposed model permits a more accurate evaluation of the lightning-induced voltages. The developed model allows to evaluate the induced overvoltages on overhead lines above a lossy ground taking into account the resistance of the groundings and the spacing between the groundings of shielding wires. This feature is determinant if one has to found the ‘optimal’ distance between two adjacent groundings of the shielding wire.

Its experimental validation has allowed to show its adequacy. The proposed model has in fact been tested and validated versus experimental results obtained using a reduced scale multi-conductor line model illuminated by an EMP simulator. The model was given different line geometries of the conductors and of the groundings of the shielding wire.

Analysis of the effect of shielding wires and surge arresters on lightning-induced

overvoltages. The performed sensitivity analysis has shown that in the mitigation effect of the shielding wire the number of groundings plays a decisive role: the mitigation effect has been found to be more dependent on the number of groundings than on the value of the grounding resistance, both in the case of lossy ground and of ideal ground. This differs from

Page 98: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 5. – Conclusions pag.

91

the case of direct strokes, for which the effectiveness of the shielding wire depends strongly on the grounding resistance.

For the cases of an ideal ground, the mitigation effect as predicted by the Rusck formula has been analyzed too, and the results have shown that the Rusck simplified formula tends to overestimate the effectiveness of the shielding wires. It is worth reminding that the Rusck expression does not cover the case of multiple grounded shielding wire (it assumes that the shielding wire is grounded at single point along the line) and that is applicable only in the assumption of perfectly conductive ground.

Concerning the effectiveness of surge arresters, it depends strongly on their number and position along the line. An ‘optimum’ number appears, for the considered case, one surge arrester each 200 m.

Development of a distribution power system model. In order to simplify the achievement

of the LEMP response of distribution systems, the developed line model has been interfaced with the Electromagnetic Transient Program (EMTP96). Such an interface is based on the use of a Bergeron loss less line which makes it possible the data exchange between the two programs (LIOV and EMTP96). In addition, as opposed to [Nucci et al. 1994], the developed interface does not require any modification of the source code of the EMTP96 because it use a Dynamic Link Library (DLL) called from the EMTP96-TACS environment. Compared to other ones proposed in the literature, allows also for the treatment of the corona phenomenon as opposed to [Orzan et al.,1996; Orzan, 1998], and line losses not dealt with in the interface of Høidalen [1997,1999].

The advantages of merging the developed line model with the EMTP96 consists essentially in the fact that (i) distribution systems of any complex configurations can be modeled (the only limit being the memory of the computer and of EMTP96) and (ii) all power component models of the EMTP library become available for lightning-induced voltage simulations.

Calculations performed with the developed LIOV-EMTP96 program have been compared with experimental results obtained by using a reduced-scale distribution line model described in [Piantini and Janiszewski, 1992, Nucci et al., 1998]. The comparison regards an overhead distribution system including surge arresters, shielding wire groundings and shunt capacitors. Overall, the agreement between the numerical results and measurements is quite satisfactory. We can conclude that LIOV-EMTP96 program represent a promising tool for the analysis of the response of a complex distribution system to indirect lightning discharge.

Estimation of the lightning performance of complex overhead distribution lines. We

have developed a procedure based on the LEMP-illuminated distribution system model, and

Page 99: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 5. – Conclusions pag.

92

on the Monte Carlo method that allows an improved evaluation of the lightning performance of distribution networks.

Such a procedure has been compared with the one proposed in the IEEE Std 1410-1997 for the same purpose: it has been shown that for those cases in which a comparison is possible (overhead single-wire line above a perfectly conducting ground, step function for the channel base current wave shape) the two methods predict basically the same results. Additionally, opposed to the IEEE procedure, the proposed one allows to take into account the ground resistivity, which plays a fundamental role in the calculation of the lightning electromagnetic field that excites the line, as well as any line configuration which may include the presence of shielding wire and surge arresters.

The results obtained show that the shielding wire appears to have a large influence on the performance of the distribution line; additionally, as analyzed for single stroke location, the spacing between two adjacent grounding of the shielding wire, seems to have the major impact in decreasing the number of induced voltages exceeding a given value.

Additional features of the proposed procedure have been developed in order to take into account the steady-state voltage and the change of coupling factor among the line conductors and the ground at the location where flashovers occur, which allows to estimate type of flashovers and the effective number of failures.

The procedure has been eventually applied for assessing the lightning performance of a typical Italian distribution line. The results obtained show that, in general, taking into account the steady-state voltage results in a larger number of flashovers, and that the increase of the pole grounding resistance produces, in general, an increase of the number of simultaneous faults to ground (two or three phases): the phase where a flashover occurs produces in fact the same shielding effect as a shielding wire; such effect tends to decrease with the increase of the pole grounding resistance.

Future possible development of the research. As mentioned at the beginning of chapter 4, although there is some evidence that

electrical distribution systems located in regions at high isoceraunic level are somewhat more affected by voltage sags, there is however no clear evidence that lightning is the main cause for these voltage sags.

An attempt to correlate indirect lightning activity with circuit breaker operation which, in turn, depend on voltage sags, is described in [Bernardi et al., 1998] who carried out a study to infer the possible correlations between lightning indirect events and breaker interventions. They used on the one hand the lightning current amplitude and stroke location coordinates provided by the Italian lightning location system (SIRF – Sistema Italiano di Rilevamento Fulmini), and on the other hand the simplified Rusck equation to calculate the corresponding lightning-induced overvoltage. The correlation they found between lightning events and circuit breakers operations was poor.

Page 100: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Chapter 5. – Conclusions pag.

93

An explanation of this result, which is in part in contradiction with experimental observations [Boonseng and Kinnares, 2001], may be the fact that the Rusck simplified coupling model was adopted without considering the distribution system complexity and the important parameters that modify, in a decisive way, the LEMP response of the distribution system (e.g. the ground conductivity and power system configuration).

We expect that, as compared with the above mentioned study, the use of LIOV-EMTP can improve the LEMP calculation, the evaluation of the coupling by means of realistic line models and eventually the evaluation of entire distribution system response.

We think that the models developed in this thesis represent an improved tool for performing the indirect lightning correlation with distribution system a-periodic disturbances, as well as for the distribution networks protection and insulation coordination, and power quality improvement.

Page 101: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

References pag.

94

References

Agrawal A.K., Price H.J., Gurbaxani S.H., “Transient response of a multiconductor transmission line excited by a nonuniform electromagnetic field”, IEEE Trans. on EMC, Vol. EMC-22, No. 2, pp. 119-129, May 1980.

Amstrong H.R., Whitehead E.R., “Field and Analytical Studies of Transmission Lines Shielding”, IEEE Trans. on PAS, Vol.87, pp.270-281, January 1968.

Anderson J.G., “Lightning performance of transmission lines”, Transmission Line reference Book, 345 kV and above, Electric Power research Institute, ch. 12, 1982.

Anderson R.B., Eriksson A.J., “Lightning parameters for engineering application”, Electra, No. 69, 1980.

Arreghini F., Ianoz M., Zweiacker P., Giri D.V., Tehori A., “SEMIRAMIS: an asymmetrical bounded wave EMP simulator with a good confinement inside the transmission line”, Proc of the 10th Int. Symposium on Electromagnetic Compatibility, Zurich, March,1993.

Barker P.P., Mancao R.T., Kvaltine D.J., Parrish D.E., “Characteristics of lightning surges measured at metal oxide distribution arresters”, IEEE Trans. on PD, Vol. 8, No. 1, January 1993.

Beierl O., “Lightning current measurements at the Peissenberg tower”, 7th ISH, ref. 81.02, Dresden, 1991.

Beierl O., “Front shape parameters of negative subsequent strokes measured at the Peissenberg tower”, Proc of the 21st International Conference on Lightning Protection, Berlin, September 21-25, 1992.

Berger K., “Messungen und resultate der Blitzforschung der Jahre 1947-1954 auf dem M.S. Salvatore”, Bull. SEV Bd 46, No. 5 and 9, 1955.

Berger K., “Methoden und Resultate der Blitzforschung auf dem Monye San Salvatore bei Lugano in dem Jahr 1963-1971”, Bull. SEV, Bd. 63 , No. 24, pp. 1403-1422, 1972.

Berger K., Anderson R.B., Kroninger H., “Parameters of lightning flashes”, Electra, No. 41, 1975.

Bermudez J.L., Rubinstein M., Rachidi F., Paolone M., “A method to find the reflection coefficients at the top and bottom of elevated strike objects from measured lightning currents”, Proc. of the 14th International Zurich Symposium and Technical Exhibition on Electromagnetic Compatibility February 20-22 2001, Zurich Switzerland.

Bernardi M., Dellera L., Garbagnati E., Sartorio G., “Leader progression model of lightning: updating of the model on the basis of recent test results”, Proc. of the International Conference on Lightning Protection, Florence, pp. 399-407, 1996.

Bernardi M., Giorni C., Biscaglia V., “Medium voltage line faults correlation with lightning events recorded with the Italian LLP system ‘CESI-SIRF’ Proc. of the International Conference on Lightning Protection 24th ICLP, Birmingham, UK, 1998.

Bewley L.V., “Traveling waves due to lightning”, Transactions A.I.E.E., Vol. 48, pp. 1050-1064, July 1929.

Bollen M.H.J., “Characterization of voltage sags experienced by three-phase adjustable-speed drives”, IEEE Transactions on PD, Vol.12, no.4, pp.1666-1671, October 1997.

Boonseng C., Kinnares V., “Analysis of harmonic for 12-pulse converter under unbalanced voltage operation due to lightning related voltage sags and short interruption”, IEEE Power Engineering Society Winter Meeting, pp: 1009 –1014, vol.3, 2001.

Borghetti A., Nucci C.A., “Estimation of the frequency distribution of lightning induced voltages on an overhead line above a lossy ground: a sensitivity analysis”, Proc. of the 24th International Conference on Lightning Protection, Birmingham, UK, 1998.

Borghetti A., Nucci C.A., “Frequency distribution of lightning induced voltages on an overhead line above a lossy ground”, Proc. of SIPDA, San Paulo, Brazil, 1999.

Borghetti A., Nucci C.A., Paolone M., Rachidi F., "Characterization of the Response of an Overhead Line to Lightning Electromagnetic Fields", Proc of the 25th International Conference on Lightning Protection, , Rhodos, Greece, September 2000. Correction: Cigré WG 33.02 meeting, Bologna, Sept. 2000a.

Page 102: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

References pag.

95

Borghetti A., Nucci C.A., Paolone M., Bernardi M., ”Effect of the lateral distance expression and of the presence of shielding wires on the evaluation of the number of lightning induced voltages”, Proc. of the 25th International Conference on Lightning Protection 18-22 September, Rhodes Greece, 2000b.

Borghetti A., Nucci C.A., Paolone M., “Guasti a terra nelle linee MT prodotti da fulminazioni indirette”, (in Italian), L’Energia Elettrica, pp. 40-43,gennaio-febbraio 2000c.

Borghetti A., Nucci C.A., Paolone M., “Lightning performances of distribution lines: sensitivity to computational methods and to data”, Power Engineering Society Winter Meeting, 2001 IEEE , Volume: 2 , pp 796 –798, 2001a.

Borghetti A., Nucci C.A., Paolone M., “Statistical Evaluation of Lightning Performances of Distribution Lines”, Proc. of the 5th Int. Conf. on Power System Transients, Rio de Janeiro, June 2001b.

Borghetti A., Nucci C.A., Paolone M., “Valutazione statistica dei guasti a terra nelle linee MT prodotti da sovratensioni indotte da fulminazioni indirette”, (in Italian), L’Energia elettrica, vol.78, pp. 1-6, 2001c.

Carson J.R., “Wave propagation in overhead wires with ground return”, Bell System Technical Journal, 5, 539-554, 1926.

Chang J.S., Janischewskyj W., Hussein A.M., Chisholm W.A., Dziurewicz P., Kawasaki Z.I., Matsmuura K., “Lightning environment at the Toronto 555 m AGL CN telecommunication tower under severe weather conditions”, proc of the International Aerospace and Ground Conference on Lightning and Static Electricity, October, Atlanta, New Jersey, 1992.

Chowdhuri P., Gross E.T.B., “Voltages induced on overhead multiconductor lines by lightning strokes”, Proc. IEE, Vol. 116, No. 4, pp. 561-565, April 1969.

Chowdhuri P., “Analysis of lightning induced voltages on overhead lines”, IEEE Transactions on Power Delivery, Vol. 4, No. 1, pp. 479-492, January 1989a.

Chowdhuri P., “Estimation of flashover rates of overhead power distribution lines by lighting strokes to nearby ground”, IEEE Transactions on PWDR, Vol. 4, No. 3, pp. 1982-1988, July 1989b.

Chowdhuri P., “Lightning-induced voltages on multiconductor overhead lines”, IEEE Transactions on Power Delivery, vol. 5, no. 2, April 1990, pp. 658-667.

Cinieri E., Fumi A., “Sulle sovratensioni indotte dal fulmine nelle linee elettriche d'energia”, (in Italian), L'Energia elettrica, No. 9, 1978.

Cinieri E., Fumi A., “Effetto della presenza di più conduttori e di funi di guardia sulle sovratensioni atmosferiche indotte nelle linee elettriche”, (In Italian), L'Energia elettrica, No. 11-12, 1979.

Cooray V., Lundquist S., “On the characteristics of some radiation fields from lightning and their possible origin in positive ground flashes”, Journal of Geophysical Research, 87:11,203-11,214, 1982.

Cooray V., Lundquist S., “Characteristics of the radiation fields from lightning in Sri Lanka in the Tropics”, Journal of Geophysical Research, 90:6099-6109, 1985.

Cooray V., De la Rosa F., “Shapes and amplitudes of initial peaks of lightning-induced voltage in power lines over finitely conducting earth: theory and comparison with experiment”, IEEE Trans. on AP, Vol. AP-34, No. 1, Jan. 1986.

Cooray V., “Horizontal fields generated by return strokes”, Radio Science, Vol. 27, No. 4, pp. 529-537, July-August 1992.

Cooray V., “A model for subsequent return strokes”, Journal of Electrostatics, 30, pp. 343-354, Elsevier, 1993.

Cooray V., “Calculating lightning-induced overvoltages in power lines: a comparison of two coupling models”, IEEE Trans. on EMC, in press 1994.

Cooray V., “Predicting the spatial and temporal variation of electromagnetic fields, currents, and speeds of subsequent return strokes”, IEEE Trans. on EMC, Vol. 40, pp. 427-435, 1998a.

Cooray V., “Some considerations on the ‘Cooray-Rubinstein’ approximation used in deriving the horizontal electric field over finitely conducting ground”, Proc. of the 24th Int. Conf. on Lightning Protection, pp. 282-286, Birmingham, Sept., 1998b.

Cooray V., Schuka V., “Lightning-induced overvoltages in power lines: validity of various approximations made in overvoltage calculations”, IEEE Trans. on EMC, 1998c.

Page 103: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

References pag.

96

Correia de Barros M.T., Borges da Silva J.F., “A non-linear propagation algorithm for transmission lines”, Proc. 8th Power Sistems Comp. Conf., pp. 772-776, Butterworths, 1984.

Correia de Barros M.T., “Efeito coroa em linhas de transporte de energia”, Ph.D. Thesis, IST-Technical University of Lisbon, 1985.

Correia de Barros M.T., Festas J., Nucci C.A., Rachidi F., “Corona on Multiconductor Overhead Lines Illuminated by LEMP”, Proc. of the 3rd Int. Conf. On Power System Transients, Budapest, June 20-24, 1999.

Darveniza M., Uman M.A., “Research into lightning protection of distribution systems II - results from Florida field work 1978 and 1979”, IEEE Transactions on PAS, Vol. 103, No. 4, April 1984.

de la Rosa F., Valdiviva R., Pérez H., Loza J., “Discussion about the inducing effects of lightning in an experimental power distribution line in Mexico”, IEEE Trans. on PWDR, Vol. 3, No. 3, pp. 1080-1089, July 1988.

de la Rosa F., Perez H.R., Galvan A.D., “Lightning-induced voltage measurements in an experimental power distribution line in Mexico”, Proc. of the 22nd International Conference on Lightning Protection, Budapest, 19-23 September, 1994.

Dellera L., Garbagnati E., “Lightning stroke simulation by means of the leader progression model, Parts I and II”, IEEE Trans. on PWRD, Vol. 5, No. 4, pp. 2009-2029, October 1990.

Diendorfer G., “Induced voltage on an overhead line to nearby lightning”, IEEE Transaction EMC, Vol. 32, No. 4, pp. 292-299, November 1990.

Diendorfer G., Uman M.A., “An improved return stroke model with specified channel-base current”, Journal of Geophysical Research, Vol. 95, No. D9, pp. 13621-13644, August 20, 1990.

Djebari B., Hamelin J., Leteinturier C., Fontaine J., “Comparison between experimental measurements of the leectromagnetic field emitted by lightning and different theoretical models. Influence of the upward velocity of the return stroke”, Proc. of the 4th International Symposium and Technical Exhibition on Electromagnetic Compatibility, Zürich, 1981.

Dorr D.S., “Point of utilization power quality study results”, IEEE Trans. on IA, Vol.: 31 Issue: 4, pp 658 –666, July-Aug. 1995.

Dugan R., McGranaghan M.F., Beaty H.W., “Electrical Power Systems Quality”, Mc Graw-Hill 1996

Eriksson A.J., ”The measurement of lightning and tunderstorm parameters”, C.S.I.R. special Report, Elek. 51, Pretoria, 1974.

Eriksson A.J., “Lightning and tall structures”, Trans. South Afr. IEE, 69 (Pt. 8): 238-252, 1978.

Eriksson A.J., Meal D.V., “Lightning performance in rural distribution line: preliminary results”, Trans. SAIEE, Vol. 71, pp.158-163, 1980.

Eriksson A.J., Meal D.V., “Lightning performance and over-voltage surge studies on a rural distribution line”, Proc. IEE, 129C, pp. 59-69, 1982.

Eriksson A.J., Stringfellow M.F., Meal D.V., “Lightning-induced overvoltages on overhead distribution lines”, IEEE Trans. on PAS, Vol. PAS-101, No. 4, pp. 960-968, April 1982.

Eriksson A.J., “An improved electrogeometric model for transmission line shielding analysis”, IEEE Trans. on PWRD, Vol. 2, pp. 871-886, July 1987.

Fernandez, M.I.; Rakov, V.A.; Uman, M.A., “Transient currents and voltages in a power distribution system due to natural lightning”, Transmission and Distribution Conference, IEEE, pp: 691 -699 vol.2, 1999a.

Fernandez, M.I.; Rambo, K.J.; Rakov, V.A.; Uman, M.A., “Performance of MOV arresters during very close, direct lightning strikes to a power distribution system”, IEEE Trans. on PD, Vol. 14 Issue: 2, pp: 411 –418, April 1999b.

Fieux R.P., Gary C.H., Hutzler B.P., Eybert-Berard A.R., Hubert P.L., Meesters A.C., Perrond P.H., Hamelin J.G., Person J.M., “Research on artificially triggered lightning in France”, IEEE Trans. on PAS, Vol. 97, pp. 725-733, 1978.

Fisher R.J., Uman M.A., “Measured electric fields risetimes for first and subsequents lightning return strokes”, Journal of Geophysical Research, 77:399-407, 1972.

Page 104: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

References pag.

97

Garbagnati E., Lo Piparo G.B., “Stazione sperimentale per il rilievo delle caratteristiche dei fulmini”, (in Italian), L'Elettrotecnica, Vol. LVII, No. 7, pp. 388-397, 1970.

Garbagnati E., Lo Piparo G.B., “Nuova stazione automatica per il rilievo delle caratteristiche del fulmine”, (in Italian), L'Energia Elettrica, No. 6, pp. 375-383, 1973.

Garbagnati E., Lo Piparo G.B., Marinoni F., “Parameters of lightning currents. Interpretation of results obtained in Italy”, Proc of the 15th International Conference on Lightning Protection, Sgedez, September 1980.

Garbagnati E., Lo Piparo G.B., “Parameter von Blitzstromen”, (in German), ETZ a), Vol. 103, No. 2, 1982.

Gary C., Dragan G., Cristescu D., “Atténuation de propagation des surtensions sous l'influence de l'effet de couronne”, CIGRE, Paris, paper 33-13, 1978.

Geldenhuys H., Eriksson A.J., Bourn G., “Fifteen years data of lightning current measurements on a 60 m mast”, Proc. of the 19th International Conference on Lightning Protection, Graz, ref. 1.7, pp. 451-456, 1988.

Georgiadis N., Rubinstein M., Uman M.A., Medelius P.J., Thomson E.M., “Lightning-induced voltages at both ends of a 488-m power distribution line”, IEEE Trans. on EMC, Vol. 34, No. 4, November 1992.

Golde R.H., “Lightning surges on overhead distribution lines caused by indirect and direct lightning strokes”, AIEE Transaction, Vol. 73, pp. 437-447, 1954.

Gomes C, Cooray V., “Concepts of Lightning Return Stroke Models”, IEEE Trans. on EMC, Vol. 42, No. 1, February 2000.

Gorin B.N., Shkilev A.V., “Measurements of lightning currents at the Ostankino tower” (in Russian), Elektrichestvo, No. 8, 1984.

Guerrieri S., Nucci C.A., Rachidi F., Rubinstein M., “On the influence of elevated strike objects on the lightning return stroke current and the distant electric field”, Proc of the International Symposium on EMC, Rome, September 13-16, 1994.

Guerrieri S., Ianoz M., Mazzetti C., Nucci C.A., Rachidi F., “Lightning-induced voltages on an overhead line above a lossy ground: a sensitivity analysis”, Proc. of 23rd International Conference on Lightning Protection (ICLP), Florence, Italy, 23-27 Sept. 1996.

Guerrieri S., “Sovratensioni indotte da fulminazioni indirette su linee di distribuzione. Modellazione ed analisi” (In Italian), PhD Thesis, University of Bologna, February 1997.

Guerrieri S., Nucci C.A., Rachidi F., “Influence of the ground resistivity on the polarity and intensity of lightning induced voltages”, Proc. of the 10th International Symposium on High Voltage Engineering, Montréal, Canada, 25-29, 1997.

Gutierrez J.A.R., Paolone M., Borghetti A., Nucci C.A., Petrache E., Rachidi F., “Lightning-Induced Overvoltage Calculation in Matlab Environment”, Proc. of the International Symposium on Power Quality SICEL 2001, 28-30 Nov. 2001, Bogotà, Colombia.

Gunther E.W. and Mehta H., “A survey of distribution system power quality-preliminary results”, IEEE Trans. on PD, Volume: 10 Issue: 1, pp 322 -329, Jan. 1995.

Hamelin J., Djebari B., Barreau R., Fontaine J., “Electromagnetic field resulting from a lightning discharge, surges induced on overhead lines, mathematical model”, Proc. of the Int. Symp. on Electromagnetic Compatibility, Rotterdam, May 1979.

Heidler F., “Analytische Blitzstromfunktion zur LEMP- Berechnung“, (in German), paper 1.9, pp. 63-66, Munich, September 16-20, 1985a.

Heidler F., “Traveling current source model for LEMP calculation”, Proc of the 6th Symposium and Technical Exhibition on Electromagnetic Compatibility, Zurich, March 5-7, 1985b.

Heidler F., Hopf C., “Lightning current and lightning electromagnetic impulse considering current reflection at the hearth's surface”, Proc. of the Int. Conf. on Lightning Protection, paper R 4-05, Budapest, 1994.

Hermosillo V.F., Cooray V., “Calculation of fault rates of overhead power distribution lines due to lightning induced voltages including the effect of ground conductivity”, IEEE Trans. on EMC, vol. 37, no. 3, pp. 392-399, August 1995.

Page 105: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

References pag.

98

Høidalen H.K.,“Lightning-induced overvoltages in low-voltage systems”, PhD Thesys, Norwegian University of Science and Technology, 1997.

Høidalen H.K.,“Calculation of lightning-induced overvoltages using MODELS”, Proc. of the International Conference on Power Systems Transients., Budapest, Hungary, pp. p.359-64,1999.

IEEE Working Group on Estimation Lightning Performance of Transmission Lines, “Estimating lightning performance of transmission lines II – Updates to analytical models”, IEEE Trans. on PWDR, Vol. 8, No. 3, pp. 1254-1267, July 1993.

IEEE Working Group on Estimation Lightning Performance of Transmission Lines, “A Simplified Method for Estimating Lightning Performance of Transmission Lines”, IEEE Trans. on PAS, Vol. 104 No.4, pp 919-932, April 1985.

IEEE Working Group on the lightning performance of distribution lines, “Guide for improving the lightning performance of electric power overhead distribution lines”, IEEE Std 1410, 1997.

Imai Y., Michishita K., Ishii M., Kawamura T., “Analysis of lightning-induced voltages on multiconductor power distribution lines taking into account of finite ground conductivity”, (in Japanese), Trans. IEE Japan, Vol. 113-B, No. 5, 1993.

Iorio R., Nucci C.A., Porrino A., Rachidi F., “Lightning-induced overvoltages on distribution overhead lines in presence of distribution transformers or short cables”, Proc. CIGRE Symp. “Power system electromagnetic compatibility”, Lausanne, October 18-20, 1993.

Ishii M., Michishita K., Hongo Y., Ogume S., “Lightning-induced voltage on an overhead wire dependent on ground conductivity”, IEEE Trans. on PD, Vol. 9, No. 1, pp. 109-118, January 1994.

Janischewskyj W., Hussein A.M., Chisholm W.A., Chang J.S., Kawasaki Z.I., Dziurewicz P., “Comprehensive measurement of lightning strokes to the CN Tower in Toronto”, Proc. of the 9th International Conference on Atmospheric Electricity 1992, Vol. III, pp. 910-913, St. Petersburg, Russia, June 15-19 1992.

Janischewskyj W., Hussein A.M., Shostak V., Dzurevych P., Chisholm W.A., “Analysis of Electromagnetic fields from lightning strikes to the Toronto CN Tower and from lightning in the surrounding area”, Proc. of the CIGRE Symp. "Power system electromagnetic compatibility", Lausanne, Switzerland, October 18-20, 1993.

Janischewskyj W., Hussein A.M., Dzurevych P., Shostak V., Chisholm W.A., “Characterization of the current wavefront parameters of lightning strikes to the CN Tower in Toronto”, Proc of the 8th Int. Symp. on High Voltage Engineering, paper No. 70a, Yokohama, Japan, August 23-37, 1994.

Jankov V., Grzybowski S., “Flashover rates of overhead distribution lines caused by nearby lightning strokes”, Proc. of the 10th International Symposium on high Voltage Engineering (ISH’97), Montréal, Canada, August 25-29 1997.

Johnk C.T.A., “Engineering electromagnetic field and waves”, John Wiley and Sons, 1975.

Koga H., Motomitsu T., Taguchi M., “Lightning surge waves induced on overhead lines”, The transactions of the IECE of Japan , Vol E 62, No. 4, pp. 216-223, April 1979.

Koga H., Motomitsu T., Taguchi M., “Lightning surge waves induced in transmission lines”, Review of the Electrical Communication Laboratory, Vol. 29, pp. 797-810, 1981.

Krider E.P., Guo C., “The peak electromagnetic power radiated by lightning return strokes”, Journal of Geophysical Research, 88:8471- 8474, 1983.

Lax P.D., Wendroff B., “System of conservations laws”, Comm. Pure Apl. Math., Vol. 13, pp. 217-237, 1960.

Leteinturier C., Wideman C., Hamelin J., “Current and electric field derivatives in triggered lightning return strokes”, Journal of Geophysical Research, Vol. 95, No. D1, pp. 811-828, January 1990.

Liew A.C., Mar S.C., “Extension of the Chowdhuri-Gross model for lightning induced voltage on overhead lines”, IEEE Trans. on PWDR, Vol. 1, No. 2, pp. 240-247, April 1986.

Lin Y.T., Uman M.A., “Electric radiation fields on lightning return strokes in three isolate Florida thunderstorms”, Journal of Geophysical Research, 78:7911-7914, 1973.

Lin Y.T., Uman M.A., Tiller J.A., Brantley R.D., Beasley W.H., Krider E.P., Weidman C.D., “Characterization of lightning return stroke electric and magnetic fields from simultaneous two-station measurements”, Journal of Geophysical Research, Vol. 84, pp. 6307-6314, 1979.

Page 106: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

References pag.

99

Lin Y.T., Uman M.A., Standler R.B., “Lightning return stroke models”, Journal of Geopysical Research, Vol. 85, No. C3, March, 1980.

Lundholm R., “Induced overvoltages surges on transmission lines and their bearing on the lighting performance at medium voltage networks”, Transactions of Chalmers University of Technology, No. 188, Gothenburg, Sweden, 1957.

Master M.J., Uman M.A., Lin Y.T., Standler R.B., “Calculations of lightning return stroke electric and magnetic fields above ground”, Journal of Geophysical Research, Vol. 86, No. C12, December 1981.

Master M.J., Uman M.A., “Transient electric and magnetic fields associated with establishing a finite electrostatic dipole”, Am. Jour. of Physics, No. 51, pp. 118-126, 1983.

Master M.J., Uman M.A., “Lightning induced voltages on power lines: Theory”, IEEE Transactions on PAS, Vol. 103, No. 9, pp. 2502-2518, September 1984.

Master M.J., Uman M.A., Beasley W.H., Darveniza M., “Lightning induced voltages on power lines: Experiment”, IEEE Tran. on PAS, Vol. 103, No. 9, pp. 2519-2529, September 1984.

Mata C.T., Fernandez M.I., Rakov V.A.; Uman M.A., “EMTP modeling of a triggered-lightning strike to the phase conductor of an overhead distribution line”, IEEE Trans on PD, vol.15, no.4; p.1175-81.Oct. 2000.

McDonald T.B., Uman M.A., Tiller J.A., Beasley W.H., “Lightning location and lower-ionosphere height determination from two-station magnetic field measurements”, Journal of Geophysical Research, 84:1727-1734, 1979.

Michishita K., Ishii M., Kawamura T., “Analysis of lightning-induced voltage taking account of horizontal electric field”, (in Japanese), Trans. IEE Japan, Vol. 111-B, No. 6, 1991.

Michishita K., IshiiM. I, “Lightning-induced voltage on overhead wire over perfectly conducting ground associated with tilted lightning strokes”, (in Japanese), Trans. IEE Japan, Vol. 112-B, No. 6, 1992.

Montandon E., Beyeler B., “The lightning measuring equipment on the Swiss PTT telecommunications tower at St. Chrischona, Switzerland”, Proc. of the 22nd International Conference on Lightning Protection, Budapest, 19-23 September, 1994.

Norinder H., “Some recent tests on the investigation of induced surges”, CIGRE, paper 303, Paris, 1936.

Nucci C.A., Mazzetti C., Rachidi F., Ianoz M., “On lightning return stroke models for LEMP calculations”, Proc. of the 19th International Conference on Lightning protection, Graz, April 1988.

Nucci C.A., Rachidi F., “Experimental validation of a modification to the Transmission Line model for LEMP calculations”, Proc. of the 8th International Symposium and Technical Exhibition on Electromagnetic Compatibilty, pp. 389-394, Zurich, 7-9 March, 1989.

Nucci C.A., Diendorfer G., Uman M.A., Rachidi F., Mazzetti C., “Lightning return-stroke models with channel-base specified current: a review and comparison”, Journal of Geophysical Research, Vol. 95, No. D12, pp. 20395-20408, November 1990.

Nucci C.A., Rachidi F., Ianoz M., Mazzetti C., “Lightning-induced overvoltages on overhead lines”, IEEE Trans. on EMC, Vol. 35, No. 1, pp. 75-86, February 1993.

Nucci C.A., Bardazzi V., Iorio R., Mansoldo A., Porrino A., “A code for the calculation of Lightning-Induced Overvoltages and its interface with the Electromagntic Transient Program”, Proc. of the 22nd International Conference on Lightning Protection, Budapest, Hungary, 19-23 September, 1994.

Nucci C.A., Rachidi F., “On the contribution of the electromagnetic field components in field-to-transmission lines interaction”, IEEE Trans. on EMC, Vol. 37, No. 4, pp. 505-508, Nov. 1995.

Nucci C.A., Borghetti A., Piantini A., Janiszewski J.M., “Lightning-induced voltages on distribution overhead lines: comparison between experimental results from a reduced-scale model and most recent approaches”, Proc. of the 24th International Conference on Lightning Protection, Birmingham, UK, 1998.

Nucci C.A., “The Lightning Induced Over-Voltage (LIOV) code”, Power Engineering Society Winter Meeting 2000. IEEE vol. 4 , pp: 2417 –2418, 2000.

Nucci C.A., Guerrieri S., Correia de Barros M.T., Rachidi, F., “Influence of Corona on the Voltages Induced by Nearby Lightning on Overhead Distribution Lines”, IEEE Trans. on PD, Vol. 15, Issue: 4, pp 1265 -1273, Oct. 2000.

Page 107: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

References pag.

100

Omick S. R., Castillo S.P., “A New Finite Difference Time-Domain Algorithm for the Accurate Modeling of Wide-Band Electromagnetic Phenomena”, IEEE Trans. on EMC, Vol. 35, No. 2, pp 215-222, May 1993.

Orzan D., Baraton P., Ianoz M., Rachidi F., “Comparaison entre deux approches pour traiter le couplage entre un champ EM et des réseaux de lignes”, 8ème Colloque International sur la Compatibilité Electromagnétique, Lille, 2-5 Septembre 1996.

Orzan D., “Couplage externe et interne entre un champ electromagnetique et un reseau de lignes multifilaires” (In French), PhD Thesis, Ecole Polytechnique Federale de Lausanne, 1998.

Paolone M., Nucci C.A., Rachidi F., “Mitigation of lightning-induced overvoltages by means of periodical grounding of shielding wire and of surge arresters”, Proc. of the 4th European Symposium on Electro Magnetic Compatibility, Brugge, Belgium, 11-15 Sept. 2000.

Paolone M., Nucci C.A., Borghetti A., Petrache E., Rachidi F., “A New Interface for Lightning Induced Overvoltages Calculation Between EMTP and LIOV code”, IEEE Summer Meeting July, Vancouver, British Columbia, Canada – EMTP user group meeting, 2001a.

Paolone M., Nucci C.A., Rachidi F., “A New Finite Difference Time Domain Scheme for the Evaluation of Lightning Induced Overvoltage on Multiconductor Overhead Lines”, Proc. of the International Conference on Power System Transient, Rio de Janeiro Brazil, 24-28 June, 2001b.

Papet-Lépine J., “Contribution au calcul des surtensions induites par la foudre dans les lignes de transport d'energie electrique”, (in French), Rev. Gen. Elect., Vol. 69, pp. 591-600, 1960.

Pettersson P. , “A unified probabilistic theory of the incidence of direct and indirect lightning strikes”, IEEE Trans. on Power Delivery, Vol. 6, No. 3, pp. 1301-1310, July 1991.

Piantini A., Janiszewski J.M., “An experimental study of lightning induced voltages by means of a scale model”, Proc. of the 21st International Conference On Lightning Protection, Berlin, Germany, September, 1992.

Rachidi F., Nucci C.A., “On the Master, Uman, Lin Standler and the Modified Transmission Line lightning return stroke current models”, Journal of Geophysical Research, Vol. 95, No. D12, pp. 20389-20393, November 1990.

Rachidi F., “Formulation of the field-to-transmission line coupling equations in terms of magnetic excitation fields”, IEEE Trans. on Electromagnetic Compatibility, Vol. 35, No. 3, August 1993.

Rachidi F., Rubinstein M., Nucci C.A., Guerrieri S., “Influence of the leader electric field change on voltages induced by very close lightning on overhead lines”, Proc. of the 22nd International Conference on Lightning Protection, Budapest, Hungary, 19-23 September, 1994.

Rachidi F., Nucci C.A., Ianoz M., Mazzetti C., “Influence of a lossy ground on lightning-induced voltages on overhead lines”, IEEE Trans. on EMC, Vol. 38, No. 3, August 1996.

Rachidi F., Nucci C.A., Ianoz M., Mazzetti C., “Response of multiconductor power lines to nearby lightning return stroke electromagnetic fields”, IEEE Trans. on PD, Vol. 12, N.3, pp. 1404-1411, July 1997.

Rachidi F., Nucci C.A., Ianoz M., “Transient analysis of multiconductor lines above a lossy ground”, IEEE Transactions on PD, Vol. 14, No. 1, pp. 294-302, January 1999.

Rachidi F., Loyka S.L., Nucci C.A., Ianoz M., “On the Singularity of the Ground Transient Resistance of Overhead Transmission Lines”, Proc. of the 25th International Conference on Lightning Protection, Rhodos, Greece, September 2000.

Rachidi, F.; Janischewskyj, W.; Hussein, A.M.; Nucci, C.A.; Guerrieri, S.; Kordi, B.; Jen-Shih Chang, “Current and electromagnetic field associated with lightning-return strokes to tall towers”, IEEE Trans. on EMC, Volume: 43 Issue: 3, pp: 356 –367, Aug. 2001.

Rakov V.A., Dulzon A.A., “Calculated electromagnetic fields of lightning return strokes”, (in Russian), Teknicheskaya Elektrodinamika, No. 1, pp. 87-89, 1987.

Rakov V.A., Uman M.A., “Some properties of negative cloud-to-ground lightning flashes versus stroke order”, Journal of Geophysical Research, Vol. 95, No. D5, pp. 5447-5453, April 1990.

Rakov V.A., Uman M.A., Thottappillil R., “Review of recent lightning research at the University of Florida”, Elektrotechnik und Informationtechnik, 112, No. 6, pp. 262-265, 1995.

Page 108: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

References pag.

101

Rakov V.A., Uman M.A., “Review and evaluation of lightning return stroke models including some aspects of their application”, IEEE Trans. on EMC, Vol. 40, pp. 403-426, 1998.

TI: New insights into lightning processes gained from triggered-lightning experiments in Florida and Alabama

Rakov V.A., Uman M.A., Rambo K.J., Fernandez M.I., Fisher R.J., Schnetzer G.H., Thottappillil R., Eybert Berard A., Berlandis J.P., Lalande P., Bonamy A., Laroche P., Bondiou Clergeries A., “New insights into lightning processes gained from triggered-lightning experiments in Florida and Alabama”, Journal of Geophysical Research. vol.103, no.D12; p.14117-30, 27 June 1998.

Rakov V.A., “Characterization of lightning electromagnetic fields and their modeling”, in Proc. of 14th International Zurich Symposium and Technical Exhibition on Electromagnetic Compatibility, Zurich, Switzerland, February 2001.

Ramo S., Whinnery J.R., Van Duzer T., “Fields and waves in communication electronics”, John Wiley and Sons, Second Edition, 1984.

Rizk F.A.M., “Modelling of Transmission Line Exposure to Direct Lightning Strokes”, IEEE Trans. on PWRD, Vol.5, No.4, pp.1983-1997, October 1990.

Rubinstein M., Tzeng A.Y., Uman M.A., Medelius P.J., Thomson E.M., “An experimental test of a theory of lightning-induced voltages on an overhead wire”, IEEE Trans. on EMC, Vol. 31, No. 4, pp. 376-383, November 1989.

Rubinstein M., “Voltages induced on a test power line from artificially initiated lightning: theory and experiment”, Ph. D. Thesis dissertation, University of Florida, Gainesville, 1991.

Rubinstein M., Rachidi F., Uman M.A., Thottaphilil R., Rakov V.A., Nucci C.A., “Characterization of vertical electric fields 500 m and 30 m from triggered lightning”, Journal of Geophysical Research, vol. 100, No. D5, pp. 8863-8872, May 1995.

Rubinstein M., “An approximate formula for the calculation of the horizontal electric field from lightning at close, intermediate, and long range”, IEEE Trans. on EMC, Vol. 38, No. 3, pp. 531-535, August 1996.

Rusck S., “Induced lightning overvoltages on power transmission lines with special reference to the overvoltage protection of low voltage networks”, Transactions of the Royal Institute of Technology, Stockholm, No. 120, 1958.

Rusk S., “Protection of distribution systems”, Lightning, Vol. 2, Ed. R.H. Golde, New York: Academic Press, Chapter 23, 1977.

Sabot A., “An engineering review on lightning, transient overvoltages and the associated elements of electromagnetic compatibility”, proc. Of the 9th International Symposium on High Voltage engineering, Graz, 1995.

Saint-Privat-D'Allier Research Group, “Research in artificially triggered lightning in France”, Proc. 3rd Symposium on Electromagnetic Compatibility, edited by T. Dvorak, E. T. H. Zentrum, Zürich, 1979.

Saint-Privat-d'Allier Research Group, “Eight years of lightning experiments at Saint-Privat-d'Allier”, Revue Générale de L'Electricité, No. 9, 1982.

Schonland B.F.J., “Progressive lightning”, part II, Proc. Roy. Soc. London, Ser. A, 143, pp. 654-674, 1934.

Shostak, V.; Janischewskyj, W.; Hussein, A.M., “Expanding the modified transmission line model to account for reflections within the continuously growing lightning return stroke channel”, Power Engineering Society Summer Meeting, 2000. IEEE , pp: 2589 -2602 vol. 4, 2000.

Tafflove A., “Computational electrodynamics: The finite difference time domain method”, Artech House, 1995.

Taylor C.D., Satterwhite R.S., Harrison C.W., “The response of a terminated two-wire transmission line excited by a non-uniform electromagnetic field”, IEEE Trans. on AP, Vol. 13, 1965.

Tesche F.M., “On the inclusion of loss in time-domain solutions of electromagnetic interaction problems”, IEEE Trans. on EMC, Vol. 32, No. 1, pp. 1-4, 1990.

Tesche F.M., “Comparison of the transmission line and scattering models for computing the HEMP response of overhead cables”, IEEE Trans. on EMC, Vol. 34, No. 2, May, 1992.

Page 109: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

References pag.

102

Tesche F.M., Ianoz M.V., Karlsson T., “EMC Analysis methods and computational models”, Wiley Interscience, N.Y, 1997.

Thomson E.M., Medelius P.J., Rubinstein M., Uman M.A., Johnson J., Stone J.W., “Horizontal electric fields from lighting return strokes”, Journal Geophysical Research, 93, n. D3, pp. 2429- 2441, 1988.

Thottapillil R., McLain D.K., Uman M.A., Diendorfer G., “Extension of the Diendorfer-Uman lightning return stroke model to the case of a variable upward return stroke speed an variable downward discharge current speed”, Journal of Geophysical Research, Vol. 96, no D9, pp 17,14317,150, September 20, 1991.

Thottappillil R., Uman M.A., “Advances in lightning research”, Trends in Geophysical Research, 2, 1993a.

Thottappillil R., Uman M.A., “Comparison of lightning return-stroke models”, Journal of Geophysical Research, 93, 98, 22,903-22,914, December 20, 1993b.

Thottappillil R., Uman M.A., “Lightning return-stroke model with height variable discharge time constant”, Journal of Geophysical Research, 94, 99, 22,773-22,780, 1994.

Tiller J.A., Uman M.A., Lin Y.T., Brantley D., Krider E.P., McLain D., “Correlated electric and magnetic fields from lightning return strokes Journal of Geophysical Research, Vol. 80, pp. 373-376, 1976.

Uman M.A., McLain D.K., “Magnetic field of lightning return stroke”, Journal of Geophysical Research, Vol. 74, 1969.

Uman M.A., Krider E.P., “A Review of Natural Lightning: Experimental Data and Modeling”, IEEE Trans. on EMC, Vol. 24, No.G24, May 1982.

Uman M.A., “The lightning discharge”, Academic Press, Orlando FL, 1987.

Uman M.A., Rakov V.A., Rambo K.J., Vaught T.W., Fernandez M.I., Bach J.A., Su Y., Eybert-Berard A., Berlandis J.P., Bador B., Lalande P., Chauzy S., Souia S., Weidman C.D., Rachidi F., Rubinstein M., Nucci C.A., Guerrieri S., Høidalen H.K., Cooray V., “1995 Triggered lightning campaign at Camp Blanding, Florida”, EOS, Trans. American Geophysical Union, 1995 Fall meeting, vol. 76, No. 46, 7 Nov., 1995/Supplement.

Uman M.A., Rakov V.A., Schnetzer G.H., Rambo K.J., Crawford D.E., Fisher R.J., “Time derivative of the electric field 10, 14, and 30 m from triggered lightning strokes”, Journal of Geophysical-Research. vol.105, no.D12, p.15577-95., 27 June 2000.

Wagner C.F., Mc Cann G.D., “Induced Voltages on Transmission Lines”, AIEE Transactions, Vol. 61, pp. 916- 930, 1942.

Wagner C.F., Cross I.W., Lloyd B.L., 2High voltage impulse tests on transmission lines”, AIEE Trans., Vol. 73, Part III, pp. 196-209, April 1954.

Wagner K.W., “Elektromagnetische ausgleichsvorgange in freileitungen und kabeln”, (in German), par. 5, Leipzig, 1908.

Wait, J.R., “Concerning horizontal electric field of lightning”, IEEE Trans. on EMC, Vol. 39, No. 2, May 1997.

Weidman C.D., Krider E.P., “The fine structure of lightning return stroke wave forms”, Journal of Geophysical Research, 83:6239- 6247, 1978. ("Correction", Journal of Geophysical Research, 87:7351, 1982).

Willett J.C., Idone V.P., Orville R.E., Leteinturier C., Eybert-Berard A., Barret L., Krider E.P., “An experimental test of the ‘trasmission line model’ of electromagnetic radiation from triggered lightning return stroke”, Journal of Geophysical Research, Vol. 93, pp. 3867-3878, 1988.

Willett, J.C.; Krider, E.P., “Rise times of impulsive high-current processes in cloud-to-ground lightning”. IEEE Trans. on AP, Volume: 48 Issue: 9 , pp: 1442 –1451, Sept. 2000.

Yacoub Z., Rubinstein M., Uman M.A., “Voltages induced on power distributon line by overhead cloud lightning”, Proc. 1991 Inter. Conf. on Lightning and Static Electricity, Cocoa Beach, Florida, April 16-19, 1991.

Yokoyama S., “Experimental analysis of earth wires for induced lightning surges”, IEEE Proc., Vol. 127, pt. C, No. 1, January, 1980.

Yokoyama S., Miyake K., Mitani H., Takanishi A., “Simultaneous measurement of lightning induced voltages with associated stroke currents”, IEEE Trans. on PAS, Vol. 102, No. 8, pp. 2420-2429, August 1983.

Page 110: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

References pag.

103

Yokoyama S., “Calculation of lightning-induced voltages on overhead multiconductor systems”, IEEE Trans. on PAS, Vol. 103, No. 1, pp. 100-108, January 1984.

Yokoyama S., Miyake K., Mitani H., Yamazaki N., “Advanced observations of lightning induced voltage on power distribution lines”, IEEE Trans. on PWDR, Vol. 1, No. 2, pp. 129-139, April 1986.

Yokoyama S., Miyake K., Fukui S., “Advanced observations of lighting induced voltages on power distribution lines (II)", IEEE Trans. on PWDR, Vol. 4, No. 4, pp. 2196-2203, October 1989.

Zeddam, Degague P., Leray R., “Etude des perturbations induites par une décharge orageuse sur un câble de telecommunication” (In French), Ann. Télécommun., 43, No. 11-12, 1988.

Zeddam, Degauque P., “Current and voltage induced on a telecommunication cable by a lightning stroke”, Lightning Electromagnetics, Edited by R.L. Gardner, pp. 377-400, Hemisphere Publ. Corp., 1990.

Page 111: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Appendix pag.

104

Appendix A.1. – Numerical treatment of line transverse discontinuities in 1st order FDTD scheme

The 1st order spatial Point Centered Finite Difference integration scheme for a single-

conductor line illuminated by an external electro magnetic field, around grounding point is shown in Fig. A.1

∫ih

z dztzxE0

),,(

ΓVoltage FD node Current FD node

ikn ik+1

n vk+2n vk+1

n vk

n ik+2n

dx dx/2

k spatial discretization n time discretization dx spatial discretization

ik-1n

ik’ n ik”

n

ign

Known variables: • All internal node scattered

voltages and currents at time step n

• Ground resistance Rt • Vertical Electric Field Ez

Unknown variables:

• vk+1n

• ikn • ik+1

n Constant:

• Line Height hi • Operator Γ

Fig. A.1. Insertion of discontinuity point, at a generic point along a single-conductor line, in the 1st order

Point Centered Finite Difference integration scheme. The treatment of a grounding point, located anywhere along the line, involves a

modification of the numerical solution of the Agrawal model. It is handled as a discontinuity point in the spatial grid of the Point Centered Finite Difference integration scheme.

In the numerical discretization of the Agrawal single-conductor coupling equations [Nucci et al., 1994] the equation that allows to extract a generic current node at time step n, known all variables at time step n-1, is the following:

+

∆−−+= −+

−1

41

1

3 2nk

nk

nk

nk

nkn

k iAx

vvEhEhAi (A.1)

where the sense of the symbol that appear in (A.1) is the same of the paragraph 3.1.2. A3 and A4 are constants depending on the line inductance L:

∆=

∆=

tLA

tLA ';'

4

1

3 (A.2)

Page 112: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Appendix pag.

105

If we write equation (A.1) for nodes k and k+1 of Fig. A.1 we obtain the first two equations of the solution system:

+

∆−−+= −+

−1

41

1

3 2nk

nk

nk

nk

nkn

k iAx

vvExExAi (A.3)

+

∆−−+= −

+++

−++

+114

12111

31 2nk

nk

nk

nk

nkn

k iAxvvExExAi (A.4)

To obtain the third equation of the solution system we apply the Kirchoff current

equation, at the grounding node, for currents ign, ik n, ik n:

nk

nk

ng iii ''' −= (A.5)

Currents ik

n, ikn can be expressed as a function of the adjacent current node assuming

the following linear spatial interpolation:

23 1

'

nk

nkn

kiii −−= (A.6)

23 21

''

nk

nkn

kiii ++ −= (A.7)

Besides, the node voltage vk+1

n can be expressed as in (3.1):

∫+=+

ihez

nnk (x,z,t)dzE)Γ ( igv

01 (A.8)

By introducing (A.5), (A.6) and (A.7) in (A.8) we obtain the third equation of the

solution system:

∫+

+−−= ++−+

ihez

nk

nk

nk

nkn

k (x,z,t)dzEiiiiv0

2111 2

33Γ (A.9)

FDTD 1st order multi-conductor line. The model for a multi-conductor line discontinuity

treatment is similar to that of the single-conductor line. We shall consider a discontinuity at one of the conductors of the bundle as a discontinuity of all conductors, in that the conductors which are not connected to ground are considered grounded through an infinite resistance. We can rewrite (A.3), (A.4) and (A.9) for a multi-conductor line as follows (j is the grounded conductor):

Page 113: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Appendix pag.

106

[ ] [ ] [ ] [ ] [ ] [ ] [ ][ ]

+

∆−−+= −+

−1

41

1

3 2

nk

nk

nk

nk

nkn

k iAx

vvExExAi (A.10)

[ ] [ ] [ ] [ ] [ ] [ ] [ ][ ]

+

∆−−+= −

+++

−++

+114

12111

31 2

nk

nk

nk

nk

nkn

k iAx

vvExExAi (A.11)

[ ] [ ] [ ] [ ] [ ] [ ]

+

+−−= ∫++−+

ihez

nk

nk

nk

nkn

k (x,z,t)dzEii ii ΓK v0

2111 2

33 (A.12)

where

[ ] [ ] [ ]

=

=

=

nk

nk

nk

nk

nk

nk

nk

nk

nk

nk

nk

nk

nk

nk

nk

ExNC

ExExEx

Ex

vNC

vvv

v

iNC

iii

i:321

;:321

;:321

(A.13)

=

NC

i

hez

hez

hez

hez

hez

(x,z,t)dzE

(x,z,t)dzE

(x,z,t)dzE

(x,z,t)dzE

(x,z,t)dzE

0

0

0

0

0

:

3

2

1

(A.14)

[ ] [ ] [ ] [ ]t

LA

tL

A ijij

∆=

∆=

4

1

3 ; (A.15)

and matrix [ ΓK ]:

[ ]

=

NCNCKΓ|||KΓ|KΓ|KΓ

000

000000000

33

22

11

(A.16)

Page 114: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Appendix pag.

107

Appendix A.2. – Comparison between 1st and 2nd order FDTD integration schemes

A first comparison of the newly proposed FDTD 2nd order integration scheme with the 1st

order one has been performed making reference to a 2 km long, 10 m high single-conductor line above a lossy ground shown in Fig. A.2. The ground conductivity is 0.001 S/m and its relative permittivity is 10. The stroke location is at 50 m from the left-end line terminal. The lightning channel base current peak value is 60 kA and its maximum time derivative is 120 kA/ms. The return stroke speed is 1.2⋅108 m/s. The LEMP is computed adopting the MTL return stroke model and the value of the spatial and temporal steps adopted for the simulations are 10 m and 10-8 s respectively.

2 km

10 m

1 cm

Zc

50 m

Stroke Location Zc

Fig. A.2. Line geometry for the comparison between FDTD 1st and 2nd order in presence of lossy ground. In Fig. A.3 we show the results calculated both with the 1st order and 2nd order FDTD

algorithms. For both cases, we show the results considering the effect of the ground resistivity both in the electromagnetic field and in the calculation of line parameters (lossy line) and the results obtained taking into account ground losses only in the electromagnetic field calculation (ideal line).

A comparison between the two methods has been performed also for the case of a line with surge arresters. To perform these simulations, we have used the LIOV- EMTP96 program (see paragraph 3.2).

Page 115: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Appendix pag.

108

a)

0

50

100

150

200

250

300

350

400

0 1 2 3 4 5 6

Time [µs]

Indu

ced

Ove

rvol

tage

[kV

]

0 m FDTD 1st order lossy line0 m FDTD 2nd order lossy line0 m FDTD 1st order ideal line0 m FDTD 2nd order ideal line

b)

-550

-450

-350

-250

-150

-50

0 1 2 3 4 5 6

Time [µs]

Indu

ced

Ove

rvol

tage

[kV

]

500 m FDTD 1st order lossy line500 m FDTD 2nd order lossy line500 m FDTD 1st order ideal line500 m FDTD 2nd order ideal line

c)

-950

-850

-750

-650

-550

-450

-350

-250

-150

-50

4 5 6 7 8 9 10

Time [µs]

Indu

ced

Ove

rvol

tage

[kV

]

2000 m FDTD 1st order lossy line2000 m FDTD 2nd order lossy line2000 m FDTD 1st order ideal line2000 m FDTD 2nd order ideal line

Fig. A.3. Lightning induced overvoltages calculated at three different observation points of the line of Fig. A.2, a) x=0 m, b) x=500 m, c) x=2 km, using 1st and 2nd order FDTD scheme. Field calculation: lossy ground

(0.001 S/m), line impedance: ideal line and lossy line.

Page 116: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Appendix pag.

109

It can be seen that the wave-shapes computed using the 2nd order FDTD algorithm are less affected by numerical oscillations, especially for observation points approaching the line far-end.

Fig. A.4 show the geometry of the line used for the simulations and Fig. A.5 shows the numerical results. Again, it can be seen that the proposed 2nd order scheme leads to an improvement of the computed results, in terms of numerical stability.

2 km

10 m

1 cm

500 m

Stroke Location

Surge Arrester

Surge Arrester

Surge Arrester

Surge Arrester

Surge Arrester

500 m

50 m

Fig. A.4. Line geometry for the comparison between FDTD 1st order ad 2nd order in presence of surge

arresters, using the developed interface between LIOV and EMTP96.

a)

-40

-30

-20

-10

0

10

20

30

40

0 5 10 15 20

Time [µs]

Indu

ced

Ove

rvol

tage

[kV

]

0 m FDTD 1st order0 m FDTD 2nd order

Page 117: University of Bologna - unibo.it · PDF fileUniversity of Bologna ... – Transmission line coupling models ... parameters related to the corona model; L':

Appendix pag.

110

b)

-40

-30

-20

-10

0

10

20

30

40

50

0 5 10 15 20

Time [µs]

Indu

ced

Ove

rvol

tage

[kV

]

500 m FDTD 1st order500 m FDTD 2nd order

c)

-40

-30

-20

-10

0

10

20

30

40

0 5 10 15 20

Time [µs]

Indu

ced

Ove

rvol

tage

[kV

]

2000 m FDTD 1st order2000 m FDTD 2nd order

Fig. A.5. Lightning induced overvoltage at two observation points a) x=0 m, b) x=500 m, c) x=2000 m of

Fig. A.4. Comparison between FDTD 1st order and 2nd order in presence of surge arresters. With the presence of non-linear components the above reported comparison show, again,

that the proposed 2nd order scheme improve the computed results in terms of numerical stability. Indeed the increase numerically stability is obtained without significant increase in the computation time1.

1 The calculation of the exciting lightning electromagnetic field representing, for the problem of interest,

the bulk of the computation time.